Installation Instructions SensaGuard™ 18 mm Plastic Barrel—440N-Z21S16*, 440N-Z21S26* IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. Installation Instructions Installation must be in accordance with the following steps and stated specifications and should be carried out by suitable competent personnel. The unit is not to be used as a mechanical stop. Guard stops and guides must be fitted. Adherence to the recommended maintenance instructions forms part of the warranty. This device is intended to be part of the safety related control system of a machine. Before installation, a risk assessment should be performed to determine whether the specifications of this device are suitable for all foreseeable operational and environmental characteristics of the machine to which it is to be fitted. Refer to Technical Specifications below for certification information and ratings. Technical Specifications ENGLISH: This instruction sheet is available in multiple languages at www.rockwellautomation.com/literature. Select publication language and type "SensaGuard" in the search field. GERMAN: Dieses Instruktionsblatt kann in mehreren Sprachen unter www.rockwellautomation.com/literature gelesen werden. Bitte Ihre Sprache anwählen und "SensaGuard" im Suchfeld eintippen. FRENCH: Ces instructions sont disponibles dans différentes langues à l'adresse suivante www.rockwellautomation.com/literature. Sélectionner la langue puis taper “SensaGuard” dans le champ de recherche. ITALIAN: La presente scheda d'istruzione è disponibile in varie lingue sul sito www.rockwellautomation.com/literature. Selezionare la lingua desiderata e digitare "SensaGuard" nel campo di ricerca. SPANISH: Puede encontrar esta hoja de instrucciones en varios idiomas en www.rockwellautomation.com/literature. Seleccione el idioma de publicación y escriba "SensaGuard" en el campo de búsqueda. PORTUGUESE: Esta folha de instruções está disponível em várias línguas em www.rockwellautomation.com/literature. Seleccione a língua de publicação e entre com "SensaGuard" no espaço de busca. POLISH: Ta kartka z instrukcjami jest dostepna w wielu jezykach na stronie: www.rockwellautomation.com/literature Wybierz jezyk publikacji i wpisz w polu poszukiwania "SensaGuard". The presence of spare actuators compromise the integrity of the safety systems. Personal injury or death, property damage or economic loss can result. Appropriate management controls, working procedures and alternative protective measures should be introduced to control their use and availability. Do not defeat, tamper, remove or bypass this unit. Severe injury to personnel could result. The sensor MUST be connected to a Class 2 SELV 24V DC, +10%/-15% power supply. Safety Classification Type 4 Interlocking Device per ISO 14119 (Low Coding) PLe, Cat 4 per ISO 13849-1 SIL CL3 per IEC 62061 and IEC 61508 Standards ISO 14119, IEC 60947-5-3, IEC 61508, IEC 62061, ISO 13849-1, UL508, CSA 22.2 No.14 Certifications TÜV, CE Marked for all applicable directives, cULus Functional Safety Data PFH D : 1.12 - 10 -9 ATTENTION WARNING Operating Characteristics Outputs (guard door closed, actuator in place) Environmental Sensing Distance 18 mm Actuator 30 mm Actuator Assured Make 15 mm 25 mm Assured OFF 25 mm 35 mm Typical Misalignment (±7 mm in both axes) Repeat Accuracy 10% of sensing range Max. output current (all outputs) 200 mA Input Current 50 mA (no load supply current) Operational Current, Min. 1 mA DC Off-state Current <0.5 mA DC Max. no. of switches, connected in series Unlimited. See Unit Response Time section on page 4. Operating Voltage 24V DC +10%/-15% Class 2 SELV power supply Frequency of operating cycle 1 Hz Response Time (Off) 54 ms first switch, 18 ms for each additional switch Case Material Polycarbonate Actuator Material Polycarbonate Outputs Description Status Safety 2 x PNP, 0.2 A max. ON (+24V DC) Auxiliary 1 x PNP, 0.2 A max. OFF (0V DC) Operating Temperature [C (F)] -10…+55 ° (14…131 °) Operating Humidity 5…95% relative Washdown Rating NEMA 3, 4X, 12, 13, IP69k Shock & Vibration IEC 68-2-27 30 g, 11 ms/IEC 68-2-6 10…55 Hz Radio Frequency IEC 61000-4-3 IEC 61000-4-6

IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE.OSSD outputs. Green LED flashes. 0 ms 54 ms 72 ms 90 ms Actuator 1 is out of sensing range. Actuator 2 and 3 are in sensing range

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

  • Installation InstructionsSensaGuard™ 18 mm Plastic Barrel—440N-Z21S16*, 440N-Z21S26*

    IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE.

