66
Industrial detectors Fire detectors for industrial risks P31.312.000en / 02.14 Chapter 6 - 1 © Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com | Product Sheet | Detecon UniVario FMX5000 IR 3-channel infrared Àame detector with three-way optics test for complete function monitoring. Very high responsivity and ¿ltering of interfrence such as sunlight and hot surfaces through intelligent evaluation algorithms UniVario FMX5000 UV Flame detector with spectral sensitivity in the ultraviolet range. High response sensitivity with monitoring area up to 676 m 2 . Interference such as cosmic radiation and thunderstorms (lightning) is ¿ltered out intelligent evaluation algorithms with integrated self-testing for monitoring the functionality (optical test). UniVario WMX5000 Heat detector with a robust stainless steel heat sensor. A microcontroller monitors the functionality and analyses data. The detector can be freely con¿gured for any application. For this, response temperatures, response classes and indices can be adjusted. Can be expanded by adding an LCD display. UniVario WMX5000 FS Heat detector for heavy-duty daily use with a robust stainless steel heat sensor rod or Àexible hose which protrudes from the enclosure. Thermoelectric sensors for response temperatures up to 850 °C (1562 °F). A microcontroller monitors the functionality and analyses data. Prominent response temperatures and all response classes can be freely con¿gured, along with rate-of-rise and static (¿xed temperature) response behaviour. Can be expanded by adding an LCD display. UniVario A family of industrial ¿re detectors based on a uniform platform. Highly variable, with a modular system for maximum adaptability. Conventional detectors are available and can be changed to analog addressable detectors by adding the communication module KMX5000 AP / KMX5000 AP Ex. To achieve the best possible protection in each individual scenario, ¿re detectors of different designs and response sensitivity are used according to the requirements of each protected site. They work indoors and outdoors; in the direct vicinity of the protected site like UniVario WMX5000, or from further a¿eld like UniVario FMX5000 UV; in clean room environments as well as in extremely dirty process conditions. Equipped internally with the very latest advanced technology, they also feature a robust and attractive enclosure design. This new generation of high-tech ¿re detectors is substantially prefabricated, is easy and quick to install and can be easily integrated into existing solutions, making them an affordable alternative to conventional systems. One major advantage of the new range is their ability to forward detector data to databases for the purposes of analysis, maintenance or statistics compilation. Variations of UniVario detectors for conventional lines or analogue addressable systems are available, well graded for different hazard areas. The UniVario detector series with state of the art technology has big advantages due to lower installation costs in analogue addressable systems and increased safety due to permanent data transfer between control panel and detectors.

Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Embed Size (px)

Citation preview

Page 1: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsFire detectors for industrial risks

P31.

312.

000e

n / 0

2.14

Chapter 6 - 1© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

UniVario FMX5000 IR

3-channel infrared ame detector with three-way optics test for complete function monitoring. Very high responsivity and ltering of interfrence such as sunlight and hot surfaces through intelligent evaluation algorithms

UniVario FMX5000 UV

Flame detector with spectral sensitivity in the ultraviolet range. High response sensitivity with monitoring area up to 676 m2. Interference such as cosmic radiation and thunderstorms (lightning) is ltered out intelligent evaluation algorithms with integrated self-testing for monitoring the functionality (optical test).

UniVario WMX5000

Heat detector with a robust stainless steel heat sensor. A microcontroller monitors the functionality and analyses data. The detector can be freely con gured for any application. For this, response temperatures, response classes and indices can be adjusted. Can be expanded by adding an LCD display.

UniVario WMX5000 FS

Heat detector for heavy-duty daily use with a robust stainless steel heat sensor rod or exible hose which protrudes from the enclosure. Thermoelectric sensors for response temperatures up to 850 °C (1562 °F). A microcontroller monitors the functionality and analyses data. Prominent response temperatures and all response classes can be freely con gured, along with rate-of-rise and static ( xed temperature) response behaviour. Can be expanded by adding an LCD display.

UniVarioA family of industrial re detectors based on a uniform platform. Highly variable, with a modular system for maximum adaptability.

Conventional detectors are available and can be changed to analog addressable detectors by adding the communication module KMX5000 AP / KMX5000 AP Ex.

To achieve the best possible protection in each individual scenario, re detectors of different designs and response sensitivity are used according to the requirements of each protected site. They work indoors and outdoors; in the direct vicinity of the protected site like UniVario WMX5000, or from further a eld like UniVario FMX5000 UV; in clean room environments as well as in extremely dirty process conditions. Equipped internally with the very latest advanced technology, they also feature a robust and attractive enclosure design. This new generation of high-tech re detectors is substantially prefabricated, is easy and quick to install and can be easily integrated into existing solutions, making them an affordable alternative to conventional systems. One major advantage of the new range is their ability to forward detector data to databases for the purposes of analysis, maintenance or statistics compilation.Variations of UniVario detectors for conventional lines or analogue addressable systems are available, well graded for different hazard areas. The UniVario detector series with state of the art technology has big advantages due to lower installation costs in analogue addressable systems and increased safety due to permanent data transfer between control panel and detectors.

Page 2: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsFire detectors for industrial risks

P31.

312.

000e

n / 0

2.14

Chapter 6 - 2© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Bracket Console Base Base 3M16 Base LCD Base+Isolator Relay module Comms module Service device

FMX5000 IR

F

FMX5000 IR HR

Bracket HR

Base HR

FMX5000 UV

F

FMX5000 UVs

F

WMX5000

W

WMX5000 FS

W

WMX5000 FS Flex

W

WMX5000 single hole

W

WMX5000 VA

F

Overview accessories UniVario

Page 3: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsFire detectors for industrial risks

P31.

312.

000e

n / 0

2.14

Chapter 6 - 3© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Ex barrier Bracket Console Base Base Ex Comms module

Comms module Ex

Service device

FMX5000 IR 3GD

F *1

FMX5000 IR Ex

F

FMX5000 UV 3GD

F *1

*1) The service device should only be used outside of the explosion hazardous zone

2G1D

3GD

3GD

Overview accessories UniVario

Page 4: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsFire detectors for industrial risks

P31.

312.

000e

n / 0

2.14

Chapter 6 - 4© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Ex barrier Bracket Console Base Base Ex Comms module

Comms module Ex

Service device

WMX5000 3GD W *1

WMX5000 Ex W

WMX5000 FS 3GD W *1

WMX5000 FS Ex W

WMX5000 FS Flex 3GD W *1

WMX5000 FS Flex Ex W

WMX5000 single hole 3GD W *1

WMX5000 single hole Ex W

*1) The service device should only be used outside of the explosion hazardous zone

3GD

2G1D

3GD

3GD

2G1D

2G1D

3GD

2G1D

Overview accessories UniVario

Page 5: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario IR fl ame detector

P31.

312.

330

- 1en

/ 02

.13

Chapter 6 - 5© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

FMX5000 IR Order no.: 907481Triple IR ame detector for the detection of typical res. Inclu-ding 3 channel optic test monitoring all functional characteri-stics of detector.Designed for use in rough industrial environments. Equipped for operation as a conventional detector.

Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.

Technical specifi cations Detection method 3 IR Sensors

Sensitivity class 1

Viewing angle 90°

Operating voltage 7.6 V - 30 V DC

Quiescent current 2.3 mA

Alarm current approx. 15 mA

Alarm indication 1 LED red

Fault indication current approx. 15 mA

Fault indication 1 LED yellow

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminium Relative humidity

(IEC721-3-3)0 to 95%

no condensation Speci cation according to EN 54 Part 10

Weight 820 g (1.8 lbs)

Dimensions 100 x 50 mm (dia. x H)3.9 x 2 inch (dia. x H)

Optional accessoriesParallel indicator LMX5000 908499Weather protection MX5000 complete 910134KMX5000 AP communication module 905883Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Bracket MX5000 904757Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

Product features• Highly reliable against false alarms, e.g. from hot sur-

faces or sunlight.• A microcontroller monitors the functionality and analyses

the recorded data. Faults can be indicated on the detector or on a separate line.

• Service interface, history memory.• Connection of remote indicator possible.• 3-channel optic test.

Approvals / marking

G 209141 0786-CPD-20784

Page 6: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario IR fl ame detector

P31.

312.

330

- 2en

/ 02

.13

Chapter 6 - 6© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

FMX5000 IR HR Art.-Nr.: 909404 Triple IR ame detector for the detection of typical res. Inclu-ding 3 channel optic test monitoring all functional characteri-stics of detector.Variante HR (high ressistance) designed for use in highly rough industrial environments such as chemical industry. Designed for operation as a conventional detector.

Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.

Optional accessoriesParallel indicator LMX5000 908499Weather protection MX5000 complete 910134KMX5000 AP communication module 905883Silicone-free design

Not included in deliveryBase UniVario MX5000 HR 909406Bracket MX5000 904757Mounting device bracked MX5000 HR 909359Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)

Product features• Highly reliable against false alarms, e.g. from hot sur-

faces or sunlight• A microcontroller monitors the functionality and analyses

the recorded data. Faults can be indicated on the detector or on a separate line

• Service interface, history memory• Connection of remote indicator possible• 3-channel optic test

Approvals / marking

G 209141 0786-CPD-20784

Technical specifi cations Detection method 3 IR Sensors

Sensitivity class 1

Viewing angle 90°

Operating voltage 7.6 V - 30 V DC

Quiescent current 2.3 mA

Alarm current approx. 15 mA

Alarm indication 1 LED red

Fault indication current approx. 15 mA

Fault indication 1 LED yellow

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminium Relative humidity

(IEC721-3-3)0 to 95%

no condensation Speci cation according to EN 54 Part 10

Weight 820 g (1.8 lbs)

Dimensions 100 x 50 mm (dia. x H)3.9 x 2 inch (dia. x H)

Page 7: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario UV fl ame detector

P31.

312.

310e

n / 0

2.13

Chapter 6 - 7© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

FMX5000 UV Order no.: 904702 UV ame detector for the detection of typical res. Including UV optic test monitoring all functional characteristics of detector.Designed for use in rough industrial environments. Designed for operation as a conventional detector.

Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.

Technical specifi cationsDetection method UV sensor

Sensitivity class 1

Viewing angle 90°

Operating voltage 7.6 V - 30 V DC

Quiescent current approx. 0.25 mA

Alarm current approx. 15 mA

Alarm indication 1 red LED

Fault indication current approx. 15 mA

Fault indication 1 yellow LED

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 10

Weight 820 g (1.8 lbs)

Dimensions 100 x 50 mm (dia. x H)3.9 x 2 inch (dia. x H)

Optional accessoriesParallel indicator 908499Weather protection MX5000 complete 910134KMX5000 AP communication module 905883Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Bracket MX5000 904757Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

Product features• Highly reliable against false alarms, e.g. from lightning

ashes or strong sunlight.• A microcontroller monitors the functionality and analyses

the recorded data. Faults can be indicated on the detector or on a separate line.

• Service interface, history memory.• Connection of remote indicator possible.

Approvals / marking

G 206132 0786-CPD-20286

Page 8: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario UV fl ame detector

P31.

312.

310e

n / 0

2.13

Chapter 6 - 8© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

FMX5000 UVs Order no.: 907375 UV ame detector for the detection of typical res. Designed for use in rough industrial environments. Designed for operation as a conventional detector.

Expansion for a detector with Loop AP protocol via KMX5000 AP communication module.

Technical specifi cationsDetection method UV sensor

Sensitivity class 1

Viewing angle 90°

Operating voltage 7.6 V - 30 V DC

Quiescent current approx. 0.25 mA

Alarm current approx. 15 mA

Alarm indication 1 red LED

Fault indication current approx. 15 mA

Fault indication 1 yellow LED

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%No condensation

Speci cation according to EN 54 Part 10

Weight 820 g (1.8 lbs)

Dimensions 100 x 50 mm (dia. x H)3.9 x 2 inch (dia. x H)

Optional accessoriesParallel indicator 908499Weather protection MX5000 complete 910134KMX5000 AP communication module 905883Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Bracket MX5000 904757Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

Product features• Highly reliable against false alarms, e.g. from lightning

ashes or strong sunlight.• A microcontroller monitors the functionality and analyses

the recorded data. Faults can be indicated on the detector or on a separate line.

• Service interface, history memory.• Connection of external signal indication possible.

Approvals / marking

G 206132 0786-CPD-20286

Page 9: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Heat detectors, standard

P31.

312.

110

- 1en

/ 02

.14

Chapter 6 - 9© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 Order no.: 905441 The WMX5000 heat detectors are designed to detect open res with rapid rise of temperature, e.g.: – Flammable liquids and gases – Highly ammable plastics. They are designed speci cally for operation in polluted industrial environments, both indoors and outdoors. In addition to static temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early re detection.Designed for operation as a conventional detector.Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.

Technical specifi cationsDetection method NTC sensor

Response classes A1, A2, B, C, indices S, R

Response temperatures 0 °C to +90 °C(+32 °F to +194 °F)

Operating voltage 7.6 V - 30 V DC

Quiescent current approx. 0.15 mA

Alarm current consumption approx. 15 mA

Alarm indication 1 red LED

Normal operation indication 1 green LED, ashingCurrent indicationFault indication approx. 15 mA

Fault indication 1 yellow LED (2nd line)

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 5

Weight 520 g (1.2 lbs)

Dimensions 130 x 84 mm (dia. x H)5.1 x 3.3 inch (dia. x H)

Optional accessoriesDetector remote indicator 801297Weather protection MX5000 complete 910134KMX5000 AP communication module 905883Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Bracket MX5000 904757Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

Product features• Robust stainless steel heat sensor, resistant against

impact and vibration.• Freely con gurable response temperatures and classes in

accordance with EN54-5, along with rate-of-rise and static responses. Con guration via DIP switches on the detector.

