28
Industrial Energy Management with Visual MESA at BP Lingen refinery Availability Department – BP Lingen refinery Soteica ERTC Annual Meeting – Vienna 2012

Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

  • Upload
    haquynh

  • View
    217

  • Download
    2

Embed Size (px)

Citation preview

Page 1: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Industrial Energy Management with Visual MESA at BP Lingen refinery

Availability Department – BP Lingen refinery

Soteica

ERTC Annual Meeting – Vienna ‐ 2012

Page 2: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Outline

• Introduction– BP Lingen refinery– Visual MESA

• Energy system description• Project objectives• Project schedule and model summary• Benefits• Conclusions

Page 3: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Introduction (I)

• BP Lingen refinery– One of the most complex refineries in the world– Located in North West Germany– Considered one of Europe's leading conversion refineries– In keeping with efforts to protect the environment, all of the gasoline 

and diesel fuel products are essentially free of sulphur– Refining capacity of 93 thousand barrels per day of crude oil

• Visual MESA energy management system implemented

Page 4: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Introduction (II)

Hydrogen             Fuel                Steam               Water           ElectricityUtilities Systems

External Utilities Contracts

Emissions Regulations

ProcessIndustrialSite

Real Time and “What‐if” Planning Optimizer that finds the optimal way to operate  utilities subject to contractual, environmental and operational constraints

OptimumUtilitiesOperationsReport

Measurements OptimumSet Points

KPI Monitoringand AccountingReports

Page 5: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Introduction (III)• Visual MESA is a 1st Principles Modeling and Optimization (SQP 

MINLP) program for fuels, steam, BFW, condensate, hydrogen and electrical systems, including emissions

• Fields of application:– Real Time Optimization– Monitoring, Auditing and Accounting– Engineering– Planning– Real Time Validated Energy and Emissions KPI Calculation Server

• Currently in use in more than 70 refineries and petrochemical sites

Page 6: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Energy system description

• Set of fired boilers and process furnaces burning fuel gas• Steam network with three steam pressure levels• Set of steam turbogenerators• Two cogeneration units

– Production of 50 MW of electricity from two natural gas powered gas turbines, for use on site and for sale of the excess energy

– The gas turbines have steam injection and heat recovery steam generator with postcombustion

• Different economic trade‐offs (among electricity, steam and fuel networks)

• Many challenges to operate the energy system at minimum cost, within the constraints (e.g. emissions)

Page 7: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Project Objectives

• Monitoring and reduction of the refinery's total energy costs

• Monitoring equipment performance• Balancing the various energy costs• Developing "What if" studies

Page 8: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Project Schedule

• Data collection• Software installation (August 2010)• Functional Design Specifications• Model building and optimization configuration• Training (January 2011)• Model review• Burning period• Project and model documentation (July 2011)

Page 9: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Model scope

• Steam, fuels, emissions, boiler feed water, condensates and electricity system

• Optimization Objective function:Total Energy costs = Fuels + Electricity + Other costs

(Fuel Oil/Natural Gas/LPG (Propane/Butane)/ Electricity/Water)

Page 10: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Visual MESA GUI (main view)

Page 11: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Power plant model view

Page 12: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Optimization variables• Cogeneration

– GTs loads– Steam injection to GTs– Fuel Gas to post‐combustion

• Steam production at boilers– Fuel Gas / Fuel Oil to a fired boiler– Fuel Gas to the other fired boilers

• Turbo generators management– TGs loads

• Pump swaps (steam turbines / electrical motors switches)– 6 possible switches for 40‐1.5bar steam turbines)– 36 switches 11‐1.5bar steam turbines– Condensing Turbines 

• Electricity exportation (or importation)• Natural Gas / Butane / Propane make‐up to FG system• Steam letdown and vents

Page 13: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Constraints

• Equipment  related (i.e. burners capacity)• Operational constraints• Utilities process plants demand• Contractual • Environmental 

– NOx and SO2 emissions limits– CO2 emissions (monitoring)

85 Optimization variables (54 discrete variables)29 Constraints

Page 14: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Benefits

Page 15: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Day to Day Optimization• Steam production balance • Gas Turbines loads and steam injection• Turbogenerators loads• Natural Gas / Butane / Propane make‐up to FG network

• Pump swaps• The remaining variables (for example, steam let down flow 

rates) are consequences of the changes mentioned before, being manipulated automatically by the control system

Page 16: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Energy costs reduction examples

• Natural Gas / Butane / Propane addition to FG network

• Gas Turbine loads• Pump swaps

Page 17: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Example 1: Minimization of butane addition to FG network

Butane reduction

Page 18: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Example 1 (cont): Minimization of butane addition to FG network

Energy cost reductionaround 5% on total energy cost

Butane reductionto FG networkaround 3 t/h

Delta Cost (Current minus Optimized)

Page 19: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Example 1 (cont): Effect on heaters (furnaces)

FG flow increase at a furnace(around 0.15 t/h)

Burners FG pressure(around 0.25 bar increase)

below the constraint of 1.5 bar

Page 20: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Example 2: Optimization of Gas Turbines loads

Although electricity exportation penalty increase

Gas turbine load increase operating at higher efficiency

Page 21: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Example 3: Optimization of Pump swaps

Steam vent eliminated

Page 22: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Example 3: Optimization of Pump swaps

Several pump swapsA maximum pump swaps constraint required

Economic impact of 1.4% cost reduction on total energy cost

Page 23: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Performance monitoring (equipment efficiency)

Gas turbine heat rate

Deviation

Gas turbine theoretical heat rate

Page 24: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Performance monitoring (equipment efficiency)

Fired boiler efficiency

Turbogenerator efficiency

Page 25: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

System auditing (steam imbalances)

Steam imbalance 1,5 bar header

Page 26: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Case studies

• Gas Turbine Off‐line washing evaluation• Effect of start/stop of equipment:

– Fired boilers– Turbo‐generators– Large steam condensing turbines

• Use of NG lines in fired boilers

Page 27: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Different model uses

• Client‐server model– Shift supervisors, Operators, Engineers– Optimization on shift basis

• Standalone model use– Engineering and planning studies

• Sustainability of the up to date model• Key Performance Indicators server• Instrumentation review

Page 28: Industrial Energy Management with MESA at BP Lingen … · Industrial Energy Management with ... Turbogenerator efficiency. ... ERTC_Annual_2012_BP_Soteica_vfinal.ppt [Compatibility

Conclusions

• Visual MESA implemented at BP Lingen refinery• As a result of the project, a better knowledge of utilities 

system interactions has been acquired, understanding all decision variables and the associated constraints which sometimes are hidden

• Ability to react on line to capture business opportunities to reduce energy costs and improve emissions management, getting significant energy savings