3
DUCT LEAK TEST FORM Form EN-MPS-718a FEMC / RPSC Page 1 of 3 Revision 1 9/5/06 Approved by Wayne L. Cornell ENGINEER DATE (M/D/YYYY) PROJECT STATION MCMURDO PALMER SOUTH POLE BLDG. NO. BUILDING NAME LOCATION LEAKAGE TESTS The need to verify leakage control by field-testing is not present when adequate methos of assembly and sealing are used. Leakage tests are an added expense in system installation. It is not recommended that duct systems constructed to 3-in. w.g. (water gage) class or lower be tested since it is generally recognized as not being cost effective. For duct systems constructed to 4-in. w.g. class and higher, the designer must determine if justification for testing exists. If it does, he or she must clearly designate the contract documents the portions of the system(s) to be tested and must specify appropriate test methods. GENERAL TESTING PROCEDURES Conventional leak testing is based on positive pressure mode analysis. It involves inserting temporary plugs (plates, sheets, balloons, bags, etc.) in openings in a section of duct and connecting a blower and a flowmeter to the section of ductwork being tested in such a manner that pressurizing the duct will cause air escaping from the test section to pass through the flowmeter. 1. Select a test pressure not in excess of the pressure class rating of the duct. 2. Calculate the allowable or allocated leakage using leakage factors related to the duct surface area. 3. Select a limited section of duct for which the estimated leakage of duct will not exceed the capacity of the test apparatus. 4. Connect the blower and flowmeter to the duct section and provide temporary seals at all open ends of the ductwork. 5. To prevent over-pressurizing of the ducts, start the blower with the variable inlet damper closed. Controlling pressure carefully, pressurize the duct section to the required level. 6. Read the flowmeter and compare the leakage in cfm (cubic feet per minute) per square foot with the allowable rate determined in Step 3. 7. Complete test report form (next two pages). 8. Remove temporary blanks and seals. 9. More detailed information on duct leakage and testing is available in the SMACNA HVAC Air Duct Leakage Test Manual. For information on ordering and prices, write the Sheet Metal and Air Conditioning Contractors’ National Association, P.O. Box 221230, Chantilly, VA 20153-1230; call 703/803-2980; fax 703/803-3732; see www.smacna.org on the Internet.

hvacductleaktest-718a

Embed Size (px)

DESCRIPTION

Leak Test

Citation preview

  • DUCT LEAK TEST FORM

    Form EN-MPS-718a FEMC / RPSC Page 1 of 3 Revision 1 9/5/06 Approved by Wayne L. Cornell

    ENGINEER DATE (M/D/YYYY) PROJECT STATION MCMURDO PALMER SOUTH POLE BLDG. NO. BUILDING NAME LOCATION

    LEAKAGE TESTS The need to verify leakage control by field-testing is not present when adequate methos of assembly and sealing are used. Leakage tests are an added expense in system installation. It is not recommended that duct systems constructed to 3-in. w.g. (water gage) class or lower be tested since it is generally recognized as not being cost effective. For duct systems constructed to 4-in. w.g. class and higher, the designer must determine if justification for testing exists. If it does, he or she must clearly designate the contract documents the portions of the system(s) to be tested and must specify appropriate test methods.

    GENERAL TESTING PROCEDURES Conventional leak testing is based on positive pressure mode analysis. It involves inserting temporary plugs (plates, sheets, balloons, bags, etc.) in openings in a section of duct and connecting a blower and a flowmeter to the section of ductwork being tested in such a manner that pressurizing the duct will cause air escaping from the test section to pass through the flowmeter.

    1. Select a test pressure not in excess of the pressure class rating of the duct. 2. Calculate the allowable or allocated leakage using leakage factors related to the duct

    surface area. 3. Select a limited section of duct for which the estimated leakage of duct will not exceed

    the capacity of the test apparatus. 4. Connect the blower and flowmeter to the duct section and provide temporary seals at all

    open ends of the ductwork. 5. To prevent over-pressurizing of the ducts, start the blower with the variable inlet damper

    closed. Controlling pressure carefully, pressurize the duct section to the required level. 6. Read the flowmeter and compare the leakage in cfm (cubic feet per minute) per square

    foot with the allowable rate determined in Step 3. 7. Complete test report form (next two pages). 8. Remove temporary blanks and seals. 9. More detailed information on duct leakage and testing is available in the SMACNA HVAC

    Air Duct Leakage Test Manual. For information on ordering and prices, write the Sheet Metal and Air Conditioning Contractors National Association, P.O. Box 221230, Chantilly, VA 20153-1230; call 703/803-2980; fax 703/803-3732; see www.smacna.org on the Internet.

    rainwabrHighlight

  • DUCT LEAK TEST (continued)

    Form EN-MPS-718a FEMC / RPSC Page 2 of 3 Revision 1 9/05/063/24/2008 Approved by Wayne L. Cornell

    TECHNICIAN DATE (M/D/YYYY) PROJECT STATION MCMURDO PALMER SOUTH POLE BLDG. NO. BUILDING NAME SYSTEM NO. TRAVERSE LOCATION AREA SERVED/ZONE SYSTEM DESCRIPTION OF DUCTWORK UNDER TEST

    DUCT DESIGN OPERATING STATIC PRESSURE W.G. DUCT DESIGN TEST STATIC PRESSURE W.G. DUCT CAPACITY CFM MAXIMUM ALLOWABLE LEAKAGE: (DUCT CAPACITY CFM) (LEAK FACTOR ) = CFM

    Test Results TEST APPARATUS BLOWER ORIFICE: TUBE SIZE DIAMETER ORIFICE SIZE DIAMETER CALIBRATED: TEST STATIC PRESSURE: TEST ORIFICE DIFFERENTIAL PRESSURE: W.G. LEAKAGE CFM CERTIFIED BY:

    rainwabrHighlight

  • DUCT LEAK TEST

    (concluded)

    Form EN-MPS-718a FEMC / RPSC Page 3 of 3 Revision 1 9/5/06 Approved by Wayne L. Cornell

    AREA & SYSTEM DUCT PRESSURE CLASS ALLOWABLE

    LEAKAGE MEASURED LEAKAGE

    TITLE 2 WITNESS WITNESS PRINTED NAME RAYTHEON POLAR SERVICES REP. WITNESS PRINTED NAME REMARKS

    rainwabrHighlight