IM Starting&Control

Embed Size (px)

Citation preview

  • 8/3/2019 IM Starting&Control

    1/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 1

    1 Starting of Cage Induction Motors

    There are a number of ways of starting squirrel cage induction motors. Each method has its

    own characteristics and place of correct application. The most commonly used methods are

    outlined in the following paragraphs.

    1.1 Direct-On-Line (DOL) Starting

    At standstill, the cage-type induction motor is similar to a transformer with a shorted

    secondary winding. Hence, the application of rated voltage to the stator winding causes a

    high stator current of around 6 times the rated full-load value, at low power-factor. This

    current quickly decreases as the machine accelerates and slip decreases. The high starting

    current is generally not a problem for the motor itself, since the machine thermal time

    constant is usually much greater than the rotor run-up time. However, it has to be taken

    into account when choosing protection devices for the machine, such as fuses andoverloads. The protection devices are normally designed to effectively ignore this starting

    characteristic.

    An induction motor with a Direct-On-Line (DOL) starter is shown in Fig. 1. Note the fuse

    and overload sensor (OLS) used as protection devices. The drawing of large starting

    currents, in all but small machines, causes the supply voltage in the vicinity of the machine

    to fall, or dip slightly. This is due to the voltage drop across the source impedance and

    may be explained with reference to Fig. 1 in which the voltage at the main distribution

    board is given by: V = ES - Idol ZS

    The system voltage dip may lead to objectionable lamp 'flicker' if excessive or frequent.

    Incandescent lamps are particularly sensitive to fluctuations of voltage magnitude in that afluctuation of 0.5% at a frequency of 8-Hz will cause annoying lamp flicker. Thus, frequent

    starting could be particularly problematic. In addition to incandescent lamp dimming,

    voltage dips can affect other motors running on the same supply, e.g. increase in running

    slip or possibly stalling. This simple method is therefore used where system capacity and

    stiffness is sufficient to stand the high inrush currents without excessive voltage drop.

    The following factors are to be considered while selecting the type of starting:

    Size: e.g. DOL starting of pump motors up to 45-kW.

    Inertia of Load: e.g. DOL starting of fan motors up to 18.6-kW.

    Frequent Start: e.g. DOL starting of pump motors up to 15-kW.

    It is good practice to avoid, where possible, simultaneous starting of motors, which may

    lead to excessive voltage drops.

    I

    Z

    ES V~

    S

    Other loads

    M

    oo

    DOLcontactor

    starter

    OLSFuse

    Fig.1: Connections and equivalent circuit for DOL starting

  • 8/3/2019 IM Starting&Control

    2/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 2

    1.2 Reduced Voltage Starting

    - Star-Delta starting

    This starting method is employed when the motor windings are connected in delta () for

    normal operation and in star (Y) during start-up. Fig.2 shows a / starter in which three

    contactors (RLS) per phase are used to connect the stator windings in Y and/or . At

    starting, the star (S) contactors are closed while the delta contactors R are open to allow the

    stator windings to be Y connected. When the motor picks up speed and current falls below

    a set value, the star contactors S are de-energised and after a very short delay (to reduce

    electrical transients) the delta () contactors R are energised connecting the stator winding

    in delta.

    Fig.2: Winding connections for Y-start -run (Y/) method

    When the Y-connected motor is started, the stator phase voltage is reduced to 1 3/ , or

    58%, of its normal running value (line voltage). The star phase current is, therefore, also

    reduced by 1 3/ of its normal running delta phase value.

    To consider the effect of star-delta starting on the motor line current, assume an effective

    motor impedance of Z /phase, as shown in the figure below.

    I Line

    VPhase

    R

    Y

    B

    VLine

    R

    Y

    B

    I PhaseVLine

    Z

    Z

    Z

    ZZ

    Z

    I Line

    Y

    If the motor is started in delta-connection (i.e. DOL) then:

  • 8/3/2019 IM Starting&Control

    3/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 3

    IV

    ZPhase

    Line

    i.e.I IV

    Z Line Phase

    Line

    3 3

    However, for the star-connected motor the starting line current is significantly reduced as

    follows from:

    I IV

    Z

    V

    Z

    V

    Z Line Phase

    Phase Line Line

    / 3 1

    3I I Line Line

    1

    3.

    The advantage of this scheme is that no equipment other than a / starter is needed.

    However, the disadvantages are that all six ends of the stator windings must be accessible

    and six 1-core cables or two 3-core cables are required between the starter and the motor.

    In addition, both the starting current and torque are greatly reduced, since the

    electromagnetic torque developed by the motor (at any slip) is directly proportional to the

    square of the applied winding voltage (phase voltage) i.e. T k V 2 where kis a constant.

    If the motor is started with delta-connection (i.e. DOL), VLine = VPhase, and therefore

    T k V DOL Line2. For Y-connected windings during start-up, V VPhase Line / 3 , so that

    T k VLine ( / )32

    meaning that:

    TT

    k V

    k VDOL

    Line

    Line

    3 1

    3

    2

    2.

    The starting torque is 1/3 of that available with DOL starting (the low torque leads to an

    increased run-up time) which makes this method suitable for applications where load

    torque during acceleration is low. Note that since the line current for star connection is also

    1/3 of the DOL value as shown above, the Torque/Line Ampere for the machine remainsconstant.

    - Autotransfomer starting

    In this method, an auto-transformer is placed in series with the motor during starting as

    shown in Fig.3 and the corresponding single-line diagram in Fig. 4-b. The transformer

    action reduces the voltage applied to the motor terminals (by transformer ratio) and the line

    current is consequently less than the motor current. For this reason this method is usually

    used in applications where complete motor acceleration at reduced amperes is needed.

    At starting, the contactor R is open and S & Y are closed so that the stator windings are

    supplied via the low-voltage taps of an autotransformer (Fig.4-b). After run-up, during

    normal running, the switching states of the contactors are changed (R is closed and S&Y

    are open) to allow the machine direct on-line connection.

    Fig.3: Motor terminal connections for auto-transformer starting

  • 8/3/2019 IM Starting&Control

    4/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 4

    MV

    IDOL

    MV

    xV

    x IDOL

    I = x2 IDOL

    (a) (b)

    Fig. 4: Single-line diagram for DOL (a) and auto-transformer (b) starting

    In Fig. 4-a, a voltage V is directly applied to the motor, which results in a starting current

    of IDOL (DOL starting). When starting by an autotransformer, each phase of the motor

    windings is supplied with xVvolts which results in a phase current of xIDOL . Consider

    now the power-balance of the autotransformer:

    V I xV x I DOL i.e. I x I DOL2

    From the above expression it is obvious that when starting with an autotransformer atx-pu.

    tapping (x is less than 1), the starting current is reduced tox2

    of the DOL value.

    As with the / starting, due to the lower applied voltage, the starting torque is also

    reduced:

    TT

    xV

    VxX

    DOL

    2

    2

    2

    so that the Torque/Ampere is unchanged.

    Three tappings are commonly provided with an autotransformer starter (e.g. 40, 60, 75 %

    or 50, 65, 80 % of full voltage) but only one is used during starting. For example, if a 50%

    tapping is used, the motor current is reduced by a factor of 2 and the line starting current is

    reduced to of that with DOL starting. Note that the starting torque is also reduced by a

    factor of 4.

    The main advantages of this scheme are that only a 3-core cable is required between the

    starter and the motor and that the value of tapping (x) can be chosen to suit the

    circumstances. Note that the motor may be either star or delta connected.The main disadvantages are the loss in the starting torque and that the autotransformer

    starter (its cost is comparable to or in excess of the / starter) is only utilised during

    starting.

    2 Effects of Source Impedance on Motor Starting

    In the previous section, the effects of source impedance on starting performance of the

    induction motor were ignored, i.e. the motor terminal voltage was assumed constant.However, the flow of starting current through the source impedance creates a voltage drop,

    which reduces the voltage at the terminals of the motor.

  • 8/3/2019 IM Starting&Control

    5/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 5

    For DOL starting the induction motor and supply system may be represented by the

    equivalent circuit shown in Fig.5, where:

    Zm is the motor standstill impedance per phase and

    ZS is the source impedance.

    Hence IE

    Z ZDOL

    S

    S m

    and V I ZZ

    Z ZE DOL DOL m

    m

    S m

    S

    When starting with a / starter, the starting

    line current is reduced to 1/3 of the DOL

    value. For the same supply voltage ES, this is

    equivalent to increasing the motor effective

    impedance by a factor of 3 (i.e. 3Zm). Thusthe equivalent circuit becomes that in Fig.6,

    which gives:

    IE

    Z Z

    S

    S m

    3

    and V I ZZ

    Z ZEm

    m

    S m

    S

    33

    3

    With autotransformer starting, the effective

    standstill impedance as seen at the terminals

    of the autotransformer, shown in Fig.7, can beexpressed as:

    ZV

    I

    V

    x V

    Z

    Z

    xin

    LX

    m

    m '' ''

    ''2 2

    Hence IE

    ZZ

    x

    LXS

    Sm

    2

    and V I ZE

    ZZ

    x

    Z

    x

    Z

    Z x Z E LX in

    S

    Sm

    m m

    m S

    S' '

    2

    2 2

    Several important observations can be made from the above expressions:

    1/31

    /1

    3

    sm

    sm

    ms

    ms

    DOL

    Y

    ZZ

    ZZ

    ZZ

    ZZ

    I

    Ii.e. the line current is generally lower for Y/

    starting as compared to DOL as expected. For instance, if sm ZZ then

    DOLY

    II 5.0 and forsm

    ZZ 4 this is only 38% of DOL current.

