INSTALLATION MANUAL

ULTRAFLEXPOWER SUPPLY

UF1500 Series

3055 Del Sol Blvd.San Diego, CA 92154

Phone: (619) 575-4400Fax: (619) 429-1011

P/N: IMUE1500 Rev. CDATE: February 2002

Page 2: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 2 of 17

TABLE OF CONTENTSINTRODUCTION 4

CERTIFICATION 4

WARRANTY 4

APPLICABILITY 4

INSTALLATION MANUAL 4

SAFETY AGENCY APPROVALS 4

GENERAL SAFETY INSTRUCTIONS 5

INPUT FUSE 6

RECEIPT AND UNPACKING 6

MOUNTING REQUIREMENTS AND COOLING 7

INPUT POWER CONNECTIONS 7

AC INPUT AND OUTPUT POWER RATINGS 7

EMI 8

INPUT TRANSIENT/ESD PROTECTION 8

REMOTE SENSE 8

OUTPUT VOLTAGE ADJUSTMENT (TRIMMING) 9

CURRENT LIMIT PROTECTION 9

OVERVOLTAGE PROTECTION (OVP) 9

OUTPUT LOAD REGULATION 9

OUTPUT LINE REGULATION 9

HOLD UP TIME AFTER POWER LOSS 9

Page 3: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 3 of 17

TURN-OFF/TURN-ON 9

TURN ON TIME 9

NOISE AND RIPPLE 9

DYNAMIC LOAD TRANSIENT RESPONSE 10

DYNAMIC CROSS REGULATION 10

TEMPERATURE COEFFICIENT 10

NO LOAD OPERATION 10

OVER TEMPERATURE SHUTDOWN 10

OPERATING ENVIRONMENT 10

SIZE AND WEIGHT 10

COOLING 11

SHOCK & VIBRATION 11

PACKAGE DROP 11

RELIABILITY PREDICTION 11

MATING SIGNAL & CONTROL CONNECTOR INFORMATION 11

GLOBAL SIGNALS 11

OUTPUT MODULE SIGNALS & FEATURES 12

MODULE RATING WITH MODEL NUMBERS: UE Z 1 - X X X X X X 14

NOTE: ENERGY HAZARDS 15

THERMAL DERATING GUIDELINE 15

MAXIMUM POWER VS. AC LINE 15

LABEL / CONNECTION DIAGRAM 17

Page 4: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 4 of 17

LAMBDAPower Supply

Installation Manual

INTRODUCTION

The “UltraFlex” is a product family of fan-cooled, multi-output, power factor corrected switchmode power supplies. The flexible design offers a high quality, cost-effective solution for thehigh volume OEM market.

CERTIFICATIONLambda certifies that this product meets published specifications at the time of shipment fromthe factory.

WARRANTYThis power supply is warranted against defects in material and workmanship for a period ofthree years from date of shipment. During this period Lambda will either repair or replace thisproduct at the discretion of Lambda . No other warranty is implied or given.

APPLICABILITYThis manual applies to the UltraFlex UF1500 Series power supply. Manual part no.IMUE1500.

PART NUMBER CONFIGURATION

U E Z 1- _ _ _ _ _ _ _

UltraFlex Case Code

Global Signals Output Module Codes [SEE PAGE 14] EN55022 Level B, FCC20780 Class A Cond. EMI

INSTALLATION MANUALThis manual contains important information regarding the proper installation and operation ofthe power supply mounted inside the host equipment.

SAFETY AGENCY APPROVALSThe UltraFlex power supply series complies with the following regulatory specifications:UL1950, IEC950, CSA 22.2 No.950, EN60950. This product is certified and allowed to carryUL combined Canada/U.S. Recognized Component Mark, DEMKO.CE Marked in accordance with the Low Voltage directive (73,23/EEC) as amended by the CEMarking directive (93/68/EEC).NOTE: CE Mark does not include compliance to either EMC or medical device directives.

PLEASE READ THE SAFETY AND INSTALLATION INSTRUCTIONS BEFOREINSTALLATION OR USE OF THIS PRODUCT.

Page 5: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 5 of 17

SAFETY SYMBOL:This symbol indicates dangerous voltages present within the power supply. Isolationtransformers should be used between the AC mains and the power supply if work is to becarried out with the safety covers removed.

GENERAL SAFETY INSTRUCTIONSThe UltraFlex power supply series is designed for use within other equipment or enclosures. Access is restricted to authorized personnel only.

