22
www.lennoxemea.com APPLICATION GUIDE DUCTABLE AIR TREATMENT UNIT INALTO 2581 - 27851 W 381 - 5668 m 3 /h INALTO-AGU-1801-E Check ongoing validity of certicate : www.eurovent-certication.com

INALTO - Lenergy Magyarország Kft. | Energetika

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

www.lennoxemea.com

APPLICATIONGUIDE

DUCTABLE AIR TREATMENT UNIT

INALTO2581 - 27851 W381 - 5668 m3/h

INALTO-AGU-1801-E

Check ongoing validity of certifi cate :www.eurovent-certifi cation.com

• 1 •

INALTO-V / INALTO-DS-VINALTO-H / INALTO-DS-H

INALTO A 05 R H DS

A

05

R

H

DS

Application Guide /INALTO-AGU-1801-E

DUCTABLE AIR TREATMENT UNIT

Unit typeDuctable air treatment unit

StructureSingle or double skin galvanized steel sheet

Fan groupDouble-inlet centrifugal fans

MotorSingle-phase asynchronous Synchronous EC Motor

Air fi lterFiltering polyester fabric enclosed within a metal frame

CoilCopper pipe into aluminium fi nsin continuous block

Hydraulic connectionLeft (when viewing the air supply)

Certifi cationEurovent

Terminal board included

A = 3-speed AC fanE = EC fan

Size

Hydraulic connectionsR = Right / S = Left

H = Horizontal installationV = Vertical installation

Double skin

MODEL NUMBER DESCRIPTION

• 2 • Application Guide / INALTO-AGU-1801-E

UNIT DESCRIPTIONThe ductable air treatment units are available in 2 versions and 7 sizes. Units are extremely suitable for small centralized conditioning systems connected by a small ducting network. The small height of these units, make them the convenient solution for false ceiling installation.

GENERAL DESCRIPTION

INALTO A__ _ H AC motor, horizontal installation, single skin version

INALTO E__ _ H EC motor ,horizontal installation, single skin version

INALTO A__ _ V AC motor, vertical installation, single skin version

INALTO E__ _ V EC motor, vertical installation, single skin version

INALTO A__ _ H DS AC motor, horizontal installation, double skin version

INALTO E__ _ H DS EC motor ,horizontal installation, double skin version

INALTO A__ _ V DS AC motor, vertical installation, double skin version

INALTO E__ _ V DS EC motor, vertical installation, double skin version

VERSIONS

STANDARD UNIT COMPOSITION

Structure

INALTO - STANDARD VERSIONMade of galvanized steel, it is insulated in all parts in direct contact with the conditioned air. Insulated condensate tray made of galvanised steel, complete with drain plug for complete drainage. Ceiling-anchoring slots for easy fi xing and levelling of the unit.

INALTO DS - DOUBLE SKIN VERSIONDouble skin panels 15 mm thickness in galvanized steel inside and in white pre-painted galvanized steel outside. Thermal and sound insulation with 35 kg/m3 density mineral wool.

Fan groupDouble-inlet centrifugal fans with statically and dynamically balanced horizontally-oriented aluminium impellers. Single-phase asynchronous electric motor with overload cutout. 6 speeds of rotation (3 connected) or EC motor. The motor is directly coupled to the fans and cushioned with fl exible mountings to ensure low noise.

• 3 •

CO2

-50%

150

135

120

105

90

75

60

45

30

15

0200 300 400 500 600 700 800 900

- 454% - 363% - 070% - 878%- 74477 %

- 575%

(W)

m3/h

Application Guide /INALTO-AGU-1801-E

GENERAL DESCRIPTION

Standard motor

Effi ciencyCO2 emissions

EC motor

Air fi lterFiltering Polyester fabric enclosed within a metal frame to facilitate withdrawal and cleaning. Filtering rate of the standard model: EU3.Available with different fi ltering rate and thikness on request.

CoilCoils are made of copper pipe expanded into aluminium fi ns.Copper headers with male fi ttings (GAS threads) and easily accessible air vents.The water connections are located on the left (looking at the air outlet). On request, the water connections can be placed on the right side of the unit

MATTER OF SAVING AND RESPECT FOR THE ENVIRONMENT

The INALTO series can also be equipped with an innovative brushless synchronous motor controlled by a dedicated inverter board, which allows to modulate with accurate precision, the speed of the fan limiting the energy supply to the actual workload required, without unnecessary waste.Compared to a unit with traditional asynchronous motor, the EC motor ensures an exceptional reduction of energy consumption by more than 75%, even during the operation at low rpm.As well as bringing considerable savings in economic terms and relative decrease of CO2 emissions in the environment, the series with EC motor is able to signifi cantly improve the environmental comfort through constant modulation in air fl ow rate, with the benefi t of an immediate and precise achievement of the thermal load required by the user and its maintenance throughout the day and greater noiselessness guaranteed by a targeted management of the number of revolutions.

PRINCIPLE OF OPERATION

In the EC motor the permanent magnet is secured to the crankshaft (motor), andthe windings instead are fi xed on the outer structure called the stator.The EC motors control board, with an appropriate electronic modulation of the voltage signals on the different windings, allows to create a rotating magnetic fi eld that induces the motor in motion.A series of sensors provides the adjustment board the motor position, according to which this provides to electronically change the power on the windings, so as to correctly arrange the rotating magnetic fi eld.For this reason the EC motor is also defi ned Brushless, that is devoid of brushes: the ECM motor is not equipped with brushes and collector as instead are the DC motors.

LOOKING AT THE FUTURE

By this type of fan motors, the users can be personalise the speeds according to their request, by means of any control which can easily be designed.This opens a new perspective to room air conditioning. In fact the fan coil manufacturer can program valves, motors and clutches by menas of the same logic, with the result that the fi nal user can get an optimised system of room conditioning with a low CO2 impact.By using these type of motors, it is possible to satisfy the requirements of the “ecodesign” prescriptions suggested by Eurovent and is also in line with the future requirements, given a lower input power demand.

