Upload
others
View
0
Download
0
Embed Size (px)
Citation preview
Indoor Environmental Quality
LEED® Leadership in Energy and Environmental Design
Goals:Improving ventilationManaging air contaminantsSpecifying less toxic materialsAllowing occupants to have control over their environmentsProviding daylight and viewsReducing background noise and providing good acoustics in schoolsMold Prevention (schools)
Indoor Environmental Quality
Indoor Environmental Quality
IEQ Prerequisite 1Minimum Indoor Air Quality
IntentTo establish minimum indoor air quality (IAQ) performance to enhance indoor air quality inbuildings, thus contributing to the comfort and well‐being of the occupants.
NC: REQSCHOOLS: REQCS: REQ
RequirementsNC, SCHOOLS & CSCASE 1 – Mechanically Ventilated Spaces
Meet the minimum requirements of Sections 4 through 7 of ASHRAE Standard 62.1‐ 2007, Ventilation for Acceptable Indoor Air Quality (with errata but without addenda).
Mechanical ventilation systems must be designed using the ventilation rate procedure or the applicable local code, whichever is more stringent.
IEQ Prerequisite 1Minimum Indoor Air Quality
RequirementsCSMechanical ventilation systems installed during core and shell construction must be capable of meeting projected ventilation levels based on anticipated future tenant requirements.
IEQ Prerequisite 1Minimum Indoor Air Quality
RequirementsNC, SCHOOLS & CSCASE 2 – Naturally Ventilated Spaces
Naturally ventilated buildings must comply with ASHRAE Standard 62.1‐2007, Paragraph 5.1 (with errata but without addenda).
IEQ Prerequisite 1Minimum Indoor Air Quality
ImplementationASHRAE 62.1–2007 establishes minimum requirements for ventilation air rates in various types of occupied zones and building ventilation systems.
The standard takes into account an area’s square footage, number of occupants and their activities, and the ventilation system.
IEQ Prerequisite 1Minimum Indoor Air Quality
ImplementationThere are three basic methods for ventilating buildings:Active Ventilation (i.e., mechanical ventilation)Passive Ventilation (i.e., natural ventilation)Mixed‐mode Ventilation (i.e., .both mechanical and natural ventilation)
IEQ Prerequisite 1Minimum Indoor Air Quality
ImplementationMechanically Ventilated SpacesShould use the ventilation rate procedure detailed In ASHRAE 62.1‐2007.
IEQ Prerequisite 1Minimum Indoor Air Quality
ImplementationNaturally Ventilated SpacesShould use the ventilation rate procedure detailed In ASHRAE 62.1‐2007, Section 5.1.
IEQ Prerequisite 1Minimum Indoor Air Quality
ImplementationAll naturally ventilated spaces must be within 25 feetof (and permanently open to) operable wall or roof openings to the outdoors; the operable area also must be at least 4% of the space’s net occupiable floor area.
IEQ Prerequisite 1Minimum Indoor Air Quality
ImplementationInterior spaces without direct openings to the outdoors can be ventilated through adjoining rooms if the openings between rooms are unobstructed and at least 8% or 25 square feet of the area is free.
IEQ Prerequisite 1Minimum Indoor Air Quality
ImplementationMixed‐Mode Ventilated SpacesFor mixed‐mode ventilated spaces and hybrid ventilation systems, meet the minimum ventilationrates required by Chapter 6 of ASHRAE 62.1–2007
IEQ Prerequisite 1Minimum Indoor Air Quality
Referenced StandardsAmerican National Standards Institute (ANIS)/ ASHRAE Standard 62.1–2007: Ventilation for Acceptable Indoor Air Quality
IEQ Prerequisite 1Minimum Indoor Air Quality
RequirementsNC, SCHOOLS & CSCase 1 – Mechanically Ventilated Spaces
Increase breathing zone outdoor air ventilation rates to all occupied spaces by at least 30% above the minimum rates required by ASHRAE Standard 62.1‐2007
IEQ Credit 2Increased Ventilation
NC: 1 pointSCHOOLS: 1 pointCS: 1 point
RequirementsNC, SCHOOLS & CSCase 2 – Naturally Ventilated Spaces
Design natural ventilation systems for occupied spaces to meet the recommendations set forth in theCarbon Trust “Good Practice Guide 237” (1998).
IEQ Credit 2Increased Ventilation
NC: 1 pointSCHOOLS: 1 pointCS: 1 point
RequirementsDetermine that natural ventilation is an effective strategy for the project by following the flow diagram process shown in Figure 1.18 of the Chartered Institution of Building Services Engineers (CIBSE) Applications Manual 10: 2005, Natural Ventilation in Non‐domestic Buildings.AND
Option 1Use diagrams and calculations to show that the design of the natural ventilation systems
OR
Option 2Use a macroscopic, multizone, analytic model to predict that room‐by‐room airflows will effectively naturally ventilate for at least 90% of occupied spaces.
IEQ Credit 2Increased Ventilation
NC: 1 pointSCHOOLS: 1 pointCS: 1 point
IEQ Prerequisite 2Environmental Tobacco Smoke (ETS) Ctrl
IntentNC & CSTo prevent or minimize exposure of building occupants, indoor surfaces and ventilation air distribution systems to environmental tobacco smoke (ETS).
