Upload
others
View
11
Download
0
Embed Size (px)
Citation preview
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018 1
Installation�Instructions�-�Confi�guring
IQ422, IQ4NC/00, IQ4NC/12Controllers
Important: Retain these instructions
These instructions shall be used by trained service personnel only. If the equipment is used in a manner not specifiedbytheseinstructions,theprotectionprovidedbytheequipmentmaybeimpaired. https://partners.trendcontrols.com
1 Isolate All Power (includinganyI/Osupplies)
1 BEFORE STARTING CONFIGURATION
CONTENTS1 BeforeStartingConfiguration.......................................12 Configuration.................................................................1
3 Connect to IQ4xx........................................................104 Reset to Defaults.........................................................12
2 CONFIGURATION
Read�&�Agree�to�End�User�Licence�Agreement
Additional Documentation Required
▪ SETManual(TE200147) ▪ IPToolManual(TE200638) ▪ IQToolMonitorAppletManual(TE201298) ▪ IQToolAddresserAppletManual(TE201299) ▪ IQ4ConfigurationManual(TE201263)
Note: PDF copies are included with SET installation in the following folder: C:\...\Trend Control Systems\Documentation
IQ422, IQ4NC/00, IQ4NC/12 Installation Instructions-Mounting(TG201264) SETManual(TE200147)
Prepare Ethernet Network (ifusingEthernet)
Install DHCP ServerIftheIPaddresssettings(IPaddress,subnetmask,defaultrouter,WINSandDNSservers’addresses)aretobesuppliedbyaDHCPserver,ensureone is installedon theEthernetsegment to which the IQ422, IQ4NC/00, IQ4NC/12 isconnected.
Install WINS ServerIf host names are being used for IP addressing across arouter,aWINSservermustbeinstalled.
Install DNS ServerIfemailalarmsarebeingsent,andtheemailserveraddressisidentifiedbyinternetdomainname,aDNSservermustbeinstalled.
IQ422, IQ4NC/00, IQ4NC/12 Installation Instructions-Mounting(TG201264)
PSU
PSU
O
I
O
I
O
I
Install the IQ422, IQ4NC/00, IQ4NC/12 Install�SET�on�PC�/�Laptop
WARNING Connecting leadsmay be connectedtopowersupplies.Isolatebeforetouching.
2 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12� Installation�Instructions�-�Confi�guring
6 Select Terminator Switch Position (IQ4NCusingMS/TPnetworkonly)
3 Peel�Off��Top�Serial�Label�&�Retain
5 Disconnect All I/O4 Open�Rotating�Covers
2 Open Panel / Enclosure
2 CONFIGURATION (continued)
Serial
Number
n q 4 e y e c p 4 1 2 3 4 5
Q422B_V53440388 O/S
Q422B_V53440388
n q 4 e y e c p 4 1 2 3 4 5
00:10:70:0D:1E:92MAC Addr
IQ411-1010U5000Part No:
LAN
422
MAC
Addr
IP
Addr
LAN
Location
S/No:
MAC Addr 00.10.70.00.UD.BBS/No:
Q3B____X73010003
IP Addr Location
TerminatoroutofcircuitTerminatorincircuit
IQ422, IQ4NC/00, IQ4NC/12 Installation Instructions - Mounting (TG201264) fordetailsofterminatoruse.
Leave Power, Ethernet, Current loop LAN, USB, RS232,andMS/TPconnected(whereappropriate).
WARNING Opening the panel may exposedangerousvoltages.
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018 3
Installation�Instructions�-�Confi�guring IQ422, IQ4NC/00, IQ4NC/12
8 Close�Rotating�Covers
10 Check�Power�&�Watchdog�Indicators
9 Switch On Power to IQ4xx
7 Connect�PC�/�Laptop
11 Check Ethernet Indicators (ifEthernetisconnected)
2 CONFIGURATION (continued)
O
I
Either:viaEthernetHub/Switch Or:usingdirectconnection
Note: To connect with SET a vCNC is required (see step 14). SET can connect when on a diff erent subnet.
Note: Other methods of connection are available see ‘Connect to IQ4xx’ on page 10.
Normal operation indicationPower
Watchdog
Fault indicationsPower Checkinputpowersupply
Watchdog Devicefault.TryresettingtheIQ4xxtodefaultsettings(seepage12).
