INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER DEPARTMENT NORTH HAVEN, MAINE AUGUST 13, 2019

INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL)OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK

NORTH HAVEN WATER DEPARTMENTNORTH HAVEN, MAINE

AUGUST 13, 2019

Page 2: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK

NORTH HAVEN WATER DEPARTMENT

NORTH HAVEN, MAINE

AUGUST 13, 2019 SCOPE: On August 13, 2019 Underwater Solutions Inc. inspected the 280,000-gallon welded steel potable water storage tank to provide information regarding the overall condition and integrity of this tank and removed the sediment accumulation from the floor. EXTERIOR INSPECTION: The entire exterior of this water storage tank was inspected, to include walls and coating, manways, anchor bolts, foundation, ladder and safety cage, overflow, roof, vent and hatch. Walls and Coating The exterior steel wall panels and associated welds appeared sound and remain free of obvious fatigue or failures at this time. The average dry film thickness of the protective coating system applied to the exterior steel wall panels was measured during this inspection. The dry film thickness of the coating system applied to the exterior wall surfaces was found as follows:

Row Mil Thickness Row Mil Thickness

1. 6.6 mils 6. 10.8 mils 2. 6.0 mils 7. 6.2 mils 3. 10.6 mils 8. 11.2 mils 4. 6.2 mils 9. 9.7 mils 5. 9.0 mils

Page 3: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER DEPARTMENT NORTH HAVEN, MAINE AUGUST 13, 2019 PAGE 2 The American Water Works Association (AWWA) recommends a dry film thickness of 7.0 to 10.0 mils of coating film thickness be applied to the exterior surfaces of steel potable water storage tanks to provide adequate protection for steel structures. The protective coating applied to these welded steel surfaces appeared to have been applied uniformly and the average dry film thickness of the protective coating applied to the third, fifth, sixth, eighth and ninth rows of wall panels above the tank base meets the AWWA’s recommendations, while the average dry film thickness of the protective coating applied to the remaining rows of wall panels is below the AWWA’s recommendations at this time. Although a decline in the coating film thickness was measured throughout four rows of wall panels, the coating system applied to these welded steel surfaces remains having good adhesion value, however has become chalky due to weathering. A mild to moderate, non-uniform accumulation of mildew throughout the exterior walls has caused a decline in the overall aesthetics. RECOMMENDATION(S): It is our recommendation to pressure-wash the exterior wall surfaces at 3,000 P.S.I. using a 40° tip to remove the accumulated mildew and chalking from these surfaces in an effort to preserve the adhesion value of the protective coating, while improving the overall aesthetics. Manways Two, 24” inside diameter manways penetrate the lowest row of wall panels approximately 19” above the tank base and are securely installed and free of obvious leakage. The protective coating applied to the easternmost manway has an average dry film thickness of 4.9 mils and is below the AWWA’s recommendations, however the protective coating on these steel surfaces appeared to have been applied uniformly and was found having good adhesion value at this time. The protective coating applied to the westernmost manway has an average dry film thickness of 6.3 mils and is below the AWWA’s recommendations, however the protective coating on these steel surfaces appeared to have been applied uniformly and was found having good adhesion value at this time. Spray-painted graffiti remains on the surfaces of this manway; however, no other obvious vandalism was evident at this time. RECOMMENDATION(S): It is our recommendation to remove the graffiti from the surfaces of the westernmost manway to improve the aesthetics.

