SAFETY WARNING Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. The three types of advisories are defined as follows: WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe NOTICE Indicates a situation that could result in equipment or property-damage only accidents. © 2020 Trane 1 2 3 4 5 6 7 Installation Instructions Air-Fi™ Wireless Communications Sensor (WCS-SD-SB) June 2020 BAS-SVN071E-EN Addressing Overview UC/BCI Tracer SC group 1 UC/BCI WCI WCI GRP NET NET GRP NET 1 1 1 1 1 WCI WCI WCI GRP NET GRP NET GRP NET 1 2 1 2 1 2 WCI WCI WCI GRP NET GRP NET GRP NET 2 1 2 1 2 1 WCI WCI WCI GRP NET GRP NET GRP NET 2 2 2 2 2 2 WCI UC/BCI UC/BCI UC/BCI UC/BCI UC/BCI UC/BCI GRP 1 Tracer SC group 2 Sn: 1 UC: 101 Network 2 Network 1 Network 1 Network 2 101 102 201 202 301 302 401 402 Sn: 1 UC: 102 Sn: 1 UC: 201 Sn: 1 UC: 202 Sn: 1 UC: 301 Sn: 1 UC: 302 Sn: 1 UC: 401 Sn: 1 UC: 402 Sn: 2 UC: 402 gn: 11 gn: 11 gn: 12 gn: 12 gn: 21 gn: 21 gn: 22 gn: 22 gn: 22 Group and network addresses must match. UC/BCI addresses must match. Sensor addresses default to 1. If multiple sensors are wired to a UC/BCI, each sensor must have a unique address. WCS WCS WCS WCS WCS WCS WCS WCS WCS In this example, UC/BCI 402 has two sensors connected to it. So the address of the second sensor must be set to “2”. For multiple sensor installations, refer to BAS-SVX40*-EN. Remove the cover Pull the insulation strip from between the batteries RH sensor module A 2% relative humidity sensor module, available as a separate part (X13790973030; model WCS-SH), can be installed on a WCS either before or after the WCS is powered up. Install RH sensor module in this location Set unit controller address Press to set 1st digit of UC address. Press Pres Press to set 2nd digit of UC address. Press Press to set 3rd digit of UC address. Press Press to set group address. Press Press to set net address. Set group and net address Press and hold the Address button for 3 seconds Sensor display legend: : group, network : unit controller : wireless sensor Set sensor address Press to change sensor number, if multiple sensors are used. To exit address mode, press the Address button and hold for 3 seconds. After addresses are set, the WCS will immediately attempt to join the network and associate with the controller. Error code E2 will appear on the sensor display until the WCS successfully joins the network. Error code E1 will be displayed until association is successful. You can press the center button twice at any time to cause the WCS to reattempt to join the network and to associate with Model Number: X13790955010, X13790955040, X13790955050,X13790968010, X13790956010, X13790969010, X13790973010 X39641265001

Installation Instructions A 2% relative humidity ... - Trane

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Installation Instructions A 2% relative humidity ... - Trane

SAFETY WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

The three types of advisories are defined as follows:

WARNINGIndicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTIONIndicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe

NOTICE Indicates a situation that could result in equipment or property-damage only accidents.

© 2020 Trane

1 2 3

4 5 6 7

Installation Instructions

Air-Fi™ WirelessCommunications Sensor (WCS-SD-SB)

June 2020 BAS-SVN071E-EN

Addressing Overview

UC/BCI

Tracer SC group 1

UC/BCI

WCI WCI

GRP NET NET

GRP NET

1 1 1

1 1

WCI

WCI WCI

GRP NETGRP NET

GRP NET

1 2 1 2

1 2

WCI

WCI WCI

GRP NETGRP NET

GRP NET

2 1 2 1

2 1

WCI

WCI WCI

GRP NETGRP NET

GRP NET

2 2 2 2

2 2

WCI

UC/BCI UC/BCI UC/BCI UC/BCI UC/BCI UC/BCI

GRP

1

Tracer SC group 2

Sn: 1

UC: 101

Network 2Network 1 Network 1 Network 2

101 102 201 202 301 302 401 402

Sn: 1UC: 102

Sn: 1

UC: 201Sn: 1

UC: 202Sn: 1

UC: 301Sn: 1

UC: 302Sn: 1

UC: 401 Sn: 1

UC: 402

Sn: 2

UC: 402gn: 11 gn: 11 gn: 12 gn: 12 gn: 21 gn: 21 gn: 22

gn: 22 gn: 22

Group andnetworkaddresses must match.

