69
Installation Manual Truck Edition UT-1280 Undermount Systems January 2017 Revision 0 TK-56374-1-IM

Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

Thermo King has a policy of coninuous product and data improvements and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

Thermo King – by Trane Technologies (NYSE: TT), a global climate innovator – is a worldwide leader in sustainable transport temperature control solutions. Thermo King has been providing transport temperature control solutions for a variety of applications, including trailers, truck bodies, buses, air, shipboard containers and railway cars since 1938. For more information, visit www.thermoking.com or www.tranetechnologies.com

©2020 Trane Technologies

TK 56374-1-IM Jan 2017

Installation Manual

Truck EditionUT-1280 Undermount Systems

January 2017

Revision 0

TK-56374-1-IM

Page 2: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3
Page 3: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

Installation Manual

Truck EditionUT-1280 SystemsTK 56374-1-IM (Rev. 0

t© 2017 Ther A. U.S.A.

CopyrighPrinted in

Undermount, 01/17)

mo King Corp., Minneapolis, MN, U.S.

Page 4: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

2

onnected device with a web browser.

com/SE/?SID=SV_2octfSHoUJxsk6x to complete

Installation Manual

Release HistoryReleased (01/17)

Customer Satisfaction SurveyLet your voice be heard!

Your feedback will help improve our manuals. The survey is accessible through any Internet-c

Scan the Quick Response (QR) code or click or type the web address http://irco.az1.qualtrics.the survey.

Page 5: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

3

UT-1280 Systems

Page 6: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

4

sing unit and UTSE or S-3 remote evaporator systems

ons warranties express or implied, with respect to ould not be regarded as all-inclusive or covering ent should be consulted.

, maintained, repaired or altered as, in the

erty damage or any other direct, indirect, any information, recommendations or

Introduction

This installation manual was written to assist with the installation of a Thermo King UT-1280 condenonto trucks specifically designed and built for refrigerated applications.

Due to its complexity, you should not attempt this installation unless you:

• Are an experienced mechanic.

• Can safely lift 34 kilos (75 lbs).

• Have a basic understanding of electricity and electrical wiring.

• Are certified in the repair and maintenance of refrigeration systems.

• Have the necessary tools and equipment to complete the installation.

This manual is published for informational purposes only. Thermo King makes no representatithe information recommendations and descriptions contained herein. Information provided shall contingencies. If further information is required, Thermo King Corporation Service Departm

Thermo King’s warranty shall not apply to any equipment which has been “so installedmanufacturer’s judgment, to affect its integrity.”

Manufacturer shall have no liability to any person or entity for any personal injury, propspecial, or consequential damages whatsoever, arising out of the use of this manual ordescriptions contained herein.

Page 7: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

5

Table of Contents

Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6UT-1280 Condenser Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 10UTSE (NAD - A/P) Evaporator Dimensions . . . . . . . . . . . . . . . . . 11S-3 + S-3 Evaporator Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 12HMI Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Important Installation Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Required Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20Condenser Installation Kit Components . . . . . . . . . . . . . . . . . . . 22Evaporator Installation Kit Components . . . . . . . . . . . . . . . . . . . . 24Uncrating the UT-1280 Condenser . . . . . . . . . . . . . . . . . . . . . . . 26Installing the UT-1280 Condenser . . . . . . . . . . . . . . . . . . . . . . . . 28Installing the Fuel Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Installing HMI Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

Installing the Battery Box (Option) . . . . . . . . . . . . . . . . . . . . . . . . 34Installing UTSE Evaporator - NAD - A/P . . . . . . . . . . . . . . . . . . . . 36Installing S-3 + S-3 Evaporators . . . . . . . . . . . . . . . . . . . . . . . . . . 38Removing Holding Charge and Refrigerant Tubing Best Practice 42Connecting Refrigeration Tubing–UTSE Evaporator . . . . . . . . . . 44Connecting Refrigeration Tubing–S-3 + S-3 Evaporators . . . . . . 46Installing Drain Hoses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Electrical Connections–UTSE Evaporator . . . . . . . . . . . . . . . . . . 50Electrical Connections–S-3 + S-3 Evaporators . . . . . . . . . . . . . . . 52Evaporator Drain Hose Resistance Wire Installation Guide . . . . . 54System Leak Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56System Evacuation and Charging . . . . . . . . . . . . . . . . . . . . . . . . . 58Installing the S-3 Evaporator Covers . . . . . . . . . . . . . . . . . . . . . . 62UNIT CHECK LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64

Page 8: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

6

) holding charge of Nitrogen.

ng charge of Nitrogen. This

isture from entering the

before completing the ondensing unit holding nes, leak testing the system,

the potential harm to the here.

f refrigerant into the

Safety Precautions

CautionThermo King UT-1280 condensing units are shipped with a 35-69 kPa (5-10 psiThis holding charge may be safely vented into the atmosphere.

Thermo King remote evaporators are shipped with a 35-69 kPa (5-10 psi) holdiholding charge may be safely vented into the atmosphere.

IMPORTANT: Do not release the holding charge until necessary to prevent mosystem.

SEVERE COMPRESSOR DAMAGE will result from operating the engine/motorsystem installation which includes: installing the components, releasing the ccharge, releasing the remote unit holding charge, soldering the refrigeration lievacuation and clean-up, and charging the system.

Recover RefrigerantAt Thermo King, we recognize the need to preserve the environment and limit ozone layer that can result from allowing refrigerant to escape into the atmosp

We strictly adhere to a policy that promotes the recovery and limits the loss oatmosphere.

Page 9: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

7

s contaminated with moisture or standard oils,

n R-404A units

e tools certified for and dedicated to R-404A s and non-HFC refrigerants or oils will

Safety Precautions

R-404A

DO NOT use Polyol Ester based oil in standard Thermo King units.

DO NOT mix Polyol Ester and standard synthetic compressor oils.

Keep Polyol Ester compressor oil in tightly sealed containers. If Polyol Ester oil becomedispose of properly-DO NOT USE!

CAUTION: Use ONLY Polyol Ester based refrigeration oil (TK P/N 203-413) i

CAUTION: When servicing Thermo King R-404A units, use only those servicrefrigerant and Polyol Ester compressor oils. Residual non-HFC refrigerantcontaminate R-404A systems.

Page 10: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

8

r goggles or safety glasses. eration oil, and battery acid can e eyes (see First Aid under

ands away from fans and belts when should also be considered when compressor service valves.

auge manifold hoses are in good m come in contact with a belt, fan t surface.

ll mounting bolts are tight and are of particular application

oles in the unit unless absolutely into the unit may weaken structural ed into electrical wiring can cause fire

il fins are very sharp and can cause r leather work gloves to prevent

Safety Precautions

The symbol appears next to a point that is particularly important:

DANGER: Addresses a circumstance that, if encountered, will lead to death or serious injury

WARNING: Addresses a circumstance that, if encountered, might lead to death or serious injury.

CAUTION: Addresses a circumstance that, if encountered, may cause damage to equipment or minor injury.

DANGER: Thermo King recommends a forklift with the correct capacity rating be used to safely lift and install the UT condenser unit to prevent equipment damage or personal injury.

