  • INSTALLATION & OWNER’S MANUAL

    IMM - SOFTWARE AND SOFT DOG.

    Thank you very much for purchasing our product, Before using it, please read this manual carefully and keep it for future reference.

  • NOTE

    CONTENTS PAGE

    ● Thismanualgivesdetaileddescriptionoftheprecautionsthatshouldbebroughttoyourattention during operation.

    ● Inordertoensurecorrectserviceofthispaper,pleasereadthismanualcarefullybeforeusing the unit.

    ● Forconvenienceoffuturereference,keepthismanualafterreadingit.

    ● Astheproductupdates,thisdocumentwillbechangedwithoutpriornotice.

    IMM INTRODUCTION ................................................................................................................................ 1

    SOFTWARE INSTALLATION .................................................................................................................... 4

    SETTING .................................................................................................................................................... 5

    OPERATION INSTRUCTION ..................................................................................................................... 8

    TROUBLESHOOTING ..............................................................................................................................32

    APPENDIX ................................................................................................................................................34

  • Owner‘sManual

    1

    1. IMM INTRODUCTION

    1.1 IMM system introduction

    IMMsystemistheshortnameofIntelligentManager.Itconsistsofthreeparts:IMMsoftware,M-interfacewebgatewayandV4+outdoorunitrefrigerantsystem.TheIMMsystemcanconnect4M-interfacegatewaysatmost,totallycouldjoinup64refrigerantsystems.TheIMMsoftwarecancommunicatewithnetworkandM-INTERFACEgateway,tocontrolandmanagetherefrigerantsystem.TheIMMsystemframeworkastheFig.1-1display.

    IMMsoftwareinstalledinthecomputer,andtheM-INTERFACEgatewayconnectstothecomputerthroughLANport.LaptopandPadcanvisitWEBpageofM-INTERFACEthroughwirelessnetwork.

    1.2 Models which could be inserted

    1) Projectswhichdonotneedelectricquantitydivision:canfreelyinsertV4+units.

    2) Projectswhichneedelectricquantitydivision:connecttheV4+seriesoutdoorunitsandindoorunits,andwiringtheM-netterminalcommunicationwirefromtheoutdoorside.

    3) Details consult relevant technical personnel.

    1.3 IMM network introduction

    IMMsoftwareincludesserversoftware,cline-sidesoftwareanddatabasesoftware.Installtheserversoftwareandthedatabasesoftware in thesamecomputer, thiscomputerandtheM-INTERFACEshouldbeinthesamesubnetsegment(fordetails,pleasereferto3.1).Thecline-sidecanconnecttotheserverthroughthelocalorremotenetwork.

    Fig.1-1

  • Owner‘sManual

    2

    1.3.2 Remote network connection

    Theclient-sideandserveralsocanusetheremotenetwork(VPN)connection.VPNhasrouterestablishingandcomputerestablishingmethods,andtheremotenetworkconnectionneedssomeITknowledgeandneedstheITprofessionalstoassist.1) Routerestablishing

    VPNtunnelsestablishbetweenrouters,andthencanvisitWEBinterfacethroughVPNtunnels.VPNServercanbeestablishedbyoneselfandalsocanberented.Itstopologystructureasfollowdisplay:

    2)computerestablishing

    UseVPNclient-sidesoftwareandVPNServer toestablishVPNtunnel, thenusercanvisittheserver throughVPNtunnel.VPNclient-sidesoftwareandVPNServercanbeachievedbycommercialways.Itstopologystructureasfollowdisplay:

    1.3.1 Local network connection

    Thecline-sidecanconnect totheserver throughthe localnetwork, the localnetworkconnec-tionasthefollowingdisplay:

    Fig.1-4

    Fig.1-3

    Fig.1-2

  • Owner‘sManual

    3

    1.4 IMM software functions

    UsercanoperatetheIMMclient-sidesoftwaretomonitoringtheair-conditioningsystem.ThefunctionsofferedbyIMMsoftwareasthefollowingdisplay:

    Mainfunctionsasfollow:1) Device monitoring

    Offercontrolandmanagementofindoor/outdoorunitfortheM-INTERFACEgateway.

    2) Device guide Usercanseethelocationoftheair-conditioningdevice.

    3) Schedulemanagement Offers schedule control function of indoor unit.

    4) Energysavingmanagement Offers energy saving control function of indoor unit.

    5)Statisticsofenergyconsumption Offerselectricquantitydivisionfunctionofair-conditioningsystem.