    Installation InstructionsInstallation must be in accordance with the following steps and stated specifications and should be carried out by suitable competent personnel. The unit is not to be used as a mechanical stop. Guard stops and guides must be fitted. Adherence to the recommended maintenance instructions forms part of the warranty.

    This device is intended to be part of the safety related control system of a machine. Before installation, a risk assessment should be performed to determine whether the specifications of this device are suitable for all foreseeable operational and environmental characteristics of the machine to which it is to be fitted. Refer to Technical Specifications below for certification information and ratings.

    Technical Specifications

    ENGLISH: This instruction sheet is available in multiple languages at www.rockwellautomation.com/literature. Select publication language and type "SensaGuard" in the search field.

    GERMAN: Dieses Instruktionsblatt kann in mehreren Sprachen unter www.rockwellautomation.com/literature gelesen werden. Bitte Ihre Sprache anwählen und "SensaGuard" im Suchfeld eintippen.

    FRENCH: Ces instructions sont disponibles dans différentes langues à l'adresse suivante www.rockwellautomation.com/literature. Sélectionner la langue puis taper “SensaGuard” dans le champ de recherche.

    ITALIAN: La presente scheda d'istruzione è disponibile in varie lingue sul sito www.rockwellautomation.com/literature. Selezionare la lingua desiderata e digitare "SensaGuard" nel campo di ricerca.

    SPANISH: Puede encontrar esta hoja de instrucciones en varios idiomas en www.rockwellautomation.com/literature. Seleccione el idioma de publicación y escriba "SensaGuard" en el campo de búsqueda.

    PORTUGUESE: Esta folha de instruções está disponível em várias línguas em www.rockwellautomation.com/literature. Seleccione a língua de publicação e entre com "SensaGuard" no espaço de busca.

    POLISH: Ta kartka z instrukcjami jest dostepna w wielu jezykach na stronie: www.rockwellautomation.com/literature Wybierz jezyk publikacji i wpisz w polu poszukiwania "SensaGuard".

    The presence of spare actuators compromise the integrity of the safety systems. Personal injury or death, property damage or economic loss can result. Appropriate management controls, working procedures and alternative protective measures should be introduced to control their use and availability.

    Do not defeat, tamper, remove or bypass this unit. Severe injury to personnel could result. The sensor MUST be connected to a Class 2 SELV 24V DC, +10%/-15% power supply.

    Safety ClassificationType 4 Interlocking Device per ISO 14119 (Low Coding)PLe, Cat 4 per ISO 13849-1SIL CL3 per IEC 62061 and IEC 61508

    StandardsISO 14119, IEC 60947-5-3, IEC 61508, IEC 62061, ISO 13849-1, UL508, CSA 22.2 No.14

    Certifications TÜV, CE Marked for all applicable directives, cULus

    Functional Safety Data PFHD: 1.12 - 10-9

    ATTENTION

    WARNING

    Operating Characteristics

    Outputs(guard door closed, actuator in place)

    Environmental

    Sensing Distance 18 mm Actuator 30 mm Actuator

    Assured Make 15 mm 25 mm

    Assured OFF 25 mm 35 mm

    Typical Misalignment (±7 mm in both axes)

    Repeat Accuracy 10% of sensing range

    Max. output current (all outputs) 200 mA

    Input Current 50 mA (no load supply current)

    Operational Current, Min. 1 mA DC

    Off-state Current

  • Protection

    Dimensions [mm (in.)]

    Mode of Operation

    Status indicators:

    • “Power/Fault” LED illuminates green: Door/guard closed, safety outputs active.

    • “Power/Fault” LED illuminates red: Door/guard open, safety outputs off.

    • “Power/Fault” LED flashes red: Unit failure. See Diagnostic section on page 3.

    • “Power/Fault” LED flashes green: Safety inputs off.

