43
INSTALLATION - OPERATING & MAINTENANCE MANUAL ECOLOGIC 08-2002

INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

  • Upload
    others

  • View
    12

  • Download
    0

Embed Size (px)

Citation preview

Page 1: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

INSTALLATION -OPERATING &MAINTENANCE MANUAL

ECOLOGIC08-2002

Page 2: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions
Page 3: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 1

CONTENTS

1. PREFACE ....................................................................................................................................... 3

2. WARRANTY ................................................................................................................................... 4

3. SAFETY ......................................................................................................................................... 43.1. Safety Definitions ............................................................................................................................ 53.2. Warning labels ............................................................................................................................. 5-6

4. LAY-OUT AND INSTALLATION ..................................................................................................... 74.1. Preparations ................................................................................................................................... 74.2. Delivery and Transport .................................................................................................................... 9

4.2.1. Warnings .................................................................................................................... 104.2.2. Antifreeze protection .................................................................................................. 10

4.3. Installation ................................................................................................................................... 104.4. Commissioning ............................................................................................................................. 124.5. Start-up ................................................................................................................................... 124.6. De-commissioning ........................................................................................................................ 13

5. COOLING PROCESS .................................................................................................................. 14

6. MODELS NUMBERS DESCRIPTION .......................................................................................... 15

6.1 ECOLOGIC™ CHILLER MODELS .............................................................................................. 166.1. Models ................................................................................................................................... 166.2. Construction ................................................................................................................................. 166.3.Part Summary ................................................................................................................................ 176.4. Refrigerant flow diagrams ............................................................................................................. 18

6.4.1. ECOLOGIC™ chillers with Climatic Control System .................................................. 186.4.2. ECOLOGIC™ chillers with Climatic II Control System ............................................... 21

6.5. Checking of the ECOLOGIC™ chiller ........................................................................................... 246.6. Part Descriptions .......................................................................................................................... 24

6.6.1. Main Components ...................................................................................................... 246.6.2. Accessories ................................................................................................................ 256.6.3. Control panel and safety features ............................................................................... 256.6.4. Options ....................................................................................................................... 26

7. SAFETY DURING OPERATION................................................................................................... 297.1. Safety and Protection Features ..................................................................................................... 297.2. Safety during de-commissioning ................................................................................................... 29

8. CONTROL .................................................................................................................................... 30

9. MAINTENANCE ........................................................................................................................... 309.1. General ................................................................................................................................... 309.2. Maintenance schedule for operating personnel ............................................................................ 329.3. Maintenance schedule for qualified personnel .............................................................................. 339.4.Replacement of warning labels ...................................................................................................... 35

10. FAULT MESSAGES AND FAULTS .............................................................................................. 35

11. REFRIGERANT HANDLING ........................................................................................................ 3611.1. General ................................................................................................................................... 3611.2. Technical points to remember ..................................................................................................... 36

11.2.1. The glide effect ........................................................................................................ 3611.2.2. Charging the installation with refrigerant .................................................................. 3611.2.3. Charging of an installation with R-407c .................................................................... 37

12. POSSIBLE FAULT CAUSES ........................................................................................................ 37

13. ABBREVIATIONS ........................................................................................................................ 38

Page 4: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 2 - IOM ECOLOGIC

COPYRIGHT

All the technical and technological information contained in this manual, including any drawing andtechnical descriptions provided by us, remain the property of Lennox and must not be utilised (exceptin the operation of this product), reproduced, issued to or made available to third parties without theprior written agreement of Lennox.

Page 5: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 3

1.PREFACE

Please read this operating manual prior tocommissioning the ECOLOGIC™ chiller. Familia-rise yourself with the operation and control of theECOLOGIC™ chiller and closely follow the instruc-tions.

We would like to stress the importance of training withrespect to the correct handling of the chiller. Pleaseconsult Lennox on the options available in this field.

It is important that this manual be stored in a perma-nent location in the vicinity of the ECOLOGIC™ chiller.For the sake of clarity, important items in this manualare shown as follows:

Text Important general instructions.

Text Important instructions relating tonormal operating conditions.

! NOTE text Danger of damage to the chiller.

! NOTE text Danger of personal injury.

PREFACE

This manual contains important instructions regardingthe commissioning of the ECOLOGIC™ chiller. It alsoincludes important instructions to prevent personalinjury and damage to the machine during operation.Furthermore, in order to promote fault-free operationof the chiller, maintenance information has beenincluded.

Please do not hesitate to contact one of our employeesshould you require further information on specific chillersubjects.

Order related documentation will be forwarded underseparate cover. This documentation consists of:

! CE declaration.

! Operating manual for control system.

! Installation Operating manual

! Wiring diagram.

! Refrigerant flow diagram.! Unit detail are given on unit nameplate.

FOR NETHERLAND : the STEK logbook, includingthe required certificates will be handed over by theinstallation technician or left with the machine followingcommissioning by Lennox.

The data published in this manual is based on the mostrecent information available. It is supplied conditionalto later modifications. We reserve the right to modifythe construction and/or design of our ECOLOGIC™chillers, at any time, without prior notification orobligation to adapt previous supplies accordingly.

Any work on the Chiller should be carried out bytrained and licenced competent technician.

The following risks are present on the unit :

! risk of electrical shock

! risk of injury from rotating parts

! risk of injury from sharp edges andheavy weight

! risk of injury from high pressure gas

! risk of injury from high and lowtemperatures components.

Page 6: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 4 - IOM ECOLOGIC

3.2. Warning labels

The chiller is marked with the following warning labels toalert to potential hazards (on or near the potentiallyhazardous part).

Check regularly that the warning labels are still in the cor-rect positions on the machine and replace them if necessary.Relevant instructions are provided in chapter 9.4.

WARRANTY & SAFETY

High temperatures Electrical voltage

Rotating parts Sharp parts

2.WARRANTY

The warranty of the chillers is subject to the warrantydefinitions as agreed upon in the order.It is expected that the design and installation of theunit utilises good working practices.

The warranty will be legally null and void if:

! Service and maintenance have notbeen executed in accordance with theregulations, repairs have not beencarried out by Lennox personnel or havebeen implemented without prior writtenpermission by Lennox.

! Modifications have been made to theequipment without prior writtenpermission by Lennox.

! Settings and protections have beenmodified without prior writtenpermission by Lennox.

! Non-original or other than the prescribedrefrigerants or lubricants are used.

! The equipment has not been installedand/or connected in accordance with theinstallation instructions.

! The equipment is being used improperly,incorrectly, negligently or not inaccordance with its nature and/orpurpose.

! A flow protection device is not fitted.

In these circumstances Lennox is indemnified fromany product liability claims from third parties.

In the event of a warranty claim the machine serialnumber and Lennox order number must be quoted.

3. SAFETY

The safety information contained in this manual isprovided as a guide for the safe handling of thisinstallation. Lennox does not vouch for thecompleteness of this information and can thereforenot accept liability for any possible omissions.

In the ECOLOGIC™ chiller, heat is being transportedby a pressurised refrigerant, with changes in pressureand temperature. Fans have been provided todischarge heat into the environment. The entire processtaking place in the chiller is described in chapter 4.The protection of operating and maintenance person-nel was central in the design of the ECOLOGIC™chiller. Safety features have been included to preventexcessive pressure in the system. Sheet metal partshave been fitted to prevent inadvertent contact with (hot)pipes. The fans are equipped with protective grids andthe electrical control panel is completely touch-proof.This excludes some parts operating at a safe voltage(< 50 Volt). The service panels can only be openedusing tools.

Notwithstanding the fact that the ECOLOGIC™chiller is equipped with extensive safety and pro-tection features, the utmost care and attention isneeded when carrying out operations on the ma-chine. Furthermore, ear protection should be wornwhen working on or in the vicinity of theECOLOGIC™ chiller. Operations on the cooling cir-cuit or electrical equipment should be carried outby authorised personnel.

3.1. Safety Definition

The ECOLOGIC™ chiller meets the following safetydefinitions:

!!!!! Pr-EN-378-1.

!!!!! EU Directive 89/392/EG ("Machine Directive").

!!!!! EN-60204-1.

!!!!! "EMC Directive".

!!!!! Pressure Equipment Directive 97/23/CE.

!!!!! RLK (Netherlands)

And is provided with CE markings.(on the condition that thenecessary options are present)(for further information see II-A declaration).

Page 7: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 5

Fig. 1. Warning labels on the outside of the 1F, 2F and 3F-models.

Fig. 2. Warning labels on the inside of 1F, 2F and 3F-models.

The illustrations below indicate the various warning label locations on the unit.

WARRANTY & SAFETY

Page 8: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 6 - IOM ECOLOGIC

Fig. 3. Warning labels on the outside of 4F, 6F and 8F-models.

Fig. 4. Warning labels on the inside of 4F, 6F and 8F-models.

WARRANTY & SAFETY

Page 9: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 7

LAY-OUT AND INSTALLATION

4. LAY-OUT AND INSTALLATION

! NOTE:

This chapter contains important instructionsrelating to the safe installation of the ECOLOGIC™chiller.

4.1. Preparations

The following preparations are important for theinstallation of the ECOLOGIC™ chiller:

! The ECOLOGIC™ air-cooled chiller isdesigned for outdoor installation. Pleaseconsult Lennox prior to implementing othertypes of installation.

! The foundations and lay-out should provideadequate space around the machine forchecking and service operations. The safetyaspect of these operations should also betaken into account. This free area is alsorequired for an unrestricted air supply to thecondenser. The free area is set with aminimum all round clearance of 1.5 m,providing there are no objects in the vicinitythat are higher than the machine itself.Locate the chiller where it is least affectedby wind (install windbreaks where windspeeds > 2.2 m/s). The foundations shouldprovide for the machine to be level, affordsufficient support for the load and keepvibration to a minimum.

