iCM-RP Room pressure controller • Room pressure monitor 1 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com Performance features Microprocessor controlled room pressure regulation with a full-graphic LC-display and a numerical room pressure signaling in Pascal Compact control system in a wall housing Integrated operator panel with status display and alarm acknowledgement Integrated optional limit value monitoring of the room under- or overpressure with visual or optional acoustical alarm Constant room pressure maintenance freely programmable All system data is stored fail-safe in an EEPROM Running time of the actuator 3 s for 90 °, running time delay freely programmable Free parameterization of the system data via the internal menu or laptop with software PC2500, e. g. regulation time, over- or underpressure Internal static differential pressure sensor with a high long-term stability for the steady measurement of the actual value within a range of ± 50 Pa or optional -80 to +20 Pa (external) Fast predicitve control algorithm Fast, steady and precise control via direct activation of the actuator with feedback potentiometer Closed loop Monitoring of the customer provided ventilation system Suitable as room supply air or exhaust air controller Analogue actual value output 0(2) to 10 V DC/10 mA) Two digital inputs for up to three different room pressure setpoint settings (e. g. airlocks, day/night operation) Relay contact 1 x A for limit value monitoring Internal power supply 230 V AC Product description Function descriptionPerformance features Product description Microprocessor controlled system for regulation and monitoring of the constant room pressure maintenance. It has to be maintained a constant over- or underpressure in clean rooms or laboratories compared to adjoining rooms (e. g. corridor). This avoids the intrusion respectively loosing of contaminated or uncleaned air with an excessive dust content depending on the application. The room pressure controller iCM-RP regulates independently the necessary free programmable room under- or overpressure. The setpoint setting occurs via the digital inputs (parameterization via password protected internal menu or laptop with PC2500 software (USB ash drive)). The adjusted room pressure actual value is shown on the full graphic LC display as a numerical value in Pascal. Exceeding or undercut of the adjusted setpoint setting triggers the visual (red LED) and optional acoustical alarm. The room pressure controller iCM-RP is a suitable system supplement for the fume hood controller iCM-F-0 (regulation to a constant air inow) to guarantee the constant room pressure maintenance of the laboratory. Together with the duct pressure controller iCM-DP which regulates a bypass damper or the frequency converter of the fan directly SCHNEIDER provides a completely integrated and independent regulation system. Functional description Microprocessor controlled fast regulation system for a constant pressure maintenance of rooms. A fast control algorithm compares the room pressure setpoint with the measured room pressure of the static differential pressure sensor and controls fastly, precisely and steadily independent of pressure uctuations within the duct net. The parameterized constant room under- or overpressure is therefore constantly maintained. The room pressure to be regulated is freely adjustable and can be stored fail-safe in an EEPROM. The control velocity is very fast (control time < 3 s) and the actuator running time for 90 ° can be freely adjusted within a range of 3 s to 24 s. Due to the high control velocity the installation of a door respectively window contact is mandatory, to achieve a steady control behaviour and to avoid unnecessary control cycles during the opening and closing of doors or windows. While using the door or window contact the current control value is „frozen“, this means the room pressure regulation is inactive. The contact can be parameterized as NO (normally open or NC (normally closed). The SCHNEIDER dampers for the room pressure controller iCM-RP are available in round or rectangular versions. The room pressure controller iCM-RP regulates independently and has an internal limit value monitoring with a potential-free relay output each for the the upper and lower limit value. iCM-RP-1 DK-200-S-K-0-0-RR-1

iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

  • Upload
    others

  • View
    21

  • Download
    0

Embed Size (px)

Citation preview

Page 1: iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

iCM-RPRoom pressure controller • Room pressure monitor

1 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com

Performance features

Microprocessor controlled room pressure regulation with a full-graphic LC-display and a numerical room pressure signaling in Pascal Compact control system in a wall housing Integrated operator panel with status display and alarm

acknowledgement Integrated optional limit value monitoring of the

room under- or overpressure with visual or optional acoustical alarm Constant room pressure maintenance freely

programmable All system data is stored fail-safe in an EEPROM Running time of the actuator ≤ 3 s for 90 °, running

time delay freely programmable Free parameterization of the system data via the

internal menu or laptop with software PC2500, e. g. regulation time, over- or underpressure Internal static differential pressure sensor with a high

long-term stability for the steady measurement of the actual value within a range of ± 50 Pa or optional -80 to +20 Pa (external) Fast predicitve control algorithm Fast, steady and precise control via direct activation of

the actuator with feedback potentiometer Closed loop Monitoring of the customer provided ventilation system Suitable as room supply air or exhaust air controller Analogue actual value output 0(2) to 10 V DC/10 mA) Two digital inputs for up to three different room

pressure setpoint settings (e. g. airlocks, day/night operation) Relay contact 1 x A for limit value monitoring Internal power supply 230 V AC

Product description ● Function description● Performance features

Product description

Microprocessor controlled system for regulation and monitoring of the constant room pressure maintenance. It has to be maintained a constant over- or underpressure in clean rooms or laboratories compared to adjoining rooms (e. g. corridor). This avoids the intrusion respectively loosing of contaminated or uncleaned air with an excessive dust content depending on the application.

