Infrared Thermography Survey Prepared for: Prepared by: Henry Plunkett Qualified assistant: Henry Plunkett Date: 31 January 2020

Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: [email protected]

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermography Survey

Prepared for: Prepared by: Henry Plunkett Qualified assistant: Henry Plunkett

Date: 31 January 2020

Page 2: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

2

Section 1, Preamble:

Report Guidelines This Report of Infrared Inspection provides complete documentation of thermal patterns

detected in your in your equipment, structure or system. It uses a subjective evaluation to

help you prioritize repairs to provide the greatest return from this inspection and your

maintenance.

The Report of Infrared Inspections meets the documentation requirements of the

Infraspection Institute Standard for Infrared Inspection of Electrical Systems and Rotating

Equipment, as well as standards, practices and specifications published by ASTM, NFPA

and NETA.

How Infrared Thermography Works Infrared Imagers “see” the heat radiated from your equipment in real time, just like a video

camera sees visible light. In colour thermograms, colours in the scene are matched to the

reference bar. Colours appearing closer to the top of the reference bar indicate higher

temperatures. Colours appearing closer to the bottom of the reference bar indicate lower

temperatures.

Repairs and Priority Ratings Each thermogram is given a Subjective Repair Priority Rating which is based upon your

qualified assistant’s opinion of how critical the subject item is to the safe and profitable

operation of your overall system. The Inspection Summary section of this report explains

how to use this Subjective Repair Priority Rating to help you determine how quickly you

need to investigate and correct the potential problem. Overheating can cause premature

deterioration and costly, unplanned failure of your equipment. Overheating connectors,

conductors and components will never get better. In fact, the temperature and rate of

deterioration will increase with time. No one can predict when a failure will occur. As a

result we suggest that you use the Subjective Repair Priority Ratings as a guide but that

you investigate and take the appropriate corrective measures as soon as possible.

Page 3: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

3

A Hypothetical Fault Cycle of a “Hotspot”

The birth of a hot spot is shown at point “A”.

This hot spot can progress in many ways:

1) It can fail in a matter of hours after birth;

2) It can follow the simulated pattern as shown in the graph and fail at any point or go

indefinitely.

The only thing to keep in mind is that it will never cure itself. It will eventually FAIL.

Temperature Versus Deterioration

An investigation of hundreds of contactors has shown that many with small temperature

rises (5 to 10ºC) above ambient were seriously deteriorated and others with temperatures

of 100ºC or more had very little deterioration and vice versa.

The reason for this paradox is that excessive heating over an extended period causes

connections to arc and burn to the point where severe deterioration takes place. Arcing

causes the connector to weld to the conductor which forms a low resistance path for

Page 4: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

4

current flow. As a result, heating of the components drops and may even cease entirely for

a time. These unintentional welds are generally poor ones and are easily broken by

mechanical stress, high load or fault currents. Once such a weld separates, heating and

arcing takes place again until the connector re-welds to the conductor. Meanwhile,

disintegration continues and, if not detected by inspection, the equipment eventually fails.

Conclusion : Don’t be misled by temperature. Temperature does not necessarily

indicate the severity of a fault. Consider the importance of each faulty component

within the framework of your whole system. Which faults, when they fail, will cause

you the greatest interruption.

Qualitative Report

Please note, that unless otherwise stated this is a qualitative report. That is, we are only

concerned with the thermal patterns that have been observed, and not the actual

reported temperature. With an emissivity value to set 1.0 in the thermal imagers

computer, the temperature values serve only as a reference and do not provide an

accurate measurement of temperature. Temperature values stated are apparent

temperatures only, and as such are understated values. This means that in most cases the

temperature values will be the most conservative value and that actual temperatures may

be significantly greater.

Inspection Summary For the equipment inspected, we have recorded thermogram(s) and/or photographs to

document conditions found during our inspection. These thermograms and/or photographs

appear on the Image Pages found in section 3 of this report.

As a reference, each Image Page contains Evaluation Priority Ratings. Subjective

Evaluation Ratings are based upon the Qualified Thermographer’s opinion of the subject

item’s importance to the safe and continuous operation of the facility.

Page 5: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

5

The following risk matrix and colour coding has been developed to aid in prioritising

repairs.

Risk Matrix Qualitative Thermal Pattern observed

Low Medium

High

Extreme

Location of Thermal Exception/ Impact of Fault

House services light and power

House services AC

Tenancy Sub-mains

Main SW/ACB/ Major retailer

Page 6: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

6

Section 2, Image summary:

Glossary of Terms:

OK - No observable thermal exception. The result of “OK” indicates that no heat anomaly was found at the time of inspection. This does not guarantee that no fault is present. Circuits are required to be under load for testing to provide adequate results. While all reasonable care and effort was taken to ensure load was optimal at the time of inspection, it is not possible to have all circuits under load at the time of testing. NA – No Access. No Access could be due to site safety concerns, hazards, locks, obstacles/obstructions, or protective coverings preventing line of sight access to the components. Recommend fitting of IR transmissive windows. OFF – Circuit not in use or not running. General Fault – No thermal anomaly at time of survey, however other safety/OHS/non-compliance issue noted. Refer to section 4, for images and further details

Page 7: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

7

Below is an overall summary of the issues found, based on the risk matrix:

Survey Number

Location Equipment / Asset ID Image # General condition and

Compliance Priority

1 DB P-2 Arcade and Mall Light Time Switch

OK

2 DB P-2 Court and Down Lights

Time Switch

OK

3 DB P-2 Car Park Lighting Time

Switch

OK

4 DB P-2 Lighting Breakers 1

OK

5 DB P-2 Lighting Breakers 2 Fault detailed in Section 4,

Compliance and Condition Report below.

