FLUTED METAL DECK WITH CONCRETE FILL MINERAL WOOL TYPICAL STEEL FASTENERS BY DESIGN DRYWALL SCREW 1" LOWER THAN TRACK LEG 5/8" TYPE "X" DRYWALL 1 2 " NOMINAL JOINT (1" JOINT PROTECTION) #8 x 1/2" FRAMING SCREW METAL STUD BY DESIGN CEMCO SLOTTED TRACK DEFLECTION DRIFT ANGLE DDA-1 (BOTH SIDES) NOTE: SINGLE LAYER OF 5 8 " TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING RECTORSEAL FLAMESAFE/BIOSTOP SPRAY OVER MINERAL WOOL ( 1 2 " OVERLAP METAL) ON ONE SIDE ONLY DISCLAIMER: CEMCO assumes no liability for failure resulting from the use of it's drawings, computations, or for failure resulting from the use of alternate materials, or improper application or installation. This drawing is supplied solely to assist in the selection and application of CEMCO products. This drawing is generic in nature and should not be used in design or construction without an independent evaluation by a qualified Architect or Engineer of Record. All warranties of any kind, express or implied, including but not limited to the implied warranties of merchantability and fitness for a particular purpose are disclaimed. 263 N. Covina Lane. City of Industry, CA 91744 PHONE (800) 775-2362 ENG. DEPT. FAX (626) 369-7243 WWW.CEMCOSTEEL.COM REVISION: SCALE: 3"=1'-0" JOB NO.: UL DETAILS SHEET NO.: DRAWN BY: T. GARIBEKIAN DATA: 01/27/14 APPROVED BY: F. SESMA DATE: 01/27/14 SD87 HW-D-0518 STANDARD WALL, PERPENDICULAR TO FLUTED DECK ASSEMBLY RATING: 2 HR

HW-D-0518 STANDARD WALL, PERPENDICULAR TO FLUTED DECKcemcosteel.com/sites/default/files/DDA-1 Details.pdf · fluted metal deck with concrete fill mineral wool typical steel fasteners

  • Upload
    others

  • View
    32

  • Download
    0

Embed Size (px)

Citation preview

FLUTED METAL DECKWITH CONCRETE FILL

MINERAL WOOL

TYPICAL STEELFASTENERS BY DESIGN

DRYWALL SCREW1" LOWER THANTRACK LEG

5/8" TYPE "X"DRYWALL

12" NOMINAL JOINT

(1" JOINT PROTECTION)

#8 x 1/2" FRAMINGSCREW

METAL STUDBY DESIGN

CEMCO SLOTTEDTRACK

DEFLECTION DRIFTANGLE DDA-1(BOTH SIDES)

NOTE: SINGLE LAYER OF 58" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

RECTORSEALFLAMESAFE/BIOSTOPSPRAY OVER MINERALWOOL (12" OVERLAPMETAL) ON ONE SIDEONLY

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T. GARIBEKIANDATA: 01/27/14APPROVED BY: F. SESMADATE: 01/27/14

SD87

HW-D-0518 STANDARD WALL, PERPENDICULAR TO FLUTED DECK

ASSEMBLY RATING: 2 HR

#8 x 1/2" FRAMINGSCREW

FLUTED METAL DECKFILLED WITH CONCRETE

DRYWALL SCREW1" LOWER THANTRACK LEG

CEMCO FAS STRAP

5/8" TYPE "X" DRYWALL

CEMCO SLOTTEDTRACK

METAL STUDBY DESIGN

NOTE: SINGLE LAYER OF 5 8" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

DEFLECTION DRIFTANGLE DDA-1(BOTH SIDES)

12" NOMINAL JOINT

(1" JOINT PROTECTION)

12" NOMINAL JOINT

(1" JOINT PROTECTION)

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T.GARIBEKIANDATA: 01/27/14APPROVED BY: F. SESMADATE: 01/27/14