    6) Device management Offersthegroupdivisionfunctionofair-conditioningdevice.

    7) Data statistics Providesthestatuschangingrecordsofindoorunit,outdoorunitandM-INTERFACEgateway.

    8) Log Offersalltherecordsoftheclient-sideoperationswhichoperatedbytheuser.

    Fig.1-5

  • Owner‘sManual

    4

    Table.2-1

    2. SOFTWARE INSTALLATION

    2.1 Installation preparation

    BeforetheIMMsoftware installation, itneedstomakesuretheair-conditioningsystemoperatednormally,M-INTERFACEgatewayworkednormally, thecommunicationbetweenM-INTERFACEgatewayandair-conditioningsystemwasnormal,and itneedstomeet thefollowinghardwareandsystemrequirements.

    2.2 Software installation

    About thedetailspleaseconsult relevant technicalpersonnel.Thissystemneedstoberegularlycheckedbytheprofessionaltoensureitrunscorrectly.

    Specification Recommendation Remark

    PC

    CPU:i3oraboveInternalstorage:2GoraboveHarddisk:120GoraboveKeyboard/MousewithmiddlewheelNetwork:108ASE-TScreenresolutionshouldover1024*768Screensizeshouldover17inch

    RecommendedthatIBMorDELLproducts

    Mustbedesktop(Notebookcomputerorother types of computers isnotallowed),andensure the computer worksnormallybeforeinstallingthesoftware.

    SystemMicrosoftWindowsXPProfes-sionalServicePack3/Windows7Flagshipedition32-bitsystems.

    Document form NTFS

  • Owner‘sManual

    5

    Afterconfiguration,clickthe“OK”button.

    3. SETTING

    3.1 IP address setting

    Default IPofM-INTERFACEgateway is192.168.100.40,subnetcovercode is255.255.255.0.TheM-INTERFACEgateand IMMservermustbestayed in thesamesubnetwork, twowaysofrealization:amendtheM-INTERFACEgateIPandconfigurethestaticstateIPforserver.

    3.1.1 Configure static IP

    Generallyconfiguresingle IP, if the IPaddressofcomputercannotbeamended, thenconfigureseveralIP.Methodsasfollow(Takewindows7systemforexample):1)ConfiguresingleIP

    OpenthepropertydialogueboxtoconfiguretheIPaddressandsubnetcovercode,forexample:IP:192.168.100.44,subnetcovercode:255.255.255.0.

    Fig.3-1

  • Owner‘sManual

    6

    Fig.3-2

    2)ConfigureseveralIP

    BeforeconfigureseveralIP,itneedtoconfigureastatisticIPaddress.Openthepropertydialoguebox,selectthe“Advanced”,anddisplaytheTCP/IPsettingdialogueboxasfollow:

    Click the “Add” button in IP address bar, add a IP address in the same net areawith“192.168.100.40”,e.g.:IP:192.168.100.101,subnetcovercode:255.255.255.0,andthenclick the“Add”button.

    3.1.2 Amend gateway IP

    BeforeamendingtheIPaddressofM-INTERFACEgateway,itneedsacomputertovisittheWEBpageofM-INTERFACE,thenentertheIPaddressamendingpagethroughthecomputer.Thepagedisplayasfollow:

  • Owner‘sManual

    7

    Fig.3-3

    Aftertyping,click“OK”tosave.DonotconflictwithotherIPinthenetwork,detailedIPaddressassignmentneedstoconsultthenetworkadministrator.

    3.2 Software operation setting

    Beforesoftwareoperation,set theserversoftware,client-sidesoftwareanddatabasesoftware.Aboutthedetailssettingpleaseconsultrelevanttechnicalpersonnel.Aftersetting, insertthedongle(dongleisonlyusedforthissystem,pleasekeepthedongleproperly),andstarttheserversoftwareandthenstarttheclient-sidesoftware.

  • Owner‘sManual

    8

    4. OPERATION INSTRUCTION

    4.1 User login

    OperatetheIMMclient-sidesoftware,popupthelogininterfaceasthefollowdisplay:

    Fig.4-1

    After“Connecttotheserversuccessfully”wasdisplayedatthelowerleftofthelogininterface,thencan carry out the login operations. Stepsofcarryingouttheloginoperationsasfollow:1)Typeinuser’spassword,thedefaultisuser;2)Choosewhethersavethepassword;3)Click[OK]tocarryoutlogin;4)Click[Cancel]toexitthispage;

    Whenclickedthe“OK”button,afterloginsuccessfully,thenenterintothesystemhomepage.Ifloginfailed,pleaserefertoAppendix5.1.