GENERAL FEATURES

EC motors are completely interchangeable with those of the already well known motors. Mechanical structure and cradles are in fact the same and the only difference is having replaced the transfomer with the electronic control case.Moreover, these motors have been designed to give a performance similar to the standard ones, but with the possibility of being used with a 0-10V control..

• 4 •

INALTO 05

INALTO 11

INALTO 15

INALTO 25

INALTO 28

INALTO 49

INALTO 57

W

MAX 3010 5728 8786 10924 14511 23350 26171

MED 2896 5634 7725 8970 13009 21768 23958

MIN 2662 5408 6896 6550 11620 17549 21520

W

MAX 2136 4138 6326 7864 10581 17320 19401

MED 2047 4064 5505 6370 9389 16038 17608

MIN 1876 3888 4876 4590 8320 12689 15650

l/h

MAX 536 1009 1551 1934 2589 4167 4687

MED 513 991 1363 1586 2318 3878 4282

MIN 471 952 1217 1158 2071 3117 3845

kPa

MAX 9,9 13,3 17,8 17 19,5 20,2 26,4

MED 9,1 12,9 14,2 12 16,1 18,4 22,2

MIN 7,9 12 11,6 6,9 13,2 12,1 18,8

W

MAX 4080 7580 11380 14170 19040 31190 34360

MED 3930 7460 10070 11760 17130 29080 31460

MIN 3660 7180 9080 8770 15400 23600 28360

l/h

MAX 358 665 997 1242 1669 2735 3012

MED 345 654 883 1031 1502 2550 2758

MIN 321 630 797 769 1351 2069 2486

kPa

MAX 12,7 16,6 11,4 7,9 15,2 33,5 22,8

MED 11,9 16,1 9,2 5,7 12,7 29,6 19,6

MIN 10,5 15,1 7,7 3,4 10,5 20,5 16,3

W

MAX 4610 8560 12860 16030 21520 35230 38850

MED 4430 8420 11380 13300 19360 32840 35570

MIN 4130 8110 10260 9910 17410 26640 32050

l/h

MAX 405 752 1130 1408 1890 3095 3413

MED 390 740 1000 1169 1702 2885 3124

MIN 362 712 901 870 1529 2341 2815

kPa

MAX 15,5 20,3 13,9 9,6 18,6 40,8 27,9

MED 14,5 19,7 11,2 6,9 15,5 36,1 23,9

MIN 12,7 18,4 9,4 4,1 12,8 25 19,9

Application Guide / INALTO-AGU-1801-E

4 pipe system (4R+2 coil)

CO

OLI

NG

MO

DE

Wat

er in

let t

empe

ratu

re: 7

°CW

ater

out

let t

empe

ratu

re: 1

2°C

Air

inle

t tem

pera

ture

: 27°

C D

B -

19°C

WB

Total cooling capacity

Sensible cooling capacity

Water fl ow rate

Water pressure drop

HEA

TIN

G M

OD

ETA

ir te

mp.

: 20°

CW

ater

inle

t tem

pera

ture

: 65/

55°C Heating capacity

Water fl ow

Water pressure drop

HEA

TIN

G M

OD

EA

ir te

mp.

: 20°

CW

ater

inle

t tem

pera

ture

: 70/

60°C Heating capacity

Water fl ow rate

Water pressure drop

In case of AC motor, the MIN/MED/MAX speeds are the wired speeds among the 6 available on the motor.In case of EC motor, the MIN/MED/MAX speeds are the EUROVENT tested speeds.Standard unit with free outlet: external static pressure = 0 Pa Sound power level: ISO 23741 Sound pressure level: 8,6 dB(A) lower that the sound power level for a room of 90 m3 with a reverberation time of 0,5 sec. Supported power supply: ~230V / 1ph / 50-60Hz

TECHNICAL DATA

• 5 •

INALTO 05

INALTO 11

INALTO 15

INALTO 25

INALTO 28

INALTO 49

INALTO 57

m3/h

MAX 484 966 1478 1868 2651 4598 5187

MED 459 944 1245 1437 2275 4144 4548

MIN 369 894 1079 963 1956 3062 3904

Pa

MAX 57 55 73 88 72 63 72

MED 50 50 50 50 50 50 50

MIN 39 44 37 22 37 26 37

dB(A)

MAX 62 68 63 66 70 72 74

MED 60 67 59 58 67 69 70

MIN 56 67 55 55 63 61 66

MAX 61 65 66 67 71 74 75

MED 59 64 60 59 66 70 69

MIN 55 64 54 56 62 61 65

MAX 53 59 54 57 61 63 65

MED 51 58 50 49 58 60 61

MIN 47 58 46 46 54 52 57

MAX 52 56 57 58 62 65 66

MED 50 55 51 50 57 61 60

MIN 46 55 45 47 53 52 56

dB(A)

MAX 61 64 66 67 71 74 75

MED 59 63 60 58 66 70 69

MIN 55 64 57 53 62 61 65

MAX 61 64 66 67 71 74 75

MED 59 63 60 58 66 70 69

MIN 55 64 57 53 62 61 65

MAX 52 55 57 58 62 65 66

MED 50 54 51 49 57 61 60

MIN 46 55 48 44 53 52 56

MAX 52 55 57 58 62 65 66

MED 50 54 51 49 57 61 60

MIN 46 55 48 44 53 52 56

Application Guide /INALTO-AGU-1801-E

4 pipe system (4R+2 coil)