NC: REQSCHOOLS: REQCS: REQ
IEQ Prerequisite 2Environmental Tobacco Smoke (ETS) Ctrl
IntentSCHOOLSTo eliminate exposure of building occupants, indoor surfaces, and ventilation air distribution systems to environmental tobacco smoke (ETS).
NC: REQSCHOOLS: REQCS: REQ
RequirementsCase 1 ‐ All ProjectsOption 1Prohibit smoking in the building.
Locate any exterior designated smoking areas at least 25 feetaway from entries, outdoor air intakes and operable windows.
IEQ Prerequisite 2Environmental Tobacco Smoke (ETS) Control
RequirementsOROption 2Prohibit smoking in the building except in designated smoking areas.
Prohibit on‐property smoking within 25 feet of entries, outdoor air intakes and operable windows.
IEQ Prerequisite 2Environmental Tobacco Smoke (ETS) Control
Requirements
IEQ Prerequisite 2Environmental Tobacco Smoke (ETS) Ctrl
Directly exhausted to the outdoorsEnclosed with impermeable deck‐to‐deck partitionsOperate exhaust sufficient to create a negative pressure differential with the surrounding spaces of at least an average of 5 Pascals (Pa) (0.02 inches of water gauge) and a minimum of 1 Pa when the doors to the smoking rooms are closed.
RequirementsCase 2 – Residential and Hospitality
Prohibit smoking in all common areas of the building.Prohibit on‐property smoking within 25 feet of entries, outdoor air intakes and operable windows.Weather‐strip all exterior doors and operable windows in the residential units to minimize leakage from outdoors.Minimize uncontrolled pathways for ETS transfer between individual residential units by sealing penetrations in walls, ceilings and floors in the residential units and by sealing vertical chases adjacent to the units.Weather‐strip all doors in the residential units leading to common hallways to minimize air leakage into the hallway.Demonstrate acceptable sealing of residential units by a blower door test conducted in accordance with ANSI/ASTM‐E779‐03, Standard Test Method for Determining Air Leakage Rate By Fan Pressurization.
IEQ Prerequisite 2Environmental Tobacco Smoke (ETS) Control
ImplementationFor all projects, prohibit smoking within the building.
Post signage designating smoking and nonsmoking areas and ensure that the 25‐foot setback requirements are met for all doors, operable windows,and building air intakes.
If smoking areas exist within the building, install separate and isolated ventilation systems.
IEQ Prerequisite 2Environmental Tobacco Smoke (ETS) Control
ImplementationResidential and Hospitality Projects:
Tight ConstructionSeal PenetrationsSeal vertical ChasesWeather‐strip doors leading to common hallwaysConduct Blower Door Test (ASTM E779‐03)
IEQ Prerequisite 2Environmental Tobacco Smoke (ETS) Control
Referenced StandardsAmerican National Standards Institute (ANSI)/ASTME–779–03, Standard Test Method for Determining Air Leakage Rate by Fan Pressurization
Residential Manual for Compliance with California’s 2001 Energy Efficiency Standards (For Low Rise Residential Buildings), Chapter 4
IEQ Prerequisite 2Environmental Tobacco Smoke (ETS) Control
IEQ Prerequisite 3Minimum Acoustical Performance
IntentIEQ Prerequisite 3To provide classrooms that are quiet so that teachers can speak to the class without straining their voices and students can effectively communicate with each other and the teacher.
IEQ Credit 9To provide classrooms that facilitate better teacher‐to‐student and student‐to‐student communication through effective acoustical design.
NC: NASCHOOLS: REQCS: NA
IEQ Credit 9Enhanced Acoustical Performance
NC: NASCHOOLS: REQCS: NA
RequirementsIEQ Prerequisite 3Meet reverberation time requirements as specified in ANSI Standard S12.60‐2002, Acoustical Performance Criteria, Design Requirements and Guidelines for Schools.
Achieve a maximum background noise level from HVAC systems in classrooms and other core learning spaces of 45 dBA.
AND
IEQ Prerequisite 3Minimum Acoustical Performance
IEQ Credit 9Enhanced Acoustical Performance
RequirementsCase 1 ‐ Classrooms and Core Learning Spaces <20,000 CFOption 1Confirm that 100% of all ceiling areas (excluding lights, diffusers and grilles) in all classrooms and core learning spaces are finished with a material that has a Noise Reduction Coefficient (NRC) of 0.70 or higher.
OR
IEQ Prerequisite 3Minimum Acoustical Performance
IEQ Credit 9Enhanced Acoustical Performance
RequirementsOption 2Confirm that the total area of acoustical wall panels, ceiling finishes, and other sound absorbent finishes equals or exceeds the total ceiling area of the room (excluding lights, diffusers and grilles) Materials must have an NRC of 0.70 or higher to be included in the calculation.
IEQ Prerequisite 3Minimum Acoustical Performance
IEQ Credit 9Enhanced Acoustical Performance
RequirementsCase 2 ‐ Classrooms and Core Learning Spaces ≥ 20,000 CF
Confirm through calculations described in ANSI Standard S12.60‐2002 that all classrooms and core learning spaces greater than or equal to 20,000 cubic feet are designed to have a reverberation time of 1.5 seconds or less.
