23
Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North Edinburgh, EH13 9DS 23 rd March 2018 Ceiling Condition Survey Report

Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Insert Image here –

move to back

Oxgangs Primary School

60 Oxgangs Road North

Edinburgh, EH13 9DS

23rd March 2018

Ceiling Condition Survey Report

Page 2: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Ceiling Condition Survey Report – Oxgangs Primary School, 60 Oxgangs Road North, Edinburgh, EH13 9DS _____________________________________________________________________________________________________________

_______________________________________________________________________________________________________________ March 2018 EH18005

1

Ceiling Condition Survey Report Oxgangs Primary School, 60 Oxgangs Road North, Edinburgh, EH13 9DS For and on behalf of

Section Contents Page Nr 1.0 Background 2

2.0 Internal Condition Survey Report 3 – 5 3.0 Summary 6 Declaration 7 Limitations and Exclusions 7 Appendices Appendix i - Inspection Checklist Appendix ii - Survey photographs Appendix iii - Floor Plans Revision Record

Revision Date Section Changed

Changes

- 28/03/2018 - Issued

Page 3: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Ceiling Condition Survey Report – Oxgangs Primary School, 60 Oxgangs Road North, Edinburgh, EH13 9DS _____________________________________________________________________________________________________________

_______________________________________________________________________________________________________________ March 2018 EH18005

2

1.0 Background 1.1 Summers-Inman received instruction on Friday 16th March 2018 from Murdo McLeod of

The City of Edinburgh Council, to carry out a condition survey at Oxgangs Primary School, 60 Oxgangs Road North, Edinburgh EH13 9DS. Survey access was arranged for Sunday 18th March and Monday 19th March 2018.

1.2 The purpose of the survey report is to advise on the condition of the ceilings of the

property. 1.3 The subject property is situated approximately 4 miles south west of Edinburgh’s city

centre. 1.4 The property is a mixture of single and two storey buildings providing schooling facilities for

children under the age of eleven. The structure is of metal frame construction with profiled metal sheet roof, metal soffits and fascias. External wall finishes consist of brickwork and smooth render, windows are metal double glazed, and the external doors are a combination of metal with glazed panes and solid metal doors. The property has small grassed and tarmac paving areas and is surrounded by 2m high metal post and wire fence on all sides of the property.

1.5 Internally the building has mixture of suspend ceilings, the underside of the metal sheet

roofing and suspended plaster board. The internal walls are combination of solid plastered, plasterboard stud, painted blockwork and folding partitions. The flooring coverings are a mixture of carpet or vinyl finishes.

1.6 The property was constructed circa 2002. 1.7 For the purposes of this report the front elevation of the building is taken as facing north. 1.8 The survey was undertaken by Iain Macdonald BSc (Hons), Building Surveyor on Sunday

18th March and Monday 19th March 2018. Weather conditions during the inspections were sunny with occasional snowfall, with an outside temperature of approximately 0-2˚C.

1.9 The extent of our survey involved a non-disruptive inspection of the building fabric and

access above suspended ceilings was via a ladder. The roof coverings and associated elements were inspected from ground level.

Page 4: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Ceiling Condition Survey Report – Oxgangs Primary School, 60 Oxgangs Road North, Edinburgh, EH13 9DS _____________________________________________________________________________________________________________

_______________________________________________________________________________________________________________ March 2018 EH18005

3

2.0 Internal Condition Survey

The following section of the report provides details on any defects noted and the current condition of the internal building fabric of Oxgangs Primary School. The suspended ceiling and the void above the ceiling were specifically inspected, but if there were defects noted elsewhere which were of particular concern these have been identified. During the inspection it was noted that several of the defects were reoccurring within a number of the rooms throughout the school. Where the exact location of the defect is not recorded below, please reference Appendix i – Inspection Checklist for the location of the defect. Note: Please also refer to Appendix ii – Survey photographs and Appendix iii – Floor Plans, for all element references.

