9
Work: HVAC Designs, Inc. // Collection Vol. 1

HVAC Designs Book

Embed Size (px)

Citation preview

Page 1: HVAC Designs Book

Wor

k:HVAC Designs, Inc. // Collection Vol. 1

Page 2: HVAC Designs Book

North

HVAC SCHEDULES + DETAILS

x

SCALE 1/8"=1'-0"1 OF 1

DRAWINGHVAC

CLASSIFICATION : Commercial Add + RemodelCONDITIONED SQ. FT.: 6949PROJECT STATE, ZIP: Temple Terrace FloridaPROJECT ADDRESS: 5903 E 130th AvenuePROJECT NAME: American Youth Academy 6949 w

PERMIT SET8/26/2008

DRAWING DATE

T

H

HVAC SYMBOLS

FMC 603.151 WAY THROW

CEILING REGISTER

FMC 603.152 WAY THROW

REGISTERCEILING

FMC 603.153 WAY THROW

CEILING REGISTER

FMC 603.154 WAY THROW

CEILING REGISTER

FMC 603.15CORNER THROW

CEILING REGISTER

FMC 603.152 WAY THROW

WALL REGISTER

FMC 603.152 WAY THROW

FLOOR REGISTER

AIR FMC 603.15FILTER RETURNFLOOR GRILLE

AIR FMC 603.15FILTER RETURNCEILING GRILLE

AIR FMC 603.15FILTER RETURN

WALL GRILLE

FMC 603.15DUCTED T/A

CEILING GRILLE

FMC 603.15DIRECT T/ A

WALL GRILLE

FMC SECTION 603DUCTWORK

FLEXIBLE

FMC SECTION 603DUCTWORK

RECTANGULAR

SECTION 603BOXES FMC

AIR DISTRIBUTION

FMC SECTION 602PLENUM TRUNK

RETURN AIR

FMC SECTION 602PLENUM TRUNK

SUPPLY AIR

CAP FMC 504ROOF / WALLDRYER VENT

FMC 505 - 506ROOF / WALL CAP

RANGE VENT

ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED

FMC SECTION 606SMOKE DETECTOR

DUCT MOUNTED

FEC 13-613ABOVE FLOOR

THERMOSTAT @ 60"

FMC SECTION 307DRAIN TO GRASS

CONDENSATE

PIPING FMC 1101REFRIGERANT

CONTROL /

FMC SECTION 403EF-1 or as NOTED

EXHAUST FAN

FMC SECTION 306ACCESS PANEL

EQUIPMENT

FMC SECTION 307TO DRYWELLCONDENSATE

FMC SECTION 607FIRE DAMPER

DUCT MOUNTED

FMC 603.15CONTROL DAMPER

AIR VOLUME

303 --- 312FMC SECTIONS

STANDHANDLER ONVERTICAL AIR

FMC 303 -- 312AIR DAMPER

ZONE CONTROL

D

R R

DS

FMC 303 -- 312DAMPER

BYPASS AIR

303 -- 312FMC SECTIONS

ON SLABCONDENSING UNIT

ZD

BP

303 --- 312FMC SECTIONS

STRUCTUREFROM

MOUNTHANDLER

HORIZONTAL AIR

303 -- 312FMC SECTIONS

ROOF MOUNTEDPACKAGE UNIT

303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT

30 CFM T/ADOOR

1" UNDERCUT

303 -- 312SECTIONS

FMCHANDLER

AIRDUCTLESS

= DEVICE NECK SIZE

= BRANCH DUCT SIZE

ADJUSTMENTS= AIRFLOW CFM

Walk In Closet

Bedroom

4"

32

8x4

TYPICAL ROOM

DUCTBRANCHTYPICAL

DEVICETYPICAL AIR

BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR

E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE

O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN

S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT

ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN

D

HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.

IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND

HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DDRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING

HVAC NOTES

Class

Corridor 1

Locker G

Restroom G Mech Locker B

Office

Reading

Computers

Media Electric Office 102 Office 101

Server

Break

Office 121 Office 123 Office 125

Office 122

Lobby

22x22,9",199 CFM22x22,9",199 CFM

22x22,9",199 CFM

22x22,9",199 CFM

22x22,8",171 CFM

22x22,8",171 CFM

22x22,6",97 CFM

8x4,4",51 CFM

22x22,9",263 CFM

22x22,8",171 CFM

22x22,8",161 CFM

22x22,8",161 CFM

22x22,8",161 CFM

22x22,9",263 CFM

22x22,9",300 CFM22x22,9",206 CFM

22x22,9",206 CFM

22x22,9",238 CFM

22x22,9",238 CFM

22x22,9",300 CFM

22x22,9",300 CFM

22x22,9",171 CFM

22x22,7",140 CFM

22x22,6",103 CFM

22x22,7", 157 CFM

22x22,5",85 CFM

22x22, 6",70 CFM

22x22,8", 174 CFM22x22,9",238 CFM 22x22,9",238 CFM

Corridor 2

22x22,9", 266 CFM

22x22,9", 266 CFM

Restroom

Restroom B

22x22,5",88 CFM

Corridor 3

22x22, 18", -794 22x22,18",-686

22x22,5",81 CFM

8x4,4",29 CFM

22x22, 14", -500

22x22, 14", -460

22x22, 14", -520

8x4,4",51 CFM 8x4,4",36 CFM

Corridor 4

22x22,5",67 CFM

22x22,16",-860 CFM

Science

22x22,14",-620 CFM

22x22,8",168 CFM

22x22,8",168 CFM

Office 12022x22,7",-103 CFM

22x22,9", -174 CFM

22x22,8", -157 CFM

22x22,16",-889 CFM

22x22,8", -157 CFM

22x22,7", 157 CFM

22x22,5",86 CFM

Pricipal Office

22x22,6",93 CFM

ON SLAB

CU-5

ABOVE CEILINGMECH ROOM

AHU-1 ABOVE CEILINGMECH ROOM

AHU-3ABOVE CEILINGMECH ROOM

AHU-2

ABOVE CEILINGMECH ROOM

AHU-4

WALL MOUNT

AHU-5NO OCCUPANCY

600 CFM R/A600 CFM S/A

AIR HANDLERDUCTLESS

EF-2VTE

EF-1VTE

ON SLAB

CU-4ON SLAB

CU-1ON SLAB

CU-2

ON SLAB

CU-3

12x16

14x16

24x12

24x12

24x12 24x12

24x12

24x12

24x12

24x18

24x18

24x18

24x18

24x12

14x12 14x12 10x12

14x1210x12 8x12

12x16

14x12

16x12

10x12

6x12

16x16,9",-300 CFM

16x16, 9",-300 CFM

12x12,7",-125 CFM16x16,9",-300 CFM

16x16,9",-200 CFM10x10 10x14 10x14 10x12

EF-3VTE

300 MAX CFMDOOR MOUNT

GRILLE - WALL /TRANSFER AIR

TYPICAL (x6) 16x16

14x12

VTE,FILTER,SET TO 368 CFMTYPICAL (x4) 9" FRESH AIR DUCT

FL BERS #884813-885-2258

HVAC DesignsNeil Fimbel

Designed By:

