Upload
mdarifur-rahman
View
215
Download
0
Embed Size (px)
Citation preview
8/15/2019 HVDC_Voltage Control.docx - Copy
1/8
Transmission and Distribution
EEE-471
Limitations of HVAC Transmission:
1. Reactive Loss and DroFor ac transmission, there are lagging reactive VA loss and leading
reactive VA loss due to L & C of the line and the transmission would be
economical if these two losses balance each other at all points along
the line. This happens when the load is terminated with characteristic
impedance of the line. However, it is not possible to operate the line at
characteristic load conditions all the time. Thus this causes reactive
loss in the line. eactive drop in the line due to L & C is also signi!cant
in case of ac transmission.
!. "tabi#it$ The power transmitted over a line of reactance "#$ per phase is,
P=VsVr
X sinδ
%aimum stead' state power occurs when, δ =90° .
Considering transient condition, δ is not generall' more than 30°
for e(cient stable operation of the s'stem.)tabilit' considerations impose serious limits on the distance of power
transmission over ac lines. For dc transmission problem of stabilit'
doesn$t arise.%. Current Carr$in& Caacit$
*n ac transmission, current carr'ing capacit' is reduced due to
charging current. This charging current is appreciabl' high for
underground cables. This charging current ma' be as high as +A per
-m for -V cable. The length of the cable for which the cable
charging current becomes e/ual to the thermal current limit is 0nown
as critical length and limits the distance of power transmission.4. 'erranti E(ect
The rise of receiving end voltage under leading VA on the line at no
load ma' be serious and limits the distance of power transmission overac lines.
Advanta&es of HVDC Transmission:
+. *n case of dc transmission, onl' two conductors are needed for single
line. 1sing earth return, onl' one conductor is enough and with two
conductors and earth return, the capacit' of the line is doubled. *n case
8/15/2019 HVDC_Voltage Control.docx - Copy
2/8
of ac transmission, at least three conductors are necessar' and for
double circuit, si conductors would be necessar'.2. High voltage dc line needs less space compared to ac line of the same
voltage and si3e. This reduces space to be maintained.4. The electrical !eld strength at the surface of conductor can be 56
higher on overhead lines and about three times higher on cables incase of ac as compared to dc. Thus dc cables are less epensive than
ac cables.. There is no need to maintain s'nchronism between two ac s'stems
connected together b' a dc lin0. *f transmission is interrupted due to
voltage drop or an' other fault, it is reestablished after clearance of
fault irrespective of s'nchronism.5. 7ower 8ow through dc lines can be easil' controlled via grid control of
the values.9. Terminals & lines can be built in stages. :c line voltage can be
increased graduall' b' stepwise installation of increased number of
conductors and power capacit' of the dc lin0 will also increase
accordingl'.;. Two ac power s'stems having dii? %ono@polar>ii? i@polar>iii? Homo@polar
*n mono@polar line, onl' one conductor is used and earth is used as return
path.
8/15/2019 HVDC_Voltage Control.docx - Copy
3/8
i@polar lines have two conductors. Bne operating with >ve? polarit' and the
other with D>ve? polarit'. There are two converters of e/ual voltage ratings &
connected in series at each end of the dc line. The =unction of the converters
ma' be grounded at one end or at both ends. *f it is grounded at both ends,
each line can be operated individuall'.
FigE %ono@polar
FigE i@polar
FigE Homo@polar
8/15/2019 HVDC_Voltage Control.docx - Copy
4/8
+o,er o, in HVDC transmission #ine:
L is the line resistance. er &ci are the resistance of converter & recti!er
respectivel'. The current in the line is given b',
Rcr+ R L+¿ Rci
I d=V ¿cos∝−V oicosβ
¿
*nternal voltage can be controlled b' an' or both of the following methods.
>a? rid Control>b? Tap@change Control
Rectication:
The average value of dc for n@phase is given b',
8/15/2019 HVDC_Voltage Control.docx - Copy
5/8
V o= 1
2π
n
∫π
2−π
n
π
2+π n
V m sinθdθ
¿V
msin ( π
n)
π
n
For 4@ ∅ , nG4,
V o=
V msin (
π
3)
π 3
V o=3V m
π
√ 32
For 9@ ∅ , nG9,
V o=
V msin (
π
6
)
π
6
∴V o=3V m
π
%- ∅ /rid&e Rectier:
8/15/2019 HVDC_Voltage Control.docx - Copy
6/8
FigE 4@ ∅ ridge ecti!er
The output voltage for n@phase is,
V o=V
maxsin ( π
n)
π
n
*n this case,
V max=√ 3V m
For nG9,
V o=√ 3V m
sin (
π
6 )π
6
¿3√ 3 Vm
π
0nversion:
8/15/2019 HVDC_Voltage Control.docx - Copy
7/8
planation of d transmission advantages b' math formulaeE
Pac= E
1 E
2
X sinδ
Pdc= Ed1− Ed2
V d R Ed 2
Ihere, Ed 1− Ed2 can be varied easil' and e
8/15/2019 HVDC_Voltage Control.docx - Copy
8/8
¿ √ 2
cos ∅
)ince, ∅≤1 , power per conductor in case of dc is more than ac.
+o,er er Circuit:
Let us compare power transmission capabilities of a 4@phase single circuit
line and a bi@polar line.
Pd=2 ρd∧ Pa=3 ρa
Ihere, ρd∧ ρa are power transmitted per conductor of dc & ac lines
respectivel'.
Pd
Pa=
2 ρd
3 ρa=
2V d I d
3V a I acos ∅=
2V d I d
3V d
√ 2 I dcos∅
= 2√ 23cos ∅
= 2.8283cos ∅
)ince, ∅ ≤1 , power transmission capabilit' of bi@polar line is the same as
that of three phase single circuit line.
o "tabi#it$ +rob#em:As we 0now,
Pac= E
1 E
2
X sinδ
Therefore, higher the value of #, lower will be capabilit' to transmit power
and also increase of angle δ which means less stabilit'.