Refer to Section 4

6 DB P-2 Lighting Breakers 3

OK

7 DB P-2 Lighting Breakers 4

OK

8 DB P-2 Space Frame Track

Lights

OK

9 DB P-2 Lighting Breakers 5 Fault detailed in Section 4,

Compliance and Condition Report below.

Refer to Section 4

10 DB P-2 Supply to Contactor Coil

C18 DBP3

OK

11 DB P-2 Pylon Sign Time Switch

OK

12 DB P-2 Lighting Breakers 6

OK

13 DB P-2 Main Switch

OK

14 DB P-2 Logo and Signs Breakers

OK

15 DB P-2 Blank Panel

OK

16 DB P-2 Blank Panel

OK

Quantity Fault Rating Recommendations

3 Low Possible deficiency and warrants further monitoring.

2 Medium Indicates deficiency; prioritize repair.

5 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Page 8: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

8

17 DB P-2 Inside Security Lights

OK

18 DB 2 Meter Panel 1

OK

19 DB 2 Meter Panel 2

OK

20 DB 2 Meter Panel 4

OK

21 DB 2 Meter Panel 6

OK

22 DB 2 Meter Panel 8

OK

23 DB 2 Meter Panel 10

OK

24 DB 2 Meter Panel 12

OK

25 DB 2 Meter Panel 3

Ok

26 DB 2 Meter Panel 5

OK

27 DB 2 Meter Panel 7

OK

28 DB 2 Meter Panel 9

OK

29 DB 2 Meter Panel 11

OK

30 DB 2 Fuses Fault detailed in Section 4,

Compliance and Condition Report below.

Refer to Section 4

31 DB 2 Fuses 1 Fault detailed in Section 4,

Compliance and Condition Report below.

Refer to Section 4

32 DB 2 Fuses 2 IV_00297 Fault detailed in Section 4, Compliance and Condition Report below.

HIGH

33 DB 2 Fuses 3 IV_00299

HIGH

34 DB 2 Fuses 4 OK

35 DB 1 Meter Panel 1 IV_00295

LOW

36 DB 1 Meter Panel 2

OK

37 DB 1 Meter Panel 3

OK

38 DB 1 Meter Panel 4

OK

39 DB 1 Meter Panel 6

OK

40 DB 1 Meter Panel 8

OK

41 DB 1 Meter Panel 10

OK

42 DB 1 Meter Panel 12 Fault detailed in Section 4,

Compliance and Condition Refer to

Section 4

Page 9: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

9

Report below.

43 DB 1 Meter Panel 5

OK

44 DB 1 Meter Panel 7

OK

45 DB 1 Meter Panel 9

OK

46 DB 1 Meter Panel 11

OK

47 DB 1 Shop 45 Meter Fault detailed in Section 4,

Compliance and Condition Report below.

Refer to Section 4

48 DB 1 Sumo Salad

OK

49 DB 1 Fuses 1

OK

50 DB 1 Fuses 2

OK

51 DB 1 Fuses 3

OK

52 DB 1 Fuses 4

OK

53 House Services DB

P3 Blank Panel

OK

54 House Services DB

P3 PE Override Switch and

contactors

OK

55 House Services DB

P3 Power Breakers

Fault detailed in Section 4, Compliance and Condition Report below.

Refer to Section 4

56 House Services DB

P3 Lighting Breakers 1

OK

57 House Services DB

P3 Main Switch

OK

58 House Services DB

P3 Lighting Breakers 2

Fault detailed in Section 4, Compliance and Condition Report below.

Refer to Section 4

59 Tenancy DB 3 Office West Main Isolator

NA

60 Tenancy DB 3 Subway Shop

NA

61 Tenancy DB 3 DB P3 Main Isolator

NA

62 Tenancy DB 3 DB P3 Meter

OK

63 Tenancy DB 3 Tenancy 51-59 Meter

Panel

OK

64 Tenancy DB 3 Tenancy 61-69 Meter Panel

OK

65 Tenancy DB 3 Tenancy 71-79 Meter

Panel

OK

66 Tenancy DB 3 Main Switch

NA

67 Tenancy DB 3 Tenancies 51-60 Isolator

NA

Page 10: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

10

68 Tenancy DB 3 Shop 74

NA

69 Tenancy DB 3 Shop 78

NA

70 Tenancy DB 3 Tenancies 61-70 Isolator

NA

71 Tenancy DB 3 Tenancies 71-79 Isolator

NA

72 Tenancy DB 3 Cable Zone

OK

73 Tenancy DB 3 Tenancy 51-60 Breakers

OK

74 Tenancy DB 3 Tenancy 61-70 Breakers

OK

75 Tenancy DB 3 Tenancy 71-79 Breakers IV_00310

MEDIUM

76 Plant Room 5 AHU 5A Motor

OK

77 Plant Room 5 AHU 5B Motor

OK

78 Plant Room 5

Smoke Exhaust Fans Panel

Smoke Exhaust Fans

OK

79

Plant Room 5 Mechanical

Services Switch Board 5

Main Isolator

NA

80

Plant Room 5 Mechanical

Services Switch Board 5

Condenser Unit Supply Isolator

NA

81

Plant Room 5 Mechanical

Services Switch Board 5

Meter Panel

OK

82

Plant Room 5 Mechanical

Services Switch Board 5

Fuses

OK

83

Plant Room 5 Mechanical

Services Switch Board 5

Air Supply Fan Switches

Fault detailed in Section 4, Compliance and Condition Report below.

