INSTALLATION & OWNER’S MANUAL
IMM - SOFTWARE AND SOFT DOG.
Thank you very much for purchasing our product, Before using it, please read this manual carefully and keep it for future reference.
NOTE
CONTENTS PAGE
● Thismanualgivesdetaileddescriptionoftheprecautionsthatshouldbebroughttoyourattention during operation.
● Inordertoensurecorrectserviceofthispaper,pleasereadthismanualcarefullybeforeusing the unit.
● Forconvenienceoffuturereference,keepthismanualafterreadingit.
● Astheproductupdates,thisdocumentwillbechangedwithoutpriornotice.
IMM INTRODUCTION ................................................................................................................................ 1
SOFTWARE INSTALLATION .................................................................................................................... 4
SETTING .................................................................................................................................................... 5
OPERATION INSTRUCTION ..................................................................................................................... 8
TROUBLESHOOTING ..............................................................................................................................32
APPENDIX ................................................................................................................................................34
Owner‘sManual
1
1. IMM INTRODUCTION
1.1 IMM system introduction
IMMsystemistheshortnameofIntelligentManager.Itconsistsofthreeparts:IMMsoftware,M-interfacewebgatewayandV4+outdoorunitrefrigerantsystem.TheIMMsystemcanconnect4M-interfacegatewaysatmost,totallycouldjoinup64refrigerantsystems.TheIMMsoftwarecancommunicatewithnetworkandM-INTERFACEgateway,tocontrolandmanagetherefrigerantsystem.TheIMMsystemframeworkastheFig.1-1display.
IMMsoftwareinstalledinthecomputer,andtheM-INTERFACEgatewayconnectstothecomputerthroughLANport.LaptopandPadcanvisitWEBpageofM-INTERFACEthroughwirelessnetwork.
1.2 Models which could be inserted
1) Projectswhichdonotneedelectricquantitydivision:canfreelyinsertV4+units.
2) Projectswhichneedelectricquantitydivision:connecttheV4+seriesoutdoorunitsandindoorunits,andwiringtheM-netterminalcommunicationwirefromtheoutdoorside.
3) Details consult relevant technical personnel.
1.3 IMM network introduction
IMMsoftwareincludesserversoftware,cline-sidesoftwareanddatabasesoftware.Installtheserversoftwareandthedatabasesoftware in thesamecomputer, thiscomputerandtheM-INTERFACEshouldbeinthesamesubnetsegment(fordetails,pleasereferto3.1).Thecline-sidecanconnecttotheserverthroughthelocalorremotenetwork.
Fig.1-1
Owner‘sManual
2
1.3.2 Remote network connection
Theclient-sideandserveralsocanusetheremotenetwork(VPN)connection.VPNhasrouterestablishingandcomputerestablishingmethods,andtheremotenetworkconnectionneedssomeITknowledgeandneedstheITprofessionalstoassist.1) Routerestablishing
VPNtunnelsestablishbetweenrouters,andthencanvisitWEBinterfacethroughVPNtunnels.VPNServercanbeestablishedbyoneselfandalsocanberented.Itstopologystructureasfollowdisplay:
2)computerestablishing
UseVPNclient-sidesoftwareandVPNServer toestablishVPNtunnel, thenusercanvisittheserver throughVPNtunnel.VPNclient-sidesoftwareandVPNServercanbeachievedbycommercialways.Itstopologystructureasfollowdisplay:
1.3.1 Local network connection
Thecline-sidecanconnect totheserver throughthe localnetwork, the localnetworkconnec-tionasthefollowingdisplay:
Fig.1-4
Fig.1-3
Fig.1-2
Owner‘sManual
3
1.4 IMM software functions
UsercanoperatetheIMMclient-sidesoftwaretomonitoringtheair-conditioningsystem.ThefunctionsofferedbyIMMsoftwareasthefollowingdisplay:
Mainfunctionsasfollow:1) Device monitoring
Offercontrolandmanagementofindoor/outdoorunitfortheM-INTERFACEgateway.
2) Device guide Usercanseethelocationoftheair-conditioningdevice.
3) Schedulemanagement Offers schedule control function of indoor unit.
4) Energysavingmanagement Offers energy saving control function of indoor unit.
5)Statisticsofenergyconsumption Offerselectricquantitydivisionfunctionofair-conditioningsystem.
