Installation and Maintenance Instructions Touchscreen Programmable Thermostat Touchscreen programmable room thermostat, with clear LCD for controlling on/off times and temperatures Reliance Worldwide Corporation (UK) Ltd Worcester Road, Evesham, Worcester, WR11 4RA, UK Tel: +44 (0)1386 712 400 Fax: +44 (0)1895 712 401 www.rwc.co.uk Reliance Worldwide Corporation (UK) Ltd reserves the right to make changes to the product which may affect the accuracy of information contained in this leaflet. ZINS100051_001_11/15

Installation and Maintenance Instructions · 2020-07-06 · Setting the clock time & day.....7 Heating program details ... This installation guide is provided to give instruction

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Installation and Maintenance Instructions · 2020-07-06 · Setting the clock time & day.....7 Heating program details ... This installation guide is provided to give instruction

Installation and Maintenance Instructions

Touchscreen Programmable Thermostat

Touchscreen programmable room thermostat, with clear LCD for controlling on/off times and temperatures

Reliance Worldwide Corporation (UK) LtdWorcester Road,

Evesham,Worcester, WR11 4RA,

UK

Tel: +44 (0)1386 712 400 Fax: +44 (0)1895 712 401

www.rwc.co.uk

Reliance Worldwide Corporation (UK) Ltd reserves the right to make changes to the product which may affect the accuracy of information contained in this leaflet.

ZINS100051_001_11/15

Page 2: Installation and Maintenance Instructions · 2020-07-06 · Setting the clock time & day.....7 Heating program details ... This installation guide is provided to give instruction

17

Page 3: Installation and Maintenance Instructions · 2020-07-06 · Setting the clock time & day.....7 Heating program details ... This installation guide is provided to give instruction

116

Contents Reliance Worldwide Corporation (UK) Ltd....2

General function............................................3

Working parameters & specification.............4

Installation;....................................................4 Location....................................5 Mounting...................................5

Wiring Diagram.............................................6

LCD Display..................................................6

Settings; Switch thermostat on/off................7 Setting the clock time & day...........7 Heating program details.................8 Manual override when in time program control mode....................9 Manual temperature control...........10

Advanced Settings;.......................................10 Parameter table...............11 Detailed...........................11

Troubleshooting.............................................15

Notes.............................................................16

Notes

Page 4: Installation and Maintenance Instructions · 2020-07-06 · Setting the clock time & day.....7 Heating program details ... This installation guide is provided to give instruction

2 15

Reliance Worldwide Corporation (UK) Ltd

Reliance Worldwide Corporation (UK) Ltd are part of the Australian based group of companies collectively known as Reliance Worldwide Corporation, with the UK brand known as Reliance Water Controls.

Reliance Worldwide Corporation (UK) Ltd is a specialist in the design, distribution and technical support for temperature and flow controls.

With group offices and manufacturing plants throughout the world RWC offers a wealth of knowledge and expertise which is reflected throughout our products. Being part of many specialised trade associations and having our own UKAS accredited laboratory, makes us at the forefront of any new regulations or changes which impact the industry, and allows for continous product development and innovation, within our specialised product area.

Our core product range is related to thermostatic control, with the manufacturing undertaken at our head office in Brisbane Australia, we have an extensive range of thermostatic mixing valves, shower control valves, and taps all which use the same high quality technology to control the temperature of water, within this range we have different valves to suit various applications and working parameters, including both TMV2 and TMV3 approved controls.

RWC, are market leaders of OEM controls with a complete range of safety valves for use in G3 unvented systems and a wide range of Underfloor heating controls (UFH) to allow for safe distribution of hot water, throughout a property. This range includes; thermostatic control valves for safe hot water temperatures, manifolds to enable even distribution, complete UFH kits to allow ease of installation & commisioning, and a range of modern and stylish programmers to complement these controls.

TroubleshootingSympton Cause Action

No display No electrical power to thermostat Check thermostat is switched “on”, and that the fused spur is switched “on”.

Check fuse in fused spur.

Check Live and Neutral is connected to correct terminals on thermostat.

No heat to heating zone Room thermostat not set correctly Set the thermostat to a higher temperature setting to “demand” heat.

Thermal actuators / UFH pump not wired correctly

Check that the thermal actuators / UFH pump are connected to the Live output terminal (3) on the thermostat via the UFH wiring centre.