10s
Normal operation indicationOK RX or
Fault indicationsOK CheckEthernet
RJ45 StandardEthernetcable(Cat5etwistedpair)max100m(109yds)
StandardEthernetcable(Cat5etwistedpair)max100m(109yds)
RJ45
Hub/SwitchRouter
Note: All LEDs illuminate for several seconds after switch on.
Watchdog(red)
Power(green)
OK(green)
RX(yellow)
4 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12� Installation�Instructions�-�Configuring
12 Connect to the IQ4xx
13 Set�up�IP�Addressing�Details�(ifusingEthernet)
2 CONFIGURATION (continued)
n q 4 e y e c p 4 1 2 3 4 5
Q422B_V53440388 O/S
00:10:70:0D:1E:92MAC Addr
IQ422-1010U5000Part No:
LAN
IP
Addr
422
Thenfind the IQ4NC, IQ422by itsMACaddressasshownonseriallabel
SETManual(TE200147)IPToolManual(TE200638)
UseIPTool–seestep12–tochooseeitherstatic(fixed)ordynamic(DHCP)addressing:
Dynamic�(DHCP)�Addressing�(default)
Parameter ValueDeviceMode
Static�(Fixed)�Addressing
Parameter ValueDeviceMode
IPAddressEnterrequiredvalueinformat:
xxx.xxx.xxx.xxxSubnetMaskDefault RouterWINSServer
Whensettodynamic(DHCP)addressingtheunitautomaticalobtains its IP addressing details (IP address, subnetmask,default router, WINS server and DNS server) from thenetwork’s DHCP (Dynamic Host Configuration Protocol)server. IfnoDHCPserver is found, theunitdefaults to link/localmodewhereitautonegotiatesitsIPaddresswithotherdevicesonitsEthernetsegment,
Note: It is recommended that link/local only be used on a single segment system.
When set to static (fixed) addresssing the IP addressingdetailsmustbeconfiguredmanually.
Note: If email alarms are being sent, and the email server address is identified by internet domain name, then a DNS server must also be specified using Text Comms.
IPToolManual(TE200638)
UsingthePC/laptop(seestep7)runSET/IPTool
14 Set up Virtual CNCs (ifrequired)
Bydefault,IQ4NCshave4enabledvCNCs(4,5,6,and7)andIQ422shave3disabledvCNCs.AvCNCmustbeenabledif connection to a supervisor, tool or display is required. Ifnecessarydisable/configurethemtoavoidaddressconflicts.
Use IPTool–seestep12– tosetup theaddressandportnumberofeachvCNC.
Parameter RangeAddress 0(disabled),1,4to9,11to119PortNumber 1to32767
Default = 10000 plus the address(e.g.address23setsportto10023)
OncethevCNCsetupinIPTooliscomplete,useIQSETtoconfigurethevCNCs.
▪ UsingIQSETconnecttooneofthecontroller’svCNCs. ▪ Youwillbeprompted topress theservicebuttonon the
controller.OncepressedtheSecure�Site�Configuration dialogueboxisdisplayed.
▪ Configure the vCNCs as required, and enter thecredentialsfortheCNCUsermodule.
Note: configuring the vCNCs require physical access to the controller ensure this is done before leaving site.
SETManual(TE200147)IPToolManual(TE200638)
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018 5
Installation�Instructions�-�Configuring IQ422, IQ4NC/00, IQ4NC/12
15 Set up IQ4NC Communication Mode (ifusingIQ4NC)
16 Check�Trend�Current�Loop�Network�Indicators�(ifcurrentloopnetworkbeingused)
17 Check MS/TP Network Indicators (IfIQ4NCusingMS/TPnetwork)
▪ ConnectaPCdirectlytotheIQ4usinganEthernetcable,see‘ConnecttoIQ4’onpage10.
▪ Usingawebbrowser,e.g. InternetExplorer,access thecontroller’swebpagesandselectModules>Networks to displaytheNC�Configuration�Wizard.
▪ Click required mode, and if necessary specify anyparameterse.g.LANnumber.
▪ Click ;thecontrollerwillrestart.
