Inspection Snapshot Inspection ID: 625121 Inspection Time: 08:21 AM - 03:05 PM Inspection Start Date: 10/15/2018 Inspection End Date: 10/18/2018 Property ID: NY005021400 Property Type: Public Housing Property Name: INDEPENDENCE Inspection State: Successful Score: 71c Inspection Summary Report (POA) for Inspection #625121 Report generation date/time: 10/18/2018 06:30 PM Score Version: 1 Page: 1 of 43 Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Inspection Snapshot

Inspection ID: 625121 Inspection Time: 08:21 AM - 03:05 PM

Inspection StartDate: 10/15/2018

Inspection EndDate: 10/18/2018

Property ID: NY005021400 Property Type: Public Housing

Property Name: INDEPENDENCE

Inspection State: Successful Score: 71c

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 1 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 2: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Property Profile

Property Name: INDEPENDENCEScattered Site? No Multiple Site? No

Address Line 1: 85 TAYLOR AVENUE

Address Line 2:City: BROOKLYN State: NY

ZIP: 11211 Extension: ____

Phone: (718) 782-9505 Extension:Fax: (718) 388-9419 Email: [email protected]

Type

Building Units

Expected Actual Sampled Expected Actual Sampled

Residential 6 6 6 609 609 26

Common 0 - - -

Total 6 6 6 609 609 26

Occupancy InformationNo. of Occupied Units Occupancy Rate Inspect Vacant Units

608 100% No

Comments

Flat roof in bldg 2, 5 and 6 No access for brick pointing 2767763 All others flat roofinspected No bed bugs reported Boiler room is offline due to repairs. Temporary rentalboilers are in trailers units 3-8D 6-14C 3-21E and 6-19B temp offline for fire

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 2 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 3: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Participant Profile

Management Agent [Primary Contact / Not Present During Inspection]Name (F, MI, L): Sybille LouisOrganization: NYCHAAddress Line 1: 250 BroadwayAddress Line 2:City: New York State: NY

ZIP: 10007 Extension:Phone: (212) 306-6059 Extension:Fax: (718) 624-7245 Email: [email protected]

Executive Director [Not Present During Inspection]Name (F, MI, L): Vito MustaciuoloOrganization: NYCHAAddress Line 1: 250 BroadwayAddress Line 2:City: New York State: NY

ZIP: 10007 Extension:Phone: (212) 306-3416 Extension:Fax: (212) 306-8888 Email: [email protected]

Site Manager [Present During Inspection]Name (F, MI, L): Alicia MaynardOrganization: NYCHAAddress Line 1: 85 Taylor AvenueAddress Line 2:City: Brooklyn State: NY

ZIP: 11211 Extension:Phone: (718) 782-9505 Extension:Fax: (718) 388-9419 Email: [email protected]

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 3 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 4: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Score Summary

AreaPossiblePoints

Deductions(ExcludingH&S)

Pre H&SPoints

H&SDeductions

Final Points

Site 16.56 0.00 16.56 4.70 11.86Building Exterior 16.73 2.20 14.53 0.00 14.53Building Systems 22.30 0.00 22.30 0.00 22.30Common Area 8.92 4.30 4.62 1.72 2.89Unit 35.49 3.92 31.57 12.15 19.41Total 100.00 10.42 89.58 18.58 70.99

Score Version: 1 Score Date: 10/18/2018 Final Score: 71c

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 4 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 5: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Health & Safety Summary

Site Buildings Units Total

Non-Life Threatening (NLT)

Actual 1 1 37 39

Projected 1 1 867 869

Life Threatening (LT)

Actual 0 6 3 9

Projected 0 6 70 76

Smoke Detectors (SD)

Actual 0 0 0 0

Projected 0 0 0 0

Overall

Actual 1 7 40 48

Projected 1 7 937 945

Health and Safety Narrative1 site, 6 buildings and 26 units were inspected.

48 health and safety deficiencies(HSD) wereobserved.

Percentage Inspected:Site (PIS): 100%Building (PIB): 100%Unit (PIU): 4%

Projected HSD:Site = (Actual HSDS) / PISBuilding = (Actual HSDB) / PIBUnit = (Actual HSDU) / PIU

If all buildings and units were inspected, it isprojected that a total of 945 health and safetydeficiencies would apply to the property.

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 5 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 6: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Systemic Deficiencies

Type Area Item DeficiencyB/U withdefects

TotalB/U %

Ordinary Site Hazards HS - Tripping (Hazards) 1 1 100

Ordinary CA Emergency/Fire Exits HS - Emergency/Fire Exits Blocked/Unusable (Emergency/Fire Exits)

2 6 33

Ordinary CA Doors CA - Damaged Hardware/Locks(Doors)

2 6 33

Ordinary CA Floors CA - Peeling/Needs Paint (Floors) 2 6 33

Ordinary CA Graffiti CA - Graffiti 4 6 67

Ordinary CA Ceiling CA - Peeling/Needs Paint (Ceiling) 2 6 33

Ordinary CA Floors CA - Peeling/Needs Paint (Floors) 4 6 67

Ordinary CA Walls CA - Peeling/Needs Paint (Walls) 5 6 83

Ordinary Unit Walls Unit - Peeling/Needs Paint (Walls) 16 26 62

Ordinary Unit Windows Unit - Inoperable/Not Lockable(Windows)

18 26 69

Note:B/U - Indicates Buildings or Units

BE - Indicates Building Exterior

BS - Indicates Building Systems

CA - Indicates Common Areas

Capital items are repairs that generally require large cash outlays. (Items such as new roofs and new appliances)

Ordinary items are repairs that require smaller cash outlays. (Items such as light fixtures, fire extinguishers and smoke detectors)

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 6 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 7: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Building/Unit Summary

Entity Expected Actual # Inspected # Reported Uninspectable

Building 6 6 6 0

Unit 609 609 26 2

Building 140001 - 1 [ Sample , Inspected ]

Address Line 1: 85 TAYLOR STREET

Address Line 2:City: BROOKLYN State: NY

Zip: 11211 Extension: ____

Type Constructed In Floors Expected Unit CountActual Unit

Count

Elevator Structure 1965 21 98 98

Comments:

Unit # # Bedrooms Occupied?UnInspectedReason?

1-6F 2 Bedrooms Yes

1-10E 1 Bedroom Yes

1-14F 2 Bedrooms Yes

1-18E 1 Bedroom Yes

Building 140002 - 2 [ Sample , Inspected ]

Address Line 1: 130 CLYMER STREET

Address Line 2:City: BROOKLYN State: NY

Zip: 11211 Extension: ____

Type Constructed In Floors Expected Unit CountActual Unit

Count

Elevator Structure 1965 21 107 107

Comments:

Unit # # Bedrooms Occupied?UnInspectedReason?

2-5D 4 Bedrooms Yes No Access

2-10E 1 Bedroom Yes

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 7 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 8: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

2-14D 3 Bedrooms Yes

2-15A 2 Bedrooms Yes

2-19B 1 Bedroom Yes No Access

2-21E 1 Bedroom Yes

Building 140003 - 3 [ Sample , Inspected ]

Address Line 1: 125 TAYLOR STREET

Address Line 2:City: BROOKLYN State: NY

Zip: 11211 Extension: ____

Type Constructed In Floors Expected Unit CountActual Unit

Count

Elevator Structure 1965 21 106 106

Comments:

Unit # # Bedrooms Occupied?UnInspectedReason?