SD88

HW-D-0524 STANDARD WALL, OFFSET & PARALLEL UNDER FLUTED DECK

CONFIGURATION "A"ASSEMBLY RATING: 2 HR

DRYWALL SCREW 1"LOWER THAN TRACKLEG

5/8" TYPE "X" DRYWALL

RECTORSEALFLAMESAFE/ BIOSTOPSPRAY OVER MINERALWOOL 1/2" LAP OVERMETAL (ONE SIDEONLY)

CEMCO SLOTTEDTRACK

METAL STUDBY DESIGN

PRE-FORMEDMINERAL WOOL PLUG

FLUTED METAL DECKFILLED WITH CONCRETE

2" STRAP BY DESIGN

#8 x 1/2" FRAMINGSCREW

DEFLECTION DRIFTANGLE DDA-1(BOTH SIDES)

NOTE: SINGLE LAYER OF 5 8" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

12" NOMINAL JOINT

(1" JOINT PROTECTION)

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T. GARIBEKIANDATA: 01/27/14APPROVED BY: F. SESMADATE: 01/27/14

SD89

HW-D-0524 STANDARD WALL, OFFSET & PARALLEL UNDER FLUTED DECK

CONFIGURATION "B"ASSEMBLY RATING: 2 HR

MINERAL WOOL

CONCRETE DECK

DRYWALL SCREW1" LOWER THANTRACK LEG

5/8" TYPE "X"DRYWALL

#8 x 1/2" FRAMINGSCREW

METAL STUDBY DESIGN

CEMCO SLOTTEDTRACK

DEFLECTION DRIFTANGLE DDA-1(BOTH SIDES)

NOTE: SINGLE LAYER OF 5 8" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

12" NOMINAL JOINT

(1" JOINT PROTECTION)

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T.GARIBEKIANDATA: 01/27/14APPROVED BY: F. SESMADATE: 01/27/14

SD93

HW-D-0620 STANDARD WALL, PARALLEL & OFFSET UNDER FLUTED DECK

CONFIGURATION "B"ASSEMBLY RATING: 2 HR

CONCRETE DECK

DRYWALL SCREW1" LOWER THANTRACK LEG

5/8" TYPE "X"DRYWALL

#8 x 1/2" FRAMINGSCREW

METAL STUDBY DESIGN

CEMCO SLOTTEDTRACK

DEFLECTION DRIFTANGLE DDA-1(BOTH SIDES)

NOTE: SINGLE LAYER OF 5 8" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

12" NOMINAL JOINT

(1" JOINT PROTECTION)

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T.GARIBEKIANDATA: 01/27/14APPROVED BY: F. SESMADATE: 01/27/14

SD94

HW-D-0620 STANDARD WALL, PARALLEL AND DIRECTLY UNDER FLUTED DECK

CONFIGURATION "A"ASSEMBLY RATING: 2 HR

TYPICAL STEELFASTENERS BY DESIGN

DRYWALL SCREW1" LOWER THANTRACK LEG

5/8" TYPE "X"DRYWALL

#8 x 1/2" FRAMINGSCREW

METAL STUDBY DESIGN

CEMCO SLOTTEDTRACK

DEFLECTION DRIFTANGLE DDA-1(BOTH SIDES)

NOTE: SINGLE LAYER OF 5 8" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

CONCRETE SLAB

OPEN WEB TRUSS ORJOIST

FURRING CHANNEL @24" O.C.

