    Table o

    INDEX . . . . . . . . . . . . . . . . . . . . . . . . .

    HAZARD IDENTIFICATION . . . . . . .

    INTRODUCTION . . . . . . . . . . . . . . . . .

    IMPORTANT INFORMATION . . . . . . .

    OPERATOR SAFETY GUIDELINES F

    PIPE PREPARATION . . . . . . . . . . . .

    TOOL RATINGS . . . . . . . . . . . . . . . . .

    EXPLANATION OF CRITICAL RADIU

    DIMENSIONS . . . . . . . . . . . . . . . . . . .

    GROOVE DIMENSIONS . . . . . . . . . . .Rigid Radius-Cut Groove Specificati

    Flexible Radius-Cut Groove Specific

    GASKET SELECTION. . . . . . . . . . . . .

  • 8/12/2019 I-300

    3/84

    FLANGE ADAPTERS FOR GROOVE

    IRON PIPE INSTALLATION INSTRUC

    Flange Washer Notes for 3 24 inch

    Sizes Style 341 Vic-Flange Adap

    Style 341 Vic-Flange Adapter 3 1

    Sizes. . . . . . . . . . . . . . . . . . . . . . .

    Style 341 Vic-Flange Adapter 14

    Sizes. . . . . . . . . . . . . . . . . . . . . . .

    VALVE INSTALLATION AND OPERA

    VALVES AND PLUG VALVES . . . . . .

    CHECK VALVE INSTALLATION AND

    Series 317 Check Valve. . . . . . . . . .

    PLUG VALVE INSTALLATION AND O

    Series 365 Vic-Plug Valve (Ductile Ir

    Series 366 Vic-Plug Valve (IPS Ends

    PRODUCT DATA. . . . . . . . . . . . . . . .

    Grooved and Plain-End Pipe CouplinVic-Flange Adapters. . . . . . . . . . . . .

    Fittings . . . . . . . . . . . . . . . . . . . . . . .

    Grooved Pipe Valves . . . . . . . . . . . .

    HELPFUL INFORMATION . . . . . . . .

    English and Metric Conversion Char

    Commercial AWWA Pipe Sizes and

    (ANSI/AWWA C-150) . . . . . . . . . .

    A i W i h f C i

  • 8/12/2019 I-300

    4/84

    The following table provides a listing of proyou need additional copies of any installatio1-800-PICK VIC. NOTE:If two sources of inindex, Victaulic recommends the use of bot

    Product

    Depend-O-Lok Couplings

    FireLock Automatic Sprinkler Products

    FireLock CPVC Piping Products

    FireLock Fire Protection Valves and Accessories

    FIT Products

    Pipe Preparation Tools

    Pressfit Products

    Series 317 AWWA Check Valve

    Series 365 AWWA Vic-Plug Valve(3 12/80 300 mm)

    Series 365 AWWA Vic-Plug Valve(14 18/350 450 mm)

    Series 366 AWWA Vic-Plug Valve

    Series 377 Vic-Plug Balancing Valve

  • 8/12/2019 I-300

    5/84

    Series 782 TA Bypass

    Series 785 TA TBVS Sweated-End Mini CircuitBalancing Valve

    Series 786 TA STAS Soldered-End CircuitBalancing Valve

    Series 787 TA STAD NPT Female Threaded CircuBalancing Valve

    Series 788 TA STAF Flanged-End CircuitBalancing Valve

    Series 789 TA STAG Grooved-End CircuitBalancing Valve

    Series 793 Knife Gate Valve

    Series 797 Knife Gate Valve

    Vic-300 Butterfly Valve

    Style 005 FireLock Rigid Coupling

    Style 07 Zero-Flex Rigid Coupling(1 12/25 300 mm)

    Style 07 Zero-Flex Rigid Coupling(14 24/350 600 mm)

    Style 22 Coupling for Vic-Ring Adapters and

    Shouldered-end Pipe

    Style 31 Coupling for AWWA Ductile Iron

    Style 31 Coupling for Vic-Ring Adapters andShouldered-end Pipe

    Product

  • 8/12/2019 I-300

    6/84

    Style 399 V-Grip Coupling for Plain-end Ductile Iro

    Style 441 Vic-Flange for Stainless Steel

    Style 475 Lightweight, Flexible Stainless SteelCoupling

    Style 489 Rigid Coupling for Stainless Steel(11/4 4/40 100 mm)

    Style 489 Rigid Coupling for Stainless Steel(6 12 and 139,7 318,5 Metric and JIS Sizes)

    Style 606 Rigid Coupling for Copper Tubing

    Style 641 Vic-Flange Adapter for Copper Tubing

    Style 707-IJ Transition Coupling for NPS to JIS

    Style 720 TestMaster II Alarm Test Module

    Style 720 TestMaster II Alarm Test Module withPressure Relief Option

    Style 730 Vic-Strainer Tee-Type

    Style 731-G Suction Diffuser

    Style 732 Wye-Type Vic-Strainer

    Style 733 Venturi Flow Metering Sensor

    Style 734/734S Orifice/Indicator Flow MeteringSystem

    Style 735 Fire Pump Test Meter

    Style 738 TA Portable Differential Meter

    Product

  • 8/12/2019 I-300

    7/84

    Style 994 Vic-Flange Adapter for HDPE

    Style 995 Coupling for Plain-end IPS and MetricHDPE

    Style 997 Transition Coupling for HDPE to Steel

    Style 2970 Aquamine Coupling for Plain-end IPSPVC

    Style 2971 Aquamine Transition Coupling for PlainEnd IPS PVC to Plain-End HDPE

    Style 2972 Aquamine Transition Coupling for PlainEnd IPS PVC to Grooved IPS Steel

    Style HP-70 Rigid Coupling (2 12/50 300 mm

    Style HP-70 Rigid Coupling (14 16/350 400mm)

    Style HP-70ES Rigid Coupling with EndSeal or FirR Gaskets (2 12/50 300 mm)

    Product

  • 8/12/2019 I-300

    8/84

    In

  • 8/12/2019 I-300

    9/84

    HAZARD IDENTIFICATION

    Definitions for identifying various hazard

    This safety alert symbol indicatyou see this symbol, be alert toCarefully read and fully unders

    DANGER

    The use of the word DANGER identifiesan immediate hazard with a likelihood of

    death or serious personal injury if instruc-tions, including recommended precau-tions, are not followed.

    CAUTION

    The use of the word CAUTION identifiespossible hazards or unsafe practices thatcould result in personal injury and productor property damage if instructions, includ-

    ing recommended precautions, are not fol-lowed.

  • 8/12/2019 I-300

    10/84

    INTRODUCTION

    This field assembly and installation handboVictaulic mechanical piping products for AWvides easy reference to proper installation ibook, Victaulic offers the following handboo

    I-100 Installation Instructions for IPS and

    and Aluminum Products I-500 Installation Instructions for Pressfi

    I-600 Installation Instructions for Coppe

    I-800 Installation Instructions for FireLoc

    I-900 Installation Instructions for HDPE

    Additional copies of installation information lic stocking distributors, upon request.

    Always follow good piping practices. Specinal loads, internal loads, performance stand

    exceeded.