    Short-circuit Incorporated

    Current Limitation Incorporated

    Overload Incorporated

    False Pulse Incorporated

    Transient Noise Incorporated

    Reverse Polarity Incorporated

    Overvoltage Incorporated

    Thermal Shutdown/Restart Incorporated

    Electrical Life 10 x 106

    30 mm Actuator

    48.92[1.926]

    19.81[0.78]

    22.22[0.875]

    48.92[1.926]

    19.81[0.78]

    22.22[0.875]

    30.40[1.197]

    16.84[0.663]

    3.17[0.125]

    4.57[0.18]

    2 places

    Dia.

    Sensor18 mm Actuator

    67.06[2.640]2.03

    [.080]

    M18X1

    36.47[1.436]

    13.72[0.54] 15.87

    [0.625]

    36.47[1.436]

    13.72[0.54]

    15.87[0.625]

    4.57[0.180] DIA

    19.81[0.78]

    3.17[0.125]

    15.42[0.607]

    2 PLACES

    2

    Mounting InformationUse non-removable screws, bolts, or nuts to mount the switch and actuator. Do not over torque the mounting hardware.

    Position the switch and actuator so they are aligned with each other.

    Mount the switch and actuator to removable guard, door, or gate. Keep the switch and actuator within the sensing range below.

    This switch is not meant to be fully embedded in metal. Use the stainless steel version (440N-Z21S17* or 440N-Z21U17*) for embedding.

    Nut Torque Specification

    Plastic Barrel Switch: 2.26 N•m (20 in•lb)Plastic Actuators: 2.26 N•m (20 in•lb)

    Minimum Distance Between Sensors

    Misalignment Curve

    18 mm Unit with 18 mm Target

    There must be a minimum spacing of 4 mm (0.157 in.) if actuator and sensor face approaches laterally. This will prevent false triggering due to the side lobe areas.

    18 mm Actuator

    75 mm

    Sensor1

    Sensor2

    30 mm Actuator

    100 mm

    Sensor1

    Sensor2

    Lateral Misalignment Tolerance—mm (in)

    Face

    to Fa

    ce D

    istan

    ce—

    mm

    -15(-0.59)

    -10(-0.39)

    -5(-0.19)

    0 5(0.19)

    10(0.39)

    15(0.59)

    0

    5

    10

    15

    20

    25

    -25(-0.98)

    -20(-0.787)

    20(0.787)

    25(0.98)

    Side Lobe Side Lobe

    Assured SensingDistance

    OFF OFF

    ON

    Assured SensingDistance

    OFF

    IMPORTANT

  • 18 mm Unit with 30 mm Target

    Wiring Diagram

    8-Pin Unit

    Recommended mating cable, 2 m (6.5 ft)—889D-F8AB-2. Replace the 2 with 5 (5 m) or 10 (10 m) for standard cable lengths.

    There must be a minimum spacing of 7 mm (0.275 in.) if actuator and sensor face approaches laterally. This will prevent false triggering due to the side lobe areas.

    Pin Number Wire Color Signal

    1 White Aux. Outputs

    2 Brown +24V

    3 Green NA

    4 Yellow OSSD 2, +24V Input

    5 Grey OSSD 1

    6 Pink OSSD 2

    7 Blue 0V

    8 Red OSSD 1, +24V Input

    0

    5

    10

    15

    20

    25

    30

    35

    -30(-1.18)

    -20(-0.787)

    -10(-0.39)

    0 10(0.39)

    20(0.787)

    30(1.18)

    Face

    to Fa

    ce D

    istan

    ce—

    mm

    Side Lobe Side Lobe

    Assured SensingDistanceOFF OFF

    ON

    Lateral Misalignment Tolerance—mm (in)

    Assured SensingDistance

    OFF

    IMPORTANT

    47

    68

    1

    5

    23

    Brown

    White

    Blue

    Pink

    Grey

    Green

    Red

    Yellow

    3

    5-Pin Unit

    Recommended cordset, 2m (6.5 ft) - 889D-F5AC-2. Replace the 2 with 5 (5 m) or 10 (10 m) for standard cable lengths.

    Note: If the user does not require the auxiliary signal, a 4-pin cordset (889D-F4AC-2) can be used.