The room pressure controller iCM-RP regulates independently the necessary free programmable room under- or overpressure. The setpoint setting occurs via the digital inputs (parameterization via password protected internal menu or laptop with PC2500 software (USB fl ash drive)).

The adjusted room pressure actual value is shown on the full graphic LC display as a numerical value in Pascal. Exceeding or undercut of the adjusted setpoint setting triggers the visual (red LED) and optional acoustical alarm.

The room pressure controller iCM-RP is a suitable system supplement for the fume hood controller iCM-F-0 (regulation to a constant air infl ow) to guarantee the constant room pressure maintenance of the laboratory. Together with the duct pressure controller iCM-DP which regulates a bypass damper or the frequency converter of the fan directly SCHNEIDER provides a completely integrated and independent regulation system.

Functional description

Microprocessor controlled fast regulation system for a constant pressure maintenance of rooms. A fast control algorithm compares the room pressure setpoint with the measured room pressure of the static differential pressure sensor and controls fastly, precisely and steadily independent of pressure fl uctuations within the duct net.The parameterized constant room under- or overpressure is therefore constantly maintained.

The room pressure to be regulated is freely adjustable and can be stored fail-safe in an EEPROM. The control velocity is very fast (control time < 3 s) and the actuator running time for 90 ° can be freely adjusted within a range of 3 s to 24 s.

Due to the high control velocity the installation of a door respectively window contact is mandatory, to achieve a steady control behaviour and to avoid unnecessary control cycles during the opening and closing of doors or windows.While using the door or window contact the current control value is „frozen“, this means the room pressure regulation is inactive. The contact can be parameterized as NO (normally open or NC (normally closed).

The SCHNEIDER dampers for the room pressure controller iCM-RP are available in round or rectangular versions.

The room pressure controller iCM-RP regulates independently and has an internal limit value monitoring with a potential-free relay output each for the the upper and lower limit value.

iCM-RP-1

DK-200-S-K-0-0-RR-1

Page 2: iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

iCM-RPRoom pressure controller • Room pressure monitor

2 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com

Block diagram 1: room pressure controller iCM-RP

VAV/CAV

Supply air (variable) Exhaust air

(variable/constant)

Lab room (-) = negative pressure

Floor (+) = positive pressure

DK

+ -

T

Door contact

-10 Pa

iCM

+-Set VmaxI/O

Room Pressure

p

iCM-RP

50 Pa-+

Room pressure control-Supply air with Damper DK

Damper DK with high speed actuator

Parameterization

The parameterization of the setpoints and the readout of the actual value occur via laptop and software PC2500 (USB fl ash drive) or the integrated menu.

Constant room regulation

The room pressure controller iCM-RP is delivered in a wall housing, already contains the static differential pressure transmitter (± 50 Pa) and is suitable for the independent room pressure control of supply air as well as for exhaust air.

In block diagram 1 the room pressure controller iCM-RP follows the variable respectively constant room exhaust air and maintains the room pressure within the laboratory rooms in a constant underpressure (e. g. -10 Pa) via the room supply air although the exhaust air volume fl ow is re-gulated variably via the temperature sensor T.

The room pressure controller iCM-RP can control rooms in under- or overpressure by a suitably connected static dif-ferential pressure transmitter. Laboratories are controlled in underpressure while clean rooms are controlled in over-

pressure to avoid the intrusion of „unclean“ air into the clean room.

When used in laboratories (underpressure) the static dif-ferential pressure transmitter of the iCM-RP measures the pressure difference between the corridor (+) and the clean room (+) und generates the actual value signal for the to be adjusted setpoint.

When used in clean rooms (overpressure) the pressure difference between corridor (-) and the clean room (+) is measured. In this case the (-) connection of the differential pressure transmitter is led through the corridor.

The volume fl ow for the room exhaust air can also be con-veyed in a two-stage operation (day/night operation) or via a constant volume fl ow controller (CAV).

Due to the fast and precise control algorithm and the fast running actuator with „Fast Direct Drive“ activation it is pos-sible to adjust relatively airtight rooms smoothly as well. For extremly airtight rooms we recommend SCHNEIDER‘s VCP500 which is especially developed for this application.(see technical data sheet VCP500).