6) Device management Offersthegroupdivisionfunctionofair-conditioningdevice.
7) Data statistics Providesthestatuschangingrecordsofindoorunit,outdoorunitandM-INTERFACEgateway.
8) Log Offersalltherecordsoftheclient-sideoperationswhichoperatedbytheuser.
Fig.1-5
Owner‘sManual
4
Table.2-1
2. SOFTWARE INSTALLATION
2.1 Installation preparation
BeforetheIMMsoftware installation, itneedstomakesuretheair-conditioningsystemoperatednormally,M-INTERFACEgatewayworkednormally, thecommunicationbetweenM-INTERFACEgatewayandair-conditioningsystemwasnormal,and itneedstomeet thefollowinghardwareandsystemrequirements.
2.2 Software installation
About thedetailspleaseconsult relevant technicalpersonnel.Thissystemneedstoberegularlycheckedbytheprofessionaltoensureitrunscorrectly.
Specification Recommendation Remark
PC
CPU:i3oraboveInternalstorage:2GoraboveHarddisk:120GoraboveKeyboard/MousewithmiddlewheelNetwork:108ASE-TScreenresolutionshouldover1024*768Screensizeshouldover17inch
RecommendedthatIBMorDELLproducts
Mustbedesktop(Notebookcomputerorother types of computers isnotallowed),andensure the computer worksnormallybeforeinstallingthesoftware.
SystemMicrosoftWindowsXPProfes-sionalServicePack3/Windows7Flagshipedition32-bitsystems.
Document form NTFS
Owner‘sManual
5
Afterconfiguration,clickthe“OK”button.
3. SETTING
3.1 IP address setting
Default IPofM-INTERFACEgateway is192.168.100.40,subnetcovercode is255.255.255.0.TheM-INTERFACEgateand IMMservermustbestayed in thesamesubnetwork, twowaysofrealization:amendtheM-INTERFACEgateIPandconfigurethestaticstateIPforserver.
3.1.1 Configure static IP
Generallyconfiguresingle IP, if the IPaddressofcomputercannotbeamended, thenconfigureseveralIP.Methodsasfollow(Takewindows7systemforexample):1)ConfiguresingleIP
OpenthepropertydialogueboxtoconfiguretheIPaddressandsubnetcovercode,forexample:IP:192.168.100.44,subnetcovercode:255.255.255.0.
Fig.3-1
Owner‘sManual
6
Fig.3-2
2)ConfigureseveralIP
BeforeconfigureseveralIP,itneedtoconfigureastatisticIPaddress.Openthepropertydialoguebox,selectthe“Advanced”,anddisplaytheTCP/IPsettingdialogueboxasfollow:
Click the “Add” button in IP address bar, add a IP address in the same net areawith“192.168.100.40”,e.g.:IP:192.168.100.101,subnetcovercode:255.255.255.0,andthenclick the“Add”button.
3.1.2 Amend gateway IP
BeforeamendingtheIPaddressofM-INTERFACEgateway,itneedsacomputertovisittheWEBpageofM-INTERFACE,thenentertheIPaddressamendingpagethroughthecomputer.Thepagedisplayasfollow:
Owner‘sManual
7
Fig.3-3
Aftertyping,click“OK”tosave.DonotconflictwithotherIPinthenetwork,detailedIPaddressassignmentneedstoconsultthenetworkadministrator.
3.2 Software operation setting
Beforesoftwareoperation,set theserversoftware,client-sidesoftwareanddatabasesoftware.Aboutthedetailssettingpleaseconsultrelevanttechnicalpersonnel.Aftersetting, insertthedongle(dongleisonlyusedforthissystem,pleasekeepthedongleproperly),andstarttheserversoftwareandthenstarttheclient-sidesoftware.
Owner‘sManual
8
4. OPERATION INSTRUCTION
4.1 User login
OperatetheIMMclient-sidesoftware,popupthelogininterfaceasthefollowdisplay:
Fig.4-1
After“Connecttotheserversuccessfully”wasdisplayedatthelowerleftofthelogininterface,thencan carry out the login operations. Stepsofcarryingouttheloginoperationsasfollow:1)Typeinuser’spassword,thedefaultisuser;2)Choosewhethersavethepassword;3)Click[OK]tocarryoutlogin;4)Click[Cancel]toexitthispage;
Whenclickedthe“OK”button,afterloginsuccessfully,thenenterintothesystemhomepage.Ifloginfailed,pleaserefertoAppendix5.1.
