6
Improved Active Power Filter Performance for Distribution Systems with Renewable Generation P. Acufia*, L. Monin*, IEEE Fellow Member, M. Rivera t , IEEE Member, J. Rodriguez t , IEEE Fellow Member, and J. Dixon + , IEEE Senior Member *Dep. of Electrical Engineering Univ. de Concepci6n Concepcion, CHILE [email protected] [email protected] t Dep. of Electronics Engineering + Dep. of Electrical Engineering Pontificia Univ. Cat6lica de Chile Univ. Tecnica Federico Santa Maria Valparaiso, CHILE [email protected] [email protected] Santiago, CHILE [email protected] Ahstract-A predictive control algorithm specially devel- oped for shunt active power filters aimed to compensate reactive power and current harmonics components is presented and analyzed. The proposed predictive control algorithm is implemented in a three-phase four-leg voltage- source inverter (4L-VSI). The use of a 4L-VSI allows the compensation of current harmonics, reactive power and neutral current harmonics generated by single-phase non-linear loads. A detailed mathematical model of the filter, including the effect of the power system equivalent impedance is derived and used to design the proposed predictive control algorithm. The proposed active power filter and associated control scheme performance and compensation effectiveness are demonstrated by simulation and with experimental results. Index Terms-Active power filter, Current control, Fi- nite control set model predictive control, Four-leg inverters. I. NOMENCLATURE AC Alternating current DC Direct current PWM Pulse width modulation VSI Voltage source inverter Vdc DC voltage iL Load current vector [ i Lu i Lv i L w]T Vs System voltage vector [vs u Vsv vsw]T i� Reference current vector [ i� u i� v i� w]T Zn Neutral line current L f Filter inductance Rf Filter resistance II. INTRODUCTION Renewable generation affects power quality due to its nonlinear characteristic. Solar generation plants and wind power generators must be connected to the grid through high power static PWM converters. Moreover, the non- uniform nature of power generation affects directly volt- age regulation and distortion in power systems. This new scenario in power distribution systems will force the use of more accurate compensation schemes. Although active power filters implemented with three- phase four-leg voltage-source inverters have already been presented in the technical literature [1], [2], the principal contribution of this paper is the development of the predictive control algorithm for this specific application. Traditionally, active power filters have been controlled using PI controllers, for the current as well as for the DC voltage loops. The PI controllers must be designed based on a linear model. The active power filter is a non linear system; therefore compensation effectiveness as well as transient response depends on how accurate is the associated developed linear model. A good design using linear PI controllers reflects in the transient performance of the active power filter, specially its ability to follow the current reference, and the capacity to keep the DC voltage constant and equal to the reference signal [2]-[7]. So far, predictive control implemented in power con- verters has been used mainly in induction motor drive applications [8]-[15]. In case of active power filter, predictive control algorithm has the advantage that the converter output impedance is constant and well known, since the output ripple filter is part of the active power filter design, simpliing the non linear model and the predictive control implementation. Therefore, a detailed discrete time model that includes system nonlinearities of the output power filter can be developed and used to 978-1-4673-2421-2/12/$31.00 ©2012 IEEE 1344

Improved Active Power Filter Performance for Distribution

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Improved Active Power Filter Performance for Distribution

Improved Active Power Filter Performance for Distribution Systems with Renewable Generation

P. Acufia*, L. Monin*, IEEE Fellow Member, M. Riverat, IEEE Member, J. Rodriguez t, IEEE Fellow Member, and J. Dixon+, IEEE Senior Member

*Dep. of Electrical

Engineering

Univ. de Concepci6n

Concepcion, CHILE

[email protected]

[email protected]

tDep. of Electronics

Engineering

+Dep. of Electrical

Engineering

Pontificia Univ. Cat6lica de

Chile

Univ. Tecnica Federico Santa

Maria

Valparaiso, CHILE

[email protected]

[email protected]

Santiago, CHILE

[email protected]

Ahstract-A predictive control algorithm specially devel­

oped for shunt active power filters aimed to compensate

reactive power and current harmonics components is

presented and analyzed. The proposed predictive control

algorithm is implemented in a three-phase four-leg voltage­

source inverter (4L-VSI). The use of a 4L-VSI allows

the compensation of current harmonics, reactive power

and neutral current harmonics generated by single-phase

non-linear loads. A detailed mathematical model of the

filter, including the effect of the power system equivalent

impedance is derived and used to design the proposed

predictive control algorithm. The proposed active power

filter and associated control scheme performance and

compensation effectiveness are demonstrated by simulation

and with experimental results.

