Contents Page IMPORTANT! Please Read Before Starting .................................. 2 1. GENERAL .......................................................... 3 1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Unit 1-3. Optional Copper Tubing Kit 1-4. Type of Copper Tube and Insulation Material 1-5. Additional Materials Required for Installation 2. INSTALLATION SITE SELECTION ................... 4 2-1. Indoor Unit 2-2. Outdoor Unit 3. HOW TO INSTALL THE INDOOR UNIT ............ 12 3-1. Remove the Rear Panel from the Unit 3-2. Make a Hole 3-3. Install the Rear Panel on the Wall 3-4. Removing and Installing the Grille 3-5. Shape the Indoor Side Tubing 3-6. Wiring Instructions 3-7. Wire Size and Length 3-8. Wiring Instructions for Inter-unit Connections 3-9. Mounting 3-10. Frame Fastening Method 3-11. Drain Hose 4. HOW TO INSTALL THE OUTDOOR UNIT ........ 22 4-1. Wiring Instructions for the Outdoor Unit 4-2. Routing the Tubing and Wiring 5. REFRIGERANT TUBING .................................. 23 5-1. Use of the Flaring Method 5-2. Flaring Procedure with a Flare Tool 5-3. Caution before Connecting Tubes Tightly 5-4. Connecting Tubing between Indoor and Outdoor Units 5-5. Insulation of Refrigerant Tubing 5-6. Taping the Tubes 5-7. Finishing the Installation 6. AIR PURGING................................................... 25 Air Purging with a Vacuum Pump (for Test Run) Basic Functions of the Service Valves Pump Down Service Valve Connections This air conditioner uses the new refrigerant R410A. Refrigerant service valve size = 5/16" NOTE 85264190498000 © SANYO 2010 INSTALLATION INSTRUCTIONS Model Combinations Combine indoor and outdoor units only as listed below. Indoor Unit Outdoor Unit KHS3082 CH3082 KHS3682 CH3682 Power Source: 60 Hz, single-phase, 230/208 V – Inverter Split System Air Conditioner – COOL/ DRY/HEAT Model Be sure to read the yellow instruction sheet attached to the outdoor unit for models using the new refrigerant R410A. The illustrations are based on the typical appearance of a standard model. Consequently, the shape may differ from that of the air conditioner that you are installing. NOTE 7. REMOTE CONTROL UNIT INSTALLATION POSITION ......................................................... 29 7-1. Mounting on a Wall 8. ADDRESS SWITCH .......................................... 30 8-1. Address Setting of the Remote Control Unit SANYO North America Corporation In Canada Commercial Solutions Division SANYO Canada Inc. 2055 Sanyo Ave., San Diego 201 Creditview Road, Woodbridge CA 92154, U.S.A. Ontario, L4L 9T1, Canada W 09-191 CH3082-3682 2/16/10 1:17 PM Page a

INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

ContentsPage

IMPORTANT!Please Read Before Starting .................................. 2

1. GENERAL .......................................................... 31-1. Tools Required for Installation (not supplied)1-2. Accessories Supplied with Unit1-3. Optional Copper Tubing Kit1-4. Type of Copper Tube and Insulation Material1-5. Additional Materials Required for Installation

2. INSTALLATION SITE SELECTION ................... 42-1. Indoor Unit2-2. Outdoor Unit

3. HOW TO INSTALL THE INDOOR UNIT ............ 123-1. Remove the Rear Panel from the Unit3-2. Make a Hole3-3. Install the Rear Panel on the Wall3-4. Removing and Installing the Grille3-5. Shape the Indoor Side Tubing3-6. Wiring Instructions3-7. Wire Size and Length3-8. Wiring Instructions for Inter-unit Connections3-9. Mounting3-10. Frame Fastening Method3-11. Drain Hose

4. HOW TO INSTALL THE OUTDOOR UNIT ........ 224-1. Wiring Instructions for the Outdoor Unit4-2. Routing the Tubing and Wiring

5. REFRIGERANT TUBING .................................. 235-1. Use of the Flaring Method5-2. Flaring Procedure with a Flare Tool5-3. Caution before Connecting Tubes Tightly5-4. Connecting Tubing between Indoor and

Outdoor Units5-5. Insulation of Refrigerant Tubing5-6. Taping the Tubes5-7. Finishing the Installation

6. AIR PURGING................................................... 25■ Air Purging with a Vacuum Pump (for Test Run)■ Basic Functions of the Service Valves■ Pump Down■ Service Valve Connections

This air conditioner uses the new refrigerant R410A.Refrigerant service valve size = 5/16"NOTE

85264190498000 © SANYO 2010

INSTALLATION INSTRUCTIONS

Model Combinations

Combine indoor and outdoor units only as listedbelow.

Indoor Unit Outdoor Unit

KHS3082 CH3082

KHS3682 CH3682

Power Source:60 Hz, single-phase, 230/208 V

– Inverter Split System Air Conditioner – COOL/DRY/HEAT Model

Be sure to read the yellow instruction sheetattached to the outdoor unit for models using thenew refrigerant R410A.

The illustrations are based on the typical appearance ofa standard model. Consequently, the shape may differfrom that of the air conditioner that you are installing.

NOTE

7. REMOTE CONTROL UNIT INSTALLATION POSITION ......................................................... 297-1. Mounting on a Wall

8. ADDRESS SWITCH .......................................... 308-1. Address Setting of the Remote

Control Unit

SANYO North America Corporation In CanadaCommercial Solutions Division SANYO Canada Inc.2055 Sanyo Ave., San Diego 201 Creditview Road, WoodbridgeCA 92154, U.S.A. Ontario, L4L 9T1, Canada

W

09-191 CH3082-3682 2/16/10 1:17 PM Page a

Page 2: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

2

IMPORTANT! Please Read Before Starting

This air conditioning system meets strict safety and operatingstandards. As the installer or service person, it is an importantpart of your job to install or service the system so it operatessafely and efficiently.

For safe installation and trouble-free operation, youmust:● Carefully read this instruction booklet before beginning.● Follow each installation or repair step exactly as shown.● Observe all local, state, and national electrical codes.● Pay close attention to all warning and caution notices

given in this manual.This symbol refers to a hazardor unsafe practice which canresult in severe personal injuryor death.

This symbol refers to a hazardor unsafe practice which canresult in personal injury or prod-uct or property damage.

If Necessary, Get HelpThese instructions are all you need for most installationsites and maintenance conditions. If you require help for aspecial problem, contact our sales/service outlet or yourcertified dealer for additional instructions.

In Case of Improper InstallationThe manufacturer shall in no way be responsible for improp-er installation or maintenance service, including failure tofollow the instructions in this document.

SPECIAL PRECAUTIONS

When Wiring

ELECTRICAL SHOCK CAN CAUSE SEVEREPERSONAL INJURY OR DEATH. ONLY AQUALIFIED, EXPERIENCED ELECTRICIANSHOULD ATTEMPT TO WIRE THIS SYSTEM.

• Do not supply power to the unit until all wiring and tubingare completed or reconnected and checked.

• Highly dangerous electrical voltages are used in thissystem. Carefully refer to the wiring diagram and theseinstructions when wiring. Improper connections andinadequate grounding can cause accidental injury ordeath.

• Ground the unit following local electrical codes.• Connect all wiring tightly. Loose wiring may cause over-

heating at connection points and a possible fire hazard.

When Transporting

Be careful when picking up and moving the indoor and out-door units. Get a partner to help, and bend your knees whenlifting to reduce strain on your back. Sharp edges or thin alu-minum fins on the air conditioner can cut your fingers.

When Installing…

…In a Ceiling or Wall

Make sure the ceiling/wall is strong enough to hold theunit’s weight. It may be necessary to construct a strongwood or metal frame to provide added support.

…In a Room

Properly insulate any tubing run inside a room to prevent“sweating” that can cause dripping and water damage towalls and floors.

…In Moist or Uneven Locations

Use a raised concrete pad or concrete blocks to provide asolid, level foundation for the outdoor unit. This preventswater damage and abnormal vibration.

