Upload
john-williams-rosas-solier
View
220
Download
0
Embed Size (px)
Citation preview
8/20/2019 Installation Guide 01 - Parte 3
1/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 8 (Optional) Installing Batteries and Cables
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
68
8 (Optional) Installing Batteries and Cables
l Smoking and sparks are prohibited near batteries.
l Switch off battery circuit breakers before installing batteries.
l Comply with regulations and warnings of the battery manufacturer.
l Use tools with insulated handles, otherwise, batteries may be burnt out and personal injurymay occur.
l During battery operations, wear goggles, rubber gloves, and protective clothes. Remove
conductive articles such as watches, bracelets, and rings.
l If battery acid gets in the eyes, rinse with cold water for more than 15 minutes and seekmedia advice immediately. If battery acid contacts skin or clothing, wash with soap and
water immediately.
l
Do not use metal to simultaneously contact two or more battery terminals. Do not usemetal to simultaneously touch battery terminals and grounded objects (for example,
battery compartment); otherwise, transient short circuit occurs, which produces sparks or
explosion.
l During battery installation, never short-circuit or reversely connect positive and negative battery terminals. Connect the negative battery cable before the positive battery cable.
l Secure battery cables to a torque specified in battery documentation. Loose connections
will result in excessive voltage drop or cause batteries to burn out when the current is
large.
The following describes how to install the first layer of battery. All batteries are installed in
the same manner. Figure 8-1 shows battery installation completed.
8/20/2019 Installation Guide 01 - Parte 3
2/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 8 (Optional) Installing Batteries and Cables
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
69
Figure 8-1
Battery installation completed
8.1 (Optional) Installing Antitheft Baffle Plate Bases forthe Battery Cabinet
Procedure
Step 1 Remove screw caps from the position for installing antitheft baffle plate bases on the battery
cabinet.
Step 2 Install the antitheft baffle plate bases on the cabinet.
8/20/2019 Installation Guide 01 - Parte 3
3/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 8 (Optional) Installing Batteries and Cables
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
70
Figure 8-2
Installing antitheft baffle plate bases
----End
8.2 Installing Busbars
Prerequisites
Install busbars when there are two battery cabinets.
Procedure
Step 1 Take out positive and negative busbars from the fitting bag, and remove insulation covers.
Properly store the covers and reinstall them after installing battery cables.
Step 2
Remove screw caps from the position for installing battery cabinet busbars.
Step 3 Install two negative busbars on the left panels of two battery cabinets respectively.
8/20/2019 Installation Guide 01 - Parte 3
4/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 8 (Optional) Installing Batteries and Cables
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
71
Step 4
Install two positive busbars on the right panels of two battery cabinets respectively, as shownin Figure 8-3.
Figure 8-3
Installing busbars
(1) Negative busbar (2) Positive busbar
----End
8/20/2019 Installation Guide 01 - Parte 3
5/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 8 (Optional) Installing Batteries and Cables
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
72
8.3 Installing Battery Strings
Prerequisites
Ensure that batteries are from the same manufacturer and of the same model and have a close
voltage. New and old batteries cannot be used together.
Procedure
Step 1
Install batteries into the battery compartment in the sequence shown in Figure 8-4.
Figure 8-4
Installing battery strings
----End
8.4 Installing Copper Bars Between Batteries
Procedure
Step 1
Remove the insulation cover from the batteries.
Step 2
Install copper bars between batteries.
Step 3
Reinstall the insulation covers onto the two batteries in the middle.
8/20/2019 Installation Guide 01 - Parte 3
6/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 8 (Optional) Installing Batteries and Cables
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
73
Figure 8-5
Installing copper bars between batteries
----End
8.5 Installing Battery Cables (One Battery Cabinet)Prerequisites
When installing battery cables, install the negative cable before the positive cable.
Procedure
Step 1
Lay out battery cables. Secure one end of a negative battery cable to the battery circuit breaker on the power cabinet, and the other end to the negative battery terminal.
After you install all negative battery cables, install positive battery cables.
8/20/2019 Installation Guide 01 - Parte 3
7/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 8 (Optional) Installing Batteries and Cables
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
74
Step 2
Secure one end of a positive battery cable to the RTN+busbar on the power cabinet, and the
other end to the positive battery terminal.
Step 3
Reinstall insulation covers for batteries on the left and right.
Figure 8-6 Installing battery cables (using the TP48200A-HX09A5 as an example)
----End
8.6 Installing Battery Cables (Two Battery Cabinets)
Prerequisites
When installing battery cables, install the negative cable before the positive cable.