2.1 Support wires for ceiling grid incorrectly fitted

2.1.1 The support wires which secure the ceiling tile grid should be positioned at 1.2m intervals. The wires should also run vertically from the grid to a secure fixing above. The support wires for a section of the ceiling grid above the first-floor cloakroom have been fitted at an angle of approximately 45o and do not run vertically. (See photo 02)

2.2 No support wires to light fittings

2.2.1 Although each light fitting appeared secure within the ceiling grid, the lighting manufacturer’s details suggest that each light fitting should have support wires connecting the fitting to an independent fixing. Several light fittings housed within the suspended ceiling grid do not have this support wire. (See photo 03)

2.3 Snapped support wires to light fittings

2.3.1 As mentioned within 3.2.1, the lighting manufacturer’s details suggest that each light fitting

should have support wire connecting the fitting to an independent fixing. Several support wires had snapped and thus not securing the light fittings. (See photo 04)

2.4 Support wires for light fittings not tied with clip

2.4.1 The lighting manufacturer’s details suggest that the ends of the support wire should be held in placed with a plastic clip (see photo 05), but the support wire, to several of the lighting fittings, have been tied together without the plastic clip. (See photo 06)

2.5 Support wires for light fittings tied around water pipe

2.5.1 As previously mentioned within 3.2.1, it is suggested that each light fitting should have support wire connecting the fitting to an independent fixing. Several support wires have been tied around pipework located within the ceiling void, rather than to an independent fixture. (See photo 07)

2.6 Support wires for light fittings not tied to independent fixture

2.6.1 Several of the light fitting support wires have not been secured to an independent fixing but to an alternative support, such as cable trays/ducts. While these alternative supports are themselves secured independent of the ceiling tile grid, if the cable trays/ducts are adjusted/reconfigured there is the opportunity that the support wire for the lighting may be removed and not refixed. (See photo 08)

Page 5: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Ceiling Condition Survey Report – Oxgangs Primary School, 60 Oxgangs Road North, Edinburgh, EH13 9DS _____________________________________________________________________________________________________________

_______________________________________________________________________________________________________________ March 2018 EH18005

4

2.7 Light fitting not incorporated correctly within ceiling tile grid

2.7.1 There are isolated light fittings which are not sitting flat within the ceiling tile grid. (See

photo 09)

2.8 Loose or missing ceiling tiles

2.8.1 To ensure that a suspended ceiling tile stays ridged all ceiling tiles must be fitted within the grid, otherwise it may become unbalanced or destabilised. Various ceiling tiles, predominately half tiles to the edge of the ceiling tile grid, where not fitted correctly within the ceiling grid or are missing. (See photos 10-12)

2.9 Loose sections of ceiling tile grid

2.9.1 There are isolated sections of the ceiling tile grid with are loose and/or bent. These sections are predominately located to the edge of the ceiling tile grid. (See photos 12-15)

2.10 Debris and additional ceiling tiles located above the ceiling grid

2.10.1 In several locations throughout the school, there are additional ceiling tiles and debris located on top of the suspended ceiling. (See photo 016) These items could add additional weight to the suspended ceiling which it has not been designed for.

2.10.2 A hook, similar to the one found on a coat hanger, was hanging out from between a ceiling tile and the ceiling grid, within Room 012, Nursery.

2.11 Bowing ceiling tiles

2.11.1 In several locations, vents and speakers are housed within the ceiling tiles, and the additional weight has caused the ceiling tile to bow downwards. (See photos 22-24)

2.11.2 The brackets for a ceiling mounted speaker within Room 044, WC, are loose and resulting in the speaker not being secured correctly in position. (See photo 25)

2.12 Potential breach of fire seal

2.12.1 Within Room 047, Store, all services which transfer through the wall to the adjoining stairwell must be sealed with a fire seal. There is a metal air duct which transfers from the stair through to the store. The duct should be connected to a vent housed within the suspended ceiling, but a section of the ducting is missing. (See photo 26)

2.13 Insulation with ducting

2.13.1 Within Room 045, Corridor, glass wool insulation was noted within the air ducting, potential blocking the flow of air through the duct. (See photo 27)

2.14 Pipework not supported

2.14.1 A 110mm horizontal uPVC pipe located within the ceiling void of Room 054, WC, is resting on top of the suspended ceiling grid. The support brackets which should suspend the pipe from the roof structure have snapped. (See photo 28)

Page 6: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Ceiling Condition Survey Report – Oxgangs Primary School, 60 Oxgangs Road North, Edinburgh, EH13 9DS _____________________________________________________________________________________________________________

_______________________________________________________________________________________________________________ March 2018 EH18005

5

2.15 Loose tarpaulin around ducting penetrating through roof

2.15.1 The ducting from the large extract hood located within Room 059, Kitchen, extracts

vertically through the roof above. Where the ducting penetrates the roof, tarpaulin has been taped to the underside of the roof around the duct. Sections of the tarpaulin have come loose, resulting in it hanging within the ceiling void. (See photo 29)

2.15.2 There is loose tarpaulin within the ceiling void of Room 028, WC. Access to the ceiling void was limited and further investigation should be carried out.