    ~ E

    Z

    Zm

    I =LXx V2 ''

    Zm

    V''

    xV''

    I =mxV ''

    Zm

    Z in

    S

    S

    Fig.7: Autotransformer starting

    IES V~

    ZSoo

    ZmDOL

    DOL

    Fig. 5: DOL starting

    IES V~

    ZSoo

    3ZmY

    Y

    Fig. 6: Y/ starting

  • 8/3/2019 IM Starting&Control

    6/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 6

    11

    /313

    22

    s

    m

    sm

    ms

    ms

    Y

    LX

    Zx

    Z

    ZZ

    x

    ZZ

    ZZ

    I

    Iif 3/1

    2x i.e. 58.03/1 x .

    Therefore, if the autotransformer tap-ratio at start-up is less than 58% then the current

    loading is lower than with Y/ starting.

    13/1

    /1

    ms

    ms

    DOL

    Y

    ZZ

    ZZ

    V

    Vi.e. the voltage drop on the source impedance is smaller for

    star/delta starting method due to lower starting current as shown above.

    1/1

    3/1''

    2

    ms

    ms

    Y ZZx

    ZZ

    V

    Vfor 58.0x . Under this tap-ratio condition, the

    autotransformer starting is better than star-delta one as it gives a higher terminal

    voltage i.e. lower voltage drop.

    Example 1 : Auto-transformer starting

    A 3-phase, 93.5-kW, 460-V, 1141-rpm induction motor has the locked-rotor torque at rated

    voltage equal to 125% its full load value. If started DOL, the motor inrush current is 1-kA.

    Determine starting torque and corresponding stator inrush current if the motor is started at

    reduced voltage using an auto-transformer with a 65% tap. What is the inrush line current

    under this condition?

    Solution:

    Given the rated parameters of the motor, its full load torque is :-

    Nm-52.7821141

    935003030

    n

    PT

    The starting torque is therefore : Nm-15.97825.1 TTT DOLst .

    Since the motor input impedance is constant at standstill (n = 0 i.e. s = 1), the stator inrush

    current is proportional to the stator applied voltage. Thus, 650100065.0 mI -A.

    With the 65% tap, the motor terminal voltage is 29946065.0 mV -V. The starting

    (locked-rotor) torque is proportional to the voltage square which means that :-

    15.97865.0)( 22 DOLrated

    mat T

    V

    VT 413.27-Nm.

    The current calculated above is the secondary current of the auto-transformer. The primary

    (line) current can be easily determined from the power balance expression :-

    65065.0mline

    mlinemmlineline I

    V

    VIIVIV 422.5-A.

    Note that the above current can be actually expressed as (see Fig.4b) : DOLline IxI 2

    where x = 0.65 and DOLI =1000-A.

  • 8/3/2019 IM Starting&Control

    7/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 7

    Example 2 : Star-delta (also called Wye-Delta) starting

    A 3-phase, 45-kW, 460-V, 60-Hz, 1750-rpm induction motor has a locked-rotor impedance

    of 0.547 /phase while the torque is 140% rated. Assuming the machine is to be started

    Wye-Delta (a) sketch the starter-motor connections and explain briefly the starting

    procedure; (b) determine the starting current and torque as well as the machine pole-number. What would be the motor terminal current if started delta connected?

    Solution:

    (a) The winding connections for this starting method can be found in Fig.2. On starting, the

    supply is first applied to the motor with its stator windings star-connected (star contactors S

    are closed and delta ones R are open). As the motor accelerates, its speed stabilises when

    its developed torque become equal to its load torque. This usually happens at about 75% -

    80% of nominal speed as shown in Fig 8. The star contactors (S) are then de-energised, and

    the delta contactors (R) energised to delta-connect the stator windings. Each winding is

    now fed with the full supply voltage, and the motor adopts its normal operating

    characteristics. The run-up time with the windings star-connected is controlled by a timer

    which, typically, can be adjusted from 0 to 30 seconds. This timer is adjusted during

    commissioning to ensure that the star-delta changeover occurs, as closely as possible, at the

    point of torque equilibrium (Fig 8).

    Fig. 8: Typical starting characteristics of conventional cage induction motors: star-delta vs

    DOL method

    (b) The motor is star-connected at start-up and its starting current is therefore:-

    52.4853547.0

    460

    3

    Z

    V

    Z

    VI LL

    phasestart -A

    The full load torque of the machine can be calculated using the rated parameters provided

    as follows:-

  • 8/3/2019 IM Starting&Control

    8/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 8

    55.2451750

    4500030

    60

    2

    fl

    fl

    fl

    flfl n

    PPT -Nm

    The locked rotor torque for delta connected stator is given and it is 140% of the above

    value (this is in fact the starting torque for delta connected machine i.e. the DOL torque)i.e. 77.3434.1 flDOL TT -Nm. Bearing in mind that the torque is proportional to phase

    voltage square the following torque relationship applies:-

    59.1143

    77.343

    3

    1)

    3/( 2 start

    LL

    LL

    DOL

    start TV

    V

    T

    T-Nm.

    If started -connected then LLphase VV and the DOL line current would be :-

    57.1456547.0

    34603

    Z

    VI LLline -A.

    Finally, the machine pole-number can be determined using the fact that the rated speed isvery close to synchronous i.e. about 0.92-0.97 sn . The synchronous speed in rpm can be

    expressed aspolespolespoles

    fn

    plys

    720060120120 sup

    and the number of poles is therefore 4

    as 1800sn -rpm under this condition (this is the first synchronous speed value above the

    rated speed of the machine = 1750-rpm).

    Example 3 : Series-resistance starting

    A 3-phase, Y-connected, 230-V, 78-A, induction motor has a locked-rotor impedance0.0978 + j0.2549 /phase. The motor is to be started using series resistors in each line. (a)

    Draw starter-motor connections for this starting method and explain its mechanism; (b)

    Determine the resistance of the resistors required to limit the starting current to 3 times

    rated current; (c) Calculate the stator phase voltage at locked rotor; (d) If the locked-rotor

    torque at rated voltage and frequency is 150% rated value, what is the starting torque (in pu

    taking the rated torque as a base) at reduced voltage?

    Solution:

    (a)Series-impedance starters start the motor at reduced voltage by connecting a resistance(in this case) or reactance bank in series with the motor windings (see figures below) tolimit the inrush current during start-up. The impedance seen by the power system then

    is that of the reactance plus that of the motor. The running contacts (R) are open when

    starting (S contacts are closed) and once the motor has run up and its speed has

    stabilised (Fig.11), the resistance (reactance) bank is shorted out by closing R contacts

    (and opening S contacts), and the motor becomes DOL connected. This change-over is

    normally controlled by an adjustable timer within the starter. The ohmic value of the

    resistor or reactor is generally selected to provide approximately 70-80% rated voltage

    at the motors terminals when starting. The series impedance starter is of simple design

    and allows smooth acceleration.

  • 8/3/2019 IM Starting&Control

    9/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 9

    Fig. 9: Series resistorstarting Fig. 10: Series reactorstarting

    Fig.11: Typical characteristics for series impedance induction motor starting

    (b)The total impedance as seen from the line terminals is obviously (0.0978 + extR ) +j0.2549 /phase. Due to the system Y-connection, the voltage from line to neutral is

    79.1323/230 -V, and the locked-rotor current is to be limited to

    2347833 ratedstart II -A. The 3-phase stator and series-connected resistors

    present a balanced circuit and the current magnitudes in the respective branches are

    consequently equal. Applying Ohms law to one phase:-

    2342549.0)0978.0(

    79.132

    22

    exttotal

    LNstart

    RZ

    VI -A

    Solving the above quadratic for extR one gets 4093.0extR -.

    (c)The voltage applied to the machine (across terminals T1-T3 in the above figures) isactually the voltage drop on the motor impedance Z:-

    88.63234273.0 startm IZV -V.

  • 8/3/2019 IM Starting&Control

    10/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 10

    (d)The starting torque at reduced stator voltage of 63.88-V can be calculated from thefollowing torque ratio :-

    flstart

    start

    fl

    start

    voltsfullTT

    T

    T

    T

    T

    347.0

    88.63

    79.1325.1

    2

    2

    The starting torque is therefore 34.7% rated value or 0.347-pu.