For safe installation and operation of this product, carefully follow the instructions below:

A. Do not install, operate or test this product near water, and do not spill any liquid on it.

B. Do not touch the product when the input supply is connected.

C. Do not operate this product unless it is in a secure position.

D. When cleaning the product, make sure the input supply is disconnected and use only adamp cloth.

E. Never push objects of any kind into the product through slots in its case, as this couldresult in electric shock or a fire hazard.

F. Slots in the product case are designed for ventilation and must not be obstructed whenthe product is installed and/or operated.

G. Make sure the unit is supplied only by a power source of the type indicated on its label.

H. When securing the product, do not use screws that infringe the maximum penetrationdepth specified on the mechanical drawing within this handbook.

I. The unit covers are designed only to protect skilled personnel from hazards. They mustnot be used as part of the external covers of any equipment where they may beaccessible to operators, since, under full load conditions, parts of the unit chassis mayreach temperatures in excess of those considered safe for operator access.

J. All servicing, repair and testing of this product must be carried out by competentpersonnel who are familiar with the hazards of AC/DC line operated equipment and withthe particular dangers associated with switched mode power supplies.

K. AFTER DISCONNECTING THE AC SOURCE, ALLOW 5 MINUTES BEFORETOUCHING THE UNIT TO ALLOW CAPACITORS WITHIN THE UNIT TODISCHARGE.

L. The low-voltage output from the power supply unit shall not be user-accessible asdefined in EN 60950.

Page 6: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 6 of 17

M. A protective earth must be provided for safety in accordance with EN60950.

WARNING: It is essential that the earth grounding terminal of this product be securelyconnected to earth (hard-wired) by the end user.

N. PREVENTION OF ACCESS BY THE USER: This apparatus is intended to beaccessible to authorized personnel only. Ensure that user access to this product, wheninstalled in a host equipment, complies with EN60950. Failure to do this will invalidatethe approval given to this apparatus.

O. WARNING: All outputs used are SELV as defined in EN60950 Clause 2.3. As such, alloutputs must only be connected to circuits compliant with the requirements of SELVcomplying EN60950 Clause 2.3. circuits. Other usage will invalidate any approval givento this apparatus.

P. EARTH TERMINAL MARKING:IMPORTANT: If in the end use equipment the incoming mains cable earth wireconnects directly to the "GND" connection on the UltraFlex unit without beinginterrupted or junctioned on its way to that connection, then this connection is the mainprotective earth of the system. To comply with EN60950, UL1950, and CSA-22.2-950

requirements, this terminal must be marked with as defined in IEC417 No. 5019a.The customer should therefore affix an adhesive label which will pass the 15 secondrub test (IEC950 section 1.7.15) showing the above symbol adjacent to the earthconnection. This symbol must only be used at the first interruption/connection of theincoming earth wire.

INPUT FUSEThe AC power source line is protected by an internal ceramic body fuse contained within thepower supply enclosure located in the neutral side. Only qualified service personnel shouldreplace the internal fuse (no user access).

Notes:1. Replace the input fuse in the unit with same type and rating. Fusing requirements are

shown in Table #1. Caution: Primary fuse is located in the neutral side. 2. Additional customer supplied fuse is required in the “Line side”, same as in Table #1. 3. Internal fuses (no user access) F506, F601, rated 4A/250v Very Fast-Acting Type.

TABLE #1MODEL OUTPUT

POWERFUSE VALUE NOTES

UF1500 1500W 25A/600V Bussmann fastacting KTK-25or equivalent

RECEIPT AND UNPACKINGOn receipt, the unit should be unpacked carefully and checked for transit damage. If the unit isdamaged, do not apply power or install the unit--seek specialist advice. Read the rating labellocated on the power supply to verify that the unit has the correct input and output ratings and

Page 7: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 7 of 17

part number. All electrical tests performed on the unit prior to installation must be carried outby a qualified person familiar with AC/DC powered equipment and having the specializedknowledge required of the hazards associated with switched mode power supplies. This isparticularly essential if the unit covers are removed, which exposes many devices operating atline voltage and some operating at peak voltages of up to 400 volts.

MOUNTING REQUIREMENTS AND COOLINGThe mechanical outline drawing, contained within this pamphlet, provides the necessaryinstallation dimensions required for customer mounting and space allocation.