Page 4: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER DEPARTMENT NORTH HAVEN, MAINE AUGUST 13, 2019 PAGE 3 Anchor Bolts Twenty-four, 2-1/4” diameter steel anchor bolts extend up from the foundation through steel support chairs welded to the lowest row of wall panels. Each anchor bolt has one nut securely installed and the protective coating on these support components appeared to have been applied uniformly and was found having good adhesion value at this time. RECOMMENDATION(S): None at this time. Concrete Foundation The exposed surfaces of the 19" wide by 11" tall concrete foundation is not coated and appeared sound and remains free of cracks, spall or other obvious fatigue of the concrete. The sealant applied throughout the circumference of the tank at the junction of where the foundation and tank base meet appeared to have been applied uniformly and was found having good adhesion value at this time. Accumulated mildew throughout the foundation has caused a decline on the overall aesthetics. RECOMMENDATION(S): It is our recommendation that when the exterior wall surfaces are pressure-washed, we recommend pressure-washing the foundation to remove the accumulated mildew in an effort to improve the aesthetics. Ladder and Safety Cage A ladder and safety cage extend from ground level up through three platforms to the roof dome supported to the tank wall with fifteen sets of welded standoffs, providing safe access and egress to and from the roof. This entire ladder, including each platform remains sound, while the protective coating on these steel surfaces appeared to have been applied uniformly and was found having good adhesion value at this time. A ladder guard secured with a lock is installed at the base of the ladder/safety cage, preventing unwanted access to the ladder/roof. RECOMMENDATION(S): None at this time.

Page 5: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER DEPARTMENT NORTH HAVEN, MAINE AUGUST 13, 2019 PAGE 4 Overflow A 12” inside diameter steel overflow pipe exits the base of a welded steel weir box, extends down and is supported to the tank wall with nine welded standoffs through a 90° elbow, directing the pipe approximately 20’ away from the tank and terminating at ground level. The outlet end of the overflow pipe was free of obvious obstructions and was found with a screen installed at its end, however this screen does not have 24-mesh. The inspection hatch located on top of the weir box was not opened, however was found secured with a lock at this time. The protective coating on the steel weir box, including the steel pipe that extends from the weir box has an average dry film thickness of 7.0 mils and appeared to have been applied uniformly and was found having good adhesion value at this time. RECOMMENDATION(S): None at this time. The 20’ long overflow pipe extension is not coated and was found with mild corrosion on all surfaces, however this steel pipe extension remains sound and free of obvious fatigue/deterioration at this time. RECOMMENDATION(S): It is our recommendation to coat the surfaces of this pipe using a protective coating formulated for exterior exposure and to be applied in accordance with the product manufacturer’s surface preparation and application recommendations in an effort to halt corrosion, prevent steel fatigue/deterioration and to provide good protection for the steel. Roof The entire roof was inspected and the steel panels and associated welds appeared sound and remain free of obvious fatigue or failures at this time. The protective coating on the roof panels has an average dry film thickness of 9.8 mils and appeared to have been applied uniformly, meets the AWWA’s recommendations and was found having mostly good adhesion value, however declined film thickness (thinning) of the coating has caused mild surface corrosion (blotch rusting) to show through the coating throughout approximately 5% of the roof surfaces. These steel panels showing surface corrosion (blotch rusting) remain sound and free of obvious fatigue/deterioration at this time.

Page 6: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER DEPARTMENT NORTH HAVEN, MAINE AUGUST 13, 2019 PAGE 5 A steel stair case and steel safety railings extend from the roof access ladder up to the vent within the center of the roof and were found securely welded in-place and appeared sound at this time. The protective coating on these steel access components has an average dry film thickness of 13.0 mils and appeared to have been applied uniformly, meets the AWWA’s recommendations and was found having mostly good adhesion value, however declined film thickness (thinning) of the coating has caused mild surface corrosion (blotch rusting) to show through the coating throughout approximately 10% of the stair and safety railing surfaces. These steel stairs and safety railings showing surface corrosion (blotch rusting) remain sound and free of obvious fatigue/deterioration at this time. RECOMMENDATION(S): It is our recommendation to spot-coat the surfaces of the roof, stair case and safety railings showing surface corrosion (blotch rusting) using a protective coating formulated for exterior exposure and to be applied in accordance with the product manufacturer’s surface preparation and application recommendations in an effort to halt corrosion, prevent steel fatigue/deterioration and to provide good protection for these steel surfaces. Vent The steel vent assembly is located within the center of the roof, having a 24” inside diameter and stands 30” tall. A 36” outside diameter steel cap is installed over this vent, and a non-corrodible metal screen having 4-mesh is installed around the outside circumference of this vent at this time. The protective coating on the steel vent assembly has an average dry film thickness of 7.2 mils and appeared to have been applied uniformly, meets the AWWA’s recommendations and was found having mostly good adhesion value, however declined film thickness (thinning) of the coating has caused mild surface corrosion (blotch rusting) to show through the coating throughout less than 5% of these surfaces. These surfaces showing surface corrosion (blotch rusting) remain sound and free of obvious fatigue/deterioration at this time. RECOMMENDATION(S): It is our recommendation to spot-coat the surfaces of the vent assembly showing surface corrosion (blotch rusting) using a protective coating formulated for exterior exposure and to be applied in accordance with the product manufacturer’s surface preparation and application recommendations in an effort to halt corrosion, prevent steel fatigue/deterioration and to provide good protection for these steel surfaces.