DANGER: Never operate the unit with the discharge valve closed because it could cause the compressor to explode, causing death or serious injury.

DANGER: Never apply heat to a sealed refrigeration system or container because it could explode, causing death or serious injury

DANGER: Fluorocarbon refrigerants, in the presence of an open flame or electrical short, produce toxic gases that are severe respiratory irritants capable of causing death.

DANGER: Be careful when working with a refrigerant or refrigeration system in any enclosed or confined area with a limited air supply (i.e., a trailer, container or the hold of a ship). Refrigerant tends to displace air and can cause oxygen depletion which may result in death by suffocation.

WARNING: Always weaRefrigerant liquid, refrigpermanently damage thRefrigeration Oil).

WARNING: Keep your hthe unit is running. Thisopening and closing the

WARNING: Make sure gcondition. Never let themotor pulley, or any ho

WARNING: Make sure acorrect length for their

WARNING: Never drill hnecessary. Holes drilledcomponents. Holes drillor explosion.

WARNING: Exposed copainful lacerations. Weainjury.

Page 11: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

9

)

frost bite, the objectives of First Aid are to rther injury, to warm the affected area

ation.

d, immediately flush eyes with large amounts cal attention.

mounts of lukewarm water. Do not apply lothing and shoes. Wrap burns with dry, ct from infection/injury. Get medical

clothing before reuse.

to fresh air and use CPR or mouth-to-mouth with victim until arrival of emergency

ediately flush with plenty of water for at PHYSICIAN. Wash skin with soap and

fluorocarbon refrigerants are classified ertain precautions must be observed

or servicing a unit in which they are to the atmosphere in the liquid state, ants evaporate rapidly, freezing anything

igeration oil contact with the eyes. Avoid d contact of refrigeration oil with skin or ughly after handling refrigeration oil to

Safety Precautions (continued

Battery Installation and Cable Routing Refrigerant

First Aid

FROST BITE: In the event ofprotect the frozen area from furapidly and to maintain respir

EYES: For contact with liquiof water and get prompt medi

SKIN: Flush area with large aheat. Remove contaminated csterile, bulky dressing to proteattention. Wash contaminated

INHALATION: Move victim ventilation, if necessary. Stay medical personnel.

Refrigeration Oil

First AidIn case of eye contact, immleast 15 minutes. CALL Awater.

WARNING: Improperly installed battery could result in a fire or explosion! A Thermo King approved battery must be installed and properly secured.

WARNING: Improperly installed battery cables could result in fire or explosion! Battery cables must be installed, routed and secured properly to prevent them from rubbing, chaffing or making contact with hot, sharp or rotating components.

WARNING: Do not attach fuel lines or any additional wiring harnesses to the battery cables as this could cause an electrical fire!

CAUTION: Do not connect other manufacturer’s equipment or accessories to the Thermo King unit. This could result in severe damage to equipment and void the warranty!

CAUTION: Set all unit electrical controls to the OFF position before connecting battery cables to the battery to prevent unit from starting unexpectedly and causing personal injury.

CAUTION: Always wear protective clothing, gloves and eye wear when handling and installing batteries. Battery acid can cause serious burns when exposed to eyes or skin. If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters your eye, immediately flood it with running cold water for at least twenty minutes and get medical attention immediately.

CAUTION: Always cover battery terminals to prevent them from making contact with metal components during battery installation. Battery terminals grounding against metal could cause the battery to explode.

WARNING: Although as safe refrigerants, cwhen handling them used. When releasedfluorocarbon refrigerthey contact.

WARNING: Avoid refrprolonged or repeateclothing. Wash thoroprevent irritation.

Page 12: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

10

sions

UT-1280 Condenser Dimen
Page 13: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

11

ensions

UTSE (NAD- A/P) Evaporator Dim
Page 14: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

12

sions

WEIGHT = 52 kg (115 lb.) each

S-3 + S-3 Evaporator Dimen

Page 15: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

13

HMI Dimensions

Standard HMI Controller (LED Display)

Optional Premium HMI Controller (Graphics Display)

Page 16: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

14

tes

ing and Electrical Wiringt to minimize the amount of time the refrigeration apped and open to ambient conditions. Always keep until ready to connect and solder.and copper fittings for obstructions prior to assembly.ired that nitrogen or another inert gas be used to purge

ile soldering. This prevents oxidation and formation of ubes.er solder for joining all remote refrigerant tubes.

ion and hot gas lines.ion tubes should be secured by clamps every 600 mm

harness should be secured by clamps or tie bands m (24.00 in.).ugh (W = Wall and C = Ceiling) is required E).orator installations require two suction tubes.

s automatically turn off remote evaporators when the g door is opened. This avoids the entry of warm, moist ad space. Door switches are recommended for all stallations.

ecommended to use good quality insulated curtains on imit the amount of warm, moist air from entering the ring door openings.

Important Installation No

Safety Precautions• See “Safety Precautions” on pages 6 - 8 prior to installing and

servicing this product.

Evaporator Location• The best airflow is achieved when the evaporator is installed an

equal distance from each side wall.• It is recommended that moving bulkheads not be allowed closer

than 1219 mm (48.00 in.) or 1 pallet from the evaporator outlet (Detail A).

• The minimum clearance from the bottom of the evaporator to the top of the cargo should be 101 mm (4.00 in.) (Detail A).NOTE: This minimum clearance is required under the fan intake area only and does not refer to the LOAD LINE.

• The evaporator should be located a minimum of 51 mm (2.00 in.) from the truck wall (Detail B).

Defrost Drains• The evaporator must be properly mounted to provide a slope

towards the drain. This is accomplished by adding one 3/8 in. and one 3/16 in. washers on the drain side and only one 3/8 in. washer on the other side at each mounting surface.

• Defrost drains must exit the evaporator at a 45° angle. Drains should be 267 mm (10.50 in.) from the evaporator to the truck ceiling (Detail C).

Wall Drain Tube• CPVC• 1.00 in. ID (Internal Diameter)

Refrigerant Tub• It is importan

tubes are unctubes capped

• Check tubes • It is also requ

the tubes whscale inside t

• Use 35% silv• Insulate suct• All refrigerat

(24.00 in.).• All electrical

every 600 m• Only one tro

(Detail D & • All dual evap

Door Switches• Door switche

correspondinair into the lomulti-temp in

Door Curtains• It is always r

all doors to lload space du

Page 17: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

15

ntinued)

Important Installation Notes (co
Page 18: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

16

ontinued)

ap Plugsed to plug the two S-2 evaporator mounting access

y above the drain pan. These plugs must be installed to drain pan from spilling out of these holes and into the

Important Installation Notes (c

Defrost Drain Tube ConnectorsIMPORTANT: Follow the instructions below to prevent defrost drain tube water leaks.

All S-3 remote evaporators are equipped with a quick disconnect fitting that connects the drain pan to the drain tubes (Detail I).

To properly install the tube make sure that the tube is fully inserted past the O-ring and up to the stop inside the coupler (Detail II).

NOTE: The fitting will grip the tube before it seals with the o-ring.