• Service interface, history memory.• Connection of remote indicator possible.

Approvals / marking

G 207090 0786-CPD-20280

WMX5000 CN Order no.: 909375

Version China

Technical data see Order no 905441

Approvals / marking

Page 10: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Heat detectors, standard

P31.

312.

110

- 3en

/ 02

.14

Chapter 6 - 10© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 single hole CN Order no.: 909376

Version China

Technical data see Order no 905847

Approvals / marking

UniVario WMX5000 single hole Order no.: 905847 The single hole mounted WMX5000 heat detectors are speci cally designed for use in dryer and ventilation ducts for the detection of res with rapid rise in temperature, e.g.: – Flammable liquids and gases – Highly ammable plastics. In addition to xed temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early re detection. Designed for operation as a conventional detector.Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.

Technical specifi cationsDetection method NTC sensor

Response classes A1, A2, B, C, D indices S, R

Response temperatures 0 °C to +105 °C(+32 °F to +221 °F)

Operating voltage 7.6 V - 30 V DC

Quiescent current approx. 0.15 mA

Alarm current consumption approx. 15 mA

Alarm indication 1 red LED

Normal operation indication 1 green LED, ashingCurrent indicationFault indication approx. 15 mA

Fault indication 1 yellow LED (2nd line)

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 5

Weight 580 g (1.3 lbs)

Dimensions 130 x 133 mm (dia. x H)5.1 x 5.2 inch (dia. x H)

Optional accessoriesParallel indicator 908499Weather protection MX5000 complete 910134KMX5000 AP communication module 905883Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Single hole mounting xture 800034Single hole mounting tool 800388Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

Product features• Robust stainless steel heat sensor, resistant to impact

and vibration.• Freely con gurable response temperatures and classes in

accordance with EN54-5, along with rate-of-rise and static responses. Con guration via DIP switches on the detector.

• Service interface, history memory.• Connection of remote indicator possible.

Approvals / marking

G 207090 0786-CPD-20280

Page 11: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario High temperature heat detector FS

P31.

312.

130e

n / 0

2.14

Chapter 6 - 11© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Approvals / marking

G 207091 0786-CPD-20281

Approvals / marking

WMX5000 FS 400°C (752 °F) Order no.: 905505 The WMX5000 FS high temperature heat detectors have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools.In addition to xed temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early re detection. Designed for operation as a conventional detector.Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.

Technical specifi cationsDetection method PT1000 sensor

Response classes A1, A2, B, C, D, E, F, G, indices S, R

Response temperatures 0 °C to +400 °C(+32 °F to +752 °F)

Operating voltage 7.6 V - 30 V DC

Quiescent current approx. 0.25 mA

Alarm current consumption approx. 15 mA

Alarm indication 1 red LED

Normal operation indication 1 green LED, ashingCurrent consumptionFault indication approx. 15 mA

Fault indication 1 yellow LED (2nd line)

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 5

Weight 520 to 1600 g (1.2 to 3.5 lbs)

Dimensions 130 x 150 to 1500 mm (dia. x H)5.1 x 5.9 x 59.1 inch (dia. x H)

Optional accessoriesParallel indicator 908499KMX5000 AP communication module 905883Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Single hole mounting xture 800034Single hole mounting tool 800388 Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

NoteThe desired length of the sensor rod must be speci ed in millimetres at the time of placing the order. Alternatively, xed standard rod lengths are available to choose from.

Product features• Robust stainless steel heat rod sensor• Freely con gurable response temperatures and classes

in accordance with EN54-5, along with rate-of-rise and static responses. Con guration via DIP switches on the detector.

• Service interface, history memory.• Connection of remote indicator possible.

WMX5000 FS 400 °C (752 °F) CN Order no.: 909378

Version China

Otherwise like Order no 905505

Page 12: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario High temperature heat detector FS

P31.

312.

130e

n / 0

2.14

Chapter 6 - 12© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 FS 400 °C 200 mm(752 °F 7.9 inch)

Order no.: 906401

Version with xed rod length of 200 mm (7.9 inch)

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 680 g (1.5 lbs)

Dimensions 130 x 260 mm (dia. x H)5.1 x 10.2 inch (dia. x H)

WMX5000 FS 400 °C 400 mm(752 °F 15.8 inch)

Order no.: 906402

Version with xed rod length of 400 mm (15.8 inch)

Technical specifi cations

Response temperatures 0 °C to +400 °C(+32 °F to +752 °F)

Weight 840 g (1.9 lbs)

Dimensions 130 x 460 mm (dia. x H)5.1 x 18.1 inch (dia. x H)

WMX5000 FS 400 °C 600 mm (752 °F 23.6 inch)

Order no.: 906403

Version with xed rod length of 600 mm (33.6 inch)

Technical specifi cations

Response temperatures 0 °C to +400 °C(+32 °F to +752 °F)

Weight 1000 g (2.2 lbs)

Dimensions 130 x 660 mm (dia. x H)5.1 x 26 inch (dia. x H)

Otherwise like Order no.: 905505

Otherwise like Order no.: 905505

Otherwise like Order no.: 905505

Page 13: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario High temperature heat detector FS

P31.

312.

130e

n / 0

2.14

Chapter 6 - 13© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 FS 850°C (1562 °F) Order no.: 906454 The WMX5000 FS high temperature heat detectors have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools.In addition to xed temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early re detection. Designed for operation as a conventional detector.Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.

Technical specifi cationsDetection method PT1000 sensor

Response classes A1, A2, B, C, D, E, F, G, indices S, R

Response temperatures 0 °C to +840 °C(+32 °F to +1544 °F)

Operating voltage 7.6 V - 30 V DC

Quiescent current approx. 0.35 mA

Alarm current consumption approx. 15 mA

Alarm indication 1 red LED

Normal operation indication 1 green LED, ashingCurrent consumptionFault indication approx. 15 mA

Fault indication 1 yellow LED (2nd line)

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 5

Weight 520 to 1600 g (1.2 to 3.5 lbs)

Dimensions 130 x 150 to 1500 mm (dia. x H)5.1 x 5.9 x 59.1 inch (dia. x H)

Optional accessoriesParallel indicator 908499KMX5000 AP communication module 905883

Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Single hole mounting xture 800034Single hole mounting tool 800388 Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

NoteThe desired length of the sensor rod must be speci ed in millimetres at the time of placing the order.

Approvals / marking

Product features• Robust stainless steel heat rod sensor• Freely con gurable response temperatures and classes

in accordance with EN54-5, along with rate-of-rise and static responses. Con guration via DIP switches on the detector.

• Service interface, history memory.• Connection of remote indicator possible.

Page 14: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario High temperature heat detector FS Flex

P31.

312.

150e

n / 0

1.14

Chapter 6 - 14© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Approvals / marking

G 207091 0786-CPD-20281

WMX5000 FS Flex 400°C (752 °F) Order no.: 906176 The WMX5000 FS high temperature heat detectors have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools.In addition to xed temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early re detection. Designed for operation as a conventional detector.Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.

Technical specifi cationsDetection method PT1000 sensor

Response classes A1, A2, B, C, D, E, F, G, indices S, R

Response temperatures 0 °C to +400 °C(+32 °F to +752 °F)

Operating voltage 7.6 V - 30 V DC

Quiescent current approx. 0.25 mA

Alarm current consumption approx. 15 mA

Alarm indication 1 red LED

Normal operation indication 1 green LED, ashingCurrent consumptionFault indication approx. 15 mA

Fault indication 1 yellow LED (2nd line)

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 5

Weight 520 to 1600 g (1.2 to 3.5 lbs)

Dimensions 130 x 2000 to 9000 mm (dia. x H)5.1 x 78.7 x 354.3 inch (dia. x H)

Optional accessoriesParallel indicator 908499KMX5000 AP communication module 905883

Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Holder WMX FS, from 250 °C (482 °F) to 600 °C (1112 °F) 894679 Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

NoteThe desired length of the exible sensor rod must be speci ed in metres at the time of placing the order. The sensor rod holder is designed for application temperatures of up to 250 °C (482 °F). In case of higher application temperatures, the holder WMX FS from 250 °C (482 °F) to 600°C (1112 °F) Order no. 804679 is to be used.

Product features• Robust exible stainless steel heat sensor• Freely con gurable response temperatures and classes

in accordance with EN54-5, along with rate-of-rise and static responses. Con guration via DIP switches on the detector.

• Service interface, history memory.• Connection of remote indicator possible.

Page 15: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario High temperature heat detector FS Flex

P31.

312.

150e

n / 0

1.14

Chapter 6 - 15© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Otherwise like Order no.: 906176

Otherwise like Order no.: 906176

Otherwise like Order no.: 906176

WMX5000 FS Flex 400 °C 2 m(752 °F 79 inch)

Order no.: 906404

Version with exible hose of 2 m length (79 inch)

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 680 g (1.5 lbs)

Dimensions 130 x up to 2000 mm (dia. x H)5.1 x up to 78.73 inch (dia. x H)

WMX5000 FS Flex 400 °C 6 m(752 °F 236 inch)

Order no.: 906405

Version with exible hose of 6 m length (236 inch)

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 840 g (1.9 lbs)

Dimensions 130 x up to 6000 mm (dia. x H)5.1 x up to 236.2 inch (dia. x H)

WMX5000 FS Flex 400 °C 9 m(752 °F 354 inch)

Order no.: 906406

Version with exible hose of 9 m length (354 inch)

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 1000 g (2.2 lbs)

Dimensions 130 x up to 9000 mm (dia. x H)5.1 x up to 354.3 inch (dia. x H)

Page 16: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario High temperature heat detector FS Flex

P31.

312.

150e

n / 0

1.14

Chapter 6 - 16© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 FS Flex 850°C (1562 °F) Order no.: 906455 The WMX5000 FS high temperature heat detectors have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools.In addition to xed temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early re detection. Designed for operation as a conventional detector.Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.

Technical specifi cationsDetection method PT1000 sensor

Response classes A1, A2, B, C, D, E, F, G, indices S, R

Response temperatures 0 °C to +840 °C(+32 °F to +1544 °F)

Operating voltage 7.6 V - 30 V DC

Quiescent current approx. 0.35 mA

Alarm current consumption approx. 15 mA

Alarm indication 1 red LED

Normal operation indication 1 green LED, ashingCurrent consumptionFault indication approx. 15 mA

Fault indication 1 yellow LED (2nd line)

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 5

Weight 520 to 1600 g (1.2 to 3.5 lbs)

Dimensions 130 x 2000 to 9000 mm (dia. x H)5.1 x 78.7 x 354.3 inch (dia. x H)

Approvals / marking

Product features• Robust exible stainless steel heat sensor.• Freely con gurable response temperatures and classes

in accordance with EN54-5, along with rate-of-rise and static responses. Con guration via DIP switches on the detector.

• Service interface, history memory.• Connection of remote indicator possible.

Optional accessoriesParallel indicator 908499KMX5000 AP communication module 905883Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

NoteThe desired length of the exible sensor rod must be speci ed in metres at the time of placing the order.

Page 17: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario IR fl ame detector, Ex

P31.

312.

340

- 1en

/ 01

.14

Product Sheet | Detec�on

Chapter 6 - 17© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

UniVario FMX5000 IR 3GD Order no.: 909481Triple IR ame detector for the detection of typcal res. Including 3 channel optic test monitoring all functionalties of detector.

ATEX-approved for category 3, Gas and Dust, suitable for use in Ex zones 2 and 22.The detector must not connected with a safety barrier and a blue re alarm cable.Designed for use in rough industrial environments. Equipped for operation as a conventional detector.Expansion to a detector with Loop AP protocol via KMX5000 AP communication module.

Technical specifi cations Detection method 3 IR Sensors

Sensitivity class 1

Viewing angle 90°

Operating voltage 7.6 V - 30 V DC

Quiescent current 2.3 mA

Alarm current approx. 15 mA

Alarm indication 1 LED red

Fault indication current approx. 15 mA

Fault indication 1 LED yellow

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminium Relative humidity

(IEC721-3-3)0 to 95%

no condensation Speci cation according to EN 54 Part 10

Weight 820 g (1.8 lbs)

Dimensions 100 x 50 mm (dia. x H)3.9 x 2 inch (dia. x H)

Optional accessoriesParallel indicator LMX5000 908499KMX5000 AP communication module 905883Weather protection MX5000 complete 910134Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Bracket MX5000 904757Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

NoteThe detector will be delivered with two Ex cable glands. These cable glands have to be used at the base.

Product features• Highly reliable against false alarms, e.g. from hot sur-

faces or sunlight.• A microcontroller monitors the functionality and analyses

the recorded data. Faults can be indicated on the detector or on a separate line.