…In an Area with High Winds

Securely anchor the outdoor unit down with bolts and ametal frame. Provide a suitable air baffle.

…In a Snowy Area

Install the outdoor unit on a raised platform that is higherthan drifting snow. Provide snow vents.

When Connecting Refrigerant Tubing

• Use the flare method for connecting tubing.

• Apply refrigerant lubricant to the matching surfaces ofthe flare and union tubes before connecting them, thentighten the nut with a torque wrench for a leak-freeconnection.

• Check carefully for leaks before starting the test run.

When Servicing

• Turn the power OFF at the main power box (mains) beforeopening the unit to check or repair electrical parts andwiring.

• Keep your fingers and clothing away from any movingparts.

• Clean up the site after you finish, remembering to checkthat no metal scraps or bits of wiring have been left insidethe unit being serviced.

Others

• Ventilate any enclosed areas when installing or testingthe refrigeration system. Escaped refrigerant gas, oncontact with fire or heat, can produce dangerouslytoxic gas.

• Confirm upon completing installation that no refrigerantgas is leaking. If escaped gas comes in contact with astove, gas water heater, electric room heater or other heatsource, it can produce dangerously toxic gas.

WARNING

WARNING

CAUTION

CAUTION

09-191 CH3082-3682 2/16/10 1:17 PM Page 2

Page 3: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

3

1. General

This booklet briefly outlines where and how to install theair conditioning system. Please read over the entire setof instructions for the indoor and outdoor units and makesure all accessory parts listed are with the system beforebeginning.

1-1. Tools Required for Installation (not supplied)1. Standard screwdriver2. Phillips head screwdriver3. Knife or wire stripper4. Tape measure5. Carpenter’s level

6. Sabre saw or key hole saw7. Hacksaw8. Core bits9. Hammer

10. Drill11. Tube cutter12. Tube flaring tool13. Torque wrench14. Adjustable wrench15. Reamer (for deburring)

1-2. Accessories Supplied with Unit

Table 1

1-3. Optional Copper Tubing Kit

Copper tubing for connecting the outdoor unit to theindoor unit is available in kits which contain the narrowand wide tubing, fittings and insulation. Consult yournearest sales outlet or air conditioning workshop.

1-4. Type of Copper Tube and Insulation Material

If you wish to purchase these materials separately froma local source, you will need:

1. Deoxidized annealed copper tube for refrigerant tub-ing as detailed in Table 2.

Cut each tube to the appropriate lengths 1' to 1'4"(30 cm to 40 cm) to dampen vibration between units.

Table 2

2. Foamed polyethylene insulation for the specifiedcopper tubes as required to precise length of tubing.Wall thickness of the insulation should be not lessthan 5/16" (8 mm).

3. Use insulated copper wire for field wiring. Wire sizevaries with the total length of wiring. Refer to 3-6.Wiring Instructions for details.

Parts Figure Q’ty Parts Figure Q’ty

1

1 Tapping screw

Rawl plug

Truss-headPhillips5/32 × 5/8" (4×16 mm)

8

2AAA alkaline battery

2

10

Tapping screwTruss-headPhillips5/32 × 13/32" (4×10 mm)

2

Parts Figure Q’ty

Remote control unit

Remote control unit holder

Air clean filter

1

1Flare insulation

Drain hoseadapter

CAUTION Check local electrical codesand regulations beforeobtaining wire. Also, checkany specified instructions orlimitations.

ModelNarrow Tube Wide Tube

Outer Dia. Thickness Outer Dia. Thickness

KHS3082 3/8" (9.52 mm) 0.0314" (0.8 mm) 5/8" (15.88 mm) 0.0393" (1.0 mm)

KHS3682 3/8" (9.52 mm) 0.0314" (0.8 mm) 5/8" (15.88 mm) 0.0393" (1.0 mm)

09-191 CH3082-3682 2/16/10 1:17 PM Page 3

Page 4: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

4

1-5. Additional Materials Required for Installation

1. Refrigeration (armored) tape2. Insulated staples or clamps for connecting wire

(See local codes.)3. Putty4. Refrigeration lubricant5. Clamps or saddles to secure refrigerant tubing

2. Installation Site Selection

2-1. Indoor Unit

AVOID:

● direct sunlight.

● nearby heat sources that may affect performance of the unit.

● areas where leakage of flammable gas may be expected.

● places where large amounts of oil mist exist.

DO:

● select an appropriate position from which every corner ofthe room can be uniformly cooled. (High on a wall is best.)

● select a location that will hold the weight of the unit.

● select a location where tubing and drain hose have theshortest run to the outside. (Fig. 1)

● allow room for operation and maintenance as well as unre-stricted air flow around the unit. (Fig. 2)

● install the unit within the maximum elevation difference (H)above or below the outdoor unit and within the maximum tub-ing length (L) from the outdoor unit as detailed in Table 3 andFig. 3a.

● install the indoor unit more than 3.3' (1 m) away from anyantenna or power lines or connecting wires used for television,radio, telephone, security system, or intercom. Electrical noisefrom any of these sources may affect operation.

Drain hose

Indoor unit

Outside drainage

Fig. 1

2" (5 cm)min.

3" (7.5 cm)min.

Front View

2" (5 cm)min.

Fig. 2

INDOORUNIT

Tubing length (L)

OUTDOORUNIT

Elevationdifference (H)

Fig. 3a

WARNING To prevent abnormal heat genera-tion and the possibility of fire, donot place obstacles, enclosuresand grilles in front of or surround-ing the air conditioner in a waythat may block air flow.

Indoor unit

Floor level

Wall

Minimum height from floor level

5' (1.5 m)

Fig. 3b

For stable operation of theair conditioner, do notinstall wall-mounted typeindoor units less than 5'(1.5 m) from floor level.

CAUTION

Table 3

* If total tubing length becomes 100 to 165 ft. (Max.), charge additional refrigerant (R410A) by 0.43 oz./ft.No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.

Model

16510 to 100 0.43

Charge-less TubingLength (Actual Length)

(ft.)

Maximum TubingLength (L)

(ft.)

Maximum Elevation Difference (H)(ft.)

KHS3082KHS3682

Required Amount of Additional Refrigerant

(oz./ft.)*

If the outdoor unit is higher

If the outdoor unit is lower

100

50

09-191 CH3082-3682 2/16/10 1:17 PM Page 4

Page 5: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

● Concerning air-intake side distance “A” (Fig. 5a)The minimum for distance “A” is 6" if there are noobstructions on the air-discharge side (wall *1 side)and *2 or *4 is not present. In all other cases, the min-imum for distance “A” is 8".

● If wall *1 is on the air-discharge side (Fig. 5a), or ifobstructions are present on all 3 sides *2, *3, and *4(Fig. 5a), then the minimum distance for “B” and “C” is39-3/8". Even if there is no wall on the air-dischargeside, a minimum of 39-3/8" is required.

Fig. 5c

Air intake

Concreteor equal

About 6" (15 cm)

Min. 6" (15 cm)

Anchor bolts(4 pcs.)

About 1'4" (40 cm)

5

2-2. Outdoor Unit

AVOID:

● heat sources, exhaust fans, etc. (Fig. 4)● damp, humid or uneven locations.

DO:

● choose a place as cool as possible.● choose a place that is well ventilated.● install in a location where at least two sides are unob-

structed, so that the flow of air at the intake port orexhaust port is not blocked, and so that sufficientspace is ensured for maintenance to be carried outwithout trouble. In general the top also must be unob-structed. (Fig. 5a)

● provide a solid base (level concrete pad, concrete block,6" x 1'4" (15 x 40 cm) beams or equal), a minimum of 6"(15 cm) above ground level to reduce humidity and pro-tect the unit against possible water damage anddecreased service life. (Figs. 5b and 5c)

● install cushion rubber under unit’s feet to reducevibration and noise. (Fig. 5d)

● use lug bolts or equal to bolt down unit, reducingvibration and noise.

