# 45466K003 Page 1 INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, G1D93BU, CG90CB, & CG90UB High Efficiency 90+ Condensing Gas Furnace Manufactured By A.A.C. A Lennox International Company 421 Monroe Street Bellevue, OH 44811 The installation of the furnace, wiring, warm air ducts, venting, etc. must conform to the requirements of the National Fire Protection Association; the National Fuel Gas Code, ANSI Z223.1/NFPA No. 54 (latest edition) and the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States; CSA B149.1 (latest edition) Natural Gas and Propane Installation Codes and the Canadian Electrical Code Part 1, CSA 22.1 (latest edition) in Canada; and any state or provincial laws, local ordinances (including plumbing or wastewater codes), or local gas utility requirements. Local authorities having jurisdiction should be con- sulted before installation is made. Such applicable regulations or requirements take precedence over the general instructions in this manual. IMPORTANT Do not store combustible materials, including gasoline and other flammable vapors and liquids, near the furnace, vent pipe, or warm air ducts. The homeowner should be cau- tioned that the furnace area must not be used as a broom closet or for any other storage purposes. Such uses may result in actions that could cause property damage, personal injury, or death. WARNING This furnace is not approved for installation in a mobile home. Do not install this furnace in a mobile home. Installation in a mobile home could result in actions that could cause prop- erty damage, personal injury, or death. WARNING Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional informa- tion, consult a qualified installer, service agency, or the gas supplier. WARNING TABLE OF CONTENTS SAFETY ................................................. 2 INSTALLATION ....................................... 3 START-UP ............................................ 19 OPERATION ........................................ 20 MAINTENANCE ................................... 23 REPAIR PARTS .................................... 24 CONTROL SYSTEM DIAGNOSTICS .. 25 WIRING DIAGRAMS ............................ 26 ® ®

INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

Embed Size (px)

Citation preview

Page 1: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003 Page 1

INSTALLATION INSTRUCTIONSG1D91BU, G1D93BC, G1D93BU, CG90CB, & CG90UB

High Efficiency 90+ Condensing Gas Furnace

Manufactured ByA.A.C.

A Lennox International Company421 Monroe Street

Bellevue, OH 44811

The installation of the furnace, wiring, warm air ducts, venting, etc. must conform to the requirements of theNational Fire Protection Association; the National Fuel Gas Code, ANSI Z223.1/NFPA No. 54 (latest edition)and the National Electrical Code, ANSI/NFPA No. 70 (latest edition) in the United States; CSA B149.1(latest edition) Natural Gas and Propane Installation Codes and the Canadian Electrical Code Part 1, CSA22.1 (latest edition) in Canada; and any state or provincial laws, local ordinances (including plumbing orwastewater codes), or local gas utility requirements. Local authorities having jurisdiction should be con-sulted before installation is made. Such applicable regulations or requirements take precedence over thegeneral instructions in this manual.

IMPORTANT

Do not store combustible materials, includinggasoline and other flammable vapors andliquids, near the furnace, vent pipe, or warmair ducts. The homeowner should be cau-tioned that the furnace area must not beused as a broom closet or for any otherstorage purposes. Such uses may result inactions that could cause property damage,personal injury, or death.

WARNING

This furnace is not approved for installation ina mobile home. Do not install this furnace in amobile home. Installation in a mobile homecould result in actions that could cause prop-erty damage, personal injury, or death.

WARNING

Improper installation, adjustment, alteration, service, or maintenance can causeinjury or property damage. Refer to this manual. For assistance or additional informa-tion, consult a qualified installer, service agency, or the gas supplier.

WARNING

TABLE OF CONTENTS

SAFETY ................................................. 2

INSTALLATION....................................... 3

START-UP ............................................ 19

OPERATION ........................................ 20

MAINTENANCE ................................... 23

REPAIR PARTS .................................... 24

CONTROL SYSTEM DIAGNOSTICS .. 25

WIRING DIAGRAMS ............................ 26

��

Page 2: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003Page 2

SAFETY

The following is a list of safety rules and precautions thatmust be followed when installing this furnace.

1. Use only with the type of gas approved for thisfurnace. Refer to the furnace rating plate.

2. Install this furnace only in a location and position asspecified in the Location section on page 3 of theseinstructions.

3. Provide adequate combustion and ventilation air to thefurnace space as specified in the Combustion andVentilation Air section on page 4 of these instructions.

4. Adequate clearance must be provided around thevent-air intake terminals as specified in the Ventingsection beginning on page 5 of these instructions.

5. Combustion products must be discharged outdoors.Connect this furnace to an approved vent system only,as specified in the Venting section beginning on page 5of these instructions.

6. Never test for gas leaks with an open flame. Use acommercially available soap solution made specifi-cally for the detection of leaks to check all connec-tions, as specified in Gas Supply and Pipingbeginning on page 15 of these instructions.

7. Always install furnace to operate within the furnace’sintended temperature-rise range with a duct systemwhich has an external static pressure within theallowable range, as specified in Temperature Riseon page 21 of these instructions. See furnace ratingplate.

8. When a furnace is installed so that the supply ductscarry air circulated by the furnace to areas outside thespace containing the furnace, the return air shall alsobe handled by duct(s) sealed to the furnace casingand terminating outside the space containing thefurnace. See Circulating Air Supply on page 15 ofthese instructions.

9. A gas-fired furnace for installation in a residentialgarage must be installed as specified in the Locationsection on page 3 of these instructions.

10. The furnace is not to be used for temporary heating ofbuildings or structures under construction as specifiedin the Location section on page 3 of these instructions.

In the State of Massachusetts:This product must be installed by a licensedPlumber or Gas Fitter. When flexible connec-tors are used, the maximum length shall notexceed 36". When lever-type gas shutoffs areused, they shall be T-handle type.

WARNING

Page 3: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003 Page 3

INSTALLATION

These instructions must be placed on or near thefurnace in a conspicuous place.

The furnace design is certified by CSA International as aCategory IV furnace in compliance with the latest editionof American National Standard Z21.47/CSA Standard 2.3for Gas-Fired Central Furnaces, for operation with naturalgas or propane. Consult the rating plate on the furnace forgas type before installing.

The maximum hourly heat loss of space shall be calcu-lated in accordance with the procedure described in thecurrent manuals of Air Conditioning Contractors ofAmerica, or by any other recognized method which issuitable for local conditions, provided the results obtainedare in substantial agreement with, and not less than, thoseobtained using the procedure described in the manuals.

G1D91BU, G1D93BU, and CG90UB models shall beinstalled only as upflow furnaces. G1D93BC andCG90CB models shall be installed only as counterflow(downflow) furnaces.

Inspection of Shipment

This furnace is shipped in one package, completelyassembled and wired. The thermostat is shipped in aseparate carton when ordered.

Upon receipt of equipment, carefully inspect it for possibleshipping damage. If damage is found, it should be notedon the carrier’s freight bill. Damage claims should be filedwith the carrier immediately. Claims of shortages shouldbe filed with the seller within 5 days.

Location

To provide proper operation and satisfactory performance,care must be taken in choosing the location for this furnace.The atmosphere in which the furnace operates must be freeof contaminants such as chlorides and sulfates.

The furnace must be installed so that electrical compo-nents are protected from water. Unit must be level forproper condensate drainage.

All models are suitable for closet or utility room installation.

The furnace is suitable for installation in buildings con-structed on-site. The furnace should be centralized inrespect to the heat distribution system as much aspracticable. When installed in a utility room, the doorshould be wide enough to allow the largest part of thefurnace to enter, or permit the replacement of anotherappliance, such as a water heater.

A gas-fired furnace for installation in a residential garagemust be installed so the burner(s) and the ignition sourceare located not less than 18" above the floor. The furnaceis to be located or protected to avoid physical damage byvehicles.

If the furnace is to be installed in an attic or otherinsulated space, it must be kept free and clear ofinsulating materials.

Clearances

All servicing and cleaning of the furnace can be performedfrom the front. If installed in a closet or utility room, provide18" clearance in front for service if the door to the room isnot in line with the front of the furnace.

Refer to Table 1 on page 4 for the minimum clearances tocombustibles required for construction and proper unitoperation.

Accessibility clearances must take precedence overfire protection clearances.

Upflow models (G1D91BU, G1D93BU, & CG90UB) may beinstalled on wood flooring but shall not be installed directlyon carpeting, tile, or any other combustible material.