Index Terms-Active power filter, Current control, Fi­

nite control set model predictive control, Four-leg inverters.

I. NOMENCLATURE

AC Alternating current

DC Direct current

PWM Pulse width modulation

VSI Voltage source inverter

Vdc DC voltage

iL Load current vector [iLu iLv iLw]T

Vs System voltage vector [vsu Vsv vsw]T

i� Reference current vector [i�u i�v i�w]T

Zn Neutral line current

L f Filter inductance

Rf Filter resistance

II. INTRODUCTION

Renewable generation affects power quality due to its

nonlinear characteristic. Solar generation plants and wind

power generators must be connected to the grid through

high power static PWM converters. Moreover, the non­

uniform nature of power generation affects directly volt­

age regulation and distortion in power systems. This new

scenario in power distribution systems will force the use

of more accurate compensation schemes.

Although active power filters implemented with three­

phase four-leg voltage-source inverters have already been

presented in the technical literature [1], [2], the principal

contribution of this paper is the development of the

predictive control algorithm for this specific application.

Traditionally, active power filters have been controlled

using PI controllers, for the current as well as for the

DC voltage loops. The PI controllers must be designed

based on a linear model.

The active power filter is a non linear system; therefore

compensation effectiveness as well as transient response

depends on how accurate is the associated developed

linear model. A good design using linear PI controllers

reflects in the transient performance of the active power

filter, specially its ability to follow the current reference,

and the capacity to keep the DC voltage constant and

equal to the reference signal [2]-[7].

So far, predictive control implemented in power con­

verters has been used mainly in induction motor drive

applications [8]-[ 15]. In case of active power filter,

predictive control algorithm has the advantage that the

converter output impedance is constant and well known,

since the output ripple filter is part of the active power

filter design, simplifying the non linear model and the

predictive control implementation. Therefore, a detailed

discrete time model that includes system nonlinearities

of the output power filter can be developed and used to

978-1-4673-2421-2/12/$31.00 ©2012 IEEE 1344

Page 2: Improved Active Power Filter Performance for Distribution

[*fj ')\ Vs Z s pee - -

� Static Step-up ZL I PWM Transformer Converter

Ls io t Renewable System Loads

Energy Lj Zj Sources

-( j-( �-( f-( Rj Vdc �

-( f-( j-( f-t Shunt Active Power Filter

Figure 1. Standalone hybrid power system with Shunt Active Power Filter.

derive the predictive control algorithm.

The proposed non-linear model predicts the future

value of the injected current for all possible voltage

vectors generated by the 4L-VSI. The predictions are

evaluated with a cost function that minimizes the output

current error at the end of each sampling time. This

strategy allows fast current tracking with minimum error,

and without the necessity to use tuned controllers or

complicated control strategies. Modulators are no re­

quired in this control technique.

The current reference signal is obtained from the load

current using the dq-based transformation. This block

calculates the active power required by the converter and

delivers the current reference to the current predictive

controller. A discrete mathematical model of the con­

verter is obtained using its 16 feasible switching states.

With this model, the corresponding predicted values are

used to evaluate a cost function which deals with the

control objectives. After that, the valid switching state

that produces the minimum value of the cost function is

selected for the next sampling period.

This paper is organized as follows, in section III

the mathematical model of the 4L-VSI is presented; in

section IV the proposed control algorithm is introduced.

In section V, the current reference generation is detailed.

The proposed active power filter and associated control

scheme are validated thought simulation and experimen­

tal results in section VI. Finally, our conclusions are

given in section VII.

III. FOUR-LEG INVERTER MODEL

In Fig. 1 is shown the typical standalone hybrid power

system which consists of renewable energy sources,

AC/ AC static PWM converter for voltage conversion,

battery banks for long-term energy storage, active power

filter and arbitrary loads. The AC/ AC converters perform

maximum power point tracking to extract maximum

possible energy from the sun and wind respectively.