Airfl ow rate

Static pressure

INA

LTO

SIN

GLE

SK

IN U

NIT

Sound power levelinlet + radiated

Sound power leveloutlet

Sound pressure levelinlet + radiated

Sound pressure leveloutlet

INA

LTO

-DS

DO

UB

LE S

KIN

UN

IT

Sound power levelinlet + radiated

Sound power leveloutlet

Sound pressure levelinlet + radiated

Sound pressure leveloutlet

In case of AC motor, the MIN/MED/MAX speeds are the wired speeds among the 6 available on the motor.In case of EC motor, the MIN/MED/MAX speeds are the EUROVENT tested speeds. Standard unit with free outlet: external static pressure = 0 Pa Sound power level: ISO 23741 Sound pressure level: 8,6 dB(A) lower that the sound power level for a room of 90 m3 with a reverberation time of 0,5 sec. Supported power supply: ~230V / 1ph / 50-60Hz

TECHNICAL DATA

• 6 •

INALTO 05

INALTO 11

INALTO 15

INALTO 25

INALTO 28

INALTO 49

INALTO 57

W

MAX 3010 5728 8786 10924 14511 23350 26171

MED 2896 5634 7725 8970 13009 21768 23958

MIN 2662 5408 6896 6550 11620 17549 21520

W

MAX 2136 4138 6326 7864 10581 17320 19401

MED 2047 4064 5505 6370 9389 16038 17608

MIN 1876 3888 4876 4590 8320 12689 15650

l/h

MAX 536 1009 1551 1934 2589 4167 4687

MED 513 991 1363 1586 2318 3878 4282

MIN 471 952 1217 1158 2071 3117 3845

kPa

MAX 9,9 13,3 17,8 17 19,5 20,2 26,4

MED 9,1 12,9 14,2 12 16,1 18,4 22,2

MIN 7,9 12 11,6 6,9 13,2 12,1 18,8

W

MAX 4080 7580 11380 14170 19040 31190 34360

MED 3930 7460 10070 11760 17130 29080 31460

MIN 3660 7180 9080 8770 15400 23600 28360

l/h

MAX 358 665 997 1242 1669 2735 3012

MED 345 654 883 1031 1502 2550 2758

MIN 321 630 797 769 1351 2069 2486

kPa

MAX 12,7 16,6 11,4 7,9 15,2 33,5 22,8

MED 11,9 16,1 9,2 5,7 12,7 29,6 19,6

MIN 10,5 15,1 7,7 3,4 10,5 20,5 16,3

W

MAX 4610 8560 12860 16030 21520 35230 38850

MED 4430 8420 11380 13300 19360 32840 35570

MIN 4130 8110 10260 9910 17410 26640 32050

l/h

MAX 405 752 1130 1408 1890 3095 3413

MED 390 740 1000 1169 1702 2885 3124

MIN 362 712 901 870 1529 2341 2815

kPa

MAX 15,5 20,3 13,9 9,6 18,6 40,8 27,9

MED 14,5 19,7 11,2 6,9 15,5 36,1 23,9

MIN 12,7 18,4 9,4 4,1 12,8 25 19,9

Application Guide / INALTO-AGU-1801-E

4 pipe system (4R+2 coil)

CO

OLI

NG

MO

DE

Wat

er in

let t

empe

ratu

re: 7

°CW

ater

out

let t

empe

ratu

re: 1

2°C

Air

inle

t tem

pera

ture

: 27°

C D

B -

19°C

WB

Total cooling capacity

Sensible cooling capacity

Water fl ow rate

Water pressure drop

HEA

TIN

G M

OD

ETA

ir te

mp.

: 20°

CW

ater

inle

t tem

pera

ture

: 65/

55°C Heating capacity

Water fl ow

Water pressure drop

HEA

TIN

G M

OD

EA

ir te

mp.

: 20°

CW

ater

inle

t tem

pera

ture

: 70/

60°C Heating capacity

Water fl ow rate

Water pressure drop

In case of AC motor, the MIN/MED/MAX speeds are the wired speeds among the 6 available on the motor.In case of EC motor, the MIN/MED/MAX speeds are the EUROVENT tested speeds.Standard unit with free outlet: external static pressure = 0 Pa Sound power level: ISO 23741 Sound pressure level: 8,6 dB(A) lower that the sound power level for a room of 90 m3 with a reverberation time of 0,5 sec. Supported power supply: ~230V / 1ph / 50-60Hz

TECHNICAL DATA

• 7 •

INALTO 05

INALTO 11

INALTO 15

INALTO 25

INALTO 28

INALTO 49

INALTO 57

m3/h

MAX 484 966 1478 1868 2651 4598 5187

MED 459 944 1245 1437 2275 4144 4548

MIN 369 894 1079 963 1956 3062 3904

Pa

MAX 57 55 73 88 72 63 72

MED 50 50 50 50 50 50 50

MIN 39 44 37 22 37 26 37

dB(A)

MAX 62 68 63 66 70 72 74

MED 60 67 59 58 67 69 70

MIN 56 67 55 55 63 61 66

MAX 61 65 66 67 71 74 75

MED 59 64 60 59 66 70 69

MIN 55 64 54 56 62 61 65

MAX 53 59 54 57 61 63 65

MED 51 58 50 49 58 60 61

MIN 47 58 46 46 54 52 57

MAX 52 56 57 58 62 65 66

MED 50 55 51 50 57 61 60

MIN 46 55 45 47 53 52 56

dB(A)

MAX 61 64 66 67 71 74 75

MED 59 63 60 58 66 70 69

MIN 55 64 57 53 62 61 65

MAX 61 64 66 67 71 74 75

MED 59 63 60 58 66 70 69

MIN 55 64 57 53 62 61 65

MAX 52 55 57 58 62 65 66

MED 50 54 51 49 57 61 60

MIN 46 55 48 44 53 52 56

MAX 52 55 57 58 62 65 66

MED 50 54 51 49 57 61 60

MIN 46 55 48 44 53 52 56

Application Guide /INALTO-AGU-1801-E

4 pipe system (4R+2 coil)