Counterflow models (G1D93BC & CG90CB) are certifiedfor installation on combustible flooring provided a specialbase assembly is used. (Refer to the Duct Connection –

The condensate drain on this furnace isincorporated within the furnace and must beprimed before start-up. The condensatesystem must not be exposed to tempera-tures under 32°F. Use of heat tape is per-missible provided the rate temperature of thetape does not exceed 155°F.

CAUTION

Do not use the furnace as a heater in abuilding under construction. The furnace canbe severely damaged due to the abnormalenvironment caused by construction. Chlo-rides from sources such as paint, stain, orvarnish; tile and counter cements; adhesives;and foam insulation are abundant in a struc-ture under construction and can be highlycorrosive. Low return air temperature cancause condensation in the furnace and otherdamage that can shorten the life of the unit.

CAUTION

Page 4: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003Page 4

Unconfined Space

An unconfined space is defined as “a space whosevolume is more than 50 cubic feet per 1000 BTU per hourof the combined input rating of all appliances installed inthat space.” When a furnace is installed in an unconfinedspace in a building, it can be assumed that the infiltrationwill be sufficient to supply the required air. If the furnace isinstalled in a ventilated attic or crawl space, it is assumedthat the infiltration is sufficient to supply the required air.However, in a building of unusually tight construction,additional outdoor air should be provided.

Confined Space

A confined space is defined as “a space whose volume isless than 50 cubic feet per 1000 BTU per hour of thecombined input rating of all appliances installed in thatspace.”

If the furnace is installed in a confined space within thebuilding and combustion air is taken from a heated space,the combustion air and ventilating air must enter and leavethe space through two permanent openings of equal area.One opening shall be located within 12" of the ceiling andthe other within 12" of the floor, each having a free area of1 square inch per 1000 BTU/HR of total input rating of allappliances within the space and not less than 100 squareinches each.

If the furnace is installed in a space within a building of tightconstruction, makeup air must be supplied from outdoors. Inthis case, one opening shall be within 12" of the ceiling andone opening within 12" of the floor. If combustion ducts arevertical, each opening shall have a free area of 1 squareinch per 4000 BTU/HR of the total input rating of all appli-ances within the enclosure. If horizontal combustion ductsare run, 1 square inch per 2000 BTU/HR is required.

Contaminated Combustion Air

Excessive exposure to contaminated combustion air willresult in safety and performance related problems. Therecommended source of combustion air is outdoor air.However, the use of indoor air in most applications isacceptable if the following guidelines are followed:

1. If the furnace is installed in a confined space, it isrecommended that the necessary combustion air comefrom the outdoors by way of an attic, crawl space, airduct, or direct opening.

2. If indoor combustion air is used, there must be noexposure to the substances listed in item 5.

3. All provisions for indoor combustion air must meet therequirements for combustion air indicated in theNational Fuel Gas Code, ANSI Z223.1/NFPA 54(latest edition), and/or any applicable local codes. In

Adequate provisions for combustion air and ventilation offurnace must be made. Refer to Section 5.3, “Air forCombustion and Ventilation,” of the National Fuel GasCode, ANSI Z223.1/NFPA54 (latest edition), Sections 7.2,7.3, or 7.4 of CSA B149.1 Natural Gas and PropaneInstallation Codes (latest editions), or applicable provi-sions of the local building codes.

Counterflow Models section on page 15 for moreinformation on using the special base assembly.)

When a counterflow unit is installed on a combustiblefloor, 1" clearance must be provided between the supplyduct and the floor.

Combustion and Ventilation Air

Table 1

Minimum Clearances to Combustibles

sediStinU "0

tinUforaeR "0

tinUfotnorF "2

epiPeulF "0

poTmunelP "1

Insufficient combustion air can cause head-aches, nausea, dizziness, or asphyxiation.When considering combustion air require-ments, enough air must also be provided tomeet the needs of all fuel-burning appliancesand exhaust fans.

WARNING

Air openings in the front of the furnace mustbe kept free of obstructions. Any obstructionmay cause improper operation that can resultin a fire hazard or carbon monoxide injury.

WARNING

Page 5: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003 Page 5

Canada, see CSA B149.1, Natural Gas and PropaneInstallation Codes (latest edition).

4. The following types of installation may require outdoorair for combustion, due to chemical exposures:

• Commercial buildings• Buildings with indoor pools• Furnaces installed in laundry rooms• Furnaces installed in hobby or craft rooms• Furnaces installed near chemical storage areas

5. Exposure to the following substances in the combustionair supply may also require outdoor air for combustion:

• Permanent wave solutions• Chlorinated waxes and cleaners• Chlorine-based swimming pool chemicals• Water softening chemicals• Deicing salts or chemicals• Carbon tetrachloride• Halogen-type refrigerants• Cleaning solvents (such as perchloroethylene)• Printing inks, paint removers, varnishes, etc.• Cements and glues• Antistatic fabric softeners for clothes dryers• Masonry acid washing materials• Chlorinated laundry products• Hydrochloric acid

Venting

The high efficiency of this furnace is accomplished by theremoval of both sensible and latent heat from the flue gases.The removal of latent heat results in the condensation ofmoisture in the flue gases. This condensation occurs in thesecondary heat exchanger and in the vent system. There-fore, this furnace requires special venting considerationsand the instructions must be followed to insure properoperation. All venting must be in accordance with the codeshaving jurisdiction in the area and these instructions.

Upflow models G1D91BU, G1D93BU, and CG90UB andcounterflow models G1D93BC and CG90CB can beinstalled as either direct vent or non-direct vent units. Adirect vent (two pipe) installation requires that all the airnecessary for combustion be supplied from outside thedwelling through an air intake pipe. A non-direct vent (onepipe) installation uses air from inside the dwelling forcombustion.

The furnace is shipped with the air inlet pipe terminated tothe top panel for either inside or outside combustion air. Aninlet air restrictor plate (see Figure 1) is supplied with thisfurnace and can be found in the plastic bag containing theseInstallation Instructions and the User’s Information Manual.For installations using inside air for combustion (non-directvent), attach a 90° elbow (not supplied) to the inlet couplerand install the restrictor plate inside the elbow (see Figures8 and 9 on page 11 or Figures 13 and 14 on page 13).

If at any time in the future the installation ofthis furnace is changed to require outsidefresh air for combustion, the inlet air restrictorplate must be removed. Failure to remove theinlet air restrictor could cause improperoperation that can result in a fire hazard orcarbon monoxide injury.

WARNING

Also included in the plastic bag containing the inlet airrestriction plate is a flue pipe screen (see Figure 1). In allinstallations, this screen should be installed at the termi-nation of the flue pipe and is designed to keep objects outof the flue pipe.

For either type of installation (direct or non-direct vent),special venting considerations must be followed. Refer tothe proper section in pages 10 – 13 for the type of furnaceand venting being installed.

The venting system must be supported with mountingstraps to prevent any weight load from being applied to thevent blower. Horizontal vent pipe must be supported every5' and vertical pipe should be supported every 10' toprevent sagging and provide rigid support.

When a furnace is installed as direct vent, provisions forventilation air should follow the same requirements as ifinstalled as non-direct vent. Proper ventilation air isnecessary to maintain furnace component temperatureswithin acceptable limits.

All vents passing through floors, ceilings, and walls mustbe installed in accordance with National Fuel Gas Code,ANSI Z223.1/NFPA 54 (latest edition).

Inlet Air Restrictor Plate

Flue Pipe Screen

The inlet air restrictor platemust be installed in allinstallations using inside airfor combustion (non-directvent).

The flue pipe screenshould be installed at thetermination of the flue pipein all installations.

Figure 1

Page 6: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003Page 6

Category IV Furnace Limitations

This furnace shall not be connected to any Type B, BW, orL vent or vent connector and shall not be connected toany portion of a factory-built or masonry chimney. Thisfurnace is not to be common vented with any otherappliance. The vent pipe must not be connected to achimney flue serving a separate appliance designedto burn solid fuel.

Vent Pipe Size and Length

The vent pipe and air intake pipe (in direct vent installa-tions) should be sized in accordance with the informationfound in the appropriate table in Figure 3. One 90° elbowis equivalent to 5' of pipe. Two 45° elbows are equivalentto one 90° elbow. The minimum length certified for usewith this furnace is 5' and one elbow, not including thevent and air intake terminals.

In the event that the pipe length is in between the lengthslisted in the table, use the next larger length listed. Forexample, if a length of pipe needed to install the furnace is27', use the diameter values for the 30' row in the tables.

In all applications where the flue pipe is run throughan unconditioned space, 1/2" Armaflex or equivalentmust be used over the pipe. In extreme cold climates,3/4" Armaflex is recommended.

