EnglishInstallation manualR410A Split series
Français
EspañolManual de instalaciónSerie Split R410A
INSTALLATION MANUALR410A Split Series
ModelsRXS09LVJURXS12LVJU
00_CV_3P300674-1.indd 1 10/18/2011 10:38:27 AM
1■English
Safety Precautions•ReadtheseSafetyPrecautionscarefullytoensurecorrectinstallation.•ThismanualclassifiestheprecautionsintoDANGER,WARNINGandCAUTION.Besuretofollowalltheprecautionsbelow:theyareallimportantforensuringsafety.
DANGER ...... Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING .... Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.
CAUTION ..... Failure to follow any of CAUTION may in some cases result in grave consequences.
•Thefollowingsafetysymbolsareusedthroughoutthismanual:
Besuretoobservethisinstruction. Besuretoestablishagroundconnection. Neverattempt.
•Aftercompletinginstallation,testtheunittocheckforinstallationerrors.GivetheuseradequateinstructionsconcerningtheuseandcleaningoftheunitaccordingtotheOperationManual.
DANGER•Refrigerantgasisheavierthanairandreplacesoxygen.Amassiveleakcouldleadtooxygendepletion,especiallyinbasements,andanasphyxiationhazardcouldoccurleadingtoseriousinjuryordeath.
•Iftherefrigerantgasleaksduringinstallation,ventilatetheareaimmediately.Refrigerantgasmayproduceatoxicgasifitcomesincontactwithfiresuchasfromafanheater,stoveorcookingdevice.Exposuretothisgascouldcausesevereinjuryordeath.
•Aftercompletingtheinstallationwork,checkthattherefrigerantgasdoesnotleak.Refrigerantgasmayproduceatoxicgasifitcomesincontactwithfiresuchasfromafanheater,stoveorcookingdevice.Exposuretothisgascouldcausesevereinjuryordeath.
•Donotgroundunitstowaterpipes,telephonewiresorlightningrodsbecauseincompletegroundingcouldcauseasevereshockhazardresultinginsevereinjuryordeath,andtogaspipesbecauseagasleakcouldresultinanexplosionwhichcouldleadtosevereinjuryordeath.
•Safelydisposeofthepackingmaterials.Packingmaterials,suchasnailsandothermetalorwoodenparts,maycausestabsorotherinjuries.Tearapartandthrowawayplasticpackagingbagssothatchildrenwillnotplaywiththem.Childrenplayingwithplasticbagsfacethedangerofdeathbysuffocation.
•Donotinstallunitinanareawhereflammablematerialsarepresentduetoriskofexplosionresultinginseriousinjuryordeath.
•Donotgroundunitstotelephonewiresorlightningrodsbecauselightningstrikescouldcauseasevereshockhazardresultinginsevereinjuryordeath,andtogaspipesbecauseagasleakcouldresultinanexplosionwhichcouldleadtosevereinjuryordeath.
WARNING•Installationshallbelefttotheauthorizeddealeroranothertrainedprofessional.Improperinstallationmaycausewaterleakage,electricalshock,fire,orequipmentdamage.
•Installtheairconditioneraccordingtotheinstructionsgiveninthismanual.Incompleteinstallationmaycausewaterleakage,electricalshock,fireorequipmentdamage.
•Besuretousethesuppliedorexactspecifiedinstallationparts.Useofotherpartsmaycausetheunittocometofall,waterleakage,electricalshock,fireorequipmentdamage.
•Installtheairconditioneronasolidbasethatislevelandcansupporttheweightoftheunit.Aninadequatebaseorincompleteinstallationmaycauseinjuryorequipmentdamageintheeventtheunitfallsoffthebaseorcomesloose.
•Electricalworkshallbecarriedoutinaccordancewiththeinstallationmanualandthenational,stateandlocalelectricalwiringcodes.Insufficientcapacityorincompleteelectricalworkmaycauseelectricalshock,fireorequipmentdamage.
•Besuretouseadedicatedpowercircuit.Neveruseapowersupplysharedbyanotherappliance.Followallappropriateelectricalcodes.
•Forwiring,useawireorcablelongenoughtocovertheentiredistancewithnosplicesifpossible.Donotuseanextensioncord.Donotputotherloadsonthepowersupply.Useanonlyaseparatededicatedpowercircuit.(Failuretodosomaycauseabnormalheat,electricshock,fireorequipmentdamage.)