When the tube is in the correct position the O-ring will seal and the Teeth will grip the tube keeping it in place. Check the fit by pulling on the tube(s) to insure that it will not pull out of the fitting (Detail III).

To disconnect the tube from the fitting: press the collet into the fitting. Hold the collect in place and pull the tube out. The fitting can be re-used. Clean any burrs off the tube before re-inserting it into the fitting(Detail IV).

Evaporator CCap plugs are providholes located directlprevent water in the cargo area.

Page 19: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

17

ntinued)

Important Installation Notes (co
Page 20: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

18

ontinued)

TANT: Supplied cap plugs (2 per evap) must be to prevent water in drain pan from spilling out of les and into cargo area.

Important Installation Notes (c

IMPORinstalledthese ho

Page 21: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

19

ntinued)

Important Installation Notes (co

Optional Transverse Drain Kit

Page 22: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

20

on

on

ale

urope Only)

(60 AMP Minimum)

Detector

s

(modified drywall lift shown)

hermometer

urate readings.

Required Tools

1. Safety Glasses

2. Drill

3. Drill Bits

4. Tape Measure

5. Wire Crimpers

6. Tubing Benders

7. Hole Saw

8. 35% Silver Solder & Flux

9. Tubing Swage

10. Tubing Cuter

11. Refrigerant Oil

12. Torch Set

13. Mechanics Tools

14. Manifold Set

15. Evacuation Stati

16. Reclaiming Stati

17. Refrigerant & Sc

18. Dry Nitrogen

19. Tap & Die Set (E

20. Battery Charger

21. Electronic Leak

22. Tubing Brushes

23. Scotch Brite Pad

24. Torque Wrench

25. Mechanical Lift

26. Digital Contact T

27. Forklift

NOTE: Torque wrenches should be in good working condition and routinely calibrated to assure acc

Page 23: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

21

Required Tools

Page 24: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

22

ponents

ing Installation Components

O-ring

ws

3 sizes)

Fitting, ORS nut and O-ring

-rings

(2 sizes)

izes)

ping

Condenser Installation Kit Com

Unit Mounting Component

1. Special Washer (if required)

Fuel Pump Mounting Components

2. Fuel Pump Bracket

3. Fuel Pump

4. 1/4-20 Mounting Bolts, Washers and Locking Nuts

5. Fuel Fittings

6. Fuel Pickup Tube

Electrical Installation Components

7. Fuse Holder and 60 Amp Fuse

8. Splice Connector (2 sizes)

9. Battery Cable Lugs (2 sizes)

10. Heat Shrink Sleeving

11. Remote Evaporator Harnesses (4)

12. 5/8-11 Mounting Bolts, Washers and Locking Nuts

13. 2-Pin and 3-Pin Sockets, Pins and Wedges

14. HMI Display

15. DIN Bracket

16. Terminal Fork Connectors (2 sizes)

Refrigeration Tub

17. Brass Flange and

18. M12 x 1.75 Scre

19. Copper Elbows (

20. Copper Tee

21. Tube with ORS

22. Filter Drier and O

23. Tube Insulation

24. Metal Clamps

25. Clamps (3 sizes)

26. Band Wraps (2 s

27. Screws Self-Tap

28. Sealer

29. Sealing Gasket

30. Drain Hose

Page 25: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

23

ponents

Condenser Installation Kit Com
Page 26: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

24

ponents

ing Installation Components

er 1/2 ''x 3/8''

3 sizes)

sizes)

ews

Evaporator Installation Kit Com

Evaporator Mounting Component

1. Special Washers (3 sizes)

2. Locking Nuts (1/2-13 and M10x1.5)

3. Flat Washers (1/2 '' and 3/8'')

4. Button Plug

5. Screws, Washers and Locking nuts (1/4-20)

6. Washers (1/2''' SAE)

Electrical Installation Components

7. Terminal Ring Blue

8. Terminal Fork Blue

9. Terminal Ring (Ampli-Bond Style)

Refrigeration Tub

10. Coupling Reduc

11. Copper Elbows (

12. Cooper Tee’s (3

13. Drain Elbows

14. Drain Tube

15. Drain Hose

16. Hose Clamp

17. Clamps (2 sizes)

18. Self-Tapping scr

19. Band Wraps

Page 27: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

25

ponents

Evaporator Installation Kit Com
Page 28: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

26

denser

Uncrating the UT-1280 Con

1. Remove all shrink wrap from the unit/crate.

2. Remove four upright boards that connect top and bottom sections of crate.

3. Remove control box side cover by removing four Torx screws.

4. Remove top crate sections by removing four carriage bolts.

5. Remove “toe board” from bottom crate section.

6. Loosen 2X quarter turn bolts and latches on front panel.

7. Rotate front door 10 to 15 degrees. Pull on handles to release latches and remove front door.

8. Remove battery box (if equipped) by removing four screws.

9. Remove two screws from front bottom frame member.

10. Remove two rear steel bracket and bottom crate section.

11. Install forged eyebolts into unit’s mounting holes and use an appropriate four point lift to carefully raise unit up from the crate.

WARNING: Thermo King requires a proper lifting fixture to safely lift units.

WARNING: Lifting eyebolts must be forged steel and a minimum M12 (1/2 in.) diameter.

WARNING: Use only locking hooks to attach to the eyebolts.

Page 29: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

27

enser

Uncrating the UT-1280 Cond
Page 30: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

28

enser

tall Z-Channels to truck box supports with Grade 5 (or bolts, washers and locking nuts.

ition and install onto Z-Channels with four Grade 5 (or 16 mm x 2) mounting bolts, washers and locking nuts. e securely and torque to 176-230 N•m (130-170 ft-lb).

Installing the UT-1280 Cond

1. Fabricate and insbetter) mounting

2. Lift unit into posbetter) 5/8 x 11 (Tighten hardwar

DANGER: Mount the UT-12080 only to the truck box support channels. An improper installation could lead to serious injury! Thermo King recommends the use of fabricated Z-channels to distribute the weight evenly across the truck box support channels. All channels, brackets, and hardware must be able to support the weight of the unit.

WARNING: The use of a forklift to install the UT-1280 is recommended to prevent equipment damage or personal injury.

Page 31: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

29

nser

Installing the UT-1280 Conde
Page 32: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

30

p

y line from fuel tank to fuel pump inlet.

om the UT host unit to fuel pump outlet.

n line from fuel outlet located on end of UT to fuel rn fitting.

p harness securely to fuel pump and route harness to

p harness to mating connector inside condenser. SEE .

electrical supply connector is located in upper rear it near battery cables. Fuel pump harness should also ame hole that battery wires use.

Installing the Fuel Pum

Supplied Components

S = Supply R = Return

1. Fuel pump must be installed as close to fuel tank as possible and not more than 762 mm (30.0 in.) above fuel in tank.

2. Fuel lines should be routed in a protective housing with no kinks or sharp bends.

NOTE: Do not connect unit fuel lines into truck’s fuel system.