EXHAUST FAN SCHEDULE

FAN MARK: EF-1 EF-2 EF-3MANUFACTURER: NUTONE NUTONE GREENHECK

MODEL NUMBER: 690 QT-200 CSP-264

FAN TYPE: EXHAUST EXHAUST INLINE EXHAUST

FAN CFM: 50 200 1225

TOTAL PRESSURE: 0.25 .25 .5

FAN VOLTAGE: 120/1/60 120/1/60 120 / 1 / 60

FAN AMPERAGE: 0.5 1.0 7.8

FAN DIMEN LWH: 9X11X8 14X10X9 24X14X14

DUCT OUTLET SIZE: 3 3.25X10 TO 7 19X8

DUCT INLET SIZE: 12X11 15X11 23X13

FAN WEIGHT: 10 14 59

NOTES: 1,2 1,3 1,2

1 = VENT TO EXTERIOR 3 = WALL SWITH CONTROL

2 = INTERLOCK WITH LIGHTS

TRANE EQUIPMENTAIR HANDLER MARK: AHU-1,2,3,4UNIT MODEL NUMBER: TWE065E

UNIT DIMEN H/W/D: 63X26X21

UNIT WEIGHT: 218

SUPPLY PLENUM SIZE : 24X12

RETURN PLENUM SIZE : 24X18

SUPPLY FAN CFM / SP : 1800 / .40

SUPPLY FAN H/P : 1

OUTDOOR AIR CFM: 368

UNIT PHASE / HERTZ: 1 / 60

UNIT VOLTAGE: 208 / 240

HEATER KW: 7.2 / 9.6

HEATER BREAKER: 50 / 60

CONDENSER MARK: CU-1,2,3,4NOMINAL A/C TONS : 5

UNIT MODEL NUMBER: 2TTR4060A

UNIT VOLTAGE: 208/230/ 1 / 60

UNIT MCA / BREAKER: 34 / 50

UNIT DIMEN H/W/D: 46.4X35.1X38.7

UNIT WEIGHT: 279

TOTAL COOLING BTUH: 61,000

SENS. COOLING BTUH: 44,500

LAT. COOLING BTUH: 16,500

TOTAL HEATING BTUH: 34,120

SENSIBLE HEAT % 0.73

SEER: 14

THERMOSTAT MODEL: T8411R1002

NOTES: ALTERNATE BRAND EQUIPMENT WITH

EQUAL PERFORMANCE ARE ACCEPTABLE.

SUBMIT PERFORMANCE DATA FOR APPROVAL.

WALL

FLOOR

FMC 1101 - MAY ALSO ROUTE BELOW SLABREFRIGERANT PIPING + CONTROL WIRING

GRADEEQUIPMENT SLAB

FMC 301.13FASTENER

FMC 303CONDENSING UNIT

PIPE COVER - MAY MOUNT INTERIOR

CONDENSING UNIT DETAIL

1101CONTROL WIRING FMCREFRIGERANT PIPING +

HORIZONTAL AIR HANDLER DETAIL

FMC 401DUCT

AIR* FRESH

TOP CHORDSUSPEND FROM

1/2 THREADED ROD

FMC 303AIR HANDLER

SUPPLY AIR DUCT FMC 601FMC 601

RETURN DUCT

CONDENSATE DRAIN FMC 307

* ACCESS PANEL FMC 306.3

* CEILING

SWITCH FMC 301.2.3AUX. DRAIN PAN + FLOAT

DRAWING FOR EXACT CONFIGURATION.* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN

BUILDING AIR BALANCE SCHEDULE

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

1 Class 17 > 3 HRS 797 795 0 255

1 Science 17 > 3 HRS 686 685 0 255

1 Corridor 1 0 N/A 97 0 0 0

1 Locker G 0 N/A 51 0 300 0

1 Restroom G 0 N/A 88 0 300 0

1 Restroom B 0 N/A 81 0 300 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

2 Mech 0 > 3 HRS 51 0 0 0

2 Locker B 0 N/A 36 0 325 0

2 Restroom 0 N/A 29 0 50 0

2 Lobby 0 N/A 535 520 0 0

2 Office 2 > 3 HRS 527 500 0 40

2 Reading 17 > 3 HRS 485 460 0 255

2 Corridor 2 0 N/A 137 0 0 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

3 Media 17 > 3 HRS 900 860 0 255

3 Electric 0 N/A 67 67 T/A 0 0

3 Office 102 1 > 3 HRS 336 620 0 20

3 Office 101 1 > 3 HRS 412 0 0 20

3 Corridor 3 0 N/A 85 0 0 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

4 Computers 17 > 3 HRS 955 889 0 255

4 Break 0 N/A 86 86 T/A 0 0

4 Office 120 1 > 3 HRS 93 93 T/A 0 20

4 Office 121 1 > 3 HRS 157 157 0 20

4 Office 123 1 > 3 HRS 157 157 0 20

4 Office 125 1 > 3 HRS 174 174 0 20

4 Pricipal 1 > 3 HRS 103 103 0 20

4 Office 122 1 > 3 HRS 70 70 T/A 0 20

4 Corridor 4 0 N/A 5 0 0 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

5 SERVER 0 N/A 600 405 200 0

BUILDING TOTALS 95 > 3 HRS 7800 6325 1475 1475

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

BUILDING VENTILATION CALCULATION

TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / PERSON OR SQ FOOT

PEAK Classrooms 85 1.00 15 15 1275 15

PEAK Office 10 1.00 20 20 200 20

BUILDING TOTALS 95 1475

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

GWB, PROVIDE ACCESSINSULATION + SEALEDROOM IN ATTIC, R-19

ENCLOSED MECHANICALHIGH WALL- CORRIDOR

FROM BREAKTRANSFER AIR

DUCT AND 22x22 GRILLEFOR OFFICE - USE 7" S/A

FOR COMPUTER SERVERSTHIS ROOM IS USEDOPTIONAL ONLY IF

NOTE: AHU-5, CU-5 ARE

ENVIRO AIR EQUIPMENT

AIR HANDLER MARK: AHU-5UNIT MODEL NUMBER: ACWH1800

NOMINAL A/C TONS : 1.5

SUPPLY PLENUM SIZE : DUCTLESS

RETURN PLENUM SIZE : DUCTLESS

SUPPLY FAN CFM / SP : 600 / .40

SUPPLY FAN H/P : .35

OUTDOOR AIR CFM: 0

UNIT VOLTAGE: 200/230/ 1 / 60

UNIT DIMEN LWH: 42X12X8

UNIT WEIGHT: 29

HEATSTRIP KW: 2.5

CONDENSER MARK: CU-5UNIT MODEL NUMBER: CCW18000

UNIT VOLTAGE: 200/230/ 1 / 60

UNIT MCA / BREAKER: 12.5 / 20

UNIT DIMEN LWH: 35X12X28

UNIT WEIGHT: 156

TOTAL COOLING BTUH: 18,400

SENS. COOLING BTUH: 11,200

LAT. COOLING BTUH: 7,200

TOTAL HEATING BTUH: 17,000

SEER: 13

THERMOSTAT MODEL:

Page 3: HVAC Designs Book

North

BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR

E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE

O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN

S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT

ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN

HVAC SYMBOLS

FMC 603.151 WAY THROW

CEILING REGISTER

FMC 603.152 WAY THROW

CEILING REGISTER

FMC 603.153 WAY THROW

CEILING REGISTER

FMC 603.154 WAY THROW

CEILING REGISTER

FMC 603.15CORNER THROW

CEILING REGISTER

FMC 603.152 WAY THROW

WALL REGISTER

FMC 603.152 WAY THROW

FLOOR REGISTER

AIR FMC 603.15FILTER RETURNFLOOR GRILLE

AIR FMC 603.15FILTER RETURNCEILING GRILLE

AIR FMC 603.15FILTER RETURN

WALL GRILLE

FMC 603.15DUCTED T/A

CEILING GRILLE

FMC 603.15DIRECT T/ A

WALL GRILLE

FMC SECTION 603DUCTWORKFLEXIBLE

FMC SECTION 603DUCTWORK

RECTANGULAR

SECTION 603BOXES FMC

AIR DISTRIBUTION

FMC SECTION 602PLENUM TRUNK

RETURN AIR

FMC SECTION 602PLENUM TRUNK

SUPPLY AIR

CAP FMC 504ROOF / WALLDRYER VENT

FMC 505 - 506ROOF / WALL CAP

RANGE VENT

ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED

FMC SECTION 606SMOKE DETECTOR

DUCT MOUNTED

FEC 13-613ABOVE FLOOR

THERMOSTAT @ 60"

FMC SECTION 307DRAIN TO GRASS

CONDENSATE

PIPING FMC 1101REFRIGERANT

CONTROL /

FMC SECTION 403EF-1 or as NOTED

EXHAUST FAN

FMC SECTION 306ACCESS PANEL

EQUIPMENT

FMC SECTION 307TO DRYWELLCONDENSATE

FMC SECTION 607FIRE DAMPER

DUCT MOUNTED

FMC 603.15CONTROL DAMPER

AIR VOLUME

303 --- 312FMC SECTIONS

HANDLER ON STANDVERTICAL AIR

FMC 303 -- 312AIR DAMPER

ZONE CONTROL

DD

R R

T

DS

FMC 303 -- 312DAMPER

BYPASS AIR

303 -- 312FMC SECTIONS

ON SLABCONDENSING UNIT

ZD

BP

303 --- 312FMC SECTIONS

FROM STRUCTUREHANDLER MOUNTHORIZONTAL AIR

303 -- 312FMC SECTIONS

ROOF MOUNTEDPACKAGE UNIT

303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT

30 CFM T/A1" UNDERCUT DOOR

H

303 -- 312FMC SECTIONS

HANDLERDUCTLESS AIR

= DEVICE NECK SIZE

= BRANCH DUCT SIZE

ADJUSTMENTS= AIRFLOW CFM

Walk In Closet

Bedroom

4"

32

8x4

TYPICAL ROOM

DUCTBRANCHTYPICAL

DEVICETYPICAL AIR

SCALE 1/8"=1'-0"1 OF 1

DRAWINGHVAC

CLASSIFICATION :CONDITIONED SQ. FT.:PROJECT STATE, ZIP:PROJECT ADDRESS:

PROJECT NAME:

PERMIT SET9/19/2008

DRAWING DATE

New Commercial13352Tampa Florida14400 N Florida AveRose Lake Plaza Phase 2

FL BERS C#8508FL BERS R#884

813-885-2258HVAC Designs

Neil FimbelDesigned By:

Unit J1

Toilet 10

Toilet 9

Unit H

Toilet 8

Unit G Unit F

Toilet 6

Unit A2

Unit E

Toilet 5

Unit D Unit C Unit B

HVAC NOTES

SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.

IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT INTERIOR DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND

HVAC SYMBOL, HVAC CONTRACTOR MUST REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING

Toilet 1

Toilet 3

Unit A1

22x22,10",300 CFM

22x22,10",300 CFM22x22,10",300 CFM

22x22,10",300 CFM

12" O/A DUCT

18x18 +480 CFM O/A

22x22,10",287 CFM

22x22,10",287 CFM

Toilet 2

22x22,10",287 CFM

22x22,10",287 CFM

16"

(2) 9" O/A @ 240 CFM

(2) 24x18 R/A -960 CFM

16"

240 CFMDUCT @(2) 9" O/A

B

2 STG

ON STAND

AHU-1B

ON STAND

AHU-1A

8x4,4",53 CFM

B

22x22,10",312 CFM

22x22,10",312 CFM

22x22,10",312 CFM

22x22,10",312 CFM22x22,10",312 CFM

30x20 R/A -1240 CFM

16"

18x18 + 360 CFM O/A

ON STAND

AHU-2

HVAC DUCT SYSTEMS ARE TYPICAL FOR UNITS B,C,D,E,F

ON STANDAHU-4

ON STANDAHU-3

8x4,4",42 CFM

22x22,10",310 CFM

22x22,10",310 CFM

22x22,10",310 CFM 22x22,10",310 CFM

22x22,10",310 CFM

8x4,4",48 CFM

B

16"