Refer to Section 4

84 Main Switchboard

2 Main Connections

OK

85 Main Switchboard

2 Cable Zone 1

OK

86 Main Switchboard

2 Cable Zone 2

OK

87 Main Switchboard

2 MSSB7 Isolator

NA

88 Main Switchboard

2 MSSB8 Isolator

NA

89 Main Switchboard

2 Ammeter Panel

NA

90 Main Switchboard

2 Smoke Exhaust Main

Switch

No load on essential services. OFF

Page 11: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

11

91 Main Switchboard

2 MSSB Meter

OK

92 Main Switchboard

2 Normal Supply Main

OK

93 Main Switchboard

2 Cable Zone 3

OK

94 Main Switchboard

2 Tenancy DB 3 Isolator

IV_00302 IV_00303

HIGH

95 Main Switchboard

2 Emergency Supply Tie to

MSB 3 Main Switch

NA

96 Main Switchboard

2 Cable Zone 4

OK

97 Main Switchboard

2 MSSB4 Isolator

OK

98 Main Switchboard

2 MSSB5 Isolator

NA

99 Plant Room 4

Smoke Exhaust Fans Panel

Smoke Exhaust Fans Panel 4

No load on essential services. OFF

100

Plant Room 4 Mechanical

Services Switchboard

Main Isolator

NA

101

Plant Room 4 Mechanical

Services Switchboard

Meter Panel

OK

102

Plant Room 4 Mechanical

Services Switchboard

MSSB 4A/4B

NA

103

Plant Room 4 Mechanical

Services Switchboard

Switch Panel

Fault detailed in Section 4, Compliance and Condition Report below.

Refer to Section 4

104

Plant Room 4 Mechanical

Services Switchboard

Fuses

OK

105 Plant Room 4 MSSB 4A/4B

Distribution Section No load on essential services.

OFF

106 Plant Room 4 MSSB 4A/4B

Control Section

OK

107 Plant Room 4 MSSB 4A/4B

Starter Section No load on essential services.

OFF

108 Plant Room 4 AHU 4A Motor IV_00304

LOW

109 Plant Room 4 AHU

4A Valve Controllers

Expansion Valve Controllers 1-3

OK

110 Plant Room 4 AHU

4A Valve Controllers

Controllers 4-6

OK

111 Plant Room 4 AHU

4B Valve Controllers

Expansion Valve Controllers 1-2

OK

112 Plant Room 4 AHU

4B Valve Controllers

Controllers 3-4

OK

Page 12: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

12

113 Plant Room 4 AHU 4C Motor

OK

113A Plant Room 4 AHU 4B Motor

OK

114 Food Hall DB Food Hall Main Switch

OK

115 Food Hall DB Meter Panel

OK

116 Food Hall DB Breakers

OK

117 Food Hall DB Cable Zone Fault detailed in Section 4,

Compliance and Condition Report below.

Refer to Section 4

118 Food Hall DB Main Switch Fault detailed in Section 4,

Compliance and Condition Report below.

Refer to Section 4

119 Food Hall DB Light and Power Breakers

OK

120 Food Hall DB AC Unit

OK

121 Food Hall DB Exhaust Fan Switches

OK

122 Plant Room 3 Plant

Room 3 DB Main Isolator

NA

123 Plant Room 3 Plant

Room 3 DB Fault Panel

OK

124 Plant Room 3 Plant

Room 3 DB Fuses

OK

125 Plant Room 3 Plant

Room 3 DB Contactors

Fault detailed in Section 4, Compliance and Condition Report below.

Refer to Section 4

126 Plant Room 3 Plant

Room 3 DB AHU 3

OK

127 Plant Room 3 Laundry DB

Laundry DB

OK

128 Plant Room 3 Laundry DB

Store Room 3 Breaker

OK

129 Plant Room 3 Laundry DB

Donut King Breaker

OK

130 Plant Room 3

Electric Pump Set Control

Electric Pump Set Control No load on essential services.

OFF

131 Plant Room 1 Plant

Room 1 DB Main Isolator

NA

132 Plant Room 1 Plant

Room 1 DB Fault Panel

OK

133 Plant Room 1 Plant

Room 1 DB Fuses

OK

134 Plant Room 1 Plant

Room 1 DB Contactors

Fault detailed in Section 4, Compliance and Condition Report below.

Refer to Section 4

135 Plant Room 1 Plant

Room 1 DB AHU 1

Fault detailed in Section 4, Compliance and Condition Report below.