3. Rubber grommets must be used when routing fuel lines through metal.

4. Secure all fuel lines with provided clamps.

5. Route fuel suppl

6. Route fuel line fr

7. Route fuel returtank pickup retu

8. Connect fuel pumcondenser.

9. Connect fuel pumNOTE BELOW

NOTE: Fuel pump left corner of the unexit frame through s

DANGER: Leaking fuel lines could cause a fire resulting in death or serious injury! All fuel lines must be tight and leak free!

DANGER: Do not route fuel lines together with battery cables or electrical wires as this could cause a fire!

Description Qty.

Fuel Pump Bracket 1

Fuel Pump 1

1/4-20 Bolts SS 2

1/4'' Washers SS 4

1/4-20 Locking Nuts SS 2

Fuel Fitting Assy. 2

Insulated Clamps A/R

Page 33: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

31

Installing Fuel Pump

Page 34: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

32

eranel Mounting (Detail B).ller on top or under driver panel, install mounting ngly, connect harness and mount to driver panel.

Remote Control Box Mounting (Detail C)ecure the controller harness to prevent rubbing, ontact with sharp, moving or hot components. Allow ilt cab applications. The supplied rubber grommets routing harness through sheet metal holes.roller harness to location chosen to mount remote box.

pter harness to controller harness.

retainer cover from remote control box.

harness through remote control box and insert mating e rear of HMI controller until it locks firmly in etaining screws.

ubber grommet over harness and into cutout at rear of

oller into remote box.

into control box by inserting four plastic retainers into nside rear of box.

on harness to remove any slack and then reinstall ner cover securely to remote control box.

x cover to access four mounting holes.

ounting screws to secure remote box to the cargo box.

over-tighten mounting screws or plastic remote box

op and secure the excess controller harness adequately amps.

Installing HMI ControllIMPORTANT: Always route and secure the harness to prevent rubbing, chafing or making contact with sharp, moving or hot components. Allow excess harness for tilt cab applications. Rubber grommets must be used when routing harness through sheet metal holes.

Harness Routing and Service Loops• All harnesses, except battery and fuel pump are secured to left rear of

condenser. It is important that the service loop between this point and the rear of the control box be maintained. Cables that form this service loop should not be tie banded together or to any other component. Lack of proper service loop will not allow control box to be fully extended for service procedures.

• As an aid to unit service or repair, it is advisable that the harness that goes between the condenser and the evaporators, and in-cab box cable, have extra length at the condenser end, in case unit needs to be lowered from it’s mounting position.

• If clearance between back of condenser and truck frame allows, harness may be secured along the bottom of rear frame member using holes provided for tie bands.

INTERIOR CAB DIN MOUNTINGChoose an appropriate location for the Controller inside the truck cab.

Internal Driver Panel DIN Mounting (Detail A).1. Install DIN (ISO 7736) mounting sleeve into driver panel DIN opening.

2. Bend tabs to secure in position.

3. Connect harness and install controller into DIN sleeve.

External Driver P4. To install contro

brackets accordi

(OPTIONAL) HMI NOTE: Route and schafing or making cexcess harness for tmust be used when 5. Route HMI cont

6. Attach HMI ada

7. Remove harness

8. Route controllerconnector into thposition. Install r

• Install split rcontrol box.

9. Insert HMI contr

• Secure HMI holes found i

• Lightly pull harness retai

10. Raise remote bo

• Install four m

CAUTION: Do not may be damaged.11. Provide a drip lo

with insulated cl

WARNING: If an electrical power source is connected to the unit, DO NOT turn the unit switch “ON” before installing the controller. Uncontrolled start up of the unit may result and cause personal injury.

Page 35: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

33

ler

m HMI controller includes an adapter harness h to the Standard HMI harness connector end.

Installing the HMI Control

NOTE: Premiu422550 to attac

Page 36: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

34

tion)

truck in a safe and secure location using the 5/ardware supplied in installation kit.

ce with hold down bracket and rod.

et and route cables into box.

cables to length and install the supplied terminals cables.

ive cable to negative terminal of battery.

the Positive cable to the battery yet.

strip wire ends of both the 2 wire and in-line fuse

tubing onto one wire and position it away from

plice connector, securely crimp and solder two

ink tubing over connection and then apply heat.

positive cable or 2 wire at this time. They will be ter step.

ill also be installed after unit installation is com-

Installing the Battery Box (Op

Important InformationIMPORTANT: See Safety Precautions - “Battery Installation and Cable Routing” on page 9 for additional information.

NOTE: Thermo King units are designed for one 12 volt, group 31 battery. The battery must be suitable for deep cycling, heavy duty and rated with a minimum of 95 amp/hr.

Supplied Components

Procedures1. Install battery box to

8-11 stainless steel h

2. Secure battery in pla

3. Install rubber gromm

• Cut both battery securely onto the

• Attach the negat

• DO NOT attach

4. Cut 2 wire to length,holder wire.

• Slid heat shrink connection.

• Using supplied swires together.

• Position heat shr

• DO NOT attachconnected at a la

5. Battery box cover wpleted.

WARNING: Improperly installed battery could result in a fire or explosion! A Thermo King approved battery must be installed and properly secured to the battery tray.

WARNING: Improperly installed battery cables could result in fire or explosion! Battery cables must be installed, routed and secured properly to prevent them from rubbing, chaffing or making contact with hot, sharp or rotating components.

Description Qty.

Battery Box 1

5/8-11 Bolts SS 4

5/8'' Washers SS 8

5/8-11 Locking nuts SS 4

Battery Terminal Positive 1

Battery Terminal Negative 1

Fuse Holder and 60 Amp Fuse 1

Splice Connector 1

Heat Shrink Tubing 3.00''

Page 37: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

35

tion)

Installing the Battery Box (Op
Page 38: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

36

D A/P

ng stud applications, install mounting studs, flat g nuts (Detail II).

ng bolt applications, install mounting bolts, d flat washers (Detail III).

st be used if ceiling is not flat, or if foam exists plate and truck liner (Detail II and Detail III).

ealing strips and rubber edging before installing

s to 81 N•m (60 ft-lb).

Installing UTSE Evaporator - NA

NOTE: Ceiling must be flat and mounting locations correct for proper evaporator installation and operation.

NOTE: Thermo King recommends installing the evaporator with 8 mm (5/16 in.) bolts or studs.

1. From inside the truck box, locate center line (CL) and mark its location on to truck box ceiling.

2. Measuring from the center line, locate and identify the five mounting locations.

3. At each location, drill appropriate size holes into ceiling support structure and use a tap and die to thread each hole with same pitch thread as mounting bolts or mounting studs.

4. Foam insulation must be removed from the mounting area on ceiling.

• For ceiling mounting stud applications, weld a nut (same thread as stud) onto a 1-3/4 in. hole saw and turn the nut onto the mounting stud using a socket wrench (Detail I).

• For ceiling mounting bolt applications, weld a bolt (same thread as tapped hole) onto a 1-3/4 in. hole saw and turn into the tapped hole using a socket wrench (Detail I).