•Usethespecifiedtypesofwiresforelectricalconnectionsbetweentheindoorandoutdoorunits.Followallstateandlocalelectricalcodes.Firmlyclamptheinter-unitwiresotheirterminalsreceivenoexternalstresses.Incompleteconnectionsorclampingmaycauseterminaloverheating,fireorequipmentdamage.
01_EN_3P300674-1.indd 1 10/6/2011 1:37:41 PM
2 ■English
Safety Precautions WARNING
•Afterconnectingallwiresbesuretoshapethecablessothattheydonotputunduestressontheelectricalcovers,panelsorterminals.Installcoversoverthewires.Incompletecoverinstallationmaycauseterminaloverheating,electricalshock,fireorequipmentdamage.
•Wheninstallingorrelocatingthesystem,besuretokeeptherefrigerantcircuitfreefromallsubstancesotherthanthespecifiedrefrigerant(R410A),suchasair.(Anypresenceofairorotherforeignsubstanceintherefrigerantcircuitcausesanabnormalpressurerisewhichmayresultinrupture,resultingininjury.)
•Duringpump-down,stopthecompressorbeforeremovingtherefrigerantpiping.Ifthecompressorisstillrunningandthestopvalveisopenduringpump-down,airwillbesuckedinwhentherefrigerantpipingisremoved,causingabnormallyhighpressurewhichcouldleadtoequipmentdamageorandpersonalinjury.
•Duringinstallation,attachtherefrigerantpipingsecurelybeforerunningthecompressor.Iftherefrigerantpipesarenotattachedandthestopvalveisopenduringpump-down,airwillbesuckedinwhenthecompressorisrun,causingabnormallyhighpressurewhichcouldleadtoequipmentdamageandpersonalinjury.
•Besuretoinstallagroundfaultcircuitinterrupterbreaker.Failuretoinstallagroundfaultcircuitinterrupterbreakermayresultinelectricallyshocks,orfirepersonalinjury.
CAUTION•Donotinstalltheairconditionerwheregasleakagewouldbeexposedtoopenflames.Ifthegasleaksandbuildsuparoundtheunit,itmaycatchfire.
•Establishdrainpipingaccordingtotheinstructionsofthismanual.Inadequatepipingmaycausewaterdamage.
•Tightentheflarenutaccordingtothespecifiedtorque.Atorquewrenchshouldbeused.Iftheflarenutistightenedtoomuch,theflarenutmaycrackovertimeandcauserefrigerantleakage.
•Donottouchtheheatexchangerfins.Improperhandlingmayresultininjury.
•Beverycarefulaboutproducttransportation.SomeproductsusePPbandsforpackaging.DonotuseanyPPbandsforameansoftransportation.Itisdangerous.
•Makesuretoprovideforadequatemeasuresinordertopreventthattheoutdoorunitbeusedasashelterbysmallanimals.Smallanimalsmakingcontactwithelectricalpartscancausemalfunctions,smokeorfire.Pleaseinstructthecustomertokeeptheareaaroundtheunitclean.
•Thetemperatureofrefrigerantcircuitwillbehigh,pleasekeeptheinter-unitwireawayfromcopperpipesthatarenotthermallyinsulated.
•ElectricalworkmustbeperformedinaccordancewiththeNEC/CECbyauthorizedpersonnelonly.
AccessoriesAccessoriessuppliedwiththeoutdoorunit:
Installationmanual 1
Drainplug
Thedrainplugislocatedinthebottomofthepackingcase.
1A
B
01_EN_3P300674-1.indd 2 10/6/2011 1:37:41 PM
3■English
Precautions for Selecting the Location1) Chooseaplacesolidenoughtobeartheweightandvibrationoftheunit,wheretheoperationsoundswillnotbeamplified.2) Choosealocationwherethehotairdischargedfromtheunitortheoperationsoundswillnotdisturbtheneighborsoftheuser.3) Avoidinstallingnearbedroomssothatoperationsoundswillnotbeaproblem.4) Theremustbesufficientspaceforcarryingtheunitintoandoutofthesite.5) Theremustbesufficientspaceforairpassageandnoobstructionsaroundtheairinletandtheairoutlet.6) Thesitemustbefreefromthepossibilityofflammablegasleakageinanearbyplace.7) Installunits,powercordsandinter-unitwireatleast10ft(3m)awayfromtelevisionandradiosets.Thisistopreventinterference
toimagesandsounds.(Noisesmaybeheardeveniftheyaremorethan10ft(3m)awaydependingonradiowaveconditions.)8) Incoastalareasorotherplaceswithsaltyatmosphereofsulfategas,corrosionmayshortenthelifeoftheairconditioner.9) Sincedrainflowsoutoftheoutdoorunit,donotplaceanythingundertheunitwhichmustbekeptawayfrommoisture.