IMPORTANT: Use M4 screws for mounting. Screws must not penetrate more than 1/8”(3MM) into the power supply. The UF1500 units have integral cooling fans and can be mountedin any position. However mounting orientation should not oppose the system forced airdirection, the natural convection, or system cooling draft air flow. Furthermore, the powersupply air intakes and exhaust slots must not be obstructed. The intake air temperature shouldbe limited to allow the unit to operate in accordance with the thermal derating envelope of theelectrical specifications.

INPUT POWER CONNECTIONSThe input power terminal block is located on the chassis end that also includes the fans. Safety earth ground is to be connected to the grounding post adjacent to the input powerterminal block.

The terminal functions are clearly shown on the top label of the unit.

Connections should be made using correctly sized wire gauges and colors as per applicableelectrical codes.

AC INPUTLine: BlackNeutral: WhiteGround: Green

The ground connection must be made to a well defined, low impedance ground (protectiveground). Connections must not have loose strands and the insulation must cover the wire upto the block itself. Interface terminal lugs must be fastened properly.

AC INPUT AND OUTPUT POWER RATINGS

85-265 Vac, 47-63 Hz. The input current will be limited to 20A max.

Output Power 1000W @ 85 Vac @ Ambient Temp. 0 to 50oC;1200W @100 Vac 60 oC derate output power to 75%1500W @170 Vac 70 oC derate output power to 50%

Note: Refer to Table 3 and Graphs 1 & 2 on pages 13 and 14 respectively.

Page 8: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 8 of 17

EMI(Conducted)

The UltraFlex power supply has internal EMI filtering, and complies with EN55022 level B, aswell as FCC Docket 20780 Part 15, Subpart J Class A. The end system wiring and groundingcan influence the conducted and radiated EMI pattern. The customer may require additionalEMI filtering to meet system requirements. If problems are encountered, the customer shouldcontact Lambda’s Application Engineering Staff.

INPUT TRANSIENT/ESD PROTECTIONThe UltraFlex is designed to withstand surges, line transients, and ESD as specified in thefollowing documents:

Surge: IEEE-C62.41, Category A3;EN61000-4-5 Class 4; L-L: 2KV, L-Gnd: 4KV, Criterion B.

Fast Transients: EN61000-4-4, Level 3, Criterion B.ESD: EN61000-4-2, Level 3, Criterion B.Input Dips and Variations: IEC1000-4-11, Criterion B.Radiated Immunity: EN61000-4-3, Level 3, 10 V/M.

REMOTE SENSERemote sense is provided for each output to compensate for load cable drops from the powersupply to the sense points. To meet specifications and output voltage set point of the outputmodules, the sense lines must be connected to the load or locally to the power supply outputterminals. The remote sense connections are available on the signal connector. See Table 2below for the appropriate pin numbers.

Table 2Single Output Modules Dual Output Modules

J1 pin 1 + Positive Remote Sense J2 pin 2 - Negative Remote Sense Output 1J1 pin 10 – Negative Remote Sense J2 pin 3 +Positive Remote Sense Output 1

J2 pin 4 +Positive Remote Sense Output 2J2 pin 5 - Negative Remote Sense Output 2

The following rules should be observed when using remote sense:

1) Use a twisted pair of 20-24 AWG wires for remote sense leads.2) Route the sense leads away from any high current conductors or devices

(motors, transformers, etc.) to avoid pick-up, as this may cause ripple or stabilityproblems on the power supply.

3) Never disconnect the power supply output power connections with the remotesense still connected to the load. This may damage the internal remote sensepick-up resistors.

4) The total voltage drop on the output cables must be limited to less that 0.5V.

Page 9: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 9 of 17

OUTPUT VOLTAGE ADJUSTMENT (TRIMMING)Voltage adjust potentiometers are provided for all outputs. The potentiometers are locatedadjacent to the output connections of the power supply. Use a non-conductive trim-potadjustment tool. Turn clockwise to increase the voltage. NOTE: Always monitor the corresponding output voltage while turning the potentiometer.

CURRENT LIMIT PROTECTIONAll outputs are protected by constant-current limiting circuitry. The overcurrent limits are set atthe factory between 110-150% for single outputs. The overcurrent limit settings for the dualoutput modules are as follows: Output #1: 110- 150% of rated load; Output #2: 110-150% ofrated load. Removing the overload automatically restores the output voltage. On Dual OutputModules - if Output #1 is in current limit, Output #2 voltage will also decrease.