5. Install the evaporator:

• For ceiling mountiwashers and lockin

• For ceiling mountilocking washers an

6. Aluminum spacers mubetween the mounting

7. Install supplied foam sthe evaporator.

Torque all mounting bolt

Page 39: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

37

- NAD A/P

A. 749.3 mm (29.50 in.)

B. 1498.6 mm (59.00 in.)

C. 256.4 mm (10.09 in.)

Installing the UTSE Evaporator

Page 40: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

38

rators

nstallationator cover to access mounting holes.

tion kit provides both metric and imperial nuts and e to use correct ones for your application.

Installations studs into the ceiling. Install the aluminum spacers tuds and raise evaporator into position. Loosely secure mounting studs with flat washers and locking nuts. not tighten the mounting hardware at this time.

Installationsr into position. Install aluminum spacers, mounting ers and flat washers and loosely secure evaporator to ail III). Do not tighten the mounting hardware at this

aporator. Torque each evaporator’s mounting hardware t-lb).

lled evaporator will slope slightly toward the drain or water drainage (Detail IV).

nal washers are included in kit to help assist sloping rds the drain.

Installing S-3 + S-3 Evapo

Ceiling PreparationIMPORTANT: Ceiling must be flat and mounting locations correct for proper S-3 evaporator installation. Foam insulation in ceiling must be removed from evaporator mounting area and aluminum spacers must be installed between evaporator mounting plate and truck/trailer ceiling.

• For ceiling mounting stud applications, weld a nut (same thread as stud) onto a 44.45 mm (1.75 in.) hole saw and turn nut onto mounting stud using a socket wrench (Detail I).

• For ceiling mounting bolt applications, weld a bolt (same thread as tapped hole) onto a 44.45 mm (1.75 in.) hole saw and turn into tapped mounting hole using a socket wrench (Detail I).

• Alternative method is to remove mounting studs or bolts and use a hole saw with a standard pilot drill small enough to run up into threaded hole without damaging the threads. Reinstall mounting studs or bolts.

Mounting Stud or Bolt RequirementsMounting studs or bolts used to attach evaporator(s) to ceiling must be 10.0 mm, (0.50 in., Grade 5, U.S. applications only), medium carbon steel, 120000 PSI tensile strength, cadmium plate and dichromate finish. Studs to extend below ceiling 38.0 mm (1.50 in.) to 50.1 mm (2.00 in.)

Evaporator I1. Remove evapor

NOTE: Installawashers. Be sur

Mounting Stud2. Install mounting

onto mounting sevaporator onto(Detail II). Do

Mounting Bolt3. Raise evaporato

bolts, lock washthe ceiling. (Dettime.

4. Install second evto 81 N•m (60 f

5. A properly instatubes to allow f

NOTE: Two additiothe evaporator towa

Page 41: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

39

ators

Installing S-3 + S-3 Evapor
Page 42: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

40

) holding charge of Nitrogen.

ing charge of Nitrogen. This

isture from entering the

before completing the ondensing unit holding nes, leak testing the system,

STOP

CautionThermo King UT-1280 condensing units are shipped with a 35-69 kPa (5-10 psiThis holding charge may be safely vented into the atmosphere.

Thermo King remote evaporators are shipped with a 35-69 kPa (5-10 psi) holdholding charge may be safely vented into the atmosphere.

IMPORTANT: Do not release the holding charge until necessary to prevent mosystem.

SEVERE COMPRESSOR DAMAGE will result from operating the engine/motorsystem installation which includes: installing the components, releasing the ccharge, releasing the remote unit holding charge, soldering the refrigeration lievacuation and clean-up, and charging the system.

Page 43: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

41

BLANK PAGE

Page 44: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

42

ubing Best Practice

ng Best Practiceends the use of bulk rolled refrigeration tubing

educe fittings and solder joints where applicable

(supplied in the installation kit) to all refrigerant assembly.

nitrogen or another inert gas be used to purge the g. This prevents oxidation and formation of scale

and remove internal components from check g to prevent damage.

from condenser can be routed either outside or epending on the particular installation and

uld be fabricated to prevent damage to the nd electrical wires and installed at the completion

lators used on bottles of nitrogen gas must be ef valves. The pressure in a bottle of nitrogen igh. It is high enough to cause components of ms to explode if the regulator malfunctions or is lief valve provides a safe outlet in case the e exceeds the relief valve limit.

Removing Holding Charge and Refrigerant T

Removing Holding Charge

UT Host Unit1. Slowly remove the ORS caps to release the Nitrogen holding charge.

Remote Evaporator(s)2. Slowly remove caps to release Nitrogen holding charge.

HG = Hot Gas S = Suction L= Liquid

Refrigerant Tubi• Thermo King recomm

and tube benders to r(Detail I).

• Apply refrigerant oil tube O-rings prior to

• It is also required thattubes before solderininside tubes.

• Always disassemble valves before solderin

• Refrigeration tubing inside the truck box dapplication.

• Protective covers shorefrigeration tubing aof the installation.

CAUTION: Remove holding charge from host unit and remote evaporators before proceeding to prevent personal injury!

CAUTION: Thermo King UT -1280 condenser units are shipped with a 35-69 kPa (5-10 psi) holding charge of Nitrogen. This holding charge may be vented into the atmosphere.

CAUTION: Thermo King S-2 and S-3 remote evaporators are shipped with a 35-69 kPa (5-10 psi) holding charge of Nitrogen. This holding charge may be vented to the atmosphere.

WARNING: Reguequipped with religas is extremely hrefrigeration systeset wrong. The reregulated pressur

Page 45: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

43

ubing Best Practice

Removing Holding Charge and Refrigerant T
Page 46: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

44

SE Evaporator

ly refrigerant oil (supplied in the installation kit) to O-rings prior to assembly.

in. suction tube from the evaporator to the condenser the provided flanges and O-rings (Detail II and III) to on tube to the evaporator and the condenser.

. hot gas tube from the evaporator to the condenser. tube with ORS fittings (Detail II and III).

. liquid tube from the evaporator to the filter drier tube with ORS fittings (Detail II and III).

with provided clamps (Detail IV).

ng with caulk to prevent air and water leakage.

s should be fabricated to prevent damage to the ing and electrical wires and installed at the completion n.

Connecting Refrigeration Tubing–UT

NOTE: Thermo King recommends the use of bulk rolled refrigeration tubing and tube benders to reduce fittings and solder joints where applicable (Detail I). It is also required that nitrogen or another inert gas be used to purge the tubes before soldering. This prevents oxidation and formation of scale inside tubes.

The refrigeration tubing can be routed either outside (as shown) or inside the truck box depending on the particular installation and application.

HG = Hot Gas S = Suction L= Liquid

IMPORTANT: Appall refrigerant tube

1. Fabricate a 1-3/8(Detail II). Use connect the sucti

2. Fabricate a 1/2 inUse the provided

3. Fabricate a 1/2 inUse the provided

4. Secure all tubing

5. Seal around tubi

6. Protective coverrefrigeration tubof the installatio

CAUTION: Remove holding charge from host unit and remote evaporators before proceeding to prevent personal injury!

WARNING: Regulators used on bottles of nitrogen gas must be equipped with relief valves. The pressure in a bottle of nitrogen gas is extremely high. It is high enough to cause components of refrigeration systems to explode if the regulator malfunctions or is set wrong. The relief valve provides a safe outlet in case the regulated pressure exceeds the relief valve limit.