Room pressure controller iCM-RP ● Block diagram

Page 3: iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

iCM-RPRoom pressure controller • Room pressure monitor

3 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com

Room pressure controller iCM-RP ● Operating modes ● Set values ● Parameterization

digital inputfunction input 2

(day/night)set value 1 = normal value (day) 0set value 2 = reduced value (night) 1

Table 1: iCM-RP-operating modes

0 [Pa]10020 40 60 80

Function Input 1 [V]

10

8

6

4

2

0

9

7

5

3

1

room

pre

ssur

e ac

tual

val

ue (A

-Out

1)

room pressure

setpoint 1 0

set-point 1

setpoint 2 1

set-point 2

setpoint 3 with button VMAX

set-point 3

Graph 1: constant room pressure regulation (iCM-RP)Constant room pressureThe constant room pressure is regulated depending on the digital input circuit.

The available operating modes are shown in graph 1 and table 1. A 1-point, 2-point or 3-point operation (set value 1 to 3) can be easily realized by direct activation of the digital inputs or via the button Vmax.

Setpoints 1 to 3 for room pressure specifi cation

The room pressure setpoints shown in graph 1 are parame-terized for example with the following setpoints:

setpoint 1 (normal value) = + 40 Pascal setpoint 2 (reduced value) = + 20 Pascal setpoint 3 (emergency) = + 10 Pascal

The room pressure actual value signal (A-Out1) correlates with the adjusted room pressure.

For the circuit of the digital inputs refer to table 1 and termi-nal connection plan on page 11.

Positive or negative room pressure setpoint values can be regulated for the airlock pressure controller or clean rooms.

Alarm thresholds

Two independent alarm thresholds can be parameterized with arbitrary alarm values within the sensor range. The alarm threshold values high and low affect the alarm relay. If the alarm relay sinks, the alarm threshold is exceeded or undercut and the alarm status will be signaled.

The alarm threshold values always relate to the to be adju-sted prevailing room pressure setpoint.

Example: alarm threshold value high = 5 Pascal alarm threshold value low = 3 Pascal setpoint 1 (day) = + 20 Pascal setpoint 2 (night) = - 15 Pascal

During room pressure maintenance setpoint 1 (+20 Pas-cal) the alarm threshold value high will be exceeded and signaled at > +25 Pascal and the alarm threshold value low will fall below and signaled at < +17 Pascal (alarm relay drops down).

During room pressure maintenance setpoint 2 (-15 Pas-cal) the alarm threshold value high will be exceeded and signaled at < -10 Pascal and the alarm threshold value low will fall below and signaled at (alarm relay drops down).

If the input 2 is not wired (dead) setpoint 1 will be automa-tically adjusted.

The emergency (setpoint 3) can only be activated via button Vmax. The reduced value (setpoint 2) can be activated via the button „set“ or the digital input In2.

The contacts can be parameterized as NO (normally open) or NC (normally closed).

Alarm delay timeThe alarm delay time is freely programmable within a range of 0 to 240 s. The alarm mode has to be queued for at least the adjusted time to trigger the alarm. This time period re-duces the triggering of false alarms, e. g. in case of instable air supply.

Door-/window contactTo avoid unnecessary regulation cycles by opening or closing of doors respectively windows and due to the high control velocity (< 3 s) a suitable contact has to be connected which „freezes“ the present control value for the operation time which means that for this time period the room pressure control is inactive. The contact can be parameterized to NO (normally open) or NC (normally closed).

Page 4: iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

iCM-RPRoom pressure controller • Room pressure monitor

4 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com

Damper with fast running actuator with feedback potentiometer (standard version)

The room pressure to be adjusted occurs via the damper (supply or exhaust air). The very fast running actuator (3 s for 90 °), specifi cally developed for SCHNEIDER, is directly mounted to the axis of the damper and possesses a torque of 3 Nm and is suitable for round or rectangular dampers up to a diameter of 280 mm or 250 x 250 mm.The actuator is directly activated by the control electronics. (fast direct drive). This guarantees a fast and stable control behaviour.This activation mode shows signifi cant advantages compared to the analogue actuator activation (0 to 10 V DC) because the internal control electronics of the analogue (steady) controlled actuator posssesses a hysteresis which could cause vibrations in the controller in case of narrow room pressures to be adjusted or airtight rooms. A feedback potentiometer signals the actual value of the present damper position to the control electronics. A special control algorithm provides the necessary room pressure without vibration fastly and directly.

During the activation of the actuator the actual damper adjustment (damper control) is tested at the same time. This control concept with integrated monitoring function of the actuator exceeds the high safety regulations which are mandatory for room pressure controllers.