8/20/2019 Installation Guide 01 - Parte 3
8/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 8 (Optional) Installing Batteries and Cables
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
75
Procedure
Step 1
Take out two negative battery cables. Connect one end of the cables to the negative busbarsfor two battery cabinets and the other end to battery circuit breakers on the battery cabinet.
Step 2 Take out four negative battery cables. Connect one end of the cables to negative busbars on
two battery cabinets and the other end to negative battery terminals.
Figure 8-7 Installing negative battery cables
After you install all negative battery cables, install positive battery cables.
8/20/2019 Installation Guide 01 - Parte 3
9/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 8 (Optional) Installing Batteries and Cables
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
76
Step 3
Take out two positive battery cables. Connect one end of the cables to positive busbars on two
battery cabinets and the other end to the RTN+ busbar on the power cabinet.
Step 4
Take out four positive battery cables. Connect one end of the cables to positive busbars ontwo battery cabinets and the other end to positive battery terminals.
Figure 8-8
Installing positive battery cables
Step 5
Reinstall insulation covers for batteries on the left and right.
Step 6
Reinstall the insulation covers for the busbars on the left and right of the battery cabinet, asshown in Figure 8-9.
8/20/2019 Installation Guide 01 - Parte 3
10/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 8 (Optional) Installing Batteries and Cables
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
77
Figure 8-9
Installing insulation covers for busbars
----End
8.7 (Optional) Installing Antitheft Baffle Plates for the
Battery Cabinet
Procedure
Step 1
Install antitheft baffle plates on the antitheft baffle plate bases for the battery cabinet, as
shown in Figure 8-10.
8/20/2019 Installation Guide 01 - Parte 3
11/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 8 (Optional) Installing Batteries and Cables
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
78
Figure 8-10
Installing an antitheft baffle plate
----End
8/20/2019 Installation Guide 01 - Parte 3
12/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 9 Verifying the Installation
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
79
9 Verifying the Installation9.1 Checking Hardware Installation
l Check that all screws, especially those used for electrical connections, are secured.
Check that flat washers and spring washers are installed properly.l Check that rectifiers are completely inserted into their respective slots and properly
locked.
9.2 Checking Electrical Connectionsl Check that all circuit breakers are switched off.
l Check that flat washers and spring washers are securely installed for all the OT terminalsand that all the OT terminals are intact and properly connected.
l Check that batteries are correctly installed and that battery cables are correctly connected
without being short circuited.
l Check that input and output power cables and ground cables are correctly connectedwithout being short circuited.
9.3 Checking Cable Installationl Check that all cables are securely connected.
l Check that all cables are arranged neatly and bound properly to their nearest cable ties
without being distorted or excessively bent.
l Check that cable labels are properly and securely attached in the same direction.
8/20/2019 Installation Guide 01 - Parte 3
13/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 10 Commissioning
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
80
10 Commissioning
l The following commissioning procedure may result in power failure or alarm generation.Inform the alarm center before and after the procedure.
l The commissioning involves various technologies. Only trained personnel are allowed to
perform commissioning. Perform operations strictly in compliance with commissioninginstructions.
l The commissioning is performed with power on. During commissioning, stand on dry
insulating objects, and remove conductive articles such as watches and rings. Use
insulated tools.
l During operations, do not contact two electric bodies that have different currents.
l During commissioning, check that the status of the related unit or component meets
requirements before turning on any switch.
l When you are performing operations and do not want others to operate, attach the label
"Do not turn on the switch because operations are in process." to the power distributiondevice.
l During commissioning, shut down the device immediately if any fault is detected. Rectify
the fault and proceed with the commissioning.
10.1 Connecting the AC Power Supply
Procedure
Step 1
Measure the input voltage on the AC input circuit breaker. The value should range from 85 VAC to 300 V AC.
Step 2
Switch on the AC input circuit breaker and measure the output voltage of the AC input circuit breaker. The value should range from 85 V AC to 300 V AC.
Step 3
Check that the indicators on the rectifiers are steady on.
Step 4
Measure the voltage between the -48 V busbar and the RTN+ busbar. The value should range
from -42 V DC to -58 V DC.
8/20/2019 Installation Guide 01 - Parte 3
14/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 10 Commissioning
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
81
----End
10.2 Setting the Display Language
After powering on the SMU, select English by pressing or on the LCD, and then
press to enter the standby screen.