Page 47: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

45

E Evaporator

Connecting Refrigeration Tubing – UTS
Page 48: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

46

3 Evaporators

. x 7/8 in. tee onto the S-3 Master g. Attach at 7/8 in. suction tube onto the S-3 tion fitting and connect it to tee assembly

on tube from tee fitting down to condenser and O-ring to connect suction tube to I).

1/2 in. tee onto S-3 Master evaporator’s hot . hot gas tube onto the S-3 Support g and connect it to tee assembly (Detail II).

s tube from tee fitting down to condenser S fittings to connect hot gas tube to

3/8 in. tee onto the S-3 Master evaporator’s in. liquid tube onto the S-3 Support and connect it to the tee assembly. (Detail

ube from the tee fitting to filter drier. Use the connect liquid tube to drier (Detail III).

vided clamps (Detail IV).

aulk to prevent air and water leakage.

e fabricated to prevent damage to lectrical wires and installed at completion of

Connecting Refrigeration Tubing–S-3 + S-

NOTE: Thermo King recommends the use of bulk rolled refrigeration tubing and tube benders to reduce fittings and solder joints where applicable (Detail I). It is also required that nitrogen or another inert gas be used to purge the tubes before soldering. This prevents oxidation and formation of scale inside tubes.

The refrigeration tubing can be routed either outside (as shown) or inside the truck box depending on the particular installation and application.

HG = Hot Gas S = Suction L = Liquid

1. Install a 1-3/8 in. x 7/8 inevaporator’s suction fittinSupport evaporator’s suc(Detail II).

2. Fabricate a 1-3/8 in. suctiunit. Use provided flangecondenser unit (Detail II

3. Install a 1/2 in. x 1/2 in. xgas fitting. Attach a 1/2 inevaporator’s hot gas fittin

4. Fabricate a 1/2 in. hot gaunit. Use the provided ORcondenser (Detail III).

5. Install a 1/2 in. x 3/8in. xliquid fitting. Attach a 3/8evaporator’s liquid fittingII).

6. Fabricate a 1/2 in. liquid tprovided ORS fittings to

7. Secure all tubing with pro

8. Seal around tubing with c

9. Protective covers should brefrigeration tubing and einstallation.

CAUTION: Remove the holding charge from the host unit and remote evaporators before proceeding to prevent personal injury.

WARNING: Regulators used on bottles of nitrogen gas must be equipped with relief valves. The pressure in a bottle of nitrogen gas is extremely high. It is high enough to cause components of refrigeration systems to explode if the regulator malfunctions or is set wrong. The relief valve provides a safe outlet in case the regulated pressure exceeds the relief valve limit

Page 49: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

47

S-3 Evaporators

Connecting Refrigeration Tubing S-3 +

Support

Master

Page 50: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

48

th of resistance wire into drain hose.

NOT CUT THE RESISTANCE WIRES!

e to evaporator drain outlet and secure with supplied

e to outside of truck box wall with supplied clamps

n hoses with caulk to prevent air and water leakage.

Installing Drain Hoses

IMPORTANT: For proper drainage the drain hose must slope down continuously from the remote evaporators to the wall drains with no kinks or droop.

Thermo King recommends routing each individual drain hose directly out of the truck box to allow faster water drainage.

1. Insert entire leng

IMPORTANT: DO

2. Attach drain hoshose clamps.

3. Secure drain hosand screws.

4. Seal around drai

DANGER: Never bundle resistance wires together as the amount of heat produced could result in a fire!

Page 51: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

49

Installing Drain Hoses

Page 52: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

50

vaporator

esses to Evaporator

- Connect the (3) fan harnesses to the mating 2-Pin ndenser and route harnesses to evaporator.

length and re-terminate FM wire ends with fork CH wire ends with ring terminals supplied in it.

FM wire to each FM terminal block connection

H wires to the ground stud (Detail I).

- Connect 8-Pin sensor harness to the mating denser and route harness to evaporator.

r harness connectors to mating connectors on the etail II).

Harness, attach the DH wire to the single terminal that has 2 defrost heater (DH) wires.

ensor Harness with tie bands using provided holes aporator (Details I and II).

Electrical Connections–UTSE E

NOTE: When routing harness wires from the condenser unit, allow a service loop, (in case the unit needs to be lowered from it’s mounting position), then route harness wires to evaporators.

Connecting Harn

1. Fan Harnesses connectors on co

• Cut wires to terminals andinstallation k

• Connect each(Detail I).

• Attach the C

2. Sensor Harnessconnector on con

• Attach sensoevaporator (D

3. From the Sensorblock connection

4. Secure Fan and Salong base of ev

CAUTION: All electrical wires must be properly routed and secured to prevent rubbing, chafing, or making contact with sharp, moving or hot components

CAUTION: All electrical connections must be clean and tightly secured to prevent damage to equipment.

Page 53: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

51

aporator

Electrical Connections–UTSE Ev
Page 54: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

52

Evaporators

connect Harness to Evaporators

ect harness wires from SUPPORT evaporator to orator terminal block.

TER evaporator, connect each FM wire to each FM k connection and tighten screws securely (Detail I).

H wire to the ground stud securely (Detail I).

wire from the SUPPORT evaporator to the DH onnection on MASTER evaporator.

is no DH wire, one will need to be added.

fabricate a 14 gauge wire to go from the terminal MASTER evaporator to the terminal block of the vaporator.

e fork terminals onto both ends of the wire.

ire onto the DH terminal block connection of each etail I and III).

adequately with tie bands.

Electrical Connections–S-3 + S-3

NOTE: When routing harness wires from the condenser unit, allow a service loop, (in case the unit needs to be lowered from it’s mounting position), then route harness wires to evaporators.

Connecting Harnesses to Master Evaporator

NOTE: Do not remove “Master” and “Support” nameplates until the installation is complete.

1. Fan Harnesses - Connect the (3) fan harnesses to the mating 2-Pin connectors on condenser and route harnesses to MASTER evaporator.

• Cut wires to length and re-terminate FM wire ends with fork terminals and CH wire ends with ring terminals supplied in installation kit.

• Connect each FM wire to each FM terminal block connection (Detail I).

• Attach the three CH wires to the ground stud (Detail I).

2. Sensor Harness - Connect 8-Pin sensor harness to the mating connector on condenser and route harness to MASTER evaporator.

• Attach sensor harness connectors to mating connectors on the evaporator (Detail II).

Connecting Inter

3. Route interconnMASTER evap

• On the MASterminal bloc

• Attach the C

4. Connect the DHterminal block c

NOTE: If there

• Measure andblock of the SUPPORT e

• Install #8 blu

• Attach the wevaporator (D

5. Secure all wiring

CAUTION: All electrical wires must be properly routed and secured to prevent rubbing, chafing, or making contact with sharp, moving or hot components.

CAUTION: All electrical connections must be clean and tightly secured to prevent damage to equipment.