    4.2 User log out

    Clicktheicon onupper-rightcorner,exitthesystem,andtheinterfacedisplayasfollow:

  • Owner‘sManual

    9

    4.3 System initialization

    After theuser loginsuccessfully, thenwillshowout thesysteminitializationdialogueframe,andcarryouttheinitializationofthewholesystem,updatethesysteminformation.Theitializationdialogueframedisplayasfollow:

    Fig.4-3

    Fig.4-2

  • Owner‘sManual

    10

    MenuFunction

    Display

    Informationtip

    Clickthe“Exitthesystem”button,thenwillstoptheinitializationworkandexistthesystem.

    4.4 Main interface introduction

    Thesystemhomepagedisplayasthefollow:

    Fig.4-4

    Menu:systemfunctionsmenu.Functions: functions inmenu, includedevicemonitoring,schedulemanagement,energysaving

    management,statisticsofenergyconsumption,publicdevice,datastatisticsand logetc. functions.Display:displaydetailedinformationofeachfunction.Informationtip:displaythepromptmessageandalarminformation.Theupper-rightcorneroftheinterfacewilldisplaythesoftwareversionanduser’sloginname.

    4.5 Devices monitoring

    Thispartisdisplayedas3classesofair-conditioningindoorunit,outdoorunitandM-INTERFACEgateway.Eachclasswillbedisplayedasprimarygroupandsecondarygroup.E.g.:undertheindoorunititwilldisplaytheprimarygroup:Buildings;andundertheprimarygroupitwilldisplaysecondarygroup:firstfloor,secondfloor,thirdflooretc.Detailedgroupsettingpleaserefersto4.10.

  • Owner‘sManual

    11

    4.5.1 M-INTERFACE gateway monitoring

    Choose theM-INTERFACEgatewayselection; the interfacewilldisplayall theM-INTERFACEgatewaydevicesintheIMMsystem.

    Fig.4-5Thereare3displaystatusesofM-INTERFACEgateway: lostconnection, lockedandselected.

    WhenselectedorrightmouseclickaM-INTERFACEgatewaydevice,thebottomofinterfacewoulddisplay its IPaddressand itwhetherhas limitmode,andtheusercancontrol theM-INTERFACEgatewaydevicethroughthemethodofsettingthelimitmodeparameters,emergencystopparametersandthenclick the“send”button.Usercanamendthedevicename:double-click thedevicename,thenamendit,andpressenterkeytosave.E.g.:selecttheM-INTERFACEgatewaydevicesnamed40and41(selectingmethodrefersto4.5.4),andchoosethe“limitmode”parameters,andthenclickthe“send”button,thepagedisplayasfollow:

    Fig.4-6

  • Owner‘sManual

    12

    Parameters Specifications

    Limit mode Locked:cannotoperateintheWEBpageofM-INTERFACEUn-locked:RemovethelockingofM-INTERFACEgatewaydevice.

    Emergencystop

    ----:Notcarryouttheemergencystopfunction.Stop:Carryouttheemergencystopfunction,stopallthedevicesoftheM-INTERFACEgateway.

    Icon Specifications Icon Specifications

    M-INTERFACEdeviceworknormal

    M-INTERFACEdevicelocked

    M-INTERFACEdevicelost connection

    M-INTERFACEdeviceselected

    Fig.4-7

    Iconspecifications: Table.4-2

    Aftersuccessfullyset“Limitmode”,thedeviceiconwilladdaniconwithlocker.

    Parametersspecifications: Table.4-1

    Statusselection:Thegatewaydevicehas3statuses: locked ( Locked ), lostconnection ( Offline ) and selected

    ( Selected ).Clickthecorrespondingstatusicontochecktherelativedevice.Clickthelostconnectionicon,anditwilldisplayallthedeviceswhichlostconnection.Rightclickthe“selected”icon,anditwillpopuptheselectionframeof“Allselect/cancelallselect”,choose“Allselect”thenitwillselectalltheiconsintheinterface,andclick“cancelallselect”thenitwillcancelselectingalltheicons.

    4.5.2 Outdoor unit monitoring

    Selecttheoutdoorunitclass,theleftsideofinterfacewilldisplaythegroupinformationundertheindoorunit,andtherightwilldisplaythecorrespondingoutdoordevice.

