R. Schwab, E. Mayer, A. Holm Objective and investigation In connection with the international research project of the International Energy Agency IEA-Annex 35 “Hybrid Ventilati- on in New and Retrofitted Office Buildings”, practical inve- stigations with various innovative system components have been carried out. The resulting thermal comfort was recor- ded with a thermal-comfort measuring system, similar to a climate measuring dummy. In this connection it was possible to determine the suitability for use of the system compo- nents, depending on the requirements they make on the sy- stem [1]. This project was promoted by the Federal Ministry of Economics and Labour (Project-support organisation Jü- lich) and carried out in co-operation with various industrial partners. The novel components included in this investigati- on are described in the following: Novel components Experiment room and radiant ceiling panels The floor space of the test office amounts to 27 m 2 , the aver- age height is 3 m. At the west side a double-glazed window with automatically controllable window-tilt drive is situated. At a distance of about 1 m from the window, a sample work- place with a desk top is installed. The radiant ceiling panel with integrated lighting for heating or cooling the room is suspended approximately 0.3 m below the ceiling. The win- dow is provided with blinds for daylight control (Figure 1). Solar chimney As a force for ventilating buildings, use can be made of the pressure differences in chimneys induced by the wind or cau- sed by thermal pressure differences. In the case of the solar chimney examined within the scope of these investigations (Figure 2), the driving power is increased by solar compo- nents. For this purpose the surface of the chimney, which is made of sheet metal, was provided with a black coating and insulated with acrylic glass in order to reduce heat losses. Hybrid Ventilation Systems which Meet the Demands of the Users of Office Buildings 443 Figure 1: Radiant ceiling panel with integrated lights. Figure 2: Solar chimney at the south-west corner of the experiment building

Hybrid Ventilation Systems which Meet the Demands of the

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Hybrid Ventilation Systems which Meet the Demands of the

R. Schwab, E. Mayer, A. Holm

Objective and investigation

In connection with the international research project of theInternational Energy Agency IEA-Annex 35 “Hybrid Ventilati-on in New and Retrofitted Office Buildings”, practical inve-stigations with various innovative system components havebeen carried out. The resulting thermal comfort was recor-ded with a thermal-comfort measuring system, similar to aclimate measuring dummy. In this connection it was possibleto determine the suitability for use of the system compo-nents, depending on the requirements they make on the sy-stem [1]. This project was promoted by the Federal Ministryof Economics and Labour (Project-support organisation Jü-lich) and carried out in co-operation with various industrialpartners. The novel components included in this investigati-on are described in the following:

Novel componentsExperiment room and radiant ceiling panels

The floor space of the test office amounts to 27 m2, the aver-age height is 3 m. At the west side a double-glazed window

with automatically controllable window-tilt drive is situated.At a distance of about 1 m from the window, a sample work-place with a desk top is installed. The radiant ceiling panelwith integrated lighting for heating or cooling the room issuspended approximately 0.3 m below the ceiling. The win-dow is provided with blinds for daylight control (Figure 1).

Solar chimney

As a force for ventilating buildings, use can be made of thepressure differences in chimneys induced by the wind or cau-sed by thermal pressure differences. In the case of the solarchimney examined within the scope of these investigations(Figure 2), the driving power is increased by solar compo-nents. For this purpose the surface of the chimney, which ismade of sheet metal, was provided with a black coating andinsulated with acrylic glass in order to reduce heat losses.

Hybrid Ventilation Systems which Meet the Demands of the Users of Office Buildings

443

Figure 1: Radiant ceiling panel with integrated lights.