! NOTE:

For fault-free operation the chiller should becompletely level (insert shims below vibrationabsorbers if necessary).

Please consult Lennox in the event of queries ordoubt on the lay-out options.Information on dimensions and weights is includedin the above mentioned specification sheet and thedimensional drawing of the machine.

Page 10: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 8 - IOM ECOLOGIC

LAY-OUT AND INSTALLATION

Fig.7. Free area 1F-, 2F- and 3F-models

Fig. 8. Free area 4F-, 6F- and 8F-models

1,5 m

1,5 m 1,5 m

1,5 m

1,5 m

1,5 m 1,5 m

1,5 m

Page 11: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 9

LAY-OUT AND INSTALLATION

4.2. Delivery and Transport

We recommend that the machine is checked fortransport damage immediately after delivery. Anytransport damage should be reported immediately tothe transporter and within 24 hours to Lennox. Thetransport of the machine to the installation site isprovided by Lennox. Unloading, however, is theresponsibility of the installer. If transport damage isnot reported immediately, any guarantee claims willbe void.

Also check that the delivery is complete (see packinglist) and that the required documentation is includedwith the machine (in the switch compartment).

The transport and lifting instructions illustrated in thedrawing below should be observed during transporton the assembly site.

These instructions are also displayed on the exteriorof the machine. The machine should be moved withsuitable lifting gear.

! NOTE:

The heat exchangers of the condensers are protected from damage during transport by plastic plates.The machine is also wrapped in packing foil. It is recommended to leave this protection in place duringany transport and lifting operations, and not to remove the plastic plates until commissioning (take carethat the protecting foil wrapping is not blown away!).

! NOTE:

Rubber AVM & factory accessories are to be found in the control pannel for shipping.If the unit is mounted on AVM these should be fitted to the unit before final positioning.

Page 12: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 10 - IOM ECOLOGIC

LAY-OUT AND INSTALLATION

4.2.1. WARNINGS

Water connections - Evaporator

The use of a water filter in the water circuit upstreamof the heat exchanger is mandatory. These filters mustremove all particles with a diameter greater than 1 mm.They may be supplied as an option by the manufactu-rer.

Water analysis

The water must be analysed ; the water circuitryinstalled must include all items necessary for treatmentof the water : filters, additives, intermediate exchangers,bleed valves, vents, isolating valves etc... according tothe results of the analysis.We do not advise operation of the units with open loopswhich can cause problems with oxygenation, noroperation with untreated ground water.Use of untreated or improperly treated water can causedeposits of scale, algae and sludge or cause corro-sion and errosion. It is advisable to call in a qualifiedwater treatment specialist to determine what kind oftreatment will be necessary. The manufacturer cannotaccept liability for damage caused by the use ofuntreated or improperly treated water, salt water orbrine.

4.2.2. ANTIFREEZE PROTECTION

Use glycol/water solution

ADDITION OF GLYCOL IS THE ONLY EFFICIENTWAY TO PROTECT AGAINST FREEZE-UP

The glycol/water solution must be sufficientlyconcentrated to ensure proper protection and preventformation of ice at the lowest outdoor air temperaturesexpected on an installation.Take precautions when using non passivated MEGantifreeze solutions. Corrosion can occur with theseantifreeze solutions in the presence of air.

Drain the installation

It is important to make sure that manual or automaticair bleeders are installed at all the high points of thewater circuit. To enable drainage of the circuit, makesure that drain cocks are installed at all the low pointsof the circuit.To drain the circuit, the drain cocks must be openedand an air inlet ensured : air bleeders are not designedto admit air.

FREEZE UP OF AN EVAPORATOR DUE TO COLDWEATHER CONDITIONS CANNOT GIVE RISE TOA WARRANTY CLAIM.

4.2.3. ELECTROLYTIC CORROSION

We would like to draw your attention to the problemsof corrosion due to electrolytic corrosion caused by animbalance between earthing points.

AN EVAPORATOR THAT IS PUNCTURED BYELECTROLYTIC CORROSION IS NOT COVEREDBY THE UNIT WARRANTY.

4.3. Installation

The following requirements and safety features shouldbe observed during the installation of the ECOLOGIC™chiller.

! ECOLOGIC™ chillers are designed forapplication in a closed chilled water circuit.

! When delivered the water connections of theECOLOGIC™ chillers are sealed to preventdirt from entering the system. These sealsshould be left intact as long as possible.Thewater connections of the ECOLOGIC™chiller are fitted with groove-lock couplings.On option, the two corresponding couplingsand two 20-cm long pipes with smooth endscould be included for connection. If required,the pipes can be welded, or threaded at thesmooth end to be fitted to the piping system.Obviously the groove-lock system can beused for further assembly. Whichever optionis selected, it is important that the pipes arefitted to the piping system first, and that theconnection with the chiller is made at the lastmoment.

NOTE : GREASE SEAL BEFORE INSTALLATION.

The rubber packing should be greased beforefitting the groove-lock coupling.

Ensure that the pipe connections are stress-free.When connecting the water lines to the machineensure that the connections to the machine are nottwisted or connected the wrong way around.

Page 13: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 11

LAY-OUT AND INSTALLATION

! If the machine is installed on vibrationabsorbers, compensators should beincorporated in the chilled water lines. Thesecompensators should be fitted between theconnections of the chiller and the first fixedsupport point of the piping. We recommendthat compensators are also used insituations where the machine is not installedon vibration absorbers. This will prevent thetransmission of vibration via the hydrauliccircuit.

! A flow protection, which will switch off thechiller if the chilled water flow through themachine is interrupted, should be includedin the chilled water circuit. This flowprotection could be a vane switch, anelectronic flow switch or a differentialpressure switch. With a differential pressureswitch only the pressure difference on theevaporator should be measured. The settingshould be checked regularly to preventpossible pollution.

! Provisions should also be made to measurethe amount of chilled water. These arenecessary to establish whether theECOLOGIC™ chiller is functioning within itsapplication range.

! To protect the chiller a filter should beincluded in the chilled water circuit (60 mesh,mesh size 0.25 mm). This filter should befitted directly in front of the chiller (seen inflow direction). The filter should be checkedat least twice a year. This considerablyreduces any water side pollution of theevaporator.

! The chilled water system should be flushedand clean prior to connection of theevaporator. A venting device should beinstalled at the highest point of the chilledwater circuit piping.

! If there is a possibility of the machineoperating long term at a high input watertemperature, a mixing control should beincluded in the chilled water circuit. Thismixing control should limit the water inputtemperature to the maximum acceptablevalue to prevent overloading of thecompressor and the machine from cuttingout due to a high pressure fault.

! The minimum required content of the chilledwater circuit is included in the ApplicationGuide. If the total water content of the systemis below this value, a buffer tank should beincluded in the chilled water circuit. Thecontent specified above is based on normalair conditioning applications. Highercapacities may be required if used in otherapplications. Consult Lennox if this shouldbe the case.

! Connections for the supply voltage, the startcommand, the external protections andpossible fault messages should be linked tothe relevant terminals in the control panel inaccordance with the wiring diagram.

! If additional feed-throughs are made duringinstallation, the switch compartment shouldbe thoroughly cleaned following assemblyso that no metal parts remain amongst theswitch material. Any blank plate parts leftbehind as a result of the holes being drilledshould be coated with preservative toprevent corrosion.

! Finally, it is recommended that thermometersand pressure gauges be included in the chilledwater inlet and outlet lines in the immediatevicinity of the chiller. This will simplify checkingoperations and will assist in the search for thepossible cause(s) of a fault.

Page 14: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 12 - IOM ECOLOGIC

4.4. Commissioning

Initial commissioning

The initial commissioning should be carried out byLennox. Please, contact Lennox Sales Offices in orderto make an appointment.

Checking prior to commissioning (to be carriedout by installation technician)

! Check the points mentioned in chapter 7.3.

! Check the chilled water circuit and allconnections to the chiller for leakage.

! Check the direction of the pump and the flowdirection of the chilled water. (It isrecommended to mark the direction of thepump and the flow direction in the pipingcircuit with arrows.)

! Check that the chilled water flow agrees withthe nominal flow (see Application Guide). Inpractice the flow protection will usually onlyprotect the chiller from switching on whilstthere is (practically) no flow in the chilledwater circuit. In that case the flow protectionshould be set at the highest possible value(providing this is below the nominal value).

! Rinse the piping system by operating thepump(s) for some time. Then clean all filtersin the installation.

! Check that there are no restrictions to theairflow over the condenser.

! Check that the supply voltage is correct.ECOLOGIC™ chillers are designed tooperate in a clockwise direction. Thedirection of the field should therefore bechecked and the 2 phases changed over toensure correct rotation if necessary.

! Once the lines have been connected andthe installation has been filled, the level ofmachine should be re-checked.

! Check the adjustment of the spring vibrationabsorbers if applicable.

4.5. Start-up

Prior to starting the chiller, the installation engineershould ensure that the following conditions are met:

LAY-OUT AND INSTALLATION

! The chilled water system should be filled withthe correct amount of water or water/glycol.

! The main and control current switchesshould be switched on at least 6 hours priorto start-up in order to heat the oil in thecompressor crankcases and/or oilseparators. Depending on the chiller model,this will also require the auxiliary supply tobe switched on. This supply is also switchedvia the main switch.

! The oil level in the compressor sight-glassshould be between ½ and ¾ the way up thesight-glass.

! The pressure in the refrigerant circuitsshould correspond to the pressure of therelevant refrigerant at ambient temperature.

! The chilled water pump valves should beopened.