Page 7: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER DEPARTMENT NORTH HAVEN, MAINE AUGUST 13, 2019 PAGE 6 It is also our recommendation to install a secondary, non-corrodible metal screen having 24-mesh over the existing screen around the circumference of the vent in an effort to prevent access to the interior of the tank. Hatch One, 24” inside diameter hatch provides good access to the interior through the roof. This hatch remains in good working condition and was found secured with a lock, preventing unwanted access. The protective coating on the steel hatch cover and trunk appeared to have been applied uniformly and was found having mostly good adhesion value, however declined film thickness (thinning) of the coating has caused mild surface corrosion (blotch rusting) to show through the coating throughout less than 5% of all interior and exterior surfaces. These surfaces showing surface corrosion (blotch rusting) remain sound and free of obvious fatigue/deterioration at this time. RECOMMENDATION(S): It is our recommendation to spot-coat the exterior surfaces of the hatch cover and trunk showing surface corrosion (blotch rusting) using a protective coating formulated for exterior exposure and to be applied in accordance with the product manufacturer’s surface preparation and application recommendations in an effort to halt corrosion, prevent steel fatigue/deterioration and to provide good protection for these steel surfaces. It is our recommendation to spot-coat the interior surfaces of the hatch cover and trunk showing surface corrosion (blotch rusting) using a protective coating formulated for immersion (wet contact) and having an A.N.S.I./N.S.F.61 approval for use in structures containing potable water and to be applied in accordance with the product manufacturer’s surface preparation and application recommendations in an effort to halt corrosion, prevent steel fatigue/deterioration and to provide good protection for these steel surfaces. INTERIOR INSPECTION: The entire interior of this water storage tank was inspected, to include sediment accumulations, floor, manways, piping, walls and coating, overhead, overflow and aesthetic water quality. Sediment Accumulations A uniform layer of accumulated precipitate was found on all floor surfaces, averaging 1/16" in depth.

Page 8: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER DEPARTMENT NORTH HAVEN, MAINE AUGUST 13, 2019 PAGE 7 After completing this inspection, all precipitate was removed (vacuumed) from the floor. Floor After removing the accumulated precipitate, the steel floor panels and associated welds were inspected and appeared sound and remain free of obvious fatigue or failures at this time. The protective coating on these welded steel surfaces has an average dry film thickness of 13.7 mils and appeared to have been applied uniformly, meets the AWWA’s recommendations and remains having good adhesion value at this time. Mild staining remains throughout the floor due to the accumulation of precipitate, while coating chips/flakes that has lost adhesion from the interior walls remains throughout the outside circumference of the floor due to these coating debris being too large to be removed by our vacuum system. RECOMMENDATION(S): It is our recommendation that when the tank is removed from service and de-watered to complete the re-coating of the interior walls, that the coating debris that remain on the floor be removed to prevent these debris from being drawn into the influent/effluent pipe. Manways Two 24” inside diameter manways penetrate the lowest row of wall panels approximately 19” above the floor and are securely installed and free of leakage. The protective coating on the easternmost manway has an average dry film thickness of 9.5 mils and is below the AWWA’s recommendations of 10. 5 mils, however the protective coating applied to these steel surfaces was found having good adhesion value at this time. RECOMMENDATION(S): None at this time. The protective coating on the westernmost manway has an average dry film thickness of 8.5 mils and is below the AWWA’s recommendations of 10. 5 mils, however the protective coating applied to these steel surfaces was found having mostly good adhesion value. One coating blister remains within the weld at the junction of where the manway trunk and wall panel meet, resulting in exposure of the underlying steel. Although corrosion was found on these exposed steel surfaces, no obvious fatigue (pitting) of the steel wall panel or steel trunk or fatigue of the weld was evident at this time.