4.2 User log out
Clicktheicon onupper-rightcorner,exitthesystem,andtheinterfacedisplayasfollow:
Owner‘sManual
9
4.3 System initialization
After theuser loginsuccessfully, thenwillshowout thesysteminitializationdialogueframe,andcarryouttheinitializationofthewholesystem,updatethesysteminformation.Theitializationdialogueframedisplayasfollow:
Fig.4-3
Fig.4-2
Owner‘sManual
10
MenuFunction
Display
Informationtip
Clickthe“Exitthesystem”button,thenwillstoptheinitializationworkandexistthesystem.
4.4 Main interface introduction
Thesystemhomepagedisplayasthefollow:
Fig.4-4
Menu:systemfunctionsmenu.Functions: functions inmenu, includedevicemonitoring,schedulemanagement,energysaving
management,statisticsofenergyconsumption,publicdevice,datastatisticsand logetc. functions.Display:displaydetailedinformationofeachfunction.Informationtip:displaythepromptmessageandalarminformation.Theupper-rightcorneroftheinterfacewilldisplaythesoftwareversionanduser’sloginname.
4.5 Devices monitoring
Thispartisdisplayedas3classesofair-conditioningindoorunit,outdoorunitandM-INTERFACEgateway.Eachclasswillbedisplayedasprimarygroupandsecondarygroup.E.g.:undertheindoorunititwilldisplaytheprimarygroup:Buildings;andundertheprimarygroupitwilldisplaysecondarygroup:firstfloor,secondfloor,thirdflooretc.Detailedgroupsettingpleaserefersto4.10.
Owner‘sManual
11
4.5.1 M-INTERFACE gateway monitoring
Choose theM-INTERFACEgatewayselection; the interfacewilldisplayall theM-INTERFACEgatewaydevicesintheIMMsystem.
Fig.4-5Thereare3displaystatusesofM-INTERFACEgateway: lostconnection, lockedandselected.
WhenselectedorrightmouseclickaM-INTERFACEgatewaydevice,thebottomofinterfacewoulddisplay its IPaddressand itwhetherhas limitmode,andtheusercancontrol theM-INTERFACEgatewaydevicethroughthemethodofsettingthelimitmodeparameters,emergencystopparametersandthenclick the“send”button.Usercanamendthedevicename:double-click thedevicename,thenamendit,andpressenterkeytosave.E.g.:selecttheM-INTERFACEgatewaydevicesnamed40and41(selectingmethodrefersto4.5.4),andchoosethe“limitmode”parameters,andthenclickthe“send”button,thepagedisplayasfollow:
Fig.4-6
Owner‘sManual
12
Parameters Specifications
Limit mode Locked:cannotoperateintheWEBpageofM-INTERFACEUn-locked:RemovethelockingofM-INTERFACEgatewaydevice.
Emergencystop
----:Notcarryouttheemergencystopfunction.Stop:Carryouttheemergencystopfunction,stopallthedevicesoftheM-INTERFACEgateway.
Icon Specifications Icon Specifications
M-INTERFACEdeviceworknormal
M-INTERFACEdevicelocked
M-INTERFACEdevicelost connection
M-INTERFACEdeviceselected
Fig.4-7
Iconspecifications: Table.4-2
Aftersuccessfullyset“Limitmode”,thedeviceiconwilladdaniconwithlocker.
Parametersspecifications: Table.4-1
Statusselection:Thegatewaydevicehas3statuses: locked ( Locked ), lostconnection ( Offline ) and selected
( Selected ).Clickthecorrespondingstatusicontochecktherelativedevice.Clickthelostconnectionicon,anditwilldisplayallthedeviceswhichlostconnection.Rightclickthe“selected”icon,anditwillpopuptheselectionframeof“Allselect/cancelallselect”,choose“Allselect”thenitwillselectalltheiconsintheinterface,andclick“cancelallselect”thenitwillcancelselectingalltheicons.
4.5.2 Outdoor unit monitoring
Selecttheoutdoorunitclass,theleftsideofinterfacewilldisplaythegroupinformationundertheindoorunit,andtherightwilldisplaythecorrespondingoutdoordevice.