• Service interface, history memory.• Connection of remote indicator possible.• 3-channel optic test.• For use in Ex zones 2 and 22, ATEX category 3 Gas/

Dust

Approvals / markingEx conformity in acc. with 94/9/EG:

x II 3G Ex nAc IIC T4x II 3D Ex tc IIIC T110°C IP65

Type examination certi cate: BVS 11 ATEX E135Ex conformity Russia in acc. with TP TC 012/2011:

1Ex ia IIC T6/T4 Gb0Ex ia IIC T6/T4 GaEx ia IIIC T95°C Da

G 209141 0786-CPD-20784

Page 18: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario IR fl ame detector, Ex

P31.

312.

340

- 1en

/ 01

.14

Product Sheet | Detec�on

Chapter 6 - 18© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

FMX5000 IR Ex Order no.: 911674 Triple IR ame detector for the detection of typical res. Including 3 channel optic test monitoring all functionalties of detector.ATEX and IECEx approved for category 2 Gas and 1, 2 Dust, suitable for use in Ex zones 1, 20 and 21.The detectors must be connected via a safety barrier. Designed for use in tough industrial environments. Equipped for operation as a conventional detector. Extension to a detector with Loop AP protocol via the KMX5000 AP Ex. communication module.

Approvals / markingEx conformity in acc. with 94/9/EG:

x II 2G Ex ia IIC T6/T4 Gbx II 1D Ex ia IIIC T95°C Da

Type examination certi cate: BVS 12 ATEX E088IECEx conformity: IECEx BVS 12.0056Ex conformity Russia in acc. with TP TC 012/2011:

1Ex ia IIC T6/T4 Gb0Ex ia IIC T6/T4 GaEx ia IIIC T95°C Da

G 209141 0786-CPD-20784

Product features• Highly reliable against false alarms, e.g. from hot sur-

faces or sunlight.• A microcontroller monitors the functionality and analyses

the recorded data. Faults can be indicated on the detector or on a separate line.

• Service interface, history memory.• Connection of remote indicator possible.• 3-channel optic test.• For use in Ex zones 1, 20 and 21, ATEX category 2

Gas/1, 2 Dust.

Optional accessoriesSafety barrier IS conventional 9 V 904991Safety barrier IS addressable 24 V 901324KMX5000 AP Ex communication module 912086Weather protection MX5000 complete 910134Silicone-free design

Not included in deliveryBase UniVario MX5000 Ex 912082Bracket MX5000 904757Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

Technical specifi cations Detection method 3 IR Sensors

Sensitivity class 1

Viewing angle 90°

Operating voltage 7.6 V - 30 V DC

Quiescent current 4.5 mA

Alarm current approx. 15 mA

Alarm indication 1 LED red

Fault indication current approx. 15 mA

Fault indication 1 LED yellow

Operating temperature -25 °C to +80 °C(-13 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminium Relative humidity

(IEC721-3-3)0 to 95%

no condensation Speci cation according to EN 54 Part 10

Weight 860 g (1.9 lbs)

Dimensions 100 x 50 mm (dia. x H)3.9 x 2 inch (dia. x H)

Page 19: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario UV fl ame detector Ex

P31.

312.

320

- 1en

/ 01

.14

Chapter 6 - 19© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

FMX5000 UV 3GD Order no.: 907267UV ame detector for detection of typical res. Designed for use in harsh industrial environments. Fitted for use as a conventional detector. The WMX5000 UV 3GD UV ame detectors are Atex appro-ved for Category 3 gas and dust and are intended for use in Ex Zones 2 and 22. Expansion to a detector with Loop AP protocol via the KMX5000 AP communications module. The ame detector features a built-in optical channel function test.

Technical specifi cations Detection method UV-Sensor

Sensitivity class 1

Viewing angle 90°

Operating voltage 7.6 V - 30 V DC

Quiscent current approx. 0.25 mA

Alarm current approx. 15 mA

Alarm indication 1 LED red

Fault indication current ca. 15 mA

Fault indication 1 LED yellow

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminium Relative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 10

Weight 820 g (1.8 lbs)

Dimensions 100 x 50 mm (DxH)3.9 x 2 inch (dia. x H)

Optional accessoriesParallel indicator LMX5000 908499KMX5000 AP communication module 905883Weather protection MX5000 complete 910134Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Bracket MX5000 904757Terminating resistor 1,8 K / 0,5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

NoteThe detector will be delivered with two Ex cable glands. These cable glands have to be used at the base.

Product features• High degree of immunity against false alarms, such as

storm lightning or strong sunlight.• Function monitoring and evaluation of measured values

by microcontroller, faults can be displayed on the detec-tor or a separate line.

• Service interface, history memory.• Connection of external display possible.• Use in Ex Zones 2 and 22 Atex Categorie 3 gas/dust.

Approvals / markingEx conformity in acc. with 94/9/EG:

x II 3G Ex nAc IIC T4x II 3D Ex tc IIIC T110°C IP65

EC type approval certi cate: BVS 11 ATEX E137Ex conformity Russia in acc. with TP TC 012/2011:

2Ex nAc IIC T4Ex tc IIIC T110°C IP65

applied fo applied fo

Page 20: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Heat detectors, Ex standard

P31.

312.

120

- 1en

/ 01

.14

Chapter 6 - 20© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 3GD Order no.: 907268 The WMX5000 3GD heat detectors are ATEX-approved for category 3, gas and dust, and are suitable for use in Ex zones 2 and 22. They are designed to detect open res with rapid rise of temperature, e.g.: – Flammable liquids and gases – Highly ammable plastics. They are designed speci cally for operation in dirty industrial environments, both indoors and outdoors. In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early re detection.Equipped for operation as a conventional detector. Extension to a detector with Loop AP protocol via the KMX5000 AP communication module.

Technical specifi cationsDetection method NTC sensor

Response classes A1, A2, B, C, indices S, R

Response temperatures 0 °C to +90 °C(+32 °F to +194 °F)

Operating voltage 7.6 V - 30 V DC

Quiescent current approx. 0.15 mA

Alarm current consumption approx. 15 mA

Alarm indication 1 red LED

Normal operation indication 1 green LED, ashingCurrent indicationFault indication approx. 15 mA

Fault indication 1 yellow LED (2nd line)

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 5

Weight 520 g (1.2 lbs)

Dimensions 130 x 84 mm (dia. x H)5.1 x 3.3 inch (dia. x H)

Optional accessoriesParallel indicator 908499KMX5000 AP communication module 905883Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Bracket MX5000 904757Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

Product features• Robust stainless steel heat sensor.• Freely con gurable response temperatures and classes

in accordance with EN54-5, along with rate-of-rise and static responses. Setting via DIP switches on the detector or SMX5000 service device.

• Service interface, history memory.• Connection of remote indicator possible.• For use in Ex zones 2 and 22, ATEX category 3 Gas/

Dust.

Approvals / markingEx conformity in acc. with 94/9/EC: x II 3G Ex nA II T4 x II 3D Ex tD A22 IP65 T110°CType examination certi cate: BVS 07 ATEX E 156Ex conformity Russia in acc. with TP TC 012/2011:

2Ex nAc IIC T4Ex tc IIIC T110°C IP65

G 207090 0786-CPD-20280

Page 21: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Heat detectors, Ex standard

P31.

312.

120

- 1en

/ 01

.14

Chapter 6 - 21© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 Ex Order no.: 912117 The WMX5000 3 Ex heat detectors are ATEX and IECEx approved for category 2 gas and 1,2 dust, and are suitable for use in Ex zones 1, 20 and 21. They are designed to detect open res with rapid rise of temperature, e.g.: – Flammable liquids and gases – Highly ammable plastics. They are designed speci cally for operation in dirty industrial environments, both indoors and outdoors. In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early re detection.Equipped for operation as a conventional detector. Extension to a detector with Loop AP protocol via the KMX5000 AP Ex communication module.

Optional accessoriesSafety barrier IS conventional 9 V 904991Safety barrier IS addressable 24 V 901324KMX5000 AP Ex communication module 912086Weather protection MX5000 complete 910134Silicone-free design

Not included in deliveryBase UniVario MX5000 Ex 912082Bracket MX5000 904757Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

Approvals / markingEx conformity in acc. with 94/9/EG:

x II 2G Ex ia IIC T6/T4 Gbx II 1D Ex ia IIIC T95°C Da

Type examination certi cate: BVS 12 ATEX E121IECEx conformity: IECEx BVS 12.0074Ex conformity Russia in acc. with TP TC 012/2011:

1Ex ia IIC T6/T4 Gb0Ex ia IIC T6/T4 GaEx ia IIIC T95°C Da

Product features• Robust stainless steel heat sensor.• Freely con gurable response temperatures and classes

in accordance with EN54-5, along with rate-of-rise and static responses. Setting via DIP switches on the detector or SMX5000 service device.

• Service interface, history memory.• Connection of remote indicator possible.• For use in Ex zones 1, 20 and 21, ATEX category 2

Gas/1, 2Dust.

Technical specifi cationsDetection method NTC sensor

Response classes A1, A2, B, C, indices S, R

Response temperatures 0 °C to +90 °C(+32 °F to +194 °F)

Operating voltage 7.6 V - 30 V DC

Quiescent current approx. 2.8 mA

Alarm current consumption approx. 15 mA

Alarm indication 1 red LED

Normal operation indication 1 green LED, ashingCurrent indicationFault indication approx. 15 mA

Fault indication 1 yellow LED (2nd line)

Operating temperature -25 °C to +80 °C(-13 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 5

Weight 520 g (1.2 lbs)

Dimensions 130 x 84 mm (dia. x H)5.1 x 3.3 inch (dia. x H)

G 207090 0786-CPD-20280

Page 22: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Heat detectors, Ex standard

P31.

312.

120

- 2en

/ 01

.14

Chapter 6 - 22© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 3GD single hole Order no.: 907269 The single hole mounted WMX5000 3GD heat detectors are ATEX-approved for category 3, gas and dust, and are suitable for use in Ex zones 2 and 22. They are speci cally suited for use in dryer and ventilation ducts for the detection of res with rapid rise in temperature, e.g.: – Flammable liquids and gases – Highly ammable plastics. In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early re detection. Equipped for operation as a conventional detector. Extension to a detector with Loop AP protocol via the KMX5000 AP communication module.

Technical specifi cationsDetection method NTC sensor

Response classes A1, A2, B, C, D, indices S, R

Response temperatures 0 °C to +105 °C(+32 °F to +221 °F)

Operating voltage 7.6 V - 30 V DC

Quiescent current approx. 0.15 mA

Alarm current consumption approx. 15 mA

Alarm indication 1 red LED

Normal operation indication 1 green LED, ashingCurrent indicationFault indication approx. 15 mA

Fault indication 1 yellow LED (2nd line)

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 5

Weight 580 g (1.3 lbs)

Dimensions 130 x 133 mm (dia. x H)5.1 x 5.2 inch (dia. x H)

Optional accessoriesParallel indicator 908499Weather protection MX5000 complete 910134KMX5000 AP communication module 905883Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Single hole mounting xture 800034Single hole mounting tool 800388Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Line cross-section max. 2.5 mm2 (0.004 square inch)

Product features• Robust stainless steel heat sensor, resistant against

impact and vibration.• Freely con gurable response temperatures and classes

in accordance with EN54-5, along with rate-of-rise and static responses. Con guration via DIP switches on the detector or SMX5000 service device.

• Service interface, history memory.• Connection of remote indicator possible.• For use in Ex zones 2 and 22, ATEX category 3, Gas/

Dust.

Approvals / markingEx conformity in acc. with 94/9/EC: x II 3G Ex nA II T4 x II 3D Ex tD A22 IP65 T110°CType examination certi cate: BVS 07 ATEX E 156Ex conformity Russia in acc. with TP TC 012/2011:

2Ex nAc IIC T4Ex tc IIIC T110°C IP65

G 297090 0786-CPD-20280

Page 23: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Heat detectors, Ex standard

P31.

312.

120

- 2en

/ 01

.14

Chapter 6 - 23© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 Ex single hole Order no.: 912118 The single hole mounted WMX5000 Ex heat detectors are ATEX-approved for category 2, gas and 1, 2 dust, and are suitable for use in Ex zones 1, 20 and 21. They are speci cally suited for use in dryer and ventilation ducts for the detection of res with rapid rise in temperature, e.g.: – Flammable liquids and gases – Highly ammable plastics. In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early re detection. Equipped for operation as a conventional detector. Extension to a detector with Loop AP protocol via the KMX5000 AP Ex communication module.

Technical specifi cationsDetection method NTC sensor

Response classes A1, A2, B, C, D, indices S, R

Response temperatures 0 °C to +105 °C(+32 °F to +221 °F)

Operating voltage 7.6 V - 28 V DC

Quiescent current approx. 3.0 mA

Alarm current consumption approx. 15 mA

Alarm indication 1 red LED

Normal operation indication 1 green LED, ashingCurrent indicationFault indication approx. 15 mA

Fault indication 1 yellow LED (2nd line)

Operating temperature -25 °C to +80 °C(-13 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 5

Weight 580 g (1.3 lbs)

Dimensions 130 x 133 mm (dia. x H)5.1 x 5.2 inch (dia. x H)

Optional accessoriesSafety barrier IS conventional 9 V 904991Safety barrier IS addressable 24 V 901324KMX5000 AP Ex communication module 912086Silicone-free design

Not included in deliveryBase UniVario MX5000 Ex 912082Single hole mounting xture 800034Single hole mounting tool 800388Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Line cross-section max. 2.5 mm2 (0.004 square inch)

Product features• Robust stainless steel heat sensor, resistant against

impact and vibration.• Freely con gurable response temperatures and classes

in accordance with EN54-5, along with rate-of-rise and static responses. Con guration via DIP switches on the detector or SMX5000 service device.