! Checks should be made to establish thepresence of air in the chilled water system,which should be vented if necessary.

! The chilled water pumps should now bestarted.

! If a water/glycol mixture is used, checksshould be made to ensure that the mixtureis in accordance with the design value.Samples can be taken once the pumps havecirculated the mixture for approximately 10minutes. The mixture must be brought tothe design value prior to starting the chiller.

! Checks should be made to ensure that thedischarge, suction and liquid valves in therefrigerant circuits are open (if present,optional)

Once all the above conditions have been met theECOLOGIC™ chiller can be started.

! Consult the wiring diagram and operatingmanual of the control system to familiariseyourself with the operation/control of themachine.

! Once all external release conditions havebeen met (start command, flow protection,pump switch) and the load is sufficient, theECOLOGIC™ chiller will start up.

Page 15: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 13

On all ECOLOGIC™ chillers the machine brieflyremains blocked when the mains voltage is switchedon. This is required to create the correct start-upconditions (see operating manual of the relevant controlsystem and / or the wiring diagram).

Checking the operating conditions:

The operating conditions should be checked shortlyafter start-up, but not before stable operating conditionshave been established. The following are importantvalues: discharge and suction pressure in therefrigerant circuit(s), the chilled water inlet and outlettemperatures and the ambient temperature. Comparethese conditions with the data provided.

The ECOLOGIC™ chiller will always start at the lowestcapacity level. Release of the consecutive capacitylevels will take place after a set time, depending onthe chilled water inlet and/or outlet temperature.During checking of the operating conditions, referencecan also be made to the values included in the wiringdiagram.

4.6. De-commissioning

The following actions should be completed to de-commission the ECOLOGIC™ chiller (see alsochapter 6.2):

! Remove the start command from theterminal strip on the control panel (see wiringdiagram).

! Leave the main and control current switcheson to maintain the temperature of the oil inthe compressor crankcases or oil separatorsand to keep any heating tapes operating.

! In the event that there is a risk of freezing,Lennox recommends that the chilled watercircuit be drained and blown through withcompressed air. All valves in the refrigerantcircuit(s) should be closed. The main switchshould then be switched off.

If the chiller is to be taken out of service for anextended period, the refrigerant should be pumpeddown by authorised personnel. Open discharge,suction and liquid valves (if present) and bring therefrigerant circuits to slight overpressure usingnitrogen gas. Make occasional checks to ensurethat the pressure in the system remains constant.

LAY-OUT AND INSTALLATION , CONTROL&MAINTENANCE

Page 16: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 14 - IOM ECOLOGIC

COOLING PROCESS

The ECOLOGIC™ chiller has been designed to cool wateror a water/glycol mixture. In the evaporator, heat is

extracted from the liquid to be cooled throughevaporation of refrigerant. The refrigerant is circulatedby the compressor through a closed circuit. A pressure-

enthalpy diagram of the cycle is shown below. Duringthe cycle the refrigerant is subject to the following

changes of state.

5.COOLING PROCESS

The ECOLOGIC™ chiller has been designed to coolwater or a water/glycol mixture. In the evaporator, heatis extracted from the liquid to be cooled throughevaporation of refrigerant. The refrigerant is circulatedby the compressor through a closed circuit. A pressure-enthalpy diagram of the cycle is shown below. Duringthe cycle the refrigerant is subject to the followingchanges of state.

1-2 The refrigerant gas given off by theevaporator is compressed by thecompressor, causing temperature andpressure to rise.

2-3 The compressed gas originating from thecompressor is cooled to saturationtemperature in the aircooled condenser,following which condensation occurs atconstant pressure.Finally the liquidrefrigerant is subcooled by a fewdegrees.

3-4 The subcooled liquid is expanded toevaporation pressure in the expansionvalve. Part of the liquid will evaporateduring expansion.

4-1 In the evaporator the liquid refrigerant willevaporate at constant pressure. Therequired heat is extracted from the liquid tobe cooled. Finally, in the last part of theevaporator the gaseous refrigerant issuperheated.

1

2 3

4

Vapour +liquid

Vapour (super- hea ted)

Sa turation line

Entha lpy

Pressure

L iquid (subcooled)

! Notes:

Subcooling in the condenser is required to ensure that the refrigerant flows entirely in liquid form to theexpansion valve. This valve will only operate satisfactorily if the refrigerant enters entirely in liquidform.

Superheating of the refrigerant gas in the evaporator is required to prevent the liquid refrigerant fromentering the compressor. Liquid refrigerant in the compressor could result in excessive dilution of thelubricant.

The expansion valve ensures that only the amount of refrigerant necessary to reach the requiredsuperheating of the refrigerant gas after the evaporator is allowed through.

Refrigerants R-407c and R-22 are used in the ECOLOGIC™ chillers. Both these refrigerants are includedin group L1, based on the prEN-378-1 classification, in which they are classified in safety group A1.According to this classification, A1 is the group with the lowest flammability and toxicity risk. For furtherinformation refer to the refrigerant manufacturer’s documentation, which is available on request fromLennox.

Page 17: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 15

MODEL NUMBER DESCRIPTION

WA 150 D K STD

Number of circuitsE = 1D = 2

STD = StandardSTD Plus=Standard PlusLN = Low NoiseSLN = Super Low NoiseHE = High Efficiency

RefrigerantA = R22K = R407C

Liquid ChillersWhit air cooled condenserfitted with axial fans

Cooling Capacityat Eurovent point

6. MODEL NUMBER DESCRIPTION

Page 18: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 16 - IOM ECOLOGIC

WA

=

Waterchillers,

Air-cooled

Model IDENTIFICATION

Chiller Unit version / type Circuits RefrigerantSTD/STD Plus /LN SLN / HE

2F 100E 40E45E E=Single circuit R407C

110E 65E75E

3F 90D 100E Or130D 110E R22150D D=Double circuit

4F 200D 90D230D 130D

150D6F 300D 200D

370D 230D8F 300D

370D

In addition to the already mentioned differencesbetween the versions, two fundamentally differentcontrol systems are employed in the ECOLOGIC™range, as illustrated in the table below.

Unit version Control system

High Efficiency, HE Climatic II Control SystemSuper Low Noise,SLN

Standard, STD Climatic II Control SystemStandard Plus, STD Plus OrLow Noise, LN Climatic Control System

The technical data of the ECOLOGIC™ chiller isincluded in the before-mentioned specification sheetand the dimensional drawing.

ECOLOGIC™ CHILLER MODELS

6.1 MODELS

The ECOLOGIC™ chiller is available in four basicversions: the Standard (STD), Standard Plus(STD Plus)the low noise (LN), the High Efficiency (HE) and theSuper Low Noise (SLN) version.

With the exception of the fans, the four models areconstructed of the same components. The low noiseversion is equipped with low speed fans.

This results in a lower noise level. Furthermore thecompressors in the LN version are covered withacoustic jackets and in the SLN and HE versions, thecompressors are fitted inside a sound insulatedhousing.

The model indication of the chillers is illustrated in thefollowing table.

6.2 Construction

The ECOLOGIC™ chillers are constructed of a dipped galvanised frame, made up of hot-rolled UNP beams.The housing is constructed from galvanised steel plating, all exterior parts are covered with an epoxy-polyester colour coating standard in RAL-9002. A switch compartment, housing the control panel, has beenincorporated in the machine housing. The service panels of the units are mounted with stainless steel bolts.

Page 19: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 17

Model

1F 2F 3F 4F 6F 8F

STD HE LN/STD HE LN/STD HE LN/STD HE HE

Circuits 1 1 1 2 1 2 2 2 2 2

Compressors 2 3 2 4 3 6 4 6 6 6

Condensers 1 1 1 2 1 2 2 2 2 4

Fans 1 2 2 3 (90D:2) 3 4 4 6 6 8

Evaporators 1 1 1 1 1 1 1 1 1 1

Expansion valve 1 1 1 2 1 2 2 2 2 2

Liquid valve 1 1 1 2 1 2 2 2 2 2

Filter / drier 1 1 1 2 1 2 2 2 2 2

Solenoid 1 1 1 2 1 2 2 2 2 2

Sight-glass 1 1 1 2 1 2 2 2 2 2

Delivery 1 1 1 2 1 2 2 2 2 2

Suction valve 1 1 1 2 1 2 2 2 2 2

Part

(optional)

valve1)(optional)

(optional)

(optional)

ECOLOGIC™ CHILLER MODELS

6.3. Part Summary

The ECOLOGIC™ chiller range consists of thefollowing main parts:

! Hermetic scroll compressors.! Air-cooled condensers, made up of copper

pipe, with aluminium fins, whereby the airflow is provided using axial fans.

! A plate evaporator, a single circuit plateevaporator for the E models, a double circuitplate evaporator, whereby both circuits areinterwoven, for the D models.

! Expansion valve, depending on the type ofcontrol system. thermostatic on the ClimaticControl System, thermostatic or electronicon the Climatic II Control System.

! Switch compartment containing the entireprotection and control system(see also chapter 5.7.3).

The following table shows the number of parts per model.

1): On the Climatic II, the function of the solenoid valve is handled by the electronic expansion valve.

The refrigerant flow diagrams of the various models are included in the next chapter for clarification.

The refrigerant circuits are completed with copperrefrigerant flow lines, including the followingaccessories (for each refrigerant circuit):

! Liquid valve

! Filter / drier

! Solenoid valve (optional)

! Sight-glass with moisture indicator (optional)

! Discharge and suction valve (optional)

LNSTD Plus STD Plus STD Plus STD PlusSTD STD STD STD STD

Page 20: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 18 - IOM ECOLOGIC

ECOLOGIC™ CHILLER MODELS

6.4.1.ECOLOGIC™ chillers with Climatic Control System

6.4. Refrigerant flow diagrams

WA-100E – WA110E.