Airfl ow rate

Static pressure

INA

LTO

SIN

GLE

SK

IN U

NIT

Sound power levelinlet + radiated

Sound power leveloutlet

Sound pressure levelinlet + radiated

Sound pressure leveloutlet

INA

LTO

-DS

DO

UB

LE S

KIN

UN

IT

Sound power levelinlet + radiated

Sound power leveloutlet

Sound pressure levelinlet + radiated

Sound pressure leveloutlet

In case of AC motor, the MIN/MED/MAX speeds are the wired speeds among the 6 available on the motor.In case of EC motor, the MIN/MED/MAX speeds are the EUROVENT tested speeds. Standard unit with free outlet: external static pressure = 0 Pa Sound power level: ISO 23741 Sound pressure level: 8,6 dB(A) lower that the sound power level for a room of 90 m3 with a reverberation time of 0,5 sec. Supported power supply: ~230V / 1ph / 50-60Hz

TECHNICAL DATA

• 8 •

INALTO 05

INALTO 11

INALTO 15

INALTO 25

INALTO 28

INALTO 49

INALTO 57

(E) W

MAX 94 132 224 346 529 860 1059

MED 82 126 195 270 461 762 922

MIN 73 122 174 200 410 561 820

A

MAX 0,45 0,64 1,08 1,67 2,56 4,15 5,11

MED 0,4 0,61 0,94 1,29 2,23 3,68 4,46

MIN 0,35 0,59 0,84 0,95 1,98 2,71 3,96

~230V / 1ph / 50Hz

INALTO 05

INALTO 11

INALTO 15

INALTO 25

INALTO 28

INALTO 49

INALTO 57

W

MAX 69 108 158 237 386 639 773

MED 58 96 100 113 232 464 464

MIN 42 82 70 52 155 206 309

A

MAX 0,52 0,87 1,16 1,13 1,75 2,93 3,5

MED 0,48 0,75 0,71 0,65 1,18 2,27 2,37

MIN 0,37 0,63 0,52 0,41 0,82 1,24 1,65

V

MAX 6,9 8,2 7 7,3 6,5 7,8 6,5

MED 6 7,6 5,2 4,5 5,1 6,5 5,1

MIN 4,3 6,7 4,1 2 4 3,9 4

~230V / 1ph / 50Hz

Application Guide / INALTO-AGU-1801-E

STANDARD MOTOR

Power input (E)

Absorbed current

Power input

EC MOTOR

Power input

Absorbed current

Input voltage regulation

Power input

In case of AC motor, the MIN/MED/MAX speeds are the wired speeds among the 6 available on the motor.In case of EC motor, the MIN/MED/MAX speeds are the EUROVENT tested speeds.

TECHNICAL DATA

• 9 •

05 11 15 25 28 49 57 05 11 15 25 28 49 57

L

mm

770 1070 1270 1420 1520 2190 2190 793 1093 1293 1443 1543 2233 2233

H 297 297 347 372 397 373 398 325 325 375 400 425 401 426

P 643 643 643 770 770 770 770 643 643 643 770 770 770 7702 2 2 2 2 4 4 2 2 2 2 2 4 4

05 11 15 25 28 49 57 05 11 15 25 28 49 57

L

mm

770 1070 1270 1420 1520 2190 2190 793 1093 1293 1443 1543 2213 2213

H 740 740 815 890 915 891 916 754 754 829 904 929 905 930

P 347 347 397 422 447 423 448 367 367 417 442 467 443 468

2 2 2 2 2 4 4 2 2 2 2 2 4 4

Application Guide /INALTO-AGU-1801-E

SINGLE SKIN DOUBLE SKIN

INALTO

Lenght

Height

DepthNumber of fans

SINGLE SKIN DOUBLE SKIN

INALTOLenght

Height

Depth

Number of fans

HORIZONTAL UNIT

VERTICAL UNIT

DIMENSIONS

• 10 •

INALTO 05

230 V 1 Ph 50-60 Hz

INALTO 11

INALTO 15

INALTO 25

INALTO 28

INALTO 49

INALTO 57

INALTO 05 4610 W

(70/60°C)

INALTO 11 8560 W

INALTO 15 12860 W

INALTO 25 16000 W

INALTO 28 21520 W

INALTO 49 35230 W

INALTO 57 38850 W

INALTO 05 6R 5NC PC 3650 W PH 4150 W

INALTO 11 6R 7NC PC 7750 W PH 9090 W

INALTO 15 6R 11NC PC 11870 W PH 14090 W

INALTO 25 6R 13NC PC 15600 W PH 18490 W

INALTO 28 6R 15NC PC 20100 W PH 24180 W

INALTO 49 6R 22NC PC 32970 W PH 40820 W

INALTO 57 6R 24NC PC 36270 W PH 45130 W

INALTO 05 4R 2NC PC 4930 W

INALTO 11 4R 4NC PC 9490 W

INALTO 15 4R 5NC PC 14500 W

INALTO 25 4R 6NC PC 20500 W

INALTO 28 4R 8NC PC 23900 W

INALTO 49 4R 12NC PC 37500 W

INALTO 57 4R 12NC PC 42200 W

INALTO 05 750 x 220 mm

INALTO 11 1050 x 220 mm

INALTO 15 1250 x 220 mm

INALTO 25 1400 x 220 mm

INALTO 28 1500 x 220 mm

INALTO 49-7 2170 x 220 mm

INALTO 05

10 l/h3 l/h

(0 m.c.a.)(7 m.c.a.)

INALTO 11

INALTO 15

INALTO 25

INALTO 28

INALTO 49 500 l/h100 l/h

(0 m.c.a.)(5 m.c.a.)INALTO 57

INALTO 05

10 l/h3 l/h

(0 m.c.a.)(7 m.c.a.)