• Service interface, history memory.• Connection of remote indicator possible.• For use in Ex zones 1, 20 and 21, ATEX category 2, Gas/

1, 2 Dust.

Approvals / markingEx conformity in acc. with 94/9/EG:

x II 2G Ex ia IIC T6/T4 Gbx II 1D Ex ia IIIC T95°C Da

Type examination certi cate: BVS 12 ATEX E121IECEx conformity: IECEx BVS 12.0074Ex conformity Russia in acc. with TP TC 012/2011:

1Ex ia IIC T6/T4 Gb0Ex ia IIC T6/T4 GaEx ia IIIC T95°C Da

G 207090 0786-CPD-20280

Page 24: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario High temperature heat detector FS, Ex

P31.

312.

140e

n / 0

1.14

Chapter 6 - 24© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 FS 3GD 400°C (752 °F) Order no.: 907270 The WMX5000 FS 3GD high temperature heat detectors are ATEX-approved for category 3, gas and dust, and are suitable for use in Ex zones 2 and 22. They have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools.In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early re detection.Equipped for operation as a conventional detector. Extension to a detector with Loop AP protocol via the KMX5000 AP communication module.

Technical specifi cationsDetection method PT1000 sensor

Response classes A1, A2, B, C, D, E, F, G, indices S, R

Response temperatures 0 °C to +400 °C(+32 °F to +752 °F)

Operating voltage 7.6 V - 30 V DC

Quiescent current approx. 0.25 mA

Alarm current consumption approx. 15 mA

Alarm indication 1 red LED

Normal operation indication 1 green LED, ashingCurrent consumptionFault indication approx. 15 mA

Fault indication 1 yellow LED (2nd line)

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 5

Weight 520 to 1600 g (1.2 to 3.5 lbs)

Dimensions 130 x 150 to 1500 mm (dia. x H)5.1 x 5.9 to 59.1 inch (dia. x H)

Optional accessoriesParallel indicator 908499KMX5000 AP communication module 905883Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Single hole mounting xture 800034Single hole mounting tool 800388 Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

NoteThe desired length of the sensor rod must be speci ed in millimetres at the time of placing the order. Alternatively, xed standard rod lengths are available to choose from.The detector will be delivered with two Ex cable glands. These cable glands have to be used at the base.

Product features• Robust stainless steel heat rod sensor.• Freely con gurable response temperatures and classes

in accordance with EN54-5, along with rate-of-rise and static responses. Con guration via DIP switches on the detector or SMX5000 service device.

• Service interface, history memory.• Connection of remote indicator possible.• For use in Ex zones 2 and 22, Atex category 3, Gas/Dust.

Approvals / markingEx conformity in acc. with 94/9/EC: x II 3G Ex nA II T4 x II 3D Ex tD A22 IP65 T110°CType examination certi cate: BVS 07 ATEX E 157Ex conformity Russia in acc. with TP TC 012/2011:

2Ex nAc IIC T4Ex tc IIIC T110°C IP65

G 207091 0786-CPD-20281

Page 25: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario High temperature heat detector FS, Ex

P31.

312.

140e

n / 0

1.14

Chapter 6 - 25© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 FS 3GD 400 °C 200 mm(752 °F 7.9 inch)

Order no.: 907281

With xed rod length of 200 mm (7.9 inch).

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 680 g (1.5 lbs)

Dimensions 130 x 260 mm (dia. x H)5.1 x 10.2 inch (dia. x H)

WMX5000 FS 3GD 400 °C 400 mm(752 °F 15.8 inch)

Order no.: 907282

With xed rod length of 400 mm (15.8 inch).

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 840 g (1.9 lbs)

Dimensions 130 x 460 mm (dia. x H)5.1 x 18.1 inch (dia. x H)

WMX5000 FS 3GD 400 °C 600 mm(752 °F 23.6 inch)

Order no.: 907283

With xed rod length of 600 mm (23.6 inch).

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 1000 g (2.2 lbs)

Dimensions 130 x 660 mm (dia. x H)5.1 x 26 inch (dia. x H)

Otherwise like Order no.: 907270

Otherwise like Order no.: 907270

Otherwise like Order no.: 907270

Page 26: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario High temperature heat detector FS, Ex

P31.

312.

140e

n / 0

1.14

Chapter 6 - 26© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 FS Ex 400°C Order no.: 912108

Approvals / markingEx conformity in acc. with 94/9/EC:

x II 2G Ex ia IIC T6/T4 Gbx II 1D Ex ia IIIC T95°C Da

Type examination certi cate: BVS 12 ATEX E120IECEx conformity: IECEx BVS 12.0073Ex conformity Russia in acc. with TP TC 012/2011:

1Ex ia IIC T6/T4 Gb0Ex ia IIC T6/T4 GaEx ia IIIC T95°C Da

The WMX5000 FS Ex high temperature heat detectors are ATEX- and IEC approved for category 2 gas and 1, 2 dust, and are suitable for use in Ex zones 1, 20 and 21. They have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools.In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early re detection.Equipped for operation as a conventional detector. Extension to a detector with Loop AP protocol via the KMX5000 AP Ex communication module.

Product features• Robust stainless steel heat rod sensor.• Freely con gurable response temperatures and classes

in accordance with EN54-5, along with rate-of-rise and static responses. Con guration via DIP switches on the detector or SMX5000 service device.

• Service interface, history memory.• Connection of remote indicator possible.• For use in Ex zones 1, 20 and 21, Atex category 3 Gas/

1, 2 Dust.

Optional accessoriesSafety barrier IS conventional 9 V 904991Safety barrier IS addressable 24 V 901324KMX5000 AP Ex communication module 912086Weather protection MX5000 complete 910134Silicone-free design

Not included in deliveryBase UniVario MX5000 Ex 912082Single hole mounting xture 800034Single hole mounting tool 800388 Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

NoteThe desired length of the sensor rod must be speci ed in millimetres at the time of placing the order. Alternatively, xed standard rod lengths are available to choose from.

Technical specifi cationsDetection method PT1000 sensor

Response classes A1, A2, B, C, D, E, F, G, indices S, R

Response temperatures 0 °C to +400 °C(+32 °F to +752 °F)

Operating voltage 7.6 V - 30 V DC

Quiescent current approx. 2.8 mA

Alarm current consumption approx. 15 mA

Alarm indication 1 red LED

Normal operation indication 1 green LED, ashingCurrent consumptionFault indication approx. 15 mA

Fault indication 1 yellow LED (2nd line)

Operating temperature -25 °C to +80 °C(-13 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 5

Weight 520 to 1600 g (1.2 to 3.5 lbs)

Dimensions 130 x 150 to 1500 mm (dia. x H)5.1 x 5.9 to 59.1 inch (dia. x H)

G 207091 0786-CPD-20281

Page 27: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario High temperature heat detector FS, Ex

P31.

312.

140e

n / 0

1.14

Chapter 6 - 27© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 FS Ex 400 °C 200 mm(752 °F 7.9 inch)

Order no.: 912110

WMX5000 FS Ex 400 °C 400 mm(752 °F 15.8 inch)

Order no.: 912111

WMX5000 FS Ex 400 °C 600 mm (752 °F 23.6 inch)

Order no.: 912112

With xed rod length of 200 mm (7.9 inch).

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 680 g (1.5 lbs)

Dimensions 130 x 260 mm (dia. x H)5.1 x 10.2 inch (dia. x H)

With xed rod length of 400 mm (15.8 inch).

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 840 g (1.9 lbs)

Dimensions 130 x 460 mm (dia. x H)5.1 x 18.1 inch (dia. x H)

With xed rod length of 600 mm (23.6 inch).

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 1000 g (2.2 lbs)

Dimensions 130 x 660 mm (dia. x H)5.1 x 26 inch (dia. x H)

Otherwise like Order no.: 912108

Otherwise like Order no.: 912108

Otherwise like Order no.: 912108

Page 28: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario High temperature heat detector FS Flex, Ex

P31.

312.

160e

n / 0

2.14

Chapter 6 - 28© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 FS Flex 3GD 400°C (752 °F) Order no.: 907284 The WMX5000 FS 3GD high temperature heat detectors are ATEX-approved for category 3, gas and dust, and are suitable for use in Ex zones 2 and 22. They have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools.In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early re detection. Designed for operation as a conventional detector.Expansion to a detector with Loop AP protocol via the KMX5000 AP communications module.

Technical specifi cationsDetection method PT1000 sensor

Response classes A1, A2, B, C, D, E, F, G, indices S, R

Response temperatures 0 °C to +400 °C(+32 °F to +752 °F)

Operating voltage 7.6 V - 30 V DC

Quiescent current approx. 0.25 mA

Alarm current consumption approx. 15 mA

Alarm indication 1 red LED

Normal operation indication 1 green LED, ashingCurrent consumptionFault indication approx. 15 mA

Fault indication 1 yellow LED (2nd line)

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%no condensation

Speci cation according to EN 54 Part 5

Weight 520 to 1600 g (1.2 to7.5 lbs)

Dimensions 130 x 2000 to 9000 mm (dia. x H)5.1 x 78.7 x 354.3 inch (dia. x H)

Optional accessoriesParallel indicator 908499KMX5000 AP communication module 905883Silicone-free design

Not included in deliveryBase UniVario MX5000 904701Holder WMX FS, from 250 °C (482 °F) to 600 °C (1112 °F) 894679 Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

NoteThe desired length of the exible sensor must be speci ed in metres at the time of placing the order. The sensor rod holder is designed for operation temperatures of up to 250 °C (482 °F). For higher operation temperatures, the WMX FS holder from 250 °C (482 °F) to 600 °C (1112 °F) Order no. 894679 is to be used.The detector will be delivered with two Ex cable glands. These cable glands have to be used at the base.

Product features• Robust exible stainless steel heat sensor.• Freely con gurable response temperatures and classes

in accordance with EN54-5, along with rate-of-rise and static responses. Con guration via DIP switches on the detector or SMX5000 service device.

• Service interface, history memory.• Connection of remote indicator possible.• For use in Ex zones 2 and 22, Atex category 3, Gas/Dust.

Approvals / markingEx conformity in acc. with 94/9/EC: x II 3G Ex nA II T4 x II 3D Ex tD A22 IP65 T110°CType examination certi cate: BVS 07 ATEX E 157Ex conformity Russia in acc. with TP TC 012/2011:

2Ex nAc IIC T4Ex tc IIIC T110°C IP65

G 207091 0786-CPD-20281

Page 29: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario High temperature heat detector FS Flex, Ex

P31.

312.

160e

n / 0

2.14

Chapter 6 - 29© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Approvals / marking

WMX5000 FS Flex 3GD 400 °C 2 m(752 °F 79 inch)

Order no.: 907285

Version with exible hose of 2 m length (79 inch).

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 680 g (1.5 lbs)

Dimensions 130 x up to 2000 mm (dia. x H)5.1 x up to 78.73 inch (dia. x H)

WMX5000 FS Flex 3GD 400 °C 6 m(752 °F 236 inch)

Order no.: 907286

Version with exible hose of 6 m length (236 inch).

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 840 g (1.9 lbs)

Dimensions 130 x up to 6000 mm (dia. x H)5.1 x up to 236.2 inch (dia. x H)

WMX5000 FS Flex 3GD 400 °C 9 m(752 °F 354 inch)

Order no.: 907287

Version with exible hose of 9 m length (354 inch).

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 1000 g (2.2 lbs)

Dimensions 130 x up to 9000 mm (dia. x H)5.1 x up to 354.3 inch (dia. x H)

Otherwise like Order no.: 907284

Otherwise like Order no.: 907284

Otherwise like Order no.: 907284

WMX5000 FS Flex 3GD 400 °C (752 °F) CN

Order no.: 909387

Version China

Otherwise like Order no.: 907284

Page 30: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario High temperature heat detector FS Flex, Ex

P31.

312.

160e

n / 0

2.14

Chapter 6 - 30© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 FS Flex Ex 400°C Order no.: 912113

Product features• Robust exible stainless steel heat sensor.• Freely con gurable response temperatures and classes

in accordance with EN54-5, along with rate-of-rise and static responses. Con guration via DIP switches on the detector or SMX5000 service device.

• Service interface, history memory.• For use in Ex zones 1, 20 and 21, Atex category 2,

Gas/1,2 Dust.

Approvals / markingEx conformity in acc. with 94/9/EG:

x II 2G Ex ia IIC T6/T4 Gbx II 1D Ex ia IIIC T95°C Da

Type examination certi cate: BVS 12 ATEX E120IECEx conformity: IECEx BVS 12.0073Ex conformity Russia in acc. with TP TC 012/2011:

1Ex ia IIC T6/T4 Gb0Ex ia IIC T6/T4 GaEx ia IIIC T95°C Da

G 207091 0786-CPD-20281

The WMX5000 FS Ex high temperature heat detectors are ATEX and IEC approved for category 2 gas and 1, 2 dust, and are suitable for use in Ex zones 1, 20 and 21. They have been specially designed for operation in industrial environments with aggressive media and very high application temperatures in the monitoring area. For example in exhaust ducts, engine test stands or machine tools.In addition to stated temperature detection, rapid rises in temperature can also be registered by the rate-of-rise method, for early re detection. Designed for operation as a conventional detector.Expansion to a detector with Loop AP protocol via the KMX5000 AP Ex communications module.