  • Owner‘sManual

    13

    Icon Specifications Icon Specifications Icon Specifications

    Outdoor unit lost connection(White)

    OutdoorunitisOFF,outdoorambienttemp.is21°C.(Gray)

    Outdoor unit operates cooling,outdoorambienttemp.is24°C.(Blue)

    Outdoor unit error (Red)

    Outdoor unit operates heating, outdoor ambienttemp.is24°C.(Orange)

    Outdoor unit is selected, outdoorambienttemp.is25°C.

    Theoutdoorunitdisplaystatus:error,lostconnection,cooling,heatingandselected.Selectorrightmouseclickaoutdoorunit,thenchecktheonandoffstatus,ambienttemperature,ammeterreadingsetc.detailedinformationofthisdeviceinthe“Devicedetailsinformation”.Iconspecifications: Table.4-3

    Fig.4-8

    4.5.3 Indoor unit monitoring

    Select the indoorunitclass, the leftsideof interfacewilldisplay thegroup informationunderthe indoorunit,andtherightwilldisplayall the indoorunits in theIMMsystem,select the“devicecontrol”tocarryoutthecontroloperationforoneormoresetsindoorunits;selectthe“devicedetailsinformation”tochecktheoperatingdetailinformationofadevice.1) ChecktheoperatingstatusofindoorunitChoosethe“devicedetail information”,selecta indoorunit, thenthebottomof the interfacewill

    displaytheoperatingdetailinformationofthisdevice.Displayasfollow:

    Statusselection:Theoutdoorunitdisplaystatus:error ( Error ), lostconnection( Offline ),cooling( Cool ), heating

    ( Heated ),offunit( Off )andselected( Selected ).Clicktheerror,lostconnection,cooling,heatingandselectediconsbythemouse,thentheinterfacewilldisplayallthecorrespondingstatus.E.g.:clickthecoolingicon,thenitwilldisplaythedevicesundercoolingstatusintheselectedgrouponthepage,displayasfollow:

  • Owner‘sManual

    14

    Fig.4-9

    Displayeddetail information:onandoffstatus,operatingmode,devicenameanddevicenumberetc.

    2) ControltheoperatingstatusofindoorunitChoosethe“Devicecontrol”,selectoneormoresetsindoorunits(selectingmethodrefersto4.5.4),

    in thebottomof the interfaceconfigureparameters:onandoffsetting,modesetting,operatingfanspeed, temperaturesettingandswingingsetting,andclick “send”buttonaftersetting,displayasfollow:

    Fig.4-10

  • Owner‘sManual

    15

    Icon Specifications Icon Specifications Icon Specifications

    Indooruniterror(Red)

    Indoorunitoperatesheating,indoorambienttemp.is25°C.(Orange)

    Indoorunitislocked,indoorambienttemp.is25°C.

    Indoorunitlostconnection(White)

    Indoorunitoperatesfan,indoorambienttemp.is25°C.(Green)

    Indoorunitisselected,indoorambienttemp.is25°C.

    Indoorunitoperatescooling, indoor ambienttemp.is25°C.(Blue)

    IndoorunitisOFF,indoorambienttemp.is25°C.(Gray)

    The control order is carryingout,pleasewait

    Theinterfacewilldisplaythe iconswhichwait forbeingsent,after theorderexecution, the iconswilldisappear,andtheinterfacewillberefresh,thencanviewtheoperatingstatusofthecontrolorderhadbeenexecuted. Ifcontrol failed, the“Promptmessage” in the interfacebottomwilldisplay thecontrol failed information.

    Iconspecification Table.4-4

    Statusselection:Theindoorunitdisplaystatus:error( Error ),lostconnection( Offline ),schedule( Schedule ), cooling

    ( Cool ),heating( Heated),fan( Fan ),offunit( Off ), locked( Locked )andselected( Selected ).Clicktheerror, lostconnection,schedule,cooling,heating, fan,offunit, lockedandselected iconsbythemouse,thentheinterfacewilldisplayallthecorrespondingstatus.Rightclickthe“selected”icon,anditwillpopuptheselectionframeof“Allselect/cancelallselect”,choose“Allselect”thenitwillselectalltheiconsintheinterface,andclick“cancelallselect”thenitwillcancelselectingalltheicons.Right-click the“locked” icon, then itwilldisplay the locked lists,andclick thecorresponding list thenwilldisplay the relative devices.

    4.5.4 Shortcut keys operation

    Shortcutkeysoperationsofmouse:Thesystemoffersshortcutkeysoperationsofmouse,whichconvenientfortheusertoselect/canceloneormoresetsdevicesquickly.