    Many applications require recognition of spand the use of safety factors. Qualified engthe Victaulic General Catalog (G-100) and VSelection Guide, when determining require

    NOTIC Victaulic Company maintains a continual policy of

    serves the right to change product specifications,

  • 8/12/2019 I-300

    11/84

    IMPORTANT INFORMATIO

    Victaulic AWWA grooved pipe couplings ariron pipe that is grooved to meet Victaulic sgrooved pipe couplings are for use only witvalves, and related grooved-end componenare not intended for use with plain-end pipe

    Victaulic AWWA plain-end pipe couplings aend ductile iron pipe. Victaulic AWWA size used with grooved-end pipe and/or fittings,IPS size pipe.

    Gaskets for Victaulic AWWA size grooved alubricated for proper assembly. Lubrication installation. A thin coat of Vic-Lube or anoicone or soap based lubricants, is required

    Victaulic gaskets are designed to perform ioperating conditions. As with all installationbetween temperature, continuity of service,

    05.01, Gasket Selection Guide, must be rrecommendations for each application.

  • 8/12/2019 I-300

    12/84

    OPERATOR SAFETY GUID

    1. Read and understand the operatingmanual for the tool.Read the supplied maperforming maintenance on any tool. Becom

    operations, applications, and limitations. Beards. Store the operators manual in a readiadditional copies of any literature, contact V

    2. Secure the tool, power drive, and eqand power drive are fastened securely to th

    3. Prevent accidental start-ups.Place position before plugging the tool into the elepedal control for the power source.

    4. Ground the power source.Make suan internally grounded electrical system.

    5. Operating environment.Do not opehearing protection in noisy shop operations

    6 Wear proper clothing Do not wear u

    NOTIC

    Although Victaulic pipe preparation tools are manimpossible to anticipate the combinations of circufollowing instructions are recommended for safe opways refer to the specific operating and maintenaguidelines.

  • 8/12/2019 I-300

    13/84

    13. Disconnect the power cord before ssonnel should attempt to service tools. Alwabefore servicing or making any adjustments

    14. Always maintain tools.Keep tools cdependable operation. Follow all lubricatingditions to authorized personnel for immedia

  • 8/12/2019 I-300

    14/84

    PIPE PREPARATION

    The grooved piping method is based upon receive the housings keys. The groove servallows ample depth for secure engagementness for full pressure rating.

    Ductile iron pipe must be prepared to Victaproduct style. Preparation may vary accorddimensions, and other factors. Victaulic rec

    with grooved-end AWWA products.

    The outside surface of the pipe, between thsmooth and free from deep pits and swells gasket. All rust, loose scale, oil, grease, dirremoved. Peened surfaces may require rew

    gasket (refer to ANSI/AWWA C-606 or CSA

    WARN Before setting up and operating

    understand the operating and m

    Learn the operation, applicatio

    Failure to follow these instructions

    erty damage, product damage, an

  • 8/12/2019 I-300

    15/84

    TOOL RATINGS

    The following table contains general informare designed for high use shop fabrication,fabrication. For detailed information on toolFor information about maintenance and opeoperating and maintenance instructions maing tools are designed for use on AWWA du

    other IPS materials. Requirements for AWWspecified at the time of order. In additionradius or flexible-radius grooves. This reqtime of order.

    Tool ModelPipe

    Material 3 4 6 8

    VG28GDDuctile

    IronClass 53 56

    Vic-Groover

    DuctileIron

    Class 53 56

    VG824Ductile

    Iron

    VG412Ductile

    IronClass 53

  • 8/12/2019 I-300

    16/84

    EXPLANATION OF CRITICGROOVE DIMENSIONS

    Radius Cut G

    A Dimension The A dimension, or thegroove, identifies the gasket seating area. Ttions, projections, deep pits, and swells fromvide a leak-tight seal for the gasket.

    WARN

    AWWA pipe dimensions and groove dimensions m

    charts on the following pages to ensure proper jo

    Failure to follow these specifications could result in

    joint leakage, and/or joint failure.

    A B

    OD C

    B

    R

    (Exaggerated fo

  • 8/12/2019 I-300

    17/84

    Victaulic groove specifications for cast piperequirements of ANSI/AWWA Standard C-60

    For cast pipe, the groove is cut with a radiusgroove base to reduce stress concentration

    for any pipe OD, regardless of pipe class a

    Standard preparation is with a rigid radius gsions may be used to provide expansion/coance at the joint.

    Rigid Radius Cut Groove

    Exaggerated fo

  • 8/12/2019 I-300

    18/84

    GROOVE DIMENSIONS

    ipe

    Dimensions

    inches(millimeters)

    GrooveW

    idthB

    GrooveDiameter

    C

    Radius

    R

    M

    inimum

    Allowable

    W

    allThicknessT

    asic

    Ma

    x.

    Min

    .

    Max.

    Min.

    CastIron

    Ductile

    Iron

    375

    0.4

    06

    0.

    359

    3.

    723

    3.

    703

    0.

    120

    0.

    320

    0.

    310

    9,

    5)

    (10

    ,3)

    (9,

    1)

    (94,

    6)

    (94,1

    )

    (3,

    1)

    (8,

    1)

    (7,

    9)

    375

    0.4

    06

    0.

    359

    4.

    563

    4.

    543

    0.

    120

    0.

    350

    0.

    320

    9,

    5)

    (10

    ,3)

    (9,

    1)

    (115,

    9)

    (115,4

    )

    (3,

    1)

    (8,

    9)

    (8,

    1)

    375

    0.4

    06

    0.

    359

    6.

    656

    6.

    636

    0.

    120

    0.

    380

    0.

    340

    9,

    5)

    (10

    ,3)

    (9,

    1)

    (169,

    1)

    (168,6

    )

    (3,

    1)

    (9,

    7)

    (8,

    6)

    500

    0.5

    31

    0.

    484

    8.

    781

    8.

    756

    0.

    145

    0.

    410

    0.

    360

    2,

    7)

    (13

    ,5)

    (12,

    3)

    (223,

    0)

    (222,4

    )

    (3,

    7)

    (10,

    4)

    (9,

    1)

    500

    0.5

    31

    0.

    484

    10.

    813

    10.

    78

    8

    0.

    145

    0.

    440

    0.

    380

    2,

    7)

    (13

    ,5)

    (12,

    3)

    (274,

    7)

    (274,0

    )

    (3,

    7)

    (11,

    2)

    (9,

    7)

    500

    0.5

    31

    0.

    484

    12.

    906

    12.

    87

    6

    0.

    145

    0.

    480

    0.

    400

    2,

    7)

    (13

    ,5)

    (12,

    3)

    (327,

    8)

    (327,1

    )

    (3,

    7)

    (12,

    2)

    (10,

    2)

  • 8/12/2019 I-300

    19/84

    n

    Pipe

    Dimensions

    inches(millimeters)

    GrooveW

    idthB

    GrooveDiameter

    C

    Radius

    R

    M

    inimum

    Allowable

    W

    allThicknessT

    asic

    Ma

    x.

    Min

    .

    Max.

    Min

    .

    Cast

    Iron

    Ductile

    Iron

    375

    0.4

    06

    0.

    359

    3.

    723

    3.

    703

    0.

    120

    0.

    320

    0.

    310

    9,

    5)

    (10

    ,3)

    (9,

    1)

    (94,

    6)

    (94,1

    )

    (3,

    1)

    (8,

    1)

    (7,

    9)

    375

    0.4

    06

    0.

    359

    4.

    563

    4.

    543

    0.

    120

    0.

    350

    0.