Page 9: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER DEPARTMENT NORTH HAVEN, MAINE AUGUST 13, 2019 PAGE 8 RECOMMENDATION(S): It is our recommendation that the next time this tank is removed from service and de-watered that the weld that secures the westernmost manway trunk to the wall panel be spot-coated using a protective coating formulated for immersion (wet contact) and having an A.N.S.I./N.S.F.61 approval for use in structures containing potable water and to be applied in accordance with the product manufacturer’s surface preparation and application recommendations in an effort to halt corrosion, prevent steel fatigue/deterioration and to provide good protection for the steel. Piping The influent/effluent pipe penetrates the floor approximately 6’ in from the wall, having a 12” inside diameter and is flush in the floor. A 12” inside diameter by 13” tall removable riser is installed above this pipe, serving as a silt stop. This pipe was free of obstructions and flow was leaving the tank through this pipe at the time of this inspection. The protective coating on the removable silt stop was found having good adhesion value at this time. RECOMMENDATION(S): None at this time. Walls and Coating The interior walls were inspected beginning at the floor and by spiraling the circumference of the tank up to the water surface. These steel wall panels, to include the welds between panels, appeared mostly sound at this time. The average dry film thickness of the protective coating system applied to the interior steel wall panels was measured during this inspection. The dry film thickness of the coating system applied to the interior wall surfaces was found as follows:

Row Mil Thickness Row Mil Thickness

1. 10.6 mils 6. 11.2 mils 2. 18.7 mils 7. 11.8 mils 3. 16.0 mils 8. 11.2 mils 4. 12.8 mils 9. 6.1 mils 5. 9.5 mils

Page 10: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER DEPARTMENT NORTH HAVEN, MAINE AUGUST 13, 2019 PAGE 9 The American Water Works Association (AWWA) recommends a dry film thickness of 10.5 to 15.5 mils of coating film thickness be applied to the interior surfaces of steel potable water storage tanks to provide adequate protection for steel structures. The protective coating applied to the interior wall panels and welds appeared to have been applied uniformly, however was found having poor adhesion value at this time. Adhesion loss (blistering, lifting and peeling) of the protective coating was observed throughout approximately 30% of the wall panel and horizontal weld surfaces throughout the five lowest rows of wall panels, resulting in exposure of the underlying steel. No obvious fatigue (pitting) of the steel wall panels was evident within these areas of exposure, rather mild to moderate corrosion exists at this time. Corrosion exists on the horizontal welds showing coating loss/steel exposure and fatigue (pitting) of the welds having depths ranging from barely detectable levels up to 1/16” deep was observed throughout less than 5% of the welds showing exposure at this time. Mild staining exists throughout the interior walls, beginning approximately 3” below overflow level and extends down to the floor. RECOMMENDATION(S): It is our recommendation to re-coat the interior wall panels and welds showing steel exposure using a protective coating formulated for immersion (wet contact) and having an A.N.S.I./N.S.F.61 approval for use in structure’s containing potable water and to be applied in accordance with the product manufacturer’s surface preparation and application recommendations in an effort to halt corrosion, prevent fatigue (pitting) of the wall panels and prevent further fatigue (pitting) of the welds, while providing good protection for the interior welded steel wall surfaces. Overhead The entire overhead was inspected from the water surface. These steel panels, including the welds between panels, appeared sound and remain free of obvious fatigue or failures at this time. The protective coating on these steel panels and welds appeared to have been applied uniformly and remains having good adhesion value at this time. RECOMMENDATION(S): None at this time.