58" TYPE "C" GYPSUM

WALLBOARD

12" NOMINAL JOINT

(1" JOINT PROTECTION)

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T. GARIBEKIANDATA: 01/27/14APPROVED BY: F. SESMADATE: 01/27/14

SD96

HW-D-0550 STANDARD WALL, GYPSUM WALLBOARD CEILING

ASSEMBLY RATING: 2 HR

MINERAL WOOL STUFFEDBETWEEN FRAMING ANDFIREPROOFING 50%COMPRESSED

(2) LAYERSDRYWALL

Z-CLIP

CEMCO SLOTTEDTRACK WITHDDA-1

METAL STUD

DRYWALL CUTAROUND I-BEAM WITH2" GAP

I-BEAM

DDA-1 OVER FRAMING

DDA-1 OVER FRAMING

BIOSTOP SPRAYOVER MINERAL WOOLAND 1/2 OVERLAPONTO DDA BEFOREDRYWALL ISINSTALLED (ONE SIDEOF WALL ONLY)

CEMCO SLOTTEDTRACK WITHDDA-1

NOTE: SINGLE LAYER OF 58" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

12" NOMINAL JOINT

(1" JOINT PROTECTION)

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T.GARIBEKIANDATA: 01/27/14APPROVED BY: F. SESMADATE: 01/27/14

SD97

HW-D-0573 STANDARD WALL, @ FLUTED DECK BEAM PENETRATION

ASSEMBLY RATING: 2 HR

MINERAL WOOL STUFFEDBETWEEN FRAMING ANDFIREPROOFING 50%COMPRESSED

(2) LAYERSDRYWALL

Z-CLIP

CH STUD

DRYWALL CUTAROUND I-BEAM WITH2" GAP

I-BEAM

DDA-1 OVER FRAMINGDDA-1 OVER FRAMING

BIOSTOP SPRAYOVER MINERAL WOOLAND 1/2 OVERLAPONTO DDA BEFOREDRYWALL ISINSTALLED (ONE SIDEOF WALL ONLY)

CEMCO SLOTTEDTRACK ORJ-RUNNER

NOTE: SINGLE LAYER OF 5 8" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

12" NOMINAL JOINT

(1" JOINT PROTECTION)

CEMCO SLOTTEDTRACK ORJ-RUNNER

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T.GARIBEKIANDATA: 01/27/14APPROVED BY: F. SESMADATE: 01/27/14

SD98

HW-D-0623 SHAFT WALL, @ FLUTED DECK BEAM PENETRATION

ASSEMBLY RATING: 2 HR

STEEL BEAM

SPRAYFIREPROOFING

CONCRETE SLAB OR FLUTEDMETAL DECK WITH CONCRETE FILL

STRUCTURAL STEELFIREPROOFING(THICKNESS BY OTHERS)

1/2" x 20 GA. Z-BAR OR16 GA. CRC @ 16" O.C.

CH STUD

5/8" TYPE "X" DRYWALL1" SHAFT LINER

CEMCO SLOTTEDTRACK ORJ-RUNNER

MINERAL WOOL

DEFLECTION DRIFTANGLE DDA-1(ONE SIDE ONLY)

NOTE: SINGLE LAYER OF 5 8" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

12" NOMINAL JOINT

(1" JOINT PROTECTION)

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T.GARIBEKIANDATA: 01/27/14APPROVED BY: F. SESMADATE: 01/27/14

SD99

HW-D-0622 SHAFT WALL, DIRECTLY UNDER BEAM

ASSEMBLY RATING: 2 HR

CONCRETE SLAB OR FLUTEDMETAL DECK WITH CONCRETE FILL

STEEL BEAM

STRUCTURAL FIREPROOFING(THICKNESS BY OTHERS)

1/2" x 20 GA. Z-BAR OR16 GA. CRC @ 16" O.C.

SPRAYFIREPROOFING

1/2" x 20 GA. Z-BAR OR16 GA. CRC @ 16" O.C.