Boiler not wired correctly Check that the boiler and pump are connected to the thermostat in accordance with the boiler manufacturers installation instructions. A volt free relay is available in the thermostat.

Boiler not set correctly Check boiler is switched “on” and controls correctly set.

Check boiler system pressure gauge to ensure system has been filled correctly. Note. Boiler will not function below the minimum system pressure.

Error message in display:ER1

Internal temperature sensor failure

Check that Parameter 2 Sen in Advanced settings is correctly set.

Error message in display:ER2

External sensor failure or incorrect parameter setting.

Check that external sensor is connected correctly.

Check that Parameter 2 Sen in Advanced settings is correctly set.

Thermostat always in Manual mode i.e. Timed program control mode cannot be set.

Incorrect parameter setting Check Parameter 5 Prg in Advanced settings is correctly set.Note. OF is Manual mode.

Cannot set time / temperature program for each day

Check Parameter 5 Prg in Advanced settings is correctly set.

Poor room temperature control. Check Parameter 4 Dif in Advanced settings is correctly set.

Page 5: Installation and Maintenance Instructions · 2020-07-06 · Setting the clock time & day.....7 Heating program details ... This installation guide is provided to give instruction

14 3

General Function

The RWC touchscreen programmable thermostats combine the functions of a time clock and room thermostat into a modern, simple to use controller that allows the user to programme different temperatures for different times to suit individual requirements. It offers 7-day programming; allowing each day to be set differently, if so required. Additionally the unit can be set to 5/2-day mode allowing one set of programmes to be used for weekdays with a different set available for the weekends, and a 6/1-day mode which can be set to cater for a longer working week. Each working day allows for up-to six events to be programmed.

• 7-day, 5/2-day or 6/1-day programming options for complete flexibility

• 6 programmable (time and temperature) events per working day• Pre-installed, preset time, temperature heating program• User override of temperature program setting• Manual/timed operation - user selectable• Touchscreen key lock function• Large, easy to read, back lit LCD display• Battery back up to retain settings if power failure• Frost protection if thermostat is switched off• Double temperature sensor option for underfloor heating• Available in white or black finish to suit all interior designs• Precise temperature control to +/- 1°C• Ergonomic, unobtrusive, modern styling

Parameter 12 LPDe-frost switch: Allows the de-frost function to be turned on or off so the programmer will automatically turn on once the de-frost temperature is reached. The default setting is on.

Parameter 13 TPDe-frost temperature: Allows you to set the temperature in which the de-frost function will be enabled, it is adjustable between 5°C and 12°C. The default is 5°C.

Parameter 14 SFExternal thermostat: Allows you to turn the thermostat on or off. The default is off.

Parameter 15 CFTemperature display: Allows you to adjust the programmer to display in Celsisus or Fahrenheit. The default is Celsius.

Parameter A FacFactory re set: All factory default settings can be restored.

Page 6: Installation and Maintenance Instructions · 2020-07-06 · Setting the clock time & day.....7 Heating program details ... This installation guide is provided to give instruction

4 13

Working parameters & specification

Power consumption: <2WPower supply: 85 to 265Vac 50/60HzOutput switches: Active contact Live output - terminal 3 Volt free contacts - terminals 4 & 5Max switch current: 3AOn/Off differential temperature: 0.5 to 5°CThermostat switching differential: Default 1°CTransport and storage temperature: 20 to 30°C Relative humidity: <90% RH (non condensing)Setting temperature range: 5 to 35°C (0.5°C steps)Accuracy: 1°CTerminal block - maximum wire size: 2.5mm2Ambient working temperature range: 0 to 50°CFrost Protection Function: Default 5°CExtrenal sensor temperature: 5 to 60°C

Installation

This installation guide is provided to give instruction on the best installation practices that should be observed to ensure the correct functioning of the RWC touchscreen programmable thermostat.

This product should only be installed by a qualified electrician, and should be in accordance with the current edition of the IEEE wiring regulations and any relevant standard or building regulation.

Parameter 6 RleVolt free relay setting: The relay switching condition can be set in 2 ways:1. When the main loop output is 230Vac, the relay contacts are

closed. This is the heating demand condition (Default setting).2. When the main loop output is 0V as, the relay contacts are

closed. This is the heating satisfied condition. Setting '00' corresponds with the main loop output; if the output switch is at open state 00 refers to open and when the main output switch is closed 00 refers to closed, where as setting '01' is the opposite.