Water inlet

Water outlet

Air cooled condenser

Eev

EVt SGlr SVlr FD

CF1

CF2

TE

TSla

TE

TE

PSl PSh

Vs

Vd

SCd

SCs

TE

*2

*2

CF3

Vlr

M

M

Ec

Ec

CH2

CH3

M

Ec

CH1

SCl

*1

*1

*1 *1

*1

*3

Compressers

Plate evaporator

*1: Option*2: Sensors in blindcaps at the back of the evaporator*3: For SLN-execution

Aircooledcondeser

Water inlet

Water outlet

Page 21: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 19

WA90D-STD/STD Plus LN – WA150D-STD/STD Plus LN.

Air cooled condenser circuit 1

*1: Option *2: For 130D and 150D

Air cooled condenser circuit 2

M

M

M

M

FD SVlr SGlr EVt

Eev

EVt SGlr SVlr FD

PV

Ec

Ec

Ec

Ec

CF1.1

CF1.2

TE

PSl

TSla

TE

TE

PSh

Vs

Vd

Vs

Vd

SCd

SCd

CH1

CH2

CH3

CH4

SCs

SCs

TE

PSl

PSh

Vlr

SCl Vlr

SCl

*1 *1 *1

*1

*1

*1

*1

*1

*1CF1.3

TE

*2

Water inlet

Compressorscircuit 1

Compressorscircuit 2

Water outlet

Plate evaporator

WA90D-SLN – WA150D-SLN + WA200D-STD/STD Plus LN+ WA230D-STD/STD Plus LN.

Water inlet Water outlet

Compressorscircuit 1

Compressorscircuit 2

Plate evaporator

ECOLOGIC™ CHILLER MODELS

Air cooledcondensercircuit 1

Air cooledcondensercircuit 2

Air cooledcondensercircuit 1

Air cooledcondensercircuit 2

Air cooled condenser circuit 2

Air cooled condenser circuit 1

*1: Option *2: For 200D-B/BLN and 230D-B/BLN

M

M

M

M

FD SVlr SGlr EVt

Eev

EVt SGlr SVlr FD

PV

Ec

Ec

Ec

Ec

CF1.1

CF1.2

CF2.1

CF2.2

TE

PSl

TSla

TE

TETE

PSh

Vs

Vd

Vs

Vd

SCd

SCd

CH1

CH2

CH3

CH4

SCs

SCs

TE

PSl

PSh

VlrSCl

Vlr

SCl

*1 *1 *1

*1

*1

*1

*1

*1

*1

CF1.3 CF2.3

*1

*2*2

*1: Option*2: For 200D-STD, STD Plus and 230D-STD, STD Plus

Page 22: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 20 - IOM ECOLOGIC

Air cooled condenser circuit 1

Air cooled condenser circuit 2

*1: Option

FD SVlr SGlr EVt

Eev

EVt SGlr SVlr FD VlrVlr

PV

CF1.1

CF1.2

CF1.3

CF2.1

CF2.2

CF2.3

TE

TSla

TE

TETE

PSl

PSh

Vs

Vd

Vs

Vd

SCd

SCd

SCs

SCs

TE

M

M

M

M

M

M

Ec

Ec

Ec

Ec

Ec

Ec

CH1

CH2

CH3

CH4

CH5

CH6

SCl

SCl

PSh

PSl

*1 *1

*1

*1

*1

*1

*1

*1*1

Air cooled condenser circuit 1

Air cooled condenser circuit 2

*1: Option

FD SVlr SGlr EVt

Eev

*1

SGlr SVlr FD VlrVlr

PV

TE

TSla

TE

TETE

PSl

PSh

Vs

Vd

Vs

Vd

SCd

SCd

SCs

SCs

TE

M

M

M

M

M

M

Ec

Ec

Ec

Ec

Ec

Ec

CH1

CH2

CH3

CH4

CH5

CH6

SCl

SCl

PSh

PSl

EVt

*1

*1 *1

*1

*1

*1

*1

*1

CF1.1

CF1.3

CF1.2

CF1 .4

CF2.1

CF2.3

CF2.2

CF2.4

ECOLOGIC™ CHILLER MODELS

Plate evaporator

WA200D-HE/SLN – WA230D-HE/SLN + WA300D-STD/STD Plus LN+ WA370D-STD/STD Plus LN.

Compressorscircuit 1

Water inlet

Compressorscircuit 2

Water outlet

WA300D-SLN/HE + WA370DSLN/HE.

Water inlet Water outlet

Compressorscircuit 2

Compressorscircuit 1

Plate evaporator

Air cooledcondensercircuit 1

Air cooledcondensercircuit 2

Air cooledcondensercircuit 1

Air cooledcondensercircuit 2

Page 23: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 21

6.4.2. ECOLOGIC™ chillers with Climatic II Control System

WA40E – WA75E SLN/HE.

Compressors

Plate evaporator

WA100E – WA110E.

Plate evaporator

Compressors

ECOLOGIC™ CHILLER MODELS

Water inlet

Water outlet

Air cooledcondenser*1: Option

*2: Sensor in blindcap at the back of the evaporator*3: Suction gas temperature, on suctionline, close to the header*4: Ambient temperature, mounted in the frame, below the switch panel

Water inlet

Water outlet

Air cooledcondenser

*1: Option*2: Sensor in blindcap at the back of the evaporator*3: Suctiongas temperature, on suctionline, close to the header*4: Ambient temperature, mounted in the frame, below the switch panel*5: For HE / SLN execution

Page 24: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 22 - IOM ECOLOGIC

ECOLOGIC™ CHILLER MODELS

WA90D-STD/STD Plus LN – WA150D-STD/STD PlusLN.

Plate evaporator

Water inlet Water outlet

Compressorscircuit 2

Compressorscircuit 1

WA90D-HE/SLN – WA150D-HE/SLN + WA200D-STD/STD Plus LN+ WA230D-STD/STD Plus LN.

Plate evaporator

Water inlet Water outlet

Compressorscircuit 2

Compressorscircuit 1

Air cooledcondensercurcuit1

Air cooledcondensercurcuit2

*1: Option*2: For 130D + 150D*3: Suctiongas temperature, on suctionline. closse to header*4: Ambient temperature, mounted in the frame, below the switchpanel

Air cooledcondensercurcuit1

Air cooledcondensercurcuit2

*1: Option*2: Suctiongas temperature, on suctionline, close to header*3: Ambient temperature, mounted in the frame, below the switch panel*4: For HE / SLN-execution

Page 25: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 23

WA200D-HE/SLN + WA230D-HE/SLN + WA300D-STD/STD Plus LN + WA370D-STD/STD Plus LN.

Plate evaporator

Water inlet Water outlet

Compressorscircuit 2

Compressorscircuit 1

WA300D-HE/SLN + WA370D-HE/SLN.

Plate evaporator

Water inlet Water outlet

Compressorscircuit 2

Compressorscircuit 1

Consult the refrigerant flow diagram sent to you under separate cover.

The abbreviations used in the previous refrigerant flow diagrams are explained in chapter 13.

ECOLOGIC™ CHILLER MODELS

Air cooledcondensercurcuit1

Air cooledcondensercurcuit2

*1: Option*2: Suctiongas temperature, on suctionline, close to header*3: Ambient temperature, in the frame, below the switchpanel

Air cooledcondensercurcuit1

Air cooledcondensercurcuit2

*1: Option*2: Suctiongas temperature, on suctionline, close to header*3: Ambient temperature, in the frame, below the switchpanel

Page 26: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 24 - IOM ECOLOGIC

ECOLOGIC™ CHILLER MODELS

6.5. Checking of the ECOLOGIC™ chiller

Following assembly, the ECOLOGIC™ chiller ispressure tested and checked for leakage. Therefrigerant circuits are then evacuated and providedwith the required operating charge of refrigerant. Finally,the ECOLOGIC™ chiller is test run under nominalconditions at the Lennox test site and checked forsatisfactory operation. The chillers are, therefore, readyfor operation upon delivery. It is possible to witness testrunning of the ECOLOGIC™ chiller at the Lennox testsite. In that case arrangements should be made viathe sales department.

6.6. Part Descriptions

6.6.1 Main Components

Compressors

Your ECOLOGIC™ chiller is fitted with hermetic scrollcompressors The motor and compressor are housedin a hermetically sealed housing, whereby the motorcooling is provided by the refrigerant gas. Compressorsare equipped with an oil sight-glass. The electric motoris provided with winding temperature protection (Klixonor thermistor).

Scroll compressors only operate correctly in thecorrect rotation direction. They therefore need tobe connected to a clockwise rotating field (phasesequence). Incorrect rotation can result in defects,but the compressor will not pump refrigerant, willbe unusually noisy and will switch off afterapproximately 20 minutes.

The compressors of one refrigerant circuit are linkedin parallel. A discharge and a suction valve are optionsfor each set. Capacity is controlled by the switching onor off of the compressors. The electrical system iscontrolled by the controls in the switch compartment.

! NOTE:

Due to their high volumetric output, scrollcompressors can reach a vacuum very quickly. Thecompressors should therefore not be used to suckin refrigerant, as this will surely lead to irreversibledamage.

Starting a compressor with the suction valve (Vs)closed will also lead to irreversible damage. Thesuction pressure of a scroll compressor must neverbe lower than 0.2 bar (manometer pressure).

The chillers are wired to ensure that when thesupply voltage is connected in a clockwisedirection, the compressors rotate in the correctdirection. The machines were also tested on theLennox test site using clockwise phase rotation.