NOTECannotbeinstalledhangingfromceilingorstacked.
CAUTIONWhenoperatingtheairconditionerinalowoutdoorambienttemperature,besuretofollowtheinstructionsdescribedbelow.•Topreventexposuretowind,installtheoutdoorunitwithitssuctionsidefacingthewall.
•Neverinstalltheoutdoorunitatasitewherethesuctionsidemaybeexposeddirectlytowind.
•Topreventexposuretowind,itisrecommendedtoinstallabaffleplateontheairdischargesideoftheoutdoorunit.
•Inheavysnowfallareas,selectaninstallationsitewherethesnowwillnotaffecttheunit.
Construct a large canopy.Construct a pedestal.
Install the unit high enough off the ground to prevent burying in snow.
01_EN_3P300674-1.indd 3 10/6/2011 1:37:42 PM
4 ■English
Outdoor Unit Installation Drawings
9-7/8 (250) from wall
How to remove the stop valve cover.
Remove the screw on the stop valve cover.Slide the lid downward to remove it.
How to attach the stop valve cover.
Insert the upper part of the stop valve cover into the outdoor unit to install.Tighten the screws.
Stop valve cover
Allow space for piping and electrical servicing.(F
oot b
olt-h
ole
cen
ters
)
CAUTION**Set the piping length from 4.92ft (1.5m) to 65.6ft (20m).
Where there is a danger of the unit falling, use foot bolts, or wires.
In sites with poor drainage, use block bases for outdoor unit. Adjust foot height until the unit is leveled. Otherwise, water leakage or pooling of water may occur.
(Foot bolt-hole centers)(From unit’s side)
Max. allowable piping height
Min. allowable piping length
Max. allowable piping length 65.6ft (20m)
4.92ft (1.5m)
49.2ft (15m)
Liquid pipe
Gas pipe
O.D. 1/4 inch (6.4mm)
O.D. 3/8 inch (9.5mm)
0.21oz/ft (20g/m)
Additional refrigerant required for refrigerant pipe exceeding 32.8ft (10m) in length.
**
*
* Be sure to add the proper amount of additional refrigerant. Failure to do so may result in reduced performance.
** The suggested shortest pipe length is 4.92ft (1.5m), in order to avoid noise from the outdoor unit and vibration. (Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used.) When connecting the FDXS12 indoor unit, the shortest piping length should be no less than 9.84ft (3m).
unit : inch (mm)
22-5/8 (574) 4-1/8(105.5)
12-1
/4 (3
11)
Wrap the insulation pipe with the finishingtape from bottom to top.
Allow 11-13/16 inch (300mm) of work space below the ceiling surface.
01_EN_3P300674-1.indd 4 10/6/2011 1:37:42 PM
5■English
Installation Guidelines •Whereawallorotherobstacleisinthepathofoutdoorunit’sinletoroutletairflow,followtheinstallationguidelinesbelow.•Foranyofthebelowinstallationpatterns,thewallheightontheoutletsideshouldbe47-1/4inch(1200mm)orless.
More than 1-15/16 (50)
More than 3-15/16 (100)
Side view
47-1/4(1200)or less
More than 1-15/16 (50)
More than 1-15/16 (50)
More than 5-7/8 (150)
Top view
More than 3-15/16 (100)
Top view
unit: inch (mm)
More than 5-7/8 (150)
More than 11-13/16 (300)More than 1-15/16 (50)
Wall facing one side Walls facing two sides
Walls facing three sides
Precautions on Installation•Checkthestrengthandleveloftheinstallationgroundsothattheunitwillnotcauseanyoperatingvibrationornoiseafterinstalled.•Inaccordancewiththefoundationdrawing,fixtheunitsecurelybymeansofthefoundationbolts.(Prepare4setsofM8orM10foundationbolts,nutsandwasherseachwhichareavailableonthemarket.)
•Itisbesttoscrewinthefoundationboltsuntiltheirendsare3/4inch(20mm)fromthefoundationsurface.