Materials

All pipe, fittings, primer, and solvent cement must conformwith American National Standard Institute and the Ameri-can Society for Testing and Materials (ANSI/ASTM)standards. The solvent shall be free flowing and containno lumps, undissolved particles, or any foreign matter thatadversely affects the joint strength or chemical resistanceof the cement. The cement shall show no gelation, stratifi-cation, or separation that cannot be removed by stirring.

Refer to Table 2 for approved piping and fitting materials.

cement is recommended. Metal or plastic strapping may beused for vent pipe hangers.

When making ABS joints, pieces can be prepared with acleaner. When joining ABS to PVC materials, use PVCsolvent cement as specified in ASTM D3138.

Preferred fittings are DWV style or long sweep. Seal all jointsgas tight with appropriate cement. In areas where vent andair intake pipes are exposed to abnormal stress or aresubject to damage, schedule 80 pipe should be used.

Concentric Vent Kit

A concentric vent kit (model ACVK2) is available for usewhen installing this furnace as a direct vent furnace and theair intake and vent pipe are to be run through the same hole,whether horizontally through the wall or vertically through theroof (see Figure 2). Refer to the instructions included withthe concentric vent kit for installation specifics.

Table 2

Piping and Fitting Specifications

The primers and solvents used must also meet ASTMspecifications. PVC primer is specified in ASTM F656. UsePVC solvent as specified in ASTM D2564 and ABS solventcement as specified ASTM D2235. Low temperature solvent

Figure 2

2"NominalPipe Size

3.5"

18" 5"

1"11"

Concentric Vent Kit DimensionsgnittiFdnagnipiPlairetaM

MTSAnoitacificepS

CVP04eludehcS)epiP(

5871D

CVP04eludehcS)epiPeroCralulleC(

198F

CVP04eludehcS)sgnittiF(

6642D

62-RDS)epiP(

1422D

SBA04eludehcS)epiP(

7251D

SBA04eludehcS)sgnittiF(

8642D

CVPC08&04eludehcS)epiP(

144F

VWD-SBAtneV&etsaWniarD

)sgnittiF&epiP(1662D

VWD-CVPtneV&etsaWniarD

)sgnittiF&epiP(5662D

Page 7: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003 Page 7

Horizontal Venting

The vent for this appliance shall not terminate over publicwalkways; or near soffit vents or crawl space vents orother areas where condensate or vapor could create anuisance or hazard or cause property damage; or wherecondensate vapor could cause damage or could bedetrimental to the operation of regulators, relief valves, orother equipment.

See Figures 4 and 5 on pages 8 and 9 for additionalinformation on where the horizontal vent terminal can andcannot terminate.

For direct vent installations, if the vent and air intake pipeare not equal in length and number of elbows, thendetermine the minimum pipe diameter for both the ventand air intake. If the results indicate different diameters,use the larger of the two for both the vent and air intake.Under no circumstances should the vent and airintake pipe size be different in diameter. For installationdetails, refer to the appropriate section in pages 10 – 13for the unit model and type of installation.

Figure 3

Vent Tables(numbers in inches unless specified otherwise)

Minimum Pipe Diameter40,000 – 80,000 BTU/HR Models

NR = Not Recommended

Minimum Pipe Diameter112,000 – 125,000 BTU/HR Models

Minimum Pipe Diameter90,000 – 100,000 BTU/HR Models

epiPtneVhtgneL

).tf(

swoblE°09forebmuN

0 1 2 3 4 5 6 7 8 9

5 5.1 5.1 2 2 2 2 2 2 2 201 5.1 2 2 2 2 2 2 2 2 202 2 2 2 2 2 2 2 2 2 5.203 2 2 2 2 2 2 2 5.2 5.2 5.204 2 2 2 2 2 5.2 5.2 5.2 5.2 5.205 2 2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 306 2 5.2 5.2 5.2 5.2 5.2 5.2 3 3 307 5.2 5.2 5.2 5.2 5.2 3 3 3 3 RN08 5.2 5.2 5.2 3 3 3 3 3 RN RN09 5.2 5.2 3 3 3 3 3 RN RN RN

epiPtneVhtgneL

).tf(

swoblE°09forebmuN

0 1 2 3 4 5 6 7 8 9

5 RN 2 2 2 2 2 2 5.2 5.2 5.201 2 2 2 2 2 2 5.2 5.2 5.2 5.202 2 2 2 2 2 5.2 5.2 5.2 5.2 303 2 2 2 5.2 5.2 5.2 5.2 3 3 304 2 2 5.2 5.2 5.2 3 3 3 3 305 5.2 5.2 5.2 3 3 3 3 3 3 RN06 5.2 3 3 3 3 3 3 RN RN RN07 3 3 3 3 3 RN RN RN RN RN08 3 3 3 RN RN RN RN RN RN RN09 3 3 RN RN RN RN RN RN RN RN

epiPtneVhtgneL

).tf(

swoblE°09forebmuN

0 1 2 3 4 5 6 7 8 9

5 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.201 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 5.2 302 5.2 5.2 5.2 5.2 5.2 5.2 5.2 3 3 RN03 5.2 5.2 5.2 5.2 5.2 3 3 RN RN RN04 5.2 5.2 5.2 5.2 3 RN RN RN RN RN05 5.2 3 3 RN RN RN RN RN RN RN06 3 3 RN RN RN RN RN RN RN RN

Page 8: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003Page 8 Figure 4

Sidewall Vent Terminal Clearances (Direct Vented Furnaces)

1 In accordance with the current CSA B149.1, Natural Gas andPropane Installation Code

2 In accordance with the current ANSI Z2223.1/NFPA 54, NationalFuel Gas Code

† A vent shall not terminate directly above a sidewalk or paveddriveway that is located between two single family dwellings andserves both dwellings.

‡ Permitted only if veranda, porch, deck, or balcony is fully open on aminimum of two sides beneath the floor.

* For clearances not specified in ANSI Z2223.1/NFPA 54 or CSAB149.1, the following statement shall be included:“Clearance in accordance with local installation codes and therequirements of the gas supplier and the manufacturer’s installationinstructions.”

V

X

Vent Terminal

Air Supply Inlet

Area Where Terminal IsNot Permitted

snoitallatsnInaidanaC 1 snoitallatsnISU 2

A ynoclabro,kced,hcrop,adnarev,edargevobaecnaraelC )mc03(sehcni21 )mc03(sehcni21

B denepoebyamtahtroodrowodniwotecnaraelC

<secnailpparof)mc51(sehcni603(sehcni21,)Wk3(hutB000,013(hutB000,01>secnailpparof)mc,)Wk03(hutB000,001<dna,)Wk

>secnailpparof)mc19(sehcni63)Wk03(hutB000,001

<secnailpparof)mc51(sehcni632(sehcni9,)Wk3(hutB000,01hutB000,01>secnailpparof)mc

51(hutB000,05<dna,)Wk3(rof)mc03(sehcni21,)Wk

)Wk51(hutB000,05>secnailppa

C wodniwdesolcyltnenamrepotecnaraelC * *

DehtevobadetacoltiffosdetalitnevotecnaraelclacitreV

ehtmorf)mc16(teef2foecnatsidlatnozirohanihtiwlanimretlanimretehtfoenilretnec

* *

E tiffosdetalitnevnuotecnaraelC * *

F renrocedistuootecnaraelC * *

G renrocedisniotecnaraelC * *

HevobadednetxeenilretnecfoedishcaeotecnaraelC

ylbmessarotaluger/retem

51thgiehanihtiw)mc19(teef3ehtevoba)m5.4(teef

ylbmessarotaluger/retem*

I teltuotnevrotalugerecivresotecnaraelC )mc19(teef3 *

JehtrognidliubottelniylppusrialacinahcemnonotecnaraelC

ecnailpparehtoynaottelnirianoitsubmoc

<secnailpparof)mc51(sehcni603(sehcni21,)Wk3(hutB000,013(hutB000,01>secnailpparof)mc,)Wk03(hutB000,001<dna,)Wk

>secnailpparof)mc19(sehcni63)Wk03(hutB000,001

<secnailpparof)mc51(sehcni632(sehcni9,)Wk3(hutB000,01hutB000,01>secnailpparof)mc

51(hutB000,05<dna,)Wk3(rof)mc03(sehcni21,)Wk

)Wk51(hutB000,05>secnailppa

K telniylppusrialacinahcemaotecnaraelC )m38.1(teef601nihtiwfievoba)mc19(teef3

yllatnoziroh)m3(teef

LdetacolyawevirddevaproklawedisdevapevobaecnaraelC

ytreporpcilbupno)m31.2(teef7 *

M ynoclabro,kced,hcrop,adnarevrednuecnaraelC )mc03(sehcni21 *

Page 9: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003 Page 9Figure 5

Sidewall Vent Terminal Clearances (Non-Direct Vented Furnaces)

1 In accordance with the current CSA B149.1, Natural Gas andPropane Installation Code

2 In accordance with the current ANSI Z2223.1/NFPA 54, NationalFuel Gas Code

† A vent shall not terminate directly above a sidewalk or paveddriveway that is located between two single family dwellings andserves both dwellings.