    Example 4 : Series-reactance starting

    A certain 208-V, 24-A, 60-Hz, Y-connected induction motor has a locked-rotor current of

    139.5-A at full voltage. The power factor under this condition is 0.342 lagging. The motor

    is to be started using the series-impedance method with pure inductors (of negligible

    resistance) in each line. Calculate the inductance and voltage rating of each series-

    connected inductor required so that the starting current is 200% rated.

    Solution:

    Following on from the previous example and applying Ohms law to one phase of Y-

    connected stator windings one can determine the locked-rotor impedance of the machine :-

    -861.035.139

    208

    lr

    LNm

    I

    VZ

    Since the power factor is 0.342 lagging, the impedance phase angle is therefore70342.0cos 1 .

    The total impedance of the system is the external reactance plus the motor impedance i.e.

    )809.0(294.0)70sin342.0(861.0 extext XjXjj . The starting current needs

    to be limited not to exceed 482 ratedI -A. Therefore :-

    A-48)809.0(294.0

    3/208

    22

    exttotal

    LNstart

    XZ

    VI

    From the above equation, one can solve for -675.12 extext LfX . The added

    inductance is thus 44.4extL -mH as f = 60-Hz.

    The voltage drop across each of the inductors represents their voltage rating. This is simply

    4.80675.148 extstart XI -V.

    3 Starting of Wound-Rotor Induction Motors

    The DOL starting current of a wound-rotor motor may be reduced by connecting an

    external 3-phase variable resistance in series with the rotor windings, via the slip rings. The

    value of external resistances is gradually reduced as the rotor speed increases. An interlock

    is usually employed to prevent main switch closure unless the starting resistances are attheir maximum values. The circuit arrangement and torque-slip characteristics of a wound-

    rotor type induction motor with a four-point starter are shown in Fig.12.

  • 8/3/2019 IM Starting&Control

    11/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 11

    When the required number of resistance steps is small, the starting resistors may be

    mounted on the rotor shaft and cut out using a centrifugal switch. This avoids the

    requirement of slip rings and external switchgear. However, this device is complicated if

    frequent starting is required, due to heat dissipation requirements, or if more than two

    resistance steps are required. A motor fitted with a centrifugal switch will automatically

    reset the starting resistors if stalled.

    Fig.12: Starting of a wound-rotor induction motor with a four-point starter

    As a remainder and for convenience of the following analysis, it would be useful to

    reproduce here the steady-state equivalent circuit of an induction machine (Fig.13), the

    corresponding equations as well as a typical torque-slip characteristic similar to those in

    Fig.12.

    Is Rs jXs jXr Ir

    Vn Im jXm Rr /s

    Fig.13: Steady-state per-phase equivalent circuit of an induction machine for purely

    sinusoidal supply voltage (iron loss resistance not shown)

    All the rotor parameters in Fig.13 are referred to the stator winding, by means of thetransformation ratio. Symbols in bold denote phasors. The variable resistor in the rotor

    circuit represents both rotor copper loss and power converted into mechanical. Recall that

    the stator winding of the machine can be connected in either star or delta; the equivalent

    circuit is valid for phase rather than line values, regardless of the winding connection. Thus

    Vn stands for the rated phase to neutral voltage of the stator. All the reactances are given at

    fixed, rated supply frequency.

    The general torque-slip characteristic for a 2P-pole machine shown in Fig.14 follows from

    power flow considerations in Fig.13, in the form:-

    222

    22

    2

    2

    3

    2

    3)(

    XsRR

    sRV

    f

    P

    XXsRR

    sRV

    f

    PsT

    rs

    rn

    rsrs

    rne

    (1)

  • 8/3/2019 IM Starting&Control

    12/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 12

    Temaximum (pull-out) torque

    Ten

    Test

    operating region

    slip

    1 sm sn 0 s

    0 ns speed

    Fig.14: Torque-speed curve of an induction machine for rated supply conditions

    The operating region is restricted to slips up to typically 10%, indicating that the speed of

    rotation changes with load but remains within rather narrow boundaries from no load up to

    rated load. The maximum (pull-out) torque, rated torque and starting torque, as well as the

    corresponding slips (indicated in Fig.14) can be calculated from the following expressions:

    222

    22

    2

    22

    2

    22

    2

    22

    2

    3)(

    2

    3)1(

    1

    4

    3

    2

    3

    )(

    XsRR

    sRV

    f

    PssTT

    XRR

    RV

    f

    PsTT

    XRRVf

    P

    XsRR

    sR

    Vf

    P

    ssTT

    XR

    Rs

    nrs

    nrnneen

    rs

    rneest

    ssn

    mrs

    mr

    nmeem

    s

    rm

    (2)

    Referring to the first two expressions for maximum electromagnetic torque )( emT and the

    corresponding slip (m

    s ) it is apparent that the rotor resistance (r

    R ) influencesm

    s , but not

    the magnitude of the maximum torque. It is obviously possible to obtain maximum torque

    at starting by adding the appropriate resistance in the rotor circuit (in series with the rotor

    windings) so that 1ms (see Fig. 15). Therefore the value of external resistance per phase

    required to achieve maximum torque at start-up can be determined using the first

    expression above as follows:-

    rsext

    s

    extrm RXRR

    XR

    RRs

    22

    221 (3)

    This unique property of a wound rotor (slip ring) induction machine to achieve maximum

    starting torque with relatively low supply current is its principal advantage over a cagecounterpart. It also serves as a basis for speed control of this machine (Fig.15) as we shall

    see in the following sections.

  • 8/3/2019 IM Starting&Control

    13/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 13

    Stator Te

    Radd = 0

    IM

    Load torque

    Rotor

    Increasing Radd

    Radd

    1 s1 s2 sn 0 slip

    Fig.15: Speed control of a WRIM by addition of resistance in the rotor windingbasic

    principle and torque-slip curves.

    Example 5 : External resistance control for maximum torque at start-up of a WRIM

    A 380-V, 50-Hz, 4-pole, Y-connected slip ring induction machine is fully loaded at 5-Nm.

    The stator and rotor resistance are 10- and 6.3-, respectively, while the leakage

    reactances are 12- each. A magnetising reactance can be neglected.

    (a) Determine the slip for rated operating conditions;

    (b) Calculate added resistance that will enable starting of the motor with the maximum

    starting torque.

    Solution:

    (a) Calculation of rated slip:

    Nm84.12

    2

    3

    Nm92.61

    1

    2

    3

    %2.24242.0

    Further,

    rpm5.14411rpm1500/60

    %9.3039.0

    07.395.1039676

    -:getsone,expressiontorqueratedinesknown valutheallngSubstituti

    V2203380connectionstartoduethatNote

    Nm52

    3

    constant=Nm5

    22

    2

    22

    2

    22

    2

    22

    2

    rsmrs

    mrnem

    rsrs

    rnest

    rss

    rm

    nnns

    n

    nn

    n

    rsnrs

    nrnen

    enL

    XXsRR

    sRV

    f

    PT

    XXRR

    RV

    f

    PT

    XXR

    Rs

    nsnPfn

    s

    ss

    V

    XXsRR

    sRV

    f

    PT

    TT

  • 8/3/2019 IM Starting&Control

    14/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 14

    (b) If the machine is to start with starting torque equal to maximum torque, then an

    additional rotor resistance per phase required can be calculated as follows:-

    7.191

    1

    22

    22 rsadd

    s

    addr

    mestem

    RXRRXR

    RR

    sTT

    4 Power Electronic Control of Induction Machines

    4.1 Introduction

    Three-phase induction motors are the most frequently utilised electric machines in industry

    (more than 70%). They are characterised with low cost, high reliability, high efficiency,

    simple construction and, in the case of squirrel-cage induction motors, with virtuallymaintenance-free operation. If operated with the stator three-phase voltage supply of fixed

    frequency and magnitude, induction motors will run at a speed that very slightly depends

    on loading.

    In contrast to DC machines, where the choice of speed control methods and associated

    power electronic converters that are nowadays in use is rather limited, there exists a variety

    of both speed control techniques and appropriate power electronic converters that are used

    in conjunction with 3-phase induction motor drives. A 3-phase induction machine requires

    3-phase AC supply at the stator side. In a squirrel-cage type of induction machines this is

    simultaneously the only accessible winding. However, in slip-ring induction machines

    there is more degrees of control freedom as the three-phase rotor winding may be

    approached as well. Thus the speed of an induction machine may be controlled via the

    stator voltage variations for both types of induction machines; additionally, the speed may

    be controlled in slip-ring machines from the rotor side as well. Squirrel-cage induction

    machines are by far the most frequently used. It is for this reason that the following

    discussion will be predominantly devoted to speed control methods associated with the

    alteration of the stator supply voltage. Only one method, specifically aimed at slip ring

    machines, will be looked at.