CH STUD

5/8" TYPE "X" DRYWALL1" SHAFT LINER

CEMCO SLOTTEDTRACK ORJ-RUNNER

MINERAL WOOL

DEFLECTION DRIFTANGLE DDA-1(ONE SIDE ONLY)

NOTE: SINGLE LAYER OF 58" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

12" NOMINAL JOINT

(1" JOINT PROTECTION)

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T.GARIBEKIANDATA: 01/27/14APPROVED BY: F. SESMADATE: 01/27/14

SD100

HW-D-0622 SHAFT WALL, OFFSET UNDER BEAM

ASSEMBLY RATING: 2 HR

FLUTED METAL DECKWITH CONCRETE FILL

MINERAL WOOL

TYPICAL STEELFASTENERS BY DESIGN

NOTE: SINGLE LAYER OF 58" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

RECTORSEALFLAMESAFE/BIOSTOPSPRAY OVER MINERALWOOL (12" OVERLAPMETAL) ON ONE SIDEONLY

CH STUD

5/8" TYPE "X" DRYWALL1" SHAFT LINER

CEMCO SLOTTEDTRACK ORJ-RUNNER

MINERAL WOOL

DEFLECTION DRIFTANGLE DDA-1(ONE SIDE ONLY)

12" NOMINAL JOINT

(1" JOINT PROTECTION)

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T. GARIBEKIANDATA: 01/27/14APPROVED BY: F. SESMADATE: 01/27/14

SD101

HW-D-0525 SHAFT WALL, PERPENDICULAR TO FLUTED DECK

ASSEMBLY RATING: 2 HR

CONCRETE SLABOR FLUTED METALDECK WITHCONCRETE FILL

STEEL BEAM

STRUCTURALFIREPROOFING(THICKNESS BY OTHERS)

EXPANDED METALLATH8"

1/2" x 20 GA. Z-BAR OR16 GA. CRC @ 16" O.C.

SPRAYFIREPROOFING

CH STUD

5/8" TYPE "X" DRYWALL1" SHAFT LINER

CEMCO SLOTTEDTRACK ORJ-RUNNER

MINERAL WOOL

DEFLECTION DRIFTANGLE DDA-1(ONE SIDE ONLY)

NOTE: SINGLE LAYER OF 58" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

12" NOMINAL JOINT

(1" JOINT PROTECTION)

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T.GARIBEKIANDATA: 01/27/14APPROVED BY: F. SESMADATE: 01/27/14

SD104

HW-D-0653 STANDARD SHAFT WALL, PARALLEL & CANTILEVER UNDER BEAM

ASSEMBLY RATING: 2 HR

#8 x 1/2" FRAMINGSCREW

DEFLECTION DRIFTANGLE DDA-1(FINISH SIDE ONLY)

5/8" TYPE "X"DRYWALL

METAL STUDSPACING BY DESIGN

CONCRETE SLAB

DRYWALL SCREW1" LOWER THANTRACK LEG

CEMCO SLOTTEDTRACK

NOTE: SINGLE LAYER OF 58" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

12" NOMINAL JOINT

(1" JOINT PROTECTION)

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T.GARIBEKIANDATA: 01/24/14APPROVED BY: F. SESMADATE:01/24/14

SD105

HW-D-0554 STANDARD CHASE WALL, CONCRETE SLAB

ASSEMBLY RATING: 2 HR

REVISION:

SPRAYFIREPROOFING

STEEL BEAM

STRUCTURALFIREPROOFING(THICKNESS BY OTHERS)

1/2" x 20 GA. Z-BAR OR16 GA. CRC(SPACING BY DESIGN)

CEMCO DEFLECTIONDRIFT ANGLE - DDA1(BOTH SIDES)

CONCRETE SLAB OR FLUTEDMETAL DECK WITH CONCRETE FILL

5/8" TYPE"X" DRYWALL

#8 x 1/2" FRAMINGSCREW

DRYWALL SCREW1" LOWER THAN TRACK LEG

12" NOMINAL GAP

(1" JOINT PROTECTION)CEMCO SLOTTEDTRACK

METAL STUDSPACING BY DESIGN

NOTE: SINGLE LAYER OF 58" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T.GARIBEKIANDATA: 03/12/14APPROVED BY: F. SESMADATE: 03/12/14