IEQ Prerequisite 3Minimum Acoustical Performance
IEQ Credit 9Enhanced Acoustical Performance
RequirementsIEQ Credit 9Meet the sound transmission class (STC) requirements of ANSI Standard S12.60‐2002 for building shells and partitions within core learning spaces. Windows within core learning spaces must have an STC of at least 35.
Design HVAC systems that do not exceed 40 dBA in all core learning spaces.
IEQ Prerequisite 3Minimum Acoustical Performance
IEQ Credit 9Enhanced Acoustical Performance
ImplementationDesign all classrooms and other core learning spaces to have low background noise and a short reverberation time.
Select wall assemblies that meet the STC requirements.
IEQ Prerequisite 3Minimum Acoustical Performance
IEQ Credit 9Enhanced Acoustical Performance
Referenced StandardAmerican National Standards Institute (ANSI)/ASHRAE Standard S12.60–2002, Acoustical Performance Criteria, Design Requirements, and Guidelines for Schools
ASHRAE Handbook, Chapter 47, Sound and Vibration Control, 2003 HVAC Applications
IEQ Prerequisite 3Minimum Acoustical Performance
IEQ Credit 9Enhanced Acoustical Performance
IEQ Credit 1Outdoor Air Delivery Monitoring
IntentTo provide capacity for ventilation system monitoring to help promote occupant comfort and well‐being.
NC: 1 pointSCHOOLS: 1 pointCS: 1 point
RequirementsInstall permanent monitoring systems to ensure that ventilation systems maintain design minimum requirements.
IEQ Credit 1Outdoor Air Delivery Monitoring
RequirementsConfigure all monitoring equipment to generate an alarm when the airflow values or carbon dioxide (CO2) levels vary by 10% or more from the design values via either a building automation system alarm to the building operator or a visual or audible alert to the building occupants.
AND
IEQ Credit 1Outdoor Air Delivery Monitoring
RequirementsCASE 1 ‐ FOR MECHANICALLY VENTILATED SPACESDensely Occupied Spaces >= 25 people per 1000 SF
Monitor carbon dioxide concentrationsCO2 monitoring ‐ between 3 feet and 6 feet AFF
Non‐densely occupied spacesDirect outdoor airflow measurement device capable of measuring the minimum outdoor airflow rate with an accuracy of plus or minus 15% of the design minimum outdoor air rate, as defined by ASHRAE 62.1‐2004.
IEQ Credit 1Outdoor Air Delivery Monitoring
RequirementsCASE 1 ‐ FOR NATURALLY VENTILATED SPACES
Monitor carbon dioxide concentrations
CO2 monitoring ‐ between 3 feet and 6 feet AFF
IEQ Credit 1Outdoor Air Delivery Monitoring
ImplementationMonitor the outdoor airflow rate as a way to confirm that HVAC equipment is providing the required ventilation rate.
C02 monitoring should be applied to both densely occupied mechanically ventilated and all naturally ventilated spaces.
Core & Shell projects can consider including C02 sensors in tenant spaces
IEQ Credit 1Outdoor Air Delivery Monitoring
ImplementationFeed outdoor air monitoring information to the BAS
IEQ Credit 1Outdoor Air Delivery Monitoring
Referenced StandardsAmerican National Standards Institute (ANSI)/ASHRAE Standard 62.1–2007: Ventilation for Acceptable Indoor Air Quality
IEQ Credit 1Outdoor Air Delivery Monitoring
IEQ Credit 3.1Construction IAQ Mgmt Plan, During Construction
IntentTo reduce indoor air quality (IAQ) problems resulting from construction or renovation and promote the comfort and well‐being of construction workers and building occupants.
NC: 1 pointSCHOOLS: 1 pointCS: 1 point
RequirementsNC, SCHOOLS & CS
During construction meet or exceed the recommended Control Measures of the Sheet Metal and Air Conditioning Contractors National Association (SMACNA) IAQ Guidelines for Occupied Buildings under Construction, 1995, Chapter 3.Protect stored on‐site or installed absorptive materials from moisture damage.If permanently installed air handlers are used during construction, filtration media with a Minimum Efficiency Reporting Value (MERV) of 8 shall be used at each return air grille, as determined by ASHRAE 52.2‐1999. Replace all filtration media immediately prior to occupancy.
IEQ Credit 3.1Construction IAQ Mgmt Plan, During Construction
RequirementsSCHOOLSProhibit smoking inside the building and within 25 feet of building entrances once the building is enclosed.
IEQ Credit 3.1Construction IAQ Mgmt Plan, During Construction
ImplementationAdopt an IAQ management plan to protect the HVAC system during construction, control pollutant sources and interrupt contamination pathways.
Sequence the installation of materials
Coordinate with EQ Credits 3.2 and 5
Avoid using permanently installed air handlers for temporary heating/cooling during construction
IEQ Credit 3.1Construction IAQ Mgmt Plan, During Construction
ImplementationThe referenced SMACNA standard recommends control measures in five areas:
HVAC ProtectionSource ControlPathway InterruptionHousekeepingScheduling
(Page 455)
IEQ Credit 3.1Construction IAQ Mgmt Plan, During Construction
Referenced StandardsSheet Metal and Air Conditioning Contractors National Association (SMACNA) IAQ
American National Standards Institute (ANSI)/ASHRAE Standard 52.2–1999: Method of Testing General Ventilation Air‐Cleaning Devices for Removal Efficiency by Particle Size
IEQ Credit 3.1Construction IAQ Mgmt Plan, During Construction
IEQ Credit 3.2Construction IAQ Mgmt Plan, Before Occupancy
IntentTo reduce indoor air quality (IAQ) problems resulting from construction or renovation to promote the comfort and well‐being of construction workers and building occupants.