ON STANDAHU-5

ON STANDAHU-6

Toilet 7

18x18 +360 CFM O/A

EF-1VTE

EF-1VTE

EF-1VTE

ON STAND

AHU-7

10" O/A DUCT

18x18 + 420 CFM O/A

10" O/A DUCT

10" O/A DUCT

LOBBYUNCONDITIONED

22x22,10",326 CFM

22x22,10",326 CFM

22x22,10",326 CFM

22x22,10",326 CFM

22x22,10",326 CFM

8x4,4",42 CFM

18"

C

30x20 R/A -1600 CFM

ON STAND

AHU-8

30x20 R/A - 1240 CFM

22x22,10",311 CFM

22x22,10",311 CFM

22x22,10",311 CFM

22x22,10",311 CFM

8x4,4",47 CFM

EF-1VTE

30x20 R/A -1200 CFM

ON STAND

AHU-9

16"

18x18 + 400 CFM O/A

22x22,10",311 CFM

16"

22x22,10",284 CFM

22x22,10",284 CFM

22x22,10",284 CFM

22x22,10",284 CFM

8x4,5",63 CFM

(2) 24x18 R/A - 960 CFM

B

16"

2 STG

B

10" O/A DUCT

12" O/A DUCT

EF-1VTE

22x22,10",300 CFM22x22,10",300 CFM

22x22,10",300 CFM

22x22,10",300 CFM

18x18 +480 CFM O/A

Toilet 4

B

B

+ BACKDRAFT DAMPER16x16 480 CFM 10"RELIEF AIR VENT

+ BACKDRAFT DAMPER16x16 480 CFM 10"RELIEF AIR VENT

+ BACKDRAFT DAMPER16x16 360 CFM 10"RELIEF AIR VENT

+ BACKDRAFT DAMPER16x16 360 CFM 10"RELIEF AIR VENT

+ BACKDRAFT DAMPER16x16 420 CFM 10"RELIEF AIR VENT

+ BACKDRAFT DAMPER16x16 400 CFM 10"RELIEF AIR VENT

CU-1BCU-2

RAISED PLATFORM

CU-1ACU-3CU-4CU-5

PLATFORMRAISED

CU-10A

CU-9

CU-10B

CU-8

CU-7

CU-6

Unit J2

Unit I

FROM PARKING10' MINIMUM

22x22,10",326 CFM

FROM PARKING10' MINIMUM

ON STAND

AHU-10B

ON STAND

AHU-10A

AMERICAN STANDARD SPLIT SYSTEM EQUIPMENT SCHEDULE

AIR HANDLER MARK: AHU-1A,1B,10A,10B AHU-2,3,4,5,6,7 AHU-8 AHU-9UNIT MODEL NUMBER: 2TEC3F36A 2TEC3F48A 2TEC3F60A 2TEC3F48A

UNIT DIMEN H/W/D: 46.5X24X23.5 59.5X26X23.5 59.5X26X23.5 59.5X26X23.5

UNIT WEIGHT: 125 151 155 151

SUPPLY PLENUM SIZE : 12.02X19.22 12.02X21.22 12.02X21.22 12.02X21.22

RETURN PLENUM SIZE : 18.07X19.5 18.07X21.5 18.07X21.5 18.07X21.5

SUPPLY FAN CFM / SP : 1200 / .40 1600 / .40 2000 / .40 1600 / .40

SUPPLY FAN H/P : 1/3 1/2 1 1/2

OUTDOOR AIR CFM: 240 360 420 400

UNIT PHASE / HERTZ: 1 / 60 1 / 60 1 / 60 1 / 60

UNIT VOLTAGE: 208 / 240 208 / 240 208 / 240 208 / 240

HEATER KW: 5.76 / 7.68 7.2 / 9.6 7.2 / 9.6 7.2 / 9.6

HEATER BREAKER: 40 / 45 50 / 60 50 / 60 50 / 60

CONDENSER MARK: CU-1A,1B,10A,10B CU-2,3,4,5,6,7 CU-8 CU-9NOMINAL A/C TONS : 3 4 5 4

UNIT MODEL NUMBER: 2TTR3036A 2TTR3048A 2TTR3060A 2TTR3048A

UNIT VOLTAGE: 208/230/ 1 / 60 208/230/ 1 / 60 208/230/ 1 / 60 208/230/ 1 / 60

UNIT MCA / BREAKER: 18 / 30 25 / 40 32 / 50 25 / 40

UNIT DIMEN H/W/D: 38X30.1X33 46.4X35.1X38.7 46.4X35.1X38.7 46.4X35.1X38.7

UNIT WEIGHT: 194 273 269 273

TOTAL COOLING BTUH: 34,200 47,000 58,000 47,000

SENS. COOLING BTUH: 25,400 33,800 40,000 33,800

LAT. COOLING BTUH: 8,800 13,200 18,000 13,200

TOTAL HEATING BTUH: 25,590 34,120 34,120 34,120

SENSIBLE HEAT % 0.74 0.72 0.69 0.72

SEER: 13 13 13.5 13

THERMOSTAT MODEL: T8411R1002 T8411R1002 T8411R1002 T8411R1002

NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE.

SUBMIT PERFORMANCE DATA FOR APPROVAL.

CYCLE EQUIPMENT OFF DURING UNOCCUPIED HOURS.

EXHAUST FAN SCHEDULE

FAN MARK: EF-1MANUFACTURER: NUTONE

MODEL NUMBER: QT-80

FAN TYPE: EXHAUST

FAN CFM: 80

TOTAL PRESSURE: .25

FAN VOLTAGE: 120/1/60

FAN AMPERAGE: .7

FAN DIMEN LWH: 9X9X6

DUCT OUTLET SIZE: 4

DUCT INLET SIZE: 10X10

FAN WEIGHT: 12

NOTES: 1,2

1 = VENT TO EXTERIOR

2 = INTERLOCK WITH LIGHTS

BUILDING AIR BALANCE SCHEDULE

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST / RELIEF AIR CFM FRESH AIR CFM