2.16 Ceiling tiles fitted on an angle

2.16.1 Where ceiling tiles are not installed horizontally, it is good practise to ensure the ceiling tiles are clipped in position to ensure the tiles do not slip out. Rooms 069, Store and Rooms F024 & F026, WCs, have sections of the suspended ceiling which have been fitted at an angle and the tiles have not been secured with clips. (See photos 30-31)

2.17 Unsafe light fitting

2.17.1 The light fitting within Room 024, WC, had a cracked plastic cover and a loose bolt. (See

photo 32) 2.18 Ducting not connected

2.18.1 The black flexible ducting located within the ceiling void above Room 017, Office, was not

connected. (See photo 33)

2.18.2 The ducting for the sun tunnel located within the ceiling voids above Room 009, Meeting Room, and Room 072, Office, was not connected. (See photos 34-35)

2.18.3 The ducting located within the ceiling void above Room 027, Accessible WC, was not

connected. (See photo 36)

Page 7: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Ceiling Condition Survey Report – Oxgangs Primary School, 60 Oxgangs Road North, Edinburgh, EH13 9DS _____________________________________________________________________________________________________________

_______________________________________________________________________________________________________________ March 2018 EH18005

6

3.0 Summary

3.1 The purpose of the survey report is to advise on the condition of the ceilings within the

property.

3.2 We identified the following issues associated with the ceilings in the property:

• The suspended ceiling grid support wires were not installed correctly to a section of ceiling above a cloakroom;

• Sections of the suspended ceiling grid are loose and incorrectly fitted;

• Numerous light fittings housed within the suspended ceiling grid did not have support wires installed or installed correctly, as per the manufacturers recommendations;

• Several incorrectly fitted, missing or damaged ceiling tiles and ill-fitted light fittings within the suspended ceiling grids;

• Debris housed upon the top of the suspended ceilings; • Unsecure services and missing sections of ducting within the suspended ceiling

voids; • Unsecure sheeting around services taken through the roof within the suspended

ceiling voids;

3.3 We recommend that these issues are attended to as soon as possible.

Page 8: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Ceiling Condition Survey Report – Oxgangs Primary School, 60 Oxgangs Road North, Edinburgh, EH13 9DS _____________________________________________________________________________________________________________

_______________________________________________________________________________________________________________ March 2018 EH18005

7

Declaration

Summers-Inman Construction and Property Consultants LLP

Signed

Date 28th March 2018 Iain Macdonald BSc (Hons) Building Surveyor

Summers-Inman Construction and Property Consultants LLP

Signed Date 28th March 2018 Aynsley Cheatley BSc (Hons) MRICS CMaPS Chartered Building Surveyor Director

Limitations and Exclusions

Inspection

The extent of our survey involved a non-disruptive inspection of the ceilings within the property.

It was not possible to inspect those parts of the property which were covered, unexposed or restricted by fixtures and fittings at the time of the inspection. Therefore we are unable to guarantee that all parts are free from defect.

No inspections or tests were carried out at high level or intrusively.

Deleterious and Hazardous Materials

We have advised in our report of any concerns raised in respect of deleterious and hazardous materials during our inspection. We have not commissioned any specialist investigations or tests to ascertain the presence of deleterious or hazardous materials in the fabric of the subject property.

Liability and Confidentiality

Our report is for the sole use of The City of Edinburgh Council. The content should not be issued to or used by any third party without prior written consent from Summers-Inman, which will not be unreasonably withheld or delayed.

Page 9: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Ceiling Condition Survey Report – Oxgangs Primary School, 60 Oxgangs Road North, Edinburgh, EH13 9DS _____________________________________________________________________________________________________________

_______________________________________________________________________________________________________________ March 2018 EH18005

APPENDIX i Inspection Checklist

Page 10: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

School: Oxgangs Primary School Contractor / Representative: Summers Inman LLP

Date of Survey: 18/03/2018 - 19/03/2018 Roof Condition Survey Provided: No Access

Room

No.

Purpose of Room

Classroom \ Corridor \

Store

P

h

o

t

o

R

e

f

.