INALTO 11

INALTO 15

INALTO 25

INALTO 28

INALTO 49 500 l/h100 l/h

(0 m.c.a.)(5 m.c.a.)INALTO 57

Application Guide / INALTO-AGU-1801-E

ACCESSORIES INSTALLED

Size Technical data

Special motor with fail contact

2 rows auxiliary coil for 4 pipe system

6 rows coilTechnical data:PC (W) 7-12°C (cooling)PH (W) 50°C (heating)Calculated at 6th speed

Direct expansion coil - R410AOnly for units with left hydraulic connectionsEvaporation temperature: 5°C Overheating: 5°C Condensation temperature: 45°C Sub-cooling: 10°C Air temperature: 27°C Relative humidity: 47°C Calculated at 6th speed

Drain pan cover panel

Condensate drain pump kitfor unit with left water connections

Condensate water pump kitfor unit with right water connections

ACCESSORIES

• 11 •

INALTO 05 678 x 25 x (H)245 mm (1 pc)INALTO 11 978 x 25 x (H)245 mm (1 pc)INALTO 15 1178 x 25 x (H)295 mm (1 pc)INALTO 25 1328 x 25 x (H)320 mm (1 pc)INALTO 28 1428 x 25 x (H)345 mm (1 pc)INALTO 05 678 x 48 x (H)245 mm (1 pc)INALTO 11 978 x 48 x (H)245 mm (1 pc)INALTO 15 1178 x 48 x (H)295 mm (1 pc)INALTO 25 1328 x 48 x (H)320 mm (1 pc)INALTO 28 1428 x 48 x (H)345 mm (1 pc)INALTO 05 678 x 48 x (H)245 mm (1 pc)INALTO 11 978 x 48 x (H)245 mm (1 pc)INALTO 15 1178 x 48 x (H)295 mm (1 pc)INALTO 25 1328 x 48 x (H)320 mm (1 pc)INALTO 28 1428 x 48 x (H)345 mm (1 pc)INALTO 49 1049 x 48 x (H)320 mm (2 pcs)INALTO 57 1049 x 48 x (H)345 mm (2 pcs)

INALTO 05-3 -

INALTO 25-7 -

PAM 1 INALTO 05 750 x 200 x (H)283 mmPAM 2 INALTO 11 1050 x 200 x (H)283 mmPAM 3 INALTO 15 1250 x 200 x (H)333 mmPAM 4 INALTO 25 1400 x 200 x (H)358 mmPAM 5 INALTO 28 1500 x 200 x (H)383 mmPAM 6 INALTO 49 2170 x 200 x (H)358 mmPAM 7 INALTO 57 2170 x 200 x (H)383 mmPAM-DS 1 INALTO 05 773 x 200 x (H)301 mmPAM-DS 2 INALTO 11 1073 x 200 x (H)301 mmPAM-DS 3 INALTO 15 1273 x 200 x (H)351 mmPAM-DS 4 INALTO 25 1423 x 200 x (H)376 mmPAM-DS 5 INALTO 28 1523 x 200 x (H)401 mmPAM-DS 6 INALTO 49 2193 x 200 x (H)376 mmPAM-DS 7 INALTO 57 2193 x 200 x (H)401 mmPAM 1 INALTO 05 750 x 200 x (H)283 mmPAM 2 INALTO 11 1050 x 200 x (H)283 mmPAM 3 INALTO 15 1250 x 200 x (H)333 mmPAM 4 INALTO 25 1400 x 200 x (H)358 mmPAM 5 INALTO 28 1500 x 200 x (H)383 mmPAM 6 INALTO 49 2170 x 200 x (H)358 mmPAM 7 INALTO 57 2170 x 200 x (H)383 mmPAM-DS 1 INALTO 05 773 x 200 x (H)301 mmPAM-DS 2 INALTO 11 1073 x 200 x (H)301 mmPAM-DS 3 INALTO 15 1273 x 200 x (H)351 mmPAM-DS 4 INALTO 25 1423 x 200 x (H)376 mmPAM-DS 5 INALTO 28 1523 x 200 x (H)401 mmPAM-DS 6 INALTO 49 2193 x 200 x (H)376 mmPAM-DS 7 INALTO 57 2193 x 200 x (H)401 mmRAM 1 INALTO 05 750 x 308 x 308 mmRAM 2 INALTO 11 1050 x 308 x 308 mmRAM 3 INALTO 15 1250 x 358 x 358 mmRAM 4 INALTO 25 1400 x 383 x 383 mmRAM 5 INALTO 28 1500 x 408 x 408 mmRAM 6 INALTO 49 2170 x 383 x 383 mmRAM 7 INALTO 57 2170 x 408 x 408 mm