The end position of the dampers (damper close = 0 % and damper open = 100 %) can be arbitrarily parameterized, that means the actuator stops automatically at the pro-grammed damper position and regulates just within the parameterized spectrum (e. g. between 10 to 80 %). Therefore the minimum and maximum volume fl ows can be limited without further effort.

MNMQ 15

DN

Dampermotor withfeedbackpotentiometer(for damper position)

Dampermotor,4Nm3 sec for 90 °

Feedbackpotentiometerfor damper position

Damper with fast running actuator with feedback potentiometer

Performance features damper

IMPORTANT!Actuator NMQ12 (3 Nm) can be used for round dam-pers up to a diameter of 280 mm or rectangular dam-pers up to 250 x 250 mm.For larger dampers the actuator NMQ24 (8 Nm) with additional external transformer (additional box E4) has to be used.

Page 5: iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

iCM-RPRoom pressure controller • Room pressure monitor

5 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com

Performance features software

Upward and downward control time freely parameterizableThe upward control time (damper open) and the downward control time (damper closed) is freely parameterizable in 1-second steps from 2 to 24 s. For this reason the control behaviour of the room pressure controller iCM-RP can be adjusted optimally to the room conditions (room size and tightness). Vibration tendencies can be minimized or completly avoided by optimal parameterization.

Control parameters

All project specifi c control parameters, e. g. room pressure setpoint, deadzone and close-up range can be retrieved, changed and monitored smoothly on site via the internal service level or a laptop (see overview internal menu list on page 10). A cyclic sequential retrieving and testing of control actual values and setpoints guarantees a very fast, stable and adequate room pressure regulation.

Test- and diagnosis functions

For the commisssioning, diagnosis and simple error search it is very important to have an extensive and exact overview of all measured actual values.

SCHNEIDER‘s special test and diagnosis programm via service module SVM100 or PC software PC2500 provides the service and commissioning staff with the following actual values.

The controller iCM-RP possesses additionally an integrated service level which is accessible with the functional keys via password.

actual value unitroom pressure Padamper position %

The following test functions are feasible:

Indication of digital inputs Indicates the present status of all digital inputs

Analogue inputs Indicates all analogue inputs with the present signal

voltage

Analogue outputs Indicates all analogue outputs with the present signal

voltage

Testing of actuator/damper Actuator/damper can be opened and closed with this

test function

These test and diagnosis functions facilitate and simplify the commissioning and error search signifi cantly.

ATTENTION!The room pressure controller iCM-RP is not suitable for very airtight rooms. If very airtight rooms should be adjusted exactly and pressure stably we recom-mend SCHNEIDER‘s patented room pressure priori-tized volume fl ow controller VCP500 (see technical data sheet VCP500).

Page 6: iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

iCM-RPRoom pressure controller • Room pressure monitor

6 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com

Room scheme 1 ● Room pressure controller iCM-RP with variable or constant room supply air

VAV/CAV

Supply air (variable/constant)

Exhaust air (variable)

Floor (+) = positive

pressure

Lab room (-) = negative

pressure

T

Door contact

Room pressure controller

Exhaust air with damper DK -

+-

Room Pressure

iCM-RP

-+

+

DK

The room scheme 1 correlates with the block diagram 1 (page 2), unless that the room supply air is regulated by a variable (VAV) or constant (CAV) volume fl ow controller.

The room pressure controller iCM-RP follows the room sup-ply air and maintains the constant room pressure via the room exhaust air. (e. g. -10 Pa).

Clean rooms are mainly controlled in overpressure to avvo-id the intrusion of „uncleaned“ air into the clean room.

Air lock (+) = positive

pressure against common reference

Exh

aust

air

(con

stan

t)

CAV

Supply air (variable)

DK

CAV

CAV Rau

mab

luft

(kon

stan

t)

Common(-) = reference

Door contact

Door contact

Door contact

-

+-

Room Pressure

iCM-RP

-+

+

DK

-

+-

Room Pressure

iCM-RP

-+

+

DK

-

+-

Room Pressure

iCM-RP

-+

+

Supply air (variable)

Supply air (variable)

Exh

aust

air

(con

stan

t)

Room 1 (++) = positive

pressure against common reference

Room 2 (+++) = positive

pressure against common reference

Room scheme 2 ● Airlock room pressure controller iCM-RP with variable or constant exhaust air

room reference measure-ment to

paramete-rized value [Pascal]

pressure difference to-wards corridor (atmosphere) [Pascal]

airlock common +10 +10room 1 common +20 +20Raum 2 gemeinsam +30 +30

Table 2: example values and reference measurement

Room scheme 2 shows an appli-cation with constant volume fl ow controllers (CAV) each for the room exhaust air of the different rooms.