    320

    9,

    5)

    (10

    ,3)

    (9,

    1)

    (115,

    9)

    (115,4

    )

    (3,

    1)

    (8,

    9)

    (8,

    1)

    375

    0.4

    06

    0.

    359

    6.

    656

    6.

    636

    0.

    120

    0.

    380

    0.

    340

    9,

    5)

    (10

    ,3)

    (9,

    1)

    (169,

    1)

    (168,6

    )

    (3,

    1)

    (9,

    7)

    (8,

    6)

    500

    0.5

    31

    0.

    484

    8.

    781

    8.

    756

    0.

    145

    0.

    410

    0.

    360

    2,

    7)

    (13

    ,5)

    (12,

    3)

    (223,

    0)

    (222,4

    )

    (3,

    7)

    (10,

    4)

    (9,

    1)

    500

    0.5

    31

    0.

    484

    10.

    813

    10.

    78

    8

    0.

    145

    0.

    440

    0.

    380

    2,

    7)

    (13

    ,5)

    (12,

    3)

    (274,

    7)

    (274,0

    )

    (3,

    7)

    (11,

    2)

    (9,

    7)

    500

    0.5

    31

    0.

    484

    12.

    906

    12.

    87

    6

    0.

    145

    0.

    480

    0.

    400

    2

    7 )

    ( 1 3

    5 )

    ( 1 2

    3 )

    ( 3 2 7

    8 )

    ( 3 2 7 1

    )

    ( 3

    7 )

    ( 1 2

    2 )

    ( 1 0

    2 )

  • 8/12/2019 I-300

    20/84

    GASKET SELECTION

    Many factors must be considered for optimject gaskets to temperatures beyond the retemperatures will degrade gasket life and p

    The services listed below are general servic

    only to Victaulic gaskets. Recommendationessarily imply compatibility of the coupling components for the same service. Always rSelection Guide (05.01) for gasket service r

    NOTE:These recommendations do not app

    ber-lined products. Refer to the applicable pfor recommendations.

    CAUT To ensure maximum gasket performance, always s

    service.

    Failure to select the proper gasket for the service mayage.

    Standard Gaskets for AWWA Size P

    Grade Temp. Range Compound

    Color

    Code

    S

    20F (29C)to

    Nit ilRed

  • 8/12/2019 I-300

    21/84

    SPACING REQUIREMENTSPIPING SYSTEMS

    Since the grooved piping method incorporaconsideration must be given to external dimNOTE:Allowance for insulation, when neceexamples.

    Recommended Minimum Pipe Spacing

    To allow for easy installation, insulation, and

    given to proper spacing between pipelinesplings are externally mounted housings thaaccess space to tighten the nuts. In additiointerference between piping and adjacent c

    Y + 20%

    Y

    Example with Bolt Pads Facing Each Other

    Illustrations are exagg

  • 8/12/2019 I-300

    22/84

    INSTALLATION TO ACHIEVLINEAR MOVEMENT CAPAFLEXIBLE SYSTEMS

    To achieve maximum expansion/contractionbe created by cutting flexible radius groovemust be installed with proper spacing betwbrief overview of methods to accommodate

    tion 26, Design Data, of the G-100 General

    For maximum expansion, pipe ends musthe coupling.

    1. Vertical systems can be installed as t

    couplings and using the weight of the pipe

    2. Anchor the system at one end, and inguides. Cap the system, pressurize it to fullyother end with the pipe ends fully gapped.

    3. Install the joints using a come-along

    tion, then secure the pipe to maintain the op

    For maximum contraction, pipe ends mu

    1. In vertical systems, stack the pipe byends, then anchor the pipe to maintain the

    2. In horizontal systems, install the jointscome-along to draw the pipe ends togethin position.

  • 8/12/2019 I-300

    23/84

    PIPING SUPPORT FOR RIGFLEXIBLE SYSTEMS

    Similar to other piping systems, abovegrouwith grooved pipe mechanical couplings repipes and equipment. The support or hangjoints, piping, and other components. In adallow pipeline movement, where required, a

    such as drainage. The designer must also cflexible systems while designing a support

    The tables below list the suggested maximuhorizontal, straight runs of grooved AWWA similar liquids.

    Rigid Systems

    Style 31 Couplings on ductile iron pipe that support spacing as flanged, ductile-iron pip

    with standard industry practice (i.e. MSS SP

    Ductile iron pipe that conveys water or sspaced up to 15 feet (4,6 m) maximum be(80 100 mm) sizes. For 6 36 inch (150

    NOTIC These values are not intended to be used as specifi

    apply where critical calculations are made or wheports.

    Victaulic Company is not responsible for system dsponsibility for systems that are designed imprope

  • 8/12/2019 I-300

    24/84

    GROOVED PRODUCT INSTGUIDELINES

    The following instructions are a general guipiping products. These instructions must beassembly.

    1. Always check the supplied gasket to service. Refer to page 13 for details.

    2. Valve bodies, discs, and other wettedwith the material flowing through the system

    literature, or contact Victaulic for details.

    3. Always read the operating and maintepipe preparation tools.

    4. The outside diameter and grooving d

    lished tolerances; these tolerances are subability. Refer to pipe preparation specificati

    5. Rigid, angle-pad couplings must havesides until metal-to-metal contact at the bol

    WARN Depressurize an

    to install, remov

    Failure to follow thpersonal injury, pr

    leakage, and/or jo

  • 8/12/2019 I-300

    25/84

    INSTALLATION INSPECTIO

    Proper Installation

    Proper pipe preparation and coupling instaperformance THE FOLLOWING CONDITIO

    WARN

    Always inspect

    properly installe

    Undersized or o

    grooves, eccent

    unacceptable. A

    before attemptin

    Failure to follow th

    personal injury, pro

    failure.

    PROPER INSTA

    G

    (Exaggerated fo

  • 8/12/2019 I-300

    26/84

    Installations with Undersize

    NOT ACCEPTABLE

    When the OD of the pipe or fitting is below tings key sections is considerably lowered.WORKING PRESSURE FOR THE JOINT.

    Additionally, there is little or no added compgap G between the pipe and the housing These factors can contribute to reduced ga

    Installations with Oversized NOT ACCEPTABLE

    (Exaggerated

    Undersized P

    Key

    G

    O i d Pi

  • 8/12/2019 I-300

    27/84

    Installations on Pipe with De

    NOT ACCEPTABLE

    A groove that is too deep will allow the couhave full key engagement (Figure 1 above)

    icantly reduced key engagement (Figure 2 as the conditions described in the previousFittings section. Additionally, cut grooving result in insufficient wall thickness under the

    Installations on Pipe with EcNOT ACCEPTABLE

    (Exaggerated for clarity)

    Pipe with Deep Grooves

    Figure 1

    SmallSpace

    KeyShoulder

    Eccentric G

    Key

  • 8/12/2019 I-300

    28/84

    metal contact. The only exceptions are coufied. These torque values must be achievedthat the bolt pads will have full metal-to-metconcerning an installation, contact Victaulic

    If the bolt pads are not in full metal-to-me

    1. Make sure coupling keys are engagenot rest on the outside surface of the pipe.

    2. Make sure the bolts have been tighte

    3. Make sure the gasket is not pinched. immediately.

    4. Make sure an oversized pipe or fitting

    5. Make sure the groove conforms to Vicshallow, groove the pipe to Victaulic specificard that section of pipe, and groove anoth

    Always re-inspect joints before and after theble failure. Look for gaps at the bolt pads aders. If any of these conditions exist, deprequestionable joints.