UC/BCIaddressesmust match.

Sensor addresses default to 1. If multiple sensors are wired to a UC/BCI, each sensor must have a unique address.

WCS WCS WCS WCSWCS WCS WCSWCS WCS

In this example, UC/BCI 402has two sensors connected to it. So the address of the second sensor must be set to “2”.

For multiple sensor installations, refer to BAS-SVX40*-EN.

Remove the cover

Pull the insulation strip from

between the batteries

RH sensor module

A 2% relative humidity sensor module, available as a separate part (X13790973030; model WCS-SH), can be installed on a WCS either before or after the WCS is powered up.

Install RH sensor module in this location

Set unit controller address

Press to set 1st digit of UC address.

Press Pres

Press to set 2nd digitof UC address.

Press

Press to set 3rd digit of UC address.

Press

Pressto set group address.

Press

Pressto set netaddress.

Set group and net addressPress and hold the Address button

for 3 seconds

Sensor display legend:

: group, network

: unit controller

: wireless sensor

Set sensor address

Press to change sensor number, if multiple sensors are used.

To exit address mode, press the Address button and hold for 3 seconds.After addresses are set, the WCS will immediately attempt to join the network and associate with the controller.Error code E2 will appear on the sensor display until the WCS successfully joins the network. Error code E1 will be displayed until association is successful. You can press the center button twice at any time to cause the WCS to reattempt to join the network and to associate with

Model Number: X13790955010, X13790955040, X13790955050,X13790968010,X13790956010, X13790969010, X13790973010

X39641265001

Page 2: Installation Instructions A 2% relative humidity ... - Trane

8Secure the backplate to a mounting surface

Error Codes

Possible cause Explanation/Resolution

Sensor is not associated with UC (E1)

The configured address in the sensor does not match the dials of a UC for any WCI in the same wireless network. Re-associate the sensor with the WCI by correcting the UC address in the sensor.

Sensor is not communicating (E2)

Normal for sensor configured with GRP-NET 0-0. Verify that the sensor has the correct group (GRP) and network (NET) addresses. Verify that the sensor is within radio range. If the sensor has previously joined the network, verify that WCIs in range are powered up. Press the center button on the front of the sensor twice to force association. Otherwise, set the correct GRP and NET addresses and open the wireless network to allow the sensor to join.

Sensor drains battery current during sleep (E3)

If the error persists and batteries drain prematurely, the sensor may have defective components and need to be replaced.

Internal failure (E7) Sensor display fails to communicate with the radio. Replace the sensor.

Wrong sensor address (E8)

The configured sensor address does not match the sensor address that is expected by the UC. Use Tracer TU to configure the UC for the quantity of sensors it should accept, if more than one.

Duplicate sensor (E9)Another sensor with the same configured UC address and sensor address is already associated with the UC. Resolve the duplication. This may involve waiting (up to 51 minutes) for the UC to forget the address of a failed sensor.

1 2 2

3

45678

9 0 1

3

4567

1 23

456

78

9 0

8

9 0

UC

WCS

Match to UC

ADDRESS

WCI

Testing radio signal quality between the WCS and the WCI, and WCS battery life

Symbol on sensor display Indicates...

Associated but no communication with the WCI.In this situation, only the battery level and error code will appear.

Excellent signal quality• Good signal margin for reliable communication.• Corresponds to a green link on the Tracer TU network health map.

Satisfactory signal quality:• Adequate signal quality for reliable communication.• Corresponds to a yellow link on the Tracer TU network health map.

or

Poor signal quality:• Unreliable communication.• Recommend moving the sensor or the WCI to a better location if the quality remains low for repeated

signal tests.• Corresponds to a red link on the Tracer TU network health map.

100–50% battery life remaining.

50–3% battery life remaining.

Less than 3% battery life remaining.When the remaining battery power is approximately 1%, the battery symbol will flash on the main display screen. In the test mode display screen, the empty battery symbol will not flash.