    Recommended patchcord for use with ArmorBlock® Guard Safety I/O, 2 m (6.5 ft) - 889D-F4ACDM-2. Replace the 2 with 0M3 (0.3 m), 1 (1 m), 5 (5 m), or 10 (10 m) for standard cable lengths.

    Note: Do not use a 5-pin patchcord with the ArmorBlock.

    Diagnostic

    Unit Indicators (per IEC 60073)

    Pin Number Signal

    1 +24V

    2 OSSD 1

    3 0V

    4 OSSD 2

    5 Aux.

    Device Output

    LED

    State Status Troubleshooting

    Off Not Powered NA

    Red Not Safe, OSSD not active NA

    Green Safe, OSSD active NA

    Green Flash

    Power up test or OSSD inputs not valid

    Check 24V DC or OSSD inputs (yellow and red wire)

    Red Flash

    1 Hz Flash Recoverable Fault 4 Hz Flash Non-recoverable Fault

    Recoverable fault —check OSSD outputs are not shorted to GND, 24V DC or each other.

    Cycle power.

    Refer to Technical Specifications (page 1) for certification information and ratings.

    15

    2

    4

    3

    IMPORTANT

  • TroubleshootingSeries Circuit

    Unit Response Time (does not include safety control system response time)

    Refer to Technical Specifications (page 1) for certification information and ratings.

    Refer to Technical Specifications (page 1) for certification information and ratings.

    Yel

    Red

    Brow

    n

    Gray

    Pink

    Blue

    24VDCPowerSupply

    1606-XL120D

    Switch 1

    +24

    RTN

    Switch 2

    White

    Whit

    e

    Yel

    Red

    Brow

    n

    Gray

    Pink

    Blue

    Actuator 1 Actuator 2

    Switch 3

    Whit

    e

    Yel

    Red

    Brow

    n

    Gray

    Pink

    Blue

    Actuator 3

    Switch 4

    Whit

    e

    Yel

    Red

    Brow

    n

    Gray

    Pink

    Blue

    Actuator 4

    Switch 5

    Whit

    e

    Yel

    Red

    Brow

    n

    Gray

    Pink

    Blue

    Actuator 5

    +24 V+24 V

    +24 V+24 V

    +0 V+0 V

    +0 V+0 V

    +0 V+0 V

    Actuator 2 is in sensing range.Switch 2 is functioning properlyOSSDs are energize to 24 VGreen LED is ON.

    Actuator 3 is in sensing range.Switch 3 has fault.See Table Above—Red LED is flashing

    Actuator 1 is in sensing range.Switch 1 is functioning properlyOSSDs are energize to 24 VGreen LED is ON.

    Actuator 4 is in sensing range.Switch 4 is functioning properly.Series inputs are 0 V.OSSDs are de-energized to 0V .Green LED is Flashing to indicateSeries inputs are not 24V.

    Actuator 5 is in sensing range.Switch 5 is functioning properl y .Series inputs are 0V.OSSDs are de-energized to 0V.Green LED is Flashing to indicateSeries inputs are not 24V.

    OSSD’s are OFFRecoverable fault

    IMPORTANT

    YelRed

    WhiteGrayPink

    Blue

    24V DCPowerSupply

    1606

    Sens

    or 1

    +24

    RT

    Sens

    or 2

    Brown Brown Gray

    PinkWhite

    YelRedBl

    ue

    Sens

    or 3

    Brown Yel

    RedWhiteGrayPink

    Blue

    A1

    S21

    S11 41332313S12S52

    42342414A2S34S22

    MSR127TP

    Actu

    ator

    1

    Actu

    ator

    2

    Actu

    ator

    3

    Initial Conditions:All actuators are in sensing distance.

    Actuator 1 is moved out ofsensing range.

    Sensor 2 drops the 24 volts (red and yellow) from Sensor 1 OSSD outputs.Green LED flashes.

    Sensor 3 drops the 24 volts (red and yellow) from Sensor 2 OSSD outputs.Green LED flashes.

    0 ms 54 ms 72 ms 90 ms

    Actuator 1 is out of sensing range.Actuator 2 and 3 are in sensing range.

    Actuator 1 is moved into sensing range.Sensor 1 OSSD outputs are energized.