The loads are unknown and can be of single-phase or

three-phase, balanced or unbalanced, linear or non-linear

nature. The four-leg inverter is used as an active filter.

Four-Leg Inverter P r---.---.---.---,

+

N �--�--�--�--�

io R Leq -+ eq

VxN Vo

Figure 2. Two-level four-leg inverter topology.

The power converter topology for the four-leg inverter

is shown in Fig. 2. The connection format is similar to

the conventional three-phase inverter with the fourth leg

connected to the neutral point of the system. The fourth

leg increases switching states from 8 (23) to 16 (24)

and thus offers control flexibility and improved output

voltage quality [16].

The voltage in any leg x of the inverter, measured

from the negative point of the DC voltage (N) can be

expressed in terms of switching states as,

VxN = Sx vdc, x = u, v, w, n. (1)

The mathematical model of the filter is:

R · L d io Vo = vxN - eq 10 - eq dt (2)

where Req and Leq are Thevenin equivalent filter

parameters, located to the output of the 4L-VSI.

IV. DIGITAL PREDICTIVE CURRENT CONTROL

The proposed digital predictive current control scheme

is shown in Fig. 3. This control scheme is basically an

optimization algorithm and thus it has to be implemented

digitally in the microprocessor based hardware. Conse­

quently, the analysis has to be developed using discrete

1345

Page 3: Improved Active Power Filter Performance for Distribution

mathematics in order to consider additional restrictions

such as delays and approximations, etc. [9], [17]. The

main characteristic of predictive control is the use of

the system model to predict the future behavior of the

variables to be controlled. The controller uses this infor­

mation to obtain the optimal actuation, according to a

predefined optimization criterion. The predictive control

algorithm is very easy and intuitive to understand. It

consists of three main steps as follows:

1) References and Measurements: the control objec­

tives are obtained and the necessary variables to obtain

the prediction model are measured or calculated. In this

case, the measurements of output currents, load currents

and DC-side voltage are obtained, while the neutral

output current and neutral load current are given as

explain in section V.

2) Prediction Model: as a second consideration, it is

important to obtain the converter system model for the

output current prediction. Since the controller operates in

discrete time, both the controller and the system model

need to be represented in a discrete time domain [17].

The discrete time model consists of a recursive matrix

equation that allows the system prediction. This means,

for a given sampling time Ts, it is possible to predict the

system states at any instant [k+1]Ts, with the knowledge

of system states and control variables at instant kTs. Due to the first order nature of the state equations that

describe the model in (1 )-(2), a first order approximation

for the derivative which provides sufficient accuracy is

considered in this paper:

dx x[k + 1] - x[k] dt Ts (3)

The 16 possible output current predictions can be

obtained from (2) and (3) as:

io[k + 1] = !l (VXN[k]- Yolk]) + (1 _ Req TS ) io[k]. Leq Leq (4)

As shown in (4), the output current predictions require

the output current and voltage (which is a function of

the switching signals and the DC voltage) values. The

algorithm calculates all the 16 possible conditions that

the state variables can achieve.

3) Cost Function Optimization: as a final stage, the

predicted values are used to evaluate a cost function

which deals with the control objective. To choose the

optimal switching state to be applied to the inverter, the

16 predictions obtained for io[k + 1] are compared with

their references using a cost function 9 as follows:

g[k + 1] = (i�u[k + 1] - iou[k + 1])2 + (i�v[k + 1] - iov[k + 1])2 + (i�w[k + 1] - iow[k + 1])2 + (i�n[k + 1] - ion[k + 1])2 (5)

The output current equals its reference when 9 = O. Therefore the optimization goal of the cost function is to

achieve 9 value close to zero. The voltage vector v 0 that

minimizes the cost function is chosen and then applied at

the next sampling instant. During each sampling instant,

the minimum value of 9 is selected from the 16 function

values. The algorithm selects a switching state which

produces this minimal value and then applies it during

the whole k + 1 period.

V. CURRENT REFERENCE GENERATION

The phase current reference signals are obtained from

the corresponding load currents using the dq-based

scheme shown in Fig. 4. This block calculates the active

power required by the converter and delivers the current

reference to the predictive current controller.

