Upload
brett-dillon
View
33
Download
0
Embed Size (px)
Citation preview
About Me• Author of:
• Guide to HVAC Design, Construction & Commissioning
• Developer of:
• ACCA RSI Verifier Manual & Certification Program
• NATE HVAC Verifier Training Program
AHRI Data• Region IV
• 80°F indoor cooling test temperature
• 67°F indoor wet bulb temperature
• 90°F outdoor test temperature
• 47°F outdoor heating test temperature
• 17°F outdoor heating test temperature
Code Requirements
Manual J Manual S Manual D
Blueprints & Specifications
Design Temperatures
Orientation
Internal Loads
Ventilation
Infiltration
Duct System
Manual JOEM Performance
Manual JMaterial
Devices
Length
2009 IRC Requirements• Outdoor Thermostat for heat
pumps
• N1103.1.2
• R-8 ducts in attics
• N1103.2.1
• Ducts sealed and tested
• N1103.2.2
• Repairs/replacements of existing systems
• M1202.1
• HVAC sizing based upon Manuals S & J
• M1401.3
• Heat Pump return area
• M1403.1
• Duct Design according to Manual D
• M1601.1
Code Required• Manual J & S, M1401.3 (2009)
• Manual D, M1601.1 (2009)
• Ventilation, M1507.3 (2012)
• 403.5 Mechanical ventilation (Mandatory). Outdoor air intakes and exhausts shall have automatic or gravity dampers that close when the ventilation system is not operating.
Cod
e
System Concept
Load Calculation
Equipment Selection
Air Distribution
Duct Size Calculation
Adjust, Test & Balance
Manual RS
Manual J
Manual T
Manual S
Manual D
Manual J• Indoor Design
Temperatures
• Outdoor Design Temperatures
• Windows
• Walls
• Ceilings
• Floors
Cod
e • Infiltration
• Appliances
• Occupants
• Ducts
• Ventilation
Internal Loads• Appliances
• 1200 Btu/hr
• 2400 Btu/hr
• 3600 Btu/hr
• Occupants
• BR + 1
• 230 Btu/hr x occupants
Cod
e
2009 IRC
• N1103.2.2 Mandatory duct testing
• Post-Construction, 8% leakage to outside or 12% total leakage
• Rough-in, 6% total leakage, 4% if air handler not installed
Cod
e
Systems• Furnace, > 0.50 i.w.c.
• Condensate drain
• Secondary drain pan
• Suction lines insulated
• Combustion air
• Heat pump returns
Cod
e
Equipment Selection• Heating output, Btu/hr < 140% load
• Total Cooling, Btu/hr <115% load
• Sensible capacity
• Latent capacity
• Airhandler CFM
• Auxiliary Heating
Cod
e
Manual D• Sizing Ducts
• Friction Rate
• (pressure drop x 100) / total effective length
• Slide rule
• Static pressure
Cod
e
Manual D• Peak loss = 1967 Btu/hr
• CFM = 1,967 / (1.1 x ∆T)
• ∆T = ℉ between return & supply
• Heat pumps, 25℉
• Furnaces, 55℉
• CFM = 1967 / (1.1 x 25) = 1967 / 27.5 = 72
• CFM = 1967 / (1.1 x 55) =
Cod
e
Manual D• Peak gain = 1189 Btu/hr
• Sensible gain = 932 Btu/hr
• Latent gain = 257 Btu/hr
• SHR = 932 / 1189 = 0.78
• CFM = 932 / (1.1 x ∆T)
• ∆T = ℉ between return & supply
• SHR < 0.80, 21℉
• CFM = 932 / (1.1 x 21) = 932 / 23.1 =
< 0.80 21℉
0.80 - 0.85 19℉
> 0.85 17℉Cod
e
Manual D• Required under IRC M1601.1
• Implies room-by-room load calculation must be performed
• CFM
• SHR
• ΔT supply-return
• Sensible load
• Friction rate
• Pressure drop x 100 / total effective length
Cod
e
Supply Duct Sizing
• What temperature does the air need to be to meet the load?
• How many CFM of air must be delivered to meet the load?
• Sensible Load / (1.1 x ΔT)
Return Airflow
• 350 fpm
• Return register face velocity < 400 fpm
• 90º bend between register & airhandler
Sizing Return Ducts• Sized according to Manual D
–Returns should be sized properly
•IRC M1403.1, heat pumps need > 6 sq in / 1,000 Btu/hour capacity (2 ton unit at least 14” duct)
–All areas that are conditioned should have an adequate return path
•And undercutting doors 1” isn’t enough!
Cod
e
Other Sources
• http://www.acca.org/standards/acca-speed-sheets/
• http://www.acca.org/qa/resources/
• RESNET/NATE HVAC Verifier Training & Certification
Brett Dillon CEO
www.thedillongroupinc.com [email protected]