OVERVOLTAGE PROTECTION (OVP)When any single output module voltage reaches 120-130% of nominal voltage, that channelwill shut down. When any dual output module reaches 120-140% of nominal voltage, bothoutputs of the dual module will shut down. OVP on 2V outputs is factory set to 3-3.5V, andOVP on 3.3V outputs is set to 4.3-4.8V. OVP activates the internal shutdown latch of themodule until the AC input power is recycled OFF to ON to clear the latch and resume normaloperation, once the OVP problem has been corrected.

OUTPUT LOAD REGULATION(NO LOAD/FULL LOAD/NO LOAD) Single output modules 0.4% maximum.

Dual output modules 0.8% maximum.

OUTPUT LINE REGULATION(85-265VAC 47-63 Hertz) Single output modules 0.1% maximum.

Dual output modules 0.2% maximum.

HOLD UP TIME AFTER POWER LOSS(AC INPUT)The UltraFlex output voltages will remain within specified regulation for a minimum of 16msecafter loss of applied power on the AC input at full load and nominal output voltage.

TURN-OFF/TURN-ONTurn-off/turn-on output voltage - transient overshoot is less than 3% of nominal voltage duringthe application or removal of input voltage under any condition of turn-on, turn-off, includinginhibit or enable.

TURN ON TIMEAll outputs shall be within voltage regulation limits within 1 second of application of AC power.

NOISE AND RIPPLEUltraFlex output modules meet the following specifications with a 20MHz bandwidth. Caremust be taken when conducting the following measurements: Single output modules: 2-5V, <1000W: <50mV pk –pk.

</= 5V, 1000W: <200mV pk-pk directly on the output terminals; <50mV pk-pk measured 5 inches away from the output

terminals with two – 2700 uf capacitors located at this point. > 5V: <1% pk–pk.

Page 10: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 10 of 17

Dual output modules: <1% pk-pk.

DYNAMIC LOAD TRANSIENT RESPONSEA 25% step load change will result in an output deviation (overshoot or undershoot) of lessthan 3% of nominal output voltage (150mV for <5V outputs, 400mV for the </= 5V 1000Wmodule). Output voltage will recover to within 1% of set value within 300�s (500us for the</=5V 1000W module.) Slew rate not to exceed 1A/us.

DYNAMIC CROSS REGULATIONThe effect of dynamic cross regulation on any fully loaded auxiliary channel for a load stepchange of 25% from a 75% base value on the highest rated channel, at a slew rate not toexceed 1A/us, shall be less than 0.1% for single output modules and less than 3% for dualoutput modules. The summation of the individual module powers must not exceed the totalrated power of the UF1500. This measurement is to be performed with all other channelsloaded to 50% of rated load.

TEMPERATURE COEFFICIENTThe output voltage will change less than .02% per oC over the ambient temperature range of0-50oC. (After 30 minute warm-up).

NO LOAD OPERATIONOperation at no load will not cause damage to the UltraFlex supply, however the outputvoltages may be outside the regulation band. A 1 Ampere preload is required on the highestrated output for a dual output module.

OVER TEMPERATURE SHUTDOWNThe power supply is self-protected against over-temperature conditions. A thermal shutdownrequires re-cycling of the input voltage to restore output. The fan will continue to operateduring thermal shutdown.

OPERATING ENVIRONMENTThe power supply is designed to meet the performance parameters defined above whenoperated within the following conditions:

Temperature: 0 to 50o C; -20oC Start-Up, 30 Minutes to performwithin specifications.

Humidity: 10% - 90% Non-condensing Altitude: 0 – 10,000 ft. Operating

The power supply will not be damaged during transit and storage when subjected to thefollowing conditions:

Temperature: -40oC to +85oC Humidity: 90% Non-condensing Altitude: 40,000 ft. (12Km)

SIZE AND WEIGHTH" x W" x L": 5”x5.125”x11”WEIGHT: 5.7lbs. + 0.5lbs. / used slot; maximum # of slots = 10.

Page 11: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 11 of 17

COOLINGIntegral fans provide forced-air cooling to ensure safe operation under all environmentalconditions. Care must be taken not to obstruct intake and exhaust ports.

SHOCK & VIBRATIONThe UltraFlex power supply meets the performance requirements of IEC68-2-27; 15g, 11mshalf-sine pulses.

The UltraFlex power supply meets the performance requirements of IEC68-2-64 with afrequency range of 20 - 2000Hz and acceleration of 6 Grms for a minimum of 30 minutes.

PACKAGE DROPThe UltraFlex packaging has been tested per National Safe Transit Association Project 1A.

