MODEL 2002 TYPE X RAPID EXCHANGE ® PURGE SYSTEM PROCESS AUTOMATION INSTALLATION AND OPERATION MANUAL

Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

MODEL 2002 TYPE X RAPID EXCHANGE® PURGE SYSTEM

PROCESS AUTOMATION

INSTALLATION AND OPERATION MANUAL

Page 2: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

2

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

Table of Contents

Page 2 System Purpose and Description Purpose,Systemdescription,Importantnotes

Page 3 Identifying Your System Definesspecificfeaturesofthesystem

Page 3 General Information System&materialspecifications,Spareparts,Tools

&testequipment,Systemaccessories

Page 4 Enclosure and Device Design Designrequirements,Adjacentenclosures,Device

ventilation,Temperaturelimitations

Page 5 Installation Overview Installationdiagram

Page 6 Getting Started Establishingconnectionsizes,Determiningenclosure

inlet&outletconnectionlocations

Page 7 System Mounting LH,RH,TM,BM&WMconfigurations,

FM&PMconfigurations

Page 8 Hardware Mounting Enclosureprotectionvent,Warningnameplates

Page 9 Mounting Plate Dimensions Mountingplatedimensiondiagrams

Page 10 Pneumatic Tubing Requirements Protectivegassupplyrequirements,Pneumatic

connectionrequirements

Page 12 Tubing Connection Points LH,RH,TM,BM,WM,FM,&PMconfigurations

Page 13 Tubing Installation LH,RH,TM,BM,WM,FM&PMTubing

configurations

Page 14 Electrical Supply Requirements Generalwiringrequirements,EPCUpower&alarm

signal,Enclosurewiringmethods&connections

Page 15 Electrical Power Control Unit Generallayout&conduitconnectionpoints

Page 16 EPCU Power Rating Powerratingnameplate,Assembledelectronics

Page 17 Electrical & Pneumatic Diagrams LH,RH,TM,BM,WM,FM,&PMconfigurations

Page 18 Conduit Installation EPCUelectricalconduit,Optionalintrinsicsafety

BarrierconduitandEPCUconduitconnectionparts

Page 19 Power Modules & Wiring Diagram EPCU120/220VAC&24-48VDCpowermodules

Page 20 Logic Module & Barrier Wiring OptionalISBwiringrequirements&diagram,EPCU

powercontrolmodes

Page 21 Barriers & Field Adjustments ISBdescription&factoryprogramming,LEDdisplay

indicators,Timerfunctions&settings

Page 22 Set-Up Procedure RapidExchangepurgingset-up

Page 23 Set-Up Procedure (cont.) RapidExchangepurgingset-up

Page 24 Operating Sequence ClassIpurgingoperation

Page 25 Troubleshooting Procedures

Page 26 Warranty and Liability Statements Warrantynotes,Generalterms,Limitations

Page 27 Customer Notes

Page 30 System Maintenance

Page 31 Systems Identification & Application Information

Purpose and Description

PurposePepperl+Fuchs'BebcoEPSSystemallowstheuseofgeneral-purposeornonratedelectricalorelectronicdevices,withexceptiontodevicesthatproduceexcessiveheat,utilizecombustiblegas,orexposearcingcontactstothehazardousatmosphere,inNEMA(NationalElectricalManufacturersAssociation)4or12enclosuresintheplaceofexplosionproofNEMA7enclosures.Otherpurposesincludeheat,moistureanddustcontaminationprevention.

DescriptionModel2002RapidExchangepurgingsystemoperatesonasupplyofcompressedinstrumentairorinertgas.Itregulatesandmonitorspressureofsealed(protected)enclosure(s),inordertorapidlyremoveandpreventflammablevaporaccumulationwithintheenclosure(s).Thesystemisdesignedtoaccomplishfourairexchangesandmaintaina"safe"(0.25")pressureononeormoreenclosuresnotexceedingatotalvolumeoffifteencubicfeet.AnEPV-2enclosureprotectionventisrequiredforproperoperation.Inaddition,thesystemincludesanelectricalpowercontrolunit(EPCU)thatmonitorssystemoperationandcontrolsenclosurepower.Allstart-uprequirementsmustbesatisfiedbeforetheEPCUwillenergizepowertotheenclosure(s).Thisprocessreducesthehazardous(classified)arearatingwithintheenclosure(s),inaccordancewiththeNEC-NFPA70,Article500,NFPA496andISA12.4.

Important NotesOne(1)permanentfilecopyandone(1)operationscopyofthismanualmustbestudiedandretainedbytheoperatorofthissystem.User’sagentsareresponsiblefortransferringthismanualtotheuser,priortostart-up.

Thecontentsofthismanualhavebeenarrangedtoallowtheuseofthisproductasastand-alonedeviceonequipmentandenclosuressuppliedbytheuseroritsagents.Themanual’sparametersencompassacombinationofbothNationalFireProtectionAssociation(NFPA)requirementsandPepperl+Fuchs,Inc.requirements.Pepperl+FuchsthereforeacknowledgestheuseofNFPA496asaguideline,thatwehaveenhancedcertainNFPArequirementsandthatadditionalinformationhasbeencompiledtocompletethisdocument.Themanualisintendedasacompleteguideandmustbeconsidered,unlessspecificallystatedotherwise,thatalldirectivescontainedhereinarerequirementsforsafe,practicalandefficientuseofthisproduct.

Thissystemisnotintendedforusetoprotectenclosuresordevicesthatcontainignitableconcentrationsofgasesorvapors.Thisexclusiongenerallyappliestoprocessorproductanalyzingsystemsequipment.

All specifications are subject to change without notice.

Page 3: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

3

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09Identifying Your System

Thisenclosureprotectionsystemisofferedinvariousstyles.Forproperinstallationandoperation,examinethesystemmodelnumbernameplatetoidentifythesystemstyle,areaclassification,andtype,asnotedbelow.

NOTE: Only FM certified Group B system available in STD style

General Information

System SpecificationsSystemdimensions: SeePages9&10Shippingweight(lbs.): STD-45/SA&FA-47Operatingtemp.range: -20°F-120°FSupplypressurerange: 80-120psimax.

Whenusingtheoptionalinlinefilter,max.supplypressureis80psiCapacity&filtration: 1.5oz.@20micronsSupplyrequirements: CleanairorinertgasSafepressuresetpoint: 0.25"@safepress.Safepressureflowrate: *0.1-3.5SCFHExchangepressure: 3"-5"Exchangeflowrate: **4SCFM/240SCFHExchangetime: 1minute/cubicft.Systemsupplyport: 1/4"FPTEnclosuresupplyfitting: 1/4"tubefittingEnclosurereferencefitting: 1/4"tubefittingEPCUConduitportsize: 1/2"FPTEPCUpowerfequirements: 120VAC60Hz1Ø(European220voltageonly) 240VAC50Hz1ØEPCUpowerconsumption: 500mA

Powerrelaycontacts: 20Amps@240VAC 20Amps@28VDC [email protected]: 20Amps@240VAC [email protected]: 15Amps@240VAC 10Amps@28VDC

* Enclosureintegritydeterminesactualflowrate

**Withregulatorsetto60psimin.duringexchange

Material SpecificationsFilterregulatorbody: Zincw/enamelfinishRegulatorhandle&bowl: PolycarbonateEnclosurepressuregauge: Alum.w/enamelfinishRapidexchangegauge: Polycase&brasstubeRapidexchangesolenoid: Brassw/enamelfinishTubefittings&valves: 316SSforgedbodyTubing: 316SS1/4".035weldedSystemnameplates: SilkscreenedLexan®&SSFastenerhardware: SSscrews&boltsMountingplate: 31614ga#3brushSSEPCUenclosurebody: Beadblastcastalum.Conduit&fittings(SA&FA): GalvanizedsteelEnclosurewarningnameplate: SilkscreenedSS

Lexan®isaregisteredtrademarkoftheGeneralElectricCorporation

Recommended Spare PartsQty Description Part#(supercedes)1 Enclosurepressureindicator 510023(001000)1 1/4"filterregulator 510057(002040)1 Enclosurepressurecontrolvalve 510116(003440)1 RapidExchange®valvebody(STDstyle) 510118(003460)1 1/4"Solenoidvalvebody(SA&FAstyle) 510075(002220)1 Safepressureswitch 510356(005200)1 RapidExchangepressureswitch 510358(005210)1 Series2000logicmodule-Ver.2.0 510279(005000)1 Series2000VACpowermodule 510304(005020)1 Series2000VDCpowermodule 510305(005021)1 Installation&operationmanual 129-02111 Enclosurewarningnameplate-CI 513008(EWN-1)

Referencepartnumberaboveforcurrentsparepartspricing.Immediatepricingisavailabletoallconfirmedcustomers.

Installation Tools & Testing Equipment1/2"chuckdrill

Completesetofdrillbits

1/2"&3/4"conduitknockoutpunchor1"holesaw

Completesetoftubing,conduitbending,instrumentfittingandelectricalcraftsmanhandtools

0-5"differentialpressuregaugeormanometer(connectedtotheprotectedenclosuretomeasuremaximumpressure)

2002 - STD - CI - NR - LH - ##

Series Model NumberSystem Style STD - Standard SA - Semiautomatic FA - Fully AutomaticArea Classificatio CI - Class I, Group C & D Area IB - Class I, Group B Area (STD Only)Power Control Mode NR - Normal Running CB - Conditional BypassMounting Configuratio LH - left hand left side of enclosure RH - right hand right side of enclosure TM - top mount top of enclosure BM - bottom mount bottom of enclosure WM - wall mount wall surface FM* - frame mount external frame or rack PM* - panel mount enclosure surface cutout * FM & PM configurations feature flush mount EPCU. Flush mount EPCU is not suitable for Group B Area. ## - Additional factory installed accessories

Confidential according to ISO 16016

sheet

respons.

approved

norm 1 of 1

scale: 1:1

Label for Model 2002-[STD or SA or FA]-CI Type X

date: 2005-Dec-15Only valid as long as released in EDM or with a valid production documentation!