Optional accessoriesSafety barrier IS conventional 9 V 904991Safety barrier IS addressable 24 V 901324KMX5000 AP Ex communication module 912086Weather protection MX5000 complete 910134Silicone-free design

Not included in deliveryBase UniVario MX5000 Ex 912082Holder WMX FS, from 250 °C (482 °F) to 600 °C (1112 °F) 894679 Terminating resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional fault line connection 2-leadExternal indication 2-leadRecommended cable JY (St) Y 2x2x0.8 mm (0.03 inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)

NoteThe desired length of the exible sensor must be speci ed in metres at the time of placing the order. The sensor rod holder is designed for operation temperatures of up to 250 °C (482 °F). For higher operation temperatures, the WMX FS holder from 250 °C (482 °F) to 600 °C (1112 °F) Order no. 894679 is to be used.

Technical specifi cationsDetection method PT1000 sensor

Response classes A1, A2, B, C, D, E, F, G, indices S, R

Response temperatures 0 °C to +400 °C(+32 °F to +752 °F)

Operating voltage 7.6 V - 28 V DC

Quiescent current approx. 2.8 mA

Alarm current consumption approx. 15 mA

Alarm indication 1 red LED

Normal operation indication 1 green LED, ashingCurrent consumptionFault indication approx. 15 mA

Fault indication 1 yellow LED (2nd line)

Operating temperature -25 °C to +80 °C(-13 °F to +176 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminiumRelative humidity (IEC721-3-3)

0 to 95%No condensation

Speci cation according to EN 54 Part 5

Weight 520 to 1600 g (1.2 to7.5 lbs)

Dimensions 130 x 2000 to 9000 mm (dia. x H)5.1 x 78.7 x 354.3 inch (dia. x H)

Page 31: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario High temperature heat detector FS Flex, Ex

P31.

312.

160e

n / 0

2.14

Chapter 6 - 31© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

WMX5000 FS Flex 3GD 400 °C 2 m(752 °F 79 inch)

Order no.: 912114

Version with exible hose of 2 m length (79 inch).

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 680 g (1.5 lbs)

Dimensions 130 x up to 2000 mm (dia. x H)5.1 x up to 78.73 inch (dia. x H)

WMX5000 FS Flex 3GD 400 °C 6 m(752 °F 236 inch)

Order no.: 912115

Version with exible hose of 6 m length (236 inch).

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 840 g (1.9 lbs)

Dimensions 130 x up to 6000 mm (dia. x H)5.1 x up to 236.2 inch (dia. x H)

WMX5000 FS Flex 400 °C 9 m(752 °F 354 inch)

Order no.: 912116

Version with exible hose of 9 m length (354 inch).

Technical specifi cationsResponse temperatures 0 °C to +400 °C

(+32 °F to +752 °F)Weight 1000 g (2.2 lbs)

Dimensions 130 x up to 9000 mm (dia. x H)5.1 x up to 354.3 inch (dia. x H)

Otherwise like Order no.: 912113

Otherwise like Order no.: 912113

Otherwise like Order no.: 912113

Page 32: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Detector accessories

P31.

312.

810

- 1en

/ 01

.14

Chapter 6 - 32© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

KMX5000 AP communication module Order no.: 905883 Communication module for the operation of UniVario detectors on re alarm panels with Loop AP protocol.

By simply plugging the module into the detector, a conventional detector is turned into an analogue addressable detector. The detector address is set via a DIP switch. Power supply and communications are connected via the ring bus; no additional power supply is required.

The KMX5000 AP communication module is designed for integration into UniVario series detectors and must not be used in hazard areas.

Technical specifi cationsConnection 10 spring contacts (module/detector)

Operating voltage 17 V - 28 V DC

Operating current approx. 0,3 mA

Communication protocol Loop AP

Addressing 8 position DIP switch

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

Relative humidity (IEC721-3-3)

5 to 85%no condensation

Speci cation according to EN 54 Part 18

Weight 15 g (0.03 lbs)

Dimensions 54 x 28 x 19.5 mm (LxWxH)2.1 x 1.1 x 0.8 inch (LxWxH)

Included in delivery1 KMX5000 AP communication modulePan-head screw and Spacer

Connection / mountingPlug-in module in UniVario series detectors

Approvals / marking

G 207032 0786-CPD-20315

Product features• Communication module for constant signalling of

operating condition, alarms and faults via Loop AP protocol.

• Ring bus connection, no additional power supply.• Integration in UniVario series detectors.

Page 33: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Detector accessories

P31.

312.

810

- 1en

/ 01

.14

Chapter 6 - 33© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

KMX5000 AP Ex communication module Order no.: 912086

Approvals / marking

applied for applied for

Communication module for the operation of UniVario detectors on re alarm panels with Loop AP protocol.

By simply plugging the module into the detector, a conventional detector is turned into an analogue addressable detector. The detector address is set via a DIP switch. Power supply and communications are connected via the ring bus; no additional power supply is required.

The KMX5000 AP Ex communication module is designed for integration into UniVario series detectors and may be used in hazard areas.

Product features• Communication module for constant signalling of

operating condition, alarms and faults via Loop AP protocol.

• Ring bus connection, no additional power supply.• Integration in UniVario Ex series detectors.

Included in delivery1 KMX5000 AP Ex communication modulePan-head screw and Spacer

Connection / mountingPlug-in module in UniVario Ex series detectors

Technical specifi cationsConnection 10 spring contacts (module/detector)

Operating voltage 14 V - 22 V DC

Operating current approx. 0,3 mA

Communication protocol Loop AP

Addressing 8 position DIP switch

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

Relative humidity (IEC721-3-3)

5 to 85%no condensation

Speci cation according to EN 54 Part 18

Weight 15 g (0.03 lbs)

Dimensions 54 x 28 x 19.5 mm (LxWxH)2.1 x 1.1 x 0.8 inch (LxWxH)

Ex conformity Russia in acc. with TP TC 012/2011: 1Ex ib IIC T5/T4 Gb

Page 34: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Detector accessories

P31.

312.

810

- 1en

/ 01

.14

Chapter 6 - 34© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Retaining base for all UniVario industrial re detectors.Contains cable entries, EMC and environmental seals, connecting terminals and space for the optional relay module KMX5000 RK.Enables replacement of a detector without any terminal work.

Not included in deliveryEnd of line resistor 1.8 K / 0.5 W 675235

Spare partsSeal 127 x 2.9 / 1.6 mm 904752Gland M 16 x 1.5 Ms 901861Sealing cord 8 mm Vitron 0.036 m 800605

Base MX5000 Order no.: 904701

Technical specifi cations

Base MX5000 3M16 Order no.: 907011

Material Aluminium

Relative humidity max. 100 %

Conductor cross-section max. 2.5 mm2 (0.004 square inch)

Colour red

Ambient temperature -40 °C to +100 °C(-40 °F to +212 °F)

Weight 310 g (0.7 lbs)

Technical specifi cationsMaterial Aluminium

Relative humidity max. 100 %

Conductor cross-section max. 2.5 mm2 (0.004 square inch)

Colour red

Ambient temperature -40 °C to +100 °C(-40 °F to +212 °F)

Weight 350 g (0.8 lbs)

Retaining base for all UniVario industrial re detectors.Contains cable entries, EMC and environmental seals, connecting terminals and space for the optional relay module KMX5000 RK.The third cable gland allows the interface connection with detector remote indicators or similar devices.

Not included in deliveryEnd of line resistor 1.8 K / 0.5 W 675235

Spare partsSeal 127 x 2.9 / 1.6 mm 904752Gland M 16 x 1.5 Ms 901861Sealing cord 8 mm Vitron 0.036 m 800605

Approvals / marking

Approvals / marking

Base MX5000 SF Order no.: 914235 Silicon free base. Otherwise like Order no. 904701

Page 35: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Detector accessories

P31.

312.

810

- 1en

/ 01

.14

Chapter 6 - 35© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Base for displaying status and signal messages from industrial re alarms of the UniVario series.The LCD display gives information about sensor temperature, alarms or other operating states, depending on the detector type. Includes cable entries, EMC and environmental seals and connecting terminals. Enables replacement of a detector without any terminal work.The LCD base must not be used in hazard areas.

Not included in deliveryEnd of line resistor 1.8 K / 0.5 W 675235

Spare partsSeal 127 x 2.9 / 1.6 mm 904752Gland M 16 x 1.5 Ms 901861Sealing cord 8 mm Vitron 0.036 m 800605

Base MX5000 LCD Order no.: 906127

Technical specifi cationsOperating voltage By means of the detector

Operating current 0.3 mA

Material Aluminium

Relative humidity max. 100 %

Conductor cross-section max. 2.5 mm2 (0.004 square inch)

Colour red

Ambient temperature -20 °C to +70 °C(-4 °F to +158 °F)

Weight 350 g (0.8 lbs)

Approvals / marking

Base MX5000-I Order no.: 912493

Technical specifi cations Material Aluminium

Relative humidity max. 100 %

Conductor cross-section max. 2.5 mm2 (0.004 square inch)

Colour red

Ambient temperature -20 °C to +80 °C(-4 °F to +176 °F)

Weight 530 g (1.2 lbs)

Detector base for installation of the UniVario industrial re detectors in the LoopAP ringbus.Contains cable inlets, EMC and environmental sealing as well as terminals. Not suitable for use in explosion-prone areas.The installed dual isolator increases the operational safety of the LoopAP ringbus in the event of a short-circuit.The third cable screw connection is available for connecting detector mimic panels or similar devices.

Spare partsSeal 127 x 2.9 / 1.6 mm 904752Gland M 16 x 1.5 Ms Ex 904652Sealing cord 8 mm Vitron 0.036 m 800605

Page 36: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Detector accessories

P31.

312.

810

- 1en

/ 01

.14

Chapter 6 - 36© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Detector base for installation of the UniVario industrial re detectors of the Ex series. Contains cable inlets, EMC and environmental sealing as well as terminals. In this way, detectors can be replaced without requiring con-necting work.

Not included in deliveryEnd of line resistor 1.8 K / 0.5 W 675235

Spare partsSeal 127 x 2.9 / 1.6 mm 904752Gland M 16 x 1.5 Ms Ex 904652Sealing cord 8 mm Vitron 0.036 m 800605

Base MX5000 Ex Order no.: 912082

Bracket MX5000 Order no.: 904757

Technical specifi cationsMaterial Stainless steel, 2 mm

(0.08 inch) thickBracket retention Plastic (POM), black

Weight 110 g (0.2 lbs)

Mounting bracket for UniVario MX5000 base.

Included in delivery1 bracket UniVario MX5000

2 x screws M8, hex socket size 5 mm (0.2 inch).

Not included in deliveryMounting screws for wall/ceiling-mounted installation.

Spare partsScrew M 8 904355

Technical specifi cations Material Aluminium

Relative humidity max. 100 %

Conductor cross-section max. 2.5 mm2 (0.004 square inch)

Colour red

Ambient temperature -40 °C to +100 °C(-40 °F to +212 °F)

Weight 530 g (1.2 lbs)

Approvals / markingEx conformity Russia in acc. with TP TC 012/2011:

1Ex ib IIC T5/T4 Gb

Bracket MX5000 SF Order no.: 914234 Silicon free bracket. Otherwise like Order no. 904757

Page 37: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Detector accessories

P31.

312.

810

- 1en

/ 01

.14

Chapter 6 - 37© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Isolator XP and DIS for the separation of individual line sec-tions in the event of short circuits in ring bus operation with approval for ATEX category 3 gas and dust. Are suitable for use in Ex zones 2 and 22.

Isolator ISX 284 3GD Order no.: 915864

Technical specifi cations Material Aluminium

Fault indication inside Yellow LED

IP rating (EN60529) IP 66

Colour grey

Ambient temperature -20 °C to +60 °C(-4 °F to +140 °F)

Weight 1.2 kg(2.6 lbs)

Dimensions 90 mm (dia.)3.5 inch (dia.)

Approvals / markingEx conformity in acc. with 94/9/EG:

x II 2G Ex d IIB T6 Gbx II 2D Ex tb IIIC T80°C Db

EC type approval certi cate: BVS 11 ATEX E114

Page 38: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Detector accessories

P31.

312.

810

- 1en

/ 01

.14

Chapter 6 - 38© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Relay module KMX5000 RK Order no.: 906361 Communication module for the operation of UniVario detectors, independent of any re detection system.

Dry contacts for alarm and fault signalling allow the detectors to be used as stand-alone units, in any re and hazard detection system or in building management and control systems.

The KMX5000 RK communication module is designed to be integrated into the UniVario detector base MX5000 and must not be used in hazard areas.