Refer to Section 4

136 Plant Room 2 Plant

Room 2 DB Main Isolator

NA

Page 13: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

13

137 Plant Room 2 Plant

Room 2 DB Fault Panel

OK

138 Plant Room 2 Plant

Room 2 DB Fuses

OK

139 Plant Room 2 Plant

Room 2 DB Contactors

Fault detailed in Section 4, Compliance and Condition Report below.

Refer to Section 4

140 Plant Room 2 Plant

Room 2 DB AHU 2

OK

141 DB P1 Breakers

OK

142 DB P1 Fan Sub Board

OK

143 Main Site Meter Panel 1

OK

144 Main Site DB 1 Mall Shops Switch IV_00311

HIGH

145 Main Site Food Hall DB 1 Switch

NA

146 Main Site Light and Power Fuses

NA

147 Main Site Power Factor Switch

OK

148 Main Site DB 2 Small Shops

OK

149 Main Site Blank Panel

OK

150 Main Site Busbars

OK

151 Main Site Kmart Main Switch

NA

152 Main Site Busbars

NA

153 Main Site Woolworths Main Switch

OK

154 Main Site Busbars

OK

155 Main Site PFC Isolator

OK

156 Main Site Meter Panel 2

OK

157 Main Site Ammeter Panel

OK

158 Main Site Sumo Salad Exhaust Fan

Switch

NA

159 Main Site Food Hall DB Exhaust

Fan Switch

NA

160 Main Site Air Con AH 1

NA

161 Main Site Air Con AH 2

NA

162 Main Site Air Con AH 3

NA

Page 14: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

14

163 Main Site Kmart 1 Exhaust Fan

Switch

NA

164 Main Site Kmart 2 Exhaust Fan

Switch

NA

165 Main Site Kmart 3 Exhaust Fan

Switch

NA

166 Main Site Mall 4 Exhaust Fan

Switch

NA

167 Main Site Mall 5 Exhaust Fan

Switch

NA

168 Main Site Exhaust Fan DB

OK

169 Main Site Light and Power DB P2

OK

170 Main Site Busbars

NA

171 Main Site Sprinkler Pump Switches No load on essential services.

OFF

172 Main Site Busbars IV_00315

HIGH

173 Main Site Main Transformer Switch

1 IV_00319

HIGH

174 Main Site Main Transformer Switch

2 IV_00319

HIGH

175 West Office DB Meters, Fuses and

Breakers

OK

176 Mechanical

Services Switchboard 8

Fuses and Contactors Fault detailed in Section 4,

Compliance and Condition Report below.

Refer to Section 4

176A Plant Room 8 AHU8 Motor IV_00323

LOW

177 Mechanical

Services Switchboard 7

Fuses and Contactors Fault detailed in Section 4,

Compliance and Condition Report below.

Refer to Section 4

177A Plant Room 7 AHU7 Motor

OK

178 Main Switchboard

3 Blank Panel

OK

179 Main Switchboard

3 Emergency Supply Tie to

MSB 2

OK

180 Main Switchboard

3 East Offices Isolator

NA

181 Main Switchboard

3 Power Factor Fault

Protection

NA

182 Main Switchboard

3 Tenancies Main Isolator

NA

183 Main Switchboard

3 Tenancy Sub Meters

OK

184 Main Switchboard

3 Ammeter Panel

OK

185 Main Switchboard

3 Supermarket Meter

OK

186 Main Switchboard

3 Meter Panel

OK

Page 15: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

15

187 Main Switchboard

3 PFC Isolator

NA

188 Main Switchboard

3 MSSB 6 Smoke Exhaust

Fan Switch

No load on essential services. OK

189 Main Switchboard

3 Supermarket Main

Isolator

OK

190 Main Switchboard

3 Tenancy Breakers

Fault detailed in Section 4, Compliance and Condition Report below.

Refer to Section 4

191 Office Wing East

DB Meter and Breakers

OK

192 Western Site Main

Switch Meter Panel

OK

193 Western Site Main

Switch Fuses and Breakers

OK

194 CMO DB Breakers

OK

195 Transformer Room Light and Power DB

OK

196 Transformer Room Ammeter Panel (Heater)

OK

Page 16: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

16

Section 3, Image analysis:

DB-P2, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Arcade and

Mall Lighting

Time Switch

(#1)

Court and

Down Lights

Time Switch

(#2)

Car Park

Lighting(#3)

Lighting

Breakers 1

(#4)

Lighting

Breakers 2

(#5)

Lighting

Breakers 3

(#6)

Lighting

Breakers 4

(#7)

Space Frame

Track Lights

(#8)

Lighting

Breakers 5

(#9)

Supply to

Contactor

Coil C18 DBP3

(#10)

Pylon Sign

Time Switch

(#11)

Lighting

Breakers 6

(#12)

Inside Security

Lights (#17)

Main Switch

(#13)

Logo and Signs

Breakers (#14)

Blank Panel

(#15)

Blank Panel

(#16)

Page 17: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

17

DB 2, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

2 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

DB 2

Meter

Panel 1

(#18)

Meter

Panel 2

(#19)

Meter

Panel 3

(#25)

Meter

Panel 4

(#20)

Meter

Panel 6

(#21)

Meter

Panel 8

(#22)

Meter

Panel 10

(#23)

Fuses

(#30)

Meter

Panel 5

(#26)

Meter

Panel

12

(#24)

Meter

Panel 7

(#27)

Meter

Panel 9

(#28)

Meter

Panel 11

(#29)

Fuses 1

(#31)

Fuses 2

(#32)

Fuses 3

(#33)

Fuses 4

(#34)

IV_00297 IV_00299

Page 18: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

18

Page 19: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

19

Image numbers

IV_00297

DB/ chassis/circuits

DB 2 Survey # 32 Shop 17

Load per phase

Red White Blue 29amps N/A N/A

Voltage drop across terminals

Red White Blue

MCB rating/cable size

MCB/fuse rating Cable

Fuse

Part numbers for replacement

Additional comments

Distance 0.5mtr

Circuit is running close to capacity resulting in high chance of blowing the fuse or damaging the cable.