If you select an undesired language, remove and then insert the SMU. Select a language again after theSMU restarts.
10.3 Setting the AC Input SystemIf the AC input system is dual-live wire, set the AC input system to single-phase on the LCD,as shown in Table 10-1.
If the AC input system is single-/three-phase, set the AC input system as required, as shown inTable 10-2.
Table 10-1 Setting a dual-live wire AC input system
MainMenu
Second-
LevelMenu
Third-
LevelMenu
Fourth-
LevelMenu
Default Setting
Parameters
Settings
Power
System
Basic
ParametersAC Type Single-Phase Single-Phase
Table 10-2
Setting a single- or three-phase AC input system
MainMenu
Second-
LevelMenu
Third-
LevelMenu
Fourth-
LevelMenu
Default Setting
Parameters
Settings
Power
System
Basic
ParametersAC Type Three
Phases
Both the
single-phaseand
three-phase
inputsystems are
available.
Set to thelocal input
system.
8/20/2019 Installation Guide 01 - Parte 3
15/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 10 Commissioning
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
82
10.4 Setting the Date and Time
l The LCD screen becomes dark if no button is pressed within 30 seconds.
l You need to log in again if no button is pressed within 1 minute.
l
The preset user name is admin and the preset password is 000001.
Set the date and time as required.
Table 10-3 Setting the date and time
Main Menu Second-LevelMenu
Third-LevelMenu
Default Value Setting
Setting Wizard Date and Time
NOTE
The date and
time varyaccording to
time zones. Setthe time zone,
date, and time based on the
local situation.
Date and Time - Set to the local
date and time.
Time Zone UTC +08:00
Beijing
Set to the local
time zone.
NTP Enable No Yes/No
NOTE
Set the
parameter to
Yes if you needto synchronize
the SMU time
and the site
network servertime.
10.5 Setting Battery ParametersSet the Battery N Connected , Rated Capacity and Installation Timeas required.
Table 10-4 Setting battery parameters
MainMenu
Second-
LevelMenu
Third-
LevelMenu
Fourth-
LevelMenu
Default Value Setting Value
Parameters
SettingsBattery Basic
Parameters
Battery 1
ConnectedYes If N battery
strings are
connected, setBattery 1Connected to
Battery N
Connected toYes, and set the
other parameters to
Battery 2
ConnectedYes
8/20/2019 Installation Guide 01 - Parte 3
16/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 10 Commissioning
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
83
MainMenu
Second-
LevelMenu
Third-
LevelMenu
Fourth-
LevelMenu
Default Value Setting Value
No.
RatedCapacity
150 Ah Rated capacityof the batteriesin a battery
string.
NOTE
The batteries
controlled byone circuit
breaker or fuse
are called a
battery string.
Other
Parameters
Installation
Time- Set to the
current date
l If battery routes 1 and 2 are respectively connected to a battery string (each battery string consists of
four 12 V, 150 Ah batteries in series), set Battery1 Connected and Battery2 Connected to Yes and
others to No, and set Rated Capacity to 150 Ah.
l If battery route 1 is connected to two battery strings in parallel (each battery string consists of four
12 V, 150 Ah batteries in series), set Battery1 Connected to Yes and others to No, and set Rated
Capacity to 300 Ah.
10.6 (Optional) Setting the Hibernation ParameterSet Hibernation Enable to Yes if you need to use the intelligent hibernation function of therectifiers.
Table 10-5 Setting the hibernation parameter
Main Menu Second-LevelMenu
Third-LevelMenu
Default Setting
ParametersSettings
Energy Saving HibernationEnable
No Yes
10.7 (Optional) Setting Sensor ParametersSet sensor parameters based on site requirements.
8/20/2019 Installation Guide 01 - Parte 3
17/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 10 Commissioning
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
84
Table 10-6
Sensor parameter settings
MainMenu
Second-
Level Menu
Third-
Level Menu
Fourth-
Level Menu
DefaultValue
Setting
Parameters
Settings
Power System Sensor
Config. Para.
Water Sensor None Set to Yes
or No asrequired.Smoke Sensor None
Ambient Temp.
Sensor None
Ambient Humi.
Sensor None
10.8 Setting Communications Parameters
10.8.1 Setting Parameters Before Using WebUI Management
Procedure
Step 1 Apply to the site or equipment room network administrator for a fixed IP address.
Step 2 Set the IP address, subnet mask, and gateway on the LCD, as shown in Table 10-7.