3/4
inch
(2
0mm
)
Outdoor Unit Installation1. Installing outdoor unit
1) Wheninstallingtheoutdoorunit,referto“PrecautionsforSelectingtheLocation”andthe“OutdoorUnitInstallationDrawings”.2) Ifdrainworkisnecessary,followtheproceduresbelow.
2. Drain work1) Usedrainplugfordrainage.2) Ifthedrainportiscoveredbyamountingbaseorfloorsurface,place
additionalfootbasesofatleast1-1/4inch(30mm)inheightundertheoutdoorunit’sfeet.
3) Incoldareas,donotuseadrainhosewiththeoutdoorunit.(Otherwise,drainwatermayfreeze,impairingheatingperformance.)
Drain port
Bottom frame
Drain plug
Hose (available commercially,inner dia. 5/8 inch (16mm))
01_EN_3P300674-1.indd 5 10/6/2011 1:37:42 PM
6 ■English
Outdoor Unit Installation3. Flaring the pipe end
1) Cutthepipeendwithapipecutter.2) Removeburrswiththecutsurfacefacing
downwardsothatthechipsdonotenterthepipe.3) Puttheflarenutonthepipe.4) Flarethepipe.5) Checkthattheflaringisproperlymade.
WARNING•Donotusemineraloilonflaredpart.•Preventmineraloilfromgettingintothesystemasthiswouldreducethelifetimeoftheunits.•Neverusepipingwhichhasbeenusedforpreviousinstallations.Onlyusepartswhicharedeliveredwiththeunit.•NeverinstalladriertothisR410Aunitinordertoguaranteeitslifetime.•Thedryingmaterialmaydissolveanddamagethesystem.•Incompleteflaringmaycauserefrigerantgasleakage.
4. Refrigerant piping
CAUTION•Usetheflarenutfixedtothemainunittopreventitfromcrackinganddeterioratingfromage.•Topreventgasleakage,applyrefrigerationoilonlytotheinnersurfaceoftheflare.(UserefrigerationoilforR410A.)•Usetorquewrencheswhentighteningtheflarenutstopreventdamagetotheflarenutsandgasleakage.
Flare nut tightening torque
Liquid side
1/4 inch (6.4mm)
10.4-12.7ft • lbf
(14.2-17.2N • m)
Gas side
3/8 inch (9.5mm)
24.1-29.4ft • Ibf
(32.7-39.9N • m)
Valve cap tightening torque
Liquid side
1/4 inch (6.4mm)
15.9-20.2ft • Ibf
(21.6-27.4N • m)
Gas side
3/8 inch (9.5mm)
15.9-20.2ft • Ibf
(21.6-27.4N • m)
Do not apply refrigeration
oil to the outer surface.
Flare nut
Apply refrigeration oil to
the inner surface of the
flare.
Do not apply refrigeration oil to
the flare nut to avoid tightening
with excessive torque.
[Apply oil]• Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque wrenches.
Service port cap tightening torque
7.9-10.8ft • lbf(10.8-14.7N • m)
(Cut exactly at right angles.) Remove burrs.
Set exactly at the position shown below.
A
Flaring
Die
Check
Flare’s inner surface must be flaw-free.
The pipe end must be evenly flared in a perfect circle.
Make sure that the flare nut is fitted.
A 0-0.020 inch (0-0.5mm)
Clutch-type
Flare tool for R410A
0.039-0.059 inch (1.0-1.5mm)
Clutch-type (Rigid-type)
0.059-0.079 inch (1.5-2.0mm)
Wing-nut type (Imperial-type)
Conventional flare tool
01_EN_3P300674-1.indd 6 10/6/2011 1:37:42 PM
7■English
5. Purging air and checking gas leakage
WARNING•Donotmixanysubstanceotherthanthespecifiedrefrigerant(R410A)intotherefrigerationcycle.•Whenrefrigerantgasleaksoccur,ventilatetheroomassoonandasmuchaspossible.•R410A,aswellasotherrefrigerants,shouldalwaysberecoveredandneverbereleaseddirectlyintotheenvironment.•UseavacuumpumpforR410Aexclusively.Usingthesamevacuumpumpfordifferentrefrigerantsmaydamagethevacuumpumportheunit.
•Whenpipingworkiscompleted,itisnecessarytopurgetheairandcheckforgasleakage.
•Ifusingadditionalrefrigerant,performairpurgingfromtherefrigerantpipesandindoorunitusingavacuumpump,thenchargeadditionalrefrigerant.