The room pressure controller iCM-RP regulates automatically the parameterizable room over-pressure (+) independently for each room.

Table 2 shows the paramete-rized values and the reference measurement of the static diffe-rential pressure transmitter. All room pressure controllers iCM-RP are summarized on the (-) = underpressure page and measu-re against a common reference point. This preferred measuring type guarantees the best stabi-lity, at which the reference point should be situated at a construc-tional favorable position (e. g. calm cellar room without wind load respectively air pressure changes (Attention: elevators)). The wrong measurement of rooms against each other (e. g. room 1 against airlock) leads to reinforced vibrati-on tendencies in the room pressu-

re controlling because room pressure changes e. g. in the airlock affect room 1.

Arbitrary reference measurements and iCM-RP confi gura-tions (room supply air or exhaust air) are possible, depen-ding on the applications, at wich the control stability (low vibration tendency) should always be taken into conside-ration.

Page 7: iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

iCM-RPRoom pressure controller • Room pressure monitor

7 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com

...

FUME HOOD #1

0,3 m/s

iCM

+-Set I/O

FUME HOOD #2

0,3 m/s

iCM

+-Set I/O

FUME HOOD #3

0,3 m/s

iCM

+-Set I/O

FUME HOOD #n

0,3 m/s

iCM

+-Set I/O

Room supply air (variable)

Floor (+) = positive pressure

DK

+ -

Door contact

-10 Pa

iCM

+-Set VmaxI/O

Room Pressure

p

iCM-RP

50 Pa-+

Room pressure control-Supply air with damper DK

Damper DK with high speed actuator

CAV

Room exhaust air (constant)

Labroom (-) = negative pressure

Constant speed extract fan

Fres

h ai

r

Bleed damper DK with high speed actuator (Bypass)

-420 Pa

iCM

+-Set VmaxI/O

Duct Pressure

p

iCM-DP

800 Pa-+

Duct pressure control-Extract air

with Bleed damper DK

DK

Ext

arct

air

+ -

Con

stan

t dis

char

ge

velo

city

iCM-F-0

iCM-RP

iCM-DP

Block diagram 2: complete independent laboratory control system with laboratory control system iCM-F-0 (face velocity), room pressure controller iCM-RP and duct pressure controller iCM-DP with bleed damper activation

The block diagram 2 shows a complete independent labo-ratory control system. The fume hoods are adjusted to a constant infl ow velocity via the face velocity controller iCM-F-0. Depending on the total exhaust air volume fl ow, which consists of the extracting fume hoods and the constant con-troller CAV, the supply air is compensated in such a way to maintain a constant underpressure of - 10 Pa.

The disadvantage is the direct infl uence of opened doors respectively windows on the room pressure. To avoid un-necessary regulation of the falling room pressure the con-nection of a door and/or window contact is recommended. Therefore the room pressure controller will be „frozen“ with the present damper position (inactive) when a door or win-

dow is open to reduce the wearout of the actuator and the gear signifi cantly.

In this example the duct pressure controller iCM-DP works independently as well and is chosen as a bleed damper ac-tivation. A duct pressure controller via frequency converter FU for the total supply air and exhaust air is also possible.

Further applications (block diagrams): see technical data sheet iCM-LabSystem.

Page 8: iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

iCM-RPRoom pressure controller • Room pressure monitor

8 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com

Order code: room pressure controller/damper with actuator

Order code: room pressure controller

Room pressure controller with graphic LC-display and numerical room pressure display in Pascal, mounted in a wall housing with integrated static differential transmitter ± 50 Pa, relay for upper and lower limit value and internal power supply 230 V AC.

make: SCHNEIDER type: iCM-RP-1

Order example: room pressure controller with graphic display iCM-RP-1

iCM - RP -

control operating moderoom pressure controller RP

1

differential pressure transmitter1 internal, ± 50 Pascal2 external, - 80 to + 20 Pascal

Important:DK damper with actuator has to be ordered additio-nally.

type

Order code: damper (without measuring device) with actuator, round design

DK 250 - P MM - -

materialPolypropylene (PPs) PPPs-el (electroconductive) PelPolyvinyl chloride (PVC) PVGalvanized steel SStainless steel 1.4301 (V2A) V2Stainless steel 1.4571 (V4A) V4

Damper, DN250, PPs, without damper seal , without rubber lip seal, without acoustic cladding, socket/socket, fast running actuator 3 s for 90 ° (fast direct drive SCHNEIDER).

make: SCHNEIDER type: DK-250-P-0-0-0-MM-1

Order example: damper with actuator, round design, PPs

actuator type1 SCHNEIDER standard, direct drive,12 V,

3 s für 90 °, 3 Nm8 steady impulse 24 V, 4 s für 90 °, 8 Nm

(with external 24 V transformer)

1 -

nominal diameter DN [mm]100, 110, 125, 160200, 225, 250, 280315, 355, 400

100...