3-3A 2 Bedrooms Yes

3-7F 2 Bedrooms Yes

3-11F 2 Bedrooms Yes

3-15E 1 Bedroom Yes

3-19D 3 Bedrooms Yes

Building 140004 - 4 [ Sample , Inspected ]

Address Line 1: 121 WILSON STREET

Address Line 2:City: BROOKLYN State: NY

Zip: 11211 Extension: ____

Type Constructed In Floors Expected Unit CountActual Unit

Count

Elevator Structure 1965 21 102 102

Comments:

Unit # # Bedrooms Occupied?UnInspectedReason?

4-3E 1 Bedroom Yes

4-8A 2 Bedrooms Yes

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 8 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 9: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

4-12B 1 Bedroom Yes

4-16D 3 Bedrooms Yes

4-21A 3 Bedrooms Yes

Building 140005 - 5 [ Sample , Inspected ]

Address Line 1: 99 WILSON STREET

Address Line 2:City: BROOKLYN State: NY

Zip: 11211 Extension: ____

Type Constructed In Floors Expected Unit CountActual Unit

Count

Elevator Structure 1965 21 100 100

Comments:

Unit # # Bedrooms Occupied?UnInspectedReason?

5-5B 1 Bedroom Yes

5-11D 3 Bedrooms Yes

5-17B 1 Bedroom Yes

5-21D 3 Bedrooms Yes

Building 140006 - 6 [ Sample , Inspected ]

Address Line 1: 75 WILSON STREET

Address Line 2:City: BROOKLYN State: NY

Zip: 11211 Extension: ____

Type Constructed In Floors Expected Unit CountActual Unit

Count

Elevator Structure 1965 21 96 96

Comments:

Unit # # Bedrooms Occupied?UnInspectedReason?

6-3F 2 Bedrooms Yes

6-9F 2 Bedrooms Yes

6-16F 2 Bedrooms Yes

6-21C 1 Bedroom Yes

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 9 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 10: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Certificates

Certificate Item Certificate State

Boilers Yes - This certificate is provided or is not expired

Elevators Yes - This certificate is provided or is not expired

Fire Alarms Yes - This certificate is provided or is not expired

Lead-Based Paint Disclosure Forms Yes - This certificate is provided or is not expired

Lead-Based Paint Inspection Reports No - This certificate cannot be provided or is expired

Sprinkler Systems Yes - This certificate is provided or is not expired

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 10 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 11: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Score Details

Note: The inspection software allows for the recording of the same deficiency as many times as it occurs. However, it is only scored once.

The number within the parenthesis after the Deficiency indicates the number of observations for this inspectable area. For example; "Site -

Spalling (Walkway / Steps) (4)" indicates the deficiency was observed and recorded 4 times under Site. Each individual observation can be

found in the Deficiency Details section of this report.

Item Deficiency SeverityPoints

DeductedPoints

Received

Site - INDEPENDENCE - Site(0) [Possible Points : 16.56]

Health And Safety Deficiencies

Hazards HS - Tripping (Hazards) (NLT ) Level 3 4.70

4.70 11.86

Building 140001 - 1 - Common Areas [Possible Points : 1.12]

Non-Health And Safety Deficiencies

Doors CA - Damaged Hardware/Locks (Doors) Level 3 0.31

Floors CA - Peeling/Needs Paint (Floors) Level 2 0.07

Walls CA - Peeling/Needs Paint (Walls) (2) Level 2 0.03

0.42 0.70

Building 140001 - 1 - Unit 1-6F [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Walls Unit - Peeling/Needs Paint (Walls) Level 2 0.02

Health And Safety Deficiencies

Windows Unit - Inoperable/Not Lockable (Windows) (NLT ) Level 3 0.15

0.17 1.21

Building 140001 - 1 - Unit 1-10E [Possible Points : 1.38]

Health And Safety Deficiencies

Electrical System Unit - GFI - Inoperable (Electrical System) (NLT ) Level 3 0.75

0.75 0.63

Building 140001 - 1 - Unit 1-14F [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Ceiling Unit - Peeling/Needs Paint (Ceiling) Level 2 0.02

Kitchen Items Unit - Range/Stove- Missing/Damaged/Inoperable(Kitchen)

Level 2 0.25

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 11 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 12: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Deficiency SeverityPoints

DeductedPoints

Received

Windows Unit - Inoperable/Not Lockable (Windows) Level 1 0.04

0.31 1.07

Building 140001 - 1 - Unit 1-18E [Possible Points : 1.38]

Health And Safety Deficiencies

Windows Unit - Inoperable/Not Lockable (Windows) (NLT ) Level 3 0.15

0.15 1.23

Building 140002 - 2 - Common Areas [Possible Points : 1.25]

Non-Health And Safety Deficiencies

Ceiling CA - Peeling/Needs Paint (Ceiling) Level 1 0.02

Ceiling CA - Peeling/Needs Paint (Ceiling) Level 1 0.03

Floors CA - Peeling/Needs Paint (Floors) Level 2 0.03

Floors CA - Peeling/Needs Paint (Floors) Level 2 0.07

Graffiti CA - Graffiti Level 2 0.42

Walls CA - Damaged (Walls) Level 2 0.16

Walls CA - Peeling/Needs Paint (Walls) (2) Level 1 0.02

0.75 0.51

Building 140002 - 2 - Unit 2-10E [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Ceiling Unit - Peeling/Needs Paint (Ceiling) Level 2 0.02

Doors Unit - Damaged Surface (Holes/Paint/Rust/Glass)(Doors)

Level 3 0.15

Walls Unit - Mold/Mildew/Water Stains/Water Damage(Walls)

Level 3 0.08

Windows Unit - Inoperable/Not Lockable (Windows) Level 1 0.04

Health And Safety Deficiencies

Air Quality HS - Mold and/or Mildew Observed (Air Quality)(NLT )

Level 3 0.51

Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.51

1.29 0.09

Building 140002 - 2 - Unit 2-14D [Possible Points : 1.16]

Non-Health And Safety Deficiencies

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 12 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 13: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Deficiency SeverityPoints

DeductedPoints

Received

Walls Unit - Peeling/Needs Paint (Walls) Level 1 0.01

Health And Safety Deficiencies

Windows Unit - Inoperable/Not Lockable (Windows) (NLT ) Level 3 0.15

0.16 1.00

Building 140002 - 2 - Unit 2-15A [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Walls Unit - Mold/Mildew/Water Stains/Water Damage(Walls)

Level 3 0.08

Walls Unit - Peeling/Needs Paint (Walls) Level 1 0.01

Health And Safety Deficiencies

Air Quality HS - Mold and/or Mildew Observed (Air Quality)(NLT )

Level 3 0.51

Windows Unit - Inoperable/Not Lockable (Windows) (3) (NLT ) Level 3 0.15

0.74 0.64

Building 140002 - 2 - Unit 2-21E [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Kitchen Items Unit - Range/Stove- Missing/Damaged/Inoperable(Kitchen)

Level 2 0.25

Walls Unit - Peeling/Needs Paint (Walls) Level 2 0.02

Windows Unit - Inoperable/Not Lockable (Windows) Level 1 0.04

0.31 1.07

Building 140003 - 3 - Building Exterior [Possible Points : 2.91]