Twinsburg

2002 STD X UL ID NP SS2002 SA X UL ID NP SS2002 FA X UL ID NP SS

125-0841Bchange notice.

Dieses Dokument enthält sicherheitsrelevante Angaben. Es darf nicht ohne Absprache mit dem Normenfachmann geändert werden!

This document contains safety-relevant information. It must not be altered without the authorization of the norm expert!

TECHNICAL INFORMATION:

POLYCARB 0.01”MUST BE UL/CSA APPROVED

BLACK COPY ON WHITE BACKGROUNDFULL INFORMATION PERTAINING TO PRINT FONTS,DIMENSIONS AND COLOR SCHEMES ARE CONTAINED INTHIS COREL DRAW (.CDR) FILENAME UNDER DRAWINGNUMBER 125-0841B

LABEL MATERIAL:

ADHESIVE:

COLOR:

NOTE:

US.JMB

US.SSJ

US.AAS150-0691

2.50

1.50

SCALE = 1XAll dimensions are in inches.All outside corners R=0.13

Tolerances: 2-place dec. +/- .01

APPROVED BY FM APPROVALS AS ASSOCIATED TYPE X PRESSURIZATION CONTROL

EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS. REDUCES THE INTERNAL AREA

OF A CONNECTED ENCLOSURE IN ACCORDANCE WITH DRAWING NUMBER MCL 2002.

APPROVED BY FM APPROVALS AS ASSOCIATED TYPE X PRESSURIZATION CONTROL

EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS. REDUCES THE INTERNAL AREA

OF A CONNECTED ENCLOSURE IN ACCORDANCE WITH DRAWING NUMBER MCL 2002.

APPROVED BY FM APPROVALS AS ASSOCIATED TYPE X PRESSURIZATION CONTROL

EQUIPMENT FOR USE IN HAZARDOUS LOCATIONS. REDUCES THE INTERNAL AREA

OF A CONNECTED ENCLOSURE IN ACCORDANCE WITH DRAWING NUMBER MCL 2002.

LABEL P/N: 510959 LABEL P/N: 510961

LABEL P/N: 510963

15 CUBIC FEET MAXIMUM ENCLOSURE VOLUME

CLASS I, DIVISION 1, GROUPS C & D TO NONHAZARDOUS

15 CUBIC FEET MAXIMUM ENCLOSURE VOLUME

CLASS I, DIVISION 1, GROUPS C & D TO NONHAZARDOUS

15 CUBIC FEET MAXIMUM ENCLOSURE VOLUME

CLASS I, DIVISION 1, GROUPS C & D TO NONHAZARDOUS

PURGE CONTROL FOR USE IN HAZARDOUS LOCATIONS. CLASSIFIED BY UNDERWRITERS

LABORATORIES INC. ® IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION

STANDARD FOR PURGED AND PRESSURIZED ENCLOSURES FOR ELECTRICAL EQUIPMENT

PURGE CONTROL FOR USE IN HAZARDOUS LOCATIONS. CLASSIFIED BY UNDERWRITERS

LABORATORIES INC. ® IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION

STANDARD FOR PURGED AND PRESSURIZED ENCLOSURES FOR ELECTRICAL EQUIPMENT

PURGE CONTROL FOR USE IN HAZARDOUS LOCATIONS. CLASSIFIED BY UNDERWRITERS

LABORATORIES INC. ® IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION

STANDARD FOR PURGED AND PRESSURIZED ENCLOSURES FOR ELECTRICAL EQUIPMENT

NFPA 496-1996

4S11

NFPA 496-1996

4S11

NFPA 496-1996

4S11

T3C T3C

T3C

Model 2002-STD-CI Type X Model 2002-SA-CI Type X

Model 2002-FA-CI Type X

C

LASSIFIED

®

C

LASSIFIED

®

C

LASSIFIED®

Released EDM checkout 2008-JUL-17

Page 4: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

4

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

Model 2002 System AccessoriesEnclosure Protection Vents (one required with each system)EPV-2-SA-00 Straightw/sparkarrestorEPV-2-SA-90 Rtanglew/sparkarrestor

Additional ItemsSMK-2,-3or-10 SystemmountingkitRAH Div.1remotealarmhornRAB-1 Div.1remotealarmbeaconLCK LfittingconduitkitTCK TfittingconduitkitSRM-4000 SwitchresistormoduleNJ... P+FNAMURsensorNC-4 1/4"ninetyconnectorSC-4 1/4"straightconnectorEFC-4 1/4"flushconnectorEBC-4 1/4"bulkheadconnectorEPC-12 3/4"pipeconnector

Factory Installed ItemsIS1 ChannelAbarrierIS2* ChannelBbarrierIS3* ChannelCbarrierRP1 RedundantsafepressurepwitchRP2 RedundantRapidExchangepressurepwitchL Keylockassembly

*Requirescustomprogramminginformation

Enclosure Design Requirements1. Allwindowsmustbeshatterproofandsizedassmallas

possible.

2. AllNFPA496requiredmarkingsmustbeplacedonornearallenclosuredoorsandcovers.

3. Theenclosuremustwithstandaninternalpressureoffive(5)inchesofwaterwithoutsustainingpermanentdeformationandresistallcorrosiveelementsinthesurroundingatmosphere.

4. Alllightweightobjectsintheenclosure,suchaspaperorinsulation,mustbefirmlysecured.

5. TheenclosureshouldbeconstructedfrommaterialssuchasmetalornonstaticpolycarbonatetomeetorexceedNEMA4or12performancerequirements,butdoesnotrequirethirdpartyapproval.

6. Theinstallationofobstructionsorotherbarriersthatblockorimpedetheflowofprotectivegasmustbeavoided.

7. Thecreationofairpocketsorotherareasthattrapflammablegaseswithintheenclosureordevicesmustbeavoided.

8. Theenclosureshouldbelocatedinanareawhereimpacthazardsareminimal.

9. Iftheenclosureisnonmetallicandcontainsequipmentthatutilizesorswitchespowerloadsgreaterthan2500VA,itmustbeconstructedfromsubstantiallynoncombustiblematerials,suchasmaterialsdesignedtomeetorexceedANSI/UL94ratingsof94V-0or945V.

Adjacent Enclosures1. Adjacentenclosuresmustbeprotectedbyoneofthe

followingmeans:

a) purgedorpressurizedinserieswiththeprotectedenclosure

b) purgedorpressurizedseparately

c) protectedbyothermeans;e.g.,explosionproofenclosures,hermeticallysealeddevicesorintrinsicsafecircuits

2. Adjacentpurgedorpressurizedenclosuresmustbedesignedtomeetallconstructionrequirementsabove.

Total Volume Calculation1. Thetotalvolumeofallpressurizedenclosures,devicesand

wirewaysmustbeconsidered.

2. Allenclosure,device,andwirewayvolumesmustbecalculatedwithoutconsiderationofinternallyconsumedspace.

Device Ventilation1. Encloseddeviceswithintheprotectedenclosurewhichdo

notexceed1.22in3offreevolumedonotrequireventilationtotheprotectedenclosure.

2. Ifthefreevolumeofaninternaldeviceexceeds1.22in3itmustbeprotectedbyoneofthefollowingmeans:

a) ventilatedonthetopandbottomsideswith1in2ofopeningforeach400in3ofvolumewithintheinternalprotectedenclosure,ataminimumdiameterof1/4"

b) purgedinserieswiththeprotectedenclosureorbepurgedseparatelyor

c) protectedbyothermeans;e.g.,explosionproofenclosures,hermeticallysealeddevices,orintrinsicsafecircuits.

Temperature Limitations1. Theenclosuremusthavenosurfaceareathatexceeds80

percentoftheflammableorignitablesubstance’sauto-ignitiontemperature.

2. Internaldevicesthatexceedthistemperaturemustbeprotectedbyoneofthefollowingmanners:

a) ThedeviceisenclosedinachamberthatisCULUSorFMlistedasahermeticallysealeddevicethatprohibitstheentranceofaflammableorignitablesubstance,andmaintainsasurfacetemperaturebelowtemperaturelimits.

b) Itcanbeprovenbytestingthatthedeviceswillnotignitethesubstanceinvolved.

c) ThedeviceispurgedinaseparateenclosurethatbearsanETW(enclosuretemperaturewarningnameplate).Devicesmaybeaccessedonlyafterpowerhasbeenremovedandthedevicehasbeenallowedtocooltosafetemperature,ortheareaispositivelyknowntobenonhazardous.

Page 5: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

5

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

Model 2002-STD-CI-LH Shown

Installation Overview

ENCLOSURE PROTECTION

VENT

PROTECTED ENCLOSURE

ENCLOSURE SUPPLY TUBING

ENCLOSURE REFERENCE

TUBING

ENCLOSURE CONNECTION

FITTINGS

ENCLOSURE WARNING

NAMEPLATE

ENCLOSURE PROTECTION

SYSTEM

SYSTEM SUPPLY TUBING

EPCU BREATHER DRAIN FITTING

EPCU POWER & ALARM SIGNAL WIRING CONDUIT & SEAL

PROTECTIVE GAS SUPPLY

SERVICE VALVE

Page 6: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

6

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

Getting Started

Typical Single Protected Enclosure Connections

HELPFUL HINTSIfflammablegasesarelighterthanair,theinletconnectiontoeachenclosuremustenternearabottomcorner.Theoutletconnection,foranoptionalenclosureprotectionventorpipingtoanadjacentprotectedenclosure,mustexitnearanextremeoppositetopcorner.Seediagramstotheleft.

Ifflammablegasesareheavierthanair,inletandoutletconnectionsmustbereversed.

Inallcases,themostprevalentgasmustdeterminethelocationofinletandoutletconnections.

Determining Enclosure Inlet & Outlet Connection Locations

HELPFUL HINTSToensureadequateprotectivegasflowtotheprotectedenclosure(s),allpipingandtubingmustbefullyreamed.

Precautionsmustbetakentopreventcrimpingandotherdamagetoprotectivegaspipingandtubing.