Asbestos

Register

Checked and

Cognisance

Taken

Y/N

Any Suspected

Asbestos / ACM

Materials

Y/N

Penetrations

through ceiling

for pipes \

wiring \ cabling

\fire sounders

Y/N

Type of Suspended

Ceiling

exposed grid

concealed grid

suspended

plasterboard

Room on

top floor

Y/N

Is overhead

projector

fixed to

ceiling

Y/N

Historic

Cracking

Present

Y/N

approx % of

Ceiling

with historic

cracking

0 - 100%

Fresh

Cracking

Present

Y/N

approx % of

Ceiling

with fresh

cracking

0 - 100%

Dampness

Present

Y/N

approx % of

Ceiling

with dampness

0 - 100%

Recent

Repair

Works

Y/N

approx % of

Ceiling

recently

repaired

0 - 100%

Bossing/Bul

ging of

Ceiling

Y/N

approx % of

Ceiling

with bulges

0 - 100%

Tactile Survey

Recommended

above ceiling

Y/N

Categorisation

of Cracks

1(Significant)/

2(Hairline)

Urgency of

Tactile Survey

A/B

Comments Snapped

support

wire for

recessed

lighting

No white

clip to

support

wire for

recessed

lighting

Extra ceiling

tiles stored

above

ceiling grid.

Loose

ceiling tiles

to edge of

grid

Recessed

lighting not

fitted

correctly

Check

length of

Projector's

Beam

No support

wire for

recessed

lighting

Loose

section of

ceiling grid

Secure wire

for recessed

lighting

secured

around hot

water pipe.

Secure wire

for recessed

lighting not

secured to

roof bolt

049 Classroom

2

5

2

Y N Y Exposed Grid N N N N N N N N 1

050 Classroom Y N Y Exposed Grid N N N N N N N N 1 1 1

051 Classroom

2

5

4

Y N Y Exposed Grid N N N N N N N N 1 1 1 1

052 Classroom

2

5

5

Y N Y Exposed Grid N N N N N N N N 1 1 1 1 1

037 Library

2

5

5

Y N Y Exposed Grid N N N N N N N N 1 1 1 1

038 Classroom

2

5

7

Y N Y Exposed Grid N N N N N N N N 1 1 1 1 1

039 Classroom

2

5

7

Y N Y Exposed Grid N N N N Y 1 tile N N N 1 1 1

040 Classroom

2

5

8

Y N Y Exposed Grid N Y N N Y 1 tile N N N Projector secured to ceiling grid. 1 1 1 1 1 1

042 Corridor

2

5

9

Y N Y Exposed Grid N N N N Y 2 tiles N N N 1

043 WC

2

6

0

4

-

2

Y N Y Exposed Grid N N y 1 tile N Y 2% N Y 5% N

Ceiling tile where air vent diffuser

located is bulging downwards; potential

drip from 110mm downpipe causing

tiles to be damp.

1 1 1 1

044 WC

2

6

1

7

Y N Y Exposed Grid N N N N Y 10% N N NSpeaker within ceiling tile not clipped

correctly and tile bulging downwards.1 1

047 Store & Cupboard

2

6

2

6

-

2

6

3

Y N Y Exposed Grid N N N N N N N N

Section of ducting for extract fan

missing and creating a break within fire

seal. Further investigations required for

fire seal of electrical wiring through

partition from Store to cupboard.

1 1

046 Stair & lobby Y N Y Exposed Grid N N N N N N N NReplaced ceiling tile does not have a

10mm lip to edge of tile.

056/045

/048Corridor

2

6

3

Y N Y Exposed Grid N N N N Y 10% N N N Insulation located within extract ducting 1 1 1 1 1