‡ Permitted only if veranda, porch, deck, or balcony is fully open on aminimum of two sides beneath the floor.

* For clearances not specified in ANSI Z2223.1/NFPA 54 or CSAB149.1, the following statement shall be included:“Clearance in accordance with local installation codes and therequirements of the gas supplier and the manufacturer’s installationinstructions.”

V

X

Vent Terminal

Air Supply Inlet

Area Where Terminal IsNot Permitted

snoitallatsnInaidanaC 1 snoitallatsnISU 2

A ynoclabro,kced,hcrop,adnarev,edargevobaecnaraelC )mc03(sehcni21 )mc03(sehcni21

B denepoebyamtahtroodrowodniwotecnaraelC

<secnailpparof)mc51(sehcni603(sehcni21,)Wk3(hutB000,013(hutB000,01>secnailpparof)mc,)Wk03(hutB000,001<dna,)Wk

>secnailpparof)mc19(sehcni63)Wk03(hutB000,001

foedisotrowoleb)m2.1(teef4evoba)m003(toof1;gninepo

gninepo

C wodniwdesolcyltnenamrepotecnaraelC * *

DehtevobadetacoltiffosdetalitnevotecnaraelclacitreV

ehtmorf)mc16(teef2foecnatsidlatnozirohanihtiwlanimretlanimretehtfoenilretnec

* *

E tiffosdetalitnevnuotecnaraelC * *

F renrocedistuootecnaraelC * *

G renrocedisniotecnaraelC * *

HevobadednetxeenilretnecfoedishcaeotecnaraelC

ylbmessarotaluger/retem

51thgiehanihtiw)mc19(teef3ehtevoba)m5.4(teef

ylbmessarotaluger/retem*

I teltuotnevrotalugerecivresotecnaraelC )mc19(teef3 *

JehtrognidliubottelniylppusrialacinahcemnonotecnaraelC

ecnailpparehtoynaottelnirianoitsubmoc

<secnailpparof)mc51(sehcni603(sehcni21,)Wk3(hutB000,013(hutB000,01>secnailpparof)mc,)Wk03(hutB000,001<dna,)Wk

>secnailpparof)mc19(sehcni63)Wk03(hutB000,001

foedisotrowoleb)m2.1(teef4evoba)m003(toof1;gninepo

gninepo

K telniylppusrialacinahcemaotecnaraelC )m38.1(teef601nihtiwfievoba)mc19(teef3

yllatnoziroh)m3(teef

LdetacolyawevirddevaproklawedisdevapevobaecnaraelC

ytreporpcilbupno)m31.2(teef7 )m31.2(teef7

M ynoclabro,kced,hcrop,adnarevrednuecnaraelC )mc03(sehcni21 *

Page 10: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003Page 10

Figure 6

Upflow Direct Vent – Horizontal Venting(Models G1D91BU, G1D93BU,

& CG90UB Only)

* The 18" dimension is the minimumrecommended height for extremelycold areas. In these areas,moisture in the flue gases maycondense and freeze on the airintake if this height is reduced. Inmilder climates, this may bereduced to a minimum of 6".Height may be increased asneeded provided total length is notexceeded.

(CL

OS

ED

)

DR

AIN

HO

LE

TH

RU

.

59

.69

/56

.64

THE VENT SYSTEM OFTHE FURNACE MUST

BE SELF-SUPPORTINGAND

MUST NOT APPLY ANYWEIGHT LOAD TO THE

COMBUSTIONBLOWER.

CAUTION

FLUE PIPE

THIS PIECEIS OPTIONAL.

AIR INTAKE PIPE

18” *

RUN PITCH = 1/4”PER FOOT MIN.

SEE TABLE FORPROPER PIPE SIZE.

HEIGHT TO PROVIDE12” CLEARANCE TOMAX. SNOW LEVEL.

AIR INTAKE PIPE 6”

CONDENSATECOLLAR

DO NOT INSTALL THERESTRICTOR PLATES IN

ANY DIRECT VENTAPPLICATIONS.

IMPORTANT

slope upward, away from the furnace, at a minimum pitch of1/4" per foot of run, to prevent accumulation of condensate.

Do not cement air intake into the connector on burnerbox. Use high temperature RTV silicone sealant sointake pipe can be removed if service is required.

For proper operation, the vent and air intake pipemust be installed in the same pressure zone. There-fore, in horizontal venting applications they must beon the same side of the house within the parametersshown in Figure 6.

On initial start-up of the unit, some of the water used toprime the trap system may run down into the combustionblower and cause noise.

Upflow Models G1D91BU, G1D93BU, & CG90UBDirect Vent Installation

An inlet air restrictor plate (see Figure 1 on page 5) is suppliedwith this furnace and can be found in the plastic bag containingthese Installation Instructions and the User’s InformationManual. This restrictor plate is to be used only in non-directvent applications. See the non-direct venting sections onpages 11 and 13 for more information on installing the restrictorplate in non-direct vent applications.

The flue pipe screen (see Figure 1 on page 5) should beinstalled at the termination of the flue pipe and is designedto keep objects out of the flue pipe. An additional screenshould not be placed in the intake termination. If a screenis installed, the air intake may freeze shut.

Prime the trap system by slowly pouring 1 cup of waterdown the vent pipe.

For horizontal venting, refer to Figure 6. For vertical venting,refer to Figure 7. The vent pipe on horizontal runs must

THIS PIECEIS OPTIONAL.

INTAKE PIPE

FLUE PIPE

3” MIN. - 48” MAX.

Overhead View

Upflow Direct Vent – Vertical Venting(Models G1D91BU, G1D93BU,

& CG90UB Only)

Figure 7

Page 11: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003 Page 11

Upflow Models G1D91BU, G1D93BU, & CG90UBNon-Direct Vent Installation

An inlet air restrictor plate (see Figure 1 on page 5) issupplied with this furnace and can be found in the plasticbag containing these Installation Instructions and theUser’s Information Manual. This restrictor plate is to beused only in non-direct vent applications. Attach a 90°elbow (not supplied) to the inlet coupler and install therestrictor plate inside the elbow in all non-direct ventinstallations (see Figures 8 and 9).

The flue pipe screen (see Figure 1 on page 5) should beinstalled at the termination of the flue pipe and is designedto keep objects out of the flue pipe.

Prime the trap system by slowly pouring 1 cup of waterdown the vent pipe.

For horizontal venting, refer to Figure 8. For verticalventing, refer to Figure 9. The vent pipe on horizontal runsmust slope upward, away from the furnace, at a minimumpitch of 1/4" per foot of run, to prevent accumulation ofcondensate.

Figure 8

Upflow Non-Direct VentHorizontal Venting

(Models G1D91BU, G1D93BU,& CG90UB Only)

(CL

OS

ED

)

DR

AIN

HO

LE

TH

RU

.

59

.69

/56

.64

THE VENT SYSTEM OFTHE FURNACE MUST BESELF-SUPPORTING ANDMUST NOT APPLY ANYWEIGHT LOAD TO THE

COMBUSTION BLOWER.

CAUTION

SEE TABLE FORPROPER PIPE SIZE.

RUN PITCH = 1/4PER FOOT MIN.

"

HEIGHT TO PROVIDE12 CLEARANCE TOMAX. SNOW LEVEL.

"

6"

CONDENSATECOLLAR

THE INLET AIRRESTRICTOR PLATE

MUST BE INSTALLEDON ALL NON-DIRECT

VENT INSTALLATIONS.ATTACH A 90° ELBOW

TO THE INLET COUPLERAND INSTALL THE INLETAIR RESTRICTOR PLATE

INSIDE THE ELBOW.

INLETCOUPLER

Upflow Non-Direct VentVertical Venting

(Models G1D91BU, G1D93BU,& CG90UB Only)

Figure 9

On initial start-up of the unit, some of the water used toprime the trap system may run down into the combustionblower and cause noise.