    NOTIC A SUCCESSFUL INITIAL SYSTEM PRESSURE TEST

    AND IS NOT A GUARANTEE OF LONG-TERM PERFO Victaulic will not assume any liability for pipe joinstallers failure to follow Victaulic Companys ins

    As with any pipe joining method, success is deteadherence to the instructions found in this hand

  • 8/12/2019 I-300

    29/84

    Couplings fo

    Grooved andPlain-End

    Ductile Iron Installation

    Instructions

  • 8/12/2019 I-300

    30/84

  • 8/12/2019 I-300

    31/84

    4. JOIN PIPE ENDS:Align andbring the two pipe ends together.Slide the gasket into position, andmake sure it is centered between thegrooves. Make sure no portion of the

    gasket extends into the groove oneither pipe.

    5. INSTALL HOUSINGS:Installthe housings over the gasket. Make

    fit

    fl

  • 8/12/2019 I-300

    32/84

    * Standard, rigid radius-cut grooves provide no deflection o

    Allowable Pipe-End Separation and

    Deflection for Style 31 Couplings F

    Radius-Cut Grooved, Cast (Gray/Du

    Pipe Size Allowable

    Pipe-End

    Separation *

    inches (mm)

    Deflectio

    Nominal

    Diameter inches

    (mm)

    Degrees Per

    Coupling *

    3 0 0.0941 - 21

    80 0 2,4

    4 0 0.0941 - 8

    100 0 2,4

    6 0 0.0940 - 47

    150 0 2,4

    8 0 0.0940 - 36

    200 0 2,4

    10 0 0.156 0 - 48250 0 4,0

    12 0 0.1560 - 41

    300 0 4,0

    Style 31 Helpful Information

    Pipe Size

    Socket Size

    inches

    Nominal Diameter

    inches (mm)

    3 7/8(80)

    411/16

    (100)

    6

    St l 31

  • 8/12/2019 I-300

    33/84

    Style 31Coupling 14 36 inch (350 900 mm) Size

    Style 31 Couplings, in sizes 14 36 inchesegments to ease handling and ensure c

    WARN

    Read and understand all instructions before attem

    products.

    Depressurize and drain the piping system before

    Victaulic piping products.

    Wear safety glasses, hardhat, and foot protection

    Failure to follow these instructions could result in s

    installation, and/or property damage.

  • 8/12/2019 I-300

    34/84

    2. ASSEMBLE SEGMENTS:Assemble the segments loosely intotwo equal halves, as shown above.Make sure the tongue and recess fea-tures mate properly (tongue-to-recess). Allow slight clearance

    between the segments to easeassembly onto the pipe.

    t

    t

    Tongue Recess

    Exaggerated for clarity

  • 8/12/2019 I-300

    35/84

    6. INSTALL FIRST SEGMENTASSEMBLY:Install one of the pre-assembled halves over the gasket.Make sure the housings keys engagethe grooves properly on both pipes.

    t

    Tongue Recess

    Exaggerated for clarity

  • 8/12/2019 I-300

    36/84

    Style 307

  • 8/12/2019 I-300

    37/84

    Style 307Coupling for Transitions from Grooved IPS SPipe 3 12 inch (80 300 mm) Sizes

    1. CHECK PIPE ENDS: The out-

    WARN

    Read and understand all instructions before attem

    Depressurize and drain the piping system before attaulic piping products.

    Wear safety glasses, hardhat, and foot protection.Failure to follow these instructions could result in serlation, and/or property damage.

  • 8/12/2019 I-300

    38/84

    4. JOIN PIPE ENDS:Align andbring the AWWA and IPS steel pipeends together. NOTE:Make sure noportion of the gasket extends into thegroove on either pipe.

    t

    Exaggerated for clarity

    Assembly Lug

  • 8/12/2019 I-300

    39/84

    7. TIGHTEN NUTS:Tighten all

    nuts evenly by alternating sides untilmetal-to-metal contact occurs at theangle bolt pads. NOTE:It is importantto tighten all nuts evenly to preventgasket pinching. Make sure there isequal offset at each bolt pad, as

    shown above.

    WARNING

    Angle Pad

    Contact

    Offsets

    OffsetsEqual offsets

    at both pairsof bolt pads

    Exaggerated for clarity

    Style 397

  • 8/12/2019 I-300

    40/84

    Style 397VGrip Coupling for Plain-End by Grooved4 8 inch (100 200 mm) Sizes

    The Style 397 VGrip Coupling is designend ductile iron pipe. DO NOT use this sty

    C900 PVC, HDPE, or cement pipe.

    WARN

    Read and understand all instructions before attem

    Depressurize and drain the piping system before attaulic piping products.

    Wear safety glasses, hardhat, and foot protection.Failure to follow these instructions could result in serlation, and/or property damage.

  • 8/12/2019 I-300

    41/84

    3. MARK PLAIN-END PIPE:Using a measuring tape and a bright-colored marker or paint stick, place amark 21/8inches (54 mm) from thepipe end. Make at least four of these

    marks equally-spaced around the cir-cumference of each pipe.

    4. CHECK GASKET AND LUBRI-CATE:Check the gasket to make

    v

    t

  • 8/12/2019 I-300

    42/84

    6. INSTALL HOUSINGS:Installthe housings over the gasket. NOTE:The housings are clearly markedGrooved End and Plain End. Makesure the housings keys engage the

    groove and that the plain end alignswith the pipe marks. Make sure thegasket remains in position and thatthe tongue and recess features of thehousings mate properly (tongue-to-recess).

    w

    ff

    WARNING

    Make sure the gasket does not becomerolled or pinched while installing the hous-ings.

    Collapsible washers MUST be used for as-sembly of all Style 397 Couplings.

    Failure to follow these instructions couldcause joint failure, resulting in serious per-

  • 8/12/2019 I-300

    43/84

    Allowable Pipe-End

    Separation for Style 397

    VGrip Couplings

    Pipe Size

    Allowable Pipe-End

    Separation *

    inches (mm)

    Nominal

    Diameter

    inches (mm)

    4 0.660 0.800

    100 16,8 20,3

    6 0.720 0.800150 18,3 20,3

    8 0.550 0.680200 14,0 17,3

    * AWWA plain-end couplings, when pressurized,

    will allow the pipe to separate slightly as thegrips set into the pipe. For properly assembled

    and torqued couplings, this separation should

    not exceed 1/4 inch (6,4 mm). This should be

    considered for installations in tightly confined

    areas.

    Style 397 VGrip Couplings are not designed toprovide linear or angular movement.

    Re-Use Instructions for Style

  • 8/12/2019 I-300

    44/84

    1. Check the condition of the teeth. The proper assembly. Teeth must be sharp. DOloose, or deformed teeth. Couplings may bone time after the original installation.

    2. Follow steps 1 6 of the instructions s

    3. New collapsible washers are recommously installed collapsible washers can be u

    the specifications shown in the Style 397 Tobelow. DO NOT use lubricant on bolt threpreviously installed collapsible washers.

    4. Follow the nut tightening sequence in

    WARN Depressurize and drain the piping system before a

    Style 397 VGrip Couplings.

    Victaulic Style 397 Couplings may be disassembleinstallation. Additional assemblies of couplings wgripping strength.

    Failure to follow this instruction could result in joint fadamage.