Application Guide /INALTO-AGU-1801-E

Size Technical data

Air fi lter (fi ltration grade: G3)Thickness: 25 mm

Air fi lter (fi ltration grade: G3)Thickness: 48 mm

Air fi lter (fi ltration grade: G4)Thickness: 48 mm

Size Technical data

Auxiliary drain pan

Straight intake plenumCeiling fi xing kit includedSingle skin unit

Straight intake plenumCeiling fi xing kit includedDouble skin unit

Straight supply plenum - insulatedCeiling fi xing kit includedSingle skin unit

Straight supply plenum - insulatedCeiling fi xing kit includedDouble skin unit

90° intake plenumCeiling fi xing kit includedSingle skin unit

ACCESSORIES INSTALLED

ACCESSORIES NOT INSTALLED

ACCESSORIES

• 12 •

RAM-DS 1 INALTO 05 773 x 327 x 327 mmRAM-DS 2 INALTO 11 1073 x 327 x 327 mmRAM-DS 3 INALTO 15 1273 x 377 x 377 mmRAM-DS 4 INALTO 25 1423 x 402 x 402 mmRAM-DS 5 INALTO 28 1523 x 427 x 427 mmRAM-DS 6 INALTO 49 2193 x 402 x 402 mmRAM-DS 7 INALTO 57 2193 x 427 x 427 mmRAM 1 INALTO 05 750 x 308 x 308 mmRAM 2 INALTO 11 1050 x 308 x 308 mmRAM 3 INALTO 15 1250 x 358 x 358 mmRAM 4 INALTO 25 1400 x 383 x 383 mmRAM 5 INALTO 28 1500 x 408 x 408 mmRAM 6 INALTO 49 2170 x 383 x 383 mmRAM 7 INALTO 57 2170 x 408 x 408 mmRAM-DS 1 INALTO 05 773 x 327 x 327 mmRAM-DS 2 INALTO 11 1073 x 327 x 327 mmRAM-DS 3 INALTO 15 1273 x 377 x 377 mmRAM-DS 4 INALTO 25 1423 x 402 x 402 mmRAM-DS 5 INALTO 28 1523 x 427 x 427 mmRAM-DS 6 INALTO 49 2193 x 402 x 402 mmRAM-DS 7 INALTO 57 2193 x 427 x 427 mmGAM 1 INALTO 05 753 x 90÷110 x (H)288 mmGAM 2 INALTO 11 1053 x 90÷110 x (H)288 mmGAM 3 INALTO 15 1253 x 90÷110 x (H)338 mmGAM 4 INALTO 25 1403 x 90÷110 x (H)363 mmGAM 5 INALTO 28 1503 x 90÷110 x (H)388 mmGAM 6 INALTO 49 2173 x 90÷110 x (H)363 mmGAM 7 INALTO 57 2173 x 90÷110 x (H)388 mmSRE 1-A INALTO 05 750 x 300 x (H)283 mm / 4500 WSRE 2-A INALTO 11 1050 x 300 x (H)283 mm / 7500 WSRE 3-A INALTO 15 1250 x 300 x (H)333 mm / 7500 WSRE 4-A INALTO 25 1400 x 300 x (H)358 mm / 9000 WSRE 5-A INALTO 28 1500 x 300 x (H)383 mm / 9000 WSRE 6-A INALTO 49 2170 x 300 x (H)358 mm / 15000 WSRE 7-A INALTO 57 2170 x 300 x (H)383 mm / 15000 WSRE 1-B INALTO 05 750 x 300 x (H)283 mm / 6000 WSRE 2-B INALTO 11 1050 x 300 x (H)283 mm / 9600 WSRE 3-B INALTO 15 1250 x 300 x (H)333 mm / 9600 WSRE 4-B INALTO 25 1400 x 300 x (H)358 mm / 12000 WSRE 5-B INALTO 28 1500 x 300 x (H)383 mm / 12000 WSRE 6-B INALTO 49 2170 x 300 x (H)358 mm / 19200 WSRE 7-B INALTO 57 2170 x 300 x (H)383 mm / 19200 WSRE-DS 1-A INALTO 05 773 x 300 x (H)301 mm / 4500 WSRE-DS 2-A INALTO 11 1073 x 300 x (H)301 mm / 7500 WSRE-DS 3-A INALTO 15 1273 x 300 x (H)351 mm / 7500 WSRE-DS 4-A INALTO 25 1423 x 300 x (H)376 mm / 9000 WSRE-DS 5-A INALTO 28 1523 x 300 x (H)401 mm / 9000 WSRE-DS 6-A INALTO 49 2193 x 300 x (H)376 mm / 15000 WSRE-DS 7-A INALTO 57 2193 x 300 x (H)401 mm / 15000 WSRE-DS 1-B INALTO 05 773 x 300 x (H)301 mm / 6000 WSRE-DS 2-B INALTO 11 1073 x 300 x (H)301 mm / 9600 WSRE-DS 3-B INALTO 15 1273 x 300 x (H)351 mm / 9600 WSRE-DS 4-B INALTO 25 1423 x 300 x (H)376 mm / 12000 WSRE-DS 5-B INALTO 28 1523 x 300 x (H)401 mm / 12000 WSRE-DS 6-B INALTO 49 2193 x 300 x (H)376 mm / 19200 WSRE-DS 7-B INALTO 57 2193 x 300 x (H)401 mm / 19200 W