Air-cooled condenser

The air-cooled condensers consist of one, two or fourheat exchangers, constructed of copper pipingequipped with aluminium fins. The air flow through theheat exchangers is provided by direct drive axial fans.The fans are controlled by the controls.

To protect operating and maintenance personnel frominjury, the fans are fitted with protective grids on theexhaust side (exterior of the machine).

Evaporator

The evaporator consists of a hermetically solderedpackage of stainless steel plates. The plates have beenstamped with a herringbone profile. As a result of thestaggered stacking method, channels are createdbetween the plates, through which the medium flowsin a very turbulent manner. The turbulence createscorrect heat transfer and keeps the influence ofpollution to a minimum. The plate package is arrangedin such a way that each channel through which themedium to be cooled flows is located next to a channelcontaining the evaporating refrigerant flow. This hasresulted in the creation of a very compact evaporatorwith a relatively low refrigerant content.

The double circuit plate evaporator is designed in sucha way that the consecutive refrigerant channels arealternately linked to the first or second circuit. Bothcircuits are interwoven.

The exterior of the evaporator is insulated with moistureand diffusion-proof insulation material. Optional heatingtape could be attached below the insulation material.The tape ensures that the liquid (to be cooled) in theevaporator does not freeze during low ambienttemperatures, providing there is a continuos flowthrough the evaporator. (This heating tape is not alwaysnecessary if the ECOLOGIC™ chiller is used to coola water/glycol mixture. Please refer to the chiller wiringdiagram.) On the 4F-, 6F- and 8F-models connectingpipes are fitted between the machine and theevaporator connections. These pipes are also fittedwith insulation and could possibly be fitted with optionalheating tape. The heating tape (if present) is switchedon and off by the controls.

Page 27: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 25

Thermostatic expansion valve (chillers withClimatic)

The thermostatic expansion valve is a temperature/pressure controlled regulating valve with exteriorpressure equalisation. The valve allows the correctamount of refrigerant to pass in order to achieve therequired superheating at the end of the evaporator.Temperature and pressure are measured immediatelyafter the evaporator in the suction line. Thesuperheating reduces when the load in the evaporatordrops. The valve will then adjust the refrigerant flowuntil the set (required) value is reached again.

Electronic expansion valve (Climatic II)

The function of the electronic expansion valve is thesame as that of the thermostatic expansion valve. Theprocess is managed better as a result of this valve beingcontrolled by the controls, whereby more process datais available.

6.6.2.Accessories

The refrigerant flow diagrams can also be consultedfor the descriptions of the following parts (see alsochapter 5.4). Every refrigerant circuit also includes thefollowing accessories.

Liquid valve

A valve has been fitted in the liquid line, immediatelyafter the condenser output, to be used for the refillingand pumping out of refrigerant and during operationson the filter/drier.

Filter / drier

The filter/drier is mounted in the liquid line after theliquid valve. The filter/drier absorbs any residualmoisture remaining in the chiller after the vacuumprocess.

The filter/drier also collects any residual partsoriginating from the assembly and any oil sediment.Filter/driers are applied in two versions in theECOLOGIC™ chillers.

- Hermetically seald filter/drier

- Replaceable filter/drier.

6.6.3. Control panel and safety features

The control panel conforms fully to EN-60204-1. Themain and control current groups are clearly separatedon the control panel. The ECOLOGIC™ chiller isdelivered with the wiring diagram. Part of this diagramis an illustration of the control panel layout.

Consult the operating manual of the control systemincluded in your machine (and the wiring diagram ifnecessary) for details on the operation and re-settingof the various protections.

High Pressure

The chiller is protected from excessively high operatingpressure in the high pressure side by a minimum ofone high pressure switch, which is connected to thepressure side of the compressor. The high pressureswitch will switch off the relevant circuit when the setvalue is exceeded. The high pressure switch isequipped with a reset.

Low Pressure

The chiller is protected from low operating pressure inthe low pressure side either by a low pressure switch(chillers with CLIMATIC), or by a low pressure sensor(chillers with CLIMATIC II TM), which is connected tothe controls.

Frost Protection

The evaporator is protected from damage caused byfreezing water resulting from abnormal operatingconditions by a temperature sensor in the evaporatoroutput, which is connected to the controls. (Thisprotection is not always necessary if the ECOLOGIC™chiller is used to cool a water/glycol mixture.)

ECOLOGIC™ CHILLER MODELS

Page 28: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 26 - IOM ECOLOGIC

options and accesssories

6.6.4. Options

For details on the options available on theECOLOGIC™ chiller see theApplication Guide. Consultthe wiring diagram for details of electrical options.R22

The units are supplied with HCFC22 as the refrigerant. Thisis only available as an option outside of the EEC.

When specified with R22 the unit is supplied with operationalset points and components that are suitable for operationwith the refrigerant.

Sight GlassA sight glass is provided fordetermining refrigerant con-dition if on the liquid line, onesight glass per circuit isprovided.

Low Ambient kit (all seasons)

Allows start-up and operating of the unit up to outsidetemperature down to -15°C (recommended for outsidetemperatures below +6°C).

Units equipped with basic Climatic control (Std, Std Plus &LN)

The unit is generally equipped with a low pressure switch andan antifreeze thermostat. The thermostatic expansion valveis by-passed by a solenoid valve on start-up.

Also included with this option is the compressor oil heatersand antifreeze protection heaters.

Units equipped with advanced Climatic II control (HE & SLN)

For units equipped with electronic expansion valves andCLIMATIC II, the standard programme enables the control ofthe start-up down to -20°C with no additional cost.

Alucoat 507 on condensers (Epoxy coating)

This is a anti corrosion sprayed coating that offers additionalprotection to the condenser fins for salt laden atmospheres suchas seashores and in areas of industrial pollution.

This is not suitable for heavy industrial pollution, strong alkalis,oxidizers, wet bromine and chlorine and fluorine in heavy con-centrations.

www.altena.com for additional data.

BlyGold Plus on condensers

This is an anti-corrosion coating that the coils are fully dipped inthat offers additional protection to the condenser coil for salt andmild industrial pollution.Two standards are available BlyGoldPlus Tropic the traditional gold finish for mild marine, industrialand Middle East applications. For a higher level of protection forheavy industrial and marine applications BlyGold PoluAl a silverfinish.

www.blygold.com for additional data.

Replaceable Core filter drier

Installed after thecondensers, allows thereplacement of thehygroscopic cores withouthaving to remove the bodyof the core filter.

Compressor Isolation valves

The supply and fitting ofmanual suction and dischargeisolation valves on either sideof each circuit to allow serviceon the compressors with outremoval of the full refrigerantcharge. This is recommendedif it is proposed that LENNOXcarry out the service and main-tenance work.

HP/LP gauge set

Liquid filled gauges that measuresthe evaporating Low pressure (LP)and condensing high pressure (HP)on each refrigerant circuit. Gaugesare glycerin filled to damp gas pul-sation and are mounted externally.

The gauges are compound gaugesthat display the saturated refrigeranttemperature for the variousrefrigerants available.

The same information is availableon the Climatic II controller. Becareful not to duplicate functions.Display of High and low pressure isavailable from the Climatic IIcontroller and it is not necessary toadd gauges.

Dual pressure Relief valves UDT

Refrigerant pressure relief valves are fitted on the HP and asingle pressure relief valve on LP side of the refrigerationsystem. This option has twin valves connected on a commonHP or LP header with an isolation valve. This allows onevalve to be on line at all times while the remaining valve isserviced, replaced or calibrated.

Condenser coil Guards

Removable polyestercoated metal guards thatprotect the entire conden-ser coil outer surface fromlight accidental damageduring shipping and onsite.

Also prevents to directcontact by hand of thecondenser coil sharpedges. The condensercoil guard is removable for cleaning of the condenser coil.The condenser coils guard's acts as a deterrent but do notoffer total protection.

NB : This option add 40 mm on the total unit width.

Condenser coil Guards

Compressor Isolation valves

Replaceable Core filter drier

HP/LP gauge set

Sight Glass

Page 29: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 27

options and accesssories

Mains Transformer 400V/230V

Avoids the separated power supply 230V/1/50Hz for thecompressor crankcase heaters and the optional antifreezeheater on evaporator. This enables the customer to makejust one power connection at the main switch the remainingpower to the control circuit and heaters is provided by thetransformer. The mains transformer comes fully wired andtested. This option can reduce customer's installation costsand does not require a customer to use a neutral cable.

Connection for External Trace heating

This option allows for a customer to make a connection in theLENNOX panel for external trace heating for pipe work etc.This would be activated by the antifreeze protection ther-mostat mounted on the Lennox unit. This is only possible ifAntifreeze option is selected for the chiller.

Power and control panel to IP55

Standard control panel rating is IP43which is suitable forexternal operation. In some countries the standard panelrating for external operation is to IP55. The IP55 ratingensures that the panel is waterproof when a water jet isdirected directly onto the panel. The panel also has a highermechanical strength for impact resistance.The panel is supplied with Hinged doors. Multipoint doorlatching and door seals, the wire connections are all havegland seals to maintain the IP55 sealing rating.NB :This option adds length.

Main ON/OFF switch (Door interlocked)

It allows the general cut-offand isolation of the main 3-phase power supply, when themachine is running or stopped.The main isolator also acts asa thermal overload device toprotect from excess currentdraw. If the mains transformeris fitted this switch will also cutpower from the control andanti freeze Heaters. CAUTIONIf the mains switch is in the offposition and a separate power supply is NOT provided to theanti freeze heaters Freezing can occur.The mains switch is supplied with covers on the connectionsThe mains switch is used to isolated power from the unit forsafe working on the electrical system.