    1) Selectsingleicon Left-clicktheicon,iftheiconwasframedthenmeansitwasselected.

    2) Selectseveralicons Therearetwowaysforselectingseveralicons:

    ■Selectseveraliconsasthewayofselectingsingleicon. ■Left-clickoutsidetheframeintheinterface,dragadottedlineframetoselectthecorresponding

    icons.

    3) Cancelsingleselectedicon Left-clickontheselectedicon,thencancelselectingtheicon.

    4) Cancelseveralselectedicons Therearetwowaysforcancelingseveralselectedicons:

    ■Cancelseveralselectediconsasthewayofcancelingsingleselectedicon. ■Double-clicktheleft/middle/rightkeyofthemouseintheblankplaceofthepage,tocancel

    several selected icons.

  • Owner‘sManual

    16

    FunctionshortcutkeysoperationsRight-clickthe Selected icon,thenitwillpopuptheselectionframeof“Allselect/cancelallselect”,

    choose“Allselect”and“Cancelallselected” toselectandcancelquickly.Theoperationstepsasfollow:1)Selectthe“indoorunit”or“outdoorunit”class(orprimarygrouporsecondarygroup).2)Clickastatusdisplayicon(cooling,heating,error,offunitetc.),suchasclickthecoolingstatusicon,theinterfacewilldisplaythedevicesofcorrespondinggroupundercoolingstatus.

    3)Clickthe“selectall”option,thenallthecoolingdeviceinthepagewillbeselected,andifclickthe“canceltheselectedall”,alltheselectediconswillbecanceledselecting.

    4.6 Device guide

    Offer the functionofusercansee the locationof theair-conditioningdevice.Rightclickonesecondarygroup,willpop-uptheoptionsof“Startchangingdevice’slocation”and“Changethefloorplan”,andclick“Changethefloorplan”,thendisplayasfollow:

    Fig.4-11

    Userselects thecorresponding floorplan(thepicturewillsave in themap folderof theclient-sideinstallationmenus),andthenclick“Save”button,afterfinishedtheoperation,thenclick“Close”button.Afterselect thefloorplan, thenclick“Startchangingdevice’s location”,usercanselectonedevice, and then drag it on the interface to change its location.

  • Owner‘sManual

    17

    4.7 Schedule management1) Schedulemanagementoffersthescheduleoperationsforair-conditioningindoorunit.Displayas

    follow:

    2) Schedulemanagementoperationstepsasfollow:

    ■Addthename

    Fig.4-13

    Fig.4-12

    Clickthe“Add”button,typeinschedulename.

    ■Adddevice

    Clickthe“Deviceselecting”button,thenitwillpopuptheadddeviceframeasthefollowingdisplay:

  • Owner‘sManual

    18

    Fig.4-14

    Click the “Non-selecteddevice”option,select thedeviceandclick the “add”button.Click the“Selecteddevice”option,andthenitshowsuptheselecteddevices.Choosetherelativedevices,andclick“Move”tomovethedevicesinto“Non-selecteddevice”.Afterselection,click”OK”andthenclosetheselectionframe.Thepagewilldisplaytheselecteddevices.

    Fig.4-15

  • Owner‘sManual

    19

    ■Controlparameterssetting

    Fig.4-16

    Setthetime,onandoffstatus,mode,fanspeed,temperature,swingingparameters.Clickthecancelicontocancelthesetting.

    ■ Time selecting Therearetwowaysofaddingtime:Choosedateorweek.Date:Clickthedateundercorrespondingmonth,selectthemonthanddatewhichdisplayedinred.Week:checktherelativeweek,thenthisdayofeachweekwillbelistedintheschedule.SuchasselectedMonday,theneveryMondaywillcarryoutthisschedule.

    ■SaveAftersetting,clickthesavebutton,anddisplayasthefollowing:

    Fig.4-17

  • Owner‘sManual

    20

    Fig.4-18

    Theupperleftcornerofthepagewilldisplaytheaddedschedulename.Andtherightdisplayedtheaddeddevice.If it’sthefirsttimesettingscheduleofthedevice,thentheiconwilladdthescheduleicon.Use the“Datastatistics” tocheck theexecutionstatusof theschedule.About the importanttiming plan, You should set again after 5 minutes.