Whenprotectingmultipleenclosureswithasingleenclosureprotectionsystem,theenclosuresmustbeconnectedinseriesfromthesmallesttothelargesttoensureadequateprotectivegasflow.

PROTECTED ENCLOSURE

C

B

ENCLOSURE PROTECTION VENT(Optional)

E

SUPPLY

REFERENCE

1/2" PROTECTIVE GAS SUPPLY

HEADER

ENCLOSURE PROTECTION

SYSTEM

Maximum tubing / pipe length and maximum number of bends / elbows

1/4"O.D.tubingtullyreamed

20feet10bends

1/4"O.D.tubingtullyreamed

Description

*Tubing or pipe diameter

Enclosure supply

System supply tubing

Enclosure reference

1/4"O.D.tubingtullyreamed

5feet5bends

20feet10bends

Multi - enclosure connections

3/4"I.D.pipetullyreamed

10feet5elbows

Optional remote renting

3/4"I.D.pipetullyreamed

30feet5elbows

A B EDC

ENCLOSURE PROTECTION

SYSTEM

PROTECTED ENCLOSURE

PROTECTED ENCLOSURE

D

SUPPLY

REFERENCE

B

TYPICAL MULTIPLE PROTECTED ENCLOSURE CONNECTIONS

1/2" PROTECTIVE GAS SUPPLY

HEADER

A

A

D

C

PROTECTED ENCLOSURE

*NOTE:Tubeandpipesizesaretradesizesandarenotequalininsidediameters.DONOTsubstitutetubeforpipewithsametradesize.

INLET

INLET

Connectionsforheavierthanairgasesandvapors

OUTLET

OUTLET

Connectionsforlighterthanairgasesandvapors

Page 7: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

7

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09System Mounting

IMPORTANT NOTESThe system should be mounted at EYE LEVEL.

Care must be taken to ensure the system and all protruding components are clear of all enclosure accesses (doors and covers) and conduit, pipe, tubing or cable entries.

LH, RH, TM, BM and WM configurations are intended for mounting adjacent to the protected enclosure.

LH, RH, TM & BM configurations are also suitable for 2" schedule 40 pipe mounting.

Determine the mounting configuration of your system using the diagrams on pages 9 & 10.

Remove and save the manila envelope (containing the enclosure warning nameplate) which may be taped to the outer surface of the mounting flange.

Although all systems are factory tested and calibrated, we strongly suggest a bench test of basic functions prior to installation.

Mounting LH, RH, TM, BM & WM Configurations1.Transferholepatternofsystemmountingplatetointended

surface.

2. Checkforobstructionshinderingboltfastening,drillandreamthemountingholesbeforemountingthesystem.

3. Securethesystemtotheenclosure,orothermountingsurface,usingone(1)SMK-3orequivalent-six(6)3/8"x3/4"stainlesssteelbolts,nutsandlockwashers.

*WMrequiresone(1)SMK-2orequivlent-four(4)3/8"x3/4"stainlesssteelbolts,nutsandlockwashers.

Mounting FM & PM Configurations

1. Transferpanelcutoutpatterntotheintendedsurface.

2. Checkforobstructionsthatcouldprohibitboltfasteningorsystempneumaticandelectricalconnections.

3. Cutpanelcutoutpatternontheintendedsurface.

4. Deburrallcutoutsurfaces.

5. SecuresystemtoenclosureusingSMK-10,orequivalent-ten(10)1/4"x3/4"stainlesssteelnuts,bolts,mountingclipsandlockwashers.

HELPFUL HINTSFMandPMconfigurationsaredesignedtomountthroughapanelcutoutone(1)inchsmallerthantheoverallheightandwidthofthesystemmountingplate,usingclipsandfastenersprovidedwithSMK-10.Thisdesignfeatureeliminatestheneedtodrillthesystemmountingboltholesintheprotectedenclosure.

FMconfigurationsareintendedformountingadjacenttotheprotectedenclosure.

PMconfigurationsareintendedformountingthroughacutoutintheprotectedenclosuresurface.

Typical Surface Mounted System(Model 1002-LPS-LH Type Z shown)

Typical Pipe Mounted System(Model 1002-LPS-LH Type Z shown)

Typical Panel/Frame Mounted System(Model 1002-LPS-PM Type Z shown)

Page 8: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

8

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

Hardware Mounting

Optional Enclosure Protection VentAllconfigurationsmustbemountedinatrueverticalposition.

Theventmustbelocatedtoprovideaccessforroutinetestingofthevent’sflapperassembly.Aminimum8"clearanceisrequiredbelowtheventopening.

1. Determinethevent’smountingconfiguration,i.e.,-00verticalmountor-90sidemount.Seephotosbelow.

2.Determineventlocationandlayoutventmountingholeontheprotectedenclosure(asdeterminedonpage6,“GettingStarted”).

3. Usinga1"holesawor3/4"conduitpunch,drillanddeburrtheenclosureprotectionventmountinghole.

4. Removethehubmountingnutfromtheventhubandplacethehub,withO-ringintact,throughthemountinghole.TheO-ringmustbeontheoutsideoftheprotectedenclosure.

5. Reinstallthehubmountingnuttothemountinghubfrominsidetheprotectedenclosureandtighten.

Warning Nameplate(s)AnEWN(EnclosureWarningNameplate)mustbelocatedinaprominentpositiononornearallenclosureaccesses(doorsandcovers).

One(1)EWNisprovidedwitheachsystem,locatedinthemanilaenvelopetapedtothemountingflangeofthesystem.AdditionalEWNsareavailablefromPepperl+Fuchs.

AllEWNsprovidelabeledspacesallowingthecustomertomarktheprotectedenclosurewith:1)aTCode(temperatureidentificationnumber),2)Class,GroupandDivisionofsurroundingarea,and3)NFPApressurizationTypeX,YorZ,asmayberequiredbyplantandlocalcodesandisrequiredbyNFPA496.

AnETW(EnclosureTemperatureWarningnameplate)mustbelocatedinaprominentpositiononornearallenclosureaccesses(doorsandcovers)whenthetemperatureofaninternalcomponentexceeds80percentoftheignitiontemperatureoftheflammablevapor,gasordustinvolved.

AnETWwarnstheoperatortodeenergizeallequipmentforaspecifiedlengthoftime,allowingtheprotectedequipmenttocoolbeforeopeningtheprotectedenclosure.Thelengthoftimerequiredisdeterminedbythecustomerandcanbefactoryorfieldengraved.

AllEWNsandETWsarefurnishedwithanadhesiveback,butshouldalsoberivetedorscrewedtotheprotectedenclosure.

Enclosure temperature warning nameplate

Enclosure warning nameplate - Class II

Enclosure warning nameplate - Class IEPV - 2 - SA - 00Vertical Mount

EPV - 2 - SA - 90Side Mount

Page 9: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

9

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09Mounting Plate Dimensions

IMPORTANT NOTEDimensions DO NOT include systems ordered with an area classification of IB (Class I, Division 1, Group B). Consult factory for mounting plate dimensions.

SA & FAStyles Only

SA & FAStyles Only

4.25"

20"

10.75"

.6875"

3.5625"

11"

.375" O.D.TYP. 6

13.75"

22"

11"

SA & FAStyles Only

4.25"

20.5"

10.75"

11.5"

.68

75

"

.375" O.D.TYP. 6

3.5

62

5"

13.75"

23"

12"

22"

11"

SA & FAStyles Only

SA & FAStyles Only

4.25"

21.3125"

10.75"

.6875"

3.5625"

11"

.375" O.D.TYP. 6

13.75"

2002-RH(Right hand configuration)

2002-LH(Left hand configuration)

2002-TM(Top mount configuration)

Page 10: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

10

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

2002-FM & 2002-PM(Frame & panel mount configuration)

SA & FAStyles Only

4.25"

22.3125"

10.75"

11.5".68

75

".375" O.D.

TYP. 63

.56

25

"

13.75"

23"

12"

2002-BM(Bottom mount configuration)

2002-WM(Wall mount configuration)

9"

2" 1"

.375" O.D.TYP. 4

TYPICAL -WMMOUNTING FLANGE

Add 2" to bothdimensions forSA & FA Styles

20"

6"

12.5"

22"

11"

1.25"

SA & FA Style

10.25"

13.25"

12"Panel Cutout

Panel Cutout23"

.25" O.D.TYP. 10

24"

13"

Mounting Plate Dimensions (continued)

IMPORTANT NOTEDimensions DO NOT include systems ordered with an area classification of IB (Class I, Division 1, Group B). Consult factory for mounting plate dimensions.

Page 11: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

11

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09Pneumatic Tubing Requirements

Protective Gas Supply Requirements

Theprotectivegassupplytotheprotectionsystemmustbeaclean,instrumentqualitycompressedairornitrogenandmustcontainnomorethantraceamountsofflammablegas,vaporordust.

Theprotectivegassupplycompressorintakemustoriginateinanonhazardouslocation.Suctionductpassingthrougha hazardous location and the protection system tubingand piping must be fabricated from noncombustiblematerialssuitableforprevailinghazardsandenvironmentalconditions.

Theprotectivegassupplymustoriginatefromadedicatedinstrument quality compressed air header (1/2" pipe orlarger),nofartherthantwenty(20)feetfromtheprotectionsystem.LocalcompressorsandgascylindersshouldnotbeusedbeforeconsultingwithPepperl+Fuchs.

Theprotectivegassupplytotheprotectionsystemmustberegulatedfrom120psimaximumto80psiminimum.

Pneumatic Connection RequirementsALLFITTINGSMAYBECUSTOMERORFACTORYFURNISHED

1. Forsystemsupply,one(1)SC-41/4"malestraightconnectororone(1)NC-41/4"maleelbowconnectororequivalentfittingpersystem.

NOTE:Abovefittingisrequiredonlyifprotectionsystemisfurnishedwithanoptionalin-linefilterkit(modelILFK)accessory.

One(1)similarfittingwhichwillconnecttheinertgassupplytubingtotheinertgassupplyheaderconnectionpointandone(1)lotof1/4"O.D.,.035"wallthickness,weldedorseamlessstainlesssteeltubing.