053 Corridor Y N Y Exposed Grid N N N N Y 1 tile N N N 1 1 1 1

054 WC Y N Y Exposed Grid N N N N Y 1 tile N N N110mm horizontal pipework not

supported from ceiling.1 1 1

055 WC Y N Y Exposed Grid N N N N N N N N Missing ceiling tile. 1 1 1

033 Corridor & Lobby Y N Y Exposed Grid N N N N N N N N 1 1 1 1 1

035 Stair

2

6

6

0

-

Y N Y

Underside of sheet

metal roof &

Exposed Grid

N N N N N N N N No access above ceiling grid. 1

015 Store Y N Y Exposed Grid N N N N N N N N 1 1 1 1

027a Office Y N Y Exposed Grid N N N N N N N N 1 1

024 Server Room Y N Y Exposed Grid N N N N N N N N Half ceiling tile missing. 1 1 1

031 Cleaners Cupboard Y N Y Exposed Grid N N N N N N N N 1 1 1

033 Corridor Y N Y

Underside of sheet

metal roof &

Exposed Grid

N N N N N N N N 1 1 1

058 Dining Room Y N Y Exposed Grid N N N N Y 1 tile N N N 1 1 1 1

057 Store

2

6

6

Y N Y Exposed Grid N N N N N N N N Loose/missing tiles. 1

059 Kitchen

2

6

6

7

-

Y N Y Exposed Grid y N N N N N N N

Polyethene sheeting where ducting for

industrial extraction unit penetrates

metal sheet roofing loose.

1 1 1

060 Store Y N Y Exposed Grid y N N N N N N N

CEILING VISUAL INSPECTION CHECK LIST

Page 1 of 3

Page 11: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Room

No.

Purpose of Room

Classroom \ Corridor \

Store

P

h

o

t

o

R

e

f

.

Asbestos

Register

Checked and

Cognisance

Taken

Y/N

Any Suspected

Asbestos / ACM

Materials

Y/N

Penetrations

through ceiling

for pipes \

wiring \ cabling

\fire sounders

Y/N

Type of Suspended

Ceiling

exposed grid

concealed grid

suspended

plasterboard

Room on

top floor

Y/N

Is overhead

projector

fixed to

ceiling

Y/N

Historic

Cracking

Present

Y/N

approx % of

Ceiling

with historic

cracking

0 - 100%

Fresh

Cracking

Present

Y/N

approx % of

Ceiling

with fresh

cracking

0 - 100%

Dampness

Present

Y/N

approx % of

Ceiling

with dampness

0 - 100%

Recent

Repair

Works

Y/N

approx % of

Ceiling

recently

repaired

0 - 100%

Bossing/Bul

ging of

Ceiling

Y/N

approx % of

Ceiling

with bulges

0 - 100%

Tactile Survey

Recommended

above ceiling

Y/N

Categorisation

of Cracks

1(Significant)/

2(Hairline)

Urgency of

Tactile Survey

A/B

Comments Snapped

support

wire for

recessed

lighting

No white

clip to

support

wire for

recessed

lighting

Extra ceiling

tiles stored

above

ceiling grid.

Loose

ceiling tiles

to edge of

grid

Recessed

lighting not

fitted

correctly

Check

length of

Projector's

Beam

No support

wire for

recessed

lighting

Loose

section of

ceiling grid

Secure wire

for recessed

lighting

secured

around hot

water pipe.

Secure wire

for recessed

lighting not

secured to

roof bolt

060a Store Y N Y Exposed Grid y N N N Y 10% N N N 1

064 Office Y N Y Exposed Grid y N N N N N N N 1

063 WC Y N Y Exposed Grid y N N N N N N N 1

057 Gym Hall

2

6

7

Y N NUnderside of sheet

metal roofy N N N N N N N

069 Store

2

6

8

5

-

2

Y N Y Exposed Grid Y N N N N N N N

Missing ceiling tiles; 1nr damaged ceiling

tile; Ceiling grid on angle and not

clipped.

1 1 1

068 Store Y N YSuspended

PlasterboardN N N N N N N N Unsecure wall mounted light switch.

066 Store Y N YSuspended

PlasterboardN N N N N N N N

026 Changing Room Y N Y Exposed Grid Y N N N y 2 tiles N N N 1 1

027 Shower Room Y N Y Exposed Grid Y N N N N N Y 1 tile NCeiling tile where air vent diffuser

located is bulging downwards1

028 WC

2

6

9

5

Y N Y Exposed Grid N N N N Y 1 tile N N N

Polythene sheet not secured above

damp stained tile. Limited access to

inspect further.

1

025 Corridor Y N Y Exposed Grid Y N N N N N N N 1 1

021 Changing Room Y N Y Exposed Grid Y N N Y 1 tile N N N N 1

022 Shower Room

2

7

0

Y N Y Exposed Grid Y N N y 1 tile N N N N 1 1

023 WC Y N Y Exposed Grid Y N N N N N N N 1

024 WC Y N Y Exposed Grid Y N N N N N N N

Screw loose from ceiling mounted light

fitting. Crack to plastic cover of light

fitting.