● install in a location where no antenna of a televisionor radio exists within 10' (3 m).

Outdoor unit

Hot airHeat source

Exhaust fanNO

Fig. 4

Air intake

Air dischargeMin.6" (15 cm)

Min.3'3" (100 cm)

Min. 10"(25 cm)

Ground

Obs

tacl

e

Obstacle above

Air

disc

harg

e

Min. 8" (20 cm)Air intake

*1

*2

*3

*4

A B C

Fig. 5d

Cushion rubber(Locally purchased)

Fig. 5a

Fig. 5b

Drain holes

CAUTION

CAUTION

A solid base must not coverthe hole of the bottom plate.

09-191 CH3082-3682 2/16/10 1:17 PM Page 5

Page 6: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

6

Fig. 5e

Fig. 5f

Fig. 5g

2-2-1. Installing the Unit in an Area with High Winds and in a Snowy Area

● In locations with high winds, a wind-proof duct should be fitted and direct exposure to the wind should be avoided as much as possible. (Fig. 5e)

● In regions with significant snowfall, the outdoor unit should be provided with a platform and snow-proof duct. (Fig. 5f)

■ Countermeasures against snow and wind

In regions with snow and strong wind, the following problems may occur when the outdoor unit is not provided with a platform and ducting:

a) The outdoor fan may not run and damage to the unit may occur.

b) There may be no air flow.

c) The tubing may freeze and burst.

d) The condenser pressure may drop because of strong wind, and the indoor unit may freeze.

2-2-2. Precautions for Installation in a Snowy Area

(1) The platform should be higher than the maximum snow depth. (Fig. 5g)

(2) The 2 anchoring feet of the outdoor unit should be used for the platform, and the platform should be installed beneath the air intake side of outdoor unit.

(3) The platform foundation must be firm and the unit must be secured with anchor bolts.

(4) In case of installation on a roof subject to strong wind, countermeasures must be taken to prevent the unit from being blown over.

Air discharge

Air discharge

Air discharge

Air�discharge

Outdoor unitDuct�

Platform (foundation)�

Air Intake�

Air Intake�

About 1/2 of th

e unit height�

Higher than th

e �

maximum sn

ow depth�

Without snow-proof ducting(Low platform)

Without snow-proof ducting(High platform)

09-191 CH3082-3682 2/16/10 1:17 PM Page 6

Page 7: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

7

11-13/16" 13-3/8"

25-3/16"

22-7

/8"

(6-2

1/32

")6-

5/16

"

21-25/32" (12-9/16")2-11/16"

35-1

3/16

"

37-1/32"

Air discharge

Air discharge

Air discharge

Hole for anchor bolt (4-R1/4") / Anchor bolt : 3/8" or M101

Air discharge

Air discharge

25-31/32"6-11/16"13

-3/8

"25

/32"

25/3

2"

14-3

1/32

"13

/32"

25/3

2"

Air Intake

Air discharge

Unit: inch

Air

Air Intake

1

(4-11/32")

discharge

Air discharge

2-2-3. Dimensions of Wind-proof Duct

Reference diagram for CH3082/3682

(9/1

6")

21-9

/16"

(1/4

")22

-1/4

"

23-7

/16"

(4-31/32") 4-31/32"

21-25/32"

11-13/16"

11-1

3/16

"

1-5/

16"

15/1

6"

18-1

5/16

"(1

-31/

32")

(1-3

1/32

")

(1-31/32")8-21/32"1-3/16"

22-7

/8"

Equivalent to the reverse side

Unit: inch

4- 1/4"hole

Reference diagram for wind-proof duct (locally purchased): STK-DGV160E

09-191 CH3082-3682 2/16/10 1:17 PM Page 7

Page 8: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

8

Required space around the outdoor unit

If the wind-proof duct is used, the space shown below must be secured around the outdoor unit.If the unit is used without the required space, a protective device may activate, preventing the unit from operating.

(1) Single-unit installation

CAUTION The top and both sides must remain open. If there are obstacles to the front and rear ofthe outdoor unit, the obstacle at either the front or rear must be no taller than the height ofthe outdoor unit.

(2) Multiple-unit installation

Installation in lateral rows

CAUTION The front and top must remain open.The obstacles must be no taller than the height of the outdoor unit.

CAUTION The front and both sides must remain open.

Installation in front-rear rows

Installation with intakes facing outletsInstallation with intakes facingintakes or outlets facing outlets

Min

. 39-

3/8"

or m

ore

Min

. 8"

or m

ore

8" nah t eroM

More than 9-27/32" More than 9-27/32"

More than 6"

Unit: inch

Unit: inch

More than 78-3/4"

More than 11-13/16"

More than 47-1/4"

Unit: inch

09-191 CH3082-3682 2/16/10 1:17 PM Page 8

Page 9: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

9

25-13/32"

3/32" 13-3/8" (11-15/16")

16-1

5/16

"

Air Intake

Air discharge

39-1/4"

27-7/32"

7-1/

32"

35-1

5/16

"

28-1

5/16

"

27-5/8" (11-5/8")

Air Intake

13/3

2"14

-31/

32"

25/3

2"

25/3

2"

25/3

2"13

-3/8

"4-11/32"

1(8-15/16") 25-31/32"

Air discharge

1

Unit: inch

Hole for anchor bolt (4-R1/4") / Anchor bolt: 3/8" or M10

2-2-4. Dimensions of Snow-proof Duct

Reference diagram for CH3082/3682

7

3

4

6

8

2

11

2

3

4

5

6

7

8

1

1

1

1

1

1

1

Unit: inch

Unit top, snow-proof duct

Unit right, snow-proof duct

Unit left, snow-proof duct

Unit front, snow-proof duct

Unit reverse side, snow-proof duct

Unit reverse side, snow-proof duct

Unit reverse side, reinforcement bracket for snow-proof duct

Unit left, reinforcement bracket for snow-proof duct

Fastened by screws at 14 locations

Fastened by screws at 3 locations

Fixing with

front panel2- 9/32"hole

2- 9/32"hole2- 9/32"hole

2- 9/32"hole

9/32"X13/32"hole

15-11/32"

Fastened by screws

(Same on the reverse side)

Fastened by screws at 2 locations

28-1

3/16

"16

-15/

16"

9-1/

8"

31/3

2"

2-7/32"24-3/16"28-3/16"

23 Fixing with rear panel

5/8"

6-1/

32"

28-3/16"

1-15/16"20-13/32"

5/16"

5-13

/32" 34

-23/

32"

11-7/8"

28-/

13/1

6"

16-1

5/16

"

9-1/

8"

4-1/32"Fixing with rear panel

Unit anchor holes

(Unit fixed bottom plate)

9-7/

32"

13-7

/8"

5-1/

8"

4-11/32"

1-9/

16"

5-7/8"

25/3

2"

4-27

/32"

20-7

/8"

3-27/32"

3-15/16"

4-23/32"

25-13/32"17-9/16"

Fastened by screws at 2 locations(Same on the reverse side)

Fixing with top panel

1/16" 27-9/16"

5

1

Reference diagram for snow-proof duct (locally purchased): STK-BDV80E

09-191 CH3082-3682 2/16/10 1:17 PM Page 9

Page 10: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

10

Reference diagram for snow-proof duct

Space requirements for settingCH3082/3682 with STK-BDV80E

Min. 39-3/8" or more

(1) Single-unit installation

(2) Multiple-unit installation (2 or more units)

[Obstacle to the front of unit]

Min. 6" or more

[Obstacle to the rear of unit]

(1) Single-unit installation

(3) Multiple-unit installation (2 or more units)

Note:In cases 2 and 3 the height of the obstacle must beno taller than the height of the outdoor unit.