    If a 2P-pole induction machine is supplied with a voltage of frequencyfthen the so-called

    synchronous speed of the stator revolving field can be expressed in rpm as:ns = 60f / P (4)

    From this expression it follows that the synchronous speed can be altered by simply

    changing the number of pole pairs - P. Assuming that the load torque is constant, ifP is

    doubled during operation of the machine, the synchronous speed will be halved, leading to

    operation at approximately one half of the rated speed (as slip is small under normal

    operating conditions). This method of speed control is used in low performance drives that

    typically require operation at two distinctly different operating speed (say, a washing

    machine; spinning is done at high speed, while normal washing cycle takes place at low

    speed) but where control accuracy is not an imperative.

    Speed control by pole pair changing requires a specially wounded stator and is usually

    realised by mechanically reconnecting the stator winding from one pole pair number to

    another. The linear portions of typical torque-speed characteristics for a change-over from

  • 8/3/2019 IM Starting&Control

    15/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 15

    2-pole to 4-pole stator are shown in Fig.16. Power electronics converters are obviously not

    involved in this speed control method, and its applicability is restricted to the cases where

    two discrete speed values, rather than continuous speed variation, are needed. Therefore

    speed control by pole pair changing will not be considered further on.

    The general torque expression for an induction machine (1), suggests that, for a giventorque, the speed (slip) of an induction machine can be adjusted by changing the stator

    applied voltage (V) and/or frequency (f). The two consequent methods of speed control,

    universally applicable to all the 3-phase induction machines, that will be elaborated in

    more detail are:

    (1)the speed control by stator voltage variation and(2)speed control by simultaneous stator voltage and frequency variation.The former, although relatively simple, has restricted applicability for the reasons that will

    be explained in the following; the latter is the most widely used method of speed control of

    induction machines. Finally, a method valid for slip-ring machines only based on theinsertion of a series resistance in the rotor circuit, will be discussed as well.

    Te

    load torque

    A B

    1500 3000 speed (rpm)

    Fig. 16: Speed control by changing pole pair number: drive operates either at point A or B.

    4.2 Speed Control by Stator Voltage Variation

    The equation (1) shows that electromagnetic torque developed by an induction machine is

    proportional to the square of the applied rms stator phase voltage (V). Thus, for a given

    load torque, a reduction of voltage will lead to the operation with an increased slip, i.e.,

    with a decreased speed as shown in Fig. 17. As the supply voltage is not allowed to exceed

    its rated value, this method of speed control can be utilised only for reducing the speed

    below rated. Note that, according to (3), the pull-out slip is not a function of the applied

    voltage. Hence the motor develops maximum torque at constant slip (speed), determined

    with (5), regardless of the applied voltage. However, as both maximum (pull-out) and

    starting torques are functions of the voltage squared, the reduction in voltage results in the

    reduction in starting torque which means that the motor will be able to start only light loads

    at low speeds; also a decrease of maximum torque implies that overloading capability of

    the motor is compromised. This is one of the major drawbacks of this speed control

    method.

    Another limitation of the method is that the speed drops with reducing the voltage

    incurring additional copper losses in the rotor winding due to increased slip as previously

    mentioned. Regardless of these two serious shortcomings, this speed control technique is

    widely used in two distinct cases. When the load torque is proportional to the speedsquared (pumps, ventilators, compressors, etc.) then even a small reduction in speed means

    significant reduction in the output power, which is proportional to the cube of the speed.

  • 8/3/2019 IM Starting&Control

    16/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 16

    For a number of applications having load torque of this type it is sufficient to vary the

    speed in this narrow region. The second application is in drives that run for prolonged

    periods of time with very light loads. In such a situation it is advantageous to reduce the

    voltage for light load operation as this improves the efficiency of the drive. In other words,

    considerable saving in electricity consumption may be achieved in this way.

    Te

    rated voltage

    reducing voltage

    operating region

    slip

    1 sm 0 s

    Fig.17: Torque-slip characteristics of an induction machine with speed control by stator

    voltage variation.

    Example 6: Speed control by stator voltage variation

    A 3-phase squirrel-cage induction motor drives a full load at rated slip of 3%. A stator and

    rotor resistance (referred to stator) are both equal to 0.015- and a total leakage reactance

    is X = 0.09-. (a) Calculate the necessary reduction in the stator supply voltage if the

    induction motor is to drive the same load but with a 15% slip; (b) Compare the rotor losses

    for the two operating points and comment on the results obtained.

    Solution:

    (a)Pull-out slip of the motor is:%4.16164.009.0015.0015.0 22

    22

    XR

    Rs

    s

    rm

    The reduction of the voltage to allow the operation with 15% slip at unchanged load torquecan be calculated as follows.

    37.6%.isreductionvoltageNecessary624.0

    39.009.003.0/015.0015.0

    09.015.0/015.0015.0

    03.0

    15.0

    2

    3

    2

    3

    1

    15.0and03.0:pointsoperating

    1

    22

    22

    22

    2211

    21

    22

    2

    221

    121

    22

    2

    221

    121

    1

    1

    n

    nrs

    rs

    nn

    nrs

    nrn

    rs

    r

    nrs

    nrn

    rs

    r

    en

    e

    n

    VV

    XsRR

    XsRR

    s

    s

    V

    V

    XsRR

    sRV

    XsRR

    sRV

    XsRR

    sRV

    f

    P

    XsRR

    sRV

    f

    P

    T

    T

    ss

  • 8/3/2019 IM Starting&Control

    17/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 17

    This situation is illustrated in the accompanying figure.

    Te

    rated voltage

    TL = Ten

    62.4% of

    rated voltage

    0.16 0.03 slip

    0.15

    (b)Let us now examine an increase in rotor losses that takes place with this speed controlmethod. Taking the power transferred from the stator to the rotor (electromagnetic

    power) to be Psr, for these two operating conditions one has

    nnsrcur

    srnnnsr

    nn

    nensenen

    nsrnncurnnn

    nsrnsrnnn

    n

    PPsPP

    PPPs

    PP

    Ps

    sTsTTP

    s

    PPsPPs

    PPPsP

    s

    1545.003.115.0:losscopper

    03.185.0/876.01

    :powerneticelectromag

    876.01

    11:powermechanical

    :torque(rated)sameat the15.0slipnewfor

    031.0:lossescopper;03.11

    1

    :03.0slipratedfor

    This consideration shows that power transferred from stator to rotor is the same for the two

    cases. Hence reduction in output power of 12.4% reflects itself directly on an increase in

    rotor copper loss from 3.1% to more than 15% of the rated power. As this loss takes place

    in the motor, it will essentially cause overheating. Needless to say, efficiency is sharply

    reduced. Starting problems with reduced voltage and this increase in losses are the two

    main reasons why this speed control method is not used with constant load torques. The

    situation is much improved in both respects when the load torque is proportional to the

    speed square as is the case in pump-like applications. Speed control by stator voltage

    variation is therefore applied in conjunction with this type of load in practice.

    Speed control by stator voltage variation is realised by using an AC-AC voltage controller

    in each stator phase of the machine as shown in Fig.18. The firing delay angle of the

    thyristors may be controlled to provide soft-starting as well in order to alleviate the

    starting problems of cage-type motors as will be discussed earlier. The same voltage

    controller structure is also a basic configuration used in power systems for reactive power

    compensation.

    It should be noted that although the principle of operation of an AC-AC controller is very

    simple (to be reviewed in the following section), an analysis of the system in Fig.18 is

    extremely tedious even for steady-state operation. This is due to the inductive nature of themachine, which makes the instant of cessation of the current flow through each of the

    thyristors essentially unknown. As the voltage exists as long as there is current flow, then it

  • 8/3/2019 IM Starting&Control

    18/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 18

    is actually very difficult to evaluate the actual voltage applied across the machine under

    given operating conditions. Note that the voltage value calculated in the previous example

    for reduced speed operation is the required rms value of the fundamental harmonic of the

    output phase to neutral voltage of the AC-AC voltage controller.

    IM

    R

    Y

    B

    T1

    T2

    T3

    Fig.18: Stator voltage variation of an IM using an AC-AC voltage controller

    4.3 Speed Control of Slip Ring Induction Machines

    From a set of equations (2) it follows that the pull-out slip is proportional to the added

    resistance. On the other hand, the corresponding maximum torque is not influenced at all

    by addition of resistance, indicating that overloading capability of the machine is

    unaffected. Compared with the stator voltage variation method, an addition of rotor

    resistance is to be preferred, for the following reasons: (a) any operating speed between

    zero and rated can be obtained (with the stator voltage variation speed control region is

    confined to speeds higher than pull-out speed); (b) maximum torque is not affected (with

    stator voltage variation it reduces proportionally to the stator voltage reduction squared);

    (c) additional copper loss is now developed in the added resistance, which is external to the

    machine and therefore the problem of overheating does not take place. Note however, that

    the problem of low efficiency still remains to be present: as speed is reduced, larger and

    larger portions of the total input power are dissipated in the additional resistors. A principle

    of this speed control method and resulting torque speed curves are shown in Fig.15.