Figure 2: Solar chimney at the south-west corner of the experiment building

Verwendete Distiller 5.0.x Joboptions
Dieser Report wurde automatisch mit Hilfe der Adobe Acrobat Distiller Erweiterung "Distiller Secrets v1.0.5" der IMPRESSED GmbH erstellt. Sie koennen diese Startup-Datei für die Distiller Versionen 4.0.5 und 5.0.x kostenlos unter http://www.impressed.de herunterladen. ALLGEMEIN ---------------------------------------- Dateioptionen: Kompatibilität: PDF 1.3 Für schnelle Web-Anzeige optimieren: Nein Piktogramme einbetten: Nein Seiten automatisch drehen: Nein Seiten von: 1 Seiten bis: Alle Seiten Bund: Links Auflösung: [ 2400 2400 ] dpi Papierformat: [ 606 853 ] Punkt KOMPRIMIERUNG ---------------------------------------- Farbbilder: Downsampling: Ja Berechnungsmethode: Bikubische Neuberechnung Downsample-Auflösung: 300 dpi Downsampling für Bilder über: 450 dpi Komprimieren: Ja Automatische Bestimmung der Komprimierungsart: Ja JPEG-Qualität: Maximal Bitanzahl pro Pixel: Wie Original Bit Graustufenbilder: Downsampling: Ja Berechnungsmethode: Bikubische Neuberechnung Downsample-Auflösung: 300 dpi Downsampling für Bilder über: 450 dpi Komprimieren: Ja Automatische Bestimmung der Komprimierungsart: Ja JPEG-Qualität: Maximal Bitanzahl pro Pixel: Wie Original Bit Schwarzweiß-Bilder: Downsampling: Ja Berechnungsmethode: Bikubische Neuberechnung Downsample-Auflösung: 2400 dpi Downsampling für Bilder über: 3600 dpi Komprimieren: Ja Komprimierungsart: CCITT CCITT-Gruppe: 4 Graustufen glätten: Nein Text und Vektorgrafiken komprimieren: Ja SCHRIFTEN ---------------------------------------- Alle Schriften einbetten: Ja Untergruppen aller eingebetteten Schriften: Nein Wenn Einbetten fehlschlägt: Abbrechen Einbetten: Immer einbetten: [ ] Nie einbetten: [ ] FARBE(N) ---------------------------------------- Farbmanagement: Farbumrechnungsmethode: Farbe nicht ändern Methode: Standard Geräteabhängige Daten: Einstellungen für Überdrucken beibehalten: Ja Unterfarbreduktion und Schwarzaufbau beibehalten: Ja Transferfunktionen: Anwenden Rastereinstellungen beibehalten: Ja ERWEITERT ---------------------------------------- Optionen: Prolog/Epilog verwenden: Nein PostScript-Datei darf Einstellungen überschreiben: Nein Level 2 copypage-Semantik beibehalten: Ja Portable Job Ticket in PDF-Datei speichern: Nein Illustrator-Überdruckmodus: Ja Farbverläufe zu weichen Nuancen konvertieren: Nein ASCII-Format: Nein Document Structuring Conventions (DSC): DSC-Kommentare verarbeiten: Ja DSC-Warnungen protokollieren: Nein Für EPS-Dateien Seitengröße ändern und Grafiken zentrieren: Ja EPS-Info von DSC beibehalten: Ja OPI-Kommentare beibehalten: Nein Dokumentinfo von DSC beibehalten: Ja ANDERE ---------------------------------------- Distiller-Kern Version: 5000 ZIP-Komprimierung verwenden: Ja Optimierungen deaktivieren: Nein Bildspeicher: 524288 Byte Farbbilder glätten: Nein Graustufenbilder glätten: Nein Bilder (< 257 Farben) in indizierten Farbraum konvertieren: Ja sRGB ICC-Profil: sRGB IEC61966-2.1 ENDE DES REPORTS ---------------------------------------- IMPRESSED GmbH Bahrenfelder Chaussee 49 22761 Hamburg, Germany Tel. +49 40 897189-0 Fax +49 40 897189-71 Email: [email protected] Web: www.impressed.de
Adobe Acrobat Distiller 5.0.x Joboption Datei
<< /ColorSettingsFile () /AntiAliasMonoImages false /CannotEmbedFontPolicy /Error /ParseDSCComments true /DoThumbnails false /CompressPages true /CalRGBProfile (Adobe RGB (1998)) /MaxSubsetPct 100 /EncodeColorImages true /GrayImageFilter /DCTEncode /Optimize false /ParseDSCCommentsForDocInfo true /EmitDSCWarnings false /CalGrayProfile (Adobe Gray - 20% Dot Gain) /NeverEmbed [ ] /GrayImageDownsampleThreshold 1.5 /UsePrologue false /GrayImageDict << /QFactor 0.9 /Blend 1 /HSamples [ 2 1 1 2 ] /VSamples [ 2 1 1 2 ] >> /AutoFilterColorImages true /sRGBProfile (sRGB IEC61966-2.1) /ColorImageDepth -1 /PreserveOverprintSettings true /AutoRotatePages /None /UCRandBGInfo /Preserve /EmbedAllFonts true /CompatibilityLevel 1.3 /StartPage 1 /AntiAliasColorImages false /CreateJobTicket false /ConvertImagesToIndexed true /ColorImageDownsampleType /Bicubic /ColorImageDownsampleThreshold 1.5 /MonoImageDownsampleType /Bicubic /DetectBlends false /GrayImageDownsampleType /Bicubic /PreserveEPSInfo true /GrayACSImageDict << /VSamples [ 1 1 1 1 ] /QFactor 0.15 /Blend 1 /HSamples [ 1 1 1 1 ] /ColorTransform 1 >> /ColorACSImageDict << /VSamples [ 1 1 1 1 ] /QFactor 0.15 /Blend 1 /HSamples [ 1 1 1 1 ] /ColorTransform 1 >> /PreserveCopyPage true /EncodeMonoImages true /ColorConversionStrategy /LeaveColorUnchanged /PreserveOPIComments false /AntiAliasGrayImages false /GrayImageDepth -1 /ColorImageResolution 300 /EndPage -1 /AutoPositionEPSFiles true /MonoImageDepth -1 /TransferFunctionInfo /Apply /EncodeGrayImages true /DownsampleGrayImages true /DownsampleMonoImages true /DownsampleColorImages true /MonoImageDownsampleThreshold 1.5 /MonoImageDict << /K -1 >> /Binding /Left /CalCMYKProfile (U.S. Web Coated (SWOP) v2) /MonoImageResolution 2400 /AutoFilterGrayImages true /AlwaysEmbed [ ] /ImageMemory 524288 /SubsetFonts false /DefaultRenderingIntent /Default /OPM 1 /MonoImageFilter /CCITTFaxEncode /GrayImageResolution 300 /ColorImageFilter /DCTEncode /PreserveHalftoneInfo true /ColorImageDict << /QFactor 0.9 /Blend 1 /HSamples [ 2 1 1 2 ] /VSamples [ 2 1 1 2 ] >> /ASCII85EncodePages false /LockDistillerParams true >> setdistillerparams << /PageSize [ 595.276 841.890 ] /HWResolution [ 2400 2400 ] >> setpagedevice
Page 2: Hybrid Ventilation Systems which Meet the Demands of the