400

material available nominal diameterPolypropylene (PPs) P 110, 160, 200, 225, 250, 280 315, 355, 400PPs-el (electroconductive) Pel 110, 160, 200, 225, 250, 280 315, 355, 400Polyvinyl chloride (PVC) PV 110, 160, 200, 225, 250, 280 315, 355, 400Galvanized steel S 100, 125, 160, 200, 225, 250, 280 315, 355, 400Stainless steel 1.4301 (V2A) V2 100, 125, 160, 200, 225, 250, 280 315, 355, 400Stainless steel1.4571 (V4A) V4 100, 125, 160, 200, 225, 250, 280 315, 355, 400

0 -

rubber lip seal (only steel and V2A/V4A)0 = without G = with rubber lip seal

acoustic cladding0 = without D = with acoustic cladding

0 -0 -

damper sealwith damper seal = K ohne = 0

pipe connections infl ow/outfl owMM socket/socket (only PPs und PPs-el)MF socket/fl ange (only PPs und PPs-el)FM fl ange/socket (onlyPPs und PPs-el)FF fl ange/fl ange (PPs, PPs-el, steel and stainless steel)RR pipe/pipe (only steel and stainless steel)

Important:Room pressure controller iCM-RP-1 has to be ordered additionally. From nominal diameter ≥ DN315 the delivery includes the actuator type 8 with additi-onal box E4 (external 24 V transformer).

type

Page 9: iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

iCM-RPRoom pressure controller • Room pressure monitor

9 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com

order code: damper with actuator, rectangular design

DK 600 - S -

Damper, width = 600 mm, height = 400 mm, galvanized steel, without damper seal, without acoustic clad-ding, fl ange/fl ange (standard), fast running actuator 5 s für 90 °, 8 Nm.

make: SCHNEIDER type: DK-600-400-S-0-0-2

Order example: damper (without measuring device) with actuator, rectangular design, galvanized steel

8

nominal width W [mm]200, 300, 400, 500, 600

700, 800, 900, 1000, 1200

200...

1200

material available nominal widthsW [mm]

available nominal heightsH [mm]

Polypropylene (PPs) P 200...1000 100...400PPs-el (electroconductive) Pel 200...1000 100...400Polyvinyl chloride (PVC) PV 200...1000 100...400Galvanized steel S 200...1000 100...400Stainless steel 1.4301 (V2A) V 200...1000 100...400

0 -

acoustic cladding0 = without D = with acoustic cladding

0 -400 -

nominal height H [mm]100, 160, 200

250, 300, 400

100...

400 damper seal0 = without K = with damper seal

DK-250-P-0-0-0-MM-1 DK-600-400-S-0-0-2

Remark:Room pressure controller iCM-RP-1 and damper (DK) always have to be ordered separately.

-

Order code: damper (without measuring device), with actuator

Important:Room pressure controller iCM-RP-1 has to be ordered additionally. From nominal height ≥ 250 and nominal width ≥ 250 the delivery inclu-des the actuator type 8 with additional box E4 (external 24 V transformer).

actuator type1 SCHNEIDER standard, direct drive,12 V,

3 s für 90 °, 3 Nm8 steady impulse 24 V, 4 s für 90 °, 8 Nm

(with external 24 V transformer)

type

MaterialPolypropylene (PPs) PPPs-el (electroconductive) PelPolyvinyl chloride (PVC) PVGalvanized steel SStainless steel 1.4301 (V2A) V2Stainless steel 1.4571 (V4A) V4