EthernetInternetworktotoMS/TPLAN(default)
Parameter NotesLANnumber 1,4to9,11to119BACnetIP Canbedisabled
CurrentLoopInternetworktoMS/TPLAN
Parameter NotesLANnumber 1,4to9,11to119BACnetIP Canbedisabled
EthernetInternetworktoCurrentLoopLAN
Parameter NotesLANnumber 1,4to9,11to119BACnetIP CanbedisabledBACnetMSTP
Can be enabled e.g. forconnectionofPEHAdevices
Ethernet Internetwork to Current loopInternetwork
Note: Address no longer needs to be > 100.
Parameter NotesLANnumber 1,4to9,11to119BACnetIP CanbedisabledBACnetMSTP
Can be enabled e.g. forconnectionofPEHAdevices.
ManualconfigurationE.g. Ethernet Internetwork to Current loopInternetworkplusMS/TPLan
2 CONFIGURATION (continued)
IQ4WebUserGuide(TC201256).
Note: The IQ4NC always has a LAN to connect to the internetwork so cannot join another LAN on the internetwork.
Normal operation indicationTX RX
Fault indicationsTX Checkconnectiontodownstreamdevice
RX Checkconnectiontoupstreamdevice
Normal operation indicationRX TX
Fault indicationsRX Signal not reaching RX on downstream
deviceonnetwork–checkdevice/wiringTX No TX signal from upstream device on
network–checkdevice/wiring
TX(yellow)
RX(yellow)
TX(yellow)
RX(yellow)
6 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12� Installation�Instructions�-�Configuring
19 Set�up�Trend�Addressing
18 Set up Ethernet Access Across Routers (ifrequired)
20 Write�Address�Details�on�Label
2 CONFIGURATION (continued)
IftheLANistobebuiltacrossarouter(s)detailsofdevices(on each subnet) must be specified to enable cross-routercommunications.
UseIPTool–seestep12–tospecifyIPsettingsforupto20devicesintheRemoteTrendDeviceslist:
Parameter ValueIPAddress If using dynamic (DHCP) addressing:
Enterthehostnameoftheremotedevice.
If using static (fixed) addressing:EntertheIPAddressoftheremotedevice,intheformat:xxx.xxx.xxx.xxx
SubnetMask Thesubnetmaskfortheremotedevice,intheformat:xxx.xxx.xxx.xxx
IPToolManual(TE200638)
It is recommended that atleasttwodevicesfromeachsubnetare specified. For increased reliability details of additionaldevicesshouldbespecified.
IfstaticIPaddressingisbeingusedthelistshouldcontainthedeviceswiththelowestIPaddresses.
ThesamelistmustbecopiedtootherEINCtypedevicesonthenetwork.
Hint: Ticking the check box next to the Remote Trend Devices list retains the list in IP Tool, allowing it to be easily copied to other devices:
n q 4 e y e c p 4 1 2 3 4 5
Q422B_V53440388 O/S
00:10:70:0D:1E:92MAC Addr
IQ422-1010U5000Part No:
LAN
IP
Addr
422
IPToolManual(TE200638)IQTool Addresser Applet Manual(TE201299)
If�connecting�to�a�LAN�on�Ethernet�(or�standalone�mode): ▪ UseIPTool–seestep12–tosetthedeviceaddressand
LANnumber.
IQ4xx controllers are given a default device address andLANnumberinthefactory.Thedeviceaddressissetintherange11to119onarollingbasiswiththeLANnumbersetto20. Therefore itmay be necessary to set the address/LANnumberasrequired.
Parameter ValueLocalAddress 1,4to9,11to119
(mustbeuniqueonLAN)LocalLAN 1,4to9,11to119
(must be the same for all devicesrequiredtoformaLAN).
Note: Changing the LAN number and/or device address will cause the controller to reboot.
If�connecting�to�a�LAN�on�current�loop�(with�only�IQ4�type�controllers): ▪ Use SET’s IQTool Addresser Applet, and run the
DiscoveryWizard. ▪ Select either ‘Automatic Discovery’ (recommended) or
‘Manual Discovery’. If ‘Automatic Discovery’ is chosenyoushouldthenselect‘DuplicateAddressResolution’.
Automatic Discovery: Thetoolwilldiscoverthedevices,andattempttoresolveanyduplicateaddresses.
Manual Discovery: Either scan the bar code, or presstheServiceButtonforeachcontroller.