NC: 1 pointSCHOOLS: 1 pointCS: NA
RequirementsOPTION 1 ‐ Flush‐Out
PATH 1After construction ends, prior to occupancy and with all interior finishes installed, perform a building flush‐out by supplying a total air volume of 14,000 cu.ft. of outdoor air per sq.ft. of floor area while maintaining an internal temperature of at least 60°F and relative humidity no higher than 60%.
OR
IEQ Credit 3.2Construction IAQ Mgmt Plan, Before Occupancy
RequirementsPATH 2If occupancy is desired prior to completion of the flush‐out, the space may be occupied following delivery of a minimum of :3,500 cu.ft. of outdoor air per sq. ft. of floor area to the space.
Once a space is occupied, it shall be ventilated at a minimum rate of0.30 cfm/sq.ft. of outside air or the design minimum outside air rate determined in EQ Prerequisite 1, whichever is greater.
During each day of the flush‐out period, ventilation shall begin a minimum of three hours prior to occupancy and continue during occupancy.
These conditions shall be maintained until a total of 14,000 cu.ft./sq.ft. of outside air has been delivered to the space.
IEQ Credit 3.2Construction IAQ Mgmt Plan, Before Occupancy
RequirementsOPTION 2 ‐ Air Quality Testing
Conduct testing, after construction ends and prior to occupancyDemonstrate contaminate levels are not exceededPerform additional flush‐out & Resample if necessary
IEQ Credit 3.2Construction IAQ Mgmt Plan, Before Occupancy
RequirementsAir Samples:Prior to occupancy, but normal occupied hoursAll interior finishes installed, workstations and partitions are encouraged but not requiredNot less than one sample per 25,000 sf.3 feet to 6 feet AFF over a minimum 4‐hour period
IEQ Credit 3.2Construction IAQ Mgmt Plan, Before Occupancy
IEQ Credit 3.2Construction IAQ Mgmt Plan, Before Occupancy
ImplementationOPTION 1 – Flush Out ProcedureUses HVAC to evacuate air borne contaminatesAll construction work has ended, including punch‐list items.Cleaning has finalizedFinal test and balance of HVAC and controls are functionalCommissioning may occur during Flush‐Out
IEQ Credit 3.2Construction IAQ Mgmt Plan, Before Occupancy
ImplementationOPTION 2 – Air Testing ProcedureThe baseline IAQ testing approach to credit compliance provides confirmation that major contaminants are below recognized acceptable levels prior to occupancy.
IEQ Credit 3.2Construction IAQ Mgmt Plan, Before Occupancy
Referenced StandardsU.S. Environmental Protection Agency Compendium of Methods for the Determination of Air Pollutants in Indoor Air
IEQ Credit 3.2Construction IAQ Mgmt Plan, Before Occupancy
IEQ Credit 4.1, Low Emitting MaterialsAdhesives and Sealants
IntentTo reduce the quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort and well‐being of installers and occupants.
NC: 1 pointSCHOOLS: 1 pointCS: 1 point
RequirementsNC & CSAll adhesives and sealants used on the interior of the building (defined as inside of the weatherproofing system and applied on‐site) shall comply with the requirements of the following reference standards:Adhesives, Sealants and Sealant Primers:South Coast Air Quality Management District (SCAQMD) Rule #1168.
Aerosol Adhesives: Green Seal Standard for Commercial Adhesives GS‐36
IEQ Credit 4.1, Low Emitting MaterialsAdhesives and Sealants
RequirementsSCHOOLSAll adhesives and sealants installed in the building interior (defined as inside the weatherproofing system and applied on‐site) must meet the testing and product requirements of the California Department of Health Services Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small‐Scale Environmental Chambers, including 2004 Addenda.
Schools projects may choose from IEQ Credits 4.1 ‐ 4.6 for a maximum of 4 points.
IEQ Credit 4.1, Low Emitting MaterialsAdhesives and Sealants
ImplementationThe amount of VOCs permitted in a given volume of a product is limited. The threshold limits and content within a particular product are generally expressed in grams per liter (g/L).
IEQ Credit 4.1, Low Emitting MaterialsAdhesives and Sealants
Referenced StandardsNC and CSSouth Coast Air Quality Management District (SCAQMD) Amendment to South Coast Rule 1168, VOC limits effective January 7, 2005
Green Seal Standard 36 (GS‐36), effective October 19, 2000
SchoolsCalifornia Department of Health Services Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small Scale Environmental Chambers, including 2004 Addenda
IEQ Credit 4.1, Low Emitting MaterialsAdhesives and Sealants
Referenced StandardsSchoolsCalifornia Department of Health Services Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small Scale Environmental Chambers, including 2004 Addenda
IEQ Credit 4.1, Low Emitting MaterialsAdhesives and Sealants
IEQ Credit 4.2, Low Emitting MaterialsPaints and Coatings
IntentTo reduce the quantity of indoor air contaminants that are odorous, irritating, and/or harmful to the comfort and well‐being of installers and occupants.