Non-Health And Safety Deficiencies

Walls BE- Missing Pieces/Holes/Spalling (Walls) Level 2 0.65

0.65 2.26

Building 140003 - 3 - Common Areas [Possible Points : 1.67]

Non-Health And Safety Deficiencies

Ceiling CA - Peeling/Needs Paint (Ceiling) Level 1 0.02

Ceiling CA - Peeling/Needs Paint (Ceiling) Level 1 0.02

Ceiling CA - Peeling/Needs Paint (Ceiling) Level 1 0.02

Ceiling CA - Peeling/Needs Paint (Ceiling) (2) Level 2 0.03

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 13 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 14: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Deficiency SeverityPoints

DeductedPoints

Received

Doors CA - Damaged Hardware/Locks (Doors) Level 3 0.63

Floors CA - Peeling/Needs Paint (Floors) Level 2 0.03

Graffiti CA - Graffiti Level 1 0.21

Walls CA - Peeling/Needs Paint (Walls) Level 2 0.03

Walls CA - Peeling/Needs Paint (Walls) (2) Level 2 0.03

Health And Safety Deficiencies

Emergency/FireExits

HS - Emergency/Fire Exits Blocked/Unusable(Emergency/Fire Exits) (2) (LT )

Level 3 0.63

1.66 0.02

Building 140003 - 3 - Unit 3-3A [Possible Points : 1.41]

Non-Health And Safety Deficiencies

Walls Unit - Peeling/Needs Paint (Walls) Level 2 0.02

Health And Safety Deficiencies

Bathroom Items Unit - Shower/Tub - Damaged/Missing (Bathroom)(NLT )

Level 3 0.68

0.69 0.72

Building 140003 - 3 - Unit 3-7F [Possible Points : 1.38]

Health And Safety Deficiencies

Bathroom Items Unit - Lavatory Sink - Damaged/Missing (Bathroom)(NLT )

Level 3 0.51

0.51 0.87

Building 140003 - 3 - Unit 3-11F [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Walls Unit - Peeling/Needs Paint (Walls) (3) Level 2 0.02

Health And Safety Deficiencies

Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.51

Windows Unit - Inoperable/Not Lockable (Windows) (2) (NLT ) Level 3 0.15

0.67 0.71

Building 140003 - 3 - Unit 3-15E* [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable Level 1 0.13

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 14 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 15: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Deficiency SeverityPoints

DeductedPoints

Received

(Kitchen)

Health And Safety Deficiencies

Electrical Hazards HS - Exposed Wires/Open Panels (ElectricalHazards) (LT )

Level 3 1.13

Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.51

Windows Unit - Inoperable/Not Lockable (Windows) (NLT ) Level 3 0.15

* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 1.91 0.00

Building 140003 - 3 - Unit 3-19D [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Walls Unit - Peeling/Needs Paint (Walls) Level 1 0.01

Health And Safety Deficiencies

Windows Unit - Inoperable/Not Lockable (Windows) (NLT ) Level 3 0.15

0.16 1.22

Building 140004 - 4 - Building Exterior [Possible Points : 2.80]

Non-Health And Safety Deficiencies

Doors BE - Damaged Surface (Holes/Paint/Rust/Glass)(Doors)

Level 3 1.55

1.55 1.26

Building 140004 - 4 - Common Areas [Possible Points : 1.81]

Non-Health And Safety Deficiencies

Floors CA - Peeling/Needs Paint (Floors) Level 2 0.03

Graffiti CA - Graffiti Level 2 0.42

Walls CA - Peeling/Needs Paint (Walls) Level 2 0.03

Health And Safety Deficiencies

Emergency/FireExits

HS - Missing Exit Signs (Emergency/Fire Exits) (NLT)

Level 3 0.63

1.12 0.70

Building 140004 - 4 - Unit 4-3E* [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Ceiling Unit - Mold/Mildew/Water Stains/Water Damage(Ceiling)

Level 3 0.08

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 15 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 16: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Deficiency SeverityPoints

DeductedPoints

Received

Ceiling Unit - Peeling/Needs Paint (Ceiling) Level 2 0.02

Doors Unit - Damaged Frames/Threshold/Lintels/Trim(Doors)

Level 2 0.04

Walls Unit - Peeling/Needs Paint (Walls) Level 2 0.02

Health And Safety Deficiencies

Air Quality HS - Mold and/or Mildew Observed (Air Quality)(NLT )

Level 3 0.51

Electrical System Unit - GFI - Inoperable (Electrical System) (2) (NLT ) Level 3 0.75

Windows Unit - Inoperable/Not Lockable (Windows) (NLT ) Level 3 0.15

* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 1.56 0.00

Building 140004 - 4 - Unit 4-8A [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Doors Unit - Damaged Surface (Holes/Paint/Rust/Glass)(Doors)

Level 3 0.15

Walls Unit - Peeling/Needs Paint (Walls) (2) Level 2 0.02

Health And Safety Deficiencies

Electrical System Unit - GFI - Inoperable (Electrical System) (NLT ) Level 3 0.75

0.92 0.46

Building 140004 - 4 - Unit 4-12B* [Possible Points : 1.16]

Non-Health And Safety Deficiencies

Ceiling Unit - Mold/Mildew/Water Stains/Water Damage(Ceiling)

Level 3 0.08

Ceiling Unit - Peeling/Needs Paint (Ceiling) Level 2 0.02

Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable(Kitchen)

Level 1 0.13

Walls Unit - Peeling/Needs Paint (Walls) (2) Level 2 0.02

Health And Safety Deficiencies

Air Quality HS - Mold and/or Mildew Observed (Air Quality)(NLT )

Level 3 0.51

Bathroom Items Unit - Lavatory Sink - Damaged/Missing (Bathroom)(NLT )

Level 3 0.51

Electrical Hazards HS - Exposed Wires/Open Panels (ElectricalHazards) (LT )

Level 3 1.13

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 16 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 17: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Deficiency SeverityPoints

DeductedPoints

Received

Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.51

* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 2.88 0.00

Building 140004 - 4 - Unit 4-16D* [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Bathroom Items Unit - Water Closet/Toilet-Damaged/Clogged/Missing (Bathroom)

Level 2 0.56

Ceiling Unit - Mold/Mildew/Water Stains/Water Damage(Ceiling)

Level 3 0.08

Doors Unit - Damaged Frames/Threshold/Lintels/Trim(Doors) (2)

Level 2 0.04

Doors Unit - Damaged Hardware/Locks (Doors) Level 2 0.08

Kitchen Items Unit - Refrigerator - Missing/Damaged/Inoperable(Kitchen)

Level 1 0.13

Walls Unit - Peeling/Needs Paint (Walls) (2) Level 2 0.02

Health And Safety Deficiencies

Air Quality HS - Mold and/or Mildew Observed (Air Quality)(NLT )

Level 3 0.51

Infestation HS - Insects / roaches (Infestation) (NLT ) Level 3 0.51

Windows Unit - Inoperable/Not Lockable (Windows) (2) (NLT ) Level 3 0.15

* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 2.06 0.00

Building 140004 - 4 - Unit 4-21A [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Walls Unit - Peeling/Needs Paint (Walls) (4) Level 2 0.02

0.02 1.37

Building 140005 - 5 - Common Areas* [Possible Points : 1.81]