WARNING For /230 variants hazardousvoltagesexistwhentheunitispowered.Takesuitableprecautionsifpressingservicebutton.
Note: If the LAN is not as expected after discovery it could be because of installation related reasons, e.g. wiring faults, power failure, etc. Check the devices are operating correctly and repeat discovery. If there are duplicate addresses add the devices to the grid manually, using network address and serial number. If necessary use SET’s System View to set the LAN number, and IQTool to set the address.
If� connecting� to� a� LAN� on� current� loop� (with� pre� IQ4�controllers): ▪ UseSET’sIQToolAddresserApplettomanuallyaddthe
IQ4tothegridusingtheserialnumberandaddress. ▪ UseSET’sSystemViewtosettheLANnumber.
Deviceaddress(O/S)LANnumberFixedIPAddressorHostname(ifDCHP)
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018 7
Installation�Instructions�-�Configuring IQ422, IQ4NC/00, IQ4NC/12
21 Set�Current�Loop�Baud�Rate�(IQ4NCor../LANvariantsonly,ifcurrentloopnetworkbeingused)
22 Set�up�RS232�/�USB�Port�Addressing�(ifrequired)
23 Check�LAN�OK�Indicator�(notIQ4NC)
2 CONFIGURATION (continued)
IQToolMonitorAppletManual(TE201298)SETManual(TE200147)IQ4ConfigurationManual(TE201263)
Parameter RangeSupervisorport 0,4to9,11to119
Default=0localaccessonlyUSBEngineeringport
0,4to9,11to119Default=0temporarilytakesaddress125
UseSET’sIQToolMonitorApplettosettheSupervisorPortorUSBEngineeringPortasrequired.
IQToolMonitorAppletManual(TE201298)SETManual(TE200147)IQ4ConfigurationManual(TE201263)
If the IQ4xx is to provide connection to the network forsupervisors and tools it is necessary to setup the RS232SupervisorPortorUSBEngineeringPortasrequired.
Normal operation indication
LANbuiltOK
AttemptingtobuildLAN
Note: It is normal behaviour for LAN OK indicator to extinguish for up to 1 min after detecting baud rate, then illuminate.
Fault indication (EthernetLAN)
UnabletocommunicateonLAN.Note: Only applies if current loop is disabled or is not fitted.
Fault indication (CurrentLoopLAN)
every15s Longerthan2minutesindicatesLAN/internetworkcannotbebuilt.
▪ Checkbaudsettingsofalldevicesoncurrentloop–seestep21,andcheckalldeviceconnections.
▪ Ifstillflashing,fitloopback:
8584 86 87
RX- RX+TX- TX+
IfindicatorturnsOFF,deviceisfaulty.IfON,reconnectnetworkandswitchoffallotherdevicesonthenetwork.
▪ IfstillOFF,checknetworkcablingforshortcircuitswithamultimeter(NOTMegger).
▪ IfONswitchonotherdevicesinturnuntilfaultydevicefound (i.e.LANOKgoesOFF), inspect thatdevice todetermineandandcorrectthefault.
BydefaulttheIQ4xxwillautodetectthebaudrateinuseonthecurrentloop.Ifalldevicesaresettoautodetectthebaudratechosencannotbeguaranteed, inwhichcase itmaybenecessarytomanuallysetonedevicetoaknownrate.
Use SET’s IQTool Monitor Applet to disable autobaud andspecifythebaudrate.
Module Parameter RangeIQ Lan network
Autobaud 0(disabled)or1(enabled)Baud Rate 1k2,4k8,9k6,19k2,38k4
LAN�OK(green)
8 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12� Installation�Instructions�-�Confi�guring
24 Download�Strategy
25 Check IQ422 or IQ4NC on BACnet (If/BACorIQ4NCandBACnetprotocolcommunicationsrequired)
26 Test Inputs (NotIQ4NC/.../00)
2 CONFIGURATION (continued)
SETManual(TE200147)IQ4ConfigurationManual(TE201263)
SETManual(TE200147)
O
I
Switchoff Re-connect inputsOpencovers Closecovers
O
I
Switchon
Note: An Ethernet connection is required to download both strategy and backdrop fi les. Other connection types only allow download of strategy fi les.
Note: strategy download is not recommended over current loop with baud rate <9k6.