(2) Obstacles on both sides

Top is open: Top is open:

Top is blocked by an obstacle:Top is blocked by an obstacle:

Min. 11-13/16"or more Min. 11-13/16"

or more

Min

. 6"

or m

ore

Min

. 11-

13/1

6"

or m

ore

Min. 11-13/16"or more

Min. 11-13/16"or more

Min. 11-13/16"or more

Min. 11-13/16"or more

Min

. 11-

13/1

6"or

mor

e

Min

. 19-

11/1

6"

or m

ore

Min. 9-27/32"or more

Min. 9-27/32"or more

Min

. 39-

3/8"

or m

ore

Min

. 39-

3/8"

or

mor

e

Min

. 39-

3/8"

or m

ore

09-191 CH3082-3682 2/16/10 1:17 PM Page 10

Page 11: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

11

Min. 39-3/8"or more

Min. 11-13/16"or more

Min. 11-13/16"or more

Min. 19-11/16"or more

Min. 59-1/16"or more

Min. 78-3/4"or more

(1) Single-unit installation

(2) ObInstallation is possible with the maximum 3 outdoor units.

stacles on both sides

[Installation in front-rear rows]

[Obstacles to the front and rear of unit]

• The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit.

The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit.

Unit: inch

. 3

9-3/

8"ni

Mero

m ro

"6 1/11- 91 .niM

erom ro

. 8

"ni

Mero

m r o

Min.11-13/16"or more

Min.11-13/16"or more

"8/3-93.niM

e rom ro

"61/31-11.niM

e rom ro

"61/11-91.niM

er om ro

09-191 CH3082-3682 2/16/10 1:17 PM Page 11

Page 12: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

Rear panel

Fig. 7c

Rear panel

Fig. 7b

12

Set screw only for transportation

Fig. 6

Rear panel

marks

Fig. 7a

Lefttubing

Righttubing

Right-reartubing(recommended)

Right-downwardtubing

Left-reartubing

Left-downwardtubing

Fig. 8

3. How to Install the Indoor Unit

3-1. Remove the Rear Panel from the Unit

(1) Remove and discard the set screw on the rear panel.(Fig. 6)

(2) Press the 2 ▲ marks on the frame cover and disengagethe stationary tabs from the frame. (Fig. 7a)

(3) Remove the rear panel by grasping the sections shownin Fig. 7b and pulling it in the direction shown by thearrow.

Tubing can be extended in 6 directions as shown in Fig. 8.Select the direction you need providing the shortest run tothe outside unit.

● When left tubing is to be done, switch the drain hose anddrain cap. (For details, refer to “Switching drain hose anddrain cap” on page 20.)

3-2. Make a Hole

(1) Place the rear panel from the indoor unit on the wall atthe location selected. Make sure the panel is horizontal,using a carpenter’s level or tape measure to measuredown from the ceiling. Wait until after cutting the holebefore attaching the rear panel to the wall.

(2) Determine which side of the unit you should make thehole for tubing and wiring. (Fig. 9)

In the case of left-rear tubing, use the measurement points6-7/32" (158 mm) from the marked position on the rearpanel for precise placement of the hose outlet. (Fig. 9)

(3) Before making the hole, check carefully that no studs orpipes are directly run behind the spot to be cut.

The above precautions are also applicable if tubinggoes through the wall in any other location.

NOTE

NOTE

6-7/32"(158 mm)

5-3/16"(132 mm)

Fig. 9

CAUTION Also avoid areas where elec-trical wiring or conduits arelocated.

09-191 CH3082-3682 2/16/10 1:17 PM Page 12

Page 13: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

13

Indoorside

Outdoorside

Hole should be made at a slight downward slant to theoutdoor side.

NOTE

Fig. 10

Plastic cover

INSIDE OUTSIDEWall

Slightangle

PVC pipe(Locally purchased)

Fig. 12

PVC pipe (Locally purchased)

Cut at slight angle

Fig. 11

(4) Using a sabre saw, key hole saw or hole-cutting drillattachment, cut a hole in the wall. See Table 4 andFig. 10.

Table 4

(5) Measure the thickness of the wall from the insideedge to the outside edge and cut PVC pipe at aslight angle 1/4" (6 mm) shorter than the thickness ofthe wall. (Fig. 11)

(6) Place the plastic cover over the end of the pipe (forindoor side only) and insert the pipe in the wall. (Fig.12)

3-3. Install the Rear Panel on the Wall

Be sure to confirm that the wall is strong enough to sus-pend the unit.

There are a number of screw holes on the rear panel.Using the 8 screw holes with mark is recommendedto attach the rear panel securely to the wall.

See either Item a) or b) below depending on the wall type.

a) If Wooden Wall

(1) Attach the rear panel to the wall with the 8 screwsprovided. (Fig. 13)

If you are not able to line up the holes in the rearpanel with the beam locations marked on the wall,use rawl plugs or toggle bolts to go through theholes on the panel or drill 3/16" (5 mm) dia. holes inthe panel over the stud locations and then mount therear panel.

(2) Double check with a carpenter’s level or tape mea-sure that the panel is level. This is important to install the unit properly. (Fig. 14)

(3) Make sure the panel is flush against the wall. Anyspace between the wall and unit will cause noiseand vibration.

b) If Block, Brick, Concrete or Similar Type Wall

Make 3/16" (4.8 mm) dia. holes in the wall. Insert rawlplugs for appropriate mounting screws. (Fig. 15)

Hole Dia.

3-5/32" (80 mm)

Fig. 13

Fig. 14

3/16"(4.8 mm) dia. hole

Rawl plug

Fig. 15

09-191 CH3082-3682 2/16/10 1:17 PM Page 13

Page 14: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

3-4. Removing and Installing the Grille

Basically, these models can be installed and wired with-out removing the grille. If access to any internal part isneeded, follow the steps as given below.

How to remove the grille(1) Open the front panel until it is nearly horizontal, grasp

the sections near the front panel arms on both sides,and then remove the panel by pushing the armstowards the outside while pulling the panel towardsyou.If the front panel is difficult to remove, grasp bothends of it and lift it up slightly. Move it to the left anddisengage the left arm, then move it to the right anddisengage the right arm. (Fig. 16)

(2) Lift the anti-mold filter up slightly to disengage it fromthe protrusions on the unit, and then pull downwardto remove the filter from the unit. (Fig. 16)

(3) Remove the 3 screws from the front of the unit andremove the screw covers on the bottom surface. Thenremove the 2 screws. (Fig. 17)

(4) Remove the screw on the right side cover plate andremove the cover. (Fig. 17a)

(5) Remove the lower flap by disengaging 4 pins of thelower flap in order. (Figs. 17b and 17c)(The flap is so flexible that it can be easily removed.)

(6) Lift up the grille in the direction shown by the arrowand pull the grille towards you to remove it. (Fig. 17d)

How to replace the grille(1) While aligning the top edge of the grille with the

frame, move the grille horizontally and insert the topand bottom into the frame.

(2) Press the grille firmly with your hand to ensure no gapexists between the frame and grille.

(3) Tighten the 6 screws. And fix the removed covers inplace.

(4) Grasp the sections near the front panel arms on bothsides, and hold the front panel so that it is nearly hori-zontal. Push the arm shafts towards the outside sothat they come into contact with the top of the inden-tations on the right and left sides of the air condition-er. Then push firmly until the arm shafts click intoplace. (Fig. 18)

(5) Remount the lower flap.(In remounting the flap, it cannot be turned end forend because the right and left pins of the flap differ inform. (Fig. 17c))

(6) Insert the top of the anti-mold filter, and then securethe bottom of the filter with the protrusions on the unit.

(7) When closing the front panel, push the central part ofthe front panel first and then press the bottom rightand left corners in place until you feel a click. (Fig. 19)

Check that no gap exists between the frame and thegrille.

NOTE

14

Grille

Screw cover

ScrewBottom surface

Screw (on the front)Screw (on the cover)

Screw (on the bottom)

Anti-mold filter

Front panel Arm

Protrusions

Fig. 16

Fig. 17a

Fig. 18

Front panel

Arm

Pin

Indentation

Fig. 19

Grille Upper flap

Lower flap

Fig. 17b

Lower flap

Pin

Fig. 17c

Fig. 17d

09-191 CH3082-3682 2/16/10 1:17 PM Page 14

Page 15: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

15

3-5. Shape the Indoor Side Tubing

(1) Arrangement of tubing by direction

a) Right or left tubing

Cut out the corner of the right/left frame with ahacksaw or the like. (Figs. 20 and 21)

b) Right-rear or left-rear tubing

In this case, the corner of the frame need not becut.