Non-Health And Safety Deficiencies

Doors CA - Damaged Hardware/Locks (Doors) Level 3 0.63

Doors CA - Damaged Surface (Holes/Paint/Rust/Glass)(Doors)

Level 3 0.63

Windows CA - Damaged/Missing Screens (Windows) Level 1 0.09

Health And Safety Deficiencies

Emergency/Fire HS - Emergency/Fire Exits Blocked/Unusable Level 3 0.63

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 17 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 18: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Deficiency SeverityPoints

DeductedPoints

Received

Exits (Emergency/Fire Exits) (4) (LT )

* The point deductions for this sub-area exceed the number of possible points. The points received cannot be negative so it is set to zero. 1.97 0.00

Building 140005 - 5 - Unit 5-5B [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Ceiling Unit - Peeling/Needs Paint (Ceiling) Level 2 0.02

Walls Unit - Peeling/Needs Paint (Walls) (2) Level 2 0.02

Health And Safety Deficiencies

Electrical Hazards HS - Exposed Wires/Open Panels (ElectricalHazards) (LT )

Level 3 1.13

1.16 0.23

Building 140005 - 5 - Unit 5-11D [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Floors Unit - Hard Floor Covering Missing/DamagedFlooring/Tiles (Floors) (2)

Level 2 0.09

Walls Unit - Peeling/Needs Paint (Walls) (2) Level 2 0.02

0.11 1.28

Building 140005 - 5 - Unit 5-17B [Possible Points : 1.38]

Health And Safety Deficiencies

Windows Unit - Inoperable/Not Lockable (Windows) (2) (NLT ) Level 3 0.15

0.15 1.23

Building 140005 - 5 - Unit 5-21D [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Windows Unit - Inoperable/Not Lockable (Windows) Level 1 0.04

0.04 1.34

Building 140006 - 6 - Common Areas [Possible Points : 1.25]

Non-Health And Safety Deficiencies

Floors CA - Peeling/Needs Paint (Floors) Level 2 0.03

Graffiti CA - Graffiti Level 1 0.21

Walls CA - Peeling/Needs Paint (Walls) (2) Level 2 0.03

0.28 0.98

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 18 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 19: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Deficiency SeverityPoints

DeductedPoints

Received

Building 140006 - 6 - Unit 6-3F [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Ceiling Unit - Peeling/Needs Paint (Ceiling) Level 2 0.02

Doors Unit - Damaged Surface (Holes/Paint/Rust/Glass)(Doors)

Level 3 0.15

Kitchen Items Unit - Cabinets - Missing/Damaged (Kitchen) Level 2 0.14

Walls Unit - Peeling/Needs Paint (Walls) (2) Level 2 0.02

Health And Safety Deficiencies

Windows Unit - Inoperable/Not Lockable (Windows) (2) (NLT ) Level 3 0.15

0.47 0.91

Building 140006 - 6 - Unit 6-9F [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Kitchen Items Unit - Range/Stove- Missing/Damaged/Inoperable(Kitchen)

Level 3 0.51

Walls Unit - Peeling/Needs Paint (Walls) (2) Level 2 0.02

Health And Safety Deficiencies

Windows Unit - Inoperable/Not Lockable (Windows) (2) (NLT ) Level 3 0.15

0.67 0.71

Building 140006 - 6 - Unit 6-16F [Possible Points : 1.38]

Health And Safety Deficiencies

Windows Unit - Inoperable/Not Lockable (Windows) (NLT ) Level 3 0.15

0.15 1.23

Building 140006 - 6 - Unit 6-21C [Possible Points : 1.38]

Non-Health And Safety Deficiencies

Bathroom Items Unit - Plumbing - Clogged Drains (Bathroom) Level 1 0.28

Health And Safety Deficiencies

Electrical System Unit - GFI - Inoperable (Electrical System) (2) (NLT ) Level 3 0.75

Windows Unit - Inoperable/Not Lockable (Windows) (NLT ) Level 3 0.15

1.18 0.20

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 19 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 20: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Deficiency Details

Item Location/Comments Deficiency/Severity Decisions

Site - INDEPENDENCE - Site(0)

Non-Health And Safety Deficiencies

Health And Safety Deficiencies

Hazards side walk to pakg area HS - Tripping (Hazards)(NLT) - L3

- Tripping (not related toelevators) - poses a trippingrisk

Building 140001 - 1[Sample,Inspected] - Building Exterior

None

Building 140001 - 1[Sample,Inspected] - Building Systems

None

Building 140001 - 1[Sample,Inspected] - Common Areas

Non-Health And Safety Deficiencies

Closet/Utility/Mechanical

Floor 21need paint

CA - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Closet/Utility/Mechanical

Floor 2slop sink

CA - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Halls/Corridors/Stairs Floor 1stairs

CA - Peeling/Needs Paint(Floors) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feet

Lobby Floor 1no close

CA - Damaged Hardware/Locks (Doors) - L3

- Entry Door (leads tooutside)

- Hardware is damaged ormissing

- Door does not function as itshould (it does not properlylatch).

Health And Safety Deficiencies

Infestation BasementDoor stg

HS - Other (Hazards) (NLT)- L3

- Evidence of roaches- Single dead roach or roach

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 20 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 21: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

droppings observed

Building 140001 - 1[Sample,Inspected] - Unit 1-10E

Non-Health And Safety Deficiencies

Health And Safety Deficiencies

Electrical System Bathroominop

Unit - GFI - Inoperable(Electrical System) (NLT) -L3

- GFI does not function whenself-test button is pressed

Building 140001 - 1[Sample,Inspected] - Unit 1-14F

Non-Health And Safety Deficiencies

Ceiling Bathroomneed paint

Unit - Peeling/Needs Paint(Ceiling) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feet

Kitchen Items Kitcheninop

Unit - Range/Stove- Missing/Damaged/Inoperable(Kitchen) - L2

- Range/Stove/Oven- Gas Range/Stove/Oven- Burner(s) not functioning- ONE burner is not

functioning.

Windows Living Areano stay open

Unit - Inoperable/NotLockable (Windows) - L1

- Lock/Operability- Window cannot be opened

or will not stay open (If thewindow is designed to doso.)

- Window is on 4th floor orabove

- There IS another operablewindow in the same floorarea.

Building 140001 - 1[Sample,Inspected] - Unit 1-18E

Non-Health And Safety Deficiencies

Health And Safety Deficiencies

Windows Living Areano lockable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Window cannot be opened

or will not stay open (If thewindow is designed to doso.)

- Window is on 4th floor orabove

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 21 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 22: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

- There is NOT anotheroperable window in thesame floor area.

Building 140001 - 1[Sample,Inspected] - Unit 1-6F

Non-Health And Safety Deficiencies

Walls Bedroompp bed 1

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Health And Safety Deficiencies

Windows Living Areano lockable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Building 140002 - 2[Sample,Inspected] - Building Exterior

None

Building 140002 - 2[Sample,Inspected] - Building Systems

None

Building 140002 - 2[Sample,Inspected] - Common Areas

Non-Health And Safety Deficiencies

Closet/Utility/Mechanical

Basementmeter room

CA - Damaged (Walls) - L2 - Hole(s)- Larger than a sheet of

paper, but you cannot seethrough the hole

- ONE wall is affected.