    4.8 Energy saving managementEnergysavingmanagementofferstheenergysavingcontroloperationsforair-conditioningindoor

    unit.Onlythenewtypeofindoormachinesupportsthisfunction,Displayasfollow:

    Fig.4-19

  • Owner‘sManual

    21

    Selection Specifications

    Coolingtemp.limit Setthelowestlimitofcoolingtemp.,andlimit the remote controller control

    Heating temp. limit Setthelowestlimitofheatingtemp.,andlimit the remote controller control

    On and off unit limit Limit the indoor unit on and off operations of the remote controller

    Modelimit Limit the unit cooling, heating mode operations

    Fanspeeddisplay Limitthefanspeedcontrolbytheremotecontroller

    Swinginglimit Limittheswingingcontrolbytheremotecontroller

    Remotecontrollerlimit Limittheairconditioneroperationsbytheremote controller

    Theleftsidewilldisplaytheindoorunitgroupinformation,andselectoneormoresetsindoorunitsandchoosetheenergysavingoption,thenclickthe“Set”button.Aftersetting,theairconditionericonwilldisplaythelockedicon.Ifitneedstoremovethelimit,thenchoosethe“Remove”option,andclickthe“Set”buttonforremovingthelimit,thenthelockediconwilldisappear.Ifitfailedthecontrol,checkthefailed information in the“Promptmessage”.Click therightkeyof themouseonan indoorunit,thenthebottomoftheinterfacewilldisplaythelockingdetailinformationofthisdevice.

    Optionsspecification: Table.4-5

    4.9 Statistics of energy consumption

    Thisfunctioncalculatestheresultsofthedevice’selectricquantitydivisioninaperiod.Thisfunctionneedstobeactivatedforuse.displayasfollow:

    Fig.4-20

  • Owner‘sManual

    22

    Iftheuserneedsthisfunctionpleaseconsultthedealer,andgettheactivationcodetoactivatethisfunction.Theactivatedpageasfollowingdisplay:

    Fig.4-21

    Selectthe“Starttime”,“Endtime”and“Calculatedevice”parameters,andthenclickthe“Calculate”button,thenthepagewilldisplaytheresult.Ifnotselectthe“Calculatedevice”,thenitdefaultselectsallthedevices.Displayasfollow:

    Fig.4-22

  • Owner‘sManual

    23

    Fig.4-23

    Clickthe“Setting”button,popupthedialogueframe,tosetthecalculationmethodofelectricitypriceClickthe“Export”thenitwillexportthedisplayedresultstothexls/txt/csvform.Thexlsformdisplayasfollow.

    Clickthesearchicon,andcarryoutthesearchingoperationsforthecontentsinthepage.Suchastypein“40200”,thenthepagewilldisplaythesearchingresults.

    Fig.4-24

    Energyconsumptionresultsareonlyforreference,notuseforcommercialcalculatingrecord.Abouttheelectricquantitydivisionprinciplepleaseconsultrelevanttechnicalpersonnel(usingthisfunction,itisregardedasaccepttheelectricquantitydivisionprinciple).Softwarehasthefunctionofautomaticbackupdata,Wesuggesttoexportthereportonceamonth.Ifitisneededtoquerythereportthreemonthsagofromnowon,pleaseconsultrelevanttechnicalpersonnel.

    4.10 Public device

    For thecommercialofficebuildingorapartmenthotel,and for thecorrectnessofelectricquantitydivision,itneedstosetthepublicdevice.ThecostproducedbytheidleandpublicdeviceswillbesharedbyotheruseddevicesinIMMsystem,Notdisplayintheexportreport.

  • Owner‘sManual

    24

    Fig.4-25

    Findtherelativeairconditioningdeviceintheoperateddevice,clickthe“aspublicdevice”or“asidledevice”button,anddivideittothepublicdeviceoridledevice.Idledevicemeansthedevicesarenotused;publicdevicemeansthedevicesinthepublicplace,suchasair-conditioningdevicesinthehall or corridor.

    4.11 Device management

    1) Providesthegroupdivisionfunction,convenientfordevicemanagement,displayasfollow:

    Fig.4-26

  • Owner‘sManual

    25

    Fig.4-27

    2)Clicktherelativegroupoption, thecorrespondingdevice in thegroupwillbedisplayedin theright of the page.

    ■Addgroup:Theaddinggroupmethodof theoutdoorunit is thesameas the indoorunit (Takeadding the

    secondarygroupofindoorunit):

    Fig.4-26

    Click theprimarygroup“Building”,andthenclick the“Add”button, type in thesecondarygroupname(4floor).Andclick“Save”button, thenitestablishedsecondarygroup(4floor)bothat indoorunitandoutdoorunit,andselectthedevicesneedtobeaddedinthe“4floor”,leftclickthe“4floor”andchoosethe“addtheselecteddevicesinto4floor”.