2. Forenclosuresupply,one(1)EFC-41/4"flushconnector,orone(1)EBC-41/4"feed-throughconnectororequivalentfittingpersystem.

3.Forenclosurereference,one(1)EFC-41/4"flushConnector,orone(1)EBC-41/4"feed-throughconnectororequivalentfittingpersystem.

4.One(1)lotof1/4"O.D.,.035"wallthickness,weldedorseamlessstainlesssteeltubing.

5.Formultipleenclosureconnections,two(2)EPC-101/2"pipemountinghubsorequivalentand1/2"150#ratedpipecouplings&unionsperinterconnection.

One(1)lot150#rating1/2"galvanizedoraluminumpipeandfittings,fullyreamedandunrestricted.

PM Pneumatic Connection Requirements Inadditiontoitemnumbers1,4and5above,thefollowing

fittingsarerequiredforallPMconfigurations.

1. ForsystemsupplyonPMconfigurations,one(1)additionalEBC-4orequivalent1/4"throughbulkheadfittingpersystemisrequired.

2. Foratmosphericreference,one(1)PRB-4orequivalent1/4"femalebulkheadfittingandstainlesssteelsinteredelementisrequired.

SC-4 NC-4

EBC-4EFC-4

EPC-10

ENCLOSURE SUPPLY & REFERENCE FITTINGS

SYSTEM SUPPLY FITTINGS

MULTIPLE ENCLOSURE CONNECTION FITTING

PRB-4

SYSTEM ATMOSPHERIC REFERENCE FITTING

Page 12: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

12

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

Enclosurepressuregauge

Atmospheric reference

inlet

Enclosurepressure

controlvalve

EPCUatmospheric

referencetubing

Flamearrestorfittings

RapidExchange

controlvalve

Filterregulator

System supply inlet

Enclosure supply outlet

RESVconduit

Mountingplate

Tubing Connection Points

LH, RH, TM, BM, WM & FM Configuration Connection Points

PM Configuration Connection Points

HELPFUL HINTPneumaticconnectionsarebolded.

RapidExchange

controlvalve

Filterregulator

System supply inlet

Enclosure supply outlet

Mountingplate

Venturiorifice

Enclosurepressuregauge

Enclosure reference

inlet

Enclosurepressurecontrolvalve

EPCUpressurereference

tubing

Flamearrestorfitting

RapidExchange

controlvalve

Filterregulator

System supply inlet

Enclosure supply outlet

RESVconduit

Mountingplate

Venturiorifice

(notvisible)

Enclosurepressuregauge

Enclosure reference

inlet

Enclosurepressurecontrolvalve

EPCUpressurereference

tubing

Flamearrestorfitting

STD Style SA & FA Style(with Rapid Exchange

Solenoid Valve)

Page 13: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

13

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09Tubing Installation

Tubing LH, RH, TM, BM, WM & FM ConfigurationsSystem supply connections

1. Selectorinstallaprotectivegassupplyheadertap,fittedwiththepropertubesizefittingandlocatedwithintwenty(20)feetoftheenclosureprotectionsystem.

2. Ifaservicevalveisplacedbetweentheprotectivegassupplyheaderandtheenclosureprotectionsystem,itmustbeinstalledincloseproximityoftheprotectedenclosureandbelabeledinaccordancewithNFPA496.

3. Selecttheappropriatefittingsrequiredtoconnecttheprotectivegassupplytotheprotectionsystemregulatorasdeterminedonpage11,“PneumaticTubingRequirements”.

4. Determineappropriatetubingroutefromtheprotectivegassupplyheadertotheprotectionsystemregulator.

5. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.

6. Installtubingandtightenallfittingstofittingmanufacturer’sspecifications.Securetubingtoappropriatestructuralsupportsasrequired.

Enclosure supply & reference connections

1.Chooselocationfortheenclosuresupplyconnection(s)basedontherequirementsonpage6,“GettingStarted”.

2. Placetheenclosurereferenceconnectionfittingdirectlybehindtheenclosureprotectionsystemwheneverpossible.Forsystemsprotectingmultipleenclosuresinseries,theenclosurereferenceconnectionfittingmustbeplacedonthelastenclosureintheseries.Seepage6,“GettingStarted.”

3. Drillanddeburrenclosuresupplyandreferencefittingholesontheprotectedenclosure.Mountthefittings.

4. Determineappropriateroutefortheenclosuresupplyandreferencetubing.

5. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.

6. Installtubingandtightenallfittingstofittingmanufacturer’sspecifications.Securetubingtoappropriatestructuralsupportsasrequired.

Tubing PM ConfigurationsEnclosure bulkhead fittings

1. Selectthefittingsrequiredtoinstallthesystemsupply,systemsupplybulkheadFittingandatmosphericreferencebulkheadfitting.Seepage11,“PneumaticTubingRequirements.”

2.Chooselocationforthesystemsupplybulkheadfitting.Thisfittingallowstheprotectivegassupplytopassthroughthewallofaprotectedenclosuretotheprotectionsystem’sregulatorsupplyinletconnection.

3. Chooselocationfortheatmosphericreferencebulkheadfitting.Thisfittingallowstheenclosurepressuregaugetoreferenceatmosphericpressure.

4. Drillanddeburrsystemsupplyandreferencebulkheadfittingholesintheprotectedenclosure.Mountthefittings.

System supply & referenceconnections

1. Selectorinstallaprotectivegassupplyheadertap,fittedwiththepropertubesizefittingandlocatedwithintwenty(20)feetoftheenclosureprotectionsystem.

2. Ifaservicevalveisplacedbetweentheprotectivegassupplyheaderandtheprotectionsystem,itmustbeincloseproximityoftheprotectedenclosureandlabeledinaccordancewithNFPA496.

3. Determineappropriatetubingroutefromtheprotectivegassupplyheadertothesystemsupplybulkheadfitting.

4. Determineappropriatetubingroutefromthesystemsupplybulkheadfittingtotheprotectionsystemregulator.

5. Determineappropriatetubingroutefromtheatmosphericreferencebulkheadfittingtotheenclosurepressuregauge’sreferenceinletconnection.

6. Bendtubingusingindustrialgradebenders,checktubingfittoensureproperseatingbetweenthetubingandfittings.Fullyreamalltubingends.

7. Installtubingandtightenallfittingstofittingmanufacturer’sspecifications.Securetubingasrequired.

HELPFUL HINTSAllworkmustbeperformedbytechniciansqualifiedinpneumatictubingandelectricalconduitinstallation.

Pepperl+Fuchsrecommendstheuseof.035"wallthickness,weldedorseamlessstainlesssteeltubing.

Ifflexibletubingisused,itmustbeinstalledinamannerthatprotectsitfromdamageandcorrosion.

Page 14: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

14

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

Electrical Supply Requirements

General Wiring RequirementsWARNING!This device contains electrical parts which can cause shock or injury.

Allelectricalconnections,conduitandfittingsontheprotectedenclosuremustbesuitableforthehazardouslocationinwhichtheyareinstalled.Inaddition,allconduitandwiremustbeinstalledinaccordancewithNECasrequiredandallrelevantplantandlocalcodes.

Conduitsealsmustbeutilizedonallelectricalconduitconnectionsandpouredwithanapprovedcompoundpriortooperationoftheprotectionsystem.

Exception:Donotusesealsonconduitusedasaprotected“wireway”tosupplyprotectivegastoadjacentprotectedenclosures.Thesameconduitcanbeutilizedforbothelectricalandpneumaticservicetoanadjacentprotectedenclosure(s),providedtheconduitisoversizedtoallowaminimumfreeclearanceequaltoorlargerthanthepipesizerequiredbetweenmultipleenclosuresasstatedonpage6,“GettingStarted.”

EPCU Power RequirementsTheelectricalpowercontrolunit's(EPCU)electricalpowersourcemustoriginatefromacircuitbreakerorfuseddisconnectsuitableforthehazardouslocationinwhichitisinstalled.Thepowersourceshouldbeuninterruptedandtheswitchmustbelocatedwithinfifty(50)feetoftheprotectedenclosure(s)andtheenclosureprotectionsystemandbeproperlymarked.ForEPCUpowerspecificationsseepage3,"System'sSpecifications."

Alarm Signal RequirementsPepperl+FuchsstronglyrecommendsuseoftheoptionalalarmsystemcontactsoftheEPCU,connectedtoanalarmsystemlocatedinaconstantlyattendedlocationtoindicatethefailureoftheenclosureprotectionsystem.ForEPCUalarmsignalspecificationsseepage3,"System'sSpecifications."

Typical Enclosure Wiring MethodsProtectedenclosuresmustbewiredsimilartoexplosionproofenclosures,inaccordancewithArticle500oftheNationalElectricCode-NFPA70.

Singleconductorwiringmustbeplacedinrigidmetalconduit,seal-flexconduit,orothermediumsapprovedforuseinthehazardouslocationsurroundingtheprotectedenclosure.Additionally,NFPA496requiresapprovedconduitsealsonallpressurizedenclosureconduitwiringentries,inaccordancewithNFPA70.Furthermore,theuseofanapprovedconduitsealissimplythemostpracticalwaytopreventexcessiveleakagethroughconduitconnections.

However,whileexplosion-proofenclosuresrequireconduitsealsonallcableentries,inaccordancewithNFPA70,othermethodsofsealedcableentriesthataresuitableforhazardouslocationscanbeused,suchascompressionglands.

Inconclusion,therearetwoprimarygoals.First,theinstallershouldensurethatallassociatedwiringandcableisprotectedbypressurizationorothermeans,suchasexplosion-proofconduitorintrinsicsafetybarriers.Secondly,theinstallermustensurethatallassociatedconduitandwirewaysaresealedtoconserveprotectivegas,unlesstheyareusedtosupplyprotectivegastootherenclosuresordevices.