Closet/Utility/Mechanical

Basementcompactor

CA - Peeling/Needs Paint(Floors) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feet

Closet/Utility/Mechanical

Floor 1slop sink

CA - Peeling/Needs Paint(Ceiling) - L1

- Peeling Paint or NeedsPaint

- Peeling paint on 1 to 4ceilings in common areas

Closet/Utility/ Floor 1 CA - Peeling/Needs Paint - Peeling Paint or Needs

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 22 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 23: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

Mechanical slop sink (Walls) - L1 Paint- 1 to 4 square feet of two or

more wall areas

Closet/Utility/Mechanical

Floor 9slop sink

CA - Peeling/Needs Paint(Walls) - L1

- Peeling Paint or NeedsPaint

- 1 to 4 square feet of two ormore wall areas

Halls/Corridors/Stairs Floor 1stairs

CA - Peeling/Needs Paint(Floors) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feet

Halls/Corridors/Stairs Floor 20stairs floor 20 11 and 3

CA - Graffiti - L2 - Graffiti on 2 to 5 interiorbuilding surfaces

Halls/Corridors/Stairs Floor 21need paint

CA - Peeling/Needs Paint(Ceiling) - L1

- Peeling Paint or NeedsPaint

- Peeling paint on 1 to 4ceilings in common areas

Building 140002 - 2[Sample,Inspected] - Unit 2-10E

Non-Health And Safety Deficiencies

Ceiling Bathroomnee paint

Unit - Peeling/Needs Paint(Ceiling) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feet

Doors Bathroombath hole

Unit - Damaged Surface(Holes/Paint/Rust/Glass)(Doors) - L3

- Bathroom Door- Surface is damaged- Door has holes- This condition DOES NOT

RESULT in a Health andSafety concern.

Walls Bathroomwater damage

Unit - Mold/Mildew/WaterStains/Water Damage(Walls) - L3

- Mold or Mildew (forexample, a darkened area)or Water Stains or WaterDamage (for exampleevidence of waterinfiltration)

- Greater than 1 square foot(wall surface may havefailed)

- This condition MAYRESULT in a Health ANDSafety concern

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 23 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 24: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

Windows Living Areano stay open

Unit - Inoperable/NotLockable (Windows) - L1

- Lock/Operability- Window cannot be opened

or will not stay open (If thewindow is designed to doso.)

- Window is on 4th floor orabove

- There IS another operablewindow in the same floorarea.

Health And Safety Deficiencies

Air Quality water damage HS - Mold and/or MildewObserved (Air Quality)(NLT) - L3

- Evidence of water infiltrationor other moisture producingcondition that causes mold,or mildew

- Greater than or equal to 1square foot of mold ormildew

Infestation Kitchencabinet

HS - Insects /roaches(Infestation) (NLT) - L3

- Evidence of roaches- Multiple dead roaches

observed

Building 140002 - 2[Sample,Inspected] - Unit 2-14D

Non-Health And Safety Deficiencies

Walls Bathroomneed paint

Unit - Peeling/Needs Paint(Walls) - L1

- Peeling Paint or NeedsPaint

- 1 to 4 square feet of wallarea

Health And Safety Deficiencies

Windows Bedroomno stay open

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Window cannot be opened

or will not stay open (If thewindow is designed to doso.)

- Window is on 4th floor orabove

- There is NOT anotheroperable window in thesame floor area.

Building 140002 - 2[Sample,Inspected] - Unit 2-15A

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 24 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 25: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

Non-Health And Safety Deficiencies

Walls Bathroomwater damage

Unit - Mold/Mildew/WaterStains/Water Damage(Walls) - L3

- Mold or Mildew (forexample, a darkened area)or Water Stains or WaterDamage (for exampleevidence of waterinfiltration)

- Greater than 1 square foot(wall surface may havefailed)

- This condition MAYRESULT in a Health ANDSafety concern

Walls Living Areaneed paint

Unit - Peeling/Needs Paint(Walls) - L1

- Peeling Paint or NeedsPaint

- 1 to 4 square feet of wallarea

Windows Bedroomno stay open

Unit - Inoperable/NotLockable (Windows) - L1

- Lock/Operability- Window cannot be opened

or will not stay open (If thewindow is designed to doso.)

- Window is on 4th floor orabove

- There IS another operablewindow in the same floorarea.

Health And Safety Deficiencies

Air Quality water damage HS - Mold and/or MildewObserved (Air Quality)(NLT) - L3

- Evidence of water infiltrationor other moisture producingcondition that causes mold,or mildew

- Greater than or equal to 1square foot of mold ormildew

Windows Bedroombd 1 no lockable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 25 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 26: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

Windows Kitchennot lockable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Building 140002 - 2[Sample,Inspected] - Unit 2-21E

Non-Health And Safety Deficiencies

Kitchen Items Kitcheninop

Unit - Range/Stove- Missing/Damaged/Inoperable(Kitchen) - L2

- Range/Stove/Oven- Gas Range/Stove/Oven- Burner(s) not functioning- ONE burner is not

functioning.

Walls Bathroomneed paint

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Windows Living Areainop

Unit - Inoperable/NotLockable (Windows) - L1

- Lock/Operability- Window cannot be opened

or will not stay open (If thewindow is designed to doso.)

- Window is on 4th floor orabove

- There IS another operablewindow in the same floorarea.

Building 140003 - 3[Sample,Inspected] - Building Exterior

Non-Health And Safety Deficiencies

Walls missing brick BE- Missing Pieces/Holes/Spalling (Walls) - L2

- Missing Pieces- A single missing piece (for

example, single brick orsection of siding)

Building 140003 - 3[Sample,Inspected] - Building Systems

None

Building 140003 - 3[Sample,Inspected] - Common Areas

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 26 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 27: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

Non-Health And Safety Deficiencies

Closet/Utility/Mechanical

Basementcompactor room

CA - Peeling/Needs Paint(Floors) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feet

Closet/Utility/Mechanical

Floor 20slop sink

CA - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Closet/Utility/Mechanical

Floor 21slop sink

CA - Peeling/Needs Paint(Ceiling) - L1

- Peeling Paint or NeedsPaint

- Peeling paint on 1 to 4ceilings in common areas

Closet/Utility/Mechanical

Floor 14slop sink

CA - Peeling/Needs Paint(Walls) - L1

- Peeling Paint or NeedsPaint

- 1 to 4 square feet of two ormore wall areas

Halls/Corridors/Stairs Floor 19no latch 19A

CA - Damaged Hardware/Locks (Doors) - L3

- Restroom Door or Fire/Emergency Door

- Hardware is damaged ormissing

- Door does not function as itshould (it does not properlylatch).