Flow switch

According to the unit type, 2different flow switch types ofswitch are available: -differential flow switch or apaddle flow switch. In the case when a differentialflow switch has been selectedand the option "antifreezeheater" is selected the lines tothe flow switch are protectedfrom freezing.This switch comes piped andfitted on the evaporator and istested by the factory.

The paddle switch is supplied loose for fitting in the CHILLEDwater off line by the customer. It is also required that thecustomer wire the flow switch directly back to the controlpanel terminals provided.When a unit is selected with the pump module a paddle flowswitch is supplied fitted as standard.If a chiller is operated with out a flow switch then Freezing ofthe evaporator will occur if the chiller is operated with nowater flow warranty will be voided if no flow switch is presentin the chilled water system.

Compressor acoustic enclosure

A compressorcompartment inAluzinc steel, theinternal sides arelined withaccoustic sound-insulating foam:PAE 28 mm, 3 kg/m2 mass, protec-tion films, fire clas-sification M1.

The compartmentis fitted with lift offdoors to allowaccess to the compressors.The compartment is fitted with a forced air ventilation fan tocontrol the temperature inside the compressor acousticcabinet. Standard on SLN, option on High Efficiency only.

TUV/VDE

Units manufacturing according to the TÜV/VDE norm(electrical components, pressure devices, safety valves...).This norm is no longer required as from May 2002 thePressure Equipment Directive PED required for CE markingthis supercedes all EU local pressure certification standards(TUV, ISPESL, SDM, UDT and BS).

Reinforced evaporator insulation

One additional layer of thermal insulation of the evaporatorincreases the insulation from12.7mm to 26mm closed cellfoam that is resistant to water. Classification for fire: M1.

Double water gauges

Water gauges thatmeasure the pressureon the inlet and outletof the water circuits.The standard is to haveone pressure gauge onthe water pressure re-lief valve.

Compressor acoustic enclosure

Double water gauges

Main ON/OFF switch

Paddle Flow switch

Page 30: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 28 - IOM ECOLOGIC

options and accesssories

Service Panels

This option is to provide afull panel enclosure on theStd, Std plus and LN 100Eto 150D versions.The side of the unit whichcontains the Compressorsis fully enclosed from thebase to the top of the unitwith painted RAL 9002removable sheet metalpanels.

Chilled water connections

The chilled water connec-tions on all units areVictaulic connections eachunit is supplied with aVictaulic connector andseal for the chilled waterconnections as standard.In the event the customerneeds to have a groovedVictaulic pipe stub, whichhe can weld, screw or fitflanges too. This optionprovides the two additionalpipe stubs sections groove at one end for the Victaulicconnector and unfinished at the other end for the customerto make the connection of his choice.

Electronic Expansion valves

On the Std, Std plus and LN unit'sthermostatic expansion valves arefitted as the standard.There is the option to fit electronicexpansion valve(s) (EEV) with thisoption the Liquid line solenoid valveis also not required as the EEV actsas a isolation valve.When selecting the option ofelectronic expansion valve it is alsonecessary to select the Climatic IIcontroller.

Compressor Soft Starter

This option available on all models is to provide for the loweststarting current on the compressors. The overall startingcurrent is reduced by 25% to 35% depending on the numberof compressors and model selected.

STEKIf this option is selected the chiller is built to respect the STEKregulations. The unit is fitted with refrigerant circuit isolationvalves one in the main suction and one in discharge line ofthe main distributor to the compressors and a sight glass isfitted in each refrigerant circuit.Also included is the required paperwork and certificationdocumentation.

None standard options available

Power factor Correction; Plexy glass in the panel; Emergencystop buttons; 3 phase +neural mains isolator; Phase reversalprotection; earth leakage breaker; Architectural louvers;Chilled water pressurization unit; IP65 control panel; Highpressure condenser fans; remote power hook up for remotehydraulic module.

For these and other none standard options contact the salesteam.

Chilled water connections

Climatic II (advancedcontroller)

On the Std, Std plus andLN units the standardcontroller is the basicClimatic.

Option is to have ClimaticII advanced controller,which offers additionalcontrol and functionalityover the basic Climatic controller.

Low ambient start down to -18°C and high pressure unloadingare standard features together with high and low refrigerantpressure display on each circuit as standard.

Climatic II is supplied with KP02 removable customer inter-face.

KP07 Graphic Display

The KP07 Climatic II graphicdisplay replaces the KP02 andgives a full LCD display andkeyboard for customer inter-face. This offers additionalfunctionality and controlfeatures that are not on theKP02 (see separatespecification sheet).

Water Strainer filter

Water Strainer/ filterto be installedupstream to thewater inlet, to protectthe evaporator fromany possibleimpurities (80 mi-crons efficiency).Recommended forshell and tube andmust be fitted forPlate heat exchangers.

Anti-vibration mounts

Elastic supports (Rubber)made of 2 flat and parallelframes, connectedtogether via a rubber ring,fixed under the unit at thepoints specified by ourtechnical drawings.Reduces the transmissionof vibration to the groundand the general sound level. The diameter and strength varyin accordance with the model. Delivered loose not fitted.

KP07 Graphic Display

Anti-vibration mounts

Climatic II (advanced controller)

Water Strainer filter

Electronic Expansion valves

Service Panels

Page 31: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 29

7. SAFETY DURING OPERATION

7.1. Safety and Protection Features

The safety of installation technicians and operatingpersonnel is guaranteed by the following features.

! High pressure switches will switch off thecompressors before the operating pressurehas reached the maximum acceptable value.Depending on the control system used, othermeasures will be taken beforehand (see theoperating manual of the relevant controlsystem).

! Depending on the chosen version piping isprotected by sheet metal parts.

! The main switch, if present (optional), canbe locked in the zero (off) position.

! On versions incorporating an auxiliarysupply, the latter will also be switched off bythe main switch, if present (optional).

! The service panel located in front of the maincurrent part of the control panel can only beremoved when the main switch, if present(optional), is in the zero (off) position.

! All service panels are fixed with bolts, andcan only be removed using specific tools.

! All live parts are touch proof to preventaccidents during maintenance operations(maintenance is often performed with theservice panels removed and the supplyswitched on). It is important that theprotections fitted by Lennox remain in place.If the original protections need to be removedfor maintenance purposes, they should bere-fitted in their original location/manner.Some safe voltage parts (<50V) are nottouch-proof.

! The fans on the exterior of the chiller arefitted with (fine mesh) protective grids. Toprevent inadvertent contact with a rotatingfan on the inside of the chiller duringmaintenance operations, the fans on theinside of the chiller may be also fitted with(coarse mesh) protective grids (onlyapplicable for versions where this part of theunit is accessible).

! Warning labels are located on or near partsthat could produce the following hazards:

SAFETY DURING OPERATION

High temperatures (pressure gas lines)

Electrical voltage (switch compartment).

Rotating parts (service panels providing access tothe condenser compartment).

Sharp parts (fins of the heat exchangers of the air-cooled condensers).

7.2. Safety during decommissioning

If the ECOLOGIC™ chiller is to be taken out of servicefor an extended period, or dismantled, the followingpoints should be observed:

! The machine should be isolated correctly(see chapter 7.6).

! If the chiller is to be taken out of service foran extended period, the refrigerant shouldbe pumped down by authorised personnel.The refrigerant circuits should be brought toslight overpressure using nitrogen gas.During this operation the discharge, suction,liquid and solenoid valves should be open(if present).

! If the chiller is to be dismantled, the oil andrefrigerant need to be drained off anddischarged by suitably qualified personnel.(All in accordance with the regulationsgoverning substances which affect theozone layer).

! NOTE:

ECOLOGIC™ chillers contain refrigerant underpressure. Always ensure that pressurised lines orother parts under pressure are prevented fromdamage or perforation, as this could allowrefrigerant to escape. Escaping refrigerant is ahazard for the eyes and the skin (burning - verylow temperatures) and is damaging to theenvironment. Furthermore, machines withinsufficient refrigerant will not operate correctly.

Page 32: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 30 - IOM ECOLOGIC

! NOTE:

With a roof mounted chiller, the effect of gusts ofwind should be taken into account when removingservice panels. Ensure that the panels cannot beblown away by a gust of wind during lifting. Takecare that the force of the wind on the panel doesnot result in a loss of balance and/or a fall. If thepanels have to be removed during operations,ensure that they are stacked so that they are notexposed to gusts of wind. Due to their size andweight, panels that are blown away could causedamage and/or injury.

8. CONTROL

How your ECOLOGIC™ chiller is controlled dependson the version you have chosen; see chapter 5. All therelevant information concerning operation is containedin the operating manual for the relevant control system.

SAFETY DURING OPERATION

9. MAINTENANCE

9.1. General

Regular and careful maintenance of yourECOLOGIC™ chiller is essential for long term, efficientand fault-free operation. You will be able to carry outsome maintenance operations yourself; refer to chapter9.2. Other maintenance work should be carried out bysuitably qualified and authorised personnel, see chapter9.3. Operations on the refrigerant circuit should onlybe executed by suitably trained and certified personnel.Maintenance can be carried out by the Lennox serviceorganisation, with whom a service contract can bearranged.

If faults and / or non-conformities are found, theseshould be reported to our service organisationimmediately. When doing so, it is essential that youtell us the type of machine and its serial number. If thefault occurred during the warranty period, please alsoquote the Lennox order number assigned to themachine. Consult the electrical diagram if necessaryduring checking operations.

For Netherlands :The frequency of periodic checks carried out byqualified personnel should at least be in accordancewith the applicable RLK.

These checks and operations on the refrigerant orcontrol technology part of the chiller should beregistered in the logbook. The logbook with itsassociated certificates and instruction card shouldalways be stored in/near the chiller. For example inthe control panel of the machine.