Page 10: iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

iCM-RPRoom pressure controller • Room pressure monitor

10 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com

Display actual values

Enter password

Actual values

Pressure normal

Pressure reduced

Pressure emergency

Alarm limit HIGH

Alarm limit LOW

Slow area PLUS

Slow area MINUS

Deadzone PLUS

Deadzone MINUS

Pressure sensor

Nullification

Leading sign

Rotation direction

Control type

Ramp time Up

Ramp time Down

Damper limit HIGH

Damper limit LOW

Analog output

Software version

Alarm delay

Delay start

Buzzer duration

Vmax duration

Service

Button Set

Button I/O

Relay K3/K6

Relay K2/K5

Emergency type

DIN On/Off

DIN Day/Night

DIN Emergency

Test DIN/AIN/AOUT

Test motor

Operating hours

Language

Contrast

Password

Exit

Button Vmax

Survey menu list

Page 11: iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

iCM-RPRoom pressure controller • Room pressure monitor

11 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com

K1

ROOM PRESSURE CONTROL

iCM-RPDate:2014/November/03

Rev.:1.0

Relay Light

Terminal diagram, complete

Laptop

NO

CO

M

NO

NC

CO

M

1 2 3 4 5

RS485

X1iCM

Reset

RS 232

K2 K3

Relay On/Off

Relay Alarm

3 4 5X2

6 7 8 9 101112X3 X4

131415161718

192021

LED1

ANALOGUE OUTPUT A1Out0(2)...10V DC/10mA

GNDA1-Out

X5

X6

X7

X8GND

+15V DC

X9

X10X11

Run

ProgammingX12

X13JP2

X14

CPU

12

JP1

X14

1 2

-10 Pa

iCM

+-Set VmaxI/O

12

X2

STATIC DIFFERENTIAL PRESSURE SENSOR50 Pa

Actuator NMQ12, 3Nm only suitable for damper DN <= 280mm or rectangle <= 250 x 250mm!

DIGITAL INPUTSMax. Kabellänge < 3m

Day/Night

In1

In2

On/Off

Room Pressure Controller

Air direction

Actuator with feedback potentiometer

NMQ 123 Nm3 sec

M

Room pressure (-) = negative pressure

1 2 3 4 5

Floor (+) = positive

pressure

X3

iCM

-RP

Power supplyIN: 100...240V ACOUT: 15V DC/1,3 A

NL

POWER

230 VAC50/60Hz

1 2 3X1

F1

1,0 AT

+15V

-

- P

+ P50 Pa

SUPPLY15V DC/1,3 A

Cable specification:

Cable type for 230V AC Power:minimum NYM 3 x 1,52

Cable type for In-/Outputs:IY(St)Y 2x2x0,8 Lg for Voltage supply < 60 Vminimum NYM 2 x 1,52 for Voltage supply > 60 V up to maximum 250 V

On site tubingThe tubing of the controller with the room and the delivery of the required hose nibbles and the pressure hose is done on site.

Door contactIn3

FAU

LT A

LAR

M

OP

ERAT

ION

ON

LIG

HT

ON

/OFF

Max

.: 12

A /

B16

L1,2

,3 (1

15/2

30V

AC

)

ON

/OFF

Rel

ay c

onta

ctM

ax.:

3A /

60VA

C

FAU

LT A

LAR

MR

elay

con

tact

Max

.: 3A

/ 60

VA

C

AC

TUA

TOR

NM

Q 1

515

V D

C/3

Nm

/3 s

FEED

BA

CK

-PO

TEN

TIO

MET

ER

For damper DN > 280mm or rectangle > 250 x 250mm use actuator NMQ24, 8Nm with Add-On-Box -E4. The Add-On-Box -E4 supplies 24 VAC.

Terminal diagram: room pressure controller iCM-RP

Terminal diagram

Page 12: iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

iCM-RPRoom pressure controller • Room pressure monitor

12 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com

Dimensions ● Volume fl ow ranges

Damper without measuring device PPs, round design, with actuator control operating mode: room pressure controller iCM-RP high control precision and responsivity fast and stable room pressure maintenance (< 2 s) option: airtight damper according to DIN

no-minal width

innerØ

volume fl ow VMIN, VMAX, VNOMduring fl ow velocity v

NW[mm]

D[mm]

v=approx. 0,5 m/s

VMIN[m3/h]

v=6 m/sVMAX

[m3/h]

v=approx. 10m/sVNOM

[m3/h]160 161 30 434 589

200 201 50 679 1005

250 251 80 1060 1628

315 316 130 1683 2667

400 401 217 2714 4347

Gesamtlänge = B

D

Einbaulänge = LL1 L1

Gesamtlänge = Einbaulänge = BD

1

d

K

D

model: DK-XXX-P-MM-1 (socket/socket) model: DK-XXX-P-FF-1 (fl ange/fl ange)

The adjoining table shows the volume fl ows within the ap-propriate duct fl ow velocities and nominal widths. In the laboratory (exhaust and supply air) the duct fl ow velocity v = 6 m/s should not be exceeded due to the acoustic noise (fl ow noise). In case of exceeding this value the sound pressure level of < 52 dB(A) demanded by DIN1946, part 7, can only be achieved with extensive sound absorption. The duct fl ow velocity can fell below v = 0,5 m/s because the room pressure will be adjusted and therefore the re-quired fl ow velocity (volume fl ow) is set.

no-minal width

innerØ

dimensionssocket/socket

NW[mm]

D[mm]

W[mm]

L1

[mm]L

[mm]160 161 150 40 70200 201 170 50 70250 251 175 50 75315 316 175 50 75400 401 180 50 80

no-minal width

innerØ

dimensionsfl ange/fl ange

NW[mm]

D[mm]

W[mm]

outerØ

D1 [mm]K

[mm]d

[mm]

quant.