1

020 Classroom

2

7

8

Y N Y Exposed Grid Y N N N Y 1 tile N N N 1 1 1 1

019 Office Y N Y Exposed Grid Y N N N Y 2 tiles N N N 1 1 1

017 Office

2

7

0

Y N Y Exposed Grid Y N N N N N N NBlack flexible duct above ceiling grid not

connected.1

017 Corridor Y N Y Exposed Grid Y N N N N N N N 1 1

018 Nursery Y N Y Exposed Grid Y N N N Y 2 tiles N N N 1 1 1

012/015 Nursery

2

7

1

Y N Y Exposed Grid Y N N N Y 1 tile N N N Hook hang out from ceiling tile. 1 1 1 1

014 Store Y N Y Exposed Grid Y N N N Y 1 tile N N N 1 1 1

013 WC

2

7

1

Y N Y Exposed Grid Y N N N y 1 tile N y 1 tile NCeiling tile where air vent diffuser

located is bulging downwards; 1 1 1

010/011 Corridor

2

7

2

Y N Y Exposed Grid Y N N N Y 1 tile N N N 1 1 1 1 1

007 Nursery Y N Y Exposed Grid Y N N N N N N NCeiling mounted speakers have not

clips/bracket1 1 1 1

006 Kitchen Y N Y Exposed Grid Y N N N Y 1 tile N N N 1 1

004 WC Y N Y Exposed Grid Y N N N Y 1 tile N Y 1 tile NCeiling tile where air vent diffuser

located is bulging downwards; 1 1 1

016 Laundry Y N Y Exposed Grid Y N N N N N N N 1 1 1

009 Meeting Room

2

7

2

Y N Y Exposed Grid Y N N N N N N N Sun tunnel ducting not connected. 1 1 1

073 Staff Room Y N Y Exposed Grid Y N N N N N N N 1 1 1

070 Meeting Room

2

7

5

Y N Y Exposed Grid Y N N N Y 2 tiles N N N 1 1 1

033 Corridor Y N Y Exposed Grid Y N N N N N N N 1 1 1

005 Store Y N Y Exposed Grid Y N N N Y 2 tiles N N N 1 1 1

075 Head Teacher Office Y N Y Exposed Grid Y N N N Y 1 tile N N N 1

074 Depute Head Office Y N Y Exposed Grid Y N N N N N N N 1

Page 2 of 3

Page 12: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Room

No.

Purpose of Room

Classroom \ Corridor \

Store

P

h

o

t

o

R

e

f

.

Asbestos

Register

Checked and

Cognisance

Taken

Y/N

Any Suspected

Asbestos / ACM

Materials

Y/N

Penetrations

through ceiling

for pipes \

wiring \ cabling

\fire sounders

Y/N

Type of Suspended

Ceiling

exposed grid

concealed grid

suspended

plasterboard

Room on

top floor

Y/N

Is overhead

projector

fixed to

ceiling

Y/N

Historic

Cracking

Present

Y/N

approx % of

Ceiling

with historic

cracking

0 - 100%

Fresh

Cracking

Present

Y/N

approx % of

Ceiling

with fresh

cracking

0 - 100%

Dampness

Present

Y/N

approx % of

Ceiling

with dampness

0 - 100%

Recent

Repair

Works

Y/N

approx % of

Ceiling

recently

repaired

0 - 100%

Bossing/Bul

ging of

Ceiling

Y/N

approx % of

Ceiling

with bulges

0 - 100%

Tactile Survey

Recommended

above ceiling

Y/N

Categorisation

of Cracks

1(Significant)/

2(Hairline)

Urgency of

Tactile Survey

A/B

Comments Snapped

support

wire for

recessed

lighting

No white

clip to

support

wire for

recessed

lighting

Extra ceiling

tiles stored

above

ceiling grid.

Loose

ceiling tiles

to edge of

grid

Recessed

lighting not

fitted

correctly

Check

length of

Projector's

Beam

No support

wire for

recessed

lighting

Loose

section of

ceiling grid

Secure wire

for recessed

lighting

secured

around hot

water pipe.

Secure wire

for recessed

lighting not

secured to

roof bolt

072 Office

2

7

5

6

-

Y N Y Exposed Grid Y N N N N N N N

110mm horizontal pipework not

supported from ceiling, laying of metal

roof beam; Sun tunnel ducting not

connected.