Technical specifi cationsConnection 6-conductor ribbon cable

Operating voltage 24 V (14 V - 29 V) DC

Quiescent current approx. 7 mA Current consumption with alarm relay active approx. 20 mA

Current consumption with alarm relay and fault relay active

approx. 30 mA

Voltage load,contacts Max. 60 V DC, 25 V AC

Current load, contacts max. 1 A

Fault indication 1 yellow LED (2nd line)

Operating temperature -20 °C to +80 °C(-4 °F to +176 °F)

Relative humidity (IEC721-3-3)

5 to 85%no condensation

Speci cation according to EN 54 Part 18

Weight 50 g (0.1 lbs)

Dimensions 64 x 24 x 57 mm (LxWxH)2.5 x 0.9 x 2.2 inch (LxWxH)

Included in deliveryRelay module KMX5000 RKJumperInstallation material

Connection / mountingConductor cross-section min. 0.5 mm2 (0.0008 square inch) Max. 2.5 mm2 (0.004 square inch)

Product features• Dry changeover contacts for alarm and fault signalling.• Integration into MX5000 detector base.

Approvals / marking

G 208058 0786-CPD-20314

Page 39: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Detector accessories

P31.

312.

810

- 1en

/ 01

.14

Chapter 6 - 39© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Console for the installation of UniVario ame detectors outside of monitored areas, e.g. air ducts, machine tools, containers or silos.Easy access to the detector. Bayonet socket for reliable, vibration-proof hold.Antistatic material for use in hazard areas up to zones 1 and 21.

Included in deliveryMount with at sealing and springs 906148Screw M5 904341Self-tapping screw 765233Blind rivets 885078O-ring 904759Installation drawing 906970

Console MX5000 Flame detector Order no.: 904758

Technical specifi cationsMaterial PA6 99/0701 EC

Dimensions 138 x 15 mm (WxH)6.6 x 0.6 inch (WxH)

Colour Black

Ambient temperature -20 °C to +100 °C(-4 °F to +212 °F)

Weight 145 g (0.3 lbs)

Console for the installation of UniVario heat detectors on e.g. air ducts, dryers or machine tools.Easy access to the detector. Bayonet socket for reliable, vibration-proof hold.Antistatic material for use in hazard areas up to zones 1 and 21.

Included in deliveryConsole with at sealing and springs 906148Screw M5 904341Self-tapping screw 765233Blind rivets 885078O-ring 904759Installation drawing 906970

Console MX5000 Heat detector Order no.: 906969

Technical specifi cationsMaterial PA6 99/07001 EC

Dimensions 138 x 16.2 mm (WxH)5.4 x 0.6 inch (WxH)

Colour Black

Ambient temperature -20 °C to +100 °C(-4 °F to +212 °F)

Weight 145 g (0.3 lbs)

Page 40: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Detector accessories

P31.

312.

810

- 1en

/ 01

.14

Chapter 6 - 40© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Additional equipment – weather protection for ame detec-tors of the Uni Vario series for use in case of increased solar radiation or exposure to harsh weather conditions.

Connection / mountingFasten the weather protection to the detector.

Weather protection MX5000 complete Order no.: 910134

Technical specifi cations Material Stainless steel, 0.5 mm (0.02 inch)

thick

Dimensions 140 x 110 x 220 mm (BxHxL)5.5 x 4.3 x 8.7 inch (BxHxL)

Colour internally black

Weight 300 g (0.67 lbs)

Page 41: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUniVario Test equipment

P31.

312.

911e

n / 0

2.13

Product Sheet | Detec�on

Chapter 6 - 41© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Service device SMX5000 Order no.: 906136 The service device is for the simpli ed con guration, diagnostics and function testing of the UniVario detectors, and for indicating events from the history memory.

The SMX5000 can be used on UniVario detectors with software version V01 Exx or higher.

An RS-232 interface can be used to transmit data from the history memory to the UniVario View software.

Technical specifi cationsLCD display 3 rows of 12 characters each

Operating current(depends on the detector type)

approx. 80 mA at 3 V (with background lighting)

approx. 25 mA at 3 V(without background lighting)

approx. 5 mA at 3 V (in detector mode)

Operation time(depends on the detector and battery types)

approx. 25 hrs (with background lighting)

approx. 80 hrs (without background lighting)

approx. 400 hrs(in detector mode)

Batteries required 2 x 1.5 V Mignon, type AA (LR6)

IP rating IP 20

Enclosure material ABS plastic, RAL 7038 grey

Operating temperature 0 °C to +50 °C(-32 °F to +122 °F)

Relative humidity (IEC721-3-3)

5 to 85%no condensation

Speci cation according toEN 55022/CISPR22 CL. B, EN 55024, EN 61000-6-3,

EN 61000-4-2, EN 61000-4-3,Weight 26 g (0.1 lbs)

Dimensions 165 x 92 x 30 mm (LxWxH)6.5 x 3.6 x 1.2 inch (LxWxH)

Included in delivery1 service device SMX50001 connection cable, 30-pin2 1.5 V batteries, type AA (LR6)

AccessoriesBattery 1.5 V Mignon, type AA (LR6) 906751Connection cable, 30-pin 906198

Not included in deliveryUniVario View software

Approvals / marking

Product features• Display with 3 rows of 12 characters each.• Simple operation with clear menu structure.• Operation and fault indication.

Page 42: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsIR fl ame detector

P31.

312.

330

- 3en

/ 02

.13

Chapter 6 - 42© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Approvals / marking

G 296016 0786-CPD-20312

FMX3511 Order no.: 801618Double infrared ame detector FMX3511 for the detection of open ames. Optic test monitors the functionality of the detector. Designed for use in raugh industrial environments. Equipped for operation as a conventional detector.

Technical specifi cations Detection method 2 IR Sensoren

Sensitivity class 3

Viewing angle 60 °

Operating voltage 7.6 V - 15 V DC

Quiescent current approx. 3 mA

Alarm current approx. 18 mA

Alarm indication 1 LED red

Fault indication current approx. 7 mA

Fault indication 1 LED yellow

Number of detectors per line max. 4

Electrostatic shielding Required

Operating temperature -25 °C to +80 °C(-13 °F to +176 °F)

IP rating (EN 60529) IP 65

Enclosure material Diecast aluminium, RAL5009-blue

Relative humidity (IEC721-3-3) max. 100% at + 35 °C (+95 °F)

Weight 600 g (1.3 lbs)

Dimensions 127 x 125 x 70 mm (BxHxT)5 x 4.9 x 2.8 inch (BxHxT)

Not included in deliveryMounting device bracket with insulation 801284Mounting device console 125x80Ø60 801280End of line-resistor 1.8 K / 0.5 W 675235Sun screen 801277Parallel indicator LMX5000 908499Plug for the pollution test 801079

Connection / mountingConnection cable standard detector 2-leadRecommended cable LiYCY 5x0.5 mm2 (0.0008 square inch)Cable gland M16x1.5, Brass nickel-plated, EMV

Product features• Highly reliable against false alarms, e.g. from hot sur-

faces. • A microcontroller monitors the functionality. Faults can

be indicated on the detector or on a separate line.• Connection of remote indicator possible.• Single optic test.

Page 43: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsIR fl ame detector

P31.

312.

330

- 3en

/ 02

.13

Chapter 6 - 43© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

FMX3511 SF Order no.: 801619

Silicone-free ame detector

FMX3511 0.2 sec Order no.: 902532

Flame detectors with fast response within range of milse-counds are used for object monitoring (e.g. tooling machine).

Technical specifi cations Criterion of detection Change of intensity

FMX3511 0.2 sec SF Order no.: 902767

Silicone-free ame detector

Page 44: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsIR fl ame detector

P31.

312.

330

- 4en

/ 02

.13

Chapter 6 - 44© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Approvals / marking

G 296016 0786-CPD-20312

FMX3511 BG Order no.: 891319Double infrared ame detector FMX3511 for the detection of open ames. Optic test monitors the functionality of the detector. Designed for use in raugh industrial environments. Equipped for operation as a conventional detector.

Not included in deliveryEnd of line-resistor 1.8 K / 0.5 W 675235Sun sreen 801277Parallel indicator LMX5000 908499Plug for the pollution test 801079

Connection /mountingConnection cable standard detector 2-leadRecommended cable LiYCY 5x0.5 mm2 (0.0008 square inch)Cable gland M16x1.5, brass nickel-plated, EMV

Technical specifi cations Detection method 2 IR Sensoren

Sensitivity class 3

Viewing angle 60 °

Operating voltage 7.6 V - 15 V DC

Quiescent current approx. 3 mA

Alarm current approx. 18 mA

Alarm indication 1 LED red

Fault indication current approx. 7 mA

Fault indication 1 LED yellow

Number of detectors per line max. 4

Electrostatic shielding Required

Operating temperature -25 °C to +80 °C(-13 °F to +176 °F)

IP rating (EN 60529) IP 65

Enclosure material Diecast aluminium, RAL5009-blue

Relative humidity (IEC721-3-3) max. 100% at + 35 °C (+95 °F)

Weight 750 g (1.7 lbs)

Dimensions 127 x 155 x 92 mm (BxHxT)5 x 6.1 x 3.6 inch (BxHxT)

Product features• Highly reliable against false alarms, e.g. from hot sur-

faces. • A microcontroller monitors the functionality. Faults can

be indicated on the detector or on a separate line.• Connection of remote indicator possible.• Single optic test.

Page 45: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsIR fl ame detector

P31.

312.

330

- 4en

/ 02

.13

Chapter 6 - 45© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

FMX3511 BG SF Order no.: 800029

Silicone-free ame detector

FMX3511 BG 0.2 sec Order no.: 902533

Flame detectors with fast response within range of milise-conds are used for object monitoring (e.g. tooling machine).

Technical specifi cations Criterion of detection Change of intensity

FMX3511 BG 0.2 sec SF Order no.: 902768

Silicone-free ame detector

Page 46: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsIR fl ame detector

P31.

312.

330

- 5en

/ 02

.13

Chapter 6 - 46© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Approvals / marking

G 296016 0786-CPD-20312

FMX3511 Console Order no.: 801609Double infrared ame detector FMX3511 for the detection of open ames. Optic test monitors the functionality of the detector. Version Brachet mounting. Designed for use in rough industrial environments. Equipped for operation as a conventional detector.

Not included in deliveryMounting device bracket with insulation 801284End of line-resistor 1.8 K / 0.5 W 675235Sun sreen 801277Parallel indicator LMX5000 908499Plug for the pollution test 801079

Connection / mountingConnection cable standard detector 2-leadRecommended cable LiYCY 5x0.5 mm2 (0.0008 square inch)Cable gland M16x1.5, brass nickel-plated, EMVTechnical specifi cations

Detection method 2 IR Sensoren

Sensitivity class 3

Viewing angle 60 °

Operating voltage 7.6 V - 15 V DC

Quiescent current approx. 3 mA

Alarm current approx. 18 mA

Alarm indication 1 LED red

Fault indication current approx. 7 mA

Fault indication 1 LED yellow

Number of detectors per line max. 4

Electrostatic shielding Required

Operating temperature -25 °C to +80 °C(-13 °F to +176 °F)

IP rating (EN 60529) IP 65

Enclosure material Diecast aluminium, RAL5009-blue

Relative humidity (IEC721-3-3) max. 100% at + 35 °C (+95 °F)

Weight 950 g (2.1 lbs)

Dimensions 127 x 150 x 75 mm (BxHxT)5 x 5.9 x 3 inch (BxHxT)

Product features• Highly reliable against false alarms, e.g. from hot sur-

faces. • A microcontroller monitors the functionality. Faults can

be indicated on the detector or on a separate line.• Connection of remote indicator possible.• Single optic test.

Page 47: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsIR fl ame detector

P31.

312.

330

- 5en

/ 02

.13

Chapter 6 - 47© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

FMX3511 Console 0.2 sec Order no.: 902534

Flame detectors with fast response within range of milise-conds are used for object monitoring (e.g. tooling machine).

Technical specifi cations Criterion of detection Change of intensity

Page 48: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsIR fl ame detector

P31.

312.

330

- 6en

/ 02

.13

Product Sheet | Detec�on

Chapter 6 - 48© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Approvals / marking

G 296016 0786-CPD-20312

FMX3511 Console LSP Order no.: 801610Double infrared ame detector FMX3511 for the detection of open ames. Optic test monitors the functionality of the detector. Version Brachet mounting and air ushing function. Designed for use in rough industrial environments. Equipped for operation as a conventional detector.

Not included in deliveryMounting device bracket with insulation 801284End of line-resistor 1.8 K / 0.5 W 675235Sun sreen 801277Parallel indicator LMX5000 908499Plug for the pollution test 801079Compressed air supply

Connection / mountingConnection cable standard detector 2-leadRecommended cable LiYCY 5x0.5 mm2 (0.0008 square inch)Cable gland M16x1.5, brass nickel-plated, EMV

Product features• Highly reliable against false alarms, e.g. from hot sur-

faces. • A microcontroller monitors the functionality. Faults can

be indicated on the detector or on a separate line.• Connection of remote indicator possible.• Single optic test.

Technical specifi cations Detection method 2 IR Sensoren

Sensitivity class 3

Viewing angle 60 °

Operating voltage 7.6 V - 15 V DC

Quiescent current approx. 3 mA

Alarm current approx. 18 mA

Alarm indication 1 LED red

Fault indication current approx. 7 mA

Fault indication 1 LED yellow

Number of detectors per line max. 4

Electrostatic shielding Required

Operating temperature -25 °C to +80 °C(-13 °F to +176 °F)

IP rating (EN 60529) IP 65

Enclosure material Diecast aluminium, RAL5009-blue

Relative humidity (IEC721-3-3) max. 100% at +35 °C (+95 °F)

Weight 970 g (2.1 lbs)

Dimensions 141 x 150 x 75 mm (BxHxT)5.6 x 5.9 x 3 inch (BxHxT)

Compressed air supply on site Pressure range 0.8 - 1.5 bar

Page 49: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsIR fl ame detector

P31.