Halls/Corridors/Stairs Floor 13stairs

CA - Graffiti - L1 - Graffiti on 1 interior buildingsurface

Office Floor 1closet

CA - Peeling/Needs Paint(Ceiling) - L1

- Peeling Paint or NeedsPaint

- Peeling paint on 1 to 4ceilings in common areas

Restrooms Basementneed paint

CA - Peeling/Needs Paint(Ceiling) - L1

- Peeling Paint or NeedsPaint

- Peeling paint on 1 to 4ceilings in common areas

Storage Floor 1stg 2

CA - Peeling/Needs Paint(Ceiling) - L2

- Peeling Paint or NeedsPaint

- Peeling paint on more than4 ceilings in common areas

Storage Basementelevator shop

CA - Peeling/Needs Paint(Ceiling) - L2

- Peeling Paint or NeedsPaint

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 27 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 28: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

- Peeling paint on more than4 ceilings in common areas

Storage Basementstg 1

CA - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Health And Safety Deficiencies

Emergency/Fire Exits Floor 1iron lauch room office HA4 and HA 5

HS - Emergency/Fire ExitsBlocked/Unusable(Emergency/Fire Exits) (LT)- L3

- Emergency/Fire Exits(applies only on third orlower floors)

- Blocked- Other Condition (Please

explain other condition inthe box below)

Emergency/Fire Exits Floor 1iron scretary office

HS - Emergency/Fire ExitsBlocked/Unusable(Emergency/Fire Exits) (LT)- L3

- Emergency/Fire Exits(applies only on third orlower floors)

- Blocked- Other Condition (Please

explain other condition inthe box below)

Infestation Basementcompactor room

HS - Other (Hazards) (NLT)- L3

- Evidence of roaches- Single dead roach or roach

droppings observed

Building 140003 - 3[Sample,Inspected] - Unit 3-11F

Non-Health And Safety Deficiencies

Walls Living Areaneed paint

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Walls Kitchenneed paint

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Walls Bathroomneed paint

Unit - Peeling/Needs Paint(Walls) - L1

- Peeling Paint or NeedsPaint

- 1 to 4 square feet of wallarea

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 28 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 29: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

Health And Safety Deficiencies

Infestation Kitchencabinet

HS - Insects /roaches(Infestation) (NLT) - L3

- Evidence of roaches- Multiple live roaches

observed

Windows Bedroomno lockable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Windows Bedroomno lockable bed 2

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Building 140003 - 3[Sample,Inspected] - Unit 3-15E

Non-Health And Safety Deficiencies

Kitchen Items Kitchenbroken

Unit - Refrigerator - Missing/Damaged/Inoperable(Kitchen) - L1

- Refrigerator- Door seals are deteriorated

Health And Safety Deficiencies

Electrical Hazards Hallwayexposed haway

HS - Exposed Wires/OpenPanels (Electrical Hazards)(LT) - L3

- Exposed bare wires- The exposed bare wires

ARE capped BUT NOTenclosed in a securedelectrical box OR ARE NOTcapped

Infestation Kitchencabinet

HS - Insects /roaches(Infestation) (NLT) - L3

- Evidence of roaches- Multiple dead roaches

observed

Windows Bedroomno stay open

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Window cannot be opened

or will not stay open (If thewindow is designed to doso.)

- Window is on 4th floor orabove

- There is NOT another

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 29 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 30: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

operable window in thesame floor area.

Building 140003 - 3[Sample,Inspected] - Unit 3-19D

Non-Health And Safety Deficiencies

Walls Bathroomneed paint

Unit - Peeling/Needs Paint(Walls) - L1

- Peeling Paint or NeedsPaint

- 1 to 4 square feet of wallarea

Health And Safety Deficiencies

Windows Bedroomno lockable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Building 140003 - 3[Sample,Inspected] - Unit 3-3A

Non-Health And Safety Deficiencies

Walls Bathroomneed paint

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Health And Safety Deficiencies

Bathroom Items Bathroomhot water no close

Unit - Shower/Tub -Damaged/Missing(Bathroom) (NLT) - L3

- Shower or Tub (Unit)- The hardware is missing or

is not functioning

Building 140003 - 3[Sample,Inspected] - Unit 3-7F

Non-Health And Safety Deficiencies

Health And Safety Deficiencies

Bathroom Items Bathroomhot water inop

Unit - Lavatory Sink -Damaged/Missing(Bathroom) (NLT) - L3

- Bathroom Sink- The sink''s hardware is

missing or is not functioning

Building 140004 - 4[Sample,Inspected] - Building Exterior

Non-Health And Safety Deficiencies

Doors back door BE - Damaged Surface(Holes/Paint/Rust/Glass)

- Emergency/Fire Exit Door- Surface is damaged

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 30 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 31: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

(Doors) - L3 - Door has significant peeling,cracked, or no paint.

Building 140004 - 4[Sample,Inspected] - Building Systems

None

Building 140004 - 4[Sample,Inspected] - Common Areas

Non-Health And Safety Deficiencies

Closet/Utility/Mechanical

Basementcompactor

CA - Peeling/Needs Paint(Floors) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feet

Closet/Utility/Mechanical

Floor 1slop sink

CA - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Halls/Corridors/Stairs Floor 14stairs

CA - Graffiti - L2 - Graffiti on 2 to 5 interiorbuilding surfaces

Health And Safety Deficiencies

Emergency/Fire Exits Floor 1inop

HS - Missing Exit Signs(Emergency/Fire Exits)(NLT) - L3

- Exit Signs- No adjacent or other internal

/external illumination on ornear the sign

Infestation Basementcompactor

HS - Other (Hazards) (NLT)- L3

- Evidence of roaches- Single dead roach or roach

droppings observed

Building 140004 - 4[Sample,Inspected] - Unit 4-12B

Non-Health And Safety Deficiencies

Ceiling Bathroommold

Unit - Mold/Mildew/WaterStains/Water Damage(Ceiling) - L3

- Mold or Mildew (forexample, a darkened area)or Water Stains or WaterDamage (for exampleevidence of waterinfiltration)

- Greater than 1 square foot(ceiling surface may havefailed)

- This condition MAYRESULT in a Health AND

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 31 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 32: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

Safety concern

Ceiling Bathroomneed paint

Unit - Peeling/Needs Paint(Ceiling) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feet

Kitchen Items Kitchenbroken

Unit - Refrigerator - Missing/Damaged/Inoperable(Kitchen) - L1

- Refrigerator- Door seals are deteriorated

Walls Bathroomneed paint

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Walls Kitchenneed paint

Unit - Peeling/Needs Paint(Walls) - L1

- Peeling Paint or NeedsPaint

- 1 to 4 square feet of wallarea

Health And Safety Deficiencies

Air Quality mold HS - Mold and/or MildewObserved (Air Quality)(NLT) - L3

- Evidence of water infiltrationor other moisture producingcondition that causes mold,or mildew

- Greater than or equal to 1square foot of mold ormildew

Bathroom Items Bathroommissing

Unit - Lavatory Sink -Damaged/Missing(Bathroom) (NLT) - L3

- Bathroom Sink- The sink itself is missing

Electrical Hazards Bathroomexposed bath

HS - Exposed Wires/OpenPanels (Electrical Hazards)(LT) - L3

- Exposed bare wires- The exposed bare wires

ARE capped BUT NOTenclosed in a securedelectrical box OR ARE NOTcapped

Infestation Kitchencabinet

HS - Insects /roaches(Infestation) (NLT) - L3

- Evidence of roaches- Multiple dead roaches

observed

Building 140004 - 4[Sample,Inspected] - Unit 4-16D

Non-Health And Safety Deficiencies

Bathroom Items Bathroom Unit - Water Closet/Toilet- - Toilet (Unit)

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 32 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 33: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

seat damage Damaged/Clogged/Missing(Bathroom) - L2

- Seat, hinge, cover, or flushhandle is missing ordamaged

Ceiling Bathroommold

Unit - Mold/Mildew/WaterStains/Water Damage(Ceiling) - L3

- Mold or Mildew (forexample, a darkened area)or Water Stains or WaterDamage (for exampleevidence of waterinfiltration)

- Greater than 1 square foot(ceiling surface may havefailed)

- This condition MAYRESULT in a Health ANDSafety concern

Doors Bedroomcloset

Unit - Damaged Frames/Threshold/Lintels/Trim(Doors) - L2

- All Other Doors (includescloset or other interiordoors)

- Frame is damaged causingthe door not to function orlock (this includesthresholds, lintels, trim,headers, and jambs)

Doors Bedroombed 1 closet

Unit - Damaged Frames/Threshold/Lintels/Trim(Doors) - L2

- All Other Doors (includescloset or other interiordoors)

- Frame is damaged causingthe door not to function orlock (this includesthresholds, lintels, trim,headers, and jambs)

Doors Bedroominop

Unit - Damaged Hardware/Locks (Doors) - L2

- All Other Doors (includescloset or other interiordoors)

- Hardware is damaged ormissing

- Other interior door does notfunction as it should orcannot be locked.