Page 12: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003Page 12

Counterflow Models G1D93BC & CG90CB Direct VentInstallation

An inlet air restrictor plate (see Figure 1 on page 5) is suppliedwith this furnace and can be found in the plastic bag containingthese Installation Instructions and the User’s InformationManual. This restrictor plate is to be used only in non-directvent applications. See the non-direct venting sections onpages 11 and 13 for more information on installing the restrictorplate in non-direct vent applications.

The flue pipe screen (see Figure 1 on page 5) should beinstalled at the termination of the flue pipe and is designedto keep objects out of the flue pipe. An additional screenshould not be placed in the intake termination. If a screen isinstalled, the air intake may freeze shut.

Prime the trap system by slowly pouring 1 cup of waterdown the vent pipe. For horizontal venting, refer to Figure 10.For vertical venting, refer to Figure 11. The vent pipe onhorizontal runs must slope upward, away from the fur-nace, at a minimum pitch of 1/4" per foot of run, to preventaccumulation of condensate.

The 45,000 and 67,000 BTU/HR G1D93BC modelscontain an inlet air assembly that uses two 22.5° elbowsthat attach separately from the straight inlet pipe. Thisallows the inlet pipe assembly to be removed if needed forservice. Do not cement these elbows. Refer to Figure 12for detail of this inlet air assembly.

On initial start-up of the unit, some of the water used toprime the trap system may run down into the combustionblower and cause noise.

Do not cement air inlet pipe. Use high temperatureRTV silicone sealant so inlet pipe can be removed ifservice is required.

For proper operation, the vent and air intake pipemust be installed in the same pressure zone. There-fore, in horizontal venting applications they must beon the same side of the house within the parametersshown in Figure 10.

Figure 11

Counterflow Direct Vent – Vertical Venting(Models G1D93BC & CG90CB Only)

Counterflow Direct VentHorizontal Venting

(Models G1D93BC & CG90CB Only)

Figure 10

(CL

OS

ED

)

DR

AN

HO

LE

TH

RU

.

59

.69

/56

.64

DO NOT INSTALL THERESTRICTOR PLATES IN

ANY DIRECT VENTAPPLICATIONS.

IMPORTANT

FLUE PIPE

THIS PIECEIS OPTIONAL.

AIR INTAKE PIPE

18” *

RUN PITCH = 1/4”PER FOOT MIN.

SEE TABLE FORPROPER PIPE SIZE.

AIR INLETPIPE

6”

HEIGHT TO PROVIDE12” CLEARANCE TOMAX. SNOW LEVEL.PVC COLLARS

THE VENT SYSTEM OFTHE FURNACE MUST BESELF-SUPPORTING ANDMUST NOT APPLY ANYWEIGHT LOAD TO THE

COMBUSTION BLOWER.

CAUTION

CONDENSATECOLLAR

VENT PIPE

* The 18" dimension is theminimum recommended heightfor extremely cold areas. Inthese areas, moisture in theflue gases may condense andfreeze on the air intake if thisheight is reduced. In milderclimates, this may be reducedto a minimum of 6". Height maybe increased as neededprovided total length is notexceeded.

THIS PIECEIS OPTIONAL.

INTAKE PIPE

FLUE PIPE

3” MIN. - 48” MAX.

Overhead View

Page 13: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003 Page 13

Counterflow Models G1D93BC & CG90CB Non-DirectVent Installation

An inlet air restrictor plate (see Figure 1 on page 5) issupplied with this furnace and can be found in the plasticbag containing these Installation Instructions and theUser’s Information Manual. This restrictor plate is to beused only in non-direct vent applications. Attach a 90°elbow (not supplied) to the inlet coupler and install therestrictor plate inside the elbow in all non-direct ventinstallations (see Figures 13 and 14).

BURNER BOX

22.5° ELBOWS

STRAIGHTINLET PIPE

G1D93BC45,000 & 67,000 BTU/HR Units

Figure 12

Figure 14

Counterflow Non-Direct VentVertical Venting

(Models G1D93BC & CG90CB Only)

The flue pipe screen (see Figure 1 on page 5) should beinstalled at the termination of the flue pipe and is designedto keep objects out of the flue pipe.

Prime the trap system by slowly pouring 1 cup of waterdown the vent pipe. For horizontal venting, refer to Figure13. For vertical venting, refer to Figure 14. The vent pipeon horizontal runs must slope upward, away from thefurnace, at a minimum pitch of 1/4" per foot of run, toprevent accumulation of condensate.

On initial start-up of the unit, some of the water used toprime the trap system may run down into the combustionblower and cause noise.Figure 13

Counterflow Non-Direct VentHorizontal Venting

(Models G1D93BC & CG90CB Only)

(CL

OS

ED

)

DR

AN

HO

LE

TH

RU

.

59

.69

/56

.64

THE VENT SYSTEM OFTHE FURNACE MUST BESELF-SUPPORTING ANDMUST NOT APPLY ANYWEIGHT LOAD TO THE

COMBUSTION BLOWER.

CAUTION RUN PITCH = 1/4PER FOOT MIN.

"

SEE TABLE FORPROPER PIPE SIZE.

6"

HEIGHT TO PROVIDE12 CLEARANCE TOMAX. SNOW LEVEL.

"

GROMMET

PVC COLLAR

VENT PIPE

CONDENSATECOLLAR

COUPLERINLET

THE INLET AIRRESTRICTOR PLATEMUST BE INSTALLEDON ALL NON-DIRECTVENT INSTALLATIONS.ATTACH A 90° ELBOWTO THE INLET COUPLERAND INSTALL THE INLETAIR RESTRICTOR PLATEINSIDE THE ELBOW.

Page 14: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003Page 14

Existing Venting Systems

When an existing furnace is removed or replaced, theoriginal venting system may no longer be sized to properlyvent the attached appliances. An improperly sized ventingsystem can result in spillage of flue products into the livingspace, the formation of condensate, leakage, etc. See theWARNING box below for proper test procedure.

Condensate Disposal Installation

Install the condensate drain line to the unit as follows. Thecondensate can be drained from either the right or leftside of the furnace. Install the 1/2" NPT x 3/4" PVCadapter (supplied) in the drain on the side that the drainingwill occur. Install the plastic pipe plug opposite of the drain.Using 3/4" PVC pipe, make a connection from the adapterjust installed to extend just outside the unit. Install a 3/4"PVC tee as shown in Figure 15. From the tee, install thedrain to the disposal area. The top of the tee must be leftopen for proper condensate drainage.

It is recommended that the condensate drain be routeddirectly to a locally acceptable disposal area. The conden-sate drain line should not be run directly to the outdoorsespecially in colder climates where temperatures maycause the condensate to freeze in the drain line.

Failure to follow the steps outlined below for each appliance connected to the venting system being placed into opera-tion could result in carbon monoxide poisoning or death.

The following steps shall be followed for each appliance connected to the venting system being placed into operation,while all other appliances connected to the common venting system are not in operation:

1. Seal any unused openings in the common venting system.

2. Visually inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code,ANSI Z223.1/NFPA 54 (latest edition) or the CSA B149.1 Natural Gas and Propane Installation Codes and theseinstructions. Determine that there is no blockage or restriction, leakage, corrosion, or other deficiencies which couldcause an unsafe condition.

3. As far as practical, close all building doors and windows between the space in which the appliance(s) connected to theventing system are located and other spaces in the building.

4. Close fireplace dampers.

5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such asrange hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.

6. Follow the lighting instructions. Place the unit being inspected in operation. Adjust the thermostat so appliance isoperating continuously.

7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burneroperation. Use the flame of a match or candle.

8. If improper venting is observed during any of the above tests, the venting system must be corrected in accordance withthe National Fuel Gas Code, ANSI Z223.1/NFPA 54 (latest edition) and/or the CSA B149.1 Natural Gas and PropaneInstallation Codes.

9. After it has been determined that each appliance remaining connected to the venting system properly vents whentested as outlined above, return doors, windows, exhaust fans, fireplace dampers, and any other gas-fired burningappliance to their previous conditions of use.

CARBON MONOXIDE POISONING HAZARD

WARNING

Figure 15

Condensate Disposal

TH

RU

.

59

.69

/56

.64

1/2” NPT PLUG(SUPPLIED)

1/2” NPT x 3/4” PVC ADAPTER(SUPPLIED)

3/4” PVC

TEE MUST REMAINOPEN

Page 15: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003 Page 15

Outlet Duct

For installations not equipped with a cooling coil, a remov-able access panel must be provided in the outlet duct. Theopening should be accessible when the furnace is placedin service. Smoke or reflected light may be observedinside the casing to indicate the presence of leaks in theheat exchanger. The cover for the opening shall beattached in such a manner as to prevent leaks. Therecommended opening size is 6" x 14" for all sizes.