1 UNIT A1 6 > 3 HRS 1200 960 240 240X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

2 UNIT B 9 > 3 HRS 1558 1240 360 360

2 TOILET 0 N/A 42 0 80 SWITCHED 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

3 UNIT C 9 > 3 HRS 1558 1240 360 360

3 TOILET 0 N/A 42 0 80 SWITCHED 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

4 UNIT D 9 > 3 HRS 1558 1240 360 360

4 TOILET 0 N/A 42 0 80 SWITCHED 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

5 UNIT E 9 > 3 HRS 1558 1240 360 360

5 TOILET 0 N/A 42 0 80 SWITCHED 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

6 UNIT F 9 > 3 HRS 1558 1240 360 360

6 TOILET 0 N/A 42 0 80 SWITCHED 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

7 UNIT G 9 > 3 HRS 1552 1240 360 360

7 TOILET 0 N/A 48 0 80 SWITCHED 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

8 UNIT H 12 > 3 HRS 1958 1600 400 400

8 TOILET 0 N/A 42 0 80 SWITCHED 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

9 UNIT I 10 > 3 HRS 1553 1200 400 400

9 TOILET 0 N/A 47 0 80 SWITCHED 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

10 UNIT J1 5 > 3 HRS 1137 960 240 240

10 TOILET 0 N/A 63 0 80 SWITCHED 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

11 UNIT A2 6 > 3 HRS 1147 960 240 240

11 TOILET 0 N/A 53 0 80 SWITCHED 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

12 UNIT J2 4 > 3 HRS 1200 960 240 240

BUILDING TOTALS 97 > 3 HRS 18000 14080 3920 3920

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

BUILDING VENTILATION CALCULATION

TIME CLASSIFICATION OCCS / SF DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / SF

PEAK Mechant (usable sq ft) 97 / 13066 1.00 0.3 0.3 3919.8 0.3

BUILDING TOTALS 3920 PROVIDED

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

HANDLER DETAILVERTICAL AIR

FMC 401AIR DUCT* FRESH

FMC 1101WIRING

+ CONTROLPIPING

REFRIGERANT

FMC 303AIR HANDLER

FMC 601AIR DUCTSUPPLY

FMC 307DRAIN

CONDENSATE

* CEILING

FLOOR

STANDAIR HANDLER

DRAWING FOR EXACT CONFIGURATION.* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN

WALL

FLOOR

FMC 1101REFRIGERANT PIPING + CONTROL WIRING

PLATFORMEQUIPMENT

FMC 301.13FASTENER

FMC 303CONDENSING UNIT

PIPE COVER

CONDENSING UNIT DETAIL

RAIL

Page 4: HVAC Designs Book

SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.

IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND

HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING

HVAC NOTES

North

HVAC SCHEDULES + DETAILS

x

BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR

E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE

O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN

S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT

ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN

HVAC SYMBOLS

FMC 603.151 WAY THROW

CEILING REGISTER

FMC 603.152 WAY THROW

CEILING REGISTER

FMC 603.153 WAY THROW

CEILING REGISTER

FMC 603.154 WAY THROW

CEILING REGISTER

FMC 603.15CORNER THROW

CEILING REGISTER

FMC 603.152 WAY THROW

WALL REGISTER

FMC 603.152 WAY THROW

FLOOR REGISTER

AIR FMC 603.15FILTER RETURNFLOOR GRILLE

AIR FMC 603.15FILTER RETURNCEILING GRILLE

AIR FMC 603.15FILTER RETURN

WALL GRILLE

FMC 603.15DUCTED T/A

CEILING GRILLE

FMC 603.15DIRECT T/ A

WALL GRILLE

FMC SECTION 603DUCTWORKFLEXIBLE

FMC SECTION 603DUCTWORK

RECTANGULAR

SECTION 603BOXES FMC

AIR DISTRIBUTION

FMC SECTION 602PLENUM TRUNK

RETURN AIR

FMC SECTION 602PLENUM TRUNK

SUPPLY AIR

CAP FMC 504ROOF / WALLDRYER VENT

FMC 505 - 506ROOF / WALL CAP

RANGE VENT

ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED

FMC SECTION 606SMOKE DETECTOR

DUCT MOUNTED

FEC 13-613ABOVE FLOOR

THERMOSTAT @ 60"

FMC SECTION 307DRAIN TO GRASS

CONDENSATE

PIPING FMC 1101REFRIGERANT

CONTROL /

FMC SECTION 403EF-1 or as NOTED

EXHAUST FAN

FMC SECTION 306ACCESS PANEL

EQUIPMENT

FMC SECTION 307TO DRYWELLCONDENSATE

FMC SECTION 607FIRE DAMPER

DUCT MOUNTED

FMC 603.15CONTROL DAMPER

AIR VOLUME

303 --- 312FMC SECTIONS

HANDLER ON STANDVERTICAL AIR

FMC 303 -- 312AIR DAMPER

ZONE CONTROL

D D

R R

T

DS

FMC 303 -- 312DAMPER

BYPASS AIR

303 -- 312FMC SECTIONS

ON SLABCONDENSING UNIT

ZD

BP

303 --- 312FMC SECTIONS

FROM STRUCTUREHANDLER MOUNTHORIZONTAL AIR

303 -- 312FMC SECTIONS

ROOF MOUNTEDPACKAGE UNIT

303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT

30 CFM T/A1" UNDERCUT DOOR

H

303 -- 312FMC SECTIONS

HANDLERDUCTLESS AIR

= DEVICE NECK SIZE

= BRANCH DUCT SIZE

ADJUSTMENTS= AIRFLOW CFM

Walk In Closet

Bedroom

4"

32

8x4

TYPICAL ROOM

DUCTBRANCHTYPICAL

DEVICETYPICAL AIR

1 OF 1DRAWING

HVAC

CLASSIFICATION :CONDITIONED SQ. FT.:PROJECT STATE, ZIP:PROJECT ADDRESS:

PROJECT NAME:

SCALE 1/4"=1'-0"

Permit Set9/12/2008

DRAWING DATE

New Residence1991

HDS Model Residence 1964 s

FL BERS R#884813-885-2258

HVAC DesignsNeil Fimbel

Designed By:

Dining / Living

M Bed

M Wic

Bed 4

Lav

Bed 3Bed 2

Stair / OtbPowder

Laundry

Foyer

Family / Nook / KitchenM Bath

M Toilet

12x8,116 CFM

12x8,116 CFM

8x4,4",24 CFM

8x4,4",31 CFM

12x6,6",113 CFM

12x8,8",116 CFM

12x6,6",106 CFM

12x6,6",106 CFM

12x8,334 CFM

8x4,4",13 CFM

10x6,6",99 CFM

8x4,4",5 CFM

14"

10"

14"

14"

14"