Parameter 7 Dly Volt free relay time delay: To prevent rapid switching, the operation of the volt free relay can be delayed by up to 5 minutes after the thermostat switches “on” to demand heat. The default is 0 which means there is no time delay. The volt free relay operation will have no time delay when the thermostat switches “off” when the heating is satisfied.

Parameter 8 HitMaximum setting temperature: The maximum thermostat setting temperature can be limited to between 35° and 60°C. The default is 35°C.

Parameter 9 LigBacklight: Allows the backlight to be turned on or off. The default setting is on.

Parameter 10 LTBacklight time: This is the time the backlight will remain lit for until automatically switching off it can be set between 10 and 30 seconds. The default is 15 seconds.

Parameter 11 PESound: Allows the touch screen selection sound to be turned on or off. The default setting is on.

Page 7: Installation and Maintenance Instructions · 2020-07-06 · Setting the clock time & day.....7 Heating program details ... This installation guide is provided to give instruction

12 5

Location

The RWC touchscreen programmable room thermostats are for use in either a domestic or commercial environment and should be mounted in a suitable location free from direct sun light , a heat source, or any electrical goods as these may provide a false reading.

Mounting

Please note this programmable room thermostat is designed to fit to a standard single electrical mounting box, with a depth no less than 35mm.

Un-clip the mounting bracket from the back of the programmable room thermostat.

Wire the terminals as per the wiring diagram and then secure this to the electrical mounting box using the securing screws provided, please take care to ensure the positioning lines up with the indents in the back of the casing on the programmable room thermostat.

The programmable room thermostat, will then clip on to the mounting bracket; position the top of the programmer on the bracket first and then push down the bottom to clip securely. Please do not push directly on the LCD as this may cause damage to the display.

Advanced settings; Detailed

Parameter 1 AdjRecalibration of the thermostat: This allows the thermostat to be recalibrated to suit installation requirements.

Parameter 2 SenSensor selection: This allows the temperature sensor to be selected; either the internal sensor, external or both floor sensors can be selected. The default is internal air temperature sensor.

Parameter 3 LitMaximum floor temperature limit: The maximum floor temperature can be set for underfloor heating applications. The default is 35°C.

Parameter 4 DifSwitch differential (bandwidth): This allows the switching differential to be increased. The default is 1°C which means that the heating (or pump) will switch on 1°C below the set temperature and switch off when the set temperature is achieved. The default is 1°C.

Parameter 5 PrgProgram mode: Four program methods are selectable. 1. 5 working days + 2 non working days: This allows 6 temperature changes at defined times each week day, and 2 temperature changes at defined times at the weekend.2. 6 working days + 1 non working day: This allows 6 temperature changes at defined times each working day, and 2 temperature changes at defined times for the non working day.3. 7 day program: This allows 6 temperature changes at defined times each day of the week.4. Program off. The thermostat will be in manual mode only. The default program is 5 working days and 2 non working days.

Page 8: Installation and Maintenance Instructions · 2020-07-06 · Setting the clock time & day.....7 Heating program details ... This installation guide is provided to give instruction

6 11

Wiring

Terminals 1. Live in2. Neutral in3. Live output switch4. Volt free switch contact in5. Volt free switch contact out6. External floor sensor in7. External floor sensor out

LCD Display

1. Power2. Day display3. Manual control4. Time control5. Clock/Setting

temperature/Off6. Time program7. Heating8. Menu9. Down10. Up11. Set12. Temperature13. Ambient Temperature

6

7

13

2 43

12

811 910

1

UP DOWN MENUSET

POWER

C

5

Parameter table

Parameter Description Setting Default

1Adj Recalibration -9 to +9 0°C

2Sen Sensor selection IN = internal sen-sor, OU = external sensor, AL = double sensor

IN

3Lit Maximum floor temperature limit

5°C to 60°C 35°C

4Dif Switch differential (bandwidth)

0.5°C to 5°C 1°C

5Prg Program mode 5+2, 6+1, 7 day, off 5+2

6Rle Volt free relay output condition

00 = Same state as main loop output01 = Opposite state as main loop output

00

7Dly Volt free contact time delay

0 to 5 minutes 0

8Hit Maximum tempera-ture

35°C to 60°C 35°C

9Lig Backlight On or Off On

10LT Backlight time 10 to 30 seconds 15 seconds

11PE Sound On or Off On

12LP De-frost switch On or Off On

13TP De-frost temperature 5°C to 12°C 5°C

14SF External Thermostat On/Off/SFSF - will retain setting after power has been cut