Typical Enclosure Wiring Connections

Explosionproofdevice

Seal

Intrinsicallysafeorfiberopticdevice

Adjacentpressurized

device

Independentlypressurized

device

Intrinsicallysafeorfiberopticdevice

Seal

Conduit

Conduit

Conduit

Glandfitting

Cable

Seal

Pressurizedraceway

Protectedenclosureordevice

HELPFUL HINTPepperl+Fuchsrecognizesitmaybeimpracticaltopourallelectricalconduitsealspriortoinstallationinthefield.However,allconduitconnectionsmustbesealedforpropertestingandoperationoftheenclosureprotectionsystem.Therefore,Pepperl+Fuchsrecommendstheuseoftemporarysealssuchasductsealormaskingtapeforbenchorshoptesting,priortofinalfieldinstallation.

Page 15: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

15

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09Electrical Power Control Unit

IMPORTANT NOTESFor proper moisture drainage of the Type 7 enclosure, the installer must 1) move the Type 7 breather drain to one of the bottom conduit entrances or 2) use drain seals on all conduit connected to the bottom two conduit entrances.

The Type 7 breather drain is not provided or required with PM configurations.

Top two conduit entrances will be dedicated for Intrinsic Safe wiring ONLY when the EPCU is supplied with Pepperl+Fuchs' optional ISB intrinsic safety barriers.

General Layout & Electrical Conduit Connections

EPCU LED Displays

Powermodeselectorswitch

Type7explosionproof

screwcover

Type7explosionproof

enclosure

Powermodeselectorswitch

(optionalmountinghole-factoryuseonly-)

1/2"NPTnonduitnonnectionports

typical6(seeimportantnotes

below)

LEDdisplay

Type7explosionproofbreatherdrain(seeimportantnotesbelow)

EPCUelectricalratingnameplate

AlarmOnly Alarm&Bypass

Page 16: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

16

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

EPCU Power Rating

EPCU Electrical Power Rating Nameplate

Assembled EPCU Electronics Module

TheEPCU(ElectricalPowerControlUnit)ofthisType"X"purging/pressurizationsystemisofferedinvariousstyles.Forproperinstallationandoperation,beginbyexaminingtheEPCUelectricalratingnameplatetoidentifythesysteminputvoltageandpowerrequirements,enclosurepowerandalarmcontactratingsandthirdpartyapprovalmarkings.Next,matchtheLEDdisplayofyourEPCUwithoneofthedisplaysshownonpage15.TheEPCULEDDisplaywillhelpidentifytheoptionsfeaturedonyoursysteme.g.,normalrunningmodeorconditionalbypassClassIpurging(timer)orClassIIpressurization(notimer).

MODEL 2000 ELECTRICAL POWER CONTROL UNITCAUTION: OPEN CIRCUIT BEFORE REMOVING COVER

ATTENTION: OUVRIR LE CIRCUIT AVANT D'ENLEVER LE COUVERCLE

SERIAL NO. INPUT VOLTAGE & POWER REQUIREMENTS

CSA Encl. 3CLASS I, DIV. 1, Gr C&DCLASS II, DIV. 1, Gr E, F, G HASUL & FM APPROVALS ONLY

ENCL POWER & ALARM CONTACTS ARE RATED 120/240 VAC, 20 AMPS

120 SINGLE PHASE, 60 CYCLE, 1 AMP240 SINGLE PHASE, 50 CYCLE, 1 AMP

XXXXXX

EPCU INPUT POWER REQUIREMENTS

Factorysetattimeoforder

AREA CLASSIFICATION

DefinestheareaclassificationsforwhichtheEPCUissuitablefor

operation

REQUIRED WARNING STATEMENTS

EPCU SERIALNUMBER

Logic module

120/240 VAC Power module

Power module cable

Pressure switch module

Page 17: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

17

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09Electrical & Pneumatic Diagrams

LH, RH, TM, BM, WM & FM Configurations

PM Configurations

Requiredenclosureprotectionvent

Electricalpowercontrolunit

Enclosurepressuregauge

Systemsupply

Breatherdrain

EnclosureSupplytubing

Sinteredvent

Enclosurereference

tubing Enclosurereferencebulkheadfitting

Electricalpowersupplyconduit

hubConduitsealUnionConduitseal Union

Venturiorifice

Systemsupplytubing

RegulatorProtectedenclosure

Enclosuresupplybulkheadfitting

RapidExchange

pressuregauge*RapidExchange

controlvalve

Enclosurepressurecontrolvalve

Systemtupplyconnectionfitting

*SolenoidonSA&FAstyles

Systemsupply

Atmosphericpressurereferencebulkheadfitting

Systemsupplybulkheadfitting

Inlet

Conduitseal Union Conduitseal

Requiredenclosureprotectionvent

Electricalpowersupplyconduit

hub

ElectricaleowercontrolUnit

Atmosphericreference

tubing

Electricalpowerconduit

Enclosurepressuregauge

UnionElectricalpowertoenclosure

Enclosurepressurereference

Enclosurepressurereference

Protectedenclosure

Enclosuresupply

vischarge

Systemsupplytubing

Regulator

RapidExchange-pressuregauge

*RapidExchange

controlvalve

EnclosurepressurecontrolvalveSystemsupply

connectionfitting*SolenoidonSA&FAstyles

Page 18: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

18

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

Conduit Installation

EPCU Electrical ConduitUnplugthefourunlabeledconduitentranceslocatedonthesidesandbottomoftheEPCUenclosure(Seepage15,"EPCULayout"forconduitentrancelayout).

TheinstallermustmounttheType7drainfittingsuppliedwiththesystem(exceptforPMconfigurations)inoneofthebottomconduitentrancesoftheEPCU,orutilizedrainsealsonallconduitconnectedtothebottomtwo(2)conduitentrancesoftheEPCU.

Followingtheinstructionslistedbelow,installallconduit,fittingsandseals(ordrainsealsifutilized)betweentheEPCU,alarmsystem(ifutilized)andtheprotectedenclosure(s).PlugallremainingEPCUconduitentrances.

1.Choosethelocationfortheenclosure’selectricalconduitconnection(s)basedontherequirementsonpage14,“ElectricalSupplyRequirements”.

2. Drillanddeburrenclosureconduitfittingholesintheprotectedenclosure.Mountthefittings.

3. Determineappropriateroutefortheenclosureelectricalenclosureandalarmsignalconduit.

4. Measure,cutandthreadconduit,checkconduitfittoinsureproperseating.Fullyreamallconduit.

5. Installconduitandtightenallfittingstofittingmanufacturersspecifications.Secureconduittoappropriatestructuralsupportsasrequired.

6. Sealallconduitwithanapprovedcompoundpriortooperationoftheprotectionsystem.

Optional Intrinsic Safety Barrier ConduitSystemssuppliedwithoptionalIntrinsicSafetyBarriers(ISB)willbesuppliedwithclearlylabeledisolatedconduitentries,asolidbodywirewaywithsnapcoverandplexiglasswiringpartitions.TheseaccessoriesprovideafullyisolatedwiringpathtothebarrierwiringterminallocatedonthelowerleftcorneroftheEPCULogicModule.AllISwiringmustbeisolated.

1.Choosethelocationfortheenclosure’sISconduitconnection(s)basedontherequirementsonpage14,“ElectricalSupplyRequirements”.

2. Drillanddeburrenclosureconduitfittingholesintheprotectedenclosure.Mountthefittings.

3. DetermineappropriateroutefortheISconduit.

4. Measure,cutandthreadconduit,checkconduitfittoensureproperseating.Fullyreamallconduit.

5. Installconduitandtightenallfittingstofittingmanufacturersspecifications.Secureconduittoappropriatestructuralsupportsasrequired.

6. Sealallconduitwithanapprovedcompoundpriortooperationoftheprotectionsystem.

EPCU Conduit Connection PartsFittingKitsCanBeFactoryFurnished

1. ToconnectenclosurepowerfromtheEPCUtotheprotectedenclosure,one(1)LCK(LfittingConduitKit)orequivalentconduitelbow,couplingandsealfittings.

2. ForEPCUtoenclosurewiringconnectionwithone(1)additionalconduitconnectionpath,one(1)TCK(TfittingConduitKit)orequivalentconduittee,couplingandsealfittings.

IMPORTANT NOTE: Model LCK & TCK are offered primarily to OEMs attempting to achieve a "field ready" installation. In all cases, limited pipe fitting skills will be required. Pre-cut 150# galvanized steel pipe nipples can be acquired from local plumbing shops, but a hole saw or punch and wrenches are required to install kits.

LCK “L” FittingConduit Kit

TCK “T” FittingConduit Kit

Page 19: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

19

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09Power Modules & Wiring Diagram

EPCU 120/240 VAC Power Module Layout

VAC & VDC Power Module Electrical Wiring Diagram

Isolatedcoilvoltagetransformer

Powercontrolswitchcableheader

Pressureswitchcableheader

Logicmodulecableheader

Redundantsafepressurerelay

Alarmrelay

Enclosurepowerrelays

Powermodulewiringterminal

Voltageinputselectorseader(factorysetfor

120VACpower)

1Ampinputfuse

RapidExchangesolenoidvalve(RESV)

relay

RESVfactorywiringterminal

20Ampenclosurepowerfuse

EPCU 120/240 VAC power module

1 2 3 4 5 6 7 8 9 10

20AMPFUSES

Isolatedenclosure

powerrelays

IsolatedAlarmrelay

NeuNeu

HotHot

NO Com NC

Remote alarmrelay terminals

OutInIn Out

Enclosure power supply

terminals

Field wired power module

terminalsNO NO NO NC

GndGnd

EPCU powersupply terminals

120VAC*240VAC(optionalvoltage)

*Europeansinglephase240VAConly.

Powerandalarmterminalsarefeed-thrudryswitchcontacts.

CautionshouldbeexercisedtoensurethattheEPCUwiringisproperlyconnected.

AllterminalconnectionstotheEPCUshouldbewiredwithspadeorroundlugs.

Using12gaugemaximumto16gaugeminimumwireonly,checkEPCUpowerrequirements(seepage14)andwiretotheEPCUpowersourceandalarmsystem(ifutilized).Thenroutepowersource(s)throughtheEPCUpowerinandoutterminalstoallnon-rateddeviceswithintheprotectedenclosure(s).