(2) To mount the indoor unit on the rear panel:

Hang the 3 mounting slots of the unit on theupper tabs of the rear panel. (Fig. 22)

3-6. Wiring Instructions

General precautions on wiring

(1) Before wiring, confirm the rated voltage of the unit asshown on its nameplate, then carry out the wiringclosely following the wiring diagram.

(2) Provide a power outlet to be used exclusively foreach unit, with a power supply disconnect and cir-cuit breaker for overcurrent protection provided inthe exclusive line.

(3) To prevent possible hazards due to insulation failure,the unit must be grounded.

(4) Each wiring connection must be done tightly and inaccordance with the wiring system diagram. Wrongwiring may cause the unit to misoperate or becomedamaged.

(5) Do not allow wiring to touch the refrigerant tubing,compressor, or any moving parts of the fan.

(6) Unauthorized changes in the internal wiring can bevery dangerous. The manufacturer will accept noresponsibility for any damage or misoperation thatoccurs as a result of such unauthorized changes.

Frame

Right tubingoutlet

Frame

Left tubingoutlet

Fig. 21

Fig. 22

Fig. 20

09-191 CH3082-3682 2/16/10 1:17 PM Page 15

Page 16: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

16

3-7. Wire Size and Length

Regulations on wiring diameter differ from locality to locality. For field wiring requirements, please refer to your local elec-trical codes. Carefully observe these regulations when carrying out the installation.

Refer to the wiring system diagram (Fig. 23) for the meaning of (A), (B), and (C) in Table 5.

Refer to your local codes or in the absence of local codes see the National Electric Code: ANSI/NFPA70.

NOTE

Fig. 23

WIRING SYSTEM DIAGRAM

● Be sure to comply with local codes on running the wirefrom the indoor unit to the outdoor unit (size of wire andwiring method, etc.).

● Each wire must be firmly connected.● No wire should be allowed to touch refrigerant tubing, the

compressor, or any moving part.

Disconnect switch

*

1

2

3

1

2

3

4

5Grounding line

INDOORUNIT

OUTDOOR UNIT

Field supply

Grounding line

L1

L2

Pow

er s

uppl

yS

ingl

e ph

ase

230/

208V

60H

z

Terminal Terminal

(A)

(B)

(C)

(B)

CAUTION

● Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram.The indoor unit draws its power from the outdoor unit.

● Do not run wiring for antenna, signal, or power lines of television, radio, stereo, telephone,security system, or intercom any closer than 3'4" (1 m) from the power cable and wiresbetween the indoor and outdoor units. Electrical noise may affect the operation.

● To avoid the risk of electric shock, each air conditionerunit must be grounded.

● For the installation of a grounding device, pleaseobserve local electrical codes.

● Grounding is necessary, especially for units usinginverter circuits, in order to release charged electricityand electrical noise caused by high tension.Otherwise, electrical shock may occur.

● Place a dedicated ground more than 7' (2 m) away fromother grounds and do not have it shared with other elec-tric appliances.

WARNING

Table 5

WARNING

*Disconnect switch may be required bynational or local codes.

Always comply with national and local coderequirements.

CAUTION

NOTE

Wire Size

Fuse or CircuitBreaker Capacity

LengthCH3082CH3682

It depends on wire specification and supply voltage level (*2)

35A for CH308245A for CH3682

AWG12 (min.) or bigger (*1) for CH3082AWG10 (min.) or bigger (*1) for CH3682

AWG14 or bigger

180 ft. (max.)

Disconnect switch(15A)

AWG14 or bigger

180 ft. (max.)

(AWG: American Wire Gauge)

Model (A) POWER SUPPLY WIRING (B) POWER LINE (C) CONTROL LINE

-

(*1) It depends on supply voltage level and wire specification. Consider temperature rating of wire, ambient temperature, and the number of wires inside the conduit.

(*2) Requirement of supply voltage level: AC187V to 253V (Measure voltage level at terminal plate inside the outdoor unit.)

09-191 CH3082-3682 2/16/10 1:17 PM Page 16

Page 17: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

17

3-8. Wiring Instructions for Inter-unit Connections

(1) Insert the inter-unit wiring (according to local codes)into the through-the-wall PVC pipe. Run the wiringtoward the indoor side allowing approx. 10" (25 cm)to extend from the wall face. (Fig. 24)

(2) Grasp both ends of the front panel, push the armstowards the outside, and remove the front panel byopening it towards the front and pulling it towardsyou. If the front panel is difficult to remove, graspboth ends of it and lift it up slightly. Move it to the leftand disengage the left arm, then move it to the rightand disengage the right arm.

(3) Remove the screw on the right side cover plate andopen the cover. (Fig. 25)

(4) Route the inter-unit wiring from the back of theindoor unit and pull it toward the front for connec-tion. (Fig. 26a, 26b)

(5) Connect the inter-unit wiring to the correspondingterminals on the terminal plate (Fig. 26a, 26b) whilereferring to the wiring diagram.

(6) Be sure to secure the wiring with the providedclamp.

When closing the front panel, push the central part ofthe front panel first and then press the bottom right andleft corners in place until you feel a click. (Fig. 27)

Please refer to “How to replace the grille” on page 14 forinstalling the air intake grille.

NOTE

Rearpanel

Wiring

Wall

10"(25 cm)

Plasticcover

Fig. 24

Cover

Fig. 25

Terminal plate

Fig. 26a

Earth plate Lock nut

Inter-unitwiring

Top of conduitconnector

Fig. 26b

Fig. 27

09-191 CH3082-3682 2/16/10 1:17 PM Page 17

Page 18: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

18

When connecting each power wire to the correspondingterminal, follow the instructions “How to connect wiringto the terminal” and fasten the wire securely tight withthe fixing screw of the terminal plate.

How to connect wiring to the terminal

a) For Indoor Unit

(1) Cut the wire end with a cutting pliers, then strip theinsulation to expose the wire about 9/32" (7 mm).See the label (Fig. 28) near the terminal plate.

(2) Using a screwdriver, loosen the terminal screw onthe terminal plate.

(3) Insert the wire and tighten the terminal screw com-pletely using a screwdriver.

b) For Outdoor Unit

■ For solid core wiring (or F-cable)

(1) Cut the wire end with a cutting pliers, then strip theinsulation to expose the solid wire about 15/16" (25mm). (Fig. 29)

(2) Using a screwdriver, remove the terminal screw(s)on the terminal plate.

(3) Using the pliers, bend the solid wire to form a loopsuitable for the terminal screw.

(4) Shape the loop wire properly, place it on the termi-nal plate and fix it securely with the removed termi-nal screw using a screwdriver.

■ For stranded wiring

(1) Cut the wire end with a cutting pliers, then strip theinsulation to expose the stranded wiring about 3/8"(10 mm) and tightly twist the wire ends. (Figs. 30and 31)

(2) Using a screwdriver, remove the terminal screw(s)on the terminal plate.

(3) Using a ring connector fastener or pliers, securelyclamp each stripped wire end with a ring connector.(Fig. 30)

(4) Place the ring connector wire, and replace andtighten the removed terminal screw using a screw-driver. (Fig. 32)

Solid wireLoop

Insulation

Str

ip 1

5/16

" (2

5 m

m)

Fig. 29

STRIPSIZE

9/32"(7 mm) (ACTUAL

SIZE)

Fig. 28

Stranded wire

Ringconnector

Str

ip 3

/8"

(10

mm

)

Fig. 30

Screw

Ring connector

Terminal plateWire

Specialwasher

Fig. 32

Screw and special washer

Ringconnector

Wire

WARNING Loose wiring may cause theterminal to overheat or resultin unit malfunction. A firehazard may also exist.There-fore, be sure all wiring istightly connected.