•Useahexagonalwrench(3/16inch(4mm))tooperatethestopvalverod.•Allrefrigerantpipejointsshouldbetightenedwithatorquewrenchatthespecifiedtighteningtorque.
1) Connectprojectionsideofcharginghose(whichcomesfromgaugemanifold)togasstopvalve’sserviceport.
2) Fullyopengaugemanifold’slow-pressurevalve(Lo)andcompletelycloseitshigh-pressurevalve(Hi).(High-pressurevalvesubsequentlyrequiresnooperation.)
3) Dovacuumpumpingandmakesurethatthecompoundpressuregaugereads–29.9inHg(–0.1MPa).*1
4) Closegaugemanifold’slow-pressurevalve(Lo)andstopvacuumpump.(Keepthisstateforafewminutestomakesurethatthecompoundpressuregaugepointerdoesnotswingback.)*2
5) Removecapsfromliquidstopvalveandgasstopvalve.
6) Turntheliquidstopvalve’srod90degreescounterclockwisewithahexagonalwrenchtoopenvalve.Closeitafter5seconds,andcheckforgasleakage.Usingsoapywater,checkforgasleakagefromindoorunit’sflareandoutdoorunit’sflareandvalverods.Afterthecheckiscomplete,wipeallsoapywateroff.
7) Disconnectcharginghosefromgasstopvalve’sserviceport,thenfullyopenliquidandgasstopvalves.(Donotattempttoturnvalverodbeyonditsstop.)
8) Tightenvalvecapsandserviceportcapsfortheliquidandgasstopvalveswithatorquewrenchatthespecifiedtorques.
*1.Pipelengthvs.vacuumpumpruntime
Pipelength Upto49.2ft(15m) Morethan49.2ft(15m)
Runtime Notlessthan10min. Notlessthan15min
*2.Ifthecompoundpressuregaugepointerswingsback,refrigerantmayhavewatercontentoraloosepipejointmayexists.Checkallpipejointsandretightennutsasneeded,thenrepeatsteps2)through4).
Gauge manifold
Compound pressure gauge
Pressure meter
Low-pressure valve
High-pressure valve
Charging hoses
Vacuum pump
Valve caps
Service port
Liquid stop valve
Gas stop valve
01_EN_3P300674-1.indd 7 10/6/2011 1:37:42 PM
8 ■English
Outdoor Unit Installation6. Refilling the refrigerant
Checkthetypeofrefrigeranttobeusedonthemachinenameplate.Precautions when adding R410AFill from the gas pipe in liquid form.Itisamixedrefrigerant,soaddingitingasformmaycausetherefrigerantcompositiontochange,preventingnormaloperation.
1) Beforefilling,checkwhetherthecylinderhasasiphonattachedornot.(Itshouldhavesomethinglike“liquidfillingsiphonattached”displayedonit.)
Filling a cylinder with an attached siphon
Stand the cylinder upright when filling.
There is a siphon pipe inside, so the cylinder need not be upside-down to fill with liquid.
Filling other cylinders
Turn the cylinder upside-down when filling.
•BesuretousetheR410Atoolstoensurepressureandtopreventforeignobjectsentering.
7. Refrigerant piping work7-1 Caution on pipe handling
1) Protecttheopenendofthepipeagainstdustandmoisture.2) Allpipebendsshouldbeasgentleaspossible.Useapipebenderfor
bending.
7-2 Selection of copper and heat insulation materialsWhenusingcommercialcopperpipesandfittings,observethefollowing:1) Insulationmaterial:Polyethylenefoam
Heattransferrate:0.041to0.052W/mK(0.024to0.030Btu/fth°F(0.035to0.045kcal/mh°C))BesuretouseinsulationthatisdesignedforusewithHVACSystems.
2) Besuretoinsulateboththegasandliquidpipingandtoprovideinsulationdimensionsasbelow.
Gasside LiquidsideGaspipethermal
insulationLiquidpipethermal
insulationO.D.3/8inch(9.5mm)
O.D.1/4inch(6.4mm)
I.D.15/32-19/32inch(12-15mm)
I.D.5/16-13/32inch(8-10mm)
Minimumbendradius Thickness13/32inch(10mm)Min.1-3/16inch(30mm)ormore
Thickness0.031inch(0.8mm)(C1220T-O)
•Useseparatethermalinsulationpipesforgasandliquidrefrigerantpipes.