A

ON SLABCU-1

4" DRYER VTE

7" RANGE VTE

ROOM R-19 ISULIN SEALED MECHABOVE CEILING

AHU-1

E

ZD ZD BP

WYE

8x4,4",43 CFM

ATTICACCESS TO

DUCTS DOWN

Bath 2

12x12,9",-215 CFM

12x12,7",-99 CFM 12x12,7",-91 CFM

12x12,7",-89 CFM

12"-500 CFM@ CHASE18x18 R/A

10x6,5",77 CFM

10x6,5",77 CFM

10x6,6",91 CFM

8x4,4",35 CFM

8x4,4",5 CFM

18x18, 12",-606 CFM

10"

10x6,6",89 CFM

A

A

FLOORFIRST

FLOORSECOND

12" BYPASS

TRANE HEAT PUMPAIR HANDLER MARK: AHU-1UNIT MODEL NUMBER: 2TEC3F48A

UNIT DIMEN H/W/D: 59.5X26X23.5

UNIT WEIGHT: 151

SUPPLY PLENUM SIZE : 12.02X21.22

RETURN PLENUM SIZE : 18.07X21.5

SUPPLY FAN CFM / SP : 1600 / .40

SUPPLY FAN H/P : 1/2

OUTDOOR AIR CFM: 0

UNIT PHASE / HERTZ: 1 / 60

UNIT VOLTAGE: 208 / 240

HEATER KW: 7.2 / 9.6

HEATER BREAKER: 50 / 60

CONDENSER MARK: CU-1NOMINAL A/C TONS : 4

UNIT MODEL NUMBER: 2TWR3048A

UNIT VOLTAGE: 208/230/ 1 / 60

UNIT MCA / BREAKER: 25 / 40

UNIT DIMEN H/W/D: 46.4X35.1X38.7

UNIT WEIGHT: 279

TOTAL COOLING BTUH: 46,000

SENS. COOLING BTUH: 33,200

LAT. COOLING BTUH: 12,800

TOTAL HEATING BTUH: 43,500

SENSIBLE HEAT % 0.72

SEER / HSPF : 13 / 8.4

THERMOSTAT MODEL: PROGRAM

NOTES: ALTERNATE BRAND EQUIPMENT WITH

EQUAL PERFORMANCE ARE ACCEPTABLE.

ZONING SHOWN PER MANUAL J

EXHAUST FAN SCHEDULE FAN MARK: EF-1MANUFACTURER: NUTONE

MODEL NUMBER: 690

FAN TYPE: EXHAUST

FAN CFM: 50

TOTAL PRESSURE: 0.25

FAN VOLTAGE: 120/1/60

FAN AMPERAGE: 0.5

FAN DIMEN LWH: 9X11X8

DUCT OUTLET SIZE: 3

DUCT INLET SIZE: 12X11

FAN WEIGHT: 10

NOTES: 1,2

1 = VENT TO EXTERIOR

2 = INTERLOCK WITH LIGHTS

FMC 1101+ CONTROL WIRING

REFRIGERANT PIPING

HORIZONTAL AIR HANDLER DETAIL

FMC 401DUCTAIR

* FRESH

TOP CHORDSUSPEND FROM

1/2 THREADED ROD

FMC 303AIR HANDLER

SUPPLY AIR DUCT FMC 601FMC 601

RETURN DUCT

CONDENSATE DRAIN FMC 307

* ACCESS PANEL FMC 306.3

* CEILING

SWITCH FMC 301.2.3AUX. DRAIN PAN + FLOAT

DRAWING FOR EXACT CONFIGURATION.* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN

WALL

FLOOR

FMC 1101 - MAY ALSO ROUTE BELOW SLABREFRIGERANT PIPING + CONTROL WIRING

GRADEEQUIPMENT SLAB

FMC 301.13FASTENER

FMC 303CONDENSING UNIT

PIPE COVER - MAY MOUNT INTERIOR

CONDENSING UNIT DETAIL

MARKBOX

A

B

C

D

E

F

DIMENSIONS - INCHES

N/A

H L W2W

21

17

13

*

N/A

N/A

**

13

13

13

17

1717

2121

21

18

18

18

18

18

18

= CAP SIZE EQUALS OUTLET DUCT + 1"

TRI - BOX REDUCER - BOX

WW

W2

H

L

H

L

*

*

Page 5: HVAC Designs Book

HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.

IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND

HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DDRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING

HVAC NOTES

North

HVAC SCHEDULES + DETAILS

x

BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR

E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE

O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN

S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT

ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN

HVAC SYMBOLS

FMC 603.151 WAY THROW

CEILING REGISTER

FMC 603.152 WAY THROW

CEILING REGISTER

FMC 603.153 WAY THROW

CEILING REGISTER

FMC 603.154 WAY THROW

CEILING REGISTER

FMC 603.15CORNER THROW

CEILING REGISTER

FMC 603.152 WAY THROW

WALL REGISTER

FMC 603.152 WAY THROW

FLOOR REGISTER

AIR FMC 603.15FILTER RETURNFLOOR GRILLE

AIR FMC 603.15FILTER RETURNCEILING GRILLE

AIR FMC 603.15FILTER RETURN

WALL GRILLE

FMC 603.15DUCTED T/A

CEILING GRILLE

FMC 603.15DIRECT T/ A

WALL GRILLE

FMC SECTION 603DUCTWORKFLEXIBLE

FMC SECTION 603DUCTWORK

RECTANGULAR

SECTION 603BOXES FMC

AIR DISTRIBUTION

FMC SECTION 602PLENUM TRUNK

RETURN AIR

FMC SECTION 602PLENUM TRUNK

SUPPLY AIR

CAP FMC 504ROOF / WALLDRYER VENT

FMC 505 - 506ROOF / WALL CAP

RANGE VENT

ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED

FMC SECTION 606SMOKE DETECTOR

DUCT MOUNTED

FEC 13-613ABOVE FLOOR

THERMOSTAT @ 60"

FMC SECTION 307DRAIN TO GRASS

CONDENSATE

PIPING FMC 1101REFRIGERANT

CONTROL /

FMC SECTION 403EF-1 or as NOTED

EXHAUST FAN

FMC SECTION 306ACCESS PANEL

EQUIPMENT

FMC SECTION 307TO DRYWELLCONDENSATE

FMC SECTION 607FIRE DAMPER

DUCT MOUNTED

FMC 603.15CONTROL DAMPER

AIR VOLUME

303 --- 312FMC SECTIONS

HANDLER ON STANDVERTICAL AIR

FMC 303 -- 312AIR DAMPER

ZONE CONTROL

D D

R R

T

DS

FMC 303 -- 312DAMPER

BYPASS AIR

303 -- 312FMC SECTIONS

ON SLABCONDENSING UNIT

ZD

BP

303 --- 312FMC SECTIONS

FROM STRUCTUREHANDLER MOUNTHORIZONTAL AIR

303 -- 312FMC SECTIONS

ROOF MOUNTEDPACKAGE UNIT

303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT

30 CFM T/A1" UNDERCUT DOOR

H

303 -- 312FMC SECTIONS

HANDLERDUCTLESS AIR

= DEVICE NECK SIZE

= BRANCH DUCT SIZE

ADJUSTMENTS= AIRFLOW CFM

Walk In Closet

Bedroom

4"