Twist wire ends

Fig. 31

09-191 CH3082-3682 2/16/10 1:17 PM Page 18

Page 19: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

19

3-9. Mounting

(1) To install the indoor unit, mount the indoor unit ontothe 3 tabs on the upper part of the rear plate.

(2) Hold down the air discharge outlet and press thelower part of the indoor unit until it clicks to securelyfasten to the 2 tabs on the lower part of the rearplate. (Fig. 33)

For tubing, choose either the right or left tubing directionand follow the steps below. Also, extend the support onthe back of the indoor unit as a stand to make your workeasier. (Fig. 34)

■ Right-side tubing

(1) Shape the refrigerant tubing so that it can easily gointo the wall hole. (Fig. 35)

(2) Push the wiring, refrigerant tubing, and drain hosethrough the hole in the wall. Adjust the indoor unit soit is securely seated on the rear panel. (Fig. 36)

(3) Carefully bend the tubing (if necessary) to run alongthe wall in the direction of the outdoor unit and thentape as far as the fittings. (See Caution on page 24.)The drain hose should come straight down the wallto a point where water runoff won’t stain the wall.

(4) Connect the refrigerant tubing to the outdoor unit.(After performing a leak test on the connecting part,insulate it with the tubing insulation. (Fig. 37a)) Also,refer to Section 5-4. Connecting Tubing betweenIndoor and Outdoor Units.

(5) Assemble the refrigerant tubing, drain hose, andconduit (including inter-unit wiring) as shown inFig. 37b.

NOTE

Cover

Refrigeranttubing

Rear panel

Drain hose

Inter-unitwiring

Fig. 35

Fig. 36

Fig. 33

Push

Fig. 34

Fig. 37a

Fig. 37b

Refrigerant tubing

Drain hose Conduit

Inter-unit wiring

Flareinsulation

Rear panel

09-191 CH3082-3682 2/16/10 1:17 PM Page 19

Page 20: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

20

Hole in wall

Bent part Narrow tube Wide tube

Rear panel

Fig. 38

Drain cap

Drain hose

Clamp

Fig. 39

■ Left-side tubing

(1) Lead the tubing and drain hose through the wall,allowing sufficient length for connection. Then bendthe tubing using a tube bender to make the attach-ment. (Fig. 38)

(2) Switch the drain hose and drain cap.

Switching drain hose and drain cap

(a) Locate the drain hose and the drain cap.(Fig. 39)

(b) Remove the screw fastening the drain hose onthe right side, and pull out the drain hose toremove it. (Fig. 39)

(c) Apply moderate force to pull off the drain capon the left side. (If you cannot pull it off by hand,use a long-nose pliers.)

(d) Reattach the drain hose to the left side and thedrain cap to the right side. (Fig. 40a)

Drain hoseSlide the drain hose fully onto the drain pan outlet.(It will be easy to slide when water is added.) Checkthat the screw holes in the drain bracket and thedrain pan outlet are aligned and securely in contact,then fasten them with the screw. (After attaching thedrain hose, check that it is attached securely.) (Fig. 40b)

Drain capUse a Phillips screwdriver to push the drain cap infirmly. (If it is difficult to push in, wet the cap withwater first.)

(3) Install the indoor unit on the rear panel.

(4) Connect the tubing and wiring led inside from out-doors.

(5) After completing a leak test, bundle the tubingtogether with armoring tape and store it inside thetubing storage area at the back of the indoor unitand hold it with clamps. (Figs. 40a and 41)

Fig. 40a

Fig. 40b

Fig. 41

Refrigerant tubing

Inter-unit wiring

Conduit

Drain bracket

Drain pan outlet

Drain hose

Drain bracket

Drain hose

Screw

Screw

Screw hole

Drain hose

Drain cap

Clamp

09-191 CH3082-3682 2/16/10 1:17 PM Page 20

Page 21: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

21

To unmount indoor unit

Press the 2 ▲ marks on the lower part of the indoor unitand unlatch the tabs. Then lift the indoor unit andunmount. (Fig. 42)

3-10. Frame Fastening Method

(1) Remove the screw cover on the bottom surface.(Fig. 43)

(2) Fasten the frame to the rear panel using the 2 sup-plied tapping screws 5/32" x 13/32" (4 x 10 mm).(Fig. 43)

Under normal conditions, the installation design calls fora less than 3/32" (2 mm) gap between the air conditionerunit and the wall.Confirm that the gap is appropriate (less than 2 mm).

3-11. Drain Hose

a) The drain hose should be slanted downward to theoutdoors. (Fig. 44)

b) Never form a trap in the course of the hose.

c) If the drain hose will run in the room, insulate thehose with insulation* so that chilled condensationwill not damage furniture or floors. (Fig. 45)

* Foamed polyethylene or its equivalent is recom-mended.

NOTE

WARNING

Risk of Electric Shock

Do not supply power to theunit or operate it until alltubing and wiring to the out-side unit are completed.

Condensation

Insulation material(Locally purchased)must be used.

Fig. 45

Screw cover

Screw

Fig. 43

Push

Fig. 42

Slant

Drainhose

Indoorunit

Fig. 44

09-191 CH3082-3682 2/16/10 1:17 PM Page 21

Page 22: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

22

4. How to Install the Outdoor Unit

First refer to Section 2. Installation Site Selection.

4-1. Wiring Instructions for the Outdoor Unit

Regulations on wire size differ from locality to locality. Forfield wiring requirements, please refer to your local elec-trical codes. Make sure that the installation fully complieswith all local and national regulations.

(1) Remove the 3 screws from the inspection panel.(Fig. 46a)Remove the inspection panel by sliding it downwardand pulling it toward you. (Fig. 46b)

(2) Connect the inter-unit and power supply line accord-ing to the wiring system diagram on the inspectionpanel. (Fig. 46c)

(3) When connections are completed, check that allconnections are correct as shown in the wiring sys-tem diagram.

(4) Be sure to ground the unit according to your localcodes.

4-2. Routing the Tubing and Wiring

● The tubing and wiring can be extended out in 3 direc-tions: front, rear, and right. Use a nipper or similartool to cut out the knockout holes for the inter-unitcontrol wiring outlet, power wiring outlet, and tubingoutlet from the appropriate covers A and B. (Fig. 46d)

● Route the tubing so that it does not contact thecompressor, panel, or other parts inside the unit.Increased noise will result if the tubing contactsthese parts.

● When routing the tubing, use a tube bender tobend the tubes.

CAUTION

Terminal plate

Cabinet

Screw

Inspection panel

Fig.46a Fig.46b

Fig.46c

Tubing outletFront Right

Rear

Cover B

Cover A

Inter-unitpower line

Power supply line(conduit)

Wiring outlet

Wiring outlet

(conduit)

Fig.46d

09-191 CH3082-3682 2/16/10 1:17 PM Page 22

Page 23: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

23

5. Refrigerant Tubing

5-1. Use of the Flaring Method

Many of the conventional split system air conditionersemploy the flaring method to connect refrigerant tubeswhich run between indoor and outdoor units. In thismethod, the copper tubes are flared at each end andconnected with flare nuts.

5-2. Flaring Procedure with a Flare Tool

(1) Cut the copper tube to the required length with atube cutter. It is recommended to cut approx. 12" to20" (30 to 50 cm) longer than the tubing length youestimate.

(2) Remove burrs at the end of the copper tube with atube reamer or file. This process is important andshould be done carefully to make a good flare.(Fig. 47)

When reaming, hold the tube end downward and besure that no copper scraps fall into the tube. (Fig. 48)

(3) Remove the flare nut from the unit and be sure tomount it on the copper tube.

(4) Make a flare at the end of copper tube with a flaretool.* (Figs. 49a and 49b)

(*Use “RIDGID” or equivalent.)

A good flare should have the following characteristics:

● inside surface is glossy and smooth.