    Example 7. For a wound rotor induction motor from Example 5, calculate an added

    resistance that is needed to reduce its speed from the rated value to 1000 rpm.

    Solution:

    For operation at 1000-rpm with the same load torque the following resistance is needed:

    4.483.67.547.5402168.19.0016.0equationin torqueesknown valutheallngSubstituti.Let

    2

    35

    3333.01500/)10001500(

    2

    2

    2

    1

    121

    11

    add

    addr

    addrs

    addrnene

    s

    s

    RRRRRRR

    Xs

    RRR

    sRRV

    f

    PTT

    n

    nns

  • 8/3/2019 IM Starting&Control

    19/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 19

    Example 8. A 3-phase 220-kW, 16-pole, 60-Hz slip ring induction machine drives a pump

    at rated slip of 2.5% and full load torque. The pumps torque is proportional to the speed

    squared. A rotor phase resistance is 0.0175-. Determine the value of an added resistance

    that needs to be inserted in series with the rotor phases to achieve the speed of rotation of

    300-rpm. Assume a linear torque-speed characteristic around the rated operating point.

    Solution:

    Motor torque in the operating region (i.e., for slips between rated and zero) can be

    approximated with a straight line i.e. Te = ks. Calculations in this example will be therefore

    based on this expression.

    48.0)101165.0/333.0(0175.0Thus

    resistanceaddedwithcurveat)(

    2

    35.2230

    sticcharacterinatural2

    35.2230

    Hencerpm.300istorquewith thisspeedrequiredHowever,rpm75.444

    01165.04785/5.2230025.047855.2230

    slipinresultwouldNm2230.5ofewith torquoperationsticcharacterinaturalAt

    333.0450/)300450(/

    Nm5.2230)30/300(26.2

    rpm300atstate-steadynewIn

    rad/Nms2.26=Nm4785)(

    Nm4785)439/(30220000

    rpm439450)025.01(1rpm4508/6060/60

    2

    1

    12

    22

    1

    121

    22

    2

    222

    2222

    11

    2211

    222

    rraddaddrr

    addrs

    addrne

    rs

    rne

    en

    ennene

    ss

    L

    nnLL

    nnen

    snns

    RRs

    sR

    s

    RR

    s

    R

    Xs

    RRR

    sRRV

    f

    PT

    Xs

    RR

    sRVf

    PT

    n

    xT

    TssksTksT

    nnns

    xKT

    KKTKT

    xPT

    nsnxPfn

    Torque-slip curves for this example are illustrated below.

    Te TL

    0.48

    4785 Nm

    2230.5 Nm

    0 300 444.75 n(rpm)

    439

  • 8/3/2019 IM Starting&Control

    20/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 20

    If the speed of a slip ring induction motor is to be continuously varied, it is necessary to

    provide a method of continuous additional resistance variation. This is possible if power

    electronic converters are used as shown in Fig. 19. A 3-phase bridge diode rectifier is

    connected to the rotor winding via slip rings. The output of the rectifier is connected to a

    chopper, whose circuit contains a resistor R. When the switch S (normally a transistor) is

    closed, the resistorR is short circuited; else i.e. with the switch S open, R is connected tothe rectifier output. The purpose of a large inductor DCL in the circuit is to provide almost

    level DC load current, regardless of the state of the switch S.

    Three-phase diode

    bridge rectifier LDC

    stator rotor

    IM S R

    Fig. 19: Continuous speed control of a slip ring induction machine by addition of an

    electronically controlled variable resistance in the rotor circuit.

    What now has to be considered is the correlation between the resistance R of Fig. 19 and

    per phase added resistance Radd in the rotor circuit (Fig.15) used previously in all the

    calculations. If the switch S is open all the time (duty cycle equal to zero), the resistance

    seen by the rectifier will be R. If the switch is permanently closed (unity duty cycle) then

    the equivalent resistance as seen from the rectifier terminals is zero. Hence the resistance

    presented to the rectifier by the chopper is:

    TtRR one where1 (5)

    The input rectifier current (i.e., phase rotor current) is, due to large inductance at the DC

    side, of quasi-square waveform with 120 degrees of non-zero value in each half-period. For

    a constant DC current, of value IDC, the total rms of the rotor current (i.e., rectifier input

    current) is then:

    I I d I r DC DC 1

    22

    2

    3

    2

    0

    2 3

    /

    (6)

    The required equivalent value of the added resistance per phase, Radd, is determined from

    the power balance at the input/output of the rectifier. Assuming that the rectifier, chopper

    and the DC side inductor are ideal (i.e. lossless), real power at the input of the rectifier

    must equal that delivered to the resistance of (5). Hence, using (5) and (6), one gets the

    following relationship:

    RRIRRIRIIRP addraddrDCDCeDC 15.03)1(2

    31 2

    222(7)

    Note that the value of added resistance per rotor phase in (7) is the actual value and it has

    to be referred to the stator side by means of transformation ratio in order to enable its use in

    torque calculations.

  • 8/3/2019 IM Starting&Control

    21/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 21

    Example 9: Chopper speed control of a WRIM

    For the slip ring induction machine analysed in Example 8, determine the chopper duty

    cycle that will enable operation with the calculated additional resistance per phase if the

    chopper output resistance isR = 2-.

    Solution :

    Required value of per phase added resistance was calculated as 0.48 . From (7) it follows:

    52.048.01125.048.015.0 xxRRadd

    Example 10: A 30-kW, 1170-rpm, 60-Hz slip ring induction motor has the open-circuit

    rotor voltage of 400-V. A chopper with a resistive load of 5- and switching frequency of

    200-Hz is used for continuous variations of the rotor external resistance. Calculate the

    chopper on-time required for the motor to develop a 200-Nm torque at 900-rpm.

    Solution:

    For a 60-Hz supply frequency and 1170-rpm rated speed the synchronous speed must be

    the first possible value above 1170-rpm i.e. sn 1200-rpm this corresponding to a 6-pole

    machine. The slip at 900-rpm is therefore: 25.01200/9001 s .

    The rotor voltage between the any two slip-rings for the above slip value and the locked-

    rotor (open-circuit) voltage of 400-V is: V-10040025.0 ocr EsE .

    The DC voltage of the diode bridge rectifier: V-13510035.123

    rdc EV .

    The power delivered to the rotor from the stator at 200-Nm: kW-13.2560

    2 sem

    nTP

    .

    The power dissipated as heat in the rotor circuit: W-62822513025.0 emloss PsP .

    The chopper input resistance determined from power balance:

    .-9.26282

    13522

    dc

    dce

    P

    VR

    The chopper duty-cycle calculated using (5): 42.05/9.21/1 RRfT eswon .The chopper on-time is therefore: ms-1.2200/42.0 onT .

    4.4 Soft-starting of induction motors

    Soft starters (also called solid state starters) are used for gentle starting and stopping of 3-

    phase induction motors. Pumps, centrifuges, compressors, escalators, belt conveyors, mills,

    fans, stone crushers and saws are typical applications. If a motor is not adequately protected

    the sudden change in rotation torque and speed, which occurs on starting and stopping will

    jolt the equipment linked to it. Over the long-term this can lead to increased mechanical

    wear of gearboxes, clutches, transmission and conveyor systems. Abrupt starting and

  • 8/3/2019 IM Starting&Control

    22/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 22

    stopping can also damage goods being handled by mechanical equipment. For instance, the

    filling and distribution of glass bottles and containers loaded onto a conveyor holds the

    potential for a minor disaster. One sudden jerk during starting and stopping and the whole

    process line could be turned into a mass of broken glass and dripping liquid or sticky

    product. With pumps soft starters eliminate pressure shocks in pipes and valves when the

    pump starts or stops. This poses a particular safety hazard when the transfer of volatileand/or inflammable liquids is involved.

    In all the applications mentioned previously, the back-to-back converter configuration of

    Fig.18 with associated electronics (Fig. 20) can be used to chop the sine-wave system

    power so that only a portion of the supply voltage is applied to the motor during starting

    and/or stopping. This kind of voltage control ensures smooth acceleration and deceleration

    thereby eliminating the disruptive effects of sudden starts/stops. The gradual supply of

    current to a motor also eliminates unwanted tripping, erratic current supply and motor

    overheating. The logic circuits (Fig.20) can be programmed to respond to any of several

    sensors to control the voltage: internal time ramp; current sensor feedback, or tachometerfeedback. In addition, most such starters also have provisions for reducing the voltage

    when the loading on the motor is low, thus minimizing the no load losses of the motor and

    improving its efficiency (issues related to this will be addressed in the following).