Off

15CF Temperature Display C = CelsiusF = Fahrenheit

C

AFac Reset to factory defaults

Change to “- -“ to re-set to factory default

“-“ after reset

Page 9: Installation and Maintenance Instructions · 2020-07-06 · Setting the clock time & day.....7 Heating program details ... This installation guide is provided to give instruction

10 7

Settings Switch thermostat on/offTo turn the thermostat output on or off:Press the “power” button.When the thermostat is turned “off”, the display will alternately show “OFF” and the current time. When the thermostat is turned “on”, the display will alternately show the setting temperature and current time.

To save energy, the backlight will automatically dim after 15 seconds. To switch backlight on, press the lower key area of the touchscreen (set/up/down/menu).

The thermostat has a lock function to disable the key area of the touchscreen. To lock:Press and hold SET for 3 seconds when LOC will be displayed.To unlock: Press and hold SET for 3 seconds.

Setting the clock: time and day1. Press SET and the minutes will flash. Use UP and DOWN to set

the minutes. 2. Press SET and the hours will flash. Again use UP and DOWN to

set the hours.3. Press SET and the day will flash. Note. 1 equals Monday, 2

equals Tuesday etc. Use UP and DOWN to set the correct day.4. Press POWER to save and exit to the main display.

UP DOWN MENUSET

POWER

C

UP DOWN MENUSET

POWER

C

Manual temperature control

The thermostat can be set to operate at a fixed temperature throughout the day and night.To set:

• Press MENU, a HAND icon will be displayed.• Press UP and DOWN to set the temperature.To cancel:• Press MENU, the HAND icon will disappear, and the CLOCK icon will be displayed indicating timed auto program control.

Advanced Settings

These are usually set by the installer on the initial set up.

• Press and hold “Menu” first, then press “POWER” for 3 seconds.• Press MENU to select the parameter to be adjusted, and then use

UP and DOWN to change the value, when complete press MENU to move to the next parameter.

• Press POWER to save and exit to the main display.

UP DOWN MENUSET

POWER

C

Page 10: Installation and Maintenance Instructions · 2020-07-06 · Setting the clock time & day.....7 Heating program details ... This installation guide is provided to give instruction

Heating program details

The heating program allows you to have different temperatures through the day. For example you may want to get up in the morning with the property warm, and have it cooler while you are at work, then have it warmer in the evening, and finally have it cooler while you are sleeping.The thermostat has a pre-installed time / temperature program, with 4 programming options, these can be altered using the Advanced Settings (see page 10):• 5 working day / 2 non working day: 6 time / temperature periods

for each working day and 2 time / temperature periods for non working days (Default program).

• 6 working day / 1 non working day: 6 time / temperature periods for each working day and 2 time / temperature periods for non working days.

• 7 day program: 6 time / temperature periods for each day.• Program off: Manual operation only.See table below for details on the program setup:

Time Periods Icons Default Time Default Temperature

Working days

1Wake Up

06:00

22°C

2Leave AM

08:00

3Return AM

11.30

4Leave PM

12:30

5Return PM

17:00

6Sleep

22:00

Weekends 1Wake Up

08:00

2Sleep

23:00

8 9

To modify the times / temperatures shown in the table:• Press and hold MENU for 3 seconds. • Press UP or DOWN to set the time for period 1, then press

MENU.• Press UP or DOWN to set the temperature for period 1, then

press MENU to adjust next time / temperature period.• Repeat these steps for the remaining time / temperature periods.• Finally press POWER to save the changes and exit to the main

display.

Note. Press MENU repeatedly to move to the value to be changed. Press POWER at any point to save the changes and return to the main display.

Manual override when in timed program control modeTo manually override the current temperature setting and set a different temperature for the current time period:• Press POWER to turn unit on• Press UP or DOWN to select the desired temperature.

The HAND icon will be displayed next to the CLOCK icon when the temperature override is operating.To cancel the override:• Press MENU, the HAND icon will disappear from the display.Note. The thermostat will return to the timed program at the next programmed switch point.

UP DOWN MENUSET

POWER

C