Application Guide / INALTO-AGU-1801-E

Size Technical data

90° intake plenumCeiling fi xing kit includedDouble skin unit

90° supply plenum - insulatedCeiling fi xing kit includedSingle skin unit

90° supply plenum - insulatedCeiling fi xing kit includedDouble skin unit

Intake/supply antivibrating joint

Heating section with electric heaterSingle skin unit

Heating section with electric heaterDouble skin unit

ACCESSORIES NOT INSTALLED

ACCESSORIES

• 13 •

SRA 1 INALTO 05 750 x 300 x (H)283 mmSRA 2 INALTO 11 1050 x 300 x (H)283 mmSRA 3 INALTO 15 1250 x 300 x (H)333 mmSRA 4 INALTO 25 1400 x 300 x (H)358 mmSRA 5 INALTO 28 1500 x 300 x (H)383 mmSRA 6 INALTO 49 2170 x 300 x (H)358 mmSRA 7 INALTO 57 2170 x 300 x (H)383 mmSRA-DS 1 INALTO 05 773 x 300 x (H)301 mmSRA-DS 2 INALTO 11 1073 x 300 x (H)301 mmSRA-DS 3 INALTO 15 1273 x 300 x (H)351 mmSRA-DS 4 INALTO 25 1423 x 300 x (H)376 mmSRA-DS 5 INALTO 28 1523 x 300 x (H)401 mmSRA-DS 6 INALTO 49 2193 x 300 x (H)376 mmSRA-DS 7 INALTO 57 2193 x 300 x (H)401 mmUSG 1 INALTO 05 750 x 300 x (H)283 mmUSG 2 INALTO 11 1050 x 300 x (H)283 mmUSG 3 INALTO 15 1250 x 300 x (H)333 mmUSG 4 INALTO 25 1400 x 300 x (H)358 mmUSG 5 INALTO 28 1500 x 300 x (H)383 mmUSG 6 INALTO 49 2170 x 300 x (H)358 mmUSG 7 INALTO 57 2170 x 300 x (H)383 mmUSG-DS 1 INALTO 05 773 x 300 x (H)301 mmUSG-DS 2 INALTO 11 1073 x 300 x (H)301 mmUSG-DS 3 INALTO 15 1273 x 300 x (H)351 mmUSG-DS 4 INALTO 25 1423 x 300 x (H)376 mmUSG-DS 5 INALTO 28 1523 x 300 x (H)401 mmUSG-DS 6 INALTO 49 2193 x 300 x (H)376 mmUSG-DS 7 INALTO 57 2193 x 300 x (H)401 mmSSP 1 INALTO 05 750 x 440 x (H)283 mmSSP 2 INALTO 11 1050 x 440 x (H)283 mmSSP 3 INALTO 15 1250 x 440 x (H)333 mmSSP 4 INALTO 25 1400 x 440 x (H)358 mmSSP 5 INALTO 28 1500 x 440 x (H)383 mmSSP 6 INALTO 49 2170 x 440 x (H)358 mmSSP 7 INALTO 57 2170 x 440 x (H)383 mmSSP-DS 1 INALTO 05 773 x 440 x (H)301 mmSSP-DS 2 INALTO 11 1073 x 440 x (H)301 mmSSP-DS 3 INALTO 15 1273 x 440 x (H)351 mmSSP-DS 4 INALTO 25 1423 x 440 x (H)376 mmSSP-DS 5 INALTO 28 1523 x 440 x (H)401 mmSSP-DS 6 INALTO 49 2193 x 440 x (H)376 mmSSP-DS 7 INALTO 57 2193 x 440 x (H)401 mmINALTO 05 INALTO 05 760 x 125 x (H)295 mmINALTO 11 INALTO 11 1060 x 125 x (H)295 mmINALTO 15 INALTO 15 1260 x 125 x (H)345 mmINALTO 25 INALTO 25 1410 x 125 x (H)370 mmINALTO 28 INALTO 28 1510 x 125 x (H)395 mmINALTO 49 INALTO 49 2180 x 125 x (H)370 mmINALTO 57 INALTO 57 2180 x 125 x (H)395 mmBAM 1 INALTO 05 n° 2 x Ø 200BAM 2 INALTO 11 n° 3 x Ø 200BAM 3 INALTO 15 n° 4 x Ø 200BAM 4 INALTO 25 n° 3 x Ø 300BAM 5 INALTO 28 n° 4 x Ø 300BAM 6 INALTO 49 n° 6 x Ø 300BAM 7 INALTO 57 n° 6 x Ø 300