    Style 397 Torque

    Requirements for Re-Use

    Pipe Size

  • 8/12/2019 I-300

    45/84

    Lubricant or silicone lubricant to thegasket lips and exterior

  • 8/12/2019 I-300

    46/84

    gasket lips and exterior.

    CAUTION

    Always use a compatible lubricant to pre-vent the gasket from pinching/tearing dur-ing installation.

    Failure to follow this instruction could result

    in joint leakage.

    WARN

    Wear protective gloves w

    housings contain sharp teeFailure to follow this instruct

    WARN

    Victaulic Style 399 Couplin

    6. LUBRICATE BOLT THREADS,NUTS AND WASHERS: When using

  • 8/12/2019 I-300

    47/84

    NUTS, AND WASHERS: When usingnewcollapsible washers, lubricantcan be used on the bolt threads, nuts,

    and washers to reduce the torquerequired to fully collapse the washers.

    7. Install the bolts and collapsiblewashers. Thread the nuts finger-tightonto the bolts. To ensure an even gapbetween the housings and to prevent

    gasket pinching, tighten the nutsevenly by alternating sides, as shownin Figure A above. Tighten the nutsuntil the collapsible washers are fully

    t

    Figure A

    1

    3

    4

    2

    Style 399 Helpful

    I f ti

  • 8/12/2019 I-300

    48/84

    Re-Use Instructions for Style

    1. Check the condition of the teeth. The proper assembly. Teeth must be sharp. DOloose, or deformed teeth. Couplings may bone time after the original installation

    Information

    Pipe Size

    Socket Sizeinches

    Nominal Diameterinches (mm)

    4 7/8(100)

    611/16

    (150)

    8 11/4(200)

    WARN

    Depressurize and drain the piping system before a

    Style 399 VGrip Couplings. Victaulic Style 399 Couplings may be disassemble

    installation. Additional assemblies of couplings wgripping strength.

    Failure to follow this instruction could result in joint fadamage.

    Flange Adap

  • 8/12/2019 I-300

    49/84

    Flange Adap

    for GroovedDuctile Iron

    InstallationInstructions

    Style 341 Vic Flan

    FLANGE WASHER NOTES (80 600 MM) SIZES

  • 8/12/2019 I-300

    50/84

    (80 600 MM) SIZES

    Style 341 Vic-Flange Adapter

    Style 341 Vic-Flange Adapters require a smflange face for proper sealing. Some applicAdapter is otherwise well suited, do not prosuch cases, it is recommended that a metabetween the Vic-Flange Adapter and the msealing surface.

    A. When mating to a serrated flange against the serrated flange. The Vic-Flangebetween the Vic-Flange Adapter and the fla

    B. When mating to a rubber-faced, wawasher should be placed between the valv

    C. When mating to a rubber-faced flanbe placed between the Vic-Flange Adapter

    D. When mating AWWA cast flanges twasher should be placed between two Vic-FVic-Flange Adapter (i.e. flanged valve), a flathat flange. The Vic-Flange washer must thegasket and the Vic-Flange Adapter.

    Transition rings, rather than Vic-Flange w

    Style 741 to Style 341 Vic-Flange Adapte

    mm). The lap joints of the Style 341 must

    St l 741 h ti th l i

    Style 341Vic Flange Adapter 3 12 inch (80 300 m

  • 8/12/2019 I-300

    51/84

    Vic-Flange Adapter 3 12 inch (80 300 m

    1. CHECK PIPE ENDS:The out-side surface of the pipe between the

    WARN

    Read and understand all instructions before attem

    Depressurize and drain the piping system before attaulic piping products.

    Wear safety glasses, hardhat, and foot protection.

    Failure to follow these instructions could result in serlation, and/or property damage.

  • 8/12/2019 I-300

    52/84

    3. INSTALL GASKET:Install thegasket over the pipe end. Make surethe gasket is positioned properly, asshown above. NOTE:The lettering onthe outside of the gasket must facethe gasket pocket of the Style 341Vic-Flange Adapter. When installedcorrectly, the lettering on the gasketwill not be visible.

    w

    Vic-

    Flange

    Proper Gasket Positioning

    Mating

    Flange

    Exaggerated for Clarity(Exaggerated for clarity)

    tV

  • 8/12/2019 I-300

    53/84

    6. MATE VIC-FLANGE ADAPTERAND MATING FLANGE:Join the Vic-Flange Adapter with the matingflange by aligning the bolt holes.Thread standard flange nuts finger-

    tight onto the two mating bolts.

    7. INSTALL REMAINING BOLTS/NUTS:Insert a standard flange bolt

    Tt

    t

    Style 341 Helpful Information

  • 8/12/2019 I-300

    54/84

    Total bolts required are to be supplied by the installer. Bol

    tions. Longer bolts are required when Vic-Flange Adapter

    NOTE:Style 341 Vic-Flange Adapters for AWWA ductile

    iron pipe that is grooved to Victaulic specifications. Cons

    at the joint.

    Pipe Size

    Number of BoltsRequired

    Boltinc

    Nominal Diameterinches (mm)

    34 5/8

    (80)

    48 5/8

    (100)

    6 8 3/4x(150)

    88 3/4x

    (200)

    1012 7/8

    (250)

    12 12 7/8(300)

    The shaded area of the mating face (shown atbe free from gouges, undulations, or deformittype for proper sealing.

    Style 341Vic-Flange Adapter 14 24 inch (350 600

  • 8/12/2019 I-300

    55/84

    g p (

    1. CHECK PIPE ENDS:The out-side surface of the pipe, between thegroove and the pipe end, must be

    smooth and free from deep pits andswells to provide a leak-tight seal forthe gasket. All rust, loose scale, oil,grease, dirt, and cutting particlesmust be removed. Peened surfacesmay require rework to provide a leak-

    tight seal for the gasket (refer to ANSI/AWWA C-606 or CSA B242).

    WARN

    Read and understand all instructions before attem

    Depressurize and drain the piping system before attaulic piping products.

    Wear safety glasses, hardhat, and foot protection.

    Failure to follow these instructions could result in serlation, and/or property damage.

    NOTICE

    C O

  • 8/12/2019 I-300

    56/84

    flj

    CAUTION

    Always use a compatible lubricant to pre-vent the gasket from pinching/tearing dur-ing installation.

    Failure to follow this instruction could resultin joint leakage.

    Vic-Flange

    Proper Gasket Positioning

    MatingFlange

    Exaggerated for Clarity(Exaggerated for clarity)

  • 8/12/2019 I-300

    57/84

  • 8/12/2019 I-300

    58/84

  • 8/12/2019 I-300

    59/84

    CHECK VALVE INSTALLAT

  • 8/12/2019 I-300

    60/84

    Series 317 Check Valve

    The Series 317 Check Valve is a grooved

    508 requirements for water and wastewat

    Style 31 Couplings can directly connect th

    is grooved to ANSI/AWWA C-606 rigid or

    Style 341 Vic-Flange Adapters can be usValve to pipe that is grooved to ANSI/AWW

    groove specifications.

    Style 307 Transition Couplings can be use

    Check Valve to IPS pipe.

    For installing Series 317 Check Valves intplings, Style 341 Vic-Flange Adapters, or

    the instructions supplied with the product

    Refer to the Series 317 AWWA Check Va

    structions (I-317) manual for information r

    accessory kit installation, etc.