    Fig.20: Design of an electronically controlled soft starter for induction motors

    The starting controls are set so that, initially, the voltage increases rapidly until the motor

    just begins to turn, after which the voltage rises linearly with time until full voltage is

    reached (Fig.21a). Some of these ramp-up schedules incorporate a short pulse of full (or

    nearly full) voltage to overcome the static friction of machinery that has not operated for

    some time or that is covered with frost (Fig.21b). In other schedules (Fig.21e) the starting

    current can be limited automatically to, say, 4 times the rated current.

    During stalling, when power is shut off, the motor may coast to a stop too quickly. In such

    cases the slow ramp-down feature of the electronic starter is a significant advantage

    (Fig.21d). In this phase the motor terminal voltage is reduced gradually until the motor

    comes to rest. The starter can be appropriately programmed to generate the desired ramp

    characteristics (Fig.21d) that are best suited to a particular load.

  • 8/3/2019 IM Starting&Control

    23/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 23

    Fig.21: Typical soft starting/stopping characteristics of cage induction motors

    Usually soft starters are only active during the starting and stopping procedure; the rest of

    the time the motor is supplied directly from the mains. For improved steady-state

    performance it is useful to be able to keep control of the motor and the load at all times so

    most soft starters are designed to continuously control or monitor the running of the motor

    instead of controlling it only during starting and stopping. The explanation for this can befound in the fact that once a start has been completed the motor operating efficiency

    becomes of interest. When working at or near full load, a typical 3-phase induction motor

  • 8/3/2019 IM Starting&Control

    24/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 24

    is relatively efficient, readily achieving efficiencies of 85% to 95%. However, motor

    efficiency falls dramatically when the load falls to less than 50% of rated output. In fact, a

    very few motors actually experience consistent fully rated operation, the vast majority

    being operated at much lower loads due to either over-sizing (a very frequent situation), or

    natural load variations. At light loads and mains voltages, induction motors always have

    excess magnetic flux, and suffer efficiency loss and power factor degradation as a result.By detecting the load at any instant, and adjusting the motor terminal voltage accordingly,

    it is possible to save some of the excitation energy and reduce core losses, thus improving

    the motor efficiency at light loads (as shown earlier in Section 4.2). For this reason, many

    soft-starters are often microprocessor controlled which brings them a number of important

    advantages. Firstly, all the calculations necessary to find the most optimal firing angle of

    the thyristors for any load condition is made by the micro-computer. Secondly, the start

    always synchronises with the supply voltage and a special structure of turn-on pulses

    virtually eliminates the inrush currents normally associated with motor start-up. Lastly,

    there is the absolutely step-less starting process, found only with series impedance electro-

    mechanical starters - but without the wasted energy, with improved reliability, salientcontact-less operation and with the opportunity to control the maximum current allowed to

    flow during the starting process. Other features such as soft stopping can be also included

    to give considerable control over all modes of induction motor operation.

    4.5 Speed Control by Simultaneous Stator Voltage and Frequency Variation

    All the speed control methods elaborated so far are characterised by relatively poor

    efficiency. Additionally, stator voltage variation method leads to a decrease in maximum

    torque when stator voltage is reduced. This reduction in maximum torque is a consequence

    of the field weakening in the machine i.e. the fact that, when the supply voltage is reducedwhile the applied frequency is kept constant, the machine flux reduces as well. From the

    equivalent circuit of Fig.13 it follows that the induced emf is:

    fkIjXRVIjXE sssmm (8)

    i.e. it is determined as the product of the flux and frequency. Clearly, in order to maintain

    flux constant, it is necessary to simultaneously alter both f and E. A wide speed control

    range with an induction machine can be realised only if the stator frequency f is made

    variable and reasonably high. Additionally, when f is varied, it follows from (8) that it is

    necessary to simultaneously vary the rms value of the supply voltage V. Ideally, the changeofVandfshould be done in such a way that Eis held constant. In this case both the flux

    and maximum torque of the machine will be kept constant at all operating frequencies. The

    control law that allows constant flux operation at all frequencies can be therefore expressed

    as follows:

    E/f = En /fn (9)

    A set of resulting torque-speed curves is shown in Fig. 22. The machine operating region

    above the rated speed, which is achieved by increasing frequency above rated at full

    voltage, is called the field-weakening region as the air-gap flux is then reduced.

  • 8/3/2019 IM Starting&Control

    25/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 25

    In reality however it is not possible to control the machine by using the previously stated

    law as the internal emf cannot be measured. Instead, control is done in such a way that the

    supply voltage to frequency ratio is held constant, i.e.

    V/f = Vn /fn (10)

    The consequence of this is that at low operating frequencies the stator resistance voltage

    drop (RI) becomes dominant, this significantly reducing the flux and the maximum torque

    of the machine (Fig. 22). A compromise is found usually by applying a modified voltage

    control law that contains the so-called voltage boost at low frequencies, i.e.

    V = (Vn /fn ) f + V0 (11)

    The two possible control laws are illustrated in Fig. 23.

    20 Hz 40 Hz 60 Hz 80 Hz 60 Hz, two-pole machine

    Te

    speed

    [rpm]

    E/f = En /fn

    1200 2400 3600 4800

    Base speed region Field-weakening region

    Te

    Rated voltage, rated frequency

    speed

    V/f = Vn /fn

    Fig. 22: Torque-speed characteristics of an induction machine for two control laws:

    E/f = En /fn (top) and V/f = Vn /fn (bottom)

  • 8/3/2019 IM Starting&Control

    26/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 26

    V Vn V Vn

    V0

    0 fn f 0 fn f

    Fig. 23: Voltage vs frequency relationship for V/f = Vn /fn and V = (Vn /fn )f + V0 control

    Let the ratio of operating frequency to rated frequency be a =f/fn . The original equivalent

    circuit of Fig.13 at operating frequency f now becomes as shown in Fig. 24. All the

    reactances are given for the rated frequency; hence at any other frequency they become aX.The input stator voltage is assumed to be determined using either (10) or (11).

    Is Rs jaXs jaXr Ir

    V = a Vn Im jaXm Rr /s

    Fig. 24: Steady-state equivalent circuit of an induction machine at an arbitrary frequency

    Note that slip s in the above figure is defined as per-unit (pu) value. Ifns = 60fn /P is the

    synchronous speed of a 2P-pole machine at rated frequency, then for operation at any other

    frequency

    s = (ans - n)/ans (12)

    where n denotes operating speed at this other frequency. Calculations related to V/f methodof speed control are best illustrated by means of examples.

    Example 11: V/f control of Induction machines

    A 3-phase, 60-Hz, 1728-rpm induction motor has the following parameters: stator

    resistance = rotor resistance = 0.024-; stator leakage reactance = locked rotor leakage

    reactance = 0.12-. The motor is to be controlled according to the law V/f = const.

    For an operating frequency of 12-Hz calculate:

    a) The maximum torque as a ratio of its value at the rated frequency;

    b) The starting torque and current in terms of their values at the rated frequency.c) If this motor is used to drive a load of constant torque equal to rated, calculate the motor

    speed for the supply frequency of 30-Hz.

  • 8/3/2019 IM Starting&Control

    27/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 27

    Solution:

    a) The purpose of this part of the example is to show that with V/f = constant law the air-

    gap flux in the motor is not constant; hence the maximum torque at 12-Hz will be

    consequently reduced in motoring with respect to the value at rated frequency.

    222

    2

    222

    2

    222

    22

    22

    2

    //

    1

    4

    3

    ]//[

    1

    4

    31

    4

    3)(

    1

    4

    3)(

    2.060/12/

    XaRaR

    Vf

    P

    XaRaRa

    aVf

    P

    XaRR

    Vaaf

    PafT

    XRR

    Vf

    PfT

    ffa

    ss

    nn

    ss

    nn

    ss

    nn

    nem

    ss

    nn

    nem

    n

    68.024.0)2.0/024.0(2.0/024.0

    24.0024.0024.0

    )(

    )2.0(

    )(

    )(

    22

    22

    22

    22

    nem

    nem

    ss

    ss

    nem

    nem

    ffT

    ffT

    XaRaR

    XRR

    ffT

    affT

    b) This part of the example demonstrates some additional benefits of the V/f speed control.

    As will be shown, starting at low frequency gives an increased starting torque compared to

    starting at rated frequency. Even better, this higher starting torque is achieved with reduced

    starting current.

    72.0

    24.02.0048.0

    24.0048.02.0

    )(

    )(

    )(

    )(

    6.2

    24.0048.0

    024.024.02.0048.0

    024.02.0

    )(

    )(

    2

    3

    2

    3)(

    2

    3)(

    222

    22

    222

    22

    )(

    )(

    222)(

    22)(

    22

    222

    22

    222

    222

    2

    222

    22

    22

    2

    xXaRR

    XRRa

    ffI

    affI

    XaRR

    aVaffI

    XRR

    VffI

    x

    x

    XRR

    R

    XaRR

    aR

    ffT

    affT

    XaRR

    aRV

    f

    P

    XaRR

    RVa

    af

    PaffT

    XRR

    RV

    f

    PffT

    rs

    rs

    nsts

    nsts

    rs

    nnsts

    rs

    nnsts

    rs

    r

    rs

    r

    nest

    nest

    rs

    rn

    nrs

    rn

    nnest

    rs

    rn

    nnest

    Thus V/f control undoubtedly provides high starting torque with reduced starting current.

