Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53090021-01 Printed in U.S.A. Form 09/30/38-14SI Pg 1 10-13 Replaces: 09/30/38-11SI Installation Instructions Part No: 30RA-900---064, 30RA-900---065, 30RA-900---066, and 38AP-900---005 PACKAGE USAGE PACKAGE CONTENTS GENERAL This book contains instructions for the installation of the wind baffles used on 09DPS018-030, 09DPM035-130, 30RAP010-150, 38APD025-130, and 38APS025-065 units with Motormaster ® V controls. The Motormaster V control must be purchased separately and is not provided with this kit. Wind baffles must be field installed for all units to ensure prop- er operation at low-ambient temperatures with Motormaster V electronic controller. If the unit is equipped with hail guards, they must be removed before installing the wind baffles. This kit provides factory designed wind baffles for field in- stallation when running the unit at low ambient air tempera- tures. The standard outdoor-air temperature limitation of the 30RAP010-015 chillers is –20 F (–28.0 C). The standard outdoor-air temperature limitation of the 30RAP018-030 chill- ers is 45 F (7.2 C). The standard outdoor-air temperature limita- tion of the 30RAP035-150 chillers is 32 F (0.0° C). The standard outdoor-air temperature limitation of the 38APS025-065 condensing units is 45 F (7.2 C). The standard outdoor-air temperature limitation of the 38APD025-040 and 070-130 condensing units is 32 F (0.0° C). The standard out- door-air temperature limitation of the 38APD050-060 condens- ing units is 25 F (–3.9 C). The standard outdoor-air temperature limitation of the 09DPS and 09DPM units is based on different system factors in- cluding the unit it is paired with, condensing temperature, tem- perature difference, and compressor capacity. The Motormaster V electronic control low ambient opera- tion kit can be used to extend the system operation down to –20 F (–28 C). SAFETY CONSIDERATIONS Installation of this accessory can be hazardous due to sys- tem pressures, electrical components and equipment location. Only trained, qualified installers and service technicians should install, start up, and service this equipment. When installing this accessory, observe precautions in the literature and on tags, stickers, and labels attached to the equip- ment. Follow all safety codes. Wear safety glasses and work gloves. Use care in handling equipment. PREINSTALLATION Inspect the contents of the accessory package before install- ing. File a claim with the shipper if shipping damage is found or contact your Carrier representative if any parts are missing. See Package Contents table for kit package contents. INSTALLATION NOTE: Pre-drilled holes may not be provided. Drill pilot holes as necessary using the bracket as a template. All Units Sizes 010 to 060 — To install the accessory wind baffles, perform the following procedure: 1. Install the 3 brackets to the side of the unit using screws provided. See Fig. 1-3 for location. ACCESSORY PART NUMBER QUANTITY UNITS 30RA-900---064 1 30RAP010,015 30RA-900---065 1 09DPS018,020 30RAP018,020 38APD025 38APS025 2 09DPM035-050 30RAP035,040 30RA-900---066 1 09DPS030 30RAP025,030 38APD027-030 38APS027-030 2 09DPM060 30RAP045-060 38APD040-060 38APS040,050 38AP-900---005 1 09DPM065-130 30RAP070-150 38APS065 38APD070-130 ACCESSORY PART NUMBER CONTENTS DESCRIPTION QUANTITY 30RA-900---064, 30RA-900---065, 30RA-900---066 Baffle Plate 1 Baffle Plate 1 Bracket 3 Support Bracket 2 Screws 36 or 40 38AP-900---005 Baffle Plate 1 Screw 12 WARNING Disconnect all power to the unit before performing mainte- nance or service. Electrical shock and personal injury could result. CAUTION To avoid damage to refrigerant coils and electronic compo- nents, use extreme care when drilling screw holes and attaching fasteners. 09DPS018-030, 09DPM035-130 30RAP010-150 38APD025-130, 38APS025-065 Wind Baffle Accessory

Installation Instructions · 30RAP025,030 38APD027-030 38APS027-030 2 09DPM060 30RAP045-060 38APD040-060 38APS040,050 38AP-900---005 1 09DPM065-130 30RAP070-150 38APS065 38APD070-130