Page 11: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

5

3

1

6

4

2Exterior Walls Appearing Sound Having Good Adhesion Value Of The Protective Coating And ANon-Uniform Accumulation of Mildew

Exterior Walls Appearing Sound Having Good Adhesion Value Of The Protective Coating And ANon-Uniform Accumulation of Mildew

Exterior Walls Appearing Sound Having Good Adhesion Value Of The Protective Coating And ANon-Uniform Accumulation of Mildew

Exterior Walls Appearing Sound Having Good Adhesion Value Of The Protective Coating And ANon-Uniform Accumulation of Mildew

Exterior Walls Appearing Sound Having GoodAdhesion Value Of The Protective Coating And ANon-Uniform Accumulation of Mildew

Exterior Walls Appearing Sound Having Good Adhesion Value Of The Protective Coating And ANon-Uniform Accumulation of Mildew

Page 12: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

11

9

7

12

10

8Exterior Walls Appearing Sound Having Good Adhesion Value Of The Protective Coating And ANon-Uniform Accumulation of Mildew

Exterior Walls Appearing Sound Having Good Adhesion Value Of The Protective Coating And ANon-Uniform Accumulation of Mildew

Exterior Walls Appearing Sound Having Good Adhesion Value Of The Protective Coating And ANon-Uniform Accumulation of Mildew

Exterior Walls Appearing Sound Having GoodAdhesion Value Of The Protective Coating And ANon-Uniform Accumulation of Mildew

Exterior Walls Appearing Sound Having GoodAdhesion Value Of The Protective Coating And ANon-Uniform Accumulation of Mildew

Exterior Walls Appearing Sound Having Good Adhesion Value Of The Protective Coating And ANon-Uniform Accumulation of Mildew

Page 13: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

17

15

13

18

16

14Easternmost Manway Westernmost Manway Having Sprayed Grafitti

Anchor Belt Having Good Adhesion Value Of The Protective Coating

Anchor Belt Having Good Adhesion Value Of The Protective Coating

Anchor Belt Having Good Adhesion Value Of The Protective Coating

Foundation Appearing Sound And Sealant At The Junction Where The Foundation And Tank Base Meet Having Good Adhesion Value

Page 14: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

23

21

19

24

22

20Foundation Appearing Sound And Sealant At The Junction Where The Foundation And Tank Base Meet Having Good Adhesion Value

Foundation Appearing Sound And Sealant At The Junction Where The Foundation And Tank Base Meet Having Good Adhesion Value

Ladder Extending From Ground Level Ladder, Safety Cage And Platform Having Good Adhesion Value

Ladder, Safety Cage And Platform Having Good Adhesion Value

Ladder, Safety Cage And Platform Having Good Adhesion Value

Page 15: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

29

27

25

30

28

26Overflow Weir Box And 12” Overflow Pipe Overflow Weir Box Inspection Hatch Secured With A

Lock

Lock Securing The Overflow Weir Box Inspection Hatch

Overflow Pipe Extending Away From The Tank

20’ Overflow Pipe Extension Having Mild Corrosion 20’ Overflow Pipe Extension Having Mild Corrosion