Duct Connection – Counterflow Models

If a unit is installed on a noncombustible floor, it may beinstalled directly over the supply duct or plenum. For installa-tions on combustible flooring, a special base must beordered and used. (See the Accessories section onpage 24 for more information.) To install using the specialbase assembly, see Figure 16 and the following instructions:

1. Cut a hole in the floor, sized to provide 1" clearancebetween all four sides of the duct and the edge of theflooring. The four angles on the base assembly shouldrecess into the floor joists and the base should rest onall four outside flanges.

2. Construct duct connections with right angle flanges.

Circulating Air Supply

When the furnace is installed so that the supply ductscarry air circulated by the furnace to areas outside thespace containing the furnace, the return air shall behandled by a duct or ducts sealed to the furnace casingand terminated outside the space containing the furnace.

A return air duct system is recommended. If the unit isinstalled in a confined space or closet, a return connectionmust be run, full size, to a location outside the closet. Theair duct in the closet must be tight to prevent any entranceof air from the closet into the circulating air.

If there is no complete return air duct system, the returnair connection must be sealed to the furnace casing andrun, full size, to a location outside the utility room or spacehousing the furnace to prevent a negative pressure on theventing system.

3. Drop the duct connections through the top of the baseassembly with the right angle flanges in good contactwith the glass tape on top of the base assembly.

4. Carefully position the furnace over the right angle ductflanges.

Gas Supply and Piping

Refer to the furnace rating plate to make sure the furnaceis equipped to burn the gas supplied (natural or propane).

When an air conditioning unit is used in con-junction with the furnace, the evaporator coilmust be installed in the discharge (supply) air.Do not install an evaporator coil in the returnair; excessive condensation will occur withinthe furnace.

CAUTION

Any conversion of a natural gas unit to pro-pane gas must be done by qualified person-nel using a conversion kit available from themanufacturer, following the instructions in theconversion kit. If done improperly, overfiringof the burners and improper burner operationcan result. This can create carbon monoxidewhich could cause asphyxiation.

WARNING

Combustible Floor Installation(Counterflow Models Only)

Figure 16

1"

CombustibleFlooring

WovenGlass Tape

BaseAssembly

Duct

Furnace

Page 16: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003Page 16

Gas supply piping should be installed in accordance withlocal codes and the regulations of the utility. Piping must beof adequate size to prevent undue pressure drop. Consultthe local utility or gas supplier for complete details on specialrequirements for sizing gas piping.

If local codes allow the use of a flexible gas applianceconnector, always use a new listed connector. Do not usea connector which has previously serviced another gasappliance.

Pipe connections must be tight, and a non-hardening pipecompound resistant to liquefied petroleum gases shouldbe used.

Connect the gas pipe to the furnace controls providing aground joint union as close to the controls as is possible tofacilitate removal of controls and manifold. Provide a dripleg on the outside of the furnace. A manual shutoff valveshall be installed in the gas line, outside the unit, 5' abovethe floor, or in accordance with any local codes. A testgauge connection must be installed with a 1/8" NPTplugged tapping immediately upstream of the shutoff valve(refer to Figure 17).

The furnace must be isolated from the gas supply pipingsystem by closing the individual manual shutoff valveduring any pressure testing of the gas supply pipingsystem at test pressure equal to or less than 1/2 psig(3.5 kPa) or 14" W.C. If the piping system is to be tested atpressures in excess of 1/2 psig (3.5 kPa), the furnace andits appliance main gas valve must be disconnected fromthe gas supply piping system.

The gas valve supplied with this furnace israted at 1/2 psig maximum. Any higher pres-sure may rupture the pressure regulatordiaphragm and may cause overfiring of theburners and improper burner operation. Theoverfiring may result in the creation of carbonmonoxide which could cause asphyxiation.

WARNING

After gas piping is complete, carefully check all pipingconnections (factory and field) for gas leaks. Use a leakdetecting solution or other preferred means. Some soapsused for leak detection are corrosive to certain metals.Carefully rinse piping thoroughly after leak detection hasbeen completed.

Gas Piping Connection

Figure 17

Failure to follow the safety warnings exactlycould result in serious injury, death, or prop-erty damage.

Never test for gas leaks with an open flame.Use a commercially available soap solutionmade specifically for the detection of leaks tocheck all connections. A fire or explosion mayresult causing property damage, personalinjury, or loss of life.

WARNINGFIRE OR EXPLOSION HAZARD

Page 17: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003 Page 17

Filter Rack Mounting Hole

Screw

Filter RackCorner EmbossmentsFront of Cabinet

Filter Rack Installation

Figure 18

Electrical Wiring

The furnace must be grounded and wired in accordancewith local codes or, in the absence of local codes, with theNational Electrical Code ANSI/NFPA No. 70 (latest edition)and/or CSA C22.1 Electrical Code (latest edition) if anexternal electrical source is utilized.

In all instances, other than wiring for the thermostat, thewiring to be done and any replacement of wire shallconform with the temperature limitation for Type T wire –63°F (35°C) rise.

Connect a sufficiently sized wire with ground to the furnace’sline voltage connections and ground lug. Refer to thefurnace rating plate for electrical characteristics to be usedin sizing field supply wiring and over-current protection.

The line voltage supply should be routed through areadily accessible disconnect located within sight of thefurnace. A junction box on the furnace side panel isprovided for line voltage connections. Refer to the furnacewiring diagram for specific connection information.

Proper polarity of the supply connections (“HOT”and “NEUTRAL”) must be observed to ensure thatsafety controls provide the protection intended.

A connection to the ground lug and actual earth ground(typically a ground stake or buried steel pipe) must bemaintained for proper operation.

Filters

Filters are not supplied with CG90CB or CG90UBseries furnaces.

G1D91BU and G1D93BU Models

A filter rack and cleanable 16" x 25" x 1/2" filter aresupplied with the furnace. (Models designed for more than1600 CFM nominal air delivery include two of each.) Thefilter rack is to be installed between the return air duct andthe side of the furnace. Refer to Figure 18 and the follow-ing instructions to install the filter rack:

1. Using the corner embossments as a guide, mark andcut a full-size opening in the side panel(s).

2. Using the filter rack as a template, mark and drill four7/64" diameter screw holes in the side panel(s).

3. With the filter access opening toward the front of thefurnace, use sheet metal screws to fasten the rack(s)to the side panel(s).

The filter slides in the rack from the front of the unit. Installthe filter(s) with the mesh side towards furnace.

For units that do not include a side return filter rack, kitAFILT524 can be used. Single side filter frame kitAFILTHA7 is available for single side return air connectionin installations requiring more than 1600 CFM nominal airdelivery. Bottom return filter kit AFILT529 is also availablefrom the manufacturer.

Counterflow Models:

Filters are not supplied with these furnaces; however, filtersmust be used. It is the installerís responsibility to installproperly sized filters in accordance with Table 3 on page 18.

Other filter accessories are also available from the manufac-turer including a full line of indoor air quality products. Forinformation on these products, contact the local distributor.

Risk of electrical shock. Disconnect electricalpower at the circuit breaker or service panelbefore making electrical connections. Failureto disconnect power supplies can result inproperty damage, personal injury, or death.

WARNING

Bottom Filter LocationUpflow Models

Figure 19

FilterBase

Side

Page 18: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003Page 18

Thermostat

Install a room thermostat according to the instructionsfurnished with it. Select a location on an inside wall that isnot subject to drafts, direct sunshine, or other heatsources. The initial heat anticipator setting should be equalto the total current draw of the control circuit.

Low voltage thermostat connections are to be made to theblower control board as indicated on the wiring diagram.

Humidifier

Terminals are provided on the blower control board forconnection to a 120-volt humidifier. The “HUM” terminal isenergized whenever the thermostat calls for heat. Refer tofurnace wiring diagram for specific connection information.

Continuous Low Speed Blower

If continuous blower operation on low speed is desired,connect the lowest speed motor tap to the “CONT”terminal on the blower control board (refer to the furnacewiring diagram.) The blower will operate on low speedwhenever main power is connected to the furnace, exceptwhen it operates on heating or cooling speed duringthermostat call for heat or cooling. This constant airterminal is intended for low speed only. If a motor iswired for a higher speed, the increased amp draw couldcause the board control to fail and void the warranty.

Electronic Air Cleaner

Terminals are provided on the blower control board forconnection of a 120-volt electronic air cleaner. The “EAC”terminal is energized whenever the thermostat is callingfor heat, cooling, or continuous blower. Refer to thefurnace wiring diagram for specific connection information.