Page 20: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

20

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

Logic Module & Barrier Wiring

EPCU Logic Module & Pressure Switch Module

Optional ISB Wiring Requirements

Alloptionalintrinsicsafety(IS)wiringmustbeisolatedfromallotherelectricalwiringusingthededicatedISconduitentrancesandwirewayoftheEPCU.See"OptionalISBConduitInstallation"onpage18formoredetails.Inaddition,allwiringmustbeinstalledinaccordancewiththeNECandallrelevantlocalandplantcodes.

TheintrinsicsafetybarriersaredesignedtofunctioninconjunctionwithacustomerfurnishedswitchandSRM-4000switchresistormodule,oranNJ...NAMURsensor.Thecustomersuppliedswitchmusthavedrycontactswhichcontainnoinductanceorcapacitance.

TheSRM-4000switchresistormoduleandtheNJ...NAMURsensoraresuppliedwithapproximatelyten(10)feetofwiring.Using16to18gaugeshieldedwire,thecablelengthscanbeextendedtoamaximumof100feet.

Inallapplications,themoduleoftheswitchresistormodulecablemustbeinstalledasclosetothecustomersuppliedswitchaspossibleforproperoperation.

Wiringlugsarenotrecommendedforintrinsicsafetybarrierwiringconnections.

Seepage21forbarrieroperationandfactoryprograming.

EPCU Power Control Modes

Normal Running (NR) Mode

EPCUfeaturesanon-offpushbuttonpowercontrolswitchtoactivatecontrolfunctions.Switchmustbedepressedtoinitiatestart-up.Aftercompletionofstart-up,safepressuremustbelostorswitchmustbedepressedtodeenergizeenclosurepowerrelays.

Conditional Bypass (CB) Mode

EPCUfeaturesanon-off-bypasspowercontrolswitchtoactivatecontrolfunctions.Switchmustbesetto"on"positiontoinitiatestart-up.Afterenclosurepowerisenergized,safepressuremustbelostorswitchmustbesetto"off"positiontodeenergizeenclosurepower.Afterenclosurepowerisenergized,switchmaybesetto"bypass"position,totemporarilylatchenclosurepowerrelays.AflashingLEDthenindicatesbypassengaged,andtheenclosurecanthenbeaccessedwithoutdeenergizingpower(performedunderspecificconditions).Followingaccess,safepressuremustbereestablishedtoresumenormaloperation.Atthattime,theswitchmayberesettotheonposition,withoutdisruptionofenclosurepower.Alarmrelaynormallydeenergizesonlyuponlossofsafepressure,butcanbefactoryprogrammedtodeenergizewhenbypassisengaged,ifspecifiedattimeoforder.

A B C

INTRINSICALLY SAFE AUXILIARY INPUTS

- + - + - +

( - ) BLUE ( + ) BROWN

BarrierCsocket

BarrierB(installed)

BarrierAsocket

Barrierwiring

terminal

Pressureswitchcalibrationaccess

Barrierfault&activestatusindicators

Factoryprograming

header

Redundantcontroller

(GAL)

Powermodulecableheader

EDT,SLT&RETtimers

EPCU Logic Module

Primarysafepressureswitch

LEDstatusdisplay

EPCU Pressure Switch Module

Primarymicroprocessor

Spaceforoptionalredundantsafepressure

switch

SpaceforoptionalredundantRapidExchangeswitch

RapidExchange

Switch

Page 21: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

21

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09Barriers & Field Adjustments

Optional Intrinsic Safety Barriers DescriptionTheEPCULogicModulecanaccommodateuptothreeintrinsicsafetybarriers,tointeractwithremotedevicesandaffectoperationoftheEPCU.Thebarriersareinstalledandprogrammedbythefactoryattimeoforder,andtheyaredesignedtofunctioneitherinconjunctionwithacustomerfurnishedswitchandaPepperl+Fuchsfurnishedresistornetworkcable,oraPepperl+Fuchsfurnishedproximitydetector.Eachbarrierdevelopsalowpowersignal,tocreateatwowireclosedloopcircuit.OperationalstatusofeachbarrierisindicatedbyagreenLEDtoshowactive(closedswitch)status,andbyaredLEDtoshowfaulted(linebreakage)cablestatus.Allbarrierscanbereprogrammedtoduplicateotherbarrierfunctionsasrequired,uponspecificrequest.

Optional ISB Factory Programing

Barrier A Function - when switch opens Disablesstart-upcycleDeenergizesenclosurepowerandalarmrelayFunctionsparalleltosafepressureswitch

Barrier B Function - when switch opens Notprogrammedforthismodel-customapplicationsonly

Barrier C Function - when switch closesEnergizesRESVRelay-customapplicationsonly

LED Display IndicatorsPower off: EnclosurepowerrelaysdeenergizedPower on: EnclosurepowerrelaysenergizedSafe pressure: Enclosurepressure>0.15"or0.50"w.c.Rapid Exchange: Enclosurepressure>2.0"w.c.Timer running: Exchangetimeractive-ClassIonlyAlarm active: Enclosurepressure<0.15"w.c.Bypass engaged: Controlbypassactive-CBmode

Field Adjustable Timer FunctionsEDT(ExchangeDelayTimer)(FAstyleonly)providesatimedelaytopreventRapidExchangesolenoidvalvefromenergizinguntilsafepressurecanbestabilized.

SLT(SolenoidLatchingTimer)(FAstyleonly)providesatimedelaytokeeptheRapidExchangesolenoidvalveenergizeduntilRapidExchangepressureisdetected.Ifthepressureisnotdetected,theEPCUwillreset.

RET(RapidExchangeTimer)providesatimedelayafterRapidExchangepressureisdetected,toallowfourvolumeexchanges(tenvolumesformotors)priortoenergizingtheenclosurepowerrelays.InClassIareasonly,ifRapidExchangepressureislostorinterruptedduringtimedelaycycle,theEPCUwillreset.

EDT, SLT & RET Timer Settings

POSITION TIME IN SECONDS POSITION TIME IN MINUTES

0 5 0 5 1 10 1 10 2 15 2 15 3 20 3 20 4 25 4 25 5 30 5 30 6 35 6 35 7 40 7 40 8 45 8 45 9 50 9 50 A 55 A 55 B 60 B 60 C 65 C 65 D 70 D 70 E 75 E 75 F 80 F 80

NOTE:PowermustberemovedfromtheEPCUviathelocaldisconnectswitchforapproximately10secondsfortimeradjustmentstoreset.

0 12

3

4

5

6789

A

B

C

D

EF

Rotaryswitchbody

EDT & SLT Timer RET Timer

Page 22: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

22

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

Set-up Procedure

Model 2002 Rapid Exchange Purging Set-up1.Closetheenclosurepressurecontrolregulator(allstyles)

andRapidExchangecontrolvalve(STDStyleonly)fullybyturningclockwise(CW).

2.ConnecttheinertgassupplytothesystemsupplyInletandsettheRapidExchangepressuregaugeto60psi.

3. Temporarilyconnecta0-5inchwatercolumnpressuregaugeormanometertotheprotectedenclosure.

4.Checkoperationofenclosureprotectionventasdetailedabove.See"ImportantNotes."

5.Sealenclosure(s)andadjustenclosurepressurecontrolvalvebyopeningslowlycounterclockwise(CCW)toseta“safe”pressureontheenclosurepressuregauge.

Note:Ifpressuresettingisdifficulttostabilizeorset,(seepage25,“TroubleshootingProcedures”).

IMPORTANT NOTESRegardless of any condition, the Type X Rapid Exchange system is designed to automatically withhold power to the protected enclosure while inducing Rapid Exchange®, for at least five (5) minutes. Normal exchange times should be doubled if large obstructions block inert gas flow.

To test the vent’s operation, gently prod the vent flapper open with a soft pointed object, ( example: eraser end of a pencil) ensuring that the vent valve works freely. On vertically configured vents, this can be accomplished from within the protected enclosure. Side mounted -90 configured vents can be tested by removing the pipe plug at the bottom of the mounting tee. Multiple operations require only one test per day if enclosure is not opened or left unattended.

The volume exchange rate is based on a four (4) enclosure volume exchange. Multiply the required exchange time by 2.5 for applications requiring a ten (10) volume exchange (motors).

The start-up instructionnameplate exchange time slot will feature the standard factor for this system "ONE MINUTE PER CUBIC FOOT", but the unit may feature a set of direct factor nameplates with self-adhesive backing such as “TEN MINUTES”, for application to the start-up instructions, dependent on how the system was specified and purchased. Field modification of this nameplate, to show a direct factor, is acceptable as noted above if the method used to mark the nameplate does not deface the instructions listed. Materials used for the marking must be indelible and withstand prevailing environmental conditions.

6.STD Styles-OpenRapidExchangecontrolvalvefullybyturning90°CCWandquicklyensuretheenclosureprotectionventopens.

SA & FA Styles-Withtheaidofanassistanthavingtwo1/2"combinationwrenchesonhand,placelefthandonsystemmountingplateandpullRapidExchangemanualoperatorfirmlywithrighthandandquicklyensuretheenclosureprotectionventtopens.Ifenclosureprotectionventoperatesproperly,haveassistantcarefullyplacetheopenendofbothwrenchesbehindhandletoholdthemanualoperatorintheoutpositiontemporarily.

Note:Theenclosurepressuregaugeshouldmovequicklyoffscaletotheright,thisisnormalforallRapidExchangepurgingsystems.

7. Readjusttheregulatorto60psiminimum,whileinducingRapidExchange,thetestgaugeshouldthenreadapproximately2inchesofpressureandshouldnotfluctuate.(insufficientenclosurepressurewillcausetheenclosureprotectionventto"shuttle")DONOTexceed5inchesofpressurewithintheprotectedenclosure.

8.CloseenclosurepressurecontrolvalveandRapidExchangecontrolvalve(STDStyles)orremovethetwo1/2"combinationwrenchesfrombehindthehandle.

Note:TheRapidExchangepressuregaugemaynowindicateahighersetpressurethanwasoriginallyset,thisisnormalforallRapidExchangepurgingsystems.