Owner‘sManual
13
Icon Specifications Icon Specifications Icon Specifications
Outdoor unit lost connection(White)
OutdoorunitisOFF,outdoorambienttemp.is21°C.(Gray)
Outdoor unit operates cooling,outdoorambienttemp.is24°C.(Blue)
Outdoor unit error (Red)
Outdoor unit operates heating, outdoor ambienttemp.is24°C.(Orange)
Outdoor unit is selected, outdoorambienttemp.is25°C.
Theoutdoorunitdisplaystatus:error,lostconnection,cooling,heatingandselected.Selectorrightmouseclickaoutdoorunit,thenchecktheonandoffstatus,ambienttemperature,ammeterreadingsetc.detailedinformationofthisdeviceinthe“Devicedetailsinformation”.Iconspecifications: Table.4-3
Fig.4-8
4.5.3 Indoor unit monitoring
Select the indoorunitclass, the leftsideof interfacewilldisplay thegroup informationunderthe indoorunit,andtherightwilldisplayall the indoorunits in theIMMsystem,select the“devicecontrol”tocarryoutthecontroloperationforoneormoresetsindoorunits;selectthe“devicedetailsinformation”tochecktheoperatingdetailinformationofadevice.1) ChecktheoperatingstatusofindoorunitChoosethe“devicedetail information”,selecta indoorunit, thenthebottomof the interfacewill
displaytheoperatingdetailinformationofthisdevice.Displayasfollow:
Statusselection:Theoutdoorunitdisplaystatus:error ( Error ), lostconnection( Offline ),cooling( Cool ), heating
( Heated ),offunit( Off )andselected( Selected ).Clicktheerror,lostconnection,cooling,heatingandselectediconsbythemouse,thentheinterfacewilldisplayallthecorrespondingstatus.E.g.:clickthecoolingicon,thenitwilldisplaythedevicesundercoolingstatusintheselectedgrouponthepage,displayasfollow:
Owner‘sManual
14
Fig.4-9
Displayeddetail information:onandoffstatus,operatingmode,devicenameanddevicenumberetc.
2) ControltheoperatingstatusofindoorunitChoosethe“Devicecontrol”,selectoneormoresetsindoorunits(selectingmethodrefersto4.5.4),
in thebottomof the interfaceconfigureparameters:onandoffsetting,modesetting,operatingfanspeed, temperaturesettingandswingingsetting,andclick “send”buttonaftersetting,displayasfollow:
Fig.4-10
Owner‘sManual
15
Icon Specifications Icon Specifications Icon Specifications
Indooruniterror(Red)
Indoorunitoperatesheating,indoorambienttemp.is25°C.(Orange)
Indoorunitislocked,indoorambienttemp.is25°C.
Indoorunitlostconnection(White)
Indoorunitoperatesfan,indoorambienttemp.is25°C.(Green)
Indoorunitisselected,indoorambienttemp.is25°C.
Indoorunitoperatescooling, indoor ambienttemp.is25°C.(Blue)
IndoorunitisOFF,indoorambienttemp.is25°C.(Gray)
The control order is carryingout,pleasewait
Theinterfacewilldisplaythe iconswhichwait forbeingsent,after theorderexecution, the iconswilldisappear,andtheinterfacewillberefresh,thencanviewtheoperatingstatusofthecontrolorderhadbeenexecuted. Ifcontrol failed, the“Promptmessage” in the interfacebottomwilldisplay thecontrol failed information.
Iconspecification Table.4-4
Statusselection:Theindoorunitdisplaystatus:error( Error ),lostconnection( Offline ),schedule( Schedule ), cooling
( Cool ),heating( Heated),fan( Fan ),offunit( Off ), locked( Locked )andselected( Selected ).Clicktheerror, lostconnection,schedule,cooling,heating, fan,offunit, lockedandselected iconsbythemouse,thentheinterfacewilldisplayallthecorrespondingstatus.Rightclickthe“selected”icon,anditwillpopuptheselectionframeof“Allselect/cancelallselect”,choose“Allselect”thenitwillselectalltheiconsintheinterface,andclick“cancelallselect”thenitwillcancelselectingalltheicons.Right-click the“locked” icon, then itwilldisplay the locked lists,andclick thecorresponding list thenwilldisplay the relative devices.
4.5.4 Shortcut keys operation
Shortcutkeysoperationsofmouse:Thesystemoffersshortcutkeysoperationsofmouse,whichconvenientfortheusertoselect/canceloneormoresetsdevicesquickly.