Kitchen Items Kitchenbroken

Unit - Refrigerator - Missing/Damaged/Inoperable

- Refrigerator- Door seals are deteriorated

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 33 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 34: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

(Kitchen) - L1

Walls Bathroomneed paint

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Walls Living Areaneed paint

Unit - Peeling/Needs Paint(Walls) - L1

- Peeling Paint or NeedsPaint

- 1 to 4 square feet of wallarea

Windows Living Areano open

Unit - Inoperable/NotLockable (Windows) - L1

- Lock/Operability- Window cannot be opened

or will not stay open (If thewindow is designed to doso.)

- Window is on 4th floor orabove

- There IS another operablewindow in the same floorarea.

Health And Safety Deficiencies

Air Quality mold HS - Mold and/or MildewObserved (Air Quality)(NLT) - L3

- Evidence of water infiltrationor other moisture producingcondition that causes mold,or mildew

- Greater than or equal to 1square foot of mold ormildew

Infestation Kitchencabinet

HS - Insects /roaches(Infestation) (NLT) - L3

- Evidence of roaches- Multiple dead roaches

observed

Windows Bedroomno lockable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Building 140004 - 4[Sample,Inspected] - Unit 4-21A

Non-Health And Safety Deficiencies

Walls Hallway Unit - Peeling/Needs Paint - Peeling Paint or Needs

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 34 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 35: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

need paint (Walls) - L2 Paint- Greater than 4 square feet

of wall area

Walls Bedroombed 1

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Walls Bedroombed 2

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Walls Living Areanedd paint

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Building 140004 - 4[Sample,Inspected] - Unit 4-3E

Non-Health And Safety Deficiencies

Ceiling Bathroomwater damage

Unit - Mold/Mildew/WaterStains/Water Damage(Ceiling) - L3

- Mold or Mildew (forexample, a darkened area)or Water Stains or WaterDamage (for exampleevidence of waterinfiltration)

- Greater than 1 square foot(ceiling surface may havefailed)

- This condition MAYRESULT in a Health ANDSafety concern

Ceiling Bathroomneed paint

Unit - Peeling/Needs Paint(Ceiling) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feet

Doors Hallwayhallway

Unit - Damaged Frames/Threshold/Lintels/Trim(Doors) - L2

- All Other Doors (includescloset or other interiordoors)

- Frame is damaged causingthe door not to function orlock (this includesthresholds, lintels, trim,

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 35 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 36: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

headers, and jambs)

Walls Bathroomneed paint

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Health And Safety Deficiencies

Air Quality water damage HS - Mold and/or MildewObserved (Air Quality)(NLT) - L3

- Evidence of water infiltrationor other moisture producingcondition that causes mold,or mildew

- Greater than or equal to 1square foot of mold ormildew

Electrical System Bathroominop

Unit - GFI - Inoperable(Electrical System) (NLT) -L3

- GFI does not function whenself-test button is pressed

Electrical System Kitcheninop

Unit - GFI - Inoperable(Electrical System) (NLT) -L3

- GFI does not function whenself-test button is pressed

Windows Bedroomno lockable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Building 140004 - 4[Sample,Inspected] - Unit 4-8A

Non-Health And Safety Deficiencies

Doors Bedroombed 2

Unit - Damaged Surface(Holes/Paint/Rust/Glass)(Doors) - L3

- All Other Doors (includescloset or other interiordoors)

- Surface is damaged- Door has holes.- Greater than 1 inch- This condition DOES NOT

RESULT in a Health andSafety concern.

Walls Bedroombed 1

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feet

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 36 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 37: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

of wall area

Walls Bedroombed 2

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Health And Safety Deficiencies

Electrical System Bathroominop

Unit - GFI - Inoperable(Electrical System) (NLT) -L3

- GFI does not function whenself-test button is pressed

Building 140005 - 5[Sample,Inspected] - Building Exterior

None

Building 140005 - 5[Sample,Inspected] - Building Systems

None

Building 140005 - 5[Sample,Inspected] - Common Areas

Non-Health And Safety Deficiencies

Day Care Floor 1broken

CA - Damaged/MissingScreens (Windows) - L1

- A second means of windowegress exists

- Window bars are actuallychild safety bars

Halls/Corridors/Stairs Floor 21glass cracked 21B

CA - Damaged Surface(Holes/Paint/Rust/Glass)(Doors) - L3

- Restroom Door or Fire/Emergency Door

- Surface is damaged- Door has significant peeling,

cracked, or no paint.- This condition DOES NOT

RESULT in a Health andSafety concern.

Halls/Corridors/Stairs Floor 11no latch 11A

CA - Damaged Hardware/Locks (Doors) - L3

- Restroom Door or Fire/Emergency Door

- Hardware is damaged ormissing

- Door does not function as itshould (it does not properlylatch).

Health And Safety Deficiencies

Emergency/Fire Exits Floor 1 HS - Emergency/Fire Exits - Emergency/Fire Exits

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 37 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 38: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

iron office rest room inday care

Blocked/Unusable(Emergency/Fire Exits) (LT)- L3

(applies only on third orlower floors)

- Blocked- Other Condition (Please

explain other condition inthe box below)

Emergency/Fire Exits Floor 1director office day care

HS - Emergency/Fire ExitsBlocked/Unusable(Emergency/Fire Exits) (LT)- L3

- Emergency/Fire Exits(applies only on third orlower floors)

- Blocked- Other Condition (Please

explain other condition inthe box below)

Emergency/Fire Exits Floor 1security office

HS - Emergency/Fire ExitsBlocked/Unusable(Emergency/Fire Exits) (LT)- L3

- Emergency/Fire Exits(applies only on third orlower floors)

- Blocked- Other Condition (Please

explain other condition inthe box below)

Emergency/Fire Exits Floor 1iron launch room

HS - Emergency/Fire ExitsBlocked/Unusable(Emergency/Fire Exits) (LT)- L3

- Emergency/Fire Exits(applies only on third orlower floors)

- Blocked- Other Condition (Please

explain other condition inthe box below)

Building 140005 - 5[Sample,Inspected] - Unit 5-11D

Non-Health And Safety Deficiencies

Floors Kitchendamage

Unit - Hard Floor CoveringMissing/Damaged Flooring/Tiles (Floors) - L2

- Hard Floor Covering Missing/Damaged (all flooringmaterials except carpet)

- 10% to 50% of any singlefloor

Floors Hallwaymissing

Unit - Hard Floor CoveringMissing/Damaged Flooring/Tiles (Floors) - L2

- Hard Floor Covering Missing/Damaged (all flooringmaterials except carpet)

- 10% to 50% of any singlefloor

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 38 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 39: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

Walls Hallwayneed paint

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Walls Bathroomned paint

Unit - Peeling/Needs Paint(Walls) - L1

- Peeling Paint or NeedsPaint

- 1 to 4 square feet of wallarea

Building 140005 - 5[Sample,Inspected] - Unit 5-17B

Non-Health And Safety Deficiencies

Health And Safety Deficiencies

Windows Kitchenno lokcable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Windows Living Areano lockable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Building 140005 - 5[Sample,Inspected] - Unit 5-21D

Non-Health And Safety Deficiencies

Windows Living Areano stay open

Unit - Inoperable/NotLockable (Windows) - L1

- Lock/Operability- Window cannot be opened

or will not stay open (If thewindow is designed to doso.)