  • 8/3/2019 IM Starting&Control

    28/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 28

    c) Since the motor rated speed at 60-Hz is 1728-rpm, the motor has 4 poles and the

    corresponding synchronous speed is 6060/2 = 1800-rpm.

    The rated slip is therefore: 11728/1800 = 0.04 i.e. 4%.

    givesequationstwotheseofsideshandrighttheEquating

    2

    3)(

    2

    3)(

    5.060/30/

    222

    2

    22

    2

    XasRR

    saRV

    f

    PaffT

    XsRR

    sRV

    f

    PffT

    ffa

    rs

    rn

    nnen

    nrs

    nrn

    nnen

    n

    rpm-8201rpm-900/60Hz30

    %9.8089.00198.004.26 2

    22222

    ssn

    rs

    r

    nrs

    nr

    nsnPfnaff

    sss

    XasRR

    saR

    XsRR

    sR

    Note that at rated frequency synchronous speed and operating speed are 1800-rpm and

    1728-rpm respectively; the difference of the two is 72-rpm. At 30-Hz synchronous speed

    and operating speed are 900-rpm and 820-rpm respectively; the difference between the two

    is now 80-rpm. Indeed, for constant load torque, difference between synchronous speed and

    operating speed in rpm is constant and independent of frequency if true E/f control is

    implemented. In this example V/f control is used instead, so that the difference between

    synchronous and operating speed slightly varies. Nevertheless, one notes that slip in per

    unit is substantially different (4% and 8.9%); this is a consequence of the change in

    synchronous speed when frequency varies.

    Example 12: Scalar (V/f = const) control of induction machines

    A 3-phase, 60-Hz, 460-V, 1746-rpm cage induction motor operates with constant V/f speed

    control. Assume the motor torque-speed characteristic in the range of 0 150% rated

    torque to be linear.

    a) Calculate the applied voltage and speed of the fully loaded motor at 45-Hz supplyfrequency.

    b) If the motor drives a centrifugal pump (of approximately square torque-speedcharacteristic) under rated operating conditions, determine the supply voltage and

    frequency at 75% of full-load torque.

    Solution:

    Using a linear approximation of the torque-slip (speed) curve at small slips

    ( sr RsR / and lr XsR / ) the motor torque can be written in a form convenient for the

    analysis under the conditions of constant V/f control :-

    sff

    VRps

    RfpV

    Xs

    RR

    Vpfs

    RsT L

    rr

    L

    lr

    s

    r

    22

    22

    2

    22)(

    23)(

  • 8/3/2019 IM Starting&Control

    29/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 29

    a) The machine is operated with constant V/f ratio, and therefore at 45-Hz supply

    frequency the applied voltage is :

    line)-to-(lineV-34546060

    45 r

    rr

    r Vf

    fV

    f

    V

    f

    V

    In order to determine the rotation speed at 45-Hz one should take into account that the

    machine is fully loaded, which means that the load torque is equal to the rated value. The

    motor rated slip is:-

    03.01800

    174611

    s

    rr

    n

    ns

    Since the load torque is constant, the slip frequency has to be constant too as follows from

    the above torque expression. This allows the speed to be calculated in the following way:-

    rpm-1296135096.02

    456096.0)1(

    04.003.0

    45

    60

    s

    rr

    rr

    nsn

    s

    f

    fssffs

    b) The centrifugal load torque is proportional to the speed squared and at 75% rated torque

    the corresponding speed value is:-

    rpm-08.151275.01746

    2

    rr

    rr T

    Tnn

    n

    n

    T

    T

    The slip frequency under the same loading conditions is now using the initial torque

    expression:-

    Hz-35.16003.075.075.0 sffs

    sf

    T

    T

    rrr

    and the supply frequency can be obtained as :-

    Hz-753.5160

    208.151235.1

    60)

    601()1(35.1

    f

    npff

    f

    npf

    n

    nsf

    s

    The applied line voltage required is consequently: V-77.39646060

    753.51 r

    r

    Vf

    fV .

    4.6 Control of Inverter-fed Induction Machines

    Variable voltage, variable frequency operation of induction machines is realised utilising

    autonomous inverters, in conjunction with a rectifier and a DC link circuit as shown in

    Fig.25. There are two generic structures of autonomous inverters. The first one, voltage

    source inverter (VSI), is the most frequently applied power supply source for control of

    induction motors. The second one, current source inverter (CSI), is beyond the scope of

    interest here and wont be considered. The principle of operation of a three-phase VSI is

    explained next.

  • 8/3/2019 IM Starting&Control

    30/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 30

    C

    L

    d.c.link

    +

    -

    Filter InverterControlled

    RectifierIM

    3-phfixedfrequency

    supply

    3-phvariablefrequency

    V f

    Fig.25: Variable speed drive system (top) and family of torque-speed curves with

    V/f = const control (bottom)

    The 3-phase VSI contains three inverter legs with the input voltage being provided by a

    three-phase (or single-phase) bridge rectifier with a capacitor placed at the output (Fig.25).

    The capacitor provides smoothing of the DC voltage and, for sufficiently large capacitance,

    the DC output voltage approaches a constant value for a given firing angle. It will therefore

    be assumed that inverter input voltage is constant in the subsequent analysis.

    The power circuit of a six-step voltage source inverter is shown in Fig. 26. As the inverter

    itself controls only the frequency of the output AC voltage, a controllable rectifier must be

    used in order to provide control of the output voltage magnitude via DC voltage variations

    (output voltage magnitude is proportional to the input DC voltage). Each switch in the

    inverter circuit is again composed of two back-to-back connected semiconductor devices.

    One of these two is normally a transistor switch (most commonly an IGBT), while the

    other one is a diode. The diode is essential for the correct operation of the VSI as the output

    voltage and current are out of phase due to inductive nature of the machine. It enables

    current flow when one switch in a given inverter leg is turned off and the other one turned

    on, while the current still flows in the previous direction. This diode is usually called afreewheeling or feedback diode.

    The three inverter legs are controlled in such a way that the corresponding voltages

    constitute a 3-phase system of square-wave voltages. This means that, assuming that the

    upper transistor in the leg A is fired at time instant zero, firing of upper transistor in the leg

    B will take place after 120, while firing of the upper transistor of the leg C will be delayed

    for another 120. The conduction of each of the six semiconductor switches is again 180

    so that at any time three out of six switches are on and the remaining three switches are off.

    The resulting output voltage waveforms of line-to-line voltages in Fig.27 are quasi-square

    waves, with two 60 zero intervals and two 120 non-zero intervals in which line-to-linevoltage equals plus and minus DC link voltage, respectively. A VSI operated in this 180

    conduction mode is therefore usually called a six-step inverter.

  • 8/3/2019 IM Starting&Control

    31/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 31

    The leg voltages of the inverter are given in Fig.27 with respect to the negative pole of the

    DC link. The line-to-line voltages applied to the induction machine, also illustrated in

    Fig.27, are obtained directly from the leg voltages as vAB = vAn - vBn, vBC = vBn - vCn and

    vCA = vCn - vAn . Finally, if the machine is star connected, it can be shown that in the

    system of Fig.26 line to neutral (phase) voltages of the machine (presented in the Fig.27)

    are determined with the following expressions:

    p

    C

    VDC A B C

    n

    Rectifier and inverter control: IM

    rectifier controls VDC while inverter controls

    output frequency so that V/f = Vn /fn or

    V = (Vn /fn )f + V0.

    Fig.26: 3-phase voltage source inverter (VSI) fed induction motor.

    AnBnCnC

    CnAnBnB

    CnBnAnA

    vvvv

    vvvv

    vvvv

    3/13/2

    3/13/2

    3/13/2

    (13)

    As is obvious from Fig.27, waveforms of line to line and line to neutral voltages are notsine waves. Indeed, it can be verified by Fourier analysis that they contain higher odd

    harmonics but not those divisible by three. The situation is quite similar with the current

    harmonic content.

    In the previous analysis it has been assumed that the inverter is operated in 180

    conduction mode and that variation of the inverter output voltage magnitude is achieved by

    rectifier control. Such a solution is nowadays rarely applied. Instead, the inverter is

    operated in pulse width modulated (PWM) mode and is supplied from a diode (not

    thyristor) bridge rectifier (single-phase or three-phase), so that the input DC voltage of the

    inverter is constant. This operating mode allows variations of both inverter output voltage

    and output frequency to be achieved by appropriate inverter switching.

  • 8/3/2019 IM Starting&Control

    32/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 32

    The idea of PWM can be relatively easily explained using a single-phase VSI circuit of Fig.