160 161 210 230 200 7 8

200 201 230 270 240 7 8

250 251 235 320 290 7 12

315 316 240 395 350 9 12

400 401 240 480 445 9 16

Page 13: iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

iCM-RPRoom pressure controller • Room pressure monitor

13 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com

Technical data

Generalinternal power supply 230/110 V AC/50/60 Hz/

±15 %current consumption max.

100 mA

power consumption max. 20 VArecovery time 600 msoperating temperature 0 O C bis +55 O Cair humidity max. 80 % relative,

noncondensing

Housing (iCM-RP-control unit)protection class IP 40material plastic with front foilcolor greydimensions (l x w x h) 134 x 80 x 40 mmweight approx. 1,0 kgappliance terminals screw terminal 0,75 mm2

Wall housing with integrated controller iCM-RPprotection class IP 40material steel panelcolor white, RAL 9002dimensions (l x w x h) 150 x 100 x 40 mmweight approx. 1,0 kgappliance terminals screw terminal 1,5 mm2

Relay outputsquantity 1 relay (K1)contact type operating contactswitching voltage max. 250 V ACcontinuous current max. 8 Aquantity 2 relays (K2, K3)contact type two-way/operating contactswitching voltage max. 250 V ACcontinuous current max. 3 A

Analogue output1 output 0(2) to 10 V DC, 10 mA

Analogue input1 input 0(2) to10 V DC, 1 mA

Digital inputs (galvanically isolated)quantity 2 opto-couplerinput voltage max. 24 V DC ±15 %input current max. 10 mA (per input)

Differential pressure transmittermeasurement principle staticpressure range ± 50 Pascalprecision < 0,1 %response time < 10 mssensor burst pressure 500 mbar

Actuator NMQ12, 3 Nm for dampers up to DN280 or rectangular 200x200torque 3 Nmregulating time 3 sec. for 90 °activation direct drive with integrated

power monitioringsolution < 0,5°

Actuator NMQ24, 8 Nm (only usable with additional box -E4)

for dampers from ≥ DN315 or rectangular ≥ 250x250torque 8 Nmregulating time 4 sec. for 90 °activation 2 to 10 V DCadditional external transformer necessary(e. g. additional box -E4)

230 VAC / 24 VAC / 16 VA

solution < 0,8°

Damper, round or rectangular designmaterial polypropylene (PPs)

polypropylene, electroconductive (PPs-el)polyvinyl chloride (PVC)galvanized steelstainless steel

Page 14: iCM-RP...iCM-RP Room pressure controller • Room pressure monitor Technical documentation iCM-RP • status: 01/2015 • subject to alterations • 1 Performance features Microprocessor

iCM-RPRoom pressure controller • Room pressure monitor

14 Technical documentation iCM-RP • status: 01/2015 • subject to alterations • www.schneider-elektronik.com

Dimensions ● Dimensional drawings ● Tender specifi cation

SCHNEIDER Elektronik GmbH phone: +49 (0) 6171 / 88 479 - 0 Industriestraße 4 fax: +49 (0) 6171 / 88 479 - 9961449 Steinbach • Germany e-mail: [email protected]

No

liabi

lty fo

r prin

ting

or e

rror

s or

des

ign

chan

ges

• A

ll rig

hts

rese

rved

© S

CH

NE

IDE

R

housing iCM-RP: top view housing iCM-RP: lateral view

40

Please order for the controller iCM-RP the damper DK with actuator in addition.

-10 Pa

iCM

+-Set Vmax

LOW OKAY

0 25 50

I/O

HIGH

100

150

- + - +

Tender specifi cation iCM-RPRoom pressure controller with integrated microprocessor, static differential pressure transmitter and fully graphic dis-play with numerical signaling of the room pressure actual value. Fast, constant and automatic controlling (< 3 sec) of room under- or overpressure with integrated monitoring function and acoustical alarm as well as provision of two freely programmable relay contacts (e. g. for exceeding the upper and undercut the lower limit value). All setpoints are freely parameterizable via a password secured internal servicing level or laptop with software PC2500 (USB fl ash

drive). Storage of all system data in the fail-safe EEPROM. Suitable for room pressure regulation via room supply air or exhaust air. Controller built-in a compact and shapely wall housing. Direct digital activation of the fast running actuator (< 3 s for 90 °) for exact and vibration-free room pressure regulation. Damper (round or rectangular) made of different material. All cables are pre-assembled ready to plug-in.