NC: 1 pointSCHOOLS: 1 pointCS: 1 point
RequirementsNC and CSPaints and coatings used in the building interior must meet the following conditions:Architectural paints and coatings must comply withGreen Seal Standard GS‐11
Anticorrosive and antirust paints must comply withGreen∙ Seal Standard GC‐03
Clear wood finishes, floor coatings, stains, primers, and shellacs applied to interior elements must comply with South Coast Air Quality Management District (SCAQMD) Rule 1113
IEQ Credit 4.2, Low Emitting MaterialsPaints and Coatings
RequirementsSchoolsAll paints and coatings used in the building interior must meet the testing and product requirements of the California Department of Health Services Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small‐Scale Environmental Chambers, including 2004 Addenda.
IEQ Credit 4.2, Low Emitting MaterialsPaints and Coatings
ImplementationInclude VOC limits or identify specific products within the project specifications.
For LEED for Schools projects, specify only those materials that meet the requirements of the referenced standard.
IEQ Credit 4.2, Low Emitting MaterialsPaints and Coatings
Referenced StandardsNC and CS,Green Seal Standard GS‐11, Paints, First Edition, May 20, 1993
Green Seal Standard GC‐03, Anti∙Corrosive Paints, Second Edition, January 7, 1997
South Coast Air Quality Management District (SCAQMD) Rule 1113 Architectural Coatings, effectiveJanuary I, 2004
IEQ Credit 4.2, Low Emitting MaterialsPaints and Coatings
IEQ Credit 4.3, Low Emitting MaterialsFlooring Systems
IntentTo reduce the quantity of indoor air contaminants that are odorous, irritating, and/or harmful to the comfort and well‐being of installers and occupants.
NC: 1 pointSCHOOLS: 1 pointCS: 1 point
RequirementsNC & CSOPTION 1All flooring must comply with the following as applicable to the project scope:
All carpet installed in the building interior must meet the testing and product requirements of the Carpet and Rug Institute Green Label Plus program.
IEQ Credit 4.3, Low Emitting MaterialsFlooring Systems
RequirementsAll carpet cushion installed in the building interior must meet the requirements of the Carpet and Rug Institute Green Label program.
All carpet adhesive must meet the requirements of IEQ Credit 4.1: Adhesives and Sealants, which includes a volatile organic compound (VOC) limit of 50 g/L.
IEQ Credit 4.3, Low Emitting MaterialsFlooring Systems
RequirementsAll hard surface flooring must be certified as compliant with the FloorScore standard (current as of the date of this rating system, or more stringent version) by an independent third‐party.
IEQ Credit 4.3, Low Emitting MaterialsFlooring Systems
RequirementsFlooring products covered by FloorScore include vinyl, linoleum, laminate flooring, wood flooring, ceramic flooring, rubber flooring and wall base.
IEQ Credit 4.3, Low Emitting MaterialsFlooring Systems
RequirementsAn alternative compliance path using FloorScore is acceptable for credit achievement:
100% of the non‐carpet finished flooring must be FloorScore‐certified and must constitute at least 25% of the finished floor area.
Examples of unfinished flooring include floors in mechanical rooms, electrical rooms and elevator service rooms.
IEQ Credit 4.3, Low Emitting MaterialsFlooring Systems
RequirementsConcrete, wood, bamboo and cork floor finishes such as sealer, stain and finish must meet the requirements of South Coast Air Quality Management District (SCAQMD) Rule 1113, Architectural Coatings, rules in effect on January 1, 2004.
IEQ Credit 4.3, Low Emitting MaterialsFlooring Systems
RequirementsTile setting adhesives and grout must meet South Coast Air Quality Management District (SCAQMD) Rule 1168. VOC limits correspond to an effective date of July 1, 2005 and rule amendment date of January 7, 2005.
IEQ Credit 4.3, Low Emitting MaterialsFlooring Systems
RequirementsOPTION 2All flooring elements installed in the building interior must meet the testing and product requirements of the California Department of Health Services Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small‐Scale Environmental Chambers, including 2004 Addenda.
IEQ Credit 4.3, Low Emitting MaterialsFlooring Systems
ImplementationInclude certification requirements and VOC limits and/or identify specific products within the project specifications.
For LEED for Schools projects, specify only those materials that meet the requirements of the referenced standard
IEQ Credit 4.3, Low Emitting MaterialsFlooring Systems
Referenced StandardsThe Carpet and Rug Institute (CRI) Green Label Plus Testing Program
SCAQMD Rule 1168, VOC Limits
SCAQMD Rule 1113, Architectural Coatings
FLOORScore™ Program
California Department of Health Services Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small Scale Environmental Chambers, including 2004 Addenda
IEQ Credit 4.3, Low Emitting MaterialsFlooring Systems
IEQ Credit 4.4, Low Emitting MaterialsComposite Wood and Agrifiber Products
IntentTo reduce the quantity of indoor air contaminants that are odorous, irritating, and/or harmful to the comfort and well‐being of installers and occupants.