    PLUG VALVE INSTALLATIO

  • 8/12/2019 I-300

    61/84

    When directly connecting an end cap to a b

    for pressure relief. If the ball valve is openeend cap is attached, the space between thpressurized. A sudden release of energy cawhile the space behind it is pressurized. PRTHROUGH THE TAP BEFORE ATTEMPTIN

    Series 365 Vic-Plug Valve (Ductile Iron En

    The Series 365 Vic-Plug Valve is an ecceAWWA standards and is used primarily fo

    vices.

    Style 31 Couplings can directly connect t

    that is grooved to ANSI/AWWA C-606 rigi

    tions.

    Style 341 Vic-Flange Adapters can be use

    Valve to pipe that is grooved to ANSI/AWW

    groove specifications.

    When directly connectingend cap for pressure reli

    Pressure must be ventedthe cap.

    Failure to follow these instsonal injury.

    Pro

  • 8/12/2019 I-300

    62/84

    The following information contains center-tolar overall dimensions for couplings, flangecurrent Victaulic publication for complete ducts not shown.

    GROOVED AND PLAIN-EN

    St le 31 Co pling

  • 8/12/2019 I-300

    63/84

    Style 31 Coupling

    Pipe Size

    Y Dime

    inches (m

    Nominal Diameter

    inches (mm)

    Actual Outside

    Diameter

    inches

    (mm)

    3 3.960 7.6380 100,6 193,8

    4 4.800 9.20100 121,9 233,7

    6 6.900 11.19150 175,3 284,2

    8 9.050 14.33

    200 229,9 364,0

    10 11.100 16.44250 281,9 417,6

    12 13.200 19.16300 335,3 486,7

    14 15.300 21.96

    350 388,6 557,816 17.400 23.96400 442,0 608,6

    18 19.500 26.33450 495,3 668,8

    20 21.600 28.69500 548,6 728,7

    24 25.800 33.06600 655,3 839,7

    30 32.000 39.39750 762 0 1000 5

    Style 307 Transition Coupling

    Pipe Size

  • 8/12/2019 I-300

    64/84

    Style 397 Grooved-End x Plain-End Coupling

    Style 399 Plain-End x Plain-End Coupling

    Y Dimension

    inches (mm)

    NominalDiameter

    inches

    Actual Outside

    Diameterinches

    (mm)

    3 3.960 7.3880 100,6 187,5

    4 4.800 9.00

    100 121,9 228,66 6.900 11.13

    150 175,3 282,7

    8 9.050 11.13200 229,9 352,6

    10 11.100 16.50250 281,9 419,1

    12 13.200 18.94300 335,3 481,1

    Pipe Size

    Y Dimens

    inches (mm

    Nominal

    Diameter

    inches

    Actual Outside

    Diameter

    inches

    (mm)

    4 4.800 9.67100 121,9 245,6

    6 6.900 12.44150 175 3 316 0

    VIC-FLANGE ADAPTERS

    Style 341 Vic Flange Adapter

  • 8/12/2019 I-300

    65/84

    Style 341 Vic-Flange Adapter

    Pipe Size

    A Dimension

    inches (mm)

    Nominal

    Diameter

    inches

    Actual Outside

    Diameter inches

    (mm)

    3 3.960 8.4480 100,6 214,4

    4 4.800 9.94100 121,9 252,5

    6 6.900 12.00150 175,3 304,8

    8 9.050 14.63200 229,9 371,6

    10 11.100 17.13250 281,9 435,1

    12 13.200 20.13300 335,3 511,3

    14 15.300 24.63350 388,6 625,6

    16 17.400 27.25400 442,0 692,2

    18 19.500 29.13450 495,3 739,9

    20 21.600 31.63500 548,6 803,4

    24 25.800 36.13600 655,3 917,7

    FITTINGS

    No 100-C 90 Long Radius Elbow

  • 8/12/2019 I-300

    66/84

    No. 100-C 90 Long Radius Elbow

    No. 10-C 90

    ElbowNo. 11-C 45Elbow

    No. 12-C 221/2Elbow

    No. 13-C 111/4Elbow

    Pipe Size

    No.

    100-C

    90Long

    Radius

    Elbow

    No.10-C

    90

    Elbow

    1

    4

    E

    Nominal

    Dia.

    inches

    (mm)

    Actual

    Outside Dia.

    inches

    (mm)

    C to E

    inches

    (mm)

    C to E

    inches

    (mm)

    C

    in

    (m

    3 3.960 7.75 5.50 380 100,6 196,9 139,7 7

    4 4.800 9.00 6.50 4100 121,9 228,6 165,1 1

    6 6.900 11.50 8.00 5150 175,3 292,1 203,2 1

    8 9.050 14.00 9.00 5200 229,9 355,6 228,6 1

    10 11.100 16.50 11.00 6250 281,9 419,1 279,4 1

    12 13.200 19.00 12.00 7300 335,3 482,6 304,8 1

    14 15.300 21.50 14.00 7350 388,6 546,1 355,6 1

    No. 10-BS 90Elbow

    No. 11-BS 45Elbow

    No. 20-BS Tee

  • 8/12/2019 I-300

    67/84

    Pipe Size No. 10-BS90 Elbow No. 1145 El

    Nominal

    Dia.

    mm

    (inches)

    Actual

    OutsideDia.

    mm

    (inches)

    C to E

    mm

    (inches)

    C to

    mm

    (inch

    80 98 165,1 1303 3.860 6.50 5.12

    100 118 179,8 1404 4.640 7.08 5.5

    150 170 220,0 1606 6.690 8.66 6.30

    C to E

    CtoE

  • 8/12/2019 I-300

    68/84

    No. 20-C Tee

    No. 33-C Wye

    No. 35-C Cross

    No. 30-C 45Lateral

    No. 60-C Cap

    Pipe Size

    No. 20-C

    Tee No. 33-C Wye

    Nominal

    Dia.

    inches(mm)

    Actual

    Outside

    Dia.

    inches(mm)

    C to E

    inches(mm)

    C to LE

    inches(mm)

    C to SE

    inches(mm)

    3 3.960 5.50 5.50 5.5080 100,6 139,7 139,7 139,7

    4 4.800 6.50 6.50 3.00100 121,9 165,1 165,1 76,2

    6 6.900 8.00 8.00 3.50150 175,3 203,2 203,2 88,9

    8 9.050 9.00 9.00 4.50200 229,9 228,6 228,6 114,3

    10 11.100 11.00 11.00 5.00250 281,9 279,4 279,4 127,0

    12 13.200 12.00 12.00 5.50300 335,3 304,8 304,8 139,7

    14 15.300 14.00 14.00 6.00350 388,6 355,6 355,6 152,4

    E

    No. 20-C

    Cto

    LE

    C toLE

    C toSE

    No. 30-C

    No. 21-C Bullhead Tee

    SIZE Nominal Diameter

    inches (mm)

    C to EOR

    inches (mm)

    C to EO

    inches (m

  • 8/12/2019 I-300

    69/84

    ( ) ( ) (

    4 X 4 X 6 + +100 X 100 X 150 + +

    6 X 6 X 8 8.00 8.00150 X 150 X 200 203,2 203,2

    8 X 8 X 10 11.00 11.00200 X 200 X 250 279,4 279,4

    10 X 10 X 12 + +

    250 X 250 X 300 + +

    No. 25-C Reducing Tee

    No. 30-CR 45Reducing Lateral

    No. 35-CR Reducing Cross

    Size

    Nominal Diameter

    inches (mm)