Note: SET will set up the controller’s date and time to that of the PC during download. However, they may be set up from a controller confi gured as timemaster.
ConfiguretheIQ4xxstrategyusingSET,andtestusingSET’ssimulationmode.
Use SET to download the strategy and backdrop file (ifrequired).
Use SET to check that the IQ4 BACnet functionality isoperatingbycheckingitappearscorrectlyintheSystemViewonitsBACnetnetwork.
S
Checkdigitalinputs Checkanalogueinputs
LED(yellow)
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018 9
Installation�Instructions�-�Confi�guring IQ422, IQ4NC/00, IQ4NC/12
28 Test Outputs (NotIQ4NC/.../00)
29 Connect Supervisors/Tools/DisplayPanels (ifrequired)
31 Backup�Strategy
33 Close Panel / Enclosure 32 Close�Rotating�Covers
30 Confi�gure�Web�Server
2 CONFIGURATION (continued)
Connect PCs (e.g. for supervisors/tools) and displays asdescribedin‘ConnecttoIQ4xx’onpage10.
Connectionofsupervisors,tools,displaypanelsetccanbemadedirectlytocontrollerviatheRS232LocalsupervisorPort,USBLocalEngineeringPort,WallbusPort,orEthernetport.ConnectioncanalsobemadeovertheTrendnetworkoverEthernetorthecurrentloop.
Use SET to upload the strategy and compare it with thestrategyheldbySET.
Note: An Ethernet connection is required to upload strategy and backdrop fi les. Other connection types only allow upload of strategy fi les.
SETManual(TE200147)
O
I
Switchoff Re-connect outputsOpencovers Closecovers
O
I
Switchon Checkdigitaloutputs Checkanalogueoutputs
LED(yellow)
LOAD
LED(yellow)
LOAD
ConnectiontotheIQ4webservercanbemadeviaHTTPand/or HTTPS protocol.Where HTTPS is used it will benecessarytoconfigureSSLcertificates.
Ifwebaccessisnotrequireditisrecommendedthatthewebserverisdisabledforsecurity.
IQ4ConfigurationManual(TE201263)SETManual(TE200147)
10 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12� Installation�Instructions�-�Confi�guring
1 Switch�Off��Power�to�IQ4xx 2 Open Top Cover (ifrequired)
3 Make Connection
O
I
PCviaLocalEngineeringPort(USB)Connect Directly to ControllerPCviaEthernetPort
RJ45 StandardEthernetcable(Cat5etwistedpair)max100m(109yds)
Connection use NotesIPTool ü
SET ü RequiresvCNCWebBrowser ü
Supervisor ü RequiresvCNC
PCviaLocalSupervisorPort(RS232)
CABLE/EJ101442
9wayfemaleDtype
RJ11
PC
ConnectiontotheIQ4xxcanbemadedirectlyviatheRS232LocalSupervisorPort,USBLocalEngineeringPort,orEthernetPort.Connectioncanalsobemadeoveranetwork(Ethernet).
Connection use NotesIPTool
SET ü
WebBrowser
Supervisor
Connection use NotesIPTool
SET ü
WebBrowser
Supervisor ü
IQView8viaLocalSupervisorPort(RS232)IQView8 requires its own power supply.
Note: If local supervisor port address is ‘0’ (default) communication is limited to the IQ4xx. If non-zero, communication is possible over the entire network.
RJ11 RJ11
RD/SDU-IQ2COMMSCABLE3M
USBcable
MicroBUSBconnector
3 CONNECT TO IQ4XX
IQView8
IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018 11
Installation�Instructions�-�Configuring IQ422, IQ4NC/00, IQ4NC/12
3 Make Connection (continued)
3 CONNECT TO IQ4XX (continued)
RJ11
RJ11
24VdcSupply
XW/R/IQ
Mustuseexternal24Vsupply
Connect Directly to ControllerRD-IQ, SDU-xcite, IQView4 via Local Supervisor Port(RS232)
Connect via Ethernet Network ▪ EnsuretheIQ4xxisconnectedtotheEthernetnetwork.
▪ Connecttheotherdevice(e.g.networkdisplayorPC)tosameEthernetnetworkandensurean IPconnection isavailablebetweenitandtheIQ4xx.