NC: 1 pointSCHOOLS: 1 pointCS: 1 point
RequirementsNC & CSComposite wood and agrifiber products used in the interior of the building must contain no added urea‐formaldehyde resins.
Laminate adhesives used to fabricate on‐site and shop‐applied composite wood and agrifiber assemblies must not contain added urea‐formaldehyde resins.
IEQ Credit 4.4, Low Emitting MaterialsComposite Wood and Agrifiber Products
RequirementsSCHOOLSAll composite wood and agrifiber products installed in the building interior must meet the testing and product requirements of the California Department of Health Services Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using
IEQ Credit 4.4, Low Emitting MaterialsComposite Wood and Agrifiber Products
ImplementationInclude requirements or identify specific products within the project specifications.
For LEED for Schools projects, specify only those materials that meet the requirements of the referenced standard.
IEQ Credit 4.4, Low Emitting MaterialsComposite Wood and Agrifiber Products
Referenced StandardsCalifornia Department of Health Services Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small Scale Environmental Chambers, including 2004 Addenda
IEQ Credit 4.4, Low Emitting MaterialsComposite Wood and Agrifiber Products
IEQ Credit 4.5, Low Emitting MaterialsFurniture and Seating
IntentTo reduce the quantity of indoor air contaminants that are odorous, irritating, and/or harmful to the comfort and well‐being of installers and occupants.
NC: NASCHOOLS: 1 pointCS: NA
RequirementsAll new classroom furniture must meet one of the following three options:
Option 1:The furniture must be GREENGUARD Children and Schools certified.
IEQ Credit 4.5, Low Emitting MaterialsFurniture and Seating
RequirementsOption 2:Calculated indoor air concentrations must be less than or equal to those listed below, as determined by a procedure based on the EPA Environmental Technology Verification (ETV) Large Chamber Test Protocol for Measuring Emissions of VOCs and Aldehydes (September 1999) testing protocol conducted by an independent testing laboratory.
IEQ Credit 4.5, Low Emitting MaterialsFurniture and Seating
RequirementsOPTION 3Calculated indoor air concentrations must be less than of equal to those established below for furniture systems and seating, as determined by a procedure based on the ANSI/BIFMA M7.1‐2007 and ANSI/BIFMA X7.1‐2007 testing protocol conducted by an independent testing laboratory.
IEQ Credit 4.5, Low Emitting MaterialsFurniture and Seating
IEQ Credit 4.5, Low Emitting MaterialsFurniture and Seating
ImplementationSpecify only those materials that meet the requirements of one of the referenced standards.
IEQ Credit 4.5, Low Emitting MaterialsFurniture and Seating
Referenced StandardsANSI/BIFMA X7.1‐2007, Standard for Formaldehyde and TVOC Emissions of low‐Emitting Office Furniture Systems and Seating
Environmental Technology Verification (ETV) large Chamber Test Protocol for Measuring Emissions of VOCs and Aldehydes, effective September 1999, U.S. EPA
GREENGUARD Certification Program
IEQ Credit 4.5, Low Emitting MaterialsFurniture and Seating
IEQ Credit 4.6, Low Emitting MaterialsCeiling and Wall Systems
IntentTo reduce the quantity of indoor air contaminants that are odorous, irritating, and/or harmful to the comfort and well‐being of installers and occupants.
NC: NASCHOOLS: 1 pointCS: NA
RequirementsAll gypsum board, insulation, acoustical ceiling systems, and wall coverings installed must meet the testing and product requirements of the California Department of Health Services Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small‐Scale Environmental Chambers, including 2004 Addenda.
IEQ Credit 4.6, Low Emitting MaterialsCeiling and Wall Systems
ImplementationSpecify only those materials that meet the requirements of the referenced standard.
IEQ Credit 4.6, Low Emitting MaterialsCeiling and Wall Systems
Referenced StandardsCalifornia Department of Health Services Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small Scale Environmental Chambers, including 2004 Addenda
IEQ Credit 4.6, Low Emitting MaterialsCeiling and Wall Systems
IEQ Credit 5Indoor Chemical and Pollutant Source Ctrl
IntentTo minimize building occupant exposure to potentially hazardous particulates and chemical pollutants.
NC: 1 pointSCHOOLS: 1 pointCS: 1 point
RequirementsUse entryway systems, at least 10 feet long in the direction of travel, at all regularly used entrances.
Exhaust all hazardous chemical storage and use areas.Install MERV 13 or higher filters in mechanical ventilation systems.
Provide appropriate containment for appropriate disposal of hazardous liquid waste.
IEQ Credit 5Indoor Chemical and Pollutant Source Control
ImplementationIncorporate permanent entryway systems at all high‐traffic entrances.
Locate and physically separate chemical storage areas (including areas with high‐volume copy. print, and fax equipment) in enclosed rooms away from regularly occupied adjacent spaces, and equip these areas with a dedicated exhaust system.
IEQ Credit 5Indoor Chemical and Pollutant Source Control
ImplementationDesign the mechanical system to accommodateMERV 13 filtration, and install new filters immediately prior to occupancy.
In areas where chemical concentrate mixing occurs (such as housekeeping areas and science laboratories), install appropriate liquid waste containment.