    Sensor 2 OSSD inputs (red and yellow) transition to 24V DC from Sensor 1 OSSD outputs.Sensor 2 OSSD outputs are energized

    Sensor 3 OSSD inputs (red and yellow) transition to 24V DC from Sensor 2 OSSD outputs.Sensor 3 OSSD outputs are energized.

    0 ms 360 ms 378 ms 396 ms

    OFF

    ON

    IMPORTANT

    4

  • Application Wiring Examples

    Refer to Technical Specifications (page 1) for certification information and ratings.

    K1

    +24V DC

    MSR127RP with 1 sensor, monitored manual reset, driving 100S or 700S safety controllers.

    A1 S11 S52 S12 13 23 33 41

    S21 S22 S34 A2 14 24 34 42

    MSR127RP

    Reset

    GND

    BlueG

    rayPink

    YellowRed

    Brown

    SensaGuardUnit 1

    K2

    +24V DC

    GND

    MSR127RP with 3 sensors in series, monitored manual reset, driving 100S or 700S safety controllers

    BlueG

    rayPinkYellowRed

    Brown

    SensaGuardUnit 1

    SensaGuardUnit 2

    SensaGuardUnit 3

    K1

    A1 S11 S52 S12 13 23 33 41

    S21 S22 S34 A2 14 24 34 42

    MSR127RP

    Reset

    K2BlueG

    rayPinkYellowRed

    Brown

    BlueG

    rayPink

    YellowRedBrow

    n

    MSR127RP with 3 sensors and 1 440L light curtain in series, monitored manual reset, driving 100S or 700S safety relays.Note: Light curtain must be last (farthest from MSR127).

    GND

    A1 S11 S52 S12 13 23 33 41

    S21 S22 S34 A2 14 24 34 42

    MSR127RP

    Reset

    K1 K2

    +24V DC

    BlueG

    rayPinkYellowRedBrow

    n

    SensaGuardUnit 1

    SensaGuardUnit 2

    SensaGuardUnit 3 GuardShield

    BlueG

    rayPinkYellowRedBrow

    n

    BlueG

    rayPinkYellowRedBrow

    n

    BlueG

    rayPink

    Brown

    A1 S11 S52 S12 13 23 33 41

    S21 S22 S34 A2 14 24 34 42

    MSR127TP

    GND

    MSR127RP with 1 sensor, automatic reset, driving 100S or 700S safety controllers

    +24V DC

    SensaGuardUnit 1

    K1 K2

    BlueG

    rayPinkYellowRedBrow

    n

    MSR127TP with 3 sensors in series, automatic reset, driving 100S or 700S relays.

    MSR127TP

    +24V DC

    GND

    Blue

    Gray

    Pink

    YellowRed

    Brown

    SensaGuardUnit 1

    K1

    A1 S11 S52 S12 13 23 33 41

    S21 S22 S34 A2 14 24 34 42

    K2

    Blue

    Gray

    Pink

    YellowRed

    Brown

    Blue

    Gray

    Pink

    YellowRed

    Brown

    SensaGuardUnit 3

    SensaGuardUnit 2

    MSR127TP with 3 sensors and 1 440L light curtain in series, automatic reset, driving 100S or 700S safety contactors.Note: Light curtain must be last (farthest from MSR127)

    MSR127TP

    GND

    A1 S11 S52 S12 13 23 33 41

    S21 S22 S34 A2 14 24 34 42

    K1 K2

    +24V DC

    Blue

    Gray

    Pink

    YellowRed

    Brown

    Blue

    Gray

    Pink

    YellowRed

    Brown

    Blue

    Gray

    Pink

    YellowRed

    Brown

    Blue

    Gray

    Pink

    Brown

    GuardShieldSensaGuardUnit 1SensaGuard

    Unit 3SensaGuard

    Unit 2

    IMPORTANT

    5

  • Application Wiring Examples

    Refer to Technical Specifications (page 1) for certification information and ratings.