● edge is smooth.

● tapered sides are of uniform length.

5-3. Caution before Connecting Tubes Tightly

a) Be sure to apply a sealing cap or water-proof tapeto prevent dust or water from getting into the tubesbefore they are used.

b) Be sure to apply refrigerant lubricant to the match-ing surfaces of the flare and union before connect-ing them together. This is effective for reducing gasleaks. (Fig. 50)

c) For proper connection, align the union tube andflare tube straight with each other, then screw in theflare nut lightly at first to obtain a smooth match.(Fig. 51)

NOTE

NOTE

Deburring

Before After

Fig. 47

Reamer

Coppertubing

Fig. 48

Flare tool

Flare nut

Copper tubing

Fig. 49b

Fig. 49a

Apply refrigerant lubricant here and here

Fig. 50

Flare nutUnion

Fig. 51

0 to 0.0196"(0 to 0.5 mm)

If the special R410A flare tool is used:

0.0472" (1.2 mm)

If the previous flare tool (clutch-type) is used:

Adjust so that the amount of tube protrusion is as shown in the figure.

09-191 CH3082-3682 2/16/10 1:17 PM Page 23

Page 24: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

24

5-4. Connecting Tubing between Indoor and Outdoor Units

a) Tightly connect the indoor side refrigerant tubing exten-ded from the wall with the outdoor side tubing. (Fig. 52)

b) To fasten the flare nuts, apply specified torque as:

Table 6

5-5. Insulation of Refrigerant Tubing

To prevent heat loss and wet floors due to dripping of con-densation, both tubes must be well insulated with aproper insulation material. (Fig. 53) The thickness of the insulation should be a minimum 5/16"(8 mm). (Fig. 54)

5-6. Taping the Tubes

(1) At this time, the 2 refrigerant tubes (and electrical wireif local codes permit) should be taped together witharmoring tape. The drain hose may also be includedand taped together as 1 bundle with the tubing.

(2) Wrap the armoring tape from the bottom of the outdoorunit to the top of the tubing where it enters the wall. Asyou wrap the tubing, overlap half of each previous tapeturn. (Fig. 55)

(3) Clamp the tubing bundle to wall, using 1 clamp approx.every 47" (120 cm).

Do not wind the armoring tape too tightly, since this willdecrease the heat insulation effect. Also, be sure the con-densation drain hose splits away from the bundle and dripsclear of the unit and the tubing.

5-7. Finishing the Installation

After finishing insulating and taping over the tubing, usesealing putty to seal off the hole in the wall to prevent rainand draft from entering. (Fig. 56)

NOTE

IMPORTANT

Indoor unit

Outdoor unit

Spanner

Torque wrench

Fig. 52

Insulation

Min. 5/16"(8 mm)

Thickness:min. 5/16"(8 mm)

Fig. 54

Fig. 55

Clamp

Insulated tubes

Apply putty here

Tubing

Fig. 56

CAUTION After a tube has been insulat-ed, never try to bend it into anarrow curve, as this maycause the tube to break orcrack.

Flareinsulation

Fig. 53

Tube Dia. Nut Tightening Torque

1/4" (6.35 mm) 21/32" (17 mm) Approx. 120 – 160 lbs·in (140 – 180 kgf·cm)

3/8" (9.52 mm) 7/8" (22 mm) Approx. 300 – 360 lbs·in (340 – 420 kgf·cm)

1/2" (12.70 mm) 1-1/32" (26 mm) Approx. 430 – 540 lbs·in (490 – 610 kgf·cm)

5/8" (15.88 mm) 1-5/32" (29 mm) Approx. 590 – 710 lbs·in (680 – 820 kgf·cm)

09-191 CH3082-3682 2/16/10 1:17 PM Page 24

Page 25: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

25

6. Air Purging

Air and moisture remaining in the refrigerant systemhave undesirable effects as indicated below. Therefore,they must be purged completely.

● pressure in the system rises

● operating current rises

● cooling (or heating) efficiency drops

● moisture in the air may freeze and block capillary tubing

● water may lead to corrosion of parts in the refrigerantsystem

■ Air Purging with a Vacuum Pump (for Test Run)

(1) Check that each tube (both narrow and wide tubes)between the indoor and outdoor units have beenproperly connected and all wiring for the test runhas been completed. Note that both narrow andwide tube service valves on the outdoor unit arekept closed at this stage.

(2) Using an adjustable wrench or box wrench, removethe valve caps from the service valve on both nar-row and wide tubes.

(3) Connect a vacuum pump and a manifold valve (withpressure gauges) to the service port on the widetube service valve. (Fig. 57)

(4) With the “Lo” knob of the manifold valve open, runthe vacuum pump. The operation time for the vacu-um pump varies with tubing length and the capacityof the pump. The following table shows the amountof time for evacuation:

Table 7

HiLo

Indoor unit

Outdoor unit

Manifold valve(Exclusively for R410A)

Pressuregauge

Vacuum pump

Charging hose(Exclusively for R410A)

Vacuum pump adapter(Exclusively for R410A)(with reverse flow prevention)

Fig. 57CAUTION Be sure to use a manifold valvefor air purging. If it is not avail-able, use a stop valve (field sup-ply) for this purpose.The “Hi”knob of the manifold valve mustalways be kept closed.

The required time in Table 7 is calculated based on theassumption that the ideal (or target) vacuum conditionis around 10 mmHg abs.

NOTERequired time for evacuation when

100 liter/h vacuum pump is used

If tubing length is If tubing length isless than 33 ft. (10 m) more than 33 ft. (10 m)

10 min. or more 15 min. or more

CAUTION The service port on the wide tubeservice valve uses a Schrader corevalve to access the refrigerant sys-tem.The valve core is similar tothose used in automobile tires.Therefore, be sure to use a vacuumhose connector which has a push-pin inside.

To prevent other refrigerants from being mistakenlycharged to units which use R410A, the size of thecharge port on the service valve is different from theone for other refrigerant types. For servicing such asrecharging, the specified charging hose, manifold andvacuum pump adapter (with reverse flow prevention)for R410A must be used.

NOTE

09-191 CH3082-3682 2/16/10 1:17 PM Page 25

Page 26: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

26

(5) With the vacuum pump still running, close the “Lo”knob of the manifold valve. Then stop the vacuumpump.

(6) With the hex wrench, turn the valve stem on the nar-row tube service valve counter-clockwise by 90degrees (1/4 turn) for 10 seconds, and then turn thestem clockwise to close it again. (Fig. 58)

(7) Leak test all joints at the tubing (both indoor and out-doors) with soapy water. Bubbles indicate a leak.Tight-en the joint more when leaks, then check if there is noleak. Be sure to wipe off the soap with a clean cloth.

(8) With the hex wrench, turn the wide tube servicevalve stem counter-clockwise to fully open the valve.

(9) Turn the narrow tube service valve stem counter-clockwise to fully open the valve.

(10) Loosen the vacuum hose connected to the widetube service port slightly to release the pressure.Then, remove the hose.

(11) Fasten the valve cap on the wide tube service portsecurely with an adjustable wrench or box wrench.Next, mount the valve cap on the service valve andtighten it to 170 lbs·in (200 kgf·cm) with a torquewrench. This process is very important to preventgas from leaking from the system.

(12) Test run the air conditioner. (See next page.)

(13) While the air conditioner is running, apply liquidsoap to check for any gas leaks around the servicevalves or caps.

(14) If there is no leakage, stop the air conditioner.

(15) Wipe off the soap on the tubing.

This completes air purging with a vacuum pump and theair conditioner is ready for actual operation.

CAUTION Be sure to completely insertthe hex wrench beforeattempting to turn the valve.

Fig. 58

CAUTION This may cause the refriger-ant gas to leak. In order toavoid this, take off the hosequickly.

Valve cap

Narrow tube

Hex wrench

Wide tube

Vacuum hose to manifold valve90 (1/4 turn)

09-191 CH3082-3682 2/16/10 1:17 PM Page 26

Page 27: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

27

How to Test Run the Air Conditioner

After turning on the power of the air conditioner, use theremote controller and follow the steps below to conduct thetest run.