Suggested repairs

Consider investigating possibility of increase in circuit capacity. Pull Fuse to ensure correct fuse cartridge is fitted, and that the cable is correctly protected

LOW MEDIUM HIGH EXTREME

Page 20: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

20

Page 21: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

21

Image numbers

IV_00299

DB/ chassis/circuits

DB 2 Survey # 33 Shop 21A

Load per phase

Red White Blue 26amps N/A N/A

Voltage drop across terminals

Red White Blue

MCB rating/cable size

MCB Cable

FUSE

Part numbers for replacement

Additional comments

Distance 0.5mtr

Thermal pattern consistent with cable running at full capacity

Repair suggestions

Suggest investigating possibility of increasing circuit capacity. Pull fuse to ensure correct size cartridge is fitted, and that the cable is correctly protected.

LOW MEDIUM HIGH EXTREME

Page 22: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

22

DB 1, Summary and Images:

Quantity Fault Rating Recommendations

1 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

DB 1 Meter

Panel 1

(#35)

Meter

Panel 2

(#36)

Meter

Panel 3

(#37)

Meter

Panel 4

(#38)

Meter

Panel 6

(#39)

Meter

Panel 8

(#40)

Meter

Panel 10

(#41)

Shop

45

Meter

(#47)

Meter

Panel 5

(#43)

Meter

Panel

12

(#42)

Meter

Panel 7

(#44)

Meter

Panel 9

(#45)

Meter

Panel 11

(#46)

Fuses 1

(#49)

Fuses 2

(#50)

Fuses 3

(#51)

Fuses 4

(#52)

Sumo

Salad

(#48)

IV_00295

Page 23: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

23

Page 24: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

24

Image numbers

IV_00295

DB/ chassis/circuits

DB 1 Survey # 35 Reject Shop

Load per phase

Red White Blue 22amps 20amps 8amps

Voltage drop across terminals

Red White Blue

MCB rating/cable size

MCB/fuse rating Cable

C40 6mm2

Part numbers for replacement

Additional comments

Distance O.5mtrs

Thermal signature supports current measurements indicating an unbalance three phase circuit. The electrical installation should be balanced as far as practicable in line with standard AS/NZS 3000: 2018 Appendix C.

Repair Suggestions

Ask Tenant to balance load across all three phases by assessing power demand on appliances attached to the Red and White phases and moving them to the underutilized Blue phase.

LOW MEDIUM HIGH EXTREME

Page 25: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

25

DB P3, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

House Services DB P3

Blank Panel

(#53)

PE Override

Switch (#54)

Power

Breakers (#55)

Lighting

Breakers 1 (#56)

Main Switch

(#57)

Lighting

Breakers 2 (#58)

Page 26: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

26

Tenancy DB 3, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

1 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Tenancy DB 3

Office West

Main Isolator

(#59)

Subway Shop

81(#60)

DB P3 Main

Isolator(#61)

DB P3

Meter

(#62)

Tenancy 51-59

Meter Panel(#63)

Tenancy 61-69

Meter Panel(#64)

Tenancy 71-79

Meter Panel(#65)

Main Switch(#66)

Cable

Zone(#72)

(#67)

(#68)

(#69)

(#70)

(#71)

Tenancies 51-60

Isolator (#67)

Shop 74 (#68)

Shop 78 (#69)

Tenancies 61-70

Isolator (#70)

Tenancies 71-79

Isolator (#71)

Tenancy 51-60

Breakers(#73)

Tenancy 61-70

Breakers(#74)

Tenancy 71-79

Breakers(#75)

IV_00310

Page 27: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

27

Page 28: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

28

Image numbers

IV_00310

DB/ chassis/circuits

Tenancy DB 3 Survey # 75 Requires Clarification

Load per phase

Red White Blue 1amp 22amps 16amps

Voltage drop across terminals

Red White Blue

MCB rating/cable size

MCB/fuse rating Cable

32amp Quicklag 6mm2

Part numbers for replacement

Additional comments

Distance O.5mtrs

Thermal signature supports current measurements indicating an unbalance three phase circuit. The electrical installation should be balanced as far as practicable in line with standard AS/NZS 3000: 2018 Appendix C. White Phase is also running close to circuit limit increasing chance of blowing fuse or damaging cable.

Repair suggestions

Ask Tenant to balance load across all three phases by assessing power demand on appliances attached to the White (priority) and Blue phases and moving them to the underutilized Red phase.