1) Selectsingleicon Left-clicktheicon,iftheiconwasframedthenmeansitwasselected.
2) Selectseveralicons Therearetwowaysforselectingseveralicons:
■Selectseveraliconsasthewayofselectingsingleicon. ■Left-clickoutsidetheframeintheinterface,dragadottedlineframetoselectthecorresponding
icons.
3) Cancelsingleselectedicon Left-clickontheselectedicon,thencancelselectingtheicon.
4) Cancelseveralselectedicons Therearetwowaysforcancelingseveralselectedicons:
■Cancelseveralselectediconsasthewayofcancelingsingleselectedicon. ■Double-clicktheleft/middle/rightkeyofthemouseintheblankplaceofthepage,tocancel
several selected icons.
Owner‘sManual
16
FunctionshortcutkeysoperationsRight-clickthe Selected icon,thenitwillpopuptheselectionframeof“Allselect/cancelallselect”,
choose“Allselect”and“Cancelallselected” toselectandcancelquickly.Theoperationstepsasfollow:1)Selectthe“indoorunit”or“outdoorunit”class(orprimarygrouporsecondarygroup).2)Clickastatusdisplayicon(cooling,heating,error,offunitetc.),suchasclickthecoolingstatusicon,theinterfacewilldisplaythedevicesofcorrespondinggroupundercoolingstatus.
3)Clickthe“selectall”option,thenallthecoolingdeviceinthepagewillbeselected,andifclickthe“canceltheselectedall”,alltheselectediconswillbecanceledselecting.
4.6 Device guide
Offer the functionofusercansee the locationof theair-conditioningdevice.Rightclickonesecondarygroup,willpop-uptheoptionsof“Startchangingdevice’slocation”and“Changethefloorplan”,andclick“Changethefloorplan”,thendisplayasfollow:
Fig.4-11
Userselects thecorresponding floorplan(thepicturewillsave in themap folderof theclient-sideinstallationmenus),andthenclick“Save”button,afterfinishedtheoperation,thenclick“Close”button.Afterselect thefloorplan, thenclick“Startchangingdevice’s location”,usercanselectonedevice, and then drag it on the interface to change its location.
Owner‘sManual
17
4.7 Schedule management1) Schedulemanagementoffersthescheduleoperationsforair-conditioningindoorunit.Displayas
follow:
2) Schedulemanagementoperationstepsasfollow:
■Addthename
Fig.4-13
Fig.4-12
Clickthe“Add”button,typeinschedulename.
■Adddevice
Clickthe“Deviceselecting”button,thenitwillpopuptheadddeviceframeasthefollowingdisplay:
Owner‘sManual
18
Fig.4-14
Click the “Non-selecteddevice”option,select thedeviceandclick the “add”button.Click the“Selecteddevice”option,andthenitshowsuptheselecteddevices.Choosetherelativedevices,andclick“Move”tomovethedevicesinto“Non-selecteddevice”.Afterselection,click”OK”andthenclosetheselectionframe.Thepagewilldisplaytheselecteddevices.
Fig.4-15
Owner‘sManual
19
■Controlparameterssetting
Fig.4-16
Setthetime,onandoffstatus,mode,fanspeed,temperature,swingingparameters.Clickthecancelicontocancelthesetting.
■ Time selecting Therearetwowaysofaddingtime:Choosedateorweek.Date:Clickthedateundercorrespondingmonth,selectthemonthanddatewhichdisplayedinred.Week:checktherelativeweek,thenthisdayofeachweekwillbelistedintheschedule.SuchasselectedMonday,theneveryMondaywillcarryoutthisschedule.
■SaveAftersetting,clickthesavebutton,anddisplayasthefollowing:
Fig.4-17
Owner‘sManual
20
Fig.4-18
Theupperleftcornerofthepagewilldisplaytheaddedschedulename.Andtherightdisplayedtheaddeddevice.If it’sthefirsttimesettingscheduleofthedevice,thentheiconwilladdthescheduleicon.Use the“Datastatistics” tocheck theexecutionstatusof theschedule.About the importanttiming plan, You should set again after 5 minutes.