RELIABILITY PREDICTIONReliability prediction MTBF by stress method per Bellcore TR-NWT-000332 Issue 4 (reliabilityprediction procedure for electronic equipment).

Typical Quad output supply =/> 72000 hours MTBF (e.g. 5V/12V/12V/5V).

MATING SIGNAL & CONTROL CONNECTOR INFORMATION

Lambda Kit Part #(J3) Input Connector Kit 951482(J1) Output Connector Kit 951482(J2) Dual Output Connector Kit 951492

TO ORDER CONNECTORS DIRECT FROM AMP:Single Output & Input Connector: AMP P/N 87977-3 (holds 10 Pins)Dual Output Connector: AMP P/N 87977-1 (holds 6 Pins)Pin For Above Connectors: AMP P/N 1-87309-3

GLOBAL SIGNALSThe following signals are provided as a standard feature on the UF1500 via J3. Logic levelsignal outputs are via open drain Mosfets (60VDC/100mA max ratings). Pull up resistors arerequired. Signals are referenced to the Signal Common terminal (J3 Pin 3) on the interfaceconnector.

5V DC Standby Output (J3 pin 1):Isolated 5VDC/0.3A output available whenever the input power is applied. This output is notaffected by inhibit signals. Load regulation less than or equal to 5%.

Global Output Good LED Drive (J3 pin 2):An open drain output to light an external LED indicator. If any output equipped with a DCoutput good option fails, this signal goes low. An internal 390 ohm series resistor limits thecurrent through the LED.

Global Output Good (J3 pin 4):When all output modules which have Output Good signals are within specification, this signalis high. If any output fails, this signal goes low.

Page 12: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 12 of 17

Fan Stop/Thermal Alarm (J3 pin 5):Logic signal goes low if the fan stops; or in the event of overheating, at least 10mS prior to athermal shutdown of the supply. Signal remains low until fault is cleared. If a thermal shutdownhas occurred, the input power must be re-cycled to restore output.

Input Power Fail Signal (J3 pin 6):Following the loss of input power, this signal provides at least 5mS warning prior to any outputgoing outside of it's regulation band when adjusted to Vo nominal at full load. The signal goes"Low" when input power is lost. Signal "High" on fault available as a special option.

Global Inhibit (J3 pin 8):A TTL compatible signal will turn off all output modules, depending upon the setting of theInhibit/Select function (See below.) The outputs are less than 0.5V while inhibited at no load.

Inhibit/Select (J3 pin 10):When open circuit, Global Inhibit is Active Low. When this input is shorted to signal common(Pin 3), Global Inhibit is active high.

OUTPUT MODULE SIGNALS & FEATURESOutput module options are available only with single output modules. Logic Level signaloutputs are via open collector NPN transistors (40VDC/10mA max ratings) except the ModuleInverter OK signal which is 20VDC/4mA. Pull up resistors are required. Signals are referenced to the -Remote Sense terminal. (J1 pin 10)

+Remote Sense (J1 pin 1- single output module, J2 pin 3 & 4 – dual output module):Compensates for load cable drop from power supply to sense point (.25V per terminal.) Tomeet regulation the remote sense must be connected to the load or locally to the powersupply.

Remote Voltage Adjust (J1 pin 2):This input signal may be used for remote adjustment of the output +/- 10% of nominal viaexternal resistive or current input. Requires external potentiometer (10K ohms) between +/-remote sense terminals with the wiper to remote voltage adjust pin.

Margin (J1 pin 3):Margining +/- 5% of nominal output voltage. Requires an external switch (normally open,SPDT) connected to the +/- remote sense terminals with switch common connected to Margininput.

Current Sharing (J1 pin 4):Active current sharing provides Load Sharing between two or more similar output modules towithin 10% of each output’s rated current. The current share node automatically disconnects ifa module inverter fault is detected. Modules with this option share current proportionally totheir maximum current ratings. Current sharing between modules is accomplished byconnecting J1 pin 4 of each module together. A single remote sense point must be used. Theindividual output voltages must be set to within 1% of each other to ensure the outputs arewithin a 2% capture window. Refer to Lambda application note AN-018 for additional details.

High Module Signal (J1 pin 5):When outputs are connected in parallel and the current share option is employed, only themodule with the highest output voltage will have a logic high signal (useful for systemdiagnostics). This is an open collector output signal.

Page 13: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 13 of 17

Inhibit Module (J1 pin 6 - single output module, J2 pin 1 - dual output module):A TTL "low" level signal can be applied to disable outputs to <0.5V at no load.