    28. The most frequently utilised method of PWM is the so-called sinusoidal PWM

    technique, in which the reference signal - a sine wave of desired amplitude and frequency -

    is compared with a triangular carrier wave of constant amplitude and frequency. The

    instants for turn-on and turn-off of semiconductors are then determined with intersections

    of the reference signal and the carrier wave. Switches are turned on and off in pairs: S1 andS2 are always together either on or off and similarly, S3 and S4 are always together either

    on or off. The advantage of this approach is twofold. Firstly, the inverter now becomes

    capable of controlling both the frequency and the first harmonic magnitude, so that there is

    no need for application of a controllable rectifier. Instead, a diode rectifier is quite

    sufficient. Secondly, switching now occurs not at line frequency, as is the case with a six-

    step inverter, but at much higher carrier wave frequency. This enables significantly faster

    control and, at the same time, greatly improves harmonic spectrum of the load current. The

    inverter output voltage now does not contain low order harmonics (the fifth, seventh, etc.)

    present with the six-step inverter. Instead, harmonics are situated around multiples of the

    switching frequency (i.e., triangular carrier wave frequency). Thus, if the switchingfrequency is 5-kHz (typical value nowadays), then the inverter output voltage will contain,

    apart from fundamental, higher harmonics of frequencies around 5 kHz, 10 kHz, 15 kHz

    etc. If the motor operates with 50-Hz fundamental frequency, then 5-kHz means that the

    order of the harmonic is around 100 (rather than 5, as it is in the simple VSI discussed

    previously). As the motor reactance is 100 times greater at 5-kHz than at 50-Hz, harmonic

    currents in the motor will be consequently very small.

    The principle of sinusoidal PWM applied to the single-phase bridge inverter of Fig. 28, is

    illustrated in Fig.29. The impact of amplitude variations of the reference signal on the

    output voltage waveform is evident from the same figure. The widths of the pulses in the

    two cases shown differ although output frequency and triangular carrier wave frequency arethe same. This change in pulse widths leads to subsequent difference in the values of the

    first harmonic of the output voltage. It can be shown that the fundamental harmonic of the

    output voltage waveforms shown in Fig.29 equals in frequency and in amplitude the

    reference signal.

    An extension of the PWM principle from a single-phase to a 3-phase voltage source

    inverter is rather straightforward. The reference sinusoidal voltage (which equals desired

    fundamental voltage at the inverter output) is formed on the basis of the control law for

    given operating point (say, V/f = Vn /fn law). This is further compared with the carrier

    signal (again, high frequency triangular waveform) and the intersections points representthe switching instants for the inverter legs. The 3-phase inverter however requires three

    120 mutually displaced reference sinusoidal signals in order to achieve operation with

    three-phase system of output voltages. If a triangular carrier frequency is sufficiently high,

    one carrier may be utilised for all the three phases. It can be shown that although the output

    voltage is again composed of a series of rectangular pulses, fundamental component of the

    output voltage is of the same frequency and magnitude as the reference sinusoidal signal.

  • 8/3/2019 IM Starting&Control

    33/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 33

    vAn VDC vAB VDC

    vBn vBC

    vCn vCA

    0 60 120 180 240 300 360 t []

    Leg voltages

    Line-to-line voltages

    2/3 VDC

    vA 1/3 VDC

    vB

    Line to neutral voltages

    vC

    Fig.27: Typical voltage waveforms in a VSI fed induction machine.

    In summary, it can be stated that the operation of a VSI in PWM mode yields two

    substantial benefits, when compared to operation in 180 conduction mode. A diode

    rectifier can be used instead of a controllable rectifier, since the inverter is now capable of

    controlling both the frequency and the rms value of the fundamental component of the

    output voltage. Additionally, higher harmonics of the voltage are now of substantially

    higher frequencies, meaning that current is much closer to a true sine waveform. Due to

    high control rate and improved power supply quality, the machine performance is also

    generally much better and its operation can be very smooth and free of torque ripples.

  • 8/3/2019 IM Starting&Control

    34/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 34

    Rectifier i

    S1 S3

    V C v Load

    S4 S2

    0

  • 8/3/2019 IM Starting&Control

    35/36

    EN0567Power, machines and renewable energy

    Lecture Notes - Dr M Jovanovic Page 35

    Example 13: Induction motors with V/f control and PWM inverter supply

    A 3-phase, 415-V, 50-Hz, 1440-rpm inverter-fed cage induction motor with constant V/f

    speed control drives a centrifugal pump under rated operating conditions.

    a) Using the approximate equivalent circuit of the machine, derive the torque expressionstating the meanings of all the parameters used.

    b) Show that the torque-slip (speed) characteristic is linear at small slips and that themotor torque is approximately constant providing that the slip frequency is constant.

    c) Use the above approximation to estimate the supply voltage and frequency required toreduce the drive speed to 1000-rpm.

    Solution:

    This example is closely related to the previous and the two should be considered together.

    a) The electromagnetic torque expression for a 2p-pole IM is :

    sfXsRR

    VpR

    s

    IRsT

    rs

    r

    s

    rr

    ])/[(2

    33)(

    22

    22

    where rI is the rotor phase current, srR , are the rotor and stator phase resistances

    respectively, V is the machine phase voltage, X is the total leakage reactance (stator plus

    rotor leakage), s is the slip andfis the supply frequency.

    b) Linear approximation at small slips: XRsR sr ,/

    sff

    Vcs

    f

    V

    R

    ps

    sfR

    VpRsT

    rr

    r 222

    2

    2

    2

    3

    2

    3)(

    Therefore ifsf= rotor (slip) frequency is constant then the motor torque is constant too.

    c) Centrifugal load torque at 1000-rpm and 1440-rpm (torque ratio under constant V/f

    control) :

    rrrrated

    load

    fs

    sf

    n

    n

    T

    T

    22

    1440

    1000

    Slip frequency:6060

    )1(np

    fpf

    nfff

    n

    nsf

    s

    .

    The above torque ratio now becomes (the machine is 4-pole as its rated speed is 1440-rpm

    i.e. the synchronous speed at 50-Hz is 1500-rpm) :-

    Hz-3.34120

    200060

    14405060

    100060

    60

    60

    1440

    10002

    f

    f

    p

    pf

    pnf

    npf

    fs

    sf

    rrrr

    3

    The supply voltage at 34.3-Hz is thus:

    LLV-69.28441550

    3.34 rrr

    r VffVconst

    fV

    fV

  • 8/3/2019 IM Starting&Control

    36/36

    EN0567Power, machines and renewable energy

    Example 14: Constant Volts/Hz control of IMs using a PWM voltage source inverter

    A 3-phase, 440-V, 6-pole, 50-Hz, delta-connected induction motor has the following rated

    parameters per phase: stator resistance = 0.2-; rotor resistance = 0.18-; stator and rotor

    leakage reactance = 0.58- each. The machine operates with constant V/f scalar control

    supplied from a PWM voltage source inverter.(a)The machine is subjected in service to a 40% fall in both voltage and frequency. What

    total mechanical load torque is it safe to drive so that the machine does not stall under

    these conditions?

    (b)IfV and f were both halved, what would be the increase in starting torque from thenormal DOL start? Compare the starting currents for these two cases and comment

    upon the results obtained.

    Solution:

    (a)This part of the question asks effectively for the maximum torque with voltage andfrequency reduced to 0.6 of rated values. Substituting for a = 0.6 in the expression for

    maximum torque derived earlier (refer to Example 12) one gets:

    Nm.-4.1800

    )16.16.0(2.02.0

    )4406.0(

    506.04

    33)(

    4

    3)(

    max

    22

    2

    222

    2

    max

    T

    XaRR

    aV

    af

    PafT

    ss

    r

    rr

    (b)The ratio of starting torque at reduced and full voltage and frequency for a = 0.5 is (seeExample 12) :

    88.0

    58.038.0

    16.138.05.0

    )(

    )(

    55.15.058.038.0

    16.138.0

    )(

    )(

    22

    22

    222

    22

    22

    22

    222

    22

    XaRR

    XRRa

    ffI

    affI

    aXaRR

    XRR

    ffT

    affT

    rs

    rs

    rst

    rst

    rs

    rs

    rst

    rst

    Note that due to improved power factor following the reduction of reactance (because of

    the lower supply frequency), the starting torque is increased by 55% relative to the DOL

    value while the current required to achieve this torque rise is 88% DOL value. Therefore

    the starting torque per ampere (TPA) is much higher with reduced voltage and frequency

    starting and can be calculated as follows:

    rf

    f

    rst

    rst

    st

    st

    rst

    st

    rst

    st

    TPA

    TPA

    fI

    fT

    fI

    fT

    fI

    fI

    fT

    fT

    )(

    )(

    )(

    )(

    76.188.0

    55.1

    )(

    )(

    )(

    )(

    The TPA is increased by 76% compared to DOL starting This ratio is even better at lowerf i