Page 16: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

35

33

31

36

34

32Outlet End Of Overflow Pipe Found Unobstructed And Screened

Roof Having Surface Corrosion And Blotch Rusting Showing Through Coating

Roof Having Surface Corrosion And Blotch Rusting Showing Through Coating

Roof Having Surface Corrosion And Blotch Rusting Showing Through Coating

Roof Having Good Adhesion Value Of The Protective Coating

Roof Having Good Adhesion Value Of The Protective Coating

Page 17: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

41

39

37

42

40

38Roof Having Good Adhesion Value Of The Protective Coating

Steel Roof Staircase Having Surface Corrosion And Blotch Rusting

Steel Roof Staircase Having Surface Corrosion And Blotch Rusting

Roof Safety Railings Having Surface Corrosion And Blotch Rusting

Roof Safety Railings Having Surface Corrosion And Blotch Rusting

Vent Cap

Page 18: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

47

45

43

48

46

44Vent Screen Open Access Hatch

Closed Access Hatch (Secured) Lock Securing Access Hatch

Layer Of Precipitate Layer Of Precipitate

Page 19: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

53

51

49

54

52

50Coating Debris (Chip/Flakes) That Remain On The Tank Floor

Coating Debris (Chip/Flakes) That Remain On The Tank Floor

Floor Having Good Adhesion Value Of The Protective Coating And Mild Staining

Floor Having Good Adhesion Value Of The Protective Coating And Mild Staining

Floor Having Good Adhesion Value Of The Protective Coating And Mild Staining

Floor Having Good Adhesion Value Of The Protective Coating And Mild Staining

Page 20: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

59

57

55

60

58

56Easternmost Manway Having Good Adhesion Value Of The Protective Coating

Westernmost Manway Having Good Adhesion Value Of The Protective Coating

Coating Blister And Steel Exposure At The Westernmost Manway

Unobstructed Influent/Effluent Pipe

Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Page 21: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

65

63

61

66

64

62Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Page 22: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

71

69

67

72

70

68Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Page 23: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

77

75

73

78

76

74Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Lower Rows Of The Interior Wall Surfaces Having Adhesion Loss of The Protective Coating, Exposed Steel And Corrosion

Interior Wall SurfacesThat Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Interior Wall Surfaces That Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Interior Wall Surfaces That Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Interior Wall Surfaces That Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Page 24: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

83

81

79

84

82

80Interior Wall Surfaces That Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Interior Wall Surfaces That Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Interior Wall Surfaces That Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Interior Wall Surfaces That Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Interior Wall Surfaces That Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Interior Wall Surfaces That Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Page 25: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

89

87

85

90

88

86Interior Wall Surfaces That Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Interior Wall Surfaces That Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Interior Wall Surfaces That Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Interior Wall Surfaces That Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Interior Wall Surfaces That Remain Having Good Adhesion Value Of The Protective Coating And Mild Staining

Overhead Having Good Adhesion Value Of The Protective Coating

Page 26: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

95

93

91

96

94

92Overhead Having Good Adhesion Value Of The Protective Coating

Overhead Having Good Adhesion Value Of The Protective Coating

Overhead Having Good Adhesion Value Of The Protective Coating

Overhead Having Good Adhesion Value Of The Protective Coating

Unobstructed Overflow Discharge From Cleaning

Page 27: INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) … · INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER

INSPECTION AND INTERIOR CLEANING (SEDIMENT REMOVAL) OF THE 280,000-GALLON WELDED STEEL WATER STORAGE TANK NORTH HAVEN WATER DEPARTMENT NORTH HAVEN, MAINE AUGUST 13, 2019 PAGE 10 Overflow The overflow consists of a 24” long by 12” tall cutout within the top wall panel, located approximately 4” below the junction of where the roof and walls meet. This overflow cutout was free of obvious obstructions at the time of this inspection. RECOMMENDATION(S): None at this time. Aesthetic Water Quality The aesthetic water quality was found to be good throughout this entire tank, allowing unlimited visibility for this inspection. CONCLUSION: It is the opinion of Underwater Solutions Inc. that this welded steel potable water storage tank appeared mostly sound and remains free of obvious leakage. ADDITONAL REMARKS/RECOMMENDATION(S): It is our recommendation to install an active mixer within this structure to prevent ice cap formation and to improve overall water quality. As always, we recommend that re-inspection and cleaning of all water storage facilities be performed in accordance with state and federal mandates, A.W.W.A. standards, and completed by an experienced and authorized inspection corporation.

___________________________________ UNDERWATER SOLUTIONS INC. Christopher A. Cole, Project Manager This report, the conclusions, recommendations and comments prepared by Underwater Solutions Inc. are based upon spot examination from readily accessible parts of the tank. Should latent defects or conditions which vary significantly from those described in the report be discovered at a later date, these should be brought to the attention of a qualified individual at that time. These comments and recommendations should be viewed as information to be used by the Owner in determining the proper course of action and not to replace a complete set of specifications. All repairs should be done in accordance with A.W.W.A. and/or other applicable standards.