The dq-based scheme operates in a rotating reference

frame, therefore the measured current signals must be

multiplicated by the sin(wt) and cos(wt) signals. By

using dq-transformation, the d current component is

synchronized with the corresponding phase-to-neutral

system voltage and the q current component is phase­

shifted by 90°. The synchronized sin(wt) and cos(wt)

signals are obtained from a synchronous reference frame

Phase-Locked-Loop [18]. Equation (6) shows the rela­

tion between the current in the stationary frame iLx(t)

(x = u, v, w), and its dq components (id and iq).

[::l � JH �:��t :���:l [� 1 �� 1 m:l (6)

A low-pass filter (LFP) extracts the DC components

of the line curr�nts id, resulting in harmonics references

components -id, with the corresponding negative value.

The reactive reference components of the line currents

are obtained inverting the corresponding ac and DC

components of iq. In order to keep the DC voltage

under control it is necessary to modify the amplitude

of the inverter reference current, by adding an active

power reference signal (ie) into the d-component. The

resulting signal i'd, together with i� are transformed back

to a three-phase system by the inverse Park and Clark

1346

Page 4: Improved Active Power Filter Performance for Distribution

Figure 3. Proposed predictive digital current control scheme.

io

SRF PLL

io

sin (wt)

cos (wt)

Figure 4. dq-based Current Reference Generator.

transformations as shown in (7). The cutoff frequency of

the LPF used in this paper was 20 Hz. [i�U] f2 [11 0 1 [1 0 0] [iO] ��v =Y"3 �-t13 Osinwt- :oswt �dq*' Zow v'2 -2" -1 Ocoswt smwt •

(7)

The current that flows through the neutral lines is

compensated by injecting the same instantaneous value,

obtained from the others line currents, phase-shifted by

1800, as shown in (8).

(8)

VI. SIMULATION AND EXPERIMENTAL RESULTS

A simulation model for the three-phase four-leg con­

verter with the parameters as indicated in Table I, has

been developed using MATLAB-Simulink. The objec­

tive is to verify the effectiveness of the proposed con­

trol scheme in harmonic current compensation under

different operating conditions. The active power filter

Variable

Vs f Vdc Cdc Lf Rf Ts Te

Table I SPECIFICATION PARAMETERS

Description Value a

Source voltage 55 [V] System frequency 50 [Hz] DC voltage 162 [V] DC capacitor 2200 [p,F] (2.0 pu)

Filter inductor 5.0 [mH] (0.5 pu)

Internal resistance within L f 0.6 [12] Sampling time 20 [J.is] Execution time 16 [J.is]

a Note: Vbase = 55 V and Sbase = I kVA.

was tested compensating a 6-pulse rectifier. The pro­

posed predictive algorithm was programmed using an S­

function block that allows simulation of a discrete model

to be implemented easily in a Real-Time Interface (RT!)

on the dSPACE DSII04 R&D controller board. Simula­

tions were performed considering a discrete sample time

of 20 [J-Ls],

In the simulated results shown in Fig. 5, the active

1347

Su

Sv

Sw

Sn

iL

vs

io

io

io∗

iok+1

Four–legInverter

3

4

CurrentReferenceGenerator

CostFunction

Optimizationgk+1

PredictiveModel

vdc

Page 5: Improved Active Power Filter Performance for Distribution

_ :�� ,-_._. _. '_'--,' .L-' _. _ ._. _ '_' ..J..'._' ._ ._ ._. _. _'_'.L. •. _._. _ . . _ ._ ._. --,' .---,' Vsu

5� . . . o . . .. ' . . . .... . . . . '. .... . iLu . . .