Output Good Signal (J1 pin 7):This signal goes low if output deviates by - 4% from factory settings.

Module Inverter O.K. Signal (J1 pin 8):If an output module inverter fault is detected this output goes high. This signal causes thecurrent-share node to disconnect. Maximum ratings for the output transistor are 20V/4mA.

Current Monitor (J1 pin 9):This is an analog signal proportional to the output current, 0-2VDC (2VDC at max outputcurrent). From 20%-100% of current rating the accuracy will be within 10% of the max ratedcurrent value.

-Remote Sense (J1 pin 10 –single output module, J2 pin 2 & 5 – dual output module):Compensates for load cable drop from power supply to sense point (.25V per terminal.) Tomeet module specifications the remote sense must be connected to the load or locally to thepower supply.

Page 14: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 14 of 17

MODULE RATING WITH MODEL NUMBERS: UE Z 1 - X X X X X X Module Code

TABLE 3ModuleCode

OutputVoltage DC (range)

CurrentMax

Output Power@ 50�C Max

SlotWidth

A 2 V(1.8-2.2) 30A 66W 1B 2 V(1.8-2.2) 60A 132W 2C 2 V(1.8-2.2) 100A 200W 3D 3.3 V(3.0-3.6) 30A 108W 1E 3.3 V(3.0-3.6) 60A 216W 2F 3.3 V(3.0-3.6) 100A 330W 3G 5 V(4.5-6.0) 30A 150W 1H 5 V(4.5-6.0) 60A 300W 2I 5 V(4.5-6.0) 100A 500W 3J 12 V(10.8-13.2) 17A 204W 1K 12 V(10.8-13.2) 30A 360W 2L 12 V(10.8-13.2) 50A 600W 3M 15 V(13.5-16.5) 14A 210W 1N 15 V(13.5-16.5) 24A 396W 2P 24 V(21.6-26.4) 8.5A 204W 1Q 24 V(21.6-26.4) 15A 396W 2R 24 V(21.6-26.4) 25A 600W 3S 48 V(43.2-52.8) 4A 211W 1T 48 V(43.2-52.8) 8A 384W 2U 48 V(43.2-52.8) 12.5 600W 3V 12/5 V(10.8-13.2/

4.5-6.0)10/4A 120/20W 1

W 5/12 V(4.5-6.0/10.8-13.2)

10/4A 50/48W 1

Y 12/12 V(10.8-13.2/(10.8-13.2)

10/4A 120/48W 1

Z 15/15 V(13.5-16.5/(13.5-16.5)

8/3A 120/45W 1

3 36 V(32.4-39.6) 11A 396W 25Q 20V(16.5-22.0) 15A 300W 27B 2.0V(1.6-2.5) 15A 38W 17E 3.3V(3.0-3.6) 15A 54W 17H 5.0V(4.5-6.0) 15A 90W 17K 12.0V(10.8-13.2) 7A 92W 17N 15.0V(13.5-16.5) 6A 99W 17Q 24.0V(21.6-26.4) 4A 105W 17T 48.0V(43.2-52.8) 2A 105W 18 28 V(25.2-30.8) 12A 369W 2

9E 3.3V(3.0-3.6) 200A 660W 59H 5V (4.5-6.0) 200A 1000W 59Q 24V(21.6-26.4) 41.7A 1000W 59T 48V (43.2-52.8) 20.8A 1000W 5

Page 15: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 15 of 17

NOTE: ENERGY HAZARDS

Modules Overcurrent Protection are set between 110 – 120% of max current.Certain modules are capable of providing hazardous energy (240VA) according tooutput voltage setting. Therefore, consideration should be given to electrical energyhazards from these outputs

THERMAL DERATING GUIDELINEfor UltraFlex UF1500 Power Supply Series

Derating UF1500 Series

0

20

40

60

80

100

120

-60 -40 -20 0 20 40 60 80

Temperature [C]

% O

utpu

t Po

wer

MAXIMUM POWER VS. AC LINEfor UltraFlex UF1500 Power Supply

Continuous Output Power Derating

1400

1500

(wat

ts)

Page 16: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 16 of 17

OUTLINE DRAWING

Page 17: INSTALLATION MANUAL ULTRAFLEX POWER … MANUAL ULTRAFLEX POWER SUPPLY UF1500 Series 3055 Del Sol Blvd. San Diego, CA 92154 Phone: (619) 575-4400 …

REV C Page 17 of 17

LABEL / CONNECTION DIAGRAM