Page 55: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

53

vaporators

Electrical Connections–S-3 + S-3 E
Page 56: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

54

Installation Guide

or 90 degree connector to evaporator drain tube and n firmly to engage the O-ring (Detail VI).

ire through interconnecting drain tube as far as e sure it is not bunched up (Detail VII).

tance wire into the other drain Tee connector and as III).

t no time should resistance wires from one side of the p the resistance wires from the other side.

ecting drain tube to opposite Tee connector by pushing r on firmly to engage the O-ring (Detail IX).

onnector to the evaporator drain tube by pushing the firmly to engage O-ring (Detail X).

evaporator drain tube over to wall drain. Insert nto wall drain and pull it as far down wall drain as XI).

nly one resistance wire should be installed in the n tube. Only the resistance wire from the drain tube ll should be installed in the trailer drain tube.

Evaporator Drain Hose Resistance Wire

IMPORTANT: The following information is provided as a guide to help ensure the proper routing of the drain hose resistance wires. You should supplement this guide with whatever other documentation is required for your facility.

Drain Hose Resistance Wire Installation Guide

1. Remove resistance wire from evaporator drain tube and pull wire out straight.

2. Locate evaporator defrost drain furthest from wall (i.e. in the middle of the cargo box), and measure 33.00 in. (838 mm) of resistance wire from drain pan outlet (Detail I). 20.00 in. (508 mm) for S-2 evaporators.

3. Bend resistance wire at this point and double it over (Detail II).

4. After doubling the resistance wire over (Step #3) take excess wire and insert it back into evaporator drain tube (Detail III).

5. Insert doubled over end of resistance wire into drain Tee or 90 degree connector (Detail IV) and then into crossover drain tube (Detail V).

NOTE: Use of either white or blue drain tubes is acceptable when interconnecting multiple evaporators.

6. Attach drain Teepush connector o

7. Pull resistance wpossible and mak

8. Insert other resisshown (Detail V

IMPORTANT: Adrain pan overla

9. Attach interconnthe Tee connecto

10. Attach the Tee cTee connector on

11. Attach and routeresistance wire ipossible (Detail

IMPORTANT: Owall defrost draiclosest to the wa

Page 57: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

55

Installation Guide

Evaporator Drain Hose Resistance Wire
Page 58: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

56

tions made during installation for leaks using an etector.

pressure to repair leaks. System must be vented while leak joints. Pressurize system again after a leak has

und, recover test gas to 0 psi.

System Leak Check

1. Connect leak test gas supply (R404A) to center hose of gauge manifold.

2. Attach gauge manifold hoses to suction and discharge service valves.

3. Open suction and discharge valves and pressurize system with leak test gas. If desired system pressure may be boosted using nitrogen gas.

4. Check all connecelectronic leak d

5. Recover test gasrepairing solder been repaired.

6. If no leaks are fo

Page 59: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

57

System Leak Check

Page 60: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

58

arging

sure hose from spare access port on valve V4 service ant supply. Bottle valve closed.

ice valves.

mp and open valves V1, V2, V3, and V4.

x valve. Refer to Service Bulletin T&T 246.

to 500 microns or lowest achievable level between crons. Split systems with multi-evaporators should be additional hour once 500 microns is reached.

micron level is achieved (500 to 1000 microns plus ti-evaporators), close valve V1 to isolate pump. Turn

on micron gauge after 5 minutes have elapsed. uld not exceed 2000 microns. If vacuum level exceeds er 5 minutes, a leak is present or additional evacuation

is acceptable, start pump and open valve V1 to e rise (5 minutes).

mp running, back seat suction service valve. Observe d continue to operate vacuum pump until an n level is achieved.

nd stop the pump. Observe micron gauge to confirm ins in deep vacuum. Close valve V4. Unit is now

E. Two Stage Vacuum Pump

F. To AC Power

G. Micron Gauge

H. Thermistor

System Evacuation and Ch

NOTE: The use of Thermo King Evacuation Station P/N 204-725 is required. Set up and test evacuative equipment prior to performing this operation. The UT-1280 does not have a discharge service valve, therefore it is recommended that low-loss fittings be used on any gauge sets and on evacuation station line connected to discharge line.

System Evacuation and Charging Procedures

The overall procedure is:

• Evacuate system using a Thermo King Evacuation Station.

• Place a partial charge in the system using the evacuation station.

• Remove station and place a gauge set on the UT-1280.

• Complete charging of system by simulating a 0 degree F box and a 100 degree F ambient and utilizing the built in liquid line sight glass.

System Evacuation1. Prepare unit for evacuation. Recover any refrigerant to 0 psi

(regulations may require a recovery machine to pull system pressure lower than 0 psi).

2. Before connecting refrigerant hoses to unit, close valves V1, V2, and V4.

3. Back seat suction and receiver tank service valves.

4. Attach evacuation hoses to SSV and RTDV and to the discharge port of the compressor (check condition of hose seals).

5. Install a low preshose to a refriger

6. Mid-seat all serv

7. Start vacuum pu

8. Energize Therma

9. Evacuate system500 and 1000 mievacuated for an

10. When acceptableone hour for mulpump OFF.

11. Observe readingVacuum rise sho2000 microns afttime is required.

12. If vacuum level evacuate pressur

13. With vacuum pumicron gauge anacceptable micro

14. Close valve V1 athat system remaready to charge.

CAUTION: Do not evacuate the unit until it is leak free. Units with less than full refrigerant charge should be leak checked and all leaks must be repaired.

A. V-4

B. V-3

C. V-2

D. V-1

Page 61: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

59

rging

System Evacuation and Cha
Page 62: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

60

ingthermostat to COOL. Maintain a 0 degree F/ 00 degree F/37degree C ambient. Suction psig and discharge pressure to 290-310 psig

acked). Cover the condenser coil if needed. and slowly open gauge manifold hand valve t to flow into suction service valve. Control essure increases approximately 138 kPa (20

bubbles appear in the liquid line sight glass.nt into the system by closing the low-side ve.in COOL for 10 minutes and check for sight glass. If bubbles appear, add liquid rge in the system will be about 14 lbs. / 6.6 Kg

Hoses the discharge gauge line, remove this line

.vice valve. Run unit until a 3 to 5 psig (21 to d on the suction gauge. Stop the unit. deep vacuum as this may damage the scroll

rom the suction service valve and cap the

valve and cap the valve stem.ctional check out. Stage Vacuum Pump H. Thermistor

AC Power I. Correct Refrigerant Levelron Gauge

System Evacuation and ChargInitial System ChargeThe UT-1280 utilizes a liquid line sight glass. This is used in order to attain an optimum charge given varied installations (suction/liquid line lengths vary).

DO NOT use the receive tank sight glass as an indicator of the required refrigerant level in the system.NOTE: Before charging system, make sure refrigerant lines from the gauge manifold to refrigerant supply bottle have been evacuated or purged.1. Suction service valve is back seated and receiver outlet valve is open.

Refrigerant will be added to the high side of the unit with the unit OFF.

2. Set refrigerant supply bottle for liquid. Open gauge manifold hand valve and add a partial charge of 4.1 kg (9.0 lb.) of R-404A refrigerant.

NOTE: Do not add more than this. Remainder of charge will be added through suction service valve while unit is running.3. After the liquid refrigerant is added, close gauge manifold hand valve.