▪ TomakeaconnectionwithSET,asupervisorordisplayensureavCNCisavailableinaTrenddeviceonthesameEthernet Trend network and connect to the vCNC asdescribedinthesupplieddocumentation.
Note: If connecting with IP Tool, the PC should be on the same Ethernet segment as the IQ4xx.
▪ To make a connection with a web browser run a webbrowseronthePCandaccesstheIQ4xxIPaddressorhostname.
XW/R/IQwirelesssensorreceiverviaLocalSupervisorPort(RS232)
PC Connection use NotesIPTool ü
SET ü RequiresvCNCWebBrowser ü
Supervisor ü RequiresvCNC
Note: Set local supervisor port address to ‘0’ (default) as communication is limited to the IQ422, IQ4NC/00, IQ4NC/12.
IQView4 requires its own power supply.
RJ11RJ11
RD/SDU-IQ2COMMSCABLE3M
RJ11
RJ11
IQView4
RD-IQ
SDU-xcite
StandardEthernetcable (Cat5etwistedpair) max100m(109yds)
Hub/SwitchRouter
RJ45
RD-WMBviaWallbusPort
RD-WMB
TwistedPairCablemaximumlength60m(200ft)
IQView8
PC
12 IQ422,IQ4NC/00,IQ4NC/12ControllersInstallationInstructions-ConfiguringTG201265Issue12,24-Jul-2018.
IQ422, IQ4NC/00, IQ4NC/12� Installation�Instructions�-�Confi�guring
Please send any comments about this or any other Trend [email protected]
© 2018 HoneywellProductsandSolutionsSARL,ConnectedBuildingDivision.Allrightsreserved.ManufacturedforandonbehalfoftheConnectedBuildingDivisionofHoneywellProductsandSolutionsSARL,Z.A.LaPièce,16,1180Rolle,SwitzerlandbyitsAuthorizedRepresentative,TrendControlSystemsLimited.
TrendControlSystemsLimitedreservestherighttorevisethispublicationfromtimetotimeandmakechangestothecontenthereofwithoutobligationtonotifyanypersonofsuchrevisionsorchanges.
Trend�Control�Systems�LimitedSt.Mark’sCourt,NorthStreet,Horsham,WestSussex,RH121BW,UK.Tel:+44(0)1403211888,www.trendcontrols.com
2 Reset Controller
1 Isolate Power and Disconnect All I/O
3 Re-confi�gure�Controller
The factory reset will erase the strategy and reboot thecontroller into its original configuration.While the controlleriserasingthestrategy,theWatchdogandLANOKindicatorswill flashalternately.During the reboot all indicatorswill beON. Once this process has completed the Watchdog andLANOK indicatorswillgoOFF, leaving thePower indicatorON.Thisprocessmay takeup to10minutesdependingoncontrollertype.
Do� not� switch� off�� the� controller� until� the� process� has�completed.
�4� RESET�TO�DEFAULTS
Gotostep1onpage1.
Unplug the Ethernet cable and press and hold down theservice button. While continuing to hold down the button,switchonthecontroller.Ensurethebuttonremainspressedfor2to5safterpowerisswitchedon.
WARNING FOR /230 versions: Hazardousvoltages exist in this area when the unit ispowered.Thisoperationshouldonlybeperformedaftertakingsuitableprecautions
Thestrategy,usermodules(passwords,PINsetc),alarmlogs,andplotsarecleareddownandthefollowingparameterssettodefaults:
LANnumberoutstation addressIPaddressingmodeIP addresssubnetmaskUDPportidentifierRouter 1remoteTrenddevicesVirtualvCNCs.
Timeanddateareleftattheircurrentsettings.
O
I
2to5s
22 23 24 25
RX+
28 29
WMBRX- TX+ TX-
RX OK
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3
230V
19
4 510
24V0V 0V 0V 0V 0V 0V986 7
1 2 3
Press
22 23 24 25
RX+
28 29
WMBRX- TX+ TX-
RX OK
4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 1 2 3
230V
19
4 510
24V0V 0V 0V 0V 0V 0V986 7
1 2 3
Release
Followsteps1,2,4,5and8(onpages1to3)to:
▪ IsolatePower, ▪ OpenPanel, ▪ OpenRotatingCovers, ▪ DisconnectAllI/O, ▪ CloseRotatingCovers.