SD107

HW-D-0551 STANDARD WALL, PARALLEL & CENTERED DIRECTLY UNDER BEAM

ASSEMBLY RATING: 2 HR

CONCRETE SLAB OR FLUTEDMETAL DECK WITH CONCRETE FILL

STEEL BEAM

STRUCTURALFIREPROOFING(THICKNESS BY OTHERS)

1/2" x 20 GA. Z-BAR OR16 GA. CRC(SPACING BY DESIGN)

SPRAYFIREPROOFING

EXPANDED METALLATH

CEMCO DEFLECTIONDRIFT ANGLE - DDA1(BOTH SIDES)

5/8" TYPE"X" DRYWALL

#8 x 1/2" FRAMINGSCREW

DRYWALL SCREW1" LOWER THAN TRACK LEG

CEMCO SLOTTEDTRACK

METAL STUDSPACING BY DESIGN

NOTE: SINGLE LAYER OF 5 8" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

12" NOMINAL JOINT

(1" JOINT PROTECTION)

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T.GARIBEKIANDATA: 03/14/2014APPROVED BY: F. SESMADATE: 03/14/2014

SD108

HW-D-0652 STANDARD WALL, PARALLEL & CANTILEVERED UNDER BEAM

ASSEMBLY RATING: 2 HR

RECTORSEAL/FLAMESAFE/BIOSTOPSPRAY 1/2" OVERLAPMETAL ( ON ONE SIDEONLY)

MINERAL WOOLFLUTED METAL DECKWITH CONCRETE FILL

#8 x 1/2" FRAMINGSCREW

DEFLECTION DRIFTANGLE DDA-1(FINISH SIDE ONLY)

5/8" TYPE "X"DRYWALL

METAL STUDSPACING BY DESIGN

DRYWALL SCREW1" LOWER THANTRACK LEG

CEMCO SLOTTEDTRACK

NOTE: SINGLE LAYER OF 58" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

12" NOMINAL JOINT

(1" JOINT PROTECTION)

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T.GARIBEKIANDATA: 03/14/14APPROVED BY: F. SESMADATE:03/14/14

SD110

HW-D-0553 STANDARD CHASE WALL, PERPENDICULAR TO FLUTED DECK

ASSEMBLY RATING: 2 HR

REVISION:

CONCRETE DECK

TYPICAL STEELFASTENERS BY DESIGN

DRYWALL SCREW1" LOWER THANTRACK LEG

5/8" TYPE "X"DRYWALL

12" NOMINAL JOINT

(1" JOINT PROTECTION)

#8 x 1/2" FRAMINGSCREW

METAL STUDBY DESIGN

CEMCO SLOTTEDTRACK

DEFLECTION DRIFTANGLE DDA-1(BOTH SIDES)

NOTE: SINGLE LAYER OF 58" TYPE "X" DRYWALL FOR 1 HOUR FIRE RATING

DISCLAIMER:

CEMCO assumes no liability for failure resulting from theuse of it's drawings, computations, or for failure resultingfrom the use of alternate materials, or improper applicationor installation. This drawing is supplied solely to assist inthe selection and application of CEMCO products. Thisdrawing is generic in nature and should not be used indesign or construction without an independent evaluationby a qualified Architect or Engineer of Record.All warranties of any kind, express or implied, includingbut not limited to the implied warranties of merchantabilityand fitness for a particular purpose are disclaimed.

263 N. Covina Lane.City of Industry, CA 91744PHONE (800) 775-2362ENG. DEPT.FAX (626) 369-7243WWW.CEMCOSTEEL.COM

REVISION:

SCALE: 3"=1'-0"JOB NO.: UL DETAILSSHEET NO.:

DRAWN BY: T. GARIBEKIANDATA: 03/14/14APPROVED BY: F. SESMADATE: 03/14/14

SD111

HW-D-0515 STANDARD WALL, PERPENDICULAR TO FLUTED DECK

ASSEMBLY RATING: 2 HR