(1) Set the remote controller in Test Run mode.(Fig. 59a)

a) Press and hold the QUIET button and the 1HR.TIMER button.

b) Then press and hold the ACL (Reset) button with apointed object such as the tip of a pen. After 5 sec-onds, release the ACL button first.

c) Then release the QUIET and 1HR. TIMER buttons.

d) appears and “oP-1” blinks in the remote controllerclock display area. (Fig. 59b)

(2) Start Cooling mode test run by pressing the ON/OFFoperation button of the remote controller. (Fig. 59a)

• This starts the fan producing uncooled forced air withthe 3 indicator lamps (OPERATION lamp, TIMERlamp, and LED CLEAN lamp) on the main unit blinking. (Fig. 59c)

• After 3 minutes, the system shifts into cooling opera-tion, and cool air will start to be felt. Cooling mode testrun is unaffected by the room temperature.

(3) Press the ON/OFF operation button of the remote con-troller again to stop the test run. (Fig. 59a)

(4) Finally press the ACL (Reset) button of the remote con-troller to release it from Test Run mode to return to nor-mal mode. (Fig. 59a)

• “ ” and “oP-1” will disappear from the remote con-troller clock display area.

Troubleshooting:In the event that the green OPERATION lamp is blinkingupon powering up the system, an error condition exists. Inthis case, refer to the self-diagnostics procedure on theinside of the front cover.

After the test run is completed, be sure to press the ACL(Reset) button to return to normal mode. The air conditionerwill not operate correctly if this is not done.

IMPORTANT

NOTE

Fig. 59a

Fig. 59b

Fig. 59c

1HR.TIMER

ON/OFF operation

ACL(Reset)

QUIETbutton

button

button

button

TIMER lamp

OPERATION lamp

LED CLEAN lamp

09-191 CH3082-3682 2/16/10 1:17 PM Page 27

Page 28: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

28

■ Pump DownPump down means collecting all refrigerant gas in thesystem back into the outdoor unit without losing any ofthe gas. Pump down is used when the unit is to bemoved or before servicing the refrigerant circuit.

Pump Down Procedure

Be sure to carry out pump down with the unit incooling mode.

(1) Connect the Lo side charging hose of the manifoldvalve to the service port on the wide tube servicevalve.

(2) Using a hex wrench, turn the narrow tube servicevalve clockwise all the way to close the servicevalve. (Be sure to confirm that the wide tube servicevalve is fully open.)

(3) Press the operation button and start cooling oper-ation.

(4) When the low pressure gauge reading falls to 14.2 to7.1 psi (1 to 0.5 kg/cm2), fully close the wide tubevalve stem. Then quickly stop the unit.

(5) Disconnect all gauges and hoses, and replace thevalve caps as they were before.

■ Basic Functions of the Service Valves

The basic functions of the service valves are given in Table 8 below.

ActionNarrow Tube Service

Valve (2-Way)Wide Tube Service

Valve (3-Way)

CLOSED

Fully OPEN

Fully OPEN

Shipping

Operating and

test running

the air conditioner

Measuring pressure

and gas charging

Air purging with

a vacuum pump

CLOSED

Valve capStem

O-ring

*

*

Table 8

* The service port on the wide tube ser-vice valve uses a Schrader core valveto access the refrigerant system.Therefore, be sure to use a hose con-nector which has a push-pin inside.(Fig. 60a)

PUSH

Hose with push-pin

Service valve

Fig. 60a

Close

Hexwrench

Open

Fig. 60b

CAUTION

When opening or clos-ing the service valvestem, use the hexwrench. Be sure to fullyseat the wrench beforeturning the valve.

External diameter of service portR410A: 5/16"

NOTE

09-191 CH3082-3682 2/16/10 1:17 PM Page 28

Page 29: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

a) Temporary connection:Screw in 3 – 5 turns by hand. (Fig. 60c)

b) To fasten the flare nuts, apply specified torqueas Table 9 and Fig. 60d.

Fig. 60c Fig. 60d

CAUTION

Torque wrench

Be sure to tighten the flare nut using the prescribed torque. If the nut is over-tightened, refrigerant leakage may occur.

Press

Set in place

Remote controlunit mount

Mounting screws

Rear side

Hole

To prevent loss of the remote controlunit, you can connect the remote control unit to the mount by passinga string through the remote controlunit and attachment hole.

5/32 5/8" (4 16 mm)(included)

29

7. Remote Control Unit Installation Position

The remote control unit can be operated from either anon-fixed position or a wall-mounted position.

To ensure that the air conditioner operates correctly, donot install the remote control unit in the following places:

● In direct sunlight

● Behind a curtain or other place where it is covered

● More than 26' (8 m) away from the air conditioner

● In the path of the air conditioner’s airstream

● Where it may become extremely hot or cold

● Where it may be subject to electrical or magneticinterference

● Where there is an obstacle between the remote con-trol unit and the air conditioner (since a check signalis sent from the remote control unit every 5 minutes)

7-1. Mounting on a WallBefore mounting the remote control unit, press theON/OFF operation button at the mounting location tomake sure that the air conditioner operates from thatlocation. The indoor unit should make a beeping soundto indicate that it has received the signal.

Table 9

Fig. 61

To take out the remote control unit, pull it forward.

■ Service Valve Connections

Tube Dia. Nut Tightening Torque

1/4" (6.35 mm) 21/32" (17 mm) Approx. 120 – 160 lbs·in (140 – 180 kgf·cm)

3/8" (9.52 mm) 7/8" (22 mm) Approx. 300 – 360 lbs·in (340 – 420 kgf·cm)

1/2" (12.70 mm) 1-1/32" (26 mm) Approx. 430 – 540 lbs·in (490 – 610 kgf·cm)

5/8" (15.88 mm) 1-5/32" (29 mm) Approx. 590 – 710 lbs·in (680 – 820 kgf·cm)

09-191 CH3082-3682 2/16/10 1:17 PM Page 29

Page 30: INSTALLATION INSTRUCTIONSs3.supplyhouse.com/manuals/1311268215267/58239_PROD_FILE.pdf · 3 1. General This booklet briefly outlines where and how to install the air conditioning system

30

8. Address Switch

8-1. Address Setting of the Remote Control Unit

The address can be set in order to prevent interferencebetween remote controllers when 2 indoor units areinstalled near each other. The address is normally set to“A.” To set a different address, it is necessary to changethe address on the second remote controller.

Once changed, you cannot restore the original addresssetting of the air conditioner.

(1) Switch on the power source.

(2) Break the address-setting tab marked “A” on thesecond remote controller to change the address(Fig. 62). When the tab is removed, the address isautomatically set to B (Fig. 63).

(3) Press and hold the remote controller QUIET buttonand 1HR. TIMER button. Then press and hold theACL (Reset) button with a pointed object such asthe tip of a pen. After 5 seconds, release the ACLbutton first, then release the QUIET and 1HR.TIMER buttons. “oP-1” (Test Run) appears, blinkingin the remote controller clock display area.

(4) Each time the 1HR. TIMER button is pressed, thedisplay changes as shown below. Press this button3 times to change the display to “oP-7” (Address setting). (Fig. 64)

(5) “oP-7” has now been selected for address setting.

(6) Press the ON/OFF operation button on the remotecontroller. (Fig. 64) Check that the “beep”signal-received sound is heard from the second indoor unit(approximately 5 times). The sound you hear is thesignal that the remote controller address has beenchanged.

(7) Finally press the remote controller ACL (Reset) but-ton to cancel the blinking “oP-7” display.(Fig. 64)

Changing of the second remote controller address isnow completed.

Test run mode

Selfdiagnostic mode

Address setting mode

NOTE Fig. 62

Fig. 63

Fig. 64

Tab

ACL button

1HR.TIMERbutton

ON/OFF operationbutton

ACL(Reset)button

QUIETbutton