9. SetRETtimer(seepage21fortimerlocationandsettings)forrequiredexchangetimebasedonsystemexchangerateofONEMINUTEPERCUBICFOOT,five(5)minuteminimum.

10.InstallandtightencoverofEPCU.Ensuretheconduitissealedwithapprovedcompounds.

11.Depresstheon-offpushbutton(NRmode)orturnselectorswitchtotheonposition(CBmode).EachLEDshouldilluminatefullyfortwoseconds(selftest),thenallLEDsshouldturnoffexceptPoweroff(solidred)andalarmactivated(flashingred)LEDs.

12.TurnenclosurepressurecontrolvalveslowlyCWtosettheenclosurepressureindicatortoa"Safe"0.25inchpressure.ThesafepressureLEDshouldbeon,thealarmactiveLEDshouldturnoff.Checkfora0.10to0.15inchtrippointbyslowlystrokingtheindicatorfrom0.10to0.25inchreadings.ThesafepressureandalarmactiveLEDsshouldturnonandoffwhentheindicatorreadsbetween0.10and0.15inches.

Note:FAStyleonly-RapidExchangesolenoidvalvewillengageautomaticallyupontimeoutoftheEDTtimer.Shouldtheoperatorrequireadditionaltimetosetastablesafepressureontheenclosurepressureindicator,resettheEDTtimersettingasdescribedonpage21.

Page 23: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

23

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09Set-up Procedure (cont.)

13.STD Style-OpenRapidExchangecontrolvalvefullybyturning90°CCWandquicklyensuretheenclosureprotectionventopens.TheRapidExchangeandtimeractiveLEDsshouldbeon.CheckfortrippointbyturningRapidExchangecontrolValveonandoff.TheRapidExchangeandtimerrunningLEDsshouldturnonandoffasexchangeisengagedanddisengaged,withoutdisturbingthestatusofthesafepressureLED.

SA Style-PlacelefthandonsystemmountingplateandpullRapidExchangemanualoperatorfirmlywithrighthand,untilsolenoidlatches(toholdvalveopenautomatically)thenquicklyensuretheenclosureprotectionventopens.TheRapidExchangeandtimeractiveLEDsshouldbeon.CheckfortrippointbyturningEPCUpowerswitchoffandon(toresetunit).TheRapidExchangeandtimerrunningLEDsshouldnotturnonuntilvalveismorethanhalfopen.AllowsystemtorunthroughRETtimercycleandwatchforsolenoidtodisengage.ThevalveshouldbeabletoshutoffwithoutdisturbingthestatusofthesafepressureLED.

FA Style-RapidExchangesolenoidvalvewillengageautomaticallyupontimeoutoftheEDTtimer,thenquicklyensuretheenclosureprotectionventopens.TheRapidExchangeandtimeractiveLEDsshouldbeonandSLTtimerwillberunning.CheckfortrippointbyturningEPCUpowerswitchoffandon(toresetunit).TheRapidExchangeandtimerrunningLEDsshouldnotturnonuntilvalveismorethanhalfopen.Startingagain,allowsystemtorunthroughEDT,SLTandRETtimercyclesandwatchforsolenoidtodisengage.ThevalveshouldbeabletoshutoffwithoutdisturbingthestatusofthesafepressureLED.

14.HavingensuredthatthesafepressureandtimerrunningLEDsarefunctioningproperly,Operatingprocedureslocatedonpage24maynowbefollowedtostepthroughacompletestartupcycle,ensuringthatthesystemfunctionsnormallyduringallphasesofoperation.

15.Ceasetestingandremovetestequipment.

Model 2002-STD-CB-LHFront View

Start-upinstructionnameplate

Enclosurepressuregauge

RapidExchange

pressuregauge

Enclosurepressurecontrolvalve

LEDstatusnameplate

EXPEPCUenclosure

EXPbreather

drain

Modelidentificationnameplate

RapidExchange

controlvalve

RapidExchange

pressuregauge

Bypassoperating

instructions

EPCUpowerselectorswitch

SystemLEDdisplay

RapidExchange

manualoperator

Start-upinstructionnameplate

Enclosurepressuregauge

LEDstatusnameplate

EPCUpowerselectorswitch

SystemLEDdisplay

EXPEPCUenclosure

Model 2002-FA-CB-LHFront View

Page 24: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

24

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

Operating Sequence

WARNING! Do not exceed a “safe” pressure with the enclosure pressure control regulator.

Operators must follow step-by-step sequence of the start-up instructions nameplate on the protection system.

Do not use the bypass modes without first securing a "hot work" permit.

Never leave the system unattended in bypass modes.

Rapid Exchange Purging OperationWiththeinertgassupplyon,RETtimersetproperly(STDandSAStyles),EDT,SLTandRETtimerssetproperly(FAStyles),EPCUpowerandalarmsystemenergized(ifutilized).

1.Carefullyreadstart-upinstructionnameplateonsystem.

2.Checkoperationoftheenclosureprotectionvent(modelEPV-2,ifutilized),openingitmanuallyseveraltimes.Seepage22,“HelpfulHint.”

3.Sealprotectedenclosure(s).

4. Depresstheon-offpushbutton(NRmode)orturnselectorswitchtotheonposition(CBmode).EachLEDshouldilluminatefullyfortwoseconds,thenallLEDsshouldturnoffexceptpoweroff(solidred)andalarmactivated(flashingred)LEDs.

5.TurnenclosurepressurecontrolregulatorslowlyCCWtosettheenclosurepressureindicatortoa"safe"0.25inchpressure.ThesafepressureLEDshouldbeon,thealarmactiveLEDshouldturnoff.

6. STD Style-OpenRapidExchangecontrolvalvefullybyturning90°CCWandquicklyensuretheenclosureprotectionventopens.TheRapidExchangeandtimeractiveLEDsshouldturnon.

SA Style-PlacelefthandonsystemmountingplateandpullRapidExchangemanualoperatorfirmlywithrighthand,untilsolenoidlatches(toholdvalveopenautomatically)thenquicklyensuretheenclosureprotectionventopens.TheRapidExchangeandtimeractiveLEDsshouldturnon.

FA Style-RapidExchangesolenoidvalvewillengageautomaticallyupontimeoutoftheEDTtimer,thenquicklyensuretheenclosureprotectionventopens.TheRapidExchangeandtimeractiveLEDsshouldbeonandSLTTimerwillberunning.

Note:Onallstyles,ifthesafepressureortimerrunningLEDsblinkonandoffor"flicker"duringthiscycle,EPCUwillresetRETtimer.

7. StandbyuntiltheEPCURETtimercompletesthetimingcycleandenergizesenclosurepower.SafepressureLEDshouldstayon,timerrunningLEDshouldturnoffandpoweronLEDshouldturnon.

8. STD Style-CloseRapidExchangecontrolvalvefullybyturning90°CW.TheRapidExchangeandtimeractiveLEDsshouldbeoff.

SA & FA Styles-AftercompletionoftheRETtimimgcycle,timerRunningLEDshouldturnoffandpoweronLEDshouldturnon.Atthesametime,theRapidExchangesolenoidvalveshoulddeenergizeandtheRapidExchangeLEDshouldturnoff.

9.EnsuretheprotectionsystemenclosurepressureIndicatormaintainsa“safe”0.25inchpressureforone(1)minute.Readjustenclosurepressurecontrolvalveifrequired.

10.If"safe"0.25inchpressureislost,theEPCUwilldeenergizeenclosurepowerandactivatealarmsystem(ifutilized).

Page 25: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

25

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09Troubleshooting Procedures

Problem or Fault Possible Causes Corrective Action

Enclosurepressurecontrolvalvewillnotholdasafe.25inchpressure.

Leakagearoundgasketing,covers,seams,pipingandtubingconnections,conduitconnectionsandelectricalconduitsealsoftheenclosure.

Tightenenclosurelatches:Wheretighteningisnotfeasible,andgasketingmaterialsarenotpractical,holesorgapscanbeclosedwithsiliconesealantappliedfrominsidetheprotectedenclosure.

Enclosurepressureindicatorreadingisdifficulttostabilize.

Insufficientenclosureleakageoropeningoftheventuriorificeiscrimpedtoosmall.

Removetheorifice,cutoffthecrimpedendandreamthetube,thenrecrimpandreinstallthetubetonoteeffect.Astubeisshortened,reamed,andrecrimped,sensitivitydecreases,allowingeasieradjustmentofsetpointontheenclosure.

EnclosureProtectionVent"shuttles"orflutters"

Excessiveleakagefromprotectedenclosure.

Insuffcientprotectivegassupplyheaderpressure.

Checkallpointsaboveandverifyaminimum60psiinjectionpressurereadingontheRapidExchangepressureindicatorduringRapidExchange.

Witha0.0"-5"watercolumntestgaugeinstalledproperly(see"set-upprocedures"page23),slowlyincreasetheRapidExchangeinjectionpressurewiththeRapidExchangevalveengageduntilthiseffectiseliminated.Donotexceed3inchesofpressurewithintheprotectedenclosure.

Enclosurepressureindicatorreadsa"safe"pressurebutthesafepressureLEDisnotilluminated.

ConduitsealbetweenEPCUandprotectedenclosureisnotpouredorisleakingpressurebackintotheEPCU.

EPCUbreatherdrainisclogged(allsystemsexceptPMconfigurations).Safepressureswitchisoutofcalibration.

Withareapositivelyknowntobenonhazardous,removescrewcoveroftheEPCUandattemptacompletestart-upprocedure.Ifthesystemworksproperly,checkenclosurepowerconduitsealforleakageandtheEPCUbreatherdrainforblockage.Ifthesystemdoesnotoperateproperly,calibratethesafepressureswitch.

CalibratebyslowlyadjustingCCWtodecreasethesetpoint,andCWtoraisethesetpoint.

(Donotattempttocalibratetheswitchuntilalleffortstomaketheswitchrespondproperlyhavefailed)

RapidExchangeLEDdoesnotiluminatewhenRapidExchangeisengaged.

FAStyleonly-TheRapidExchangesolenoidcontinuestocyclewithoutstartingtheRETtimer.