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Installation Instructions · 30RAP025,030 38APD027-030 38APS027-030 2 09DPM060 30RAP045-060 38APD040-060 38APS040,050 38AP-900---005 1 09DPM065-130 30RAP070-150 38APS065 38APD070-130

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Catalog No. 04-53090021-01 Printed in U.S.A. Form 09/30/38-14SI Pg 1 10-13 Replaces: 09/30/38-11SI

Installation InstructionsPart No: 30RA-900---064, 30RA-900---065, 30RA-900---066, and 38AP-900---005

PACKAGE USAGE

PACKAGE CONTENTS

GENERALThis book contains instructions for the installation of the

wind baffles used on 09DPS018-030, 09DPM035-130,30RAP010-150, 38APD025-130, and 38APS025-065 unitswith Motormaster® V controls. The Motormaster V controlmust be purchased separately and is not provided with this kit.Wind baffles must be field installed for all units to ensure prop-er operation at low-ambient temperatures with Motormaster Velectronic controller. If the unit is equipped with hail guards,they must be removed before installing the wind baffles.

This kit provides factory designed wind baffles for field in-stallation when running the unit at low ambient air tempera-tures.

The standard outdoor-air temperature limitation of the30RAP010-015 chillers is –20 F (–28.0 C). The standardoutdoor-air temperature limitation of the 30RAP018-030 chill-ers is 45 F (7.2 C). The standard outdoor-air temperature limita-tion of the 30RAP035-150 chillers is 32 F (0.0° C).

The standard outdoor-air temperature limitation of the38APS025-065 condensing units is 45 F (7.2 C). The standard

outdoor-air temperature limitation of the 38APD025-040 and070-130 condensing units is 32 F (0.0° C). The standard out-door-air temperature limitation of the 38APD050-060 condens-ing units is 25 F (–3.9 C).

The standard outdoor-air temperature limitation of the09DPS and 09DPM units is based on different system factors in-cluding the unit it is paired with, condensing temperature, tem-perature difference, and compressor capacity.

The Motormaster V electronic control low ambient opera-tion kit can be used to extend the system operation down to–20 F (–28 C).

SAFETY CONSIDERATIONS

Installation of this accessory can be hazardous due to sys-tem pressures, electrical components and equipment location.

Only trained, qualified installers and service techniciansshould install, start up, and service this equipment.

When installing this accessory, observe precautions in theliterature and on tags, stickers, and labels attached to the equip-ment.• Follow all safety codes.• Wear safety glasses and work gloves.• Use care in handling equipment.

PREINSTALLATIONInspect the contents of the accessory package before install-

ing. File a claim with the shipper if shipping damage is foundor contact your Carrier representative if any parts are missing.See Package Contents table for kit package contents.

INSTALLATION

NOTE: Pre-drilled holes may not be provided. Drill pilot holesas necessary using the bracket as a template.

All Units Sizes 010 to 060 — To install the accessorywind baffles, perform the following procedure:

1. Install the 3 brackets to the side of the unit using screwsprovided. See Fig. 1-3 for location.

ACCESSORYPART NUMBER QUANTITY UNITS

30RA-900---064 1 30RAP010,015

30RA-900---0651

09DPS018,02030RAP018,020

38APD02538APS025

2 09DPM035-05030RAP035,040

30RA-900---066

1

09DPS03030RAP025,03038APD027-03038APS027-030

2

09DPM06030RAP045-06038APD040-06038APS040,050

38AP-900---005 1

09DPM065-13030RAP070-150

38APS06538APD070-130

ACCESSORYPART NUMBER

CONTENTSDESCRIPTION QUANTITY

30RA-900---064,30RA-900---065,30RA-900---066

Baffle Plate 1Baffle Plate 1Bracket 3Support Bracket 2Screws 36 or 40

38AP-900---005Baffle Plate 1Screw 12

WARNING

Disconnect all power to the unit before performing mainte-nance or service. Electrical shock and personal injury couldresult.