Twinning

The blower control board is designed to permit “twinning”of furnaces (two furnaces connected to a common supplyand return air system, and controlled by one thermostat).An accessory kit must be ordered from the manufacturer.Specific wiring and operating instructions are includedwith the kit.

Each furnace must have its own dedicated vent system.

Table 3

Minimum Filter Requirements

1. The Airflow Descriptor is the two digits followingthe “D” in the model number.

2. Areas and dimensions shown for cleanable filtersare based on filters rated at 600 feet per minuteface velocity.

3. Typical filter sizes are shown; however, anycombination of filters whose area equals orexceeds the minimum area shown is satisfactory.

wolfriArotpircseD

sretliFelbasopsiD sretliFelbanaelC

aerA.niM).ni.qs(

eziS).ni(

.ytQ aerA.niM.ni.qs( )

eziS).ni(

.ytQ

90 084 52x02 1 042 02x61 1

01 084 52x02 1 042 02x61 1

21 675 02x61 2 882 02x61 1

41 276 02x02 2 633 02x02 1

61 867 02x02 2 483 02x02 1

02 069 52x02 2 084 52x02 1

Page 19: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003 Page 19

1. Set the room thermostat to lowest setting.

2. Remove burner access door.

3. Move the gas control knob to the “ON” position. Useonly your hand to turn the gas control knob; never usetools. If the knob will not turn by hand, don’t try torepair it; call a qualified service technician. Force orattempted repair may result in a fire or explosion.

4. Replace the burner access door.

5. Turn on the electrical power to the furnace.

6. Set the room thermostat to a point above roomtemperature to light the main burners. After theburners have ignited, set the room thermostat todesired temperature.

To Shut Down Furnace:

1. Set the room thermostat to the lowest setting.

2. Turn off all electric power to the furnace.

3. Remove burner access door.

4. Shut off the gas by moving the gas control knob to the“OFF” position.

5. Replace the burner access door.

START-UP

These furnaces are equipped with an ignition devicewhich automatically lights the burners. Do not try to lightthe burners by hand.

Before operating, smell all around the appliance area forgas. Be sure to smell next to the floor because some gasis heavier than air and will settle on the floor.

What to do if you smell gas:

• Do not try to light any appliances.

• Extinguish any open flame.

• Do not touch any electric switch; do not use anyphone in your building.

• Immediately call your gas supplier from a neighbor’sphone. Follow the gas supplier’s instructions.

• If you cannot reach your gas supplier, call the firedepartment.

Do not use this furnace if any part has been under water.Immediately call a qualified service technician to inspectthe furnace and to replace any part of the control systemand gas control which has been under water.

IMPORTANT: Refer to the Lighting Instruction label onthe furnace for instructions on operating the specificcontrols used on your unit.

Lighting Instructions

For Your Safety, Read Before Operating

If you do not follow these instructions exactly,a fire or explosion may result causing prop-erty damage, personal injury, or loss of life.

WARNING

To Start Furnace:

Be sure the manual gas control has been inthe “OFF” position for at least 5 minutesbefore starting the unit. Do not attempt tomanually light the burners.

CAUTION

Should overheating occur or the gas supplyfail to shut off, shut off the manual gas valveto the appliance before shutting off the elec-trical supply.

WARNING

Page 20: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003Page 20

OPERATION

Sequence of Operation

Heating

During a call for heat the thermostat closes the R-Wcircuit of the control board. The control board verifies limitswitches are closed and pressure switch is open. Theinduced draft blower relay closes causing the blower torun. As vent pressure is developed by the induced draftblower, the pressure switch closes. After a 15-second pre-purge, the control energizes the hot surface ignitor. Afterthe 7-second warmup time, the control energizes the maingas valve causing the main burners to ignite. The hotsurface ignitor is de-energized 3 seconds after the mainvalve opens. If flame is sensed during this time the mainvalve remains energized and the control starts the30-second heat blower “on” delay.

As heating demand is met, the thermostat de-energizes theR-W circuit. The control de-energizes the main valvecausing the burners to shut off. The induced draft blowershuts off after a 15-second post-purge delay. The circulatingair blower will continue to operate until the user-selectableheat blower “off” delay expires. The control return to standbymode once the heat blower “off” delay expires.

Fan “On”

During a fan “on” call, the thermostat energizes the R-Gcircuit of the control board, immediately causing the fan toenergize the COOL speed. The fan remains energized aslong as the thermostat calls for fan “on” operation.

If a call for cooling is energized during a fan “on” call, the fancontinues to operate at the COOL speed. If a call for heat isenergized during a fan “on” call, the control de-energizes thefan immediately and begins the heat call/ignition sequence.

At the end of the fan “on” call the thermostat de-energizesthe R-G circuit of the control, causing the fan to be de-energized immediately.

Cooling

During a call for cooling, the thermostat energizes the R-Ycircuit of the control board. After a 1-second cooling “on”delay, the control energizes the cooling fan speed. If the fanis already energized, it remains running and does not de-energize for the 1-second cooling fan “on” delay.

The call for cooling has priority over continuous fanoperation while a call for heating has priority over both acall for cooling or continuous fan. Ignition lockouts for anyreason do not affect cooling operation.

As cooling demand is met, the thermostat de-energizesthe R-Y circuit of the control board. After a 60-second

cooling “off” delay, the control de-energizes the coolingspeed fan. At the end of the cooling “off” delay period, thecontrol returns to the standby mode.

Controls

Following is a description of the operation of some of thecontrols used in this furnace. All models use one of eachcontrol, except as noted.

Pressure Switch

The pressure switch is a normally open switch thatmonitors combustion air flow. Inadequate air flow resultingfrom excessive venting system restriction or a failedcombustion blower will cause the switch to remain open.

Rollout Switch

The rollout switch is a normally closed switch that openswhen abnormal temperatures exist in the burner area. Thiscan be caused by a restricted heat exchanger causingmain burner flame to “roll out” into the vestibule area orburner box.

This switch must be manually reset by pushing the buttonon top to restore furnace operation. G1D93BC units havetwo rollout switches.

Primary Limit Control

This is a normally closed control that opens if abnormallyhigh circulating air temperatures occur. It is an automaticreset control.

Auxiliary Limit Control

This is a normally closed control that opens under abnor-mal “reverse air flow” conditions that could occur in acounterflow or horizontal installation if the circulatingblower fails. It is an automatic reset control.

Upflow models do not include an auxiliary limit control.

Interlock (Blower Door) Switch

When the blower door is removed, the interlock switchbreaks the power supply to the burner controls and blowermotor. The switch operation must be checked to confirm itis operating correctly.

Blower Control Board

The blower control board operates the circulating airblower, the combustion blower and any accessoriesconnected to it. These models feature user-selectableblower “off” delay times (60, 90, 120, and 180 seconds)that are factory set to provide a 120-second blower “off”delay on heating (see wiring diagram on page 26).

Page 21: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003 Page 21

Refer to the furnace wiring diagram while using thefollowing procedure to change motor speed:

1. Turn off electrical power to the unit.

2. Connect the desired speed tap for cooling on theblower control board.

3. For heating speed, check the temperature rise and, ifnecessary, adjust the blower speed tap to maintaintemperature rise within the range shown on thefurnace rating plate.

To use the same speed tap for both heating andcooling, install a piggyback terminal on the speed tapusing a short jumper. Wire 1/4" quick connect termi-nals on both ends to jumper the “HEAT” and “COOL”speed on the blower control board.

4. The remaining speed taps must be connected todummy terminals marked “PARK” on the blowercontrol board.

Checking and Adjusting Gas Input

The minimum permissible gas supply pressure for thepurpose of input adjustment is 5" W.C. for natural gas and11" W.C. for propane gas. This furnace requires conversionfor use with propane (see Accessories section on page 24for correct kit). The maximum inlet gas supply pressure is10.5" W.C. for natural gas and 13" W.C. for propane.

Gas input must never exceed the value shown on thefurnace rating plate. The furnace is equipped for ratedinput at manifold pressures of 3.5" W.C. for natural gas or10.0" W.C. for propane gas.

To measure the manifold pressure, disconnect the hoseand remove the barbed fitting in the downstream side ofthe gas valve and connect a water manometer or gauge(see Figure 20).

To adjust the regulator, turn the adjusting screw(s) on theregulator clockwise to increase pressure and input; coun-terclockwise to decrease pressure and input.

Replace the barbed fitting and reconnect the hose aftermeasuring and/or adjusting the regulator.