-5 �

J' �� _: 1 0AJj iW

_: 1 r" H·n -:� ;. :::� =. ,----, �

........ ---,---.�------,---....• ... '------,---, ......•.. Vdc

(50ms/div)

Figure 5. Simulation waveforms for the proposed control scheme.

filter starts to operate at t = tl. At this time, the active

power filter injects an output current io to compensate

current harmonic components, current unbalanced, and

neutral current simultaneously. Compensated system cur­

rents (is) show sinusoidal waveform, with low distortion

(T H D < 5%). At t = t2, a three-phase balanced load

change is introduced from 0.6 to 1.0 p.u. Compensated

system currents remain sinusoidal despite the change in

the load. Finally, at t = t3, a single-phase load change

is introduced in the phase u from 1.0 to 1.3 p.u. As

expected on the load side, a neutral current flows through

the fourth leg (iLn), but on the source side, no neutral

current is observed (isn). Simulated results show that

the proposed control scheme effectively eliminate current

unbalanced. Additionally, Fig. 5 shows that the DC­

voltage remains constant through the whole active power

filter operation. Experimental results corroborate the successful oper­

ation of the active filter shown in the simulations. The

dynamic performance of the active filter is tested under

balanced and unbalanced load conditions. Fig. 6 shows

the transient response when APF starts to operate. The

line current immediately becomes sinusoidal and the

capacitor-voltage behavior is as expected. The T H Di is reduced from 27.09% to 4.54%.

Tek JL • Acq Complete M Pos: O,OOOs

iLu ...

VVV

TRIGGER

Type

11m Source

I!il Slope

1m '.\J\J\J'vV a;.m Vdc Coupling -.pa:akt "Vill""� �,�! L. \t.; • �",. .\, f ,. .... 1 l J' II iii "'-CH1 50.0V CH2 SO.OV M 10.0ms Eit..r 312mV

CH3 SO.OV CH4 10.0V 10-Mar-12 03:25 <10Hz

Figure 6. Experimental transient response under APF connection.

In Fig. 7, the response of the series active filter under

load change is shown. The line current remains sinu­

soidal and the capacitor voltage returns to its reference

in two cycles, with minimum variation when the load

changes. In this case, a step change is introduced from

0.6 to 1.0 p.u.

Tek JL

"'-

• Acq Complete M Pos: O,OOOs ...

TRIGGER

Type

11m Source

!iii Slope

1m Mode

WllIiIlI Coupling

IiI! CH1 50.0V CH2 SO.OV M 10.0ms

CH3 50.0V CH4 S.OOV 10-Mar-12 04:49

CH1 ..r 32.0V

<10Hz

Figure 7. Experimental results under balanced load change (0.6 to 1.0 p.u.)

In the last case, the phase u load was increased from

1348

Page 6: Improved Active Power Filter Performance for Distribution

1.0 to 1.3 p.u. The corresponding waveforms are shown

in Fig. 8. This figure shows that the active filter is able

to compensate current flow in the neutral wire and has

fast transient performance. Moreover, results show that

the four wire output current ion is effectively controlled,

and the neutral current of the system remains close to

zero even if a unbalance of 30% is applied.

Tek • Acq Complete M Pos: O.OOOs

Vsu I ( II'

TRIGGER

Type

m Source

!!iii Slope

IiII:IliE Mode

I1a Coupling

iii! CH1 50,OV CH2 50,OV M 10,Oms CH1 f 58,OV

CH3 50,OV CH4 50,OV 11-Mar-12 04:41 <10Hl

Figure 8. Experimental results under unbalanced phase u load change (1.0 to 1.3 p.u.)

VII. CONCLUSION

An improved dynamic compensation scheme for

power distribution systems with renewable generation

with a prediction time of one sample has been proposed

to improve the distribution system current quality. The

proposed predictive control algorithm has proved to be

good alternative for active power filter applications.

The advantages of the proposed control scheme re­

lated with simplicity, modeling and implementation have

proved that predictive control schemes are a good alter­

native to classical methods proposed previously. Sim­

ulated and experimental results have shown that com­

pensation effectiveness of the active power filter is well

achieved with predictive techniques.

ACKNOWLEDGMENT

The authors wish to thank the financial support from

the the Chilean Fund for Scientific and Technological

Development (FONDECYT) through project 11 10592 Basal Project FB0821.

REFERENCES

[1] S. Naidu and D. Fernandes, "Dynamic voltage restorer based on a four-leg voltage source converter," lET Gener. Transm,

Distrib., vol. 3, no. 5, pp. 437-447, May 2009.

[2] D. Shen and P. Lehn, "Fixed-frequency space-vector­modulation control for three-phase four-leg active power filters," lET Electr. Power Appl" vol. 149, no. 4, pp. 268-274, Jul. 2002.