4.8 Energy saving managementEnergysavingmanagementofferstheenergysavingcontroloperationsforair-conditioningindoor
unit.Onlythenewtypeofindoormachinesupportsthisfunction,Displayasfollow:
Fig.4-19
Owner‘sManual
21
Selection Specifications
Coolingtemp.limit Setthelowestlimitofcoolingtemp.,andlimit the remote controller control
Heating temp. limit Setthelowestlimitofheatingtemp.,andlimit the remote controller control
On and off unit limit Limit the indoor unit on and off operations of the remote controller
Modelimit Limit the unit cooling, heating mode operations
Fanspeeddisplay Limitthefanspeedcontrolbytheremotecontroller
Swinginglimit Limittheswingingcontrolbytheremotecontroller
Remotecontrollerlimit Limittheairconditioneroperationsbytheremote controller
Theleftsidewilldisplaytheindoorunitgroupinformation,andselectoneormoresetsindoorunitsandchoosetheenergysavingoption,thenclickthe“Set”button.Aftersetting,theairconditionericonwilldisplaythelockedicon.Ifitneedstoremovethelimit,thenchoosethe“Remove”option,andclickthe“Set”buttonforremovingthelimit,thenthelockediconwilldisappear.Ifitfailedthecontrol,checkthefailed information in the“Promptmessage”.Click therightkeyof themouseonan indoorunit,thenthebottomoftheinterfacewilldisplaythelockingdetailinformationofthisdevice.
Optionsspecification: Table.4-5
4.9 Statistics of energy consumption
Thisfunctioncalculatestheresultsofthedevice’selectricquantitydivisioninaperiod.Thisfunctionneedstobeactivatedforuse.displayasfollow:
Fig.4-20
Owner‘sManual
22
Iftheuserneedsthisfunctionpleaseconsultthedealer,andgettheactivationcodetoactivatethisfunction.Theactivatedpageasfollowingdisplay:
Fig.4-21
Selectthe“Starttime”,“Endtime”and“Calculatedevice”parameters,andthenclickthe“Calculate”button,thenthepagewilldisplaytheresult.Ifnotselectthe“Calculatedevice”,thenitdefaultselectsallthedevices.Displayasfollow:
Fig.4-22
Owner‘sManual
23
Fig.4-23
Clickthe“Setting”button,popupthedialogueframe,tosetthecalculationmethodofelectricitypriceClickthe“Export”thenitwillexportthedisplayedresultstothexls/txt/csvform.Thexlsformdisplayasfollow.
Clickthesearchicon,andcarryoutthesearchingoperationsforthecontentsinthepage.Suchastypein“40200”,thenthepagewilldisplaythesearchingresults.
Fig.4-24
Energyconsumptionresultsareonlyforreference,notuseforcommercialcalculatingrecord.Abouttheelectricquantitydivisionprinciplepleaseconsultrelevanttechnicalpersonnel(usingthisfunction,itisregardedasaccepttheelectricquantitydivisionprinciple).Softwarehasthefunctionofautomaticbackupdata,Wesuggesttoexportthereportonceamonth.Ifitisneededtoquerythereportthreemonthsagofromnowon,pleaseconsultrelevanttechnicalpersonnel.
4.10 Public device
For thecommercialofficebuildingorapartmenthotel,and for thecorrectnessofelectricquantitydivision,itneedstosetthepublicdevice.ThecostproducedbytheidleandpublicdeviceswillbesharedbyotheruseddevicesinIMMsystem,Notdisplayintheexportreport.
Owner‘sManual
24
Fig.4-25
Findtherelativeairconditioningdeviceintheoperateddevice,clickthe“aspublicdevice”or“asidledevice”button,anddivideittothepublicdeviceoridledevice.Idledevicemeansthedevicesarenotused;publicdevicemeansthedevicesinthepublicplace,suchasair-conditioningdevicesinthehall or corridor.
4.11 Device management
1) Providesthegroupdivisionfunction,convenientfordevicemanagement,displayasfollow:
Fig.4-26
Owner‘sManual
25
Fig.4-27
2)Clicktherelativegroupoption, thecorrespondingdevice in thegroupwillbedisplayedin theright of the page.
■Addgroup:Theaddinggroupmethodof theoutdoorunit is thesameas the indoorunit (Takeadding the
secondarygroupofindoorunit):
Fig.4-26
Click theprimarygroup“Building”,andthenclick the“Add”button, type in thesecondarygroupname(4floor).Andclick“Save”button, thenitestablishedsecondarygroup(4floor)bothat indoorunitandoutdoorunit,andselectthedevicesneedtobeaddedinthe“4floor”,leftclickthe“4floor”andchoosethe“addtheselecteddevicesinto4floor”.