    No. 25-C

    Red. Tee

    C to EOR

    inches

    (mm)

    C to EOB

    inches

    (mm)

    4 X 3 6.50 6.50100 X 80 165,1 165,1

    6 X 3 8.00 8.00150 X 80 203,2 203,2

    X 4 8.00 8.00X 100 203,2 203,2

    C to

    No. 2

    No. 25-C Reducing Tee

    C to

  • 8/12/2019 I-300

    70/84

    16 X 6 15.00 15.00400 X 150 381,0 381,0

    X 8 15.00 15.00X 200 381,0 381,0

    X 10 15.00 15.00

    X 250 381,0 381,0X 12 15.00 15.00X 300 381,0 381,0

    X 14 15.00 15.00X 350 381,0 381,0

    18 X 8 13.00 15.50450 X 200 330,2 393,7

    X 10 13.00 15.50X 250 330,2 393,7

    X 12 13.00 15.50X 300 330,2 393,7

    X 14 16.50 16.50X 350 419,1 419,1

    X 16 16.50 16.50X 400 419,1 419,1

    20 X 6 14.00 17.00500 X 150 355,6 431,8

    No. 30-CR 45Reducing Lateral

    No. 35-CR Reducing Cross

    Size

    Nominal Diameter

    inches (mm)

    No. 25-C

    Red. Tee

    C to EOR

    inches

    (mm)

    C to EOB

    inches

    (mm)

    No. 2

    No. 25-C Reducing Tee

    C to

  • 8/12/2019 I-300

    71/84

    30 X 6 18.00 23.00750 X 150 457,2 584,2

    X 8 18.00 23.00X 200 457,2 584,2

    X 10 18.00 23.00

    X 250 457,2 584,2X 12 18.00 23.00X 300 457,2 584,2

    X 14 18.00 23.00X 350 457,2 584,2

    X 16 18.00 23.00X 400 457,2 584,2

    X 18 18.00 23.00X 450 457,2 584,2

    X 20 18.00 23.00X 500 457,2 584,2

    X 24 25.00 25.00X 600 635,0 635,0

    36 X 8 20.00 26.00900 X 200 508,0 660,4

    X 10 20.00 26.00X 250 508,0 660,4

    No. 30-CR 45Reducing Lateral

    No. 35-CR Reducing Cross

    Size

    Nominal Diameter

    inches (mm)

    No. 25-C

    Red. Tee

    C to EOR

    inches

    (mm)

    C to EOB

    inches

    (mm)

    No. 2

    E t

    N 5

  • 8/12/2019 I-300

    72/84

    No. 50-C Concentric Reducer

    No. 51-C Eccentric Reducer

    No. 10-CR 90Reducing Elbow

    No. 100-CR 90Long Radius

    Reducing Elbow

    Size

    Nominal Diameter

    inches (mm)

    No. 50-C

    Conc. Red.

    No. 51-C

    Ecc. Red.

    E to E

    inches

    (mm)

    E to E

    inches

    (mm)

    4 X 3 7.00 7.00100 X 80 177,8 177,8

    6 X 3 9.00 9.00150 X 80 228,6 228,6

    X 4 9.00 9.00X 100 228,6 228,6

    8 X 3 11.00 11.00200 X 80 279,4 279,4

    X 4 11.00 11.00X 100 279,4 279,4

    X 6 11.00 11.00X 150 279,4 279,4

    10 X 4 12.00 12.00250 X 100 304,8 304,8

    X 6 12.00 12.00X 150 304,8 304,8

    No. 5

    C

    No. 1

    E t

    No 5

  • 8/12/2019 I-300

    73/84

    18 X 8 19.00 19.00450 X 200 482,6 482,6

    X 10 19.00 19.00X 250 482,6 482,6

    X 12 19.00 19.00X 300 482,6 482,6

    X 14 19.00 19.00X 350 482,6 482,6

    X 16 19.00 19.00X 400 482,6 482,6

    20 X 8 20.00 20.00500 X 200 508,0 508,0

    X 10 20.00 20.00X 250 508,0 508,0

    X 12 20.00 20.00X 300 508,0 508,0

    No. 50-C Concentric Reducer

    No. 51-C Eccentric Reducer

    No. 10-CR 90Reducing Elbow

    No. 100-CR 90Long Radius

    Reducing Elbow

    Size

    Nominal Diameter

    inches (mm)

    No. 50-C

    Conc. Red.

    No. 51-C

    Ecc. Red.

    E to E

    inches

    (mm)

    E to E

    inches

    (mm)

    No. 5

    C

    No. 1

    E t

    No 5

  • 8/12/2019 I-300

    74/84

    30 X 6 - -750 X 150 - -

    X 8 + +X 200 + +

    X 10 + +X 250 + +

    X 12 + +X 300 + +

    X 14 + +X 350 + +

    X 16 + 30.00X 400 + 762,0

    X 18 + 30.00X 450 + 762,0

    X 20 30.00 30.00X 500 762,0 762,0

    No. 50-C Concentric ReducerNo. 51-C Eccentric Reducer

    No. 10-CR 90Reducing Elbow

    No. 100-CR 90Long Radius

    Reducing Elbow

    Size

    Nominal Diameter

    inches (mm)

    No. 50-C

    Conc. Red.

    No. 51-C

    Ecc. Red.

    E to E

    inches

    (mm)

    E to E

    inches

    (mm)

    No. 5

    C

    No. 1

  • 8/12/2019 I-300

    75/84

    No. 10-CF 90Flare

    No. 100-CF 90Long Radius Flare

    No. 43-CF Straight Flare

    No. 10-CS 90Side Outlet

    No. 20-CS Tee Side Outlet

    Pipe SizeNo. 10-CF90 Flare

    No. 100-CF90 Long Rad

    Flare

    NominalDia.

    inches(mm)

    ActualOutside

    Dia.inches(mm)

    C to Einches(mm)

    C to Finches(mm)

    C to Einches(mm)

    C toinch(mm

    3 3.960 5.50 9.00 7.75 11.80 100,6 139,7 228,6 196,9 285

    4 4.800 6.50 10.00 9.00 12.100 121,9 165,1 254,0 228,6 317

    6 6.900 8.00 11.50 11.50 15.150 175,3 203,2 292,1 292,1 381

    8 9.050 9.00 13.50 14.00 18.200 229,9 228,6 342,9 355,6 469

    10 11.100 11.00 16.50 16.50 22.250 281,9 279,4 419,1 419,1 571

    12 13.200 12.00 18.50 19.00 25.300 335,3 304,8 469,9 482,6 647

    14 15.300 14.00 21.50 21.50 29.350 388,6 355,6 546,1 546,1 736

    No

    No

    No. 10-CB Base Elbow

    No. 20-CB Base Tee

    No. 100-CB Long Radius Base Elbow

    No. 25-CB Reducing Base tee

  • 8/12/2019 I-300

    76/84

    No. 25 CB Reducing Base tee

    Pipe Size

    Base Di

    inche

    Nominal

    Dia.

    inches

    (mm)

    Actual

    Outside Dia.