    Successfullyaddedthedevice,the4floorgroupwilldisplaytheaddeddevices.Devicesonlycanbeaddedinthesecondarygroup.

    ■Changetheindoorunitmodel Fig.4-28

  • Owner‘sManual

    26

    Fig.4-30

    Whentheuserselectsthecorrespondingmodel,theindoorunitpicturewillchange.

    Selectasingleormoresetair-conditioningdeviceundersecondarygroup,rightclickthenwillasthefollowdisplay,pop-uptheoptionofchangingtheindoorunitmodel.

    ■M-INTERFACEgatewaydisplay:Clickthe“IMMWEBcontroller”,thepagedisplayasfollow:

    Fig.4-29

  • Owner‘sManual

    27

    Theleftpagewilldisplayall thegatewaydevicesandtheir terminals,clicktherelativeterminals,therightof thepagewilldisplay theair-conditioningdeviceunder the terminal;1-4are indoorunitterminals,5-8areoutdoorunitterminals.

    4.12 Data statisticsCalculatetheoperationchangingrecordsofindoorunit,outdoorunitandM-INTERFACEgateway.

    Check theexecutionstatusof thescheduleand thechangingstatusof thedevice through thisfunction.

    Fig.4-31

    Select the“Start time”, “Endtime”and“Deviceclass”parameters,andthenclick the“Calculate”button,thenthepagewilldisplaytheresult.Displayasfollow:

    Fig.4-32

  • Owner‘sManual

    28

    Fig.4-33

    Clickthesearchiconinthecalculationpage,andtheresultwillbedisplayedinthepage.Suchastypein“41106”,thenthepagewilldisplaythesearchingresultsasfollow:

    Fig.4-33

    Clickthe“Export”button;exportthepageresulttothexls/txt/csvform,thexlsformdisplayasfollow:

    4.13 Note Alarm

    Whenthedevicehaserror,thesystemautomaticallynotifytherelevantpersonnelintheformoftextmessage.Informthemthattheyshouldrepairtheairconditioningdeviceimmidiatily.

  • Owner‘sManual

    29

    Fig.4-34

    AccessSMScathardwarefirst,andthenaddtherecipientphonenumber,configurationparame-ters,When theairconditioninghaserror, thesystemautomaticallysend textmessages to therecipient.

    4.14 Log

    DisplaytheIMMsystemoperationrecordsbyalltheuser.

    Fig.4-35

    Selectthe“Starttime”,“Endtime”and“Logtype”parameters,theLogtypehas:orders,schedule,andenergysaving,loginandsmallloadprompting(meansenergy-requiringislowerthesettingvaluewhen theoutdoorunit isoperated).And thenclick the “Calculate”button,and then thepagewilldisplaytheresult.Clickthe“Reset”button,theselectionframewillbecleared.

  • Owner‘sManual

    30

    Fig.4-36

    Clickthesearchicon,andcarryoutthesearchingfunction.Suchastypein“login”,thenthepagewilldisplaythesearchingresults,displayasfollow:

    Fig.4-37

  • Owner‘sManual

    31

    Click the“Export”button;export thepageresult to thexls/txt/csv form, thexls formdisplayasfollow:

    4.15 Prompt message

    If there ispromptmessage, the iconwillbecomered.Usercanclick“Promptmessage” icon, tochecktherelativeinformation,displayasfollow:

    Fig.4-39

    Fig.4-38

    Prompttypeinclude:cleaningthefilterscreen(remindingtheusertocleanthefilterscreen),smallloadoperation,operatefailedanddisconnectwithserver.Clickapromptmessage,thebottomoftheinterfacewilldisplaydetailedinformationofthismessage.Ifchecked“PopupthenewestMessage”,thenthepromptdialogueframewillbeautopopped-upwhentherehaspromptmessage.

    4.16 Alarm message

    Whentherewasdeviceerror, lostconnection, thesystemwouldhasalarmmessage.Thealarmframedisplayasfollow:

  • Owner‘sManual

    32

    Fig.4-40

    Afterthealarmsituationremoval,thealarmframewilldisplaythealarmhasbeenremoved.Clickapromptmessage, thepagewilldisplaydetailsof this information. Ifcheckthe“Popupthenewestprompt”, then itwillautomaticallypopupthisprompt framewhenthere ispromptmessage.Whentherewasalarmmessage,itshouldbemaintainedimmediately.