    MSR200 series with 3 sensors and 1 440L light curtain, automatic reset, driving 100S or 700S safety contactors.Note: Light curtain can be attached to any input

    GuardShield

    +24V DC

    GND

    440R-H23177

    Y40 Y41S51S12 S20 S32 S11 S21 S31 S41 13 23 31 Y42 A1S32S20S12

    S42 S50 S62 S34 Y1 Y2 Y3 14 24 32 Y32 Y33 Y30 A2S62S50S42

    440R-H23179

    K1

    S32S20S12

    S62S50S42

    S32

    S32

    440R-H23180

    MSR221P MSR211P MSR230P

    K2K1

    K2 K3

    K4

    SensaGuard

    Blue

    Brown

    GrayPink

    Blue

    Brown

    Yellow

    Red

    GrayPink

    SensaGuard SensaGuard

    GrayPink GrayPink

    Blue

    Brown

    Yellow

    Red

    Blue

    Brown

    Yellow

    Red

    MSR200 series with 3 sensors and 1 440L light curtain, manual reset, driving 100S or 700S safety contactors.Note: Light curtain can be attached to any input.

    Reset

    GuardShield

    +24V DC

    GND

    440R-H23177

    Y40 Y41S51S12 S20 S32 S11 S21 S31 S41 13 23 31 Y42 A1S32S20S12

    S42 S50 S62 S34 Y1 Y2 Y3 14 24 32 Y32 Y33 Y30 A2S62S50S42

    440R-H23179

    K1

    S32S20S12

    S62S50S42

    S32

    S32

    440R-H23180

    MSR221P MSR211P MSR230P

    K2K1

    K2 K3

    K4

    SensaGuard

    Blue

    Brown

    GrayPink

    Blue

    Brown

    Yellow

    Red

    GrayPink

    SensaGuard SensaGuard

    GrayPink GrayPink

    Blue

    Brown

    Yellow

    Red

    Blue

    Brown

    Yellow

    Red

    MSR200 series with 4 sensors, automatic reset, driving 100S or 700S safety contactors.

    Yellow

    Red

    +24V DC

    GND

    440R-H23177

    Y40 Y41S51S12 S20 S32 S11 S21 S31 S41 13 23 31 Y42 A1S32S20S12

    S42 S50 S62 S34 Y1 Y2 Y3 14 24 32 Y32 Y33 Y30 A2S62S50S42

    440R-H23179

    K1

    S32S20S12

    S62S50S42

    S32

    S32

    440R-H23180

    MSR221P MSR211P MSR230P

    K2K1

    K2 K3

    K4

    SensaGuardSensaGuard

    Blue

    Brown

    GrayPink

    Blue

    Brown

    Yellow

    Red

    GrayPink

    SensaGuard SensaGuard

    GrayPink GrayPink

    Blue

    Brown

    Yellow

    Red

    Blue

    Brown

    Yellow

    Red

    MSR200 series with 4 sensors, manual reset, driving 100S or 700S safety contactors.

    Reset

    +24V DC

    GND

    440R-H23177

    Y40 Y41S51S12 S20 S32 S11 S21 S31 S41 13 23 31 Y42 A1S32S20S12

    S42 S50 S62 S34 Y1 Y2 Y3 14 24 32 Y32 Y33 Y30 A2S62S50S42

    440R-H23179

    K1

    S32S20S12

    S62S50S42

    S32

    S32

    440R-H23180

    MSR221P MSR211P MSR230P

    K2K1

    K2 K3

    K4

    SensaGuardSensaGuard

    Blue

    Brown

    GrayPink

    Blue

    Brown

    Yellow

    Red

    Yellow

    Red

    GrayPink

    SensaGuard SensaGuard

    GrayPink GrayPink

    Blue

    Brown

    Yellow

    Red

    Blue

    Brown

    Yellow

    Red

    IMPORTANT

    6

  • List of Recommended Safety Control InterfacesGSR DI, GSR DIS, GSR SI, CR30, MSR126, MSR127, MSR131, MSR138, MSR211, MSR221, MSR121, MSR320, SmartGuard™,1791DS/ES CompactBlock™ Guard Safety I/O, 1732DS/ES ArmorBlock Guard Safety I/O. Relay must have OSSD (light curtain) inputs.

    Maintenance

    Monthly

    Check the correct operation of the switching circuit. Also check for signs of abuse or tampering. Inspect the switch casing for damage.

    RepairIf there is any malfunction or damage, no attempts at repair should be made. The unit should be replaced before machine operation is allowed.

    Declaration of ConformityThis is to declare that the products shown in this document conform with the Essential Health and Safety Requirements (EHSRs) of the European Machinery Directive. These products also conform to EN 60947-5-3, EN ISO 14119, and have Third Party Approval.