LOW MEDIUM HIGH EXTREME

Page 29: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

29

Plant Room 5, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Plant Room 5

Smoke Exhaust Fans

Panel 5 (#78)

AHU 5A Motor (#76) AHU 5B Motor (#77)

Smoke Exhaust Fans

Panel 5

Mechanical Services

Switchboard 5

Air Supply Fan

Switches (#83)

Main

Isolator

(#79)

Condenser

Unit Supply

Isolator (#80)

Meter

Panel (#81)

Fuses (#82)

Page 30: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

30

Plant room 4 Main switchboard Plant room 2, Summary and

Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

1 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Main Switchboard 2

Main

Connections(#84)

Cable Zone

1(#85)

Blank Panel Cable Zone 2

(#86)

Blank Panel

Blank Panel

MSSB7 Isolator

(#87)

MSSB8 Isolator

(#88)

Ammeter Panel(#89) Smoke Exhaust Main

Switch(#90)

MSSB Meter(#91)

Normal Supply Main

Switch(#92)

Cable Zone 3

(#93)

DB3(#94)

Emergency Supply

Tie to MSB3 Main

Switch (#95)

Cable Zone 4

(#96)

MSSB4

Isolator (#97)

MSSB5

Isolator (#98)

IV_00302 and

IV_00303

Page 31: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

31

Page 32: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

32

Page 33: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

33

Image numbers

IV_00302 and IV_00303

DB/ chassis/circuits

Plant Room 4 Main Switchboard 2

Survey # 94 DB3 Main Isolator

Load per phase

Red White Blue Too dangerous to

measure Too dangerous to

measure Too dangerous to

measure

Voltage drop across terminals

Red White Blue

MCB rating/cable size

MCB/fuse rating Cable

Part numbers for replacement

Additional comments

Distance O.5mtrs

High heat signature on the Red phase may indicate the circuit is out of balance. The electrical installation should be balanced as far as practicable in line with standard AS/NZS 3000: 2018 Appendix C.

Repair suggestions

Further safe investigation into the current loads for the three phases in this circuit is warranted. This could be achieved by installing data loggers onto the other end of outgoing cables. IE: where they connect into the main switch of DB3.

LOW MEDIUM HIGH EXTREME

Page 34: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

34

Smoke Exhaust Fans

Panel 4

Plant room 4, Summary and Images:

Quantity Fault Rating Recommendations

1 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Smoke Exhaust Fans

Panel 4 (#99)

AHU 4A Motor (#108)

Mechanical Services

Switchboard 4

Switch Panel (#103)

Main

Isolator

(#100)

MSSB 4A/4B

(#102)

Meter

Panel

(#101)

Fuses (#104)

AHU 4C Motor (#113)

IV_00304

AHU 4B Motor (#113)A

Page 35: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

35

MSSB 4A/4B

Distribution Section

(#105)

Control Section

(#106)

Starter Section (#107)

AHU 4A Valve

Controllers

Expansion Valve

Controllers 1-3

(#109)

Controllers 4-6

(#110)

AHU 4B Valve

Controllers

Expansion Valve

Controllers 1-2

(#111)

Controllers 3-4

(#112)

Page 36: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

36

Page 37: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

37

Image numbers

IV_00304

DB/ chassis/circuits

Plant Room 4 Survey # 108 AHU 4A motor

Load per phase

Red White Blue N/A N/A N/A

Voltage drop across terminals

Red White Blue

MCB rating/cable size

MCB/fuse rating Cable

Part numbers for replacement

Additional comments

Distance O.5mtrs

Thermal pattern may indicate motor bearing or pulley tensioning problem.

Repair suggestions

Suggest having the motor bearing and drive pulley tension checked.

LOW MEDIUM HIGH EXTREME

Page 38: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

38

Food Hall DB, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Food Hall DB

Food Hall Main

Switch (#114)

Meter Panel (#115)

Breakers (#116)

Cable Zone (#117)

Main Switch (#118)

Light and Power

Breakers (#119)

AC Unit (#120)

Exhaust Fan Switches

(#121)

Page 39: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

39

Plant Room 3, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Plant Room 3 DB

Main Isolator (#122) Fault Panel (#123)

Fuses(#124) Contactors (#125)

AHU 3 (#126)

(#128)

Store Room 3

Breaker

Donut King

Breaker

(#129)

(#127)

Electric Pump Set Control

(#130)

Page 40: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

40

Plant Room 1, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Plant Room 1

Plant Room 1 DB

Main Isolator (#131) Fault Panel (#132)

Fuses(#133) Contactors (#134)

AHU 1 (#135)

Page 41: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

41

Plant Room 2, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Plant Room 2

Main Isolator (#136) Fault Panel (#137)

Fuses (#138) Contactors (#139)

AHU 2 (#140)

Page 42: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

42

Site Main DB, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

1 Medium Indicates deficiency; repair as time permits.

2 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Site main DB

Meter Panel 1

(#143)

(#158)

(#159)

(#160)

(#161)

(#162)

(#163)

(#164)

(#165)

(#166)

(#167)

Blank Blank

DB 1 Mall

Shops Switch

(#144)

Food Hall DB

1 Switch

(#145)

Light and Power

Fuses (#146)

Power Factor

Switch

(#147)

DB 2 Small

Shops(#148)

Blank

Panel(#149)

Busbars(#150)

Kmart Main

Switch(#151)

Sprinkler

Pump

Switches

(#171)

Woolworths

Main

Switch(#153)