312.

330

- 6en

/ 02

.13

Product Sheet | Detec�on

Chapter 6 - 49© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

FMX3511 Console LSP 0.2 sec Order no.: 902535

Flame detectors with fast response within range of milise-conds are used for object monitoring (e.g. tooling machine).

Technical specifi cations Criterion of detection Change of intensity

Page 50: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsIR fl ame detector Ex

P31.

312.

340

- 2en

/ 01

.14

Chapter 6 - 50© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

FMX3501 Ex Order no.: 903133Infrared ame detector FMX3501 Ex for the detection of open ames. Optic test monitors the functionality of the detector. Designed for use in rough industrial environments. Equipped for operation as a conventional detector. Infrared ame detector FMX3501 Ex are ATEX-approved for category 2 gas and 3 dust and are suitable for use in Ex zones 1 and 22.Intrinsically safe ame detectors must be connected by cor-respondingly marked cables to explosion hazard barriers.

Not included in deliveryMounting device bracket with insulation 801284Safety barrier IS conventional 9 V 904991End of line-resistor 1.8 K / 0.5 W 675235Sun screen 801277Plug for the pollution test 801079

Connection / mountingConnection cable standard detector 2-leadrecommended cable LiYCY 5x0.5 mm2 (0.0008 square inch)Cable gland M16x1.5, Brass nickel-plated, EMV

Technical specifi cations Detection method 2 IR Sensoren

Sensitivity class 3

Viewing angle 60 °

Operating voltage 7.6 V - 15 V DC

Quiescent current approx. 3 mA

Alarm current approx. 18 mA

Alarm indication 1 LED red

Fault indication current approx. 7 mA

Fault indication 1 LED yellow

Number of detectors per line max. 4

Electrostatic shielding Required

Operating temperatur -25 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 65

Enclosure material Diecast aluminium, RAL5009-blue

Relative humidity (IEC721-3-3) max. 100% at +35 °C (+95 °F)

Weight 600 g (1.3 lbs)

Dimensions 127 x 125 x 70 mm (BxHxT)3.9 x 2 inch (dia. x H)

Product features• Highly reliable against false alarms, e.g. from hot sur-

faces. • A microcontroller monitors the functionality. Faults can

be indicated on the detector or on a separate line.• Connection of remote indicator possible.• Single optic test.

Approvals / markingEx conformity in acc. with 94/9/EG:

x II 2G 3G Ex ib IIC T6/T4Type examination certi cate: DMT 02 ATEX E224Ex conformity Russia in acc. with TP TC 012/2011:

1Ex ib IIC T6/T4 Gb

G 296016 0786-CPD-20312

Page 51: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsIR fl ame detector Ex

P31.

312.

340

- 2en

/ 01

.14

Chapter 6 - 51© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

FMX3501 Ex SF Order no.: 903134

Silicone-free ame detector

FMX3501 Ex 0.2 sec Order no.: 903135

Flame detectors with fast response within range of milise-conds are used for object monitoring (e.g. tooling machine).

Technical specifi cations Criterion of detection Change of intensity

FMX3501 Ex 0.2 sec SF Order no.: 903136

Silicone-free ame detector

FMX3501 Ex T SF Order no.: 903138

Silicone-free ame detector

FMX3501 Ex T 0.2 sec Order no.: 903139

Flame detectors with fast response within range of milise-conds are used for object monitoring (e.g. tooling machine).

Technical specifi cations Criterion of detection change of intensity

FMX3501 Ex T 0.2 sec SF Order no.: 903140

Silicone-free ame detector

FMX3501 Ex T Order no.: 903137

Flame detector with non-latching alarm

Page 52: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsIR fl ame detector Ex

P31.

312.

340

- 3en

/ 02

.14

Product Sheet | Detec�on

Chapter 6 - 52© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

FMX3501 Ex BG Order no.: 800000Infrared ame detector FMX3501 Ex for the detection of open ames. Optic test monitors the functionality of the detector. Designed for use in rough industrial environments. Equipped for operation as a conventional detector. Infrared ame detector FMX3501 Ex are ATEX-approved for category 2 gas and 3 dust and are suitable for use in Ex zones 1 and 22.Intrinsically safe ame detectors must be connected by cor-respondingly marked cables to explosion hazard barriers.

Not included in deliverySafety barrier IS conventional 9 V 904991End of line-resistor 1.8 K / 0.5 W 675235Sun screen 801277Plug for the pollution test 801079

Connection / mountingConnection cable standard detector 2-leadRecommended cable LiYCY 5x0.5 mm2 (0.0008 square inch)Cable gland M16x1.5, brass nickel-plated, EMV

Product features• Highly reliable against false alarms, e.g. from hot sur-

faces. • A microcontroller monitors the functionality. Faults can

be indicated on the detector or on a separate line.• Connection of remote indicator possible.• Single optic test.

Technical specifi cations Detection method 2 IR Sensoren

Sensitivity class 3

Viewing angle 60 °

Operating voltage 7.6 V - 15 V DC

Quiescent current approx. 3 mA

Alarm current approx. 18 mA

Alarm inducation 1 LED red

Fault indication current approx. 7 mA

Fault indication 1 LED yellow

Number of detektors per line max. 4

Electrostatic shielding Required

Operating temperature -25 °C to +80 °C(-4 °F to +176 °F)

IP rating (EN 60529) IP 65

Enclosure material Diecast aluminium, RAL5009-blue

Relative humidity (IEC721-3-3) max. 100% at +35 °C (+95 °F)

Weight 750 g (1.6 lbs)

Dimensions 127 x 155 x 92 mm (BxHxT)5 x 6.1 x 3.6 inch (BxHxT))

Approvals / markingEx Conformity in acc. with 94/9/EG:

x II 2G 3G Ex ib IIC T6/T4Type examination certi cate: DMT 02 ATEX E224Ex conformity Russia in acc. with TP TC 012/2011:

1Ex ib IIC T6/T4 Gb

G 296016 0786-CPD-20312

FMX3501 Ex BG CN Order no.: 907436

Version China

Otherwise like Order no 800000

Approvals / marking

Page 53: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsIR fl ame detector Ex

P31.

312.

340

- 3en

/ 02

.14

Product Sheet | Detec�on

Chapter 6 - 53© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

FMX3501 Ex SF BG Order no.: 902769

Silicone-free ame detector

FMX3501 Ex 0.2 sec BG Order no.: 902721

Flame detectors with fast response within range of milise-conds are used for object monitoring (e.g. tooling machine).

Technical specifi cations Criterion of detection Change of intensity

FMX3501 Ex 0.2 sec SF BG Order no.: 902770

Silicone-free ame detector

FMX3501 Ex T SF BG Order no.: 903142

Silicone-free ame detector

FMX3501 Ex T 0.2 sec BG Order no.: 903143

Flame detectors with fast response within range of milise-conds are used for object monitoring (e.g. tooling machine).

Technical specifi cations Criterion of detection Change of intensity

FMX3501 Ex T 0.2 sec SF BG Order no.: 903151

Silicone-free ame detector

FMX3501 Ex T BG Order no.: 903141

Flame detector with non-latching alarm

Otherwise like Order no 800000

Otherwise like Order no 800000

Otherwise like Order no 800000

Otherwise like Order no 800000

Otherwise like Order no 800000

Otherwise like Order no 800000

Otherwise like Order no 800000

Page 54: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsUV fl ame detector Ex

P31.

312.

320

- 2en

/ 02

.13

Product Sheet | Detec�on

Chapter 6 - 54© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Approvals / markingEx conformity in acc. with 94/9/EG: x II 2G Ex d e IIC T6 x II 2D Ex tD A21 IP67 T80°CType examination certi cate: BVS 04 ATEX E 168 X

UMX3001 Ex Order.-no.: 903802 UV ame detector for the detection of open ames. Designed for use in rough industrial environments. Equipped for operation as a conventional detector.The UMX3001 Ex ame detectors are ATEX-approved for category 2 gas and dust and are suitable for use in Ex zones 1 and 21. The UMX3001 Ex has a pressure resistant casing.

Technical specifi cations Detections method UV-Sensor

Viewing angle 110 °

Number of detectors per line max. 4

Operating voltage 7.6 V - 13.2 V DC

Quiescent cuttent approx. 1 mA

Alarm current approx. 20 mA

Alarm indication 1 LED red

Electrostatic shielding requiered

Operating temperature -20 °C to +70 °C(-4 °F to +158 °F)

IP rating (EN 60529) IP 67

Enclosure material Diecast aluminium, silver grey

Relative humidity (IEC721-3-3) max. 95% to +35 °C (95 °F)

Weight 3 kg (6.6 lbs)

Dimensions 88 x 190 mm (BxH)3.5 x 7.5 inch (dia. x H)

Not included in deliveryEnd of line-resistor 1.8 K / 0.5 W 675235

Connection / mountingConnection cable standard detector 2-leadAdditional connection latching indication 1-leadRecommended cable LIYCY grey 5x0.5 mm2

(0.0008 square inch)Conductor cross-section max. 2.5 mm2 (0.004 square inch)Conducting cable diameter 5 mm to 9 mm (0.20 to 0.35 inch)Cable gland metal, EMV, Ex M16x1.5

Product fetures• Wide eld of view.• Fast ame response.• High water and dust protection (IP67).

Page 55: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsDetector accessories

P31.

312.

810

- 2en

/ 02

.13

Chapter 6 - 55© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Mounting device to support gas emission detectors GMX-1001CO I.

Included in delivery1 Mounting device console 80x75 Ø54 complete 9028962 Countersunk screw DIN923-M5x10 St 8357035 Self-taping screw DIN7981 C4.2x16 8850805 Blind rivet 3.2x16 alu 8850781 O-ring 60x3 Viton 1325872 Hex screw DIN933-M8x20-A2 7725522 Spring washer DIN127 B8-1.4310 820707

Not included in deliveryAdhesive LoctiteAVX 586, 50 ml 886226

NoteDo not install the mounting device console in explosion-hazard zone 1

Mounting device console 80x75 Ø54(3.1x2.9 Ø 2.1 inch)

Order no.: 902898

Technical specifi cations Material Plastic POM

Colour black

Weight 160 g (0.4 lbs)

Dimensions 112 x 112 mm (LxB)(4.4 x 4.4 inch (LxB)

Page 56: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsDetector accessories

P31.

312.

810

- 2en

/ 02

.13

Chapter 6 - 56© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Mounting device console 125x80 Ø60(4.9x3.1 Ø 2.3 inch)

Order no.: 801280

Technical specifi cations Material Plastic PETP

Colour black

Weight 350 g (0.8 lbs)

Dimensions 120 x 150 mm (LxB)(4.7 x 5.9 inch (LxB)

Mounting device to support ame detector FMX3511.

Included in delivery1 Mounting device console 125x80 Ø60 8010692 Countersunk screw DIN923-M5x10 St 8357035 Self-taping screw DIN7981 C4.2x16 8850805 Blind rivet 3.2x16 alu 8850781 O-ring 70x3 Viton 70°SH 8007742 Hex screw DIN933-M8x20-A2 7725522 Spring washer DIN127 B8-1.4310 820707

Not included in deliveryAdhesive LoctiteAVX 586, 50 ml 886226

NoteDo not install the mounting device console in explosion-hazard zone 1.

Mounting device with air ushing to support and preventive cleaning of the detector optics of ame detectors FMX3511.

Included in delivery1 Mounting device console 125x80 Ø60 LSP 8012982 Countersunk screw DIN923-M5x10 St 8357035 Self-taping screw DIN7981 C4.2x16 8850805 Blind rivet 3.2x16 alu 8850781 O-ring 60x3 Viton 70°SH 8007742 Hex screw DIN933-M8x20-A2 7725522 Spring washer DIN127 B8-1.4310 820707

Not included in deliveryAdhesive LoctiteAVX 586, 50 ml 886226Air ushing has to be supplied with compressed air on site.

NoteDo not install the mounting device console in explosion-hazard zone 1.

Mounting device console 125x80 Ø60(4.9x3.1 Ø 2.3 inch) LSP

Order no.: 801281

Technical specifi cations Medium Compressed air

Pressure range 0.8 - 1.5 bar

Connection thread G1/8“, DIN ISO228

Material Plastic PEPT

Colour black

Weight 370 g (0.8 lbs)

Dimensions 120 x 150 mm (LxB)(4.7 x 5.9 inch (LxB)

Page 57: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsDetector accessories

P31.

312.

810

- 2en

/ 02

.13

Chapter 6 - 57© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Mounting device bracket with insulation Order no.: 801284

Technical specifi cations Material bracket Stainless steel, 2 mm

(0.08 inch) thick

Material clamp Stainless steel, 1.5 mm (0.06 inch) thick

Insulating Plastic POM

Weight 160 g (0.4 lbs)

Dimensions 81.5 x 86 x 31 mm (LxBxH)(3.2 x 3.4 x1.2 inch (LxBxH)

Mounting device to support gas emission detectors, ame detectors, spark detectors and spark test light detectors.