    inches

    (mm) R U T3 3.960 4.88 0.50 0.580 100,6 124,0 12,7 14

    4 4.800 5.50 0.50 0.6100 121,9 139,7 12,7 15

    6 6.900 7.00 0.62 0.6150 175,3 177,8 15,7 17

    8 9.050 8.38 0.88 0.9200 229,9 212,9 22,4 23

    10 11.100 9.75 0.88 0.9250 281,9 247,7 22,4 23

    12 13.200 11.25 1.00 1.0300 335,3 285,8 25,4 25

    14 15.300 12.50 1.00 1.0350 388,6 317,5 25,4 25

    16 17.400 13.75 1.00 1.0400 442,0 349,3 25,4 25

    18 19.500 15.00 1.12 1.1450 495,3 381,0 28,4 28

    20 21.600 16.00 1.12 1.1500 548,6 406,4 28,4 28

    24 25.800 18.50 1.12 1.1600 655,3 469,9 28,4 28

    GROOVED PIPE VALVES

    Series 317 Check Valve

  • 8/12/2019 I-300

    77/84

    Series 365 Vic-Plug Valve (DI Ends)Series 366 Vic-Plug Valve (IPS Ends)

    Pipe SizeA

    End-to-End

    Dimension

    inches (mm)

    Nominal

    Diameter

    inches

    Actual Outside

    Diameter

    inches

    (mm)

    3 3.960 9.50

    80 100,6 241,3

    4 4.800 11.50100 121,9 292,1

    6 6.900 14.00150 175,3 355,6

    8 9.050 19.50

    200 229,9 495,310 11.100 22.00250 281,9 558,8

    12 13.200 26.00300 335,3 660,4

    Pipe Size

    A

    End-to-End D

    inches

    NominalDiameter

    inches

    Actual OutsideDiameter

    inches (mm) Series 365

    3 3 960 8 00

    Helpful In

  • 8/12/2019 I-300

    78/84

    English and Comme

    Wall Thicknes

    Approximate

    AWWA

    Decimal

    Minutes Converted

    Water PFeet-of-H

    ENGLISH AND METRIC CONVERSIO

    Convert US to Metric

    25.4 X inches (in) =

    0.3048 X feet (ft) =0.4536 X pounds (lbs) =

    28.35 X ounces (oz) =

    COMMERCIAL AWWA PIPE SIZES A

    (ANSI/AWWA C-150)

    Pipe Size

  • 8/12/2019 I-300

    79/84

    ThicknNominalDiameter

    inches (mm)

    Actual OutsideDiameter

    inches (mm) 50 51

    3 3.96 - 0.25(80) (100,6) - (6,4)

    4 4.80 - 0.26(100) (121,9) - (6,6)

    6 6.90 0.25 0.28(150) (175,3) (6,4) (7,1)

    8 9.05 0.27 0.30(200) (229,9) (6,9) (7,6)

    10 11.10 0.29 0.32(250) (281,9) (7,4) (8,1)

    12 13.20 0.31 0.34(300) (335,3) (7,9) (8,6)

    14 15.30 0.33 0.36(350) (388,6) (8,4) (9,1)

    16 17.40 0.34 0.37(400) (442,0) (8,6) (9,4)

    18 19.50 0.35 0.38(450) (495,3) (8,9) (9,7)

    20 21.60 0.36 0.39(500) (548,6) (9,1) (9,9)

    24 25.80 0.38 0.41(600) (655,3) (9,7) (10,4)

    30 32.00 0.39 0.43(750) (762,0) (9,9) (10,9)

    36 38.30 0.43 0.48(900) (914,4) (10,9) (12,2)

    APPROXIMATE WEIGHTS OF COMM

    (ANSI/AWWA C-150)

  • 8/12/2019 I-300

    80/84

    Pipe Size

    Weight of Pipe Per Foot

    Pounds/kg

    Nominal

    Dia.

    inches(mm)

    Actual

    Outside

    Dia.

    inches(mm) CL. 53 CL. 54 CL. 55 CL

    3 3.960 10.9 11.8 12.8 1(11,9) (100,6) (4,9) (5,4) (5,8) (

    4 4.800 13.8 15.0 16.1 1(100) (121,9) (6,3) (6,8) (7,3) (

    6 6.900 21.4 23.2 25.0 2(150) (175,3) (9,7) (10,5) (11,3) (1

    8 9.050 30.1 32.5 34.8 3(200) (229,9) (13,7) (14,7) (15,8) (1

    10 11.100 39.2 42.1 45.1 4(250) (281,9) (17,8) (19,1) (20,5) (2

    12 13.200 49.2 52.8 56.3 5

    (300) (335,3) (22,3) (24,0) (25,5) (2

    14 15.300 60.1 64.2 68.4 7(350) (388,6) (27,3) (29,1) (31,0) (3

    16 17.400 70.1 74.9 79.7 8(400) (442,0) (31,8) (34,0) (36,2) (3

    18 19.500 80.8 86.0 91.3 9

    (450) (495,3) (36,7) (39,0) (41,4) (420 21.600 91.5 97.5 103.4 10

    (500) (548,6) (41,5) (44,2) (46,9) (4

    24 25.800 114.4 121.6 128.8 13

    DECIMAL EQUIVALENTS OF FRACT

    Fraction in

    Inches

    Decimal

    Equivalent

    inches

    Decimal

    Equivalent

    millimeters

    Fra

    In

  • 8/12/2019 I-300

    81/84

    1/64 0.016 0,397

    1/32 0.031 0,794

    3/64 0.047 1,191

    1/16 0.063 1,588

    5/64 0.781 1,984

    3/32 0.094 2,381

    7/64 0.109 2,778

    1/8 0.125 3,175

    9/64 0.141 3,572

    5/32 0.156 3,969

    11/64 0.172 4,3663/16 0.188 4,763

    13/64 0.203 5,159

    7/32 0.219 5,556

    15/64 0.234 5,953

    1

    /4 0.250 6,35017/64 0.266 6,747

    9/32 0.281 7,144

    19/64 0.297 7,541

    5/16 0.313 7,938

    21

    /64 0.328 8,3341/3 0.333 8,467

    11/32 0.344 8,731

    23/ 0 359 9 128

    MINUTES CONVERTED TO DECIMA

    Min. Deg. Min. Deg.

    1 .0166 21 .3500

    2 0333 22 3666

  • 8/12/2019 I-300

    82/84

    2 .0333 22 .3666

    3 .0500 23 .3833

    4 .0666 24 .4000

    5 .0833 25 .4166

    6 .1000 26 .4333

    7 .1166 27 .4500

    8 .1333 28 .4666

    9 .1500 29 .4833

    10 .1666 30 .5000

    11 .1833 31 .5166

    12 .2000 32 .5333

    13 .2166 33 .550014 .2333 34 .5666

    15 .2500 35 .5833

    16 .2666 36 .6000

    17 .2833 37 .6166

    18 .3000 38 .6333

    19 .3166 39 .6500

    20 .3333 40 .6666

    WATER PRESSURE TO FEET-OF-HE

    Pounds Per

    Square Inch Feet of Head

    Pounds Per

    Square Inch Fe

    1 2.31 100

  • 8/12/2019 I-300

    83/84

    2 4.62 110

    3 6.93 120

    4 9.24 130

    5 11.54 140

    6 13.85 150

    7 16.16 160

    8 18.47 170

    9 20.78 180

    10 23.09 200

    15 34.63 250

    20 46.18 30025 57.72 350

    30 69.27 400

    40 92.36 500

    50 115.45 600

    60 138.54 700

    70 161.63 800

    80 184.72 900

    90 207.81 1000

    FEET-OF-HEAD OF WATER TO PRES

    Feet of Head

    Pounds Per

    Square Inch Feet of Head

    P

    S