CAUTION

To avoid damage to refrigerant coils and electronic compo-nents, use extreme care when drilling screw holes andattaching fasteners.

09DPS018-030, 09DPM035-13030RAP010-150

38APD025-130, 38APS025-065Wind Baffle Accessory

Page 2: Installation Instructions · 30RAP025,030 38APD027-030 38APS027-030 2 09DPM060 30RAP045-060 38APD040-060 38APS040,050 38AP-900---005 1 09DPM065-130 30RAP070-150 38APS065 38APD070-130

2

SUPPORT BRACKETBRACKETS

BAFFLEPLATE

SUPPORTBRACKET

Fig. 1 — Baffle Location and Assembly — 30RAP010,015 Units (Part No. 30RA-900---064)

a30-5634

NOTE: Dimensions are in inches.

BRACKETS

BAFFLEPLATES

SUPPORTBRACKET

SUPPORTBRACKET

BRACKETS BAFFLEPLATES

SUPPORTBRACKET

BAFFLEPLATES

BRACKETS

NOTE: Dimensions are in inches.

Fig. 2 — Baffle Location and Assembly — 09DPS018-020 Units, 09DPM035-050 Units,30RAP018,020 Units, 30RAP035,040 Units, 38APD025, and 38APS025 (Part No. 30RA-900---065)

a30-5635

Page 3: Installation Instructions · 30RAP025,030 38APD027-030 38APS027-030 2 09DPM060 30RAP045-060 38APD040-060 38APS040,050 38AP-900---005 1 09DPM065-130 30RAP070-150 38APS065 38APD070-130

3

2. Install 2 support brackets on the end brackets usingscrews provided.

3. Install baffle plates on to the brackets installed in Step 1using the screws provided.

4. For size 035-060 units, repeats Steps 1-4 to install the sec-ond accessory wind baffle on the other side of the unit.

All Units Sizes 065-150 — To install the accessorywind baffle, install the baffle plate on the end of the unit oppo-site the control panel, using the screws provided. See Fig. 4 fordimensions. See Fig. 5 for location.

BRACKETS

BAFFLEPLATES

SUPPORTBRACKET

SUPPORTBRACKET

BAFFLEPLATES

BRACKETS

BRACKETS

SUPPORTBRACKET

NOTE: Dimensions are in inches.

Fig. 3 — Baffle Location and Assembly — 09DPS030 Units; 09DPM060 Units; 30RAP025,030 Units; 30RAP045-060 Units; 38APD027-060 Units; and 38APS027-050 Units (Part No. 30RA-900---066)

a30-5636

Page 4: Installation Instructions · 30RAP025,030 38APD027-030 38APS027-030 2 09DPM060 30RAP045-060 38APD040-060 38APS040,050 38AP-900---005 1 09DPM065-130 30RAP070-150 38APS065 38APD070-130

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.Catalog No. 04-53090021-01 Printed in U.S.A. Form 09/30/38-14SI Pg 4 10-13 Replaces: 09/30/38-11SI

© Carrier Corporation 2013

74.00

27.50

TYP0.50

TYP1.07

2 SPA @ 12.13 = TYP

24.26

TYP0.62

2.05

TYP0.62

TYP0.62

1.00 TYP0.45

14.13

29.69

44.33

59.89

2X R0.156

REF1.07

71.95

TYP1.28

REF0.25

TYP3.00TYP

68.00

9.00

18.00

10X 0.312

8X 45 X CHAMFEROR 0.25 RTO SIUT TOOLING

0.13

SEE DETAIL A

B

B

B

B

DETAIL A

STIFFENING RIBTO SUIT TOOLING

SECTION B-B

NOTE: Dimensions are in inches.

Fig. 4 — Baffle Dimensions — 09DPM065-130 Units, 38APD070-130 Units, 38APS065 Units, and 30RAP070-150 (Part No. 38AP-900---005)

BAFFLEINSTALLATIONLOCATION

Fig. 5 — Baffle Installation Location — 09DPM065-130 Units, 38APD070-130 Units,38APS065 Units, and 30RAP070-150 (Part No. 38AP-900---005)