Included in delivery1 Mounting device complete with 2 oval-head screw M8x12 for xing the detector on the bracket.

Not included in deliveryClamping screw for wall/ceiling mounting.

Spare partsOval-head screw M8x12-1.4301 800596Hex. nut DIN934-M8-A2/A4 820781Spring washer DIN127 B8-1.4310 820707

Page 58: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsDetector accessories

P31.

312.

810

- 2en

/ 02

.13

Chapter 6 - 58© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Support disk mounting 90 °C (194 °F) Order no.: 891848

Technical specifi cations Enclosure material: -mounting coupling -hex. nut -oval washer -tapered block

stainless steelbrass

stainless steelPolyamid PA12, black

Operating temperature to +90 °C (+194 °F)

Weight 120 g (0.3 lbs)

Support disk mounting 250 °C (482 °F) Order no.: 800034

Otherwise like Order no. 891848.

Technical specifi cations Enclosure material: -tapered block 250 °C (482 °F)

Peck / Mod, black

Operating temperature to +250 °C (+482 °F)

Quick installation device to support detections with single-hole and bre options.

Mounting tool mounting socket - F180 Order no.: 843474

Technical specifi cations Enclosure material stainless spring band steel

Weight 90 g (0.2 lbs)

Quick installation device to support detections with single-hole.The installation is allowed up to a wall thickness of 8 mm (0.3 inch).

Flushing air device Order no.: 907822

Technical specifi cations Enclosure material: V2A and PA 12

Operating temperature -10 °C to +60 °C(-14 °F to +140 °F)

Operating pressure 0.2 to 10 bar

Weight 200 g (0.4 lbs)

Dimensions 55 x 48 mm (DxL)2.2 x 1.9 inch (DxL)

Quick installation device to support detections with single-hole and air ushing..

Page 59: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsFlame detector accessories

P31.

312.

391e

n / 0

2.14

Chapter 6 - 59© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Protection against skewness parasitic radiation (e.g. sunlight for outside applications) for the ame detector FMX3511 and FMX3501 Ex.

Connection / mountingPlug sun screen onto detector optic.

NoteAfter mounting the sunscreen can not be removed.

Sun screen FMX3511/FMX3501 Ex Order no.: 801277

Technical specifi cations Material Stainless steel, 2.5 mm (0.09 inch)

thick

Dimensions 62.5 x 53 mm (WxH)2.5 x 2.1 inch (WxH)

Colour internally black

Weight 90 g (0.2 lbs)

To clean the optic and re ective surface by ame detectors.

Included in delivery1 packaging unit (20 cleaning cloth and 10 cleaning sponge)

Cleaning kit optic Order no.: 916644

Page 60: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsGas emission detector

P31.

312.

610

- 1en

/ 02

.13

Chapter 6 - 60© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Approvals / marking

G 204121 0786-CPD-20135

GMX1001CO I Order no.: 900960Multi sensor re gas detector GMX1001CO I for the early detection of smoldering res.Designed for use in rough industrial environments (e.g. silos, chip bunkers). The GMX1001CO I detects the burning characteristic sub-stance carbon monoxide and temperature. False alarms are nearly impossible. Equipped for operation as a conventional detector.

Technical specifi cations

Detection method CO (carbon monoxide) and temperature

Alarm threshold: - Carbon monoxide - Temperature - Rate of rise measurement

40 ppm> 60 °C (140 °F)

dT > 3 °C/min. at T > 36 °C (96,8 °F)

Operating voltage 7,6 V - 40 V DC

Quiescent current approx. 0.15 mA

Alarm current approx. 18 mA

Alarm indication 1 LED red

Electrostatic shielding Required

Operating temperature -20 °C to +50 °C(-4 °F to +122 °F)

IP rating (EN 60529) IP 65

Enclosure material Diecast aluminium, RAL5009-blue

Relative humidity (IEC721-3-3)

max. 15 to +90 %no condensation

Weight 480 g (1.1 lbs)

Dimensions 122 x 80 x 69 mm (BxHxT)4.8 x 3.2 x 2.7 inch (BxHxT)

Not included in deliveryMounting device bracket with insulation 801284Mounting device console 80x75 Ø54 902898End of line-resistor 1.8 K / 0,5 W 675235Test device smoke generator RG2000 902671Parallel indicator LMX5000 908499

Connection / mountingConnection cable standard detector 2-leadConductor cross-section max. 2.5 mm2 (0.004 square inch)Fire detection cable with static shield 606061LIYCY grey 5x0.5 mm2 (0.0008 square inch)Cable gland M16x1.5, Brass nickel-plated, EMV

Spare partsScrewed mounting GMX1001COI complete 902923Sensor GMX1002CO 900968

NoteSimple one man calibration.

Product features• A microcontroller monitors the functionality and values.• Multi sensor carbon monoxide and temperature.• Connection of remote indicator possible.

Page 61: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsGas emission detector

P31.

312.

610

- 1en

/ 02

.13

Chapter 6 - 61© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Approvals / marking

GMX1001CO 300ppm Order no.: 909139

Special detector for application in areas with emissions of carbon monoxide increased due to operating conditions.

Technical specifi cations Response monoxide: - Carbon monoxide - Temperature - Differential measurement

300 ppm> 100 °C (212 °F)

dT > 3 °C/min. at T > 80 °C (176 °F)

Page 62: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsGas emission detector

P31.

312.

610

- 2en

/ 02

.13

Chapter 6 - 62© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Approvals / marking

G 204121 0786-CPD-20135

GMX1001CO I BG Order no.: 902891Multi sensor re gas detector GMX1001CO I BG for the early detection of smoldering res.Designed for use in rough industrial environments (e.g. silos, chip bunkers). The GMX1001CO I detects the burning characteristic sub-stance carbon monoxide and temperature. False alarms are nearly impossible. Designed for operation as a conventional detector.

Not included in deliveryMounting device console 80x75 Ø54 902898End of line-resistor 1.8 K / 0.5 W 675235Test device smoke generator RG2000 902671Parallel indicator LMX5000 908499

Connection / mountingConnection cable standard detector 2-leadConductor cross-section max. 2.5 mm2 (0.004 square inch)Fire detection cable with static shield 606061LIYCY grey, 5x0.5 mm2 (0.0008 square inch)Cable gland M16x1.5, Brass nickel-plated, EMV

Spare partsScrewed mounting GMX1001COI complete 902923Sensor GMX1002CO 900968

NoteSimple one man calibration.

Product features• A microcontroller monitors the functionality and values.• Multi sensor carbon monoxide and temperature.• Connection of remote indicator possible.

Technical specifi cations

Detection method CO (carbon monoxide) and temperature

Alarm threshold: - Carbon monoxide - Temperature - Rate of rise measurement

40 ppm> 60 °C (140 °F)

dT > 3 °C/min. at T > 36 °C (96,8 °F)

Operating voltage 7.6 V - 40 V DC

Quiescent current approx. 0.15 mA

Alarm current approx. 18 mA

Alarm indication 1 LED red

Electrostatic shielding Required

Operating temperature -20 °C to +50 °C(-4 °F to +122 °F)

IP rating (EN 60529) IP 65

Enclosure material Diecast aluminium, RAL5009-blue

Relative humidity (IEC721-3-3)

max. 15 to +90 %no condensation

Weight 600 g (1.3 lbs)

Dimensions 122 x 106 x 88 mm (BxHxT)4.8 x 4.2 x 3.5 inch (BxHxT)

Page 63: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsGas emission detector

P31.

312.

610

- 2en

/ 02

.13

Chapter 6 - 63© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Approvals / marking

GMX1001CO 300ppm BG Order no.: 909161

Special detector for application in areas with emissions of carbon monoxide increased due to operating conditions.

Technical specifi cations Response values: - Carbon monoxide - Temperature - Differential measurement

300 ppm> 100 °C (212 °F)

dT > 3 °C/min. at T > 80 °C (176 °F)

Page 64: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsGas emission detector

P31.

312.

610

- 3en

/ 02

.13

Chapter 6 - 64© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Approvals / marking

GMX1001CO I Console Order no.: 902893Multi sensor re gas detector GMX1001CO I Console for the early detection of smoldering res.Designed for use in rough industrial environments (e.g. silos, chip bunkers). Version bracket mount.The GMX1001CO I detects the burning characteristic sub-stance carbon monoxide and temperature. False alarms are nearly impossible. Designed for operation as a conventional detector.

Not included in deliveryMounting device bracket with insulation 801284End of line-resistor 1.8 K / 0.5 W 675235Test device smoke detector RG2000 902671Parallel indicator LMX5000 908499

Connection / mountingConnection cable standard detector 2-leadConductor cross-section max. 2.5 mm2 (0.004 square inch)Fire detection cable with static shield 606061LIYCY grey, 5x0.5 mm2 (0.0008 square inch)Cable gland M16x1.5, Brass nickel-plated, EMV

Spare partsScrewed mounting GMX1001COI complete 902923Sensor GMX1002CO 900968

NoteSimple one man calibration.

Product features• A microcontroller monitors the functionality and values.• Multi sensor carbon monoxide and temperature.• Connection of remote indicator possible.

Technical specifi cations

Detection method CO (carbon monoxide) and temperature

Alarm threshold: - Carbon monoxid - Temperature - Rate of rise measurement

40 ppm> 60 °C (140 °F)

dT > 3 °C/min. at T > 36 °C (96.8 °F)

Operating voltage 7.6 V - 40 V DC

Quiescent current approx. 0.15 mA

Alarm current approx. 18 mA

Alarm indication 1 LED red

Electrostatic shielding Required

Operating temperature -20 °C to +50 °C(-4 °F to +122 °F)

IP rating (EN 60529) IP 65

Enclosure material Diecast aluminium, RAL5009-blue

Relative humidity (IEC721-3-3)

max. 15 at +90 %no condensation

Weight 600 g (1.3 lbs)

Dimensions 122 x 112 x 75 mm (BxHxT)4.8 x 4.4 x 3 inch (BxHxT)

Page 65: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsGas emission detector

P31.

312.

610

- 3en

/ 02

.13

Chapter 6 - 65© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Approvals / marking

GMX1001CO 300ppm Console Order no.: 909162

Special detector for application in areas with emissons of carbon monoxide increased due to operating conditions.

Technical specifi cations Response values: - Carbon monoxide - Temperature - Differential measurement

300 ppm> 100 °C (212 °F)

dT > 3 °C/min. at T > 80 °C (96.8 °F)

Page 66: Industrial detectors - Viking Ibericavikingiberica.com/docs/tecnica/detection_mnx_reduced.pdf · Industrial detectors ... hazard areas. The UniVario ... rough industrial environments

Industrial detectorsGas emission detector Ex

P31.

312.

620

- 1en

/ 02

.13

Chapter 6 - 66© Viking GmbH & Co. KG | Industriestr. 10/12 | D-23843 Bad Oldesloe | www.viking-emea.com |

Product Sheet | Detec�on

Approvals / marking

G 204121 0786-CPD-20135

GMX1001CO Ex Dust Order no.: 905642Multi sensor re gas detector GMX1001CO Ex Dust for the early detection of smoldering res.Designed for use in raugh industrial environments (e.g. silos, chip bunkers). The GMX1001CO I detects the burning characteristic sub-stance carbon monoxide and temperature. False alarms are nearly impossible. Designed for operation as a conventional detector. The GMX1001CO Ex Dust gas detectors are ATEX-approved for category 1 and 2 dust and are suitable for use in Ex zone 20 and 21.

Not included in deliveryMounting device bracket with insulation 801284Mounting device console 80x75Ø54 902898End of line-resistor 1.8 K / 0.5 W 675235Test device smoke generator RG2000 902671Parallel indicator LMX5000 908499

Connection / mountingConnection cable standard detector 2-leadConductor cross-section max. 2.5 mm2 (0.004 square inch)Fire detection cable with static shield 606061LIYCY grey, 5x0.5 mm2 (0.0008 square inch)Cable gland M16x1.5, Brass nickel-plated, EMV, Ex

Spare partsScrewed GMX1001COI complete 902923Sensor GMX1002CO 900968

HinweisSimple one man calibration

Product features• A microcontroller monitors the functionality and values.• Multi sensor carbon monoxide and temperature.• Connection of remote indicator possible.

ApprovalsEx conformity in acc. with 94/9/EG: x II 1/2D Ex tD A20/21 IP65 T136°C x II 1D Ex tD A20 IP65 T136°CType examination certi cate: BVS 05 ATEX E179

Technical specifi cations

Detection method CO (carbon monoxide) and temperature

Alarm threshold: - Carbon monoxide - Temperature - Rate of rise measurement

40 ppm> 60 °C (140 °F)

dT > 3 °C/min. at T > 36 °C (96.8 °F)

Number of detectors per line max. 32

Operating voltage 7.6 V - 40 V DC

Quiescent current approx. 0.15 mA

Alarm current appro. 18 mA

Alarm indication 1 LED red

Electrostatic shielding Required

Operating temperature -20 °C to +50 °C(-4 °F to +122 °F)

IP rating (EN 60529) IP 65

Enclosure material Diecast aluminium, RAL5009-blue

Relative humidity (IEC721-3-3)

max. 15 at + 90 %no condensation

Weight 480 g (1.1 lbs)

Dimensions 122 x 80 x 69 mm (BxHxT)4.8 x 3.2 x 2.7 inch (BxHxT)