1 1

071b WC

2

7

6

Y N Y Exposed Grid Y N N N N N N N No access above ceiling grid 1 1

071a WC Y N Y Exposed Grid Y N N N N N N N No access above ceiling grid 1

003 Office Y N Y Exposed Grid Y N N N Y 1 tile N N N 1 1

008 Office Y N Y Exposed Grid Y N N N N N N N 1

071 Accessible WC Y N Y Exposed Grid Y N N N N N N N 1 1 1

061 Store Y N Y Exposed Grid Y N N N N N N N 1 1 1

001 Entrance Y N Y Exposed Grid Y N N N N N N N 1 1

062 Plant Room Y N NUnderside of sheet

metal roofY N N N N N N N

F022 Classroom Y N NUnderside of sheet

metal roofY N N N N N N N

F021 Classroom Y N NUnderside of sheet

metal roofY N N N N N N N

F020 Classroom Y N NUnderside of sheet

metal roofY N N N N N N N 1

F019 Classroom Y N NUnderside of sheet

metal roofY N N N N N N N

F013 Classroom Y N NUnderside of sheet

metal roofY N N N N N N N 1

F012 Classroom Y N NUnderside of sheet

metal roofY N N N N N N N

F011 Classroom Y N NUnderside of sheet

metal roofY N N N N N N N

F010 Classroom Y N NUnderside of sheet

metal roofY N N N N N N N

F015 WC Y N Y Exposed Grid Y N N N Y 2 tiles N Y 3 tiles NCeiling tile where air vent diffuser

located is bulging downwards; 1 1

F014 WC Y N Y Exposed Grid Y N N N N N y 3 tiles NCeiling tile where air vent diffuser

located is bulging downwards; 1 1 1 1 1

F First Floor Main Hall

2

7

3

5

-

Y N Y

Underside of sheet

metal roof &

Exposed Grid

Y N N N N N Y 1 tile N

Ceiling tile where air vent diffuser

located is bulging downwards; Support

wires for grid not correct position

1 1 1 1

F018 First Floor Store

2

7

3

Y N Y Exposed Grid Y N N N N N N NCannot inspect above ceiling grid;

Pipework exposed at low level.

F026 WC

2

7

4

2

-

Y N Y Exposed Grid Y N N N N N Y 3 tiles N

Ceiling tile where air vent diffuser

located is bulging downwards; Ceiling at

angle at window and not clipped.

1 1

F024 WC Y N Y Exposed Grid Y N N N N N y 3 tiles N

Ceiling tile where air vent diffuser

located is bulging downwards; Ceiling at

angle at window and not clipped.

1

F027 Accessible WC Y N Y Exposed Grid Y N N N Y 1 tile N N NExtract duct above ceiling grid not

connected.1 1

F028 Cleaners Cupboard Y N Y Exposed Grid Y N N N Y 1 tile N N N

F029 Classroom Y N Y Exposed Grid Y N N N Y 1 tile N N N 1 1 1

F031 Store Y N Y Exposed Grid Y N N N N N N N 1

F030 Store Y N Y Exposed Grid Y N N N N N N N 1 1 1

F032 Store Y N NUnderside of sheet

metal roofY N N N N N N N

F003 Tutorial Room Y N Y Exposed Grid Y N N N N N N N 1 1

F002 Tutorial Room Y N Y Exposed Grid Y N N N N N N N

F001Learning Support

BaseY N Y Exposed Grid Y N N N Y 1 tile N N N 1 1

Page 3 of 3

Page 13: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Ceiling Condition Survey Report – Oxgangs Primary School, 60 Oxgangs Road North, Edinburgh, EH13 9DS _____________________________________________________________________________________________________________

_______________________________________________________________________________________________________________ March 2018 EH18005

APPENDIX ii Survey Photographs

Page 14: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Appendix ii – Survey Photographs

_____________________________________________________________________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________________ The City of Edinburgh Council March 2019 Ceiling Condition Survey Report: Oxgangs Primary School, Edinburgh EH18005

Survey Photographs – Oxgangs Primary School

Photo 01: General view of a classroom. Photo 02: Support wires for ceiling grid incorrectly

fitted Photo 03: General view of no support wire to light fitting.

Photo 04: General view of snapped support wire to light fitting.

Photo 05: The ends for a support wire for a light fitting, tied in place with a plastic clip.

Photo 06: The ends for a support wire for a light fitting, not tied with plastic clip.