4. Remove hose from discharge line. A low loss fitting on this hose will prevent excessive loss of refrigerant.

5. Back seat (close) the receiver outlet valve.

6. Front seat the suction service valve (SSV). Run the unit until a 3 to 5 psig (21 to 35 kPa) reading is obtained on the suction gauge. Stop the unit. Do not run the unit into a deep vacuum as it may damage the scroll compressor.

7. Back seat (close) suction service valve.

8. Remove the evacuation station hoses.

9. Cap service valve ports, backseat (close) suction service valve (SSV).

Final System Charge 1. Install a gauge manifold set on the suction service valve and the

discharge port of the scroll compressor.

2. Start the unit and set the -17.8 degree C box and 1pressure should be 12-20(suction service valve cr

3. Observe suction pressureto allow liquid refrigeranliquid flow so suction prpsi).

4. Add refrigerant until no 5. Stop the flow of refrigera

gauge manifold hand val6. Continue to operate unit

bubbles in the liquid linerefrigerant. The total chaof refrigerant.

Removal of Refrigerant 1. With a low loss fitting on

from the unit.2. Run unit in COOL mode3. Front seat the suction ser

35 kPa reading is obtaineDO NOT run the unit into acompressor. 4. Remove the gauge line f

service port.5. Backseat suction service6. Unit is now ready for funA. V-4 E. TwoB. V-3 F. To C. V-2 G. MicD. V-1

Page 63: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

61

rging

System Evacuation and Cha
Page 64: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

62

Covers

ersCOVER into support channel of evaporator. ws.

OVER into support lip of front cover.ws.

Installing the S-3 Evaporator

Installing Cap PlugsCap plugs are provided to plug the two evaporator mounting access holes located directly above the drain pan. These plugs must be installed to prevent water in the drain pan from spilling out of these holes and into the cargo area.

1. Install supplied cap plugs - 2 per evaporator.

Installing Cov2. Install FRONT

Secure with scre

3. Install BACK CSecure with scre

Page 65: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

63

overs

Installing the S-3 Evaporator C
Page 66: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

64

ing tubing.

ose or missing bolts and hardware on remote

were installed in access mounting holes.

llation of drain tubes, drain kazoos and drain

uted refrigerant lines wiring harnesses for Check for properly routed harnesses for remote

llation of remote evaporator guards if

wiring plugs in the host evaporator.

tions, and terminals in the remote

ulk head(s) for proper fit if equipped.

START ONLY THE HOST UNIT)

ressure, coolant temperature, oil, fuel, or

e.

ure the unit functions in the correct modes and e working.

with thermostat set point at 32 F (0 C) and run

UNIT CHECK LISTUNIT CHECK LIST

Visually inspect the unit for transit and handling damage. File claim with delivery carrier.Install the unit as outlined in the Thermo King Installation Manual.

If the unit has a separate fuel tank add 10 gallons of fuel to the tank.

BEFORE STARTING THE UNIT

Check battery and battery cable installation.

Inspect fuel line routing checking for rubbing, chaffing or laying on hot surfaces.

Visually inspect the unit for the following: Loose or improperly fitting bolts, brackets, hardware, hose connections and hose routing.

Inspect all wiring connections and routing.

Check defrost drain hoses and kazoos.

Check unit mounting hardware for tightness.

Check compressor and engine mounts.

Check compressor clutch if equipped.

Install refrigeration gauge manifold. (Multi-Temp units only)

Check engine oil level.

Check condenser and evaporator section for cleanliness and signs of refrigerant leaks.

Check front bulkhead and air chute if equipped.

Check damper door, bushings and springs if equipped.

MULTI-TEMP UNITS (REMOTE EVAPORATORS)

Check evaporator(s) sections for cleanliness.

Leak test interconnect

Check for damage, loevaporator(s).

Check that cap plugs

Check for proper instatube heater wires.Check for properly roremote evaporator(s). controller.Check for proper instaequipped.Check remote harness

Check wiring, connecevaporator(s).Check compartment b

START AND RUN UNIT (ON MULTI-TEMP UNITS

Check for proper oil pcoolant leaks.

Check alternator charg

Cycle the unit and ensthe mode indicators ar

Set for continuous runthe unit to 32 F (0 C).

Page 67: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

65

ed)partment bulk head(s) if equipped.

ntinuous run. Continue to run the unit with the back ating between high speed cool and heat until at

hours preferred) are shown on the engine run time ure complete break in of the engine, time for the oving parts to take out the initial tension and

Y OPERATIONAL CHECKS

l contacts and connections by connecting to AC g.

electric motor rotation.

and check for correct modes of operation.

available to test AC.

nits leak test interconnecting tubing.

st all belt tensions using TK belt gauge 204-427.

l, coolant, refrigerant and exhaust leaks.

and coolant level.

for loosened hardware and fittings.

all skin, door and panels for correct alignment and

missioning registration process.

UNIT CHECK LIST (continuObserve and record refrigerant operating pressures in relation to ambient and box temperatures.

Verify the readings above are correct for the conditions.

When box reaches 32 F (0 C) check calibration of thermostat, thermometer and data logger.

Run unit for 30 minutes at 32 F (0 C). During this period check for correct cycling.

Reset thermostat to 50 F (10 C).

Check throttling valve while in the heat cycle.

Check operation of Modulation system if equipped.

For Single Temp units perform a controlled check of the refrigerant level. For Multi-temps check the charge per multi-temp unit procedures.

MULTI-TEMP UNITS

Install the compartment bulk head(s) if equipped.

Check for correct rotation of remote evaporator fans.

Check for correct cycling and operation of remote evaporator fans.

ALL UNITS

Initiate and check defrost operation and termination.Check operation and adjustment of damper door and remote fans. Each zone on multi-temps must be checked for proper operation.

Set the unit for Cycle Sentry Operation.

Check for proper operation of all door switches.

Remove the com

Set the unit for codoors open, alternleast 6 hours (10 hour meter to ensbelts and other madjustment.

ELECTRIC STANDB

Test AC electricapower and runnin

Check for correct

Cycle thermostat

Power source not

STOP UNIT

On Multi-temp u

Check and readju

Check for oil, fue

Check engine oil

Check entire unit

Check and adjustoperation.

Complete the com

Release unit.

Page 68: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3
Page 69: Installation Manual · 2020. 8. 13. · 4 Introduction This installation manual was written to assist with the installation of a Thermo King UT-1280 condensing unit and UTSE or S-3

Thermo King has a policy of coninuous product and data improvements and reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

Thermo King – by Trane Technologies (NYSE: TT), a global climate innovator – is a worldwide leader in sustainable transport temperature control solutions. Thermo King has been providing transport temperature control solutions for a variety of applications, including trailers, truck bodies, buses, air, shipboard containers and railway cars since 1938. For more information, visit www.thermoking.com or www.tranetechnologies.com

©2020 Trane Technologies

TK 56374-1-IM Jan 2017

Installation Manual

Truck EditionUT-1280 Undermount Systems

January 2017

Revision 0

TK-56374-1-IM