IEQ Credit 5Indoor Chemical and Pollutant Source Control
Referenced StandardsANSI/ASHRAE Standard 52.2 ‐1999, Method of Testing General Ventilation Air‐Cleaning Devices for RemovalEfficiency by Particle Size
IEQ Credit 5Indoor Chemical and Pollutant Source Control
IEQ Credit 6.1Controllability of Systems: Lighting
IntentTo provide a high level of lighting system control by individual occupants or groups in multi‐occupant spaces (such as classrooms and conference areas) and promote occupants productivity, comfort, and well‐being.
NC: 1 pointSCHOOLS: 1 pointCS: NA
RequirementsNCInstall individual lighting controls for at least 90% of occupants and provide group lighting controls for all shared multi‐occupant spaces.
IEQ Credit 6.1Controllability of Systems: Lighting
RequirementsSchoolsInstall individual lighting controls for 90% of occupants within administrative and other nonclassroom areas.
For learning spaces (including classrooms, gymnasiums, studios, and so on), provide group lighting controls. In classrooms, there must be at least two lighting modes for general illumination and AV.
IEQ Credit 6.1Controllability of Systems: Lighting
ImplementationNC & CSLighting controls in multi‐occupant spaces must sufficiently permit adjustments to meet the needs and preferences of the occupants.
Ninety percent or more of the occupants located at work spaces intended for individual use must have task lighting.
IEQ Credit 6.1Controllability of Systems: Lighting
ImplementationSCHOOLSClassrooms must have a minimum of two lighting scenes, or presets. One must be configured for general use, and the other should accommodate a typical A/V presentation.
IEQ Credit 6.1Controllability of Systems: Lighting
IEQ Credit 6.2 (IEQ C6 CS)Controllability of Sys: Thermal Comfort
IntentTo provide a high level of thermal comfort system control by individual occupants or groups in multi‐occupant spaces (such as classrooms or conference areas) and promote occupants' productivity, comfort. and wellbeing.
NC: 1 pointSCHOOLS: 1 pointCS: 1 point
RequirementsInstall comfort controls for at least 50% of building occupants.
Provide comfort system controls for( all shared multi‐occupant spaces.
LEED Core & Shell projects that do not include thermal comfort systems cannot earn this credit.
IEQ Credit 6.2 (IEQ C6 CS)Controllability of Systems: Thermal Comfort
ImplementationProvide individuals and groups the ability to adjust their thermal environment within the space.
Design the comfort systems so that 50% (or more) of individual workstations have thermal comfort controls.
Confirm that all shared multi‐occupant spaces have thermal comfort control.
IEQ Credit 6.2 (IEQ C6 CS)Controllability of Systems: Thermal Comfort
Referenced StandardsASHRAE 62.1‐2007: Ventilation for Acceptable Indoor Air Quality
ASHRAE 55‐2004, Thermal Environmental Conditions for Human Occupancy
IEQ Credit 6.2 (IEQ C6 CS)Controllability of Systems: Thermal Comfort
IEQ Credit 7.1 (IEQ C7 CS)Thermal Comfort: Design
IntentTo provide a comfortable thermal environment that promotes occupant productivity and well‐being.
NC: 1 pointSCHOOLS: 1 pointCS: 1 point
RequirementsDesign the HVAC system to comply with ASHRAE 55‐2004.
IEQ Credit 7.1 (IEQ C7 CS)Thermal Comfort: Design
RequirementsSCHOOLSFor natatoriums (swimming pool buildings), comply with "Typical Natatorium Design Conditions," defined in Chapter 4 of the ASHRAE HVAC Applications Handbook, 2003 Edition.
IEQ Credit 7.1 (IEQ C7 CS)Thermal Comfort: Design
RequirementsCSThe base building mechanical systems must allow for the tenant build out to comply with ASHRAE 55‐2004.
If the HVAC system is not included as part of the Core and shell construction, this credit cannot be earned.
IEQ Credit 7.1 (IEQ C7 CS)Thermal Comfort: Design
ImplementationThe HVAC designer evaluates the anticipated occupant within the space and designs the heating, cooling, and ventilation strategies accordingly.
The activity level and attire of the occupants directly affect how comfortable people are within a given environment.
IEQ Credit 7.1 (IEQ C7 CS)Thermal Comfort: Design
ImplementationSix primary comfort factors when designing a comfortable building:• Metabolic rate (activity level);• Clothing insulation• Air temperature• Radiant temperature• Air speed• Humidity
IEQ Credit 7.1 (IEQ C7 CS)Thermal Comfort: Design
Referenced StandardsASHRAE 55‐2004, Thermal Comfort Conditions for Human Occupancy
Chartered Institute of Building Services Engineers (CIBSE) Applications Manual 10‐2005, Natural Ventilation in Non‐Domestic Buildings
Schools: ASHRAE HVAC Applications Handbook, 2003 Edition, Chapter 4 (Places of Assembly), "Typical Natatorium Design Conditions"
IEQ Credit 7.1 (IEQ C7 CS)Thermal Comfort: Design
IEQ Credit 7.2Thermal Comfort: Verification
IntentTo provide for the assessment of building occupants' thermal comfort over time.
NC: 1 pointSCHOOLS: 1 pointCS: NA
RequirementsConduct an anonymous thermal comfort survey of building occupants within 6 to 18 months after the building has been occupied, and develop a plan for corrective action.