Successfullyaddedthedevice,the4floorgroupwilldisplaytheaddeddevices.Devicesonlycanbeaddedinthesecondarygroup.
■Changetheindoorunitmodel Fig.4-28
Owner‘sManual
26
Fig.4-30
Whentheuserselectsthecorrespondingmodel,theindoorunitpicturewillchange.
Selectasingleormoresetair-conditioningdeviceundersecondarygroup,rightclickthenwillasthefollowdisplay,pop-uptheoptionofchangingtheindoorunitmodel.
■M-INTERFACEgatewaydisplay:Clickthe“IMMWEBcontroller”,thepagedisplayasfollow:
Fig.4-29
Owner‘sManual
27
Theleftpagewilldisplayall thegatewaydevicesandtheir terminals,clicktherelativeterminals,therightof thepagewilldisplay theair-conditioningdeviceunder the terminal;1-4are indoorunitterminals,5-8areoutdoorunitterminals.
4.12 Data statisticsCalculatetheoperationchangingrecordsofindoorunit,outdoorunitandM-INTERFACEgateway.
Check theexecutionstatusof thescheduleand thechangingstatusof thedevice through thisfunction.
Fig.4-31
Select the“Start time”, “Endtime”and“Deviceclass”parameters,andthenclick the“Calculate”button,thenthepagewilldisplaytheresult.Displayasfollow:
Fig.4-32
Owner‘sManual
28
Fig.4-33
Clickthesearchiconinthecalculationpage,andtheresultwillbedisplayedinthepage.Suchastypein“41106”,thenthepagewilldisplaythesearchingresultsasfollow:
Fig.4-33
Clickthe“Export”button;exportthepageresulttothexls/txt/csvform,thexlsformdisplayasfollow:
4.13 Note Alarm
Whenthedevicehaserror,thesystemautomaticallynotifytherelevantpersonnelintheformoftextmessage.Informthemthattheyshouldrepairtheairconditioningdeviceimmidiatily.
Owner‘sManual
29
Fig.4-34
AccessSMScathardwarefirst,andthenaddtherecipientphonenumber,configurationparame-ters,When theairconditioninghaserror, thesystemautomaticallysend textmessages to therecipient.
4.14 Log
DisplaytheIMMsystemoperationrecordsbyalltheuser.
Fig.4-35
Selectthe“Starttime”,“Endtime”and“Logtype”parameters,theLogtypehas:orders,schedule,andenergysaving,loginandsmallloadprompting(meansenergy-requiringislowerthesettingvaluewhen theoutdoorunit isoperated).And thenclick the “Calculate”button,and then thepagewilldisplaytheresult.Clickthe“Reset”button,theselectionframewillbecleared.
Owner‘sManual
30
Fig.4-36
Clickthesearchicon,andcarryoutthesearchingfunction.Suchastypein“login”,thenthepagewilldisplaythesearchingresults,displayasfollow:
Fig.4-37
Owner‘sManual
31
Click the“Export”button;export thepageresult to thexls/txt/csv form, thexls formdisplayasfollow:
4.15 Prompt message
If there ispromptmessage, the iconwillbecomered.Usercanclick“Promptmessage” icon, tochecktherelativeinformation,displayasfollow:
Fig.4-39
Fig.4-38
Prompttypeinclude:cleaningthefilterscreen(remindingtheusertocleanthefilterscreen),smallloadoperation,operatefailedanddisconnectwithserver.Clickapromptmessage,thebottomoftheinterfacewilldisplaydetailedinformationofthismessage.Ifchecked“PopupthenewestMessage”,thenthepromptdialogueframewillbeautopopped-upwhentherehaspromptmessage.
4.16 Alarm message
Whentherewasdeviceerror, lostconnection, thesystemwouldhasalarmmessage.Thealarmframedisplayasfollow:
Owner‘sManual
32
Fig.4-40
Afterthealarmsituationremoval,thealarmframewilldisplaythealarmhasbeenremoved.Clickapromptmessage, thepagewilldisplaydetailsof this information. Ifcheckthe“Popupthenewestprompt”, then itwillautomaticallypopupthisprompt framewhenthere ispromptmessage.Whentherewasalarmmessage,itshouldbemaintainedimmediately.