Page 15: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Appendix ii – Survey Photographs

_____________________________________________________________________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________________ The City of Edinburgh Council March 2019 Ceiling Condition Survey Report: Oxgangs Primary School, Edinburgh EH18005

Survey Photographs – Oxgangs Primary School

Photo 07: Support wires for light fittings tied around water pipe.

Photo 08: Support wires for light fittings tied around cable tray.

Photo 09: Light fittings not sitting flat within the ceiling tile grid.

Photo 10: Loose ceiling tile. Photo 11: Loose ceiling tiles. Photo 12: Loose ceiling tile and missing section of

ceiling tile grid.

Page 16: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Appendix ii – Survey Photographs

_____________________________________________________________________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________________ The City of Edinburgh Council March 2019 Ceiling Condition Survey Report: Oxgangs Primary School, Edinburgh EH18005

Survey Photographs – Oxgangs Primary School

Photo 13: Loose section of ceiling tile grid.

Photo 14: Loose section of ceiling tile grid. Photo 15: Loose section of ceiling tile grid.

Photo 16: Additional ceiling tiles located above the ceiling grid.

Photo 17: Debris located above the ceiling grid. Photo 18: Debris located above the ceiling grid.

Page 17: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Appendix ii – Survey Photographs

_____________________________________________________________________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________________ The City of Edinburgh Council March 2019 Ceiling Condition Survey Report: Oxgangs Primary School, Edinburgh EH18005

Survey Photographs – Oxgangs Primary School

Photo 19: Redundant ceiling mounted projector support.

Photo 20: Redundant ceiling mounted projector support.

Photo 21: Cracked PVC electrical trucking.

Photo 22: Bowing ceiling tiles.

Photo 23: Bowing ceiling tiles Photo 24: Bowing ceiling tiles.

Page 18: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Appendix ii – Survey Photographs

_____________________________________________________________________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________________ The City of Edinburgh Council March 2019 Ceiling Condition Survey Report: Oxgangs Primary School, Edinburgh EH18005

Survey Photographs – Oxgangs Primary School

Photo 25: Speaker brackets not fitted correctly.

Photo 26: Potential breach of fire seal. Photo 27: Insulation within ducting.

Photo 28: Pipework not supported Photo 29: Loose tarpaulin around ducting

penetrating through roof. Photo 30: Ceiling tiles fitted on an angle

Page 19: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Appendix ii – Survey Photographs

_____________________________________________________________________________________________________________________________________________________________________________

_______________________________________________________________________________________________________________________________ The City of Edinburgh Council March 2019 Ceiling Condition Survey Report: Oxgangs Primary School, Edinburgh EH18005

Survey Photographs – Oxgangs Primary School

Photo 31: Ceiling tiles fitted on an angle. Photo 32: Cracked plastic cover and a loose bolt to

light fitting. Photo 33: Ducting not connected.

Photo 34: Sun tunnel ducting not connected. Photo 35: Sun tunnel ducting not connected.

Photo 36: Ducting not connected.

Page 20: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Ceiling Condition Survey Report – Oxgangs Primary School, 60 Oxgangs Road North, Edinburgh, EH13 9DS _____________________________________________________________________________________________________________

_______________________________________________________________________________________________________________ March 2018 EH18005

APPENDIX iii Floor Plans

Page 21: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North
Page 22: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
imacdonald
Rectangle
Page 23: Insert Image here – move to backbtckstorage.blob.core.windows.net/site1135/List/NewsDocs/Oxgang… · Insert Image here – move to back Oxgangs Primary School 60 Oxgangs Road North

Edinburgh

Block B, Canal Court

40 Craiglockhart Avenue

Edinburgh

EH14 1LT

Tel: 0131 455 9700

Leeds

4100 Park Approach

Thorpe Park

Leeds

LS15 8GB

Tel: 0113 212 7500

Leicester

6 Thorpe Way

Grove Park

Enderby

Leicester LE19 1SU

T: 0116 254 2774

London

30 High Street

Kingston Upon Thames

Surrey

KT1 1HL

Tel: 0208 549 8863

Newcastle

62 The Drive

Gosforth

Newcastle upon Tyne

NE3 4AR

Tel: 0191 284 1121

Stafford

Communications House Business Centre

University Court

Staffordshire Technology Park

Stafford, ST18 0ES

E-mail:

[email protected]

Website:

www.summers-inman.co.uk