- Window is on 4th floor orabove

- There IS another operablewindow in the same floorarea.

Building 140005 - 5[Sample,Inspected] - Unit 5-5B

Non-Health And Safety Deficiencies

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 39 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 40: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

Ceiling Bathroomneed paint

Unit - Peeling/Needs Paint(Ceiling) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feet

Walls Bathroomneed paint

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Walls Bedroomneed paint

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Health And Safety Deficiencies

Electrical Hazards Hallwayexposed hallway

HS - Exposed Wires/OpenPanels (Electrical Hazards)(LT) - L3

- Exposed bare wires- The exposed bare wires

ARE capped BUT NOTenclosed in a securedelectrical box OR ARE NOTcapped

Building 140006 - 6[Sample,Inspected] - Building Exterior

None

Building 140006 - 6[Sample,Inspected] - Building Systems

None

Building 140006 - 6[Sample,Inspected] - Common Areas

Non-Health And Safety Deficiencies

Closet/Utility/Mechanical

Floor 21slop sink

CA - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Closet/Utility/Mechanical

Basementcompactor

CA - Peeling/Needs Paint(Floors) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feet

Closet/Utility/Mechanical

Floor 1slop sink

CA - Peeling/Needs Paint(Walls) - L1

- Peeling Paint or NeedsPaint

- 1 to 4 square feet of two ormore wall areas

Halls/Corridors/Stairs Floor 2 CA - Graffiti - L1 - Graffiti on 1 interior building

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 40 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 41: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

stairs surface

Building 140006 - 6[Sample,Inspected] - Unit 6-16F

Non-Health And Safety Deficiencies

Health And Safety Deficiencies

Windows Bedroomno lockable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Building 140006 - 6[Sample,Inspected] - Unit 6-21C

Non-Health And Safety Deficiencies

Bathroom Items Bathroomclogged

Unit - Plumbing - CloggedDrains (Bathroom) - L1

- Bathroom Sink- There is a problem with the

drainage- The basin will drain, but it is

slow

Health And Safety Deficiencies

Electrical System Bathroominop

Unit - GFI - Inoperable(Electrical System) (NLT) -L3

- GFI does not function whenself-test button is pressed

Electrical System Kitcheninop

Unit - GFI - Inoperable(Electrical System) (NLT) -L3

- GFI does not function whenself-test button is pressed

Windows Living Areano lockable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Building 140006 - 6[Sample,Inspected] - Unit 6-3F

Non-Health And Safety Deficiencies

Ceiling Bathroomneed paint

Unit - Peeling/Needs Paint(Ceiling) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feet

Doors Bedroom Unit - Damaged Surface - All Other Doors (includes

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 41 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 42: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

bed 2 (Holes/Paint/Rust/Glass)(Doors) - L3

closet or other interiordoors)

- Surface is damaged- Door has holes.- Greater than 1 inch- This condition DOES NOT

RESULT in a Health andSafety concern.

Kitchen Items Kitchenlaminate damage

Unit - Cabinets - Missing/Damaged (Kitchen) - L2

- Kitchen Cabinets- Cabinets, doors, shelves, or

laminate damaged ormissing

- 10% to 50% of cabinets,doors, shelves, or laminatedamaged or missing

Walls Bathroomneed paint

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Walls Bedroombed 2

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Health And Safety Deficiencies

Windows Living Areano lockable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Windows Kitchenno lockable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Building 140006 - 6[Sample,Inspected] - Unit 6-9F

Non-Health And Safety Deficiencies

Kitchen Items Kitchen Unit - Range/Stove- Missing - Range/Stove/Oven

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 42 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 43: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Item Location/Comments Deficiency/Severity Decisions

2 inop /Damaged/Inoperable(Kitchen) - L3

- Gas Range/Stove/Oven- Burner(s) not functioning- TWO OR MORE burners

are not functioning.- This condition DOES NOT

RESULT in a Health andSafety concern.

Walls Bedroombed 1

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Walls Bedroombed 2 closet

Unit - Peeling/Needs Paint(Walls) - L2

- Peeling Paint or NeedsPaint

- Greater than 4 square feetof wall area

Windows Bedroomno open

Unit - Inoperable/NotLockable (Windows) - L1

- Lock/Operability- Window cannot be opened

or will not stay open (If thewindow is designed to doso.)

- Window is on 4th floor orabove

- There IS another operablewindow in the same floorarea.

Health And Safety Deficiencies

Windows Bedroomno lockable

Unit - Inoperable/NotLockable (Windows) (NLT)- L3

- Lock/Operability- Lock is missing or damaged

(only if the window wasdesigned to lock)

- Window is NOT accessiblefrom outside

Inspection Summary Report (POA) for Inspection #625121

Report generation date/time:10/18/2018 06:30 PM Score Version: 1 Page: 43 of 43Report template version: 04/15/2011 Note: The report generation date/time does not reflect the inspection release date/time.

Page 44: Inspection Summary Report (POA) for Inspection #625121 Documents/Brooklyn... · 2019-01-28 · Final Points Site 16.56 0.00 16.56 4.70 11.86 Building Exterior 16.73 2.20 14.53 0.00

Notice: Modifications to the Inspection Summary Report

With the rollout of the new Uniform Physical Condition Standards (UPCS) inspection software (version 4.0).PIH-REAC now has the capability to collect more detailed information about observations made during theinspection of properties. Therefore, the report has been modified to provide this detailed information, and also tomake the results of the inspection more clear. The following explains the major changes to the report.

Changes to Score Summary - The section of the report, which summarizes the score, has been modifiedto better explain how the final score was derived for the property, and the source of lost points. Additionally,score information from the two most recent inspections of the property is provided to allow comparison tothis inspection's score.

Addition of scored and non-scored deficiency reports - The section of the report that displays observeddeficiencies has been divided into two sections: the Score Report and the Deficiency Report. Non-scoreddeficiencies refer to multiple deficiencies of the same type observed with the same sub-area, they arereported for informational purposes only and are not scored. Only one deficiency of the same type for thesame sub-area is counted for scoring purposes.

Score Report - a detailed account of only the scored deficiencies by sub-area.

Deficiency Report - A detailed account of all deficiencies, both scored and non-scored, by sub-area.In addition, standardized locations and more descriptive information for each deficiency are provided.

To read more about the above, and for additional assistance in understanding the report, you may access theInspection Summary Report Guide (version 4.0) athttp://www.hud.gov/offices/reac/products/pass/inspectionrpt40.cfm