Should the driving power be insufficient, a ventilator in theduct leading to the solar chimney may be switched on.

Window ventilation system and air quality sensor

The automatic window ventilation system (Figure 3) consistsof an actuator for the position of the window with monitor-ing status and integrated automatic ventilation. On the out-side of the window a weathering sensor is installed whichprovides the electronic control with the necessary climate da-ta. In case critical climatic conditions arise, the opening of thewindow is prevented, i.e. it is automatically closed. For themeasurement of air quality and to activate the hybrid venti-lation components, a gas mix sensor [2] was utilized. The sen-sor reacts above all to volatile organic substances. To provi-de ventilation which matches the demands, the electronicsand software of the sensor permit the activation of two relaycontacts when two freely selectable boundary values of the

output signal from the sensor are exceeded. After adaptati-on and extension of the hardware it is possible to switch onthe window ventilation system after the first boundary valuehas been exceeded and to switch on the ventilator in the so-lar chimney when the second boundary value has been sur-passed.

Indoor temperature controller and equivalent-tempe-rature sensor for controlling an individual indoor climate

The Indoor temperature controller is installed near the work-place. When the window is opened, thus opening the win-dow contact, two adjustment control versions are possible(radiant ceiling panel switched on or switched off). The airtemperature sensor which is installed as standard on the in-door air temperature controller usually measures only the airtemperature. An equivalent temperature sensor [3] whichwas available at the IBP has been further developed for theprojected application. It is now possible to convert an equi-valent temperature ranging from 0 °C to 40 °C into a volta-ge from 0 V to 10 V which can be used for controlling theventilation or climate components, while the other comfortparameters of air velocity and thermal radiation are also ta-ken into account. As the sensor is fitted on the desk close tothe person working there, it can transmit the prevalent climatic scenario to the control unit.

Practical conclusions

The investigations show that in winter at temperatures of ab-out 0 °C or below, with a cyclically-controlled window venti-lation system, a feeling of excessive cold in the foot area hasto be reckoned with (Figure 4). The opening times of thewindow ought, therefore, to be further reduced. For hygie-nic reasons this cannot however always be realized. Logical-ly, but in contradiction of the idea of energy saving, the radi-ant ceiling panel should not be switched off. All in all, the in-vestigation provides evidence that all components used aresuitable for use in hybrid ventilation systems, but that thereis still room for improving the adaptation of the componentsone to another when they are used with existing automaticcontrol techniques.

Bibliography

[1] Leonhardt, H.; Mayer, E. et.al.: Investigations carried out on a hybrid ventilation system with innovative system components.IBP Report RK-07/2003 (2003).

[2] Project: “Building ventilation with air quality control”. Promoti-on reference 0329795 A-E. Supported by the Federal Ministry ofEconomics and Technology (BMWi), Villemombler Strasse 76,53123 Bonn.

[3] Schwab, R.: Influence of insolation on thermal comfort in motorvehicles. FAT publication No. 109 (1994).

(4) Zitzmann, T.: Investigations into thermal comfort and air exchan-ge in an individual office with radiant island and program-con-trolled tilting window. Diploma thesis, Coburg Polytechnic(2003).

FRAUNHOFER-INSTITUT FÜR BAUPHYSIK IBPInstitutsleitung: Prof. Dr. Gerd Hauser

Prof. Dr. Klaus SedlbauerD-70569 Stuttgart, Nobelstr. 12 (Postfach 80 04 69, 70504 Stuttgart), Tel. 07 11/9 70-00D-83626 Valley, Fraunhoferstr. 10 (Postfach 11 52, 83601 Holzkirchen), Tel. 0 80 24/6 43-0

Herstellung und Druck: Fraunhofer-Informationszentrum Raum und Bau IRB, Satz- und DruckzentrumNachdruck nur mit schriftlicher Genehmigung des Fraunhofer-Instituts für Bauphysik

Figure 3: Window ventilation system in fully tilted position.

Figure 4: Drop in the comfort value LMV (Local Mean Vote) in the foot areato below the barely-acceptable value 0.5 with the radiant ceilingpanel switched off and the window open for ventilation [4].