For new construction, also provide a permanent monitoring system to measure and record environmental variables.
Residential projects cannot earn this credit.
IEQ Credit 7.2Thermal Comfort: Verification
ImplementationCreate and administer a survey about thermal comfort conditions in person, over the phone, over networked computers, or on paper.
Have in place a plan for corrective action.
New Construction (additional requirement):Install metering equipment to record environmental variables
IEQ Credit 7.2Thermal Comfort: Verification
Referenced StandardsASHRAE 55‐2004, Thermal Environmental Conditions for Human Occupancy
IEQ Credit 7.2Thermal Comfort: Verification
IEQ Credit 8.1Daylight and Views: Daylight
IntentTo provide for the building occupants with a connection between indoor spaces and the outdoors through the introduction of daylight and views into the regularly occupied areas of the building.
NC: 1 pointSCHOOLS: 1‐3 ptsCS: 1 point
Requirements
IEQ Credit 8.1Daylight and Views: Daylight
Requirements
IEQ Credit 8.1Daylight and Views: Daylight
Implementation
IEQ Credit 8.1Daylight and Views: Daylight
ImplementationShallow floor plates, courtyards, atriums, clerestory windows, or skylights.
IEQ Credit 8.1Daylight and Views: Daylight
ImplementationFor Side Lighting Daylight Zone:
The window‐to‐floor ratio multiplied by the visible light transmittance must be between 0.150 and 0.180 to qualify.
Only window areas above 30 inches can count in the calculation.
The ceiling obstruction rules sound complicated, but they're pretty simple: If a portion of the ceiling obstructs the entrance of daylight, the related floor area must be excluded from the compliant floor area.
IEQ Credit 8.1Daylight and Views: Daylight
ImplementationFor Top Lighting Daylight Zone:The daylight zone under a skylight is the outline of the opening beneath the skylight plus, in each direction, the lesser of three options:Seventy percent of the ceiling height
One‐half the distance to the edge of the nearest skylight (to prevent double counting of floor area from multiple skylights) or
The distance to any permanent opaque partition (such as a built∙in bookshelf) farther away than 70% of the distance between the top of the partition and the ceiling.
IEQ Credit 8.1Daylight and Views: Daylight
ImplementationRoof skylights must cover between 3% and 6% of the roof area, the distance between the skylights must not be more than 1.4 times the ceiling height. and the glazing must have a minimum 0.5 VLT.
If a skylight diffuser is used, it must have a measured haze value of greater than 90%.
IEQ Credit 8.1Daylight and Views: Daylight
Referenced StandardsASTM D1003‐07E1, Standard Test Method for Haze and Luminous Transmittance of Transparent Plastics
IEQ Credit 8.1Daylight and Views: Daylight
IEQ Credit 8.2Daylight and Views: Views
IntentTo provide building occupants a connection to the outdoors through the introduction of daylight and views into the regularly occupied areas of the building.
NC: 1 pointSCHOOLS: 1 pointCS: 1 point
RequirementsProvide views to the exterior for 90% of all regularly occupied spaces.
IEQ Credit 8.2Daylight and Views: Views
RequirementsProvide views to the exterior for 90% of all regularly occupied spaces.
IEQ Credit 8.2Daylight and Views: Views
ImplementationLocate open seating areas near the exterior to maximize views for all occupants. Provide glazing for core offices and multi‐occupant spaces to enhance views.
A direct line of sight must exist through vision glazing between 30 and 90 inches above the floor.
IEQ Credit 8.2Daylight and Views: Views
ImplementationSketch a line of sight at 42 inches (typical seated eye height) across the section (looking at it from the side) to establish eye height and any obstruction to the perimeter glazing.
In plan view (looking at it from the top), the area is within sight lines drawn from perimeter vision glazing.
IEQ Credit 8.2Daylight and Views: Views
ImplementationDouble windows count too. The line of sight can be drawn through interior glazing as long as the occupant can see out another window.
The compliant area depends on the space use type.Private offices: The entire square footage of the office is counted if more than 75% of the area has a direct line of sight.
Multi‐occupant spaces: Include only the actual square footage with a direct fine of sight.
IEQ Credit 8.2Daylight and Views: Views
IEQ Credit 10Mold Prevention
IntentTo reduce the potential presence of mold in schools through preventive design and construction measures.
NC: NASCHOOLS: 1 pointCS: NA
RequirementsAchieve IEQ Credit 3.1, Construction Indoor Air Quality Management Plan, During Construction; IEQ Credit 7.1, Thermal Comfort, Design; and lEQ Credit 7.2 Thermal Comfort, Verification.
Design the HVAC system to limit relative humidity to 60% or less at all times.
Develop an ongoing IAQ management program based on the EPA publication Building Air Quality: A Guide for Building Owners and Facility Managers.
IEQ Credit 10Mold Prevention
ImplementationEliminate the potential for condensation.
Pay special attention to known generators of condensation.
Prevent mold during unoccupied periods.
Address floods and leaky or failed equipment.
Design for mold prevention.
IEQ Credit 10Mold Prevention
Referenced StandardsBuilding Air Quality; A Guide of Building Owners and Facility Managers. U.S. Environmental Protection Agency, December 1991
IEQ Credit 10Mold Prevention