[3] R. Zhang, F. Lee, and D. Boroyevich, "Four-legged three-phase PFC rectifier with fault tolerant capability," in Proc. IEEE­

PESC Conf, vol. 1, Jun. 2000, pp. 359-364, Galway, Ireland. [4] D. Zmood and D. Holmes, "Stationary frame current regulation

of PWM inverters with zero steady-state error," IEEE Trans.

Power Electron., vol. 18, no. 3, pp. 814-822, May 2003. [5] M. Ryan, R, De Doncker, and R. Lorenz, "Decoupled control of

a four-leg inverter via a new 4x4 transformation matrix," IEEE

Trans. Power Electron., vol. 16, no. 5, pp. 694-701, Sep. 2001. [6] C. Jacobina, M. de Rossiter Correa, R. Pinheiro, E. da Silva,

and A. Lima, "Modeling and control of unbalanced three-phase systems containing PWM converters," IEEE Trans. Ind. Appl"

vol. 37, no. 6, pp. 1807-1816, Dec. 2001. [7] G. Dong and O. Ojo, "Current regulation in four-leg voltage­

source converters," IEEE Trans. Ind. Electron., vol. 54, no. 4, pp. 2095-2105, Aug. 2007.

[8] J. Rodriguez, J. Pontt, C. Silva, P. Correa, P. Lezana, P. Cortes, and U. Ammann, "Predictive current control of a voltage source inverter," IEEE Trans. Ind. Electron., vol. 54, no. 1, pp. 495-503, Feb. 2007.

[9] P. Cortes, G. Ortiz, J. Yuz, J. Rodriguez, S. Vazquez, and 1. Franquelo, "Model predictive control of an inverter with out­put LC filter for UPS applications," IEEE Trans. Ind. Electron.,

vol. 56, no. 6, pp. 1875-1883, Jun, 2009. [10] R. Vargas, P. Cortes, U. Ammann, J. Rodriguez, and J. Pontt,

"Predictive control of a three-phase neutral-point-clamped in­verter," IEEE Trans, Ind. Electron., vol. 54, no. 5, pp. 2697-2705, Oct. 2007.

[11] P. Cortes, A. Wilson, S. Kouro, J. Rodriguez, and H. Abu­Rub, "Model predictive control of multilevel cascaded H-bridge inverters," IEEE Trans. Ind. Electron., vol. 57, no. 8, pp. 2691-2699, Aug. 2010.

[12] P. Lezana, R, Aguilera, and D. Quevedo, "Model predictive control of an asymmetric flying capacitor converter," IEEE

Trans, Ind. Electron., vol. 56, no. 6, pp. 1839-1846, Jun. 2009. [13] P. Correa, J. Rodriguez, I. Lizama, and D. Andler, "A predictive

control scheme for current-source rectifiers," IEEE Trans. Ind.

Electron., vol. 56, no. 5, pp. 1813-1815, May 2009. [14] M. Rivera, J. Rodriguez, B. Wu, J. Espinoza, and C. Rojas,

"Current control for an indirect matrix converter with filter resonance mitigation," IEEE Trans, Ind. Electron., vol. 59, no. 1, pp. 71-79, Jan. 2012.

[15] P. Correa, M. Pac as, and J. Rodriguez, "Predictive torque control for inverter-fed induction machines," IEEE Trans. Ind.

Electron., vol. 54, no. 2, pp. 1073-1079, Apr. 2007. [16] S. Ali and M. Kazmierkowski, "PWM voltage and current

control of four-leg VSI," in Proc, IEEE-ISlE Conf, vol. 1, Jul. 1998, pp. 196-201, Pretoria, South Africa.

[17] S. Kouro, P. Cortes, R. Vargas, U. Ammann, and J. Rodriguez, "Model predictive control - A simple and powerful method to control power converters," IEEE Trans, Ind. Electron., vol. 56, no. 6, pp. 1826-1838, Jun. 2009.

[18] R. M. Santos Filho, P. F. Seixas, P. C. Cortizo, 1. A. B. Torres, and A. F. Souza, "Comparison of three single-phase pll algorithms for ups applications," Industrial Electronics, IEEE

Transactions on, vol. 55, no. 8, pp. 2923 -2932, aug. 2008.

1349