The inspection schedules in this manual areintended as a guideline during maintenanceoperations. Lennox does not vouch for thecompleteness of this information and can thereforenot accept liability for any possible omissions.

! NOTE:

The main switch of the machine should bedisabled and locked during operations onelectrical equipment.

Page 33: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 31

! Compressors

The scroll compressors are hermeticallysealed and do not contain parts such asvalves, ball bearings or suction springs. Theytherefore do not require maintenance.

! Electrical equipment and switches

On the whole maintenance is limited to theremoval of dust and dirt at least twice ayear and cleaning of the contacts ifnecessary. The operation of measurementand control equipment shouldalso be checked periodically.

! Condenser

The heat exchanger of the condenser shouldbe checked periodically for visible pollution,and thoroughly cleaned if necessary. Itshould not be cleaned with a wire brush.

In view of the danger of damage to the fins,Lennox recommends that the cleaning becarried out by specialists.

A separate maintenance contract(specifically for the coating) can be agreedfor heat exchangers with protective coatings.

MAINTENANCE

! Evaporator

The water filter have to be checked andcleaned regulary.The evaporator should be checkedperiodically. The evaporator does not requireany maintenance other than themaintenance of its satisfactory condition orrepair of the insulation if necessary. In theevent of water side pollution, the evaporatorshould be chemically cleaned by certifiedpersonnel. Pollution can be detected byobserving a reduction in evaporationtemperature compared to a similar operatingsituation under clean conditions.

! NOTE:

Never use strong inorganic acids to clean theevaporator to prevent corrosion of the materials.

! Filter/drier

Maintenance of the filter/drier is limited to thereplacement of the ceramic cylinders on the110E-,230D-, 300D- and 370D-models orreplacement of the entire filter/drier unit onthe other machines, following moisturesaturation. However, the capacity of the filter/driers is such that replacement only needsto take place when the refrigerant circuit isopened for extensive repairs.A difference intemperature before and after the filter/drierpoints to a blockage caused by pollution. Thereplacement of filter/driers or filter/drierceramics should only be carried out bysuitably qualified and certified personnel.

Page 34: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 32 - IOM ECOLOGIC

9.2. Maintenance schedule for operating personnel

! NOTE:

Operations on the refrigerant circuit should only be executed by suitably trained and certified personnel.

Machine in operation

Compressors! NOTE: The top section of a scroll compressor in operation is hot!

Check the condition of the compressor(noise, temperature, leakage, pollution, corrosion) 4

Check the oil level (should be visible in the compressor sight-glass) 4

Refrigerant circuits

Check (if present) the refrigerant sight-glass (no gas bubbles should bevisible in the sight-glass and look out for discoloration of the moisture indicator) 4Check the condition of the piping (pollution, leakage, corrosion, vibration) 4Check the bracing of the piping (fixing, inlay material) 4Check the condition of the insulation (pollution, moisture, damage) 2

Evaporator

Check the condition of the evaporator (pollution, leakage) 2Check the condition of the insulation (pollution, seams, damage, is it tightened) 2Check the water connections (pollution, leakage, corrosion, sticking of fixings) 2

MAINTENANCE

When a chiller is restarted it will again remain blocked for a short time (see operating manual of therelevant control system and / or the wiring diagram).

Number ofinspections per year

Machine de-commissioned (main switch off and locked) Number of inspections per year

Compressors

Check the oil level of the compressors (between ½ and ¾ of the sight-glass height) 2

Control panel

Check that the switch compartment is clean and dry. 2Check the condition of the cables (corroded, burned, damaged) 2

Condenser

Check the condition of the heat exchanger (pollution, leakage, corrosion, obstructions) 4Check the condition of the fans (pollution, corrosion, axle play) 4Clean the fan blades 2Check the air flow over the assembly (fall wind, blind angle, short circuit, suction waste gas) 2Check that the fixing bolts are tightened 2Check the protective grids (fixing, holes, corrosion) 2

Page 35: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 33

9.3. Maintenance schedule for qualified personnel

MAINTENANCE

Machine in operation Number of inspections per year

Compressors

! NOTE:The top section of a scroll compressor in operation is hot.

Check the condition of the compressor (noise, temperature, leakage, pollution, corrosion) 2Check the operation of the crankcase heater (compressor switched off) 2Check the oil level (should be visible in the compressor sight-glass) 2Check the suction pressure (3 bar < suction pressure < 6 bar) 2Check the discharge pressure (10 bar < discharge pressure < 23 bar) 2Check the current (see specification sheet) 2Check the exhaust fan (on the HE and SLN versions) of the compressor housing 2(in operation as soon as one compressor is in operation)

Refrigerant circuits

Check (if present) the refrigerant sight-glass (no gas bubbles should be visible in thesight-glass and look out for discoloration of the moisture indicator) 2Check the refrigerant circuit for leakage 2Check the condition of the piping (pollution, leakage, corrosion, vibration) 2Check the bracing of the piping (fixing, inlay material) 2Check the condition of the insulation (pollution, moisture, damage) 2Check superheating of the suction gas (3K < superheating < 8 K) 2Check subcooling of the liquid (2K < subcooling < 6K) 2

Evaporator

Check the condition of the evaporator (pollution, leakage) 2Check the condition of the insulation (pollution, seams, damage, is it tightened) 2Check the water connections (pollution, leakage, corrosion, sticking of fixings) 2Check the operation of the evaporator heating (current: see wiring diagram) 2

Condenser

Check the condition of the fans (noise, pollution, temperature, corrosion) 2Check the current of the fans (current: see wiring diagram) 2

Protections

Check the operation and settings of the following protections:-The flow protection (flow switch or differential pressure switch) 2-The high pressure switches 2-The low pressure switches (on BCS) 2-The thermal protections by pushing the reset button (this will onlycheck switching off) 2-The switching off of the compressor by interrupting the Klixon or thethermal protection (remove from terminal strip) 2-Switching off the first fan on every circuit by interrupting the Klixon(remove from terminal strip) 2-The safety functions included in the controls (see operating manual of the relevant control) 2

! NOTE: See the note overleaf.

! NOTE: When the operation of the protections is checked by removing connections from theterminal strip, ensure that these are replaced in their original positions and fittedsecurely.

Page 36: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 34 - IOM ECOLOGIC

Machine de-commissioned Number of inspections per year(main switch off and locked)

Compressors

Check the oil level of the compressors (between ½ and ¾ of the sight-glass height) 2Check that the electrical connections are tightened 2

Control panel(refer to wiring diagram for settings)

Check that the switch compartment is clean and dry. 2Check the condition of the switches (pollution, corrosion) 2Check the condition of the contacts (pollution, corrosion, burning) 2Check that all connections are tightened 2Check the condition of the cable insulation (corroded, burned, damaged) 2Check the settings of the thermal protections 2Check the condition of the fuses (tightened, value) 2

Condenser

Check the condition of the heat exchanger (pollution, leakage, corrosion, obstructions) 2Clean the heat exchanger with a soft brush 2Check the condition of the fans (pollution, corrosion, axle play, imbalance) 2Clean the fan blades 2Check the protective grids (fixing, holes, corrosion) 2Check the air flow over the assembly(fall wind, dead angle, short circuit, suction waste gas) 2Check that the fixing bolts are tightened 2Check that the electrical connections are tightened 2

General

Check the assembly of the chiller (vibration absorbers, foundation, level?) 2Check the condition of the housing (tightened, pollution, corrosion) 4Check the fixing points of the removable parts 2On the HE and SLN versions check the condition of the noise insulationon the compressor housing 2Check that all warning labels are still in place 2

MAINTENANCE

When a chiller is restarted it will again remain blocked for a short time (see operating manual of therelevant control system and / or wiring diagram).

All operations on the refrigerant installation, which are subject to the stipulations in the relevant RLK,should be registered in the logbook associated with the installation (Netherlands only).

It is also advisable to register the relevant operating conditions during checking operations.

! Chilled water inlet and outlet temperature! Discharge and suction pressure! Ambient temperature! The capacity step at which the machine is operating at that point in time.

Some of this data can be gathered using the controls (see operating manual of the relevant control)

Page 37: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 35

MAINTENANCE &MAINTENANCE &MAINTENANCE &MAINTENANCE &MAINTENANCE & FAULT MESSAGES AND FAULTS

9.4. Replacement of warning labels

Missing or damaged warning labels should be replaced.A summary of all warning labels required on and in themachine is included in chapter 3.2.

Proceed as follows when fitting the warning labels:

!!!!! Clean the base using a non-aggressivedegreasant.

!!!!! Heat the area with a blow drier until it isjust warm to the touch.

!!!!! Remove the cover strip and stick thewarning label into the required position.

!!!!! Press down and ensure no air bubblesare left behind.

Leave the glue to dry for at least 24 hours beforebringing the warning label into contact with water and/or cleaning agents.

10.FAULT MESSAGES AND FAULTS

The control system in all versions of the ECOLOGIC™chiller is designed to simplify fault analysis. Theoperating manuals of the relevant controls indicate howto gain access to the required information. It may alsobe helpful to consult the wiring diagram.

Method of operation in the event of a fault:!!!!! Analyse the fault using the control

system (see operating manual of therelevant control system) and thesummary included in chapter 12, ifnecessary.

!!!!! Depending on the nature of the faultand the actions to be taken, the faultcan be remedied in situ or may requirethe assistance of qualified personnel.

! NOTE:

During operations on the machine, the supplyshould be disconnected and the main switchlocked.

Please contact the Lennox service department inthe event of a fault on the ECOLOGIC™ chiller.An indication of the possible cause of the faultwill allow us to solve the problem much moreefficiently.