Application Guide /INALTO-AGU-1801-E

Size Technical data

Re-heating/cooling section with water coilSingle skin unit

Re-heating/cooling section with water coilDouble skin unit

Humidifi cation section with drop sepa-ratorSingle skin unit

Humidifi cation section with drop sepa-ratorDouble skin unit

Air lower section (manual)Single skin unit

Air lower section (manual)Double skin unit

Aluminium damper

Intake section with circular spigots

ACCESSORIES NOT INSTALLED

ACCESSORIES

• 14 •

BAM 1 INALTO 05 n° 2 x Ø 200

BAM 2 INALTO 11 n° 3 x Ø 200

BAM 3 INALTO 15 n° 4 x Ø 200

BAM 4 INALTO 25 n° 3 x Ø 300

BAM 5 INALTO 28 n° 4 x Ø 300

BAM 6 INALTO 49 n° 6 x Ø 300

BAM 7 INALTO 57 n° 6 x Ø 300

INALTO 05 INALTO 05 748 x 6 x (H)283 mm

INALTO 11 INALTO 11 1048 x 6 x (H)283 mm

INALTO 15 INALTO 15 1248 x 6 x (H)333 mm

INALTO 25 INALTO 25 1398 x 6 x (H)358 mm

INALTO 28 INALTO 28 1498 x 6 x (H)383 mm

INALTO 49 INALTO 49 2168 x 6 x (H)358 mm

INALTO 57 INALTO 57 2168 x 6 x (H)383 mm

INALTO 05 INALTO 05 748 x 6 x (H)283 mm

INALTO 11 INALTO 11 1048 x 6 x (H)283 mm

INALTO 15 INALTO 15 1248 x 6 x (H)333 mm

INALTO 25 INALTO 25 1398 x 6 x (H)358 mm

INALTO 28 INALTO 28 1498 x 6 x (H)383 mm

INALTO 49 INALTO 49 2168 x 6 x (H)358 mm

INALTO 57 INALTO 57 2168 x 6 x (H)383 mm

Application Guide / INALTO-AGU-1801-E

Size Technical data

Supply section with circular spigots - insulated

Fix intake grill with fi lter

Adjustable supply grill

ACCESSORIES NOT INSTALLED

ACCESSORIES

• 15 •Application Guide /INALTO-AGU-1801-E

INALTO PAM RAM GAM SRE SRA USG SSP ALUMINIUM DAMPER BAM INTAKE

GRILLSUPPLY GRILL

INALTO

PAM

RAM

GAM

SRE

SRA

USG

SSP

ALUMI-NIUM

DAMPER

BAM

INTAKE GRILL

SUPPLY GRILL

ACCESSORIES

DUCTING ACCESSORIES COMPATIBILITY

ACCESSORIES

• 16 • Application Guide / INALTO-AGU-1801-E

Intake Unit Supply

PAM

RAM

GAM

SRE

SRA

USG

BAM

GRILL

RAMGAM

BAM

GRILL

GAM

PAM

RAM

SRE

SRA

USG

SRE

PAM

RAM

GAM

USG

BAM

SRA

PAM

RAM

GAM

SRE

USG

BAM

GRILL

USG

PAM

RAM

GAM

SRE

SRA

BAM

GRILL

RAM

PAM

GAM

SSP

DAMPER

BAM

GRILL

GAM

RAMBAM

GRILL

PAM

GAM

RAM

SSP

DAMPER

GRILL

PAM

SSPRAM

GAM

GRILL

PAM

DAMPERRAM

GAM

GRILL

End of ducts

SEE EXAMPLE NEXT PAGE

ASSEMBLY SEQUENCE GUIDE

ACCESSORIES

• 17 •Application Guide /INALTO-AGU-1801-E

PAM

RAM

GAM

SRE

SRA

USG

BAM

GRILL

RAM GAM

BAM

GRILL

GAM

PAM

RAM

SRE

SRA

USG

SRE

PAM

RAM

GAM

USG

BAM

SRA

PAM

RAM

GAM

SRE

USG

BAM

GRILL

USG

PAM

RAM

GAM

SRE

SRA

BAM

GRILL

RAM

PAM

GAM

SSP

DAMPER

BAM

GRILL

GAMRAM

BAM

GRILL

PAM

GAMRAM

SSP

DAMPER

GRILL

PAM

SSPRAM

GAM

GRILL

PAM

DAMPERRAM

GAM

GRILL End of ducts

Intake Unit Supply

EXAMPLE

ACCESSORIES

• 18 • Application Guide / INALTO-AGU-1801-E

Kit valves (not fi tted), including : valve + actuator + shut off valve + balancing valve

2 way valve for main coil

2 way valve kit + motor 1/230V On/Off - Main 4-rows coil

2 way valve kit + motor 1/230V On/Off - Main 6-rows coil

2 way valve kit + motor 3 points 24V - Main 4-rows coil

2 way valve kit + motor 3 points 24V - Main 6-rows coil

2 way valve kit + modulating 0-10V motor 24V

2 way valve kit + modulating 0-10V motor 24V - Main 6-rows coil

3 way valve for main coil

3 way valve kit + motor 1/230V On/Off - Main 4-rows coil

3 way valve kit + motor 1/230V On/Off - Main 6-rows coil

3 way valve kit + motor 3 points 24V - Main 4-rows coil

3 way valve kit + motor 3 points 24V - Main 6-rows coil

3 way valve + modulating 0-10V motor 24V - Main 4-rows coil

3 way valve + modulating 0-10V motor 24V - Main 6-rows coil

2 way valve for auxiliary coil

2 way valve + motors 1/230V On/Off - auxiliary coil

2 way valve + motor 3 points 24V - auxiliary coil

2 way valve + modulating 0-10V motor 24V - auxiliary coil

3 way valve for auxiliary coil

3 way valve + motors 1/230V On/Off - auxiliary coil

3 way valve + motor 3 points 24V - auxiliary coil

3 way valve + modulating 0-10V motor 24V - auxiliary coil

KIT VALVES

• 19 •Application Guide /INALTO-AGU-1801-E

INALTO 05 INALTO 11 INALTO 15 INALTO 25 INALTO 28 INALTO 49 INALTO 57

2 row auxiliary coil 1/2” 1/2” 3/4” 3/4” 1” 1” 1”

4 row coil 1/2” 3/4” 3/4” 1” 1” 1” 1/4 1” 1/2

6 row coil 3/4” 3/4” 1” 1” 1” 1/4 1” 1/2 1” 1/2

INALTO 05 INALTO 11 INALTO 15 INALTO 25 INALTO 28 INALTO 49 INALTO 572 row auxiliary coil 1/2” 1/2” 3/4” kvs 4,0 1” 1” 1” kvs 9,6 1” kvs 9,6

4 row coil 1/2” 3/4” 3/4” kvs 4,0 1” 1” 1” kvs 9,6 1” kvs 9,6

6 row coil 3/4” 3/4” kvs 4,0 1” 1” kvs 9,6 1” kvs 9,6 1” 1/4 1” 1/4

Fitting DN KVS main direction/bypass1/2" 15 1.7 / 1.3

3/4" 20 2.8 / 1.8

3/4" kvs 4.0 20 4.0 / 1.8

1" 25 5.2 / 3.3

1" kvs 9.6 25 9.6 / 8.6

1” 1/4 32 12.4 / 10.5

CONNECTION COILS DIAMETER

CONNECTION VALVES DIAMETER

VALVES TECHNICAL DATA

VALVES

+ 32 3 633 3045 +351 229 066 050

+33 1 64 76 23 23 +7 495 626 56 53

+49 (0) 211 950 79 600 +34 915 401 810

+ 39 02 495 26 200 +38 044 585 59 10

+ 31 332 471 800 +44 1604 669 100

+48 22 58 48 610

LENNOX DISTRIBUTION

+33 4 72 23 20 20

+ 32 3 633 3045 +48 22 58 48 610

+33 1 64 76 23 23 +351 229 066 050

+49 (0) 211 950 79 60 +34 915 401 810

+ 39 02 495 26 200 +38 044 585 59 10

+ 31 332 471 800 +44 1604 669 100

LENNOX DISTRIBUTION

+33 4 72 23 20 20

INALTO-AGU-1801-EDue to LENNOX EMEA ongoing commitment to quality, the specifi cations, ratings and dimensions are subject to change without notice and without incurring liability.Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.Installation and service must be performed by a qualifi ed installer and servicing agency.

SALES OFFICES :

BELGIUM AND LUXEMBOURG POLAND

FRANCE PORTUGAL

GERMANY SPAIN

ITALY UKRAINE

NETHERLANDS UNITED KINGDOM AND IRELAND

OTHER COUNTRIES :