ConduitsealbetweenEPCUandprotectedenclosureisnotpouredorisleakingpressurebackintotheEPCU.

EPCUbreatherdrainisclogged(allsystemsexceptPMconfigurations).RapidExchangepressureswitchisoutofcalibration.

Withareapositivelyknowntobenonhazardous,removescrewcoveroftheEPCUandattemptacompletestart-upprocedure.Ifthesystemworksproperly,checkenclosurepowerconduitsealforleakageandtheEPCUbreatherdrainforblockage.Ifthesystemdoesnotoperateproperly,calibratetheRapidExchangepressureswitch.

WithRapidExchangeengaged,calibratebyslowlyadjustingclockwisetodecreasethesetpoint,andcounterclockwisetoraisethesetpoint.

(Donotattempttocalibratetheswitchuntilalleffortstomaketheswitchrespondproperlyhavefailed)

Problemspersists,orifthesystemdoesnotappeartobeoperatingproperly.

Persistingproblems. ContactPepperl+FuchsApplications/CustomerServiceDepartmentat(330)486-0002formoreinformation.

Thissectioncoversthemostcommonproblemsdocumentedwiththissystem.Anyproblemsnotcoveredinthissectionshouldbeaddresseddirectlytoourfactory.Pleaseaddressallserviceneedsto:

Pepperl+Fuchs, Inc. Customer Service Department

Page 26: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

26

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

PEPPERL+FUCHS STANDARD 24-MONTH WARRANTY1. LimitedWarranty.Pepperl+Fuchs,Inc.(“P+F")warrantsPurgeUnitsandcomponentsforPurgeUnitsmanufacturedbyP+F

(“Product"or“Products")tobefreefromdefectsinmaterialandworkmanshipunderNormalUseforaperiodoftwenty-four(24)monthsfromthedateofshipmentofsuchProductsfromP+F’swarehouseorplaceofmanufacture(orfromP+F’sauthorizedrepresentativeordistributor).OnlytheoriginalpurchaserofsuchProducts(the“Customer")shallbeentitledtothebenefitoftheforegoingLimitedWarranty.Norepresentative,agentorsalesmanofP+FisauthorizedtogiveorprovideanywarrantyormakeanyrepresentationcontrarytoorinadditiontotheforegoingLimitedWarranty.

2. InspectionandClaims.CustomermustinspectandtestallProductsuponreceipt.AllclaimsundertheLimitedWarrantyprovidedhereinmustbemadewithinthirty(30)daysofthediscoveryofthedefect.CustomermustobtainshippinginstructionsfromP+FpriortoreturninganyProduct,whichProductmustbereturnedatCustomer’sexpenseinaccordancewithP+F’sinstructions.

3. LimitationsandExclusions.“NormalUse"shallmeanuseandoperationwithinratedcapacities,atthecorrectvoltage,andwithanyrequiredmaintenanceasprovidedintheapplicableP+FOperatingManuals.TheLimitedWarrantyprovidedhereindoesnotapplyto(i)anyProductswhichhavebeenalteredormodifiedinanywayordisassembledbytheCustomeroranyoneelse,(ii)anyProductswhichhavebeensubjecttomisuse,negligenceoraccident,orimproperlyinstalled,changed,substitutedorreplaced,(iii)anypartorcomponentnotmanufacturedbyP+F,or(iv)anypartorcomponentthatissubjecttowearorconsumption.ForpartsorcomponentsnotmanufacturedbyP+F,theCustomeroranyotheruserorownershallhaveonlythewarrantyprovidedbythemanufacturerofsuchpartorcomponent.TheLimitedWarrantysetforthhereinisalsosubjecttothefollowing:

(1) TheLimitedWarrantyislimitedtoelectronicandmechanicalperformanceonly,asexpresslydetailedintheproductspecifications,anddoesnotapplytocosmeticappearance;

(2) TheLimitedWarrantyshallnotapplytoanycablesattachedto,orintegratedwith,anyProducts.

(3) TheLimitedWarrantyshallnotapplytoanyProductswhicharestored,orutilized,inharshenvironmentalorelectricalconditionsoutsideP+F’swrittenspecifications.

THELIMITEDWARRANTYSETFORTHHEREINISTHEONLYWARRANTYMADEBYP+FWITHRESPECTTOTHEPRODUCTS.ITISEXPRESSLYAGREEDANDUNDERSTOODTHATP+FMAKESNOWARRANTYOFMERCHANTABILITYORFITNESSFORAPARTICULARPURPOSE.EXCEPTFORTHELIMITEDWARRANTYSETFORTHHEREIN,THEREISNOOTHERWARRANTY,EXPRESS,IMPLIEDORSTATUTORY;ANDTHEREISNOAFFIRMATIONOFFACTORPROMISEBYP+FWITHREFERENCETOTHEPRODUCTS.INNOEVENTSHALLP+FBELIABLEFORACTUALORANTICIPATEDLOSTPROFITSORFORINCIDENTALORCONSEQUENTIALORPUNITIVEDAMAGESORFORDAMAGESRESULTINGFROMBUSINESSINTERRUPTION,ORINJURYORDEATHOFPERSONS,ORINJURYTOPROPERTY.P+F’SLIABILITYONANYCLAIMOFANYKINDARISINGOUTOF,CONNECTEDWITHORRESULTINGFROMTHEDESIGN,MANUFACTURE,SALE,REPAIROROPERATIONOFAPRODUCT,SHALLNOTEXCEEDTHEPRICEALLOCABLETOTHATPRODUCTORTHEPARTTHEREOFWHICHGIVESRISETOTHECLAIM.THEREMEDYSETFORTHINTHISLIMITEDWARRANTYCONSTITUTESTHESOLEANDEXCLUSIVEREMEDYOFTHECUSTOMER.P+FSHALLNOTBELIABLEFORPENALTIESOFANYDESCRIPTION.

4. LimitationofRemedies.IntheeventofP+F’sliability,whetheronthisLimitedWarrantyorbasedoncontract,tort(including,butnotlimitedto,negligenceandstrictliability)orotherwise,Customer’ssoleandexclusiveremedywillbelimitedto,atP+F’soption,therepairorreplacement(f/o/bP+F’splaceofmanufacture)byP+Fofanynon-conformingitemsforwhichclaimismadebyCustomerinaccordancewithparagraph2,ortherepaymentoftheportionofthepurchasepricepaidbyCustomerattributabletothenon-conformingitem.

5. ResponsibilityofCustomer:SafetyandProtectionPrecautions.P+FtakesgreatcaretodesignandbuildreliableanddependableProducts;however,someProductscanfaileventually.Customermusttakeprecautionstodesignitsequipmenttopreventpropertydamageandpersonalinjuryintheunlikelyeventofafailure.ASAMATTEROFPOLICY,P+FDOESNOTRECOMMENDTHEINSTALLATIONOFPRODUCTSASTHESOLEDEVICEFORTHEPROTECTIONOFPERSONNELORPROPERTYAND,THEREFORE,THECUSTOMERSHOULDBUILDINREDUNDANCYORDUALCONTROLUSINGAPPROVEDSAFETYDEVICESFORTHESEAPPLICATIONS.

6. Conflicts.IntheeventthereisanyconflictbetweentheprovisionsofthisLimitedWarrantyandanyprovisionscontainedinanyorders,offers,acceptancesorotherwritingsorstatementsprovidedormadebyCustomertoP+F,theprovisionsofthisLimitedWarrantyshallprevail,andthecontractbetweenP+FandtheCustomershallbedeemedformedonlyupontheprovisionssetforthinthisLimitedWarranty,andanyadditionalorconflictingprovisioninsertedbyCustomershallbeofnoforceoreffect.

Warranty Terms and Conditions

Page 27: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

27

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09Notes

Page 28: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

28

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

Notes

Page 29: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

29

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09Notes

Page 30: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

30

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09

System Maintenance

Regular MaintenanceDraintheprotectionsystemregulatorfrequentlyandcleansystemwithnonsolventcleaningagentsonly.

Long-Term MaintenanceCalibratetheenclosurepressureindicatorto0inchesbyventingthepurgepressurereferenceportandtheprotectedenclosuretoatmosphereandadjustingthecalibrationscrewinthelowercenterportionoftheindicator’sface.

Fullyopentheenclosurepressurecontrolregulator,toblowoutanydepositsaroundthetipofthevalveandtoensurethattheenclosureprotectionventisoperatingproperly,thencarefullyreadjustsystemaccordingtotheset-upprocedureandoperatingsequenceonpages22-24.Replaceortightenstempackingnutasrequiredtoprohibitstempackingleakage.

Carefullydisassembletheenclosureprotectionventbylooseningthetwobottomhexnutsthatholdtheunittogether.

(DO NOT REMOVE CAP NUTS ON TOP OF VENT BODY)

Carefullycleantheflappervalveandventbodyseatswithwarmsoapandwater,beingcarefulnottoextendtheventvalvebeyonditsnormalopeningpoint,andbeingcarefulnottoexertanystressonthevalvehinge.

Examinetheentireprotectionsystemandtheprotectedenclosure(s),andreplaceanydefectivepartsduringroutineshutdownoftheprotectedenclosure(s).PartsareavailablefromPepperl+Fuchsonimmediatenoticeasrequired.

MAINTENANCE SCHEDULEDate Work performed Performed by

Page 31: Installation and Operation Manual: Model 2002 Type X Rapid ... · INSTALLATION AND OPERATION MANUAL. Model 2002 Installation and Operation Manual 2 Part No. 512352 Drawing No. 129-0211a

Model 2002 Installation and Operation Manual

31

Par

t No.

512

352

Dra

win

g N

o. 1

29-0

211a

03/

09Systems Identification & Application Information

Date of installation _____________________________________________________

Unit serial #____________________________________________________________

Item ___________________________________________________________________

Customer P.O.# ________________________________________________________

Customer project# _____________________________________________________

Service ________________________________________________________________

Type __________________________________________________________________

Features ______________________________________________________________

Application ____________________________________________________________

Notes: _______________________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________

_____________________________________________________________________________________