! NOTE:

Operations on the refrigerant circuit should onlybe executed by suitably trained and certifiedpersonnel.

ECOLOGIC™ chillers contain refrigerant underpressure. Improper operations on the refrigerantcircuit could result in refrigerant escaping. Thisrepresents a hazard to the eyes and to the skin(burning - very low temperatures). Escapingrefrigerant is also hazardous to the environment,and a chiller containing insufficient refrigerant willnot operate correctly.

Page 38: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 36 - IOM ECOLOGIC

REFRIGERANT HANDLING

11.2.Technical points to remember

11.2.1The glide effect

During measurements on the refrigerant circuit withrefrigerants consisting of a pure substance, a fixed ratioexists between the pressure and temperature in theco-existence area (where both moisture and liquid arepresent).

This does not apply, however, to refrigerant mixtureswith the glide feature. In these refrigerants the liquidhas a different temperature (bubble point) than that ofthe gas (dew point) at the same pressure.

This is important when defining subcooling andsuperheating. Subcooling should always be defined bycomparing the liquid temperature with the bubble pointtemperature at the measured pressure.

Superheating should always be defined by comparingthe temperature of the suction gas with the dew pointtemperature at the measured pressure.

11.2.2. Charging the installation with refrigerant

Installations should always be recharged via theconnection on the liquid valve (Vlr).

! NOTE:

Never attempt to start the compressor in anevacuated circuit as this would cause immediate,irreversible damage to the compressor.

! NOTE:

Due to their high volumetric output, scrollcompressors can reach a vacuum very quickly. Thecompressors should therefore not be used to suckin refrigerant, as this will surely lead to irreversibledamage. Even starting a compressor with thesuction valve (Vs) closed will lead to irreversibledamage.The suction pressure of a scrollcompressor must never be lower than 0.2 bar(manometer pressure).

11. REFRIGERANT HANDLING

11.1. General

The two refrigerants employed in ECOLOGIC™ chillers are fundamentally different. The following tablehighlights a number of these differences.

R-407c R-22Composition Mixture of 3 HFKs Pure HCFKODP (R-11 = 1) 0 0.05

GWP (CO2 = 1.0) 1600 1700

AEL [ppm] 1000 1000Boiling point [°C] -41 -44Glide YES NO

Clarification: ODP = Ozone Depletion Potential, based on the reducing output of R-11.GWP = Greenhouse Warming Potential, based on greenhouse effect of CO2.AEL = Allowable Exposure Limit.

! NOTE:ECOLOGIC™ chillers contain refrigerant under pressure. Improper operations on the refrigerant circuitcould result in refrigerant escaping. This represents a hazard to the eyes and to the skin (burning - verylow temperatures). Escaping refrigerant is also hazardous to the environment, and a chiller containinginsufficient refrigerant will not operate correctly.

Page 39: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

IOM ECOLOGIC - Page 37

REFRIGERANT HANDLING & POSSIBLE FAULT CAUSES

11.2.3. Charging of an installation with R-407c

An installation with R-407c should be charged with refrigerant in liquid form, to ensure that the correct compositionis entered.If, for any reason, part of the refrigerant content of an installation has disappeared, the installation should berecharged with refrigerant of the original composition.

! NOTE:

Operations on the refrigerant circuit should only be executed by suitably trained and certifiedpersonnel.

12. POSSIBLE FAULT CAUSES

Possible Fault Causes

Problem or fault Possible cause

Machine does not start No voltageMain switch offMachine blockedRelease conditions not met(of start command, pump switch or flow switch)Chiller in fault modeNo cooling requestMachine outside operational area

High pressure fault Polluted condenser heat exchangerDischarge valve closedThermal protections of one or more condenser fans disengaged(first fan of each circuit is protected by Klixon)Chiller overloaded, chiller operating outside design conditions

Low pressure fault Suction valve closedNot enough refrigerant for expansion valve (gas bubbles insight-glass)Filter/drier polluted (> 1 K temperature difference)Evaporator polluted on water side

Frost Protection Not enough water flow (outside operational area)Capacity control operating incorrectlyHeating tape faultyFaulty temperature sensor in water inlet or outlet

Thermal compressor protection Chiller overloaded, chiller operating outside design conditions

Klixon \ thermistor compressors Motor winding thermally overloaded, unit outside design conditions

The possible fault causes listed in the above table are guidelines to assist in locating the fault. Lennoxdoes not vouch for the completeness of this information and can therefore not accept liability for anypossible omissions.

Page 40: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

Page 38 - IOM ECOLOGIC

ABBREVIATIONS

13. ABBREVIATIONS

The following table includes meanings of the specific abbreviations used in this operating manual. Also refer tothe chapter containing information on the relevant subject. Where possible the same abbreviations are used inthe wiring and cooling technology diagram.

Abbreviation Meanings

C Climatic Control SystemCAC Condenser, Air CooledCF Condenser FanCH Compressor HermeticEc Electric heater, compressorC II Climatic II Control SystemEev Electric heater, evaporatorEVAP EvaporatorEVe Expansion Valve, electronicEVt Expansion Valve, thermostaticFD Filter DrierPSh Pressure Switch, high pressurePSl Pressure Switch, low pressurePTh Pressure Transmitter, high pressurePTl Pressure Transmitter, low pressurePV Purge ValveSCd Service Connection, dischargeSCl Service Connection, liquidSCs Service Connection, suctionSGlr Sight Glass, liquid refrigerantSV Solenoid ValveSVlr Solenoid Valve, liquid refrigerantTE Temperature (sensing) ElementTSla Temperature Switch, low ambient temperatureVd Valve, dischargeVlr Valve, liquid refrigerantVs Valve, suction

Page 41: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions
Page 42: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions
Page 43: INSTALLATION - OPERATING & MAINTENANCE MANUAL · This manual contains important instructions regarding the commissioning of the ECOLOGIC™ chiller. It also includes important instructions

www.Lennoxeurope.com

LENNOX BENELUX N.V./S.A.tél. : + 32 3 633 30 45fax : + 32 3 633 00 89e-mail : [email protected]

LENNOX JANKAtél. : + 420 2 510 88 111fax : + 420 2 579 10 393e-mail : [email protected]

LENNOX FRANCEtél. : + 33 4 72 23 20 20fax : + 33 4 78 20 07 76e-mail : [email protected]

LENNOX DEUTSCHLAND GmbHtél. : + 49 69 42 09 79 0fax : + 49 69 42 09 79 40e-mail : [email protected]

LENNOX DISTRIBUTIONtél. : + 971 4 262 9309fax : + 971 4 266 7082e-fax : + 1 240 368 73 62Mobile : 971 50 4510669e-mail : [email protected]

LENNOX BENELUX B.V.tél. : + 31 33 2471 800fax : + 31 33 2459 220e-mail : [email protected]

LENNOX POLSKA Sp. z o. o.tél. : + 48 22 832 26 61fax : + 48 22 832 26 62e-mail : [email protected]

LENNOX CLIMATIZAÇAO LDA.tél. : +351 22 999 84 60fax : +351 22 999 84 68e-mail : [email protected]

LENNOX DISTRIBUTION MOSCOWtél. : + 7 095 246 07 46fax : + 7 502 933 29 55e-mail : [email protected]

LENNOX SLOVAKIAtél. : + 421 2 44 87 19 27fax : + 421 2 44 88 64 72

LENNOX REFAC S.A.tél. : + 34 915 40 18 10fax : + 34 915 42 84 04e-mail : [email protected]

LENNOX DISTRIBUTION KIEVtél. : + 380 44 213 14 21fax : + 380 44 213 14 21e-mail : [email protected]

LENNOX INDUSTRIES LTDtél. : + 44 1604 599400fax : + 44 1604 594200e-mail : [email protected]

tél. : + 33 4 72 23 20 14fax : + 33 4 72 23 20 28e-mail : [email protected]

BELGIUM :BELGIUM :BELGIUM :BELGIUM :BELGIUM :

CZECH REPUBLIC :CZECH REPUBLIC :CZECH REPUBLIC :CZECH REPUBLIC :CZECH REPUBLIC :

FRANCE :FRANCE :FRANCE :FRANCE :FRANCE :

GERMANY :GERMANY :GERMANY :GERMANY :GERMANY :

MIDDLE EAST :MIDDLE EAST :MIDDLE EAST :MIDDLE EAST :MIDDLE EAST :

NETHERLANDS :NETHERLANDS :NETHERLANDS :NETHERLANDS :NETHERLANDS :

POLAND :POLAND :POLAND :POLAND :POLAND :

PORTUGAL :PORTUGAL :PORTUGAL :PORTUGAL :PORTUGAL :

RUSSIA :RUSSIA :RUSSIA :RUSSIA :RUSSIA :

SLOVAKIA :SLOVAKIA :SLOVAKIA :SLOVAKIA :SLOVAKIA :

SPAIN :SPAIN :SPAIN :SPAIN :SPAIN :

UKRAINE :UKRAINE :UKRAINE :UKRAINE :UKRAINE :

UNITED KINGDOM :UNITED KINGDOM :UNITED KINGDOM :UNITED KINGDOM :UNITED KINGDOM :

OTHER EUROPEANOTHER EUROPEANOTHER EUROPEANOTHER EUROPEANOTHER EUROPEANCOUNTRIES, AFRICA,COUNTRIES, AFRICA,COUNTRIES, AFRICA,COUNTRIES, AFRICA,COUNTRIES, AFRICA,

LENNOX DISTRIBUTION :LENNOX DISTRIBUTION :LENNOX DISTRIBUTION :LENNOX DISTRIBUTION :LENNOX DISTRIBUTION :

ECOLOGICIOM-EC-0802-E