Table 10-7 IP parameters
MainMenu
Second-
LevelMenu
Third-
Level Menu
Default Value Setting
Setting
Wizard
Network
ParametersIP Address 192.168.0.10 Set this parameter
according to the IP address
assigned by the network
administrator.
Subnet Mask 255.255.255.0 Set this parameter
according to the subnet
mask provided by the
network administrator.
Default
Gateway192.168.0.1 Set this parameter
according to the gateway
address provided by thenetwork administrator.
----End
8/20/2019 Installation Guide 01 - Parte 3
18/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 10 Commissioning
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
85
10.8.2 (Optional) Setting Parameters Before Using the NetEcoManagement
Networking Mode 1: over FE Port
Step 1
Apply to the site or equipment room network administrator for a fixed IP address.
Step 2 Set the IP address, subnet mask, and gateway on the LCD, as shown in Table 10-8.
Table 10-8
IP parameters
MainMenu
Second-
LevelMenu
Third-
Level Menu
Default Value Setting
Setting
Wizard
Network
ParametersIP Address 192.168.0.10 Set this parameter
according to the IP addressassigned by the network
administrator.
Subnet Mask 255.255.255.0 Set this parameter
according to the subnet
mask provided by thenetwork administrator.
Default
Gateway192.168.0.1 Set this parameter
according to the gateway
address provided by the
network administrator.
Step 3
Set the IP Addresses and Ports for the active and standby servers of the NetEco on the LCD,as described in Table 10-9.
Table 10-9
NetEco parameters
MainMenu
Second-
LevelMenu
Third-
LevelMenu
Fourth-
LevelMenu
DefaultValue
Setting
Parameters
Settings
Comm.
Parameters
Network
Parameters
NetEco
Primary IP192.168.0.10 Set an IP
address for
the active NetEco
server.
NetEco
Backup IP192.168.0.10 Set an IP
address for
the standby NetEco
server.
NetEco Port
Number31220 Set a port for
the NetEco.
8/20/2019 Installation Guide 01 - Parte 3
19/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 10 Commissioning
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
86
----End
Networking Mode 2: over RS485 Port
Step 1
Check that the following parameters are set properly: Port Mode to Manual, Protocol Type
to M/S Protocol, Baud Rate to 9600, and Comm. Address to 3.
Table 10-10 Communications parameters
MainMenu
Second-
LevelMenu
Third-
LevelMenu
Fourth-
LevelMenu
Fifth-
LevelMenu
DefaultValue
Setting
Parameters
Settings
Comm.
Parameters
Serial
Port Northbound Port
ModeManual Manual
Protocol
Type
M/S
Protocol
M/S
Protocol
M/SProtocol
Northbound BaudRate
9600 9600
Comm.
Address3 3
----End
10.8.3 (Optional) Setting Parameters Before Using the SNMPManagement
Prerequisites
Before setting SNMP parameters, obtain the information listed in Table 10-11 from the NMS.
Table 10-11
Information obtained from the NMS
Information Description
SNMP version SNMP version and port number used by the SMU and NMS.The SNMP versions include SNMPv1, SNMPv2c, and
SNMPv3.SNMP Port Number
Read Community Name If you use SNMPv1 or SNMPv2c, enter the read community
name and write community name that comply with the NMS.Otherwise, the SMU will not connect to the NMS.Write Community Name
User Name To enhance the security, you need a user name and password
for authentication if you use SNMPv3. After the authentication
succeeds, the SMU can communicate with the NMS.MD5 Password
DES Password
8/20/2019 Installation Guide 01 - Parte 3
20/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 10 Commissioning
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
87
Information Description
Trap Target Address IP address and port number reported in the alarm trap.
Trap Port
Procedure
Step 1
Apply to the site or equipment room network administrator for a fixed IP address.
Step 2
Set the IP address, subnet mask, and gateway on the LCD, as shown in Table 10-12.
Table 10-12
IP parameters
MainMenu
Second-
LevelMenu
Third-
Level
Menu
Default Value Setting
Setting
Wizard
Network
ParametersIP Address 192.168.0.10 Set this parameter
according to the IPaddress assigned by the
network administrator.
Subnet Mask 255.255.255.0 Set this parameter
according to the subnet
mask provided by thenetwork administrator.
Default
Gateway192.168.0.1 Set this parameter
according to the gateway
address provided by the
network administrator.