    5. TROUBLESHOOTING

    5.1 Login failed

    1)Failtoconnecttheserver

    Fig.5-1

  • Owner‘sManual

    33

    Theabovefiguremeansthepasswordwaswrong.Itneedstore-typeinthecorrectpassword.

    5.2 Control failed

    1) Whensettingthemodelimit,itmightbecausedcontrolfailed.Suchastheheatingmodelimithasbeenset,thenopenthecoolingmode,andwhichwillcausecontrolfailed,andthefailedinforma-tionwilldisplayinthepromptmessageframe.Itneedstoun-locktheair-conditioner,anddothemode setting again.

    2) Iflimitedtheremotecontroller,andthenusetheremotecontrollertocontroltheair-conditionerwillcause operation failed.

    3) Whencontrollingtheindoorunit,ifitwasfailed,thenfoundoutthereasonthroughthepromptmessage.

    5.3 No respond in page

    Ifthepagecannotbeoperated,thenshouldchecktheconnectingiconinthelowerleftofthepagetojudgewhetheritwasnormallyconnectedtotheserver,ifconnectionfailed,thenitneedstocontactthelocaldealerortechnicianstomaintainthenetwork.

    Carryouttheloginoperationwhenitisnotconnecttheserver,theresultbedisplayedastheabove;itshouldcheckwhether theclient-sideconfiguration informationarecorrectandthenetworkof theserverandclient-sideiswork,andtheclient-sideandthedatabasehasbeenconnected

    2)Wrongpassword

    Fig.5-2

  • Owner‘sManual

    34

    E0 Wrongphaseorderornonephase P1 Anticoldairordefrostingprotection

    E1 Communicationerror P2 High temperature protection of condenser

    E2 T1 sensor error P3 Temperature protection of compressor

    E3 T2Asensorerror P4 Temperatureprotectionofairexhaustingpipe

    E4 T2B sensor error P5 Protectionforhighairexhaustingpressure

    E5 Airexhaustingtemp.sensorerrorofT3orT4ordigitalcompressor P6

    Protectionforlowairexhaustingpressure

    E6 Zero crossing detection error P7 Poweroverpressureprotection

    E7 EEPROMerror P8 Compressorovercurrent

    E8 Fanspeeddetectionlosecontrol PF Other protections

    E9 Communicationerrorbetweenmainboardanddisplayboard 0#Communicationerrorbetweennetworkconnector module and main control board

    EA Compressorovercurrent(4times) 1#Communicationerrorbetweencentralizedmonitorandnetworkconnector module

    EB Invertermoduleprotection 2# Communicationerrorbetweencentralizedmonitorandfunctionmodule

    EC Fresherror 3#Communicationerrorbetweencentralizedmonitorandcomputer(gateway)

    ED Outdoor unit error protection 4# Orderlimitexecution

    EE Waterleveldetectionerror 5# Ordertimesout,noexecution

    EF Other errors 6# Exceptedaddressdonotexist

    P0 Temperature protection of evaporator 7# Wrong(not-supported)order

    6. APPENDIX

    6.1 Error code analysis of client-side interface

    ThefollowingerrorcodetablesaresuitablefortheV4+seriesindoorandoutdoorunits.Whentherewaserrorpleasecontacttechniciansformaintenanceimmediately.

    Indooruniterrorcodetable: Table.6-1

  • Owner‘sManual

    35

    E0 Outdoor unit communication error P2Protectionforlowairexhaustingpressure

    E1 Wrongphaseorderornonephase P3 Compressorcurrentprotection1

    E2 Indoorunitcommunicationerror P4Temperature protection of air exhaustingpipe

    E3Airexhaustingtemp.sensorerrorofT3orT4ordigitalcompressor P5

    High temperature protection of condenser

    E6 T6sensorerror P6 Invertermoduleprotection

    E9 Voltageerror P7 Compressorcurrentprotection2

    EF Other errors P8 Compressorcurrentprotection3

    H0 DSPcommunicationerror P9 Poweroverpressureprotection

    H1 Networkcommunicationerror PA Defrosting protection

    H2 Outdoorunitreducingerror(Validformain unit) PD Oil return

    H3 Outdoorunitincreasingerror(Validfor main unit) PEOil averaging

    P0Protectionforcompressortoptemperature PF

    Other protections

    P1 Protectionforhighairexhaustingpressure

    Outdooruniterrorcodetable: Table.6-2

  • MD12U-010CW202055100873