For Natural Gas: Check the furnace rate by observing thegas meter, when available, making sure all other gasappliances are turned off. The test hand on the meter

x 3600 x= Cubic Feet Per RevolutionBTU/HR INPUT # Seconds Per Revolution

HeatingValue

The heating value of the gas can be obtained from the localutility company.

For Propane Gas: The only check for the furnace rate is toproperly adjust the manifold pressure using a manometerand Table 4 on page 22. Typical manifold set point forinstallations at altitudes from 0 to 4500 feet above sea levelis 10.0" W.C.

Temperature Rise

Check the temperature rise and, if necessary, adjust blowerspeed to maintain temperature rise within the range shownon the unit rating plate.

High Altitude

In both the United States and Canada, this furnace isapproved for operation at altitudes from 0 to 4500 feet abovesea level without any required modifications. From 4500 to7500 feet, the gas manifold pressure needs to be adjustedaccording to the information shown in Table 4 on page 22.To adjust the manifold pressure, refer to previous sectionChecking and Adjusting Gas Input. For installationsabove 7500 feet, call Technical Service at 1-800-448-5872ext. 2610 for assistance.

The furnace rate must be within +/- 2% of theappliance rating input.

CAUTION

Figure 20

Checking and Adjusting Gas Input

should be timed for at least one revolution. Note thenumber of seconds for one revolution.

Page 22: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003Page 22

Manifold Pressure vs. Altitude

* Consult local utility for actual heating value.

Furnace Input = Input Factor x Nameplate Input

Above 7500 feet, call Technical Services at 1-800-448-5872 ext. 2610.

Table 4

edutitlA).tf(

saGlarutaN )PL(enaporP

tupnI tupnI tupnI tupnI tupnIrotcaF rotcaF rotcaF rotcaF rotcaF

gnitaeH*eulaVtf/UTB( 3)

dlofinaMerusserP).C.W.ni(

gnitaeH*eulaVtf/UTB( 3)

dlofinaMerusserP.C.W.ni( )

0002 849 05.3 8722 00.01 6669.0

0003 419 05.3 6912 00.01 9949.0

0004 188 05.3 6112 00.01 2339.0

0054 568 05.3 7702 00.01 9429.0

0005 948 92.3 9302 14.9 0098.0

0055 338 72.3 0002 53.9 0978.0

0006 818 52.3 4691 92.9 0868.0

0056 208 32.3 7291 42.9 0758.0

0007 787 12.3 1981 81.9 0648.0

0057 177 91.3 3581 21.9 0538.0

Page 23: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003 Page 23

It is recommended that this furnace be inspected by aqualified service technician at the beginning of eachheating season.

Filters

Filters should be checked at least every 6 weeks. Dispos-able filters should be replaced when dirty, and cleanablefilters should be cleaned regularly. It is important to keep theair filters clean, as dirty filters can restrict airflow and theblower and induced draft motors depend upon sufficient airflowing across and through them to keep from overheating.

Lubrication

The blower motor and induced draft motor are pre-lubricatedby the manufacturer and do not require further lubricatingattention. However, the motors should be cleaned periodi-cally to prevent the possibility of overheating due to anaccumulation of dust and dirt on the windings or on themotor exterior.

Condensate Collection and Disposal System

Check the condensate drain line periodically for blockage.Visual inspection of condensate flow can be done easilywhile the furnace is in operation. Use a flashlight toilluminate the discharge end of the condensate drain thatis placed in the sewer opening. If the condensate drainline becomes blocked or plugged, the furnace will notoperate properly.

MAINTENANCE

Failure to follow the safety warnings exactlycould result in dangerous operation, seriousinjury, death, or property damage.

Improper servicing could result in dangerousoperation, serious injury, death, or propertydamage.

• Before servicing, disconnect all electricalpower to furnace.

• When servicing controls, label all wires priorto disconnecting. Reconnect wires correctly.

• Verify proper operation after servicing.

WARNING

ELECTRICAL SHOCK, FIRE,OR EXPLOSION HAZARD

Main Burners

Light the burners and allow to operate for a few minutes toestablish normal burning conditions. Observe the mainburner flames. Compare this observation to Figure 21 todetermine if proper flame adjustment is present. Flameshould be predominantly blue in color and strong in appear-ance. Check that all burners are lit, and that the flame doesnot impinge on the sides of the heat exchanger.

Distorted flame or yellow tipping of the natural gas mainburner flame, or long yellow tips on propane, may becaused by lint accumulation or dirt inside the burner orburner ports, at the air inlet between the burner andmanifold pipe, or obstructions over the main burner orifice.

Use a soft brush or vacuum to clean the affected areas.

Typical Flame Appearance(Main Burners)

Figure 21

HeatExchanger

BurnerFlame

(Blue Only)

Burner

GasManifold

Page 24: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003Page 24

REPAIR PARTS

The following repair parts are available from the localdistributor. When ordering parts, include the completefurnace model number and serial number which areprinted on the rating plate located on the furnace.

Control Group

TransformerHigh limit controlAuxiliary limit (if used)Gas valveIgnition/blower control boardFlame sensorPressure switchBlower door interlock switchCombustion blower assemblyFlame rollout protector switchHot surface igniter

Heat Exchanger Group

Heat exchanger – primaryHeat exchanger – secondaryCondensate drain pan

Blower Group

Blower housing assemblyBlower wheelBlower motorBlower motor mountBlower motor capacitor

Burner Group

Gas manifoldMain burner orificesMain burners

Accessories

ALPKT572 Natural Gas to Propane Conversion Kit(G1D91BU and CG90UB)

ALPKT574 Natural Gas to Propane Conversion Kit(G1D93BU, G1D93BC, and CG90CB)

AFILTHA7 Single Side Filter Frame KitAFILT524 Side Return Filter Kit (upflow models)AFILT529 Bottom Return Filter KitAFILT525 Return Filter Kit (counterflow models)ANGKT557 Propane to Natural Gas Conversion Kit

(G1D91BU and CG90UB)ANGKT556 Propane to Natural Gas Conversion Kit

(G1D93BU, G1D93BC, and CG90CB)ATWIN579 Twinning KitACVK2 Concentric Vent KitABASE512 Combustible Floor Base (17.5" cabinets)ABASE568 Combustible Floor Base (21.0" cabinets)ABASE569 Combustible Floor Base (24.5" cabinets)

Page 25: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003 Page 25

CONTROL SYSTEM DIAGNOSTICSFailure Codes

Table 5

Troubleshooting

The following visual checks should be made beforetroubleshooting:

1. Check to see that the power to the furnace and theblower control board is on.

2. The manual shutoff valves in the gas line to thefurnace must be open.

3. Make sure all wiring connections are secure.

4. Review the Sequence of Operation (see page 20).

Start the system by setting the thermostat above the roomtemperature. Observe the system’s response. Then usethe information provided in this section to check thesystem’s operation.

The furnace has a built-in, self-diagnostic capability. If asystem problem occurs, a fault code is shown by an LEDon the control board. The control continuously monitors itsown operation and the operation of the system. If a failureoccurs, the LED will indicate the failure code. The flashcodes are presented in Table 5.

Fault Code History Button

The control stores the last five fault codes in memory. Apushbutton switch is located on the control (see Figure 22on page 26). When the pushbutton switch is pressed andreleased, the control flashes the stored fault codes. Themost recent fault code is flashed first; the oldest fault codeis flashed last.

To clear the fault code history, press and hold thepushbutton switch in for more than 5 seconds beforereleasing.

sutatSDEL noitpircseDtluaF

ffODELlortnocrolortnocotrewopoN

detcetedtluaferawdrah

nODEL noitarepolamroN

hsalF1 ffoevlavsaghtiwtneserpemalF

sehsalF2htiwdesolchctiwserusserP

fforecudni

sehsalF3htiwnepohctiwserusserP

norecudni

sehsalF4 nepohctiwstimilhgiH

sehsalF5 nepohctiwstuolloR

sehsalF6 tuokcolelcychctiwserusserP

sehsalF7 noitingionoteudtuokcoL

sehsalF8emalfynamoototeudtuokcoL

stuopord

sehsalF9 gnisahpegatloveniltcerrocnI

Page 26: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003Page 26 Figure 22

Connection DiagramP/N 45198-005

Page 27: INSTALLATION INSTRUCTIONS - The Comfort Zone · INSTALLATION INSTRUCTIONS G1D91BU, G1D93BC, ... near the furnace, vent pipe, or warm ... Install this furnace only in a location and

# 45466K003 Page 27Figure 23

Schematic DiagramP/N 45198-005