Bu

sbar

s(#1

54

)

PFC

Isolator(#155)

Meter

Panel 2

(#156)

Ammeter

Panel

(#157) Exhaust Fan

DB(#168)

Light & Power

DB P2 (#169)

Busbars(#170)

Busbars(#172)

Busbars(#152)

Main

Transformer

Switch 1

(#173)

Main

Transformer

Switch 2

(#174)

Exhaust Fan Switches

Sumo Salad

(#158)

Food Hall DB

2 (#159)

Air Con AH 1

(#160)

Air Con AH 2

(#161)

Air Con AH 3

(#162)

Blank Panel Blank Panel

Kmart 1

(#163)

Kmart 2

(#164)

Kmart 3

(#165)

Mall 4

(#166)

Mall 5

(#167)

IV_00315

IV_00311

1

IV_00319

Page 43: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

43

Page 44: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

44

Image numbers

IV_00311

DB/ chassis/circuits

Site Main Switchboard Chassis # 144 Small Shops DB

Load per phase

Red White Blue Too dangerous to

measure Too dangerous to

measure Too dangerous to

measure

Voltage drop across terminals

Red White Blue

MCB rating/cable size

MCB/fuse rating Cable

Part numbers for replacement

Additional comments

Distance O.5mtrs

High heat signature on the Red phase may indicate the circuit is out of balance. The electrical installation should be balanced as far as practicable in line with standard AS/NZS 3000: 2018 Appendix C.

Repair suggestions

Further safe investigation into the current loads for the three phases in this circuit is warranted. This could be achieved by installing data loggers on the outer end of the outgoing cables, where they connect into the main switch of the small shops DB

LOW MEDIUM HIGH EXTREME

Page 45: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

45

Page 46: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

46

Image numbers

IV_00315

DB/ chassis/circuits

Site Main Switchboard Chassis # 172 Busbars

Load per phase

Red White Blue Too dangerous to

measure Too dangerous to

measure Too dangerous to

measure

Voltage drop across terminals

Red White Blue

MCB rating/cable size

MCB/fuse rating Cable

Part numbers for replacement

Additional comments

Distance O.5mtrs

Thermal pattern on Red phase may be indicative of an increased load or a loose connection. Uneven heating on busbar may be indicative of a Localised fault in ACB

Repair suggestions

Service ACB. No history of recent servicing. Install IR windows on rear of SMDB to facilitate safe thermographic surveying of rear of ACBs

LOW MEDIUM HIGH EXTREME

Page 47: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

47

Page 48: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

48

Image numbers

IV_00319

DB/ chassis/circuits

Site Main Switchboard Survey # 173 and #174 Main Transformer Switches 1 and 2

Load per phase

Red White Blue

Voltage drop across terminals

Red White Blue

MCB rating/cable size

MCB/fuse rating Cable

Part numbers for replacement

Additional comments

Distance O.5mtrs

Uneven heat patterns across the two transformers which may indicate a potential problem. ACBs have not been serviced since 2015.

Repair suggestions

Service ACBs. Fit IR windows to rear of SMDB to facilitate safe surveying of ACBs

LOW MEDIUM HIGH EXTREME

Page 49: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

49

DB P1, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

DB P1

Breakers (#141)

Fan Sub Board

(#142)

Page 50: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

50

West office and plant room 8, Summary and Images:

Quantity Fault Rating Recommendations

1 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

West Office DB

Meters, Fuses and

Breakers (#175)

Mechanical Services Switch Board 8

Fuses and Contactors

(#176)

AHU8 Motor (#176A)

IV_00323

Page 51: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

51

Page 52: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

52

Image numbers

IV_00323

DB/ chassis/circuits

Plant Room 8 Survey # 176A AHU8 Motor

Load per phase

Red White Blue

Voltage drop across terminals

Red White Blue

MCB rating/cable size

MCB/fuse rating Cable

Part numbers for replacement

Additional comments

Distance O.5mtrs

Thermal pattern indicates a possible bearing fault or incorrect pulley tension.

Repair suggestions

Suggest having the motor bearing and drive pulley tension checked.

LOW MEDIUM HIGH EXTREME

Page 53: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

53

East office and plant room 7, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Mechanical Services Switch Board 7

Fuses and Contactors

(#177)

Office Wing East DB

Meters and Breakers

(#191)

AHU7 Motor (#177A)

Page 54: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

54

Main Switch Board 3, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Main Switch Board 3

(#178)

Emergency

Supply Tie to MSB

2 (#179)

East Offices

Isolator (#180)

Power Factor

Fault Protection (#181)

Tenancies Main Isolator(#182)

Tenancy Sub Meters

(#183) Blank Panel

Ammeter Panel

(#184)

Supermarket Meter

(#185)

Meter Panel (#186)

PFC Isolator

(#187)

MSSB 6 Smoke

Exhaust Fan Switch

(#188)

Supermarket Main

Isolator (#189)

Tenancy

Breakers (#190)

Bla

nk

Pan

el

Page 55: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

55

Western Main SMDB and CMO DB, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Western Site Main Switch

Meter Panel (#189)

Fuses and Breakers

(#190)

CMO DB

CMO DB

Breakers (#191)

Page 56: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

56

Transformer Room, Summary and Images:

Quantity Fault Rating Recommendations

0 Low Possible deficiency and warrants further monitoring.

0 Medium Indicates deficiency; repair as time permits.

0 High Corrective measures required as soon as possible.

0 Extreme Corrective measures required immediately.

Light and Power DB Ammeter Panel (Heater)

#195 #196

Page 57: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

57

Section 4, Compliance and Condition report:

Fault #001 Hazard Rating: MEDIUM

DB Mechanical Services Switchboards in Plant Rooms 1 (#134, #135), 2 (#137, #139), 3 (#123, #125, #126), 4 (#103), 5 (#83), 7 (#177) and 8 (#176)

Supporting Images:

Panel (Detailed above)

Description of Fault: Access to live terminals. Compliant at time of commissioning but requires remediation.