Step 3
Enter the IP address for the SMU in the address box of Internet Explorer. Log in to theWebUI on the login page shown in Figure 10-1.
l The preset user name is admin and the preset password is Changeme.
l You can set SNMP parameters on the WebUI locally or remotely.
8/20/2019 Installation Guide 01 - Parte 3
21/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 10 Commissioning
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
88
Figure 10-1
Login page
Step 4 On the System Settings tab page, select SNMP.
l If the SNMP version is SNMPv1 or SNMPv2c, set SNMP Version to
SNMPv1&SNMPv2c under SNMP, and then set SNMP Port Number, ReadCommunity Name, and Write Community Name, as shown in Figure 10-2.
Figure 10-2 Setting SNMPv1 and SNMPv2c parameters
l If the SNMP version is SNMPv3, set SNMP Version to SNMPv3 under SNMP, click
Add under SNMPv3, and then set User Name, MD5 Password, and DES Password, as
shown in Figure 10-3.
8/20/2019 Installation Guide 01 - Parte 3
22/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 10 Commissioning
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
89
Figure 10-3
Setting SNMPv3 parameters
Step 5 Under SNMP Trap, set Trap Target Address and Trap Port.
Step 6
Under Mib files, click Export to export the Mib file and import it to the NMS.
If there is only one NMS, perform Step 6 once.
----End
Follow-up Procedure
You can query the power system operating status, active alarms, and the names ofuser-defined dry contact inputs, and configure dry contact outputs on the NMS that is
connected over the SNMP.
10.9 Connecting the Battery Supply
Prerequisites
To avoid damage to batteries, switch on the battery circuit breaker only after you correctly set
battery parameters.
Procedure
Step 1
Switch off AC input circuit breakers.
8/20/2019 Installation Guide 01 - Parte 3
23/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide 10 Commissioning
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
90
Step 2
Switch on the battery circuit breaker.
Step 3
Switch on AC input circuit breakers.
Step 4 Switch all the circuit breakers to the appropriate status based on site requirements.
Step 5
Observe the power system for 15 minutes. If no alarm (excluding door alarms) is generated on
the LCD during this period, the voltage and current for batteries and loads are normal.
l Before delivery, the battery switch is set to AUTO and the system is under automaticcontrol.
l Open the cover and flip the battery switch to MANUAL only when you need to forcibly
connect the battery supply. Flip the battery switch back to AUTO after commissioning.
Figure 10-4 Battery switch
(1) Battery switch (behind the cover)
----End
10.10 Subsequent Operations
Procedure
Step 1
Reinstall the removed cover or panel (if there is).
Step 2
Fasten package entry module.
Step 3
The paint on the surface of the cabinet should be kept intact. Therefore, any damaged paintmust be repaired.
Step 4
Lock the cabinet door and hand over the key to the administrator. Clean the site and leave.
----End
8/20/2019 Installation Guide 01 - Parte 3
24/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide
A Associations Between Alarms and Dry Contacts on the
UIM
Issue 01 (2014-07-09) Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
91
A Associations Between Alarms and DryContacts on the UIM
Table A-1 Associations between dry contacts and alarms
Dry ContactType
Silkscreen Associated Alarm
Dry contact inputs DIN1 Dry contact input 1
DIN2 Dry contact input 2
DIN3 Dry contact input 3
DIN4 Dry contact input 4
DIN5 Dry contact input 5
DIN6 Dry contact input 6
Dry contactoutputs
The default setting
(closed: alarm;open: normal) can
be modified.
ALM1 Mains failure
ALM2 DC over/undervoltage
ALM3 Rectifier faults
ALM4 AC or DC SPD faults
ALM5 Load fuse blown, battery fuse blown, or loop
disconnection
ALM6 Battery over/undertemperature
ALM7 Door status alarm
ALM8 Heater/Air conditioner/Fan fault
alarm/Temperature control high temperature
alarm
8/20/2019 Installation Guide 01 - Parte 3
25/25
TP48200A-HX09A5 & HX09A6 & HX09A7 &
DX09A2 & TBC300A-DCA6 & DCA7 & TCA3
Installation Guide B Acronyms and Abbreviations
B Acronyms and AbbreviationsB
BBU Building base band unit
F
FE Fast Ethernet
H
HAU Heater Assembly Unit
HTTPS Hypertext Transfer Protocol Secure
L
LCD Liquid crystal display
S
SMU Site monitor unit
SNMP Simple Network Management Protocol
T
TCUC Temperature control unit C
U
UIM User interface module