5. TROUBLESHOOTING
5.1 Login failed
1)Failtoconnecttheserver
Fig.5-1
Owner‘sManual
33
Theabovefiguremeansthepasswordwaswrong.Itneedstore-typeinthecorrectpassword.
5.2 Control failed
1) Whensettingthemodelimit,itmightbecausedcontrolfailed.Suchastheheatingmodelimithasbeenset,thenopenthecoolingmode,andwhichwillcausecontrolfailed,andthefailedinforma-tionwilldisplayinthepromptmessageframe.Itneedstoun-locktheair-conditioner,anddothemode setting again.
2) Iflimitedtheremotecontroller,andthenusetheremotecontrollertocontroltheair-conditionerwillcause operation failed.
3) Whencontrollingtheindoorunit,ifitwasfailed,thenfoundoutthereasonthroughthepromptmessage.
5.3 No respond in page
Ifthepagecannotbeoperated,thenshouldchecktheconnectingiconinthelowerleftofthepagetojudgewhetheritwasnormallyconnectedtotheserver,ifconnectionfailed,thenitneedstocontactthelocaldealerortechnicianstomaintainthenetwork.
Carryouttheloginoperationwhenitisnotconnecttheserver,theresultbedisplayedastheabove;itshouldcheckwhether theclient-sideconfiguration informationarecorrectandthenetworkof theserverandclient-sideiswork,andtheclient-sideandthedatabasehasbeenconnected
2)Wrongpassword
Fig.5-2
Owner‘sManual
34
E0 Wrongphaseorderornonephase P1 Anticoldairordefrostingprotection
E1 Communicationerror P2 High temperature protection of condenser
E2 T1 sensor error P3 Temperature protection of compressor
E3 T2Asensorerror P4 Temperatureprotectionofairexhaustingpipe
E4 T2B sensor error P5 Protectionforhighairexhaustingpressure
E5 Airexhaustingtemp.sensorerrorofT3orT4ordigitalcompressor P6
Protectionforlowairexhaustingpressure
E6 Zero crossing detection error P7 Poweroverpressureprotection
E7 EEPROMerror P8 Compressorovercurrent
E8 Fanspeeddetectionlosecontrol PF Other protections
E9 Communicationerrorbetweenmainboardanddisplayboard 0#Communicationerrorbetweennetworkconnector module and main control board
EA Compressorovercurrent(4times) 1#Communicationerrorbetweencentralizedmonitorandnetworkconnector module
EB Invertermoduleprotection 2# Communicationerrorbetweencentralizedmonitorandfunctionmodule
EC Fresherror 3#Communicationerrorbetweencentralizedmonitorandcomputer(gateway)
ED Outdoor unit error protection 4# Orderlimitexecution
EE Waterleveldetectionerror 5# Ordertimesout,noexecution
EF Other errors 6# Exceptedaddressdonotexist
P0 Temperature protection of evaporator 7# Wrong(not-supported)order
6. APPENDIX
6.1 Error code analysis of client-side interface
ThefollowingerrorcodetablesaresuitablefortheV4+seriesindoorandoutdoorunits.Whentherewaserrorpleasecontacttechniciansformaintenanceimmediately.
Indooruniterrorcodetable: Table.6-1
Owner‘sManual
35
E0 Outdoor unit communication error P2Protectionforlowairexhaustingpressure
E1 Wrongphaseorderornonephase P3 Compressorcurrentprotection1
E2 Indoorunitcommunicationerror P4Temperature protection of air exhaustingpipe
E3Airexhaustingtemp.sensorerrorofT3orT4ordigitalcompressor P5
High temperature protection of condenser
E6 T6sensorerror P6 Invertermoduleprotection
E9 Voltageerror P7 Compressorcurrentprotection2
EF Other errors P8 Compressorcurrentprotection3
H0 DSPcommunicationerror P9 Poweroverpressureprotection
H1 Networkcommunicationerror PA Defrosting protection
H2 Outdoorunitreducingerror(Validformain unit) PD Oil return
H3 Outdoorunitincreasingerror(Validfor main unit) PEOil averaging
P0Protectionforcompressortoptemperature PF
Other protections
P1 Protectionforhighairexhaustingpressure
Outdooruniterrorcodetable: Table.6-2
MD12U-010CW202055100873