Wall
If no flare cap is available, cover the flare mouth with tape to keep dirt or water out.
Be sure to place a cap.
Rain
Gas pipeLiquid pipe
Gas pipe insulation
Liquid pipe insulation
Finishing tape Drain hose
Inter-unit wire
01_EN_3P300674-1.indd 8 10/6/2011 1:37:43 PM
9■English
Pump Down OperationIn order to protect the environment, be sure to pump down when relocating or disposing of the unit.
1) Removethevalvecapfromliquidstopvalveandgasstopvalve.
2) Carryoutforcedcoolingoperation.3) After5to10minutes,closetheliquidstopvalvewitha
hexagonalwrench.4) After2to3minutes,closethegasstopvalveandstopforced
coolingoperation.
Forced cooling operation
■ Using the indoor unit ON/OFF switch
PresstheindoorunitON/OFFswitchforatleast5seconds.(Theoperationwillstart.)• Forcedcoolingoperationwillstopautomaticallyafteraround15minutes.
Tostoptheoperation,presstheindoorunitON/OFFswitch.
■ Using the indoor unit’s remote controller
1) Press“MODE”buttonandselectthecoolingmode.2) Press“ON/OFF”buttontoturnonthesystem.3) Pressbothof“TEMP”buttonand“MODE”buttonatthesametime.4) Press“MODE”buttontwice.( willbedisplayedandtheunitwillenterforcedcoolingoperation.)• Forcedcoolingoperationwillstopautomaticallyafteraround30minutes.
Tostoptheoperaion,press“ON/OFF”button.
■ Using the outdoor unit forced cooling operation switch
Forcedcoolingoperationcanbeperformedwhentheoutdoorunitforcedcoolingoperationswitchispressedwithinaround3minutesafterpowerissupplied.Pushon“ ”(SW1)withascrewdriver.(Theoperationwillstart.)• Forcedcoolingoperationwillstopautomaticallyafteraround15minutes.
Tostoptheoperation,presstheswitch(SW1).
Wiring WARNING
•Donotusetappedwires,strandedwires,extensioncords,orstarburstconnections,astheymaycauseoverheating,electricalshock,orfire.•Donotuselocallypurchasedelectricalpartsinsidetheproduct.(Donotbranchthepowerforthedrainpump,etc.,fromtheterminalblock.)Doingsomaycauseelectricshockorfire.
•Besuretoinstallagroundfaultcircuitinterrupterbreaker.(Onethatcanhandlehigherharmonics.)(Thisunitusesaninverter,whichmeansthatitmustbeusedagroundfaultcircuitinterrupterbreakercapablehandlingharmonicsinordertopreventmalfunctioningofthegroundfaultcircuitinterrupterbreakeritself.)
•Useanall-poledisconnectiontypebreakerwithatleast1/8inch(3mm)betweenthecontactpointgaps.•Whencarryingoutwiringconnection,takecarenottopullattheconduit.•Donotconnectthepowerwiretotheindoorunit.Doingsomaycauseelectricshockorfire.
•Donotturnonthesafetybreakeruntilallworkiscompleted.
1) Striptheinsulationfromthewire(3/4inch(20mm)).
2) Connecttheconnectionwiresbetweentheindoorandoutdoorunitssothattheterminalnumbersmatch.Tightentheterminalscrewssecurely.Werecommendaflatheadscrewdriverbeusedtotightenthescrews.
Gas stop valve Valve cap
Hexagonal wrench
Close
Liquid stop valve
Service port
1 2 3
PushScrewdriver
Power supplyterminal block
Forced cooling operation switch(SW1)
123
1 2 3 L1L2GR
Safety breaker 15A
Ground faultcircuit interrupter
Ground
Use AWG16 if the connection wire length is less than 32.8ft (10m), or AWG14 if it is 32.8ft (10m) or more.
Outdoor unit
Indoor unit
Power supply60Hz 208-230V
Use AWG 14 wires.
01_EN_3P300674-1.indd 9 10/6/2011 1:37:43 PM
10 ■English
Wiring<Methodofmountingconduit>
1) Passwiresthroughtheconduitandsecurethemwithalocknut.2) Aftercompletingthework,reattachtheconduitmountingcoverandtheprotectionplatetoitsoriginalposition.
1 2 3
1 2 3 Power supplyterminal block
Shape wires so that the service lid and stop valve cover fit securely.
Use the specified wire type and connect it securely.