Repair Suggestion: Install locks to doors of switchboards, or to doors of plantrooms to ensure unauthorized access cannot not be gained. Install signage.

Page 58: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

58

Fault #002 Hazard Rating: MEDIUM

DB DB 1 Supporting Images:

Panel #42

Description of Fault: Live connections on Fuse holder.

Repair Suggestion: Requires covering with blank fuse carriers (preferred) or the cables should be removed from the fuse holders and terminated in insulated connectors.

Fault #003 Hazard Rating: Medium

DB DB 2 Supporting Images:

Panel #30, #31 and #32

Description of Fault: Fuse Carriers missing.

Repair Suggestion: #30 requires 3 X RS63A blank fuse carriers. #31 requires 2 X RS63A blank fuse carriers. #32 requires 1 X RS63A blank fuse carrier.

Page 59: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

59

Fault #004 Hazard Rating: Medium

DB DB P-2 and Food Hall DB Supporting Images:

Panel DB P-2 (#5, #9), Food Hall DB (#116)

Description of Fault: Cracked insulation on Busbars increasing the risk of arc flash. Continued deterioration of this insulation will lead to a high risk of arc flashover

Repair Suggestion: Replace Busbars.

Page 60: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

60

Fault #005 Hazard Rating: LOW

DB DB P-2 Supporting Images:

Panel #5 and #9

Description of Fault: Incoming cables covered in electrical tape to indicate phase. Tape adhesion is prone to deterioration.

Repair Suggestion: Lugs should be covered with phase indicating heat shrink.

Page 61: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

61

Fault #006 Hazard Rating: LOW

DB DB P-2 Supporting Images:

Panel #9

Description of Fault: Blue Phase cable taped and used as Neutral which could cause confusion and incorrect reconnection. Non-compliant colour coding.

Repair Suggestion: Replace cable with black neutral cable.

Fault #007 Hazard Rating: MEDIUM

DB DB P-2 Supporting Images: Panel #9

Description of Fault: Three single phase circuits used as a three phase circuit which creates possibility of incomplete circuit shutdown when required.

Repair Suggestion: Investigate the piece of equipment being powered by these breakers. With a view to replacing the three single phase breakers with a single three phase breaker.

Page 62: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

62

Fault #008 Hazard Rating: High

DB DB 2 Supporting Images: Panel N/A

Description of Fault: Cable ingress not protected against fire.

Repair Suggestion: Install cover plate and fire retardant bags.

Fault #009 Hazard Rating: High

DB DB P-3 Supporting Images: Panel #55 and #58

Description of Fault: Occurrence of Eaton Quicklag RCBOs that have been recalled for safety concerns.

Repair Suggestion: The manufacturer (Eaton) should be contacted to arrange replacement of these devices. #55 – 3 X Quicklag 20 Amp RCBO #58 – 1 X Quicklag 16 Amp RCBO

Page 63: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

63

Fault #010 Hazard Rating: LOW

DB DB P-3, Main Switch Board 3 and Food Hall DB

Supporting Images:

Panel DB P-3 (#74), Main Switch Board 3 (#190), Food Hall DB (#117, #118)

Description of Fault: Loose conductors terminated with insulation tape.

Repair Suggestion: Conductors should be terminated in insulated connecters.

Page 64: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

64

Fault #011 Hazard Rating: INFORMATION ONLY

DB Main Switch Board 3 Supporting Images:

Panel #178

Description of Fault: Loose Jack chain introducing a hazard and adding no real benefit.

Repair Suggestion: Jack chain was removed.

Page 65: Infrared Thermography Survey - Vantage WestInfrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020 Mob: 0488 788 398 Email: henry@vantagewest.com.au

Infrared Thermographic Survey for Vicinity Centre, Maddington Central. 31 January 2020

Mob: 0488 788 398 Email: [email protected] EC10475

65

Review and Recommendations

• Refer to section 2 and 3 to assist in prioritising repairs which have been highlighted

by this thermographic survey.

Electrical Compliance and General Condition Report

• All issues of electrical non-compliance are detailed in section 4.

• Issues which have been highlighted, should be dealt with as promptly as possible.

Electrical Maintenance

• No evidence of recent testing and maintenance of ACB’s was noted at time of site

visit.

• A fault developing in an ACB would lead to a major loss of power

• A routine of scheduled maintenance would mitigate against this risk

• ACBs 1 and 2 were last serviced in 2015.

31 January 2020

___________________

Henry Plunkett

Managing Director Vantage West Electrical Services & Technology Mob: 0488 788 398 Email: [email protected] Web: www.vantagewest.com.au