    For a comprehensive certificate please visit: www.ab.com/safety.

    Check the machine is isolated and stopped whenever the interlocked guard door is open.

    IMPORTANT: Afterinstallation and commissioning, the actuator, switch and switch lid fixing screws should be coated with tamper evident varnish or similar compound.

    7

  • o

    Rockwell Automation maintains current product environmental information on its website athttp//www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/pr

    Allen-Bradley, ArmorBlock, CompactBlock, Rockwell Software, SensaGuard, and SmartGuard are tradema

    Trademarks not belonging to Rockwell Automation are property of their respective companies.

    Publication 440N-IN010C-EN-P — September 2014 — 10000979Supersedes Publication 440N-IN010B-EN-P — August 2014

    duct-environmental-compliance.page

    rks of Rockwell Automation, Inc.

    549 Ver 00 PN-243703Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

    SensaGuard 18 mm Plastic Barrel — 440N-Z21S16*, 440N-Z21S26* Installation Instructions Installation InstructionsTechnical SpecificationsOperating CharacteristicsOutputs (guard door closed, actuator in place)EnvironmentalProtectionDimensions [mm (in.)]Mode of OperationStatus indicators:

    Mounting InformationNut Torque SpecificationMinimum Distance Between Sensors

    Misalignment Curve18 mm Unit with 18 mm Target18 mm Unit with 30 mm Target

    Wiring Diagram8-Pin Unit5-Pin Unit

    DiagnosticUnit Indicators (per IEC 60073)

    TroubleshootingSeries CircuitUnit Response Time (does not include safety control system response time)

    Application Wiring ExamplesApplication Wiring ExamplesList of Recommended Safety Control InterfacesMaintenanceMonthly

    RepairDeclaration of Conformity

    Back Cover

    /ColorImageDict > /JPEG2000ColorACSImageDict > /JPEG2000ColorImageDict > /AntiAliasGrayImages false /CropGrayImages true /GrayImageMinResolution 300 /GrayImageMinResolutionPolicy /OK /DownsampleGrayImages true /GrayImageDownsampleType /Average /GrayImageResolution 300 /GrayImageDepth -1 /GrayImageMinDownsampleDepth 2 /GrayImageDownsampleThreshold 2.00000 /EncodeGrayImages true /GrayImageFilter /DCTEncode /AutoFilterGrayImages false /GrayImageAutoFilterStrategy /JPEG /GrayACSImageDict > /GrayImageDict > /JPEG2000GrayACSImageDict > /JPEG2000GrayImageDict > /AntiAliasMonoImages false /CropMonoImages true /MonoImageMinResolution 1200 /MonoImageMinResolutionPolicy /OK /DownsampleMonoImages true /MonoImageDownsampleType /Average /MonoImageResolution 1200 /MonoImageDepth -1 /MonoImageDownsampleThreshold 1.50000 /EncodeMonoImages true /MonoImageFilter /CCITTFaxEncode /MonoImageDict > /AllowPSXObjects false /CheckCompliance [ /None ] /PDFX1aCheck false /PDFX3Check false /PDFXCompliantPDFOnly false /PDFXNoTrimBoxError true /PDFXTrimBoxToMediaBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXSetBleedBoxToMediaBox true /PDFXBleedBoxToTrimBoxOffset [ 0.00000 0.00000 0.00000 0.00000 ] /PDFXOutputIntentProfile (None) /PDFXOutputConditionIdentifier () /PDFXOutputCondition () /PDFXRegistryName () /PDFXTrapped /False

    /CreateJDFFile false /Description > /Namespace [ (Adobe) (Common) (1.0) ] /OtherNamespaces [ > /FormElements false /GenerateStructure true /IncludeBookmarks false /IncludeHyperlinks false /IncludeInteractive false /IncludeLayers false /IncludeProfiles true /MultimediaHandling /UseObjectSettings /Namespace [ (Adobe) (CreativeSuite) (2.0) ] /PDFXOutputIntentProfileSelector /NA /PreserveEditing true /UntaggedCMYKHandling /LeaveUntagged /UntaggedRGBHandling /LeaveUntagged /UseDocumentBleed false >> ]>> setdistillerparams> setpagedevice