Conduit mounting plate
Conduit1/2 inch (21.3mm)
Lock nut
Observethenotesmentionedfollowingwhenwiringtothepowersupplyterminalblock.Precautionstobetakenforpowersupplywiring.
CAUTION•Whenconnectingtheconnectionwirestotheterminalblockusingasinglecorewire,besuretoperformcurling.Problemswiththeworkmaycauseheatandfires.
Strip wire end to this point.
Excessive strip length may cause electrical shock or leakage.
Good Wrong
•Ifthestrandedwiresmustbeused,makesuretousetheroundcrimp-styleterminalforconnectiontothepowersupplyterminalblock.Placetheroundcrimp-styleterminalsonthewiresuptothecoveredpartandsecureinplace.
Stranded wire
Round crimp-styleterminal
3) Pullthewireandmakesurethatitdoesnotdisconnect.Thenfixthewireinplacewithawirestop.
Stripping wire at terminal block
Good Wrong
01_EN_3P300674-1.indd 10 10/6/2011 1:37:44 PM
11■English
Facility Setting (cooling at low outdoor temperature)This function is designed for facilities such as equipment or computer rooms. It is never to be used in a residence or office where people occupy the space.
■ Cuttingjumper4(J4)onthecircuitboardwillexpandtheoperationrangedownto14°F(–10°C).Howeveritwillstopiftheoutdoortemperaturedropsbelow–0.4°F(–18°C)andstartbackuponcethetemperaturerisesagain.
1 2 3
S70
S40
S2S90
J5J4J3
Cut J4 with nippers or a similar tools.
CAUTION•Iftheoutdoorunitisinstalledwheretheheatexchangeroftheunitisexposedtodirectwind,provideawindbreakwall.•Intermittentnoisesmaybeproducedbytheindoorunitduetotheoutdoorfanturningonandoffwhenusingfacilitysettings.•Donotplacehumidifiersorotheritemswhichmightraisethehumidityinroomswherefacilitysettingsarebeingused.Ahumidifiermightcausedewcondensationfromtheindoorunitoutletvent.
•Cuttingjumper4(J4)setstheindoorfantaptothehighestposition.Notifytheuseraboutthis.
01_EN_3P300674-1.indd 11 10/6/2011 1:37:44 PM
12 ■English
Trial Operation and Testing1. Trial operation and testing
1-1Measurethesupplyvoltageandmakesurethatitfallsinthespecifiedrange.
1-2Trialoperationshouldbecarriedoutineithercoolingorheatingmode.
•Incoolingmode,selectthelowestprogrammabletemperature;inheatingmode,selectthehighestprogrammabletemperature.1) Trialoperationmaybedisabledineithermodedependingontheroomtemperature.2) Aftertrialoperationiscomplete,setthetemperaturetoanormallevel(78°Fto82°F(26°Cto28°C)incoolingmode,
68°Fto75°F(20°Cto24°C)inheatingmode).3) Forprotection,thesystemdisablesrestartoperationfor3minutesafteritisturnedoff.
1-3Carryoutthetestoperationinaccordancewiththeoperationmanualtoensurethatallfunctionsandparts,suchasfinmovement,areworkingproperly.•Theairconditionerrequiresasmallamountofpowerinitsstandbymode.Ifthesystemisnottobeusedforsometimeafterinstallation,shutoffthecircuitbreakertoeliminateunnecessarypowerconsumption.
•Ifthecircuitbreakertripstoshutoffthepowertotheairconditioner,thesystemwillrestoretheoriginaloperationmodewhenthecircuitbreakerisopenedagain.
2. Test itemsTestitems Symptom Check
Indoorandoutdoorunitsareinstalledproperlyonsolidbases. Fall,vibration,noise
Norefrigerantgasleaks.Incompletecooling/heatingfunction
Refrigerantgasandliquidpipesandindoordrainhoseextensionarethermallyinsulated.
Waterleakage
Draininglineisproperlyinstalled. Waterleakage
Systemisproperlygrounded. Electricalleakage
Thespecifiedwiresareusedforinter-unitwiring. Inoperativeorburndamage
Indoororoutdoorunit’sairinletorairoutlethasclearpathofair.Stopvalvesareopened.
Incompletecooling/heatingfunction
Indoorunitproperlyreceivesremotecontrolcommands. Inoperative
01_EN_3P300674-1.indd 12 10/6/2011 1:37:44 PM
3P300674-1 M11B134 (1111) HT