32

8x4

TYPICAL ROOM

DUCTBRANCHTYPICAL

DEVICETYPICAL AIR

1 OF 1DRAWING

HVAC

CLASSIFICATION :CONDITIONED SQ. FT.:PROJECT STATE, ZIP:PROJECT ADDRESS:

PROJECT NAME:

SCALE 1/4"=1'-0"

Permit Set8/14/2008

DRAWING DATE

Restaurant Renovation1320Boynton Beach Florida, 33461

Marcos Pizza Renov Boynton Beach 1320 e

FL BERS #884813-885-2258

HVAC DesignsNeil Fimbel

Designed By:

Cooler

Kitchen

Restroom

Order - Cashier

22x22,10",320 CFM

22x22,10",320 CFM

22x22,10",320 CFM

22x22,10",320 CFM

22x22,10",320 CFM

22x22,10",320 CFM

8x4,4",18 CFM

22x22, 10",316 CFM

22x22, 10",316 CFM

22x22, 10",316 CFM22x22, 10",316 CFM

22x22, 10",316 CFM

ON ROOFEXISTING

RTU-2

EF-1VTE

A/C EQUIPMENTCFM MUA BY

BY OTHERS 380KITCHEN HOOD

(2) 22x22, 16", -920 CFM EA

ON ROOF

RTU-1

TYPICAL OF 2TO GUTTER / GRASSCONDENSATE DRAIN

-1380 CFM22x22, 16"

20x12

18x12

12x12 12x12

24x12

ROOFTOP EQUIPMENT SCHEDULE

PACKAGE UNIT MARK: RTU-1 RTU-2UNIT MANUFACTURER: TRANE EXISTING

UNIT MODEL NUMBER: THC063A3 THC043A3

NOMINAL A/C TONS : 5 4

UNIT CONFIGURATION: DOWNFLOW DOWNFLOW

UNIT DIMEN H/W/D: 37X45X70 37X45X70

UNIT WEIGHT: 682 669

SUPPLY PLENUM SIZE : 17X15 17X15

RETURN PLENUM SIZE : 23X14 23X14

SUPPLY FAN CFM / SP : 2000 / .4 1600 / .4

SUPPLY FAN H/P : 1 1

OUTDOOR AIR CFM: 160 220

UNIT PHASE / HERTZ: 3/60 3/60

UNIT VOLTAGE: 208/230 208/230

UNIT MCA: 28.8 22.6

UNIT MAX BREAKER: 40 35

HEATER KW: 9/12 9/12

HEATER MCA: 37.5/42.4 37.5/42.4

HEATER BREAKER: 45/45 40/45

TOTAL COOLING BTUH: 62,400 49,800

SENS. COOLING BTUH: 47,300 39,400

LAT. COOLING BTUH: 15,100 10,400

TOTAL HEATING BTUH: 40,944 40,944

SENS. HEAT % 0.76 0.79

COOLING EFFICIENCY: 13 13

THERMOSTAT MODEL: T8411R1002 T8411R1002

NOTES: ALTERNATE BRAND EQUIPMENT WITH

EQUAL PERFORMANCE ARE ACCEPTABLE.

SUBMIT PERFORMANCE DATA FOR APPROVAL.

EXHAUST FAN SCHEDULE

FAN MARK: EF-1MANUFACTURER: NUTONE

MODEL NUMBER: 690

FAN TYPE: EXHAUST

FAN CFM: 50

TOTAL PRESSURE: 0.25

FAN VOLTAGE: 120/1/60

FAN AMPERAGE: 0.5

FAN DIMEN LWH: 9X11X8

DUCT OUTLET SIZE: 3

DUCT INLET SIZE: 12X11

FAN WEIGHT: 10

NOTES: 1,2

1 = VENT TO EXTERIOR

2 = INTERLOCK WITH LIGHTS

ROOFTOP PACKAGE UNIT DETAIL

CONNECTIONCURB

CURB

601FMC

DUCTS/A

601FMC

DUCTR/A

CONNECTIONDUCT

CONNECTIONEQUIPMENT

FMC 303EQUIPMENTROOFTOP

SPAN 3 JOISTS1/4" THK

2" U CHANNEL X

ROOF

CURB

@ 18" O.C.3/8 BOLT

JOIST

EQUIPMENTROOFTOP

DUCT@ 8" O.C.SCREWS

1/2"

SEALMASTIC

CURB

EQUIPMENTROOFTOP

@ 18"" O.C.OR ANGLE1/4" PLATESCREWS

3/8"

MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOADMECHANICALLY FASTEN AND SEAL DUCTS PER FMC SECTIONS 603 AND 604MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD

BUILDING AIR BALANCE SCHEDULE

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

1 COOLER ROOM 0 N/A 78 0 0 0

1 KITCHEN 5 > 3 HRS 1922 1840 380 CFM @ HOOD 160X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

2 RESTROOM 0 N/A 18 0 50 INTERMITTENT 0

2 ORDER / CASHIER 9 VARIES 1582 1380 0 220X X X X X X X X

BUILDING TOTALS 14 VARIES 3600 3220 380 380

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

BUILDING VENTILATION CALCULATION

TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / PERSON OR SQ FOOT

PEAK Dining / Order 9 1.00 20 20 180 20

PEAK HOOD MUA 0 1.00 125 125 125 0

PEAK Kitchen / Prep 5 1.00 15 15 75 15

BUILDING TOTALS 14 380

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

Page 6: HVAC Designs Book

North

BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR

E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE

O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN

S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT

ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN

HVAC SYMBOLS

FMC 603.151 WAY THROW

CEILING REGISTER

FMC 603.152 WAY THROW

CEILING REGISTER

FMC 603.153 WAY THROW

CEILING REGISTER

FMC 603.154 WAY THROW

CEILING REGISTER

FMC 603.15CORNER THROW

CEILING REGISTER

FMC 603.152 WAY THROW

WALL REGISTER

FMC 603.152 WAY THROW

FLOOR REGISTER

AIR FMC 603.15FILTER RETURNFLOOR GRILLE

AIR FMC 603.15FILTER RETURNCEILING GRILLE

AIR FMC 603.15FILTER RETURN

WALL GRILLE

FMC 603.15DUCTED T/A

CEILING GRILLE

FMC 603.15DIRECT T/ A

WALL GRILLE

FMC SECTION 603DUCTWORKFLEXIBLE

FMC SECTION 603DUCTWORK

RECTANGULAR

SECTION 603BOXES FMC

AIR DISTRIBUTION

FMC SECTION 602PLENUM TRUNK

RETURN AIR

FMC SECTION 602PLENUM TRUNK

SUPPLY AIR

CAP FMC 504ROOF / WALLDRYER VENT

FMC 505 - 506ROOF / WALL CAP

RANGE VENT

ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED

FMC SECTION 606SMOKE DETECTOR

DUCT MOUNTED

FEC 13-613ABOVE FLOOR

THERMOSTAT @ 60"

FMC SECTION 307DRAIN TO GRASS

CONDENSATE

PIPING FMC 1101REFRIGERANT

CONTROL /

FMC SECTION 403EF-1 or as NOTED

EXHAUST FAN

FMC SECTION 306ACCESS PANEL

EQUIPMENT

FMC SECTION 307TO DRYWELLCONDENSATE

FMC SECTION 607FIRE DAMPER

DUCT MOUNTED

FMC 603.15CONTROL DAMPER

AIR VOLUME

303 --- 312FMC SECTIONS

HANDLER ON STANDVERTICAL AIR

FMC 303 -- 312AIR DAMPER

ZONE CONTROL

DD

R R

T

DS

FMC 303 -- 312DAMPER

BYPASS AIR

303 -- 312FMC SECTIONS

ON SLABCONDENSING UNIT

ZD

BP

303 --- 312FMC SECTIONS

FROM STRUCTUREHANDLER MOUNTHORIZONTAL AIR

303 -- 312FMC SECTIONS

ROOF MOUNTEDPACKAGE UNIT

303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT

30 CFM T/A1" UNDERCUT DOOR

H

303 -- 312FMC SECTIONS

HANDLERDUCTLESS AIR

= DEVICE NECK SIZE

= BRANCH DUCT SIZE

ADJUSTMENTS= AIRFLOW CFM

Walk In Closet

Bedroom

4"

32

8x4

TYPICAL ROOM

DUCTBRANCHTYPICAL

DEVICETYPICAL AIR

HVAC NOTES

SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR CALCULATIONS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION / HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DIAGRAM 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME CONTROL DAMPERS AT ALL ACCESSIBLE BRANCH DUCT TO TRUNKLINE CONNECTIONS, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (VAPOR SEAL + STRAP BOTH DUCT INNER CORE AND DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.

IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT INTERIOR DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND

HVAC SYMBOL, HVAC CONTRACTOR MUST REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING

HVAC SCHEDULES + DETAILS

x

SCALE 1/8"=1'-0"1 OF 1

DRAWINGHVAC

CLASSIFICATION :CONDITIONED SQ. FT.:PROJECT STATE, ZIP:PROJECT ADDRESS:

PROJECT NAME:

PERMIT SET9/28/2008

DRAWING DATE

Commercial Office Renovation7563 Revised 9/28/08Spring Hill Florida (Hernando)14378 Spring Hill Drive14378 Spring Hill Dr Office Renovation

FL BERS C#959FL BERS R#884

813-885-2258HVAC Designs

Neil FimbelDesigned By:

Office ExamReception

Restroom

Restroom

Exam

Consult Exam Exam

Lab

Break

Work Stations

Waiting

Reception

Office

Exam Exam

Reception

Corridor

Exam Exam

Reception

Restroom

Restroom

Waiting

U Restroom

Storage

Exam

Office

Exam

Corridor

Exam

Exam

P Restroom E Restroom

Waiting

22x22,7",124 CFM

22x22,10",347 CFM

22x22,7",130 CFM

22x22,10",347 CFM

8x4,4",31 CFM

22x22,10",347 CFM

22x22,10",347 CFM

22x22,7",129 CFM

22x22,9",257

8x4,4",21 CFM

22x22,6",101 CFM

22x22,6",108 CFM

22x22,6",99 CFM

22x22,5",64 CFM22x22,4",37 CFM

22x22,9",243 CFM

22x22,6",118 CFM

22x22,6",100 CFM

8x4,4",12 CFM

22x22,9",257

22x22,10",307 CFM

22x22,10",307 CFM

22x22,5",82 CFM

22x22,6",105 CFM

22x22,10",332 CFM

22x22,6",93 CFM

22x22,6",120 CFM

22x22,5",64 CFM

22x22,9",253

22x22,10",307 CFM

22x22,10",307 CFM

ON STAND

AHU-1

EF-1VTE

22x22,10", -304

22x22,10",-26122x22,10", -256

22x22,8",-147

22x22,6",-6422x22,6",-64

8x4,4",39 CFM

22x22,10",332 CFM8x4,4",38 CFM

22x22,9",258 CFM 22x22,7",146 CFM 22x22,9",261 CFM 22x22,10",304 CFM

22x22,7",-94

22x22, 14",-680

10x10

14x12

20x1224x12

12x1420x14

DUCT VTE6" FRESH AIR(TYPICAL x7)

(TYPICAL x7)

ON SLAB

CU-1

BUILDING AIR BALANCE SCHEDULE

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

1 Office 1 > 3 HRS 256 256 0 20

1 Exam 1 VARIES 147 147 0 15

1 Exam 1 VARIES 261 261 0 15

1 Reception 1 > 3 HRS 304 304 0 20

1 Restroom 0 N/A 38 0 90 0

1 Restroom 0 N/A 31 0 90 0

1 Exam 1 VARIES 94 94 0 10

1 Consult 1 > 3 HRS 37 37 T/A 0 20

1 Exam 1 VARIES 64 64 0 15

1 Exam 1 VARIES 64 64 0 15

1 Lab 0 VARIES 39 39 T/A 0 0

1 Work Stations 0 VARIES 665 680 0 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

2 Break 2 VARIES 243 243 0 15

2 Waiting 20 VARIES 1389 1292 0 75

2 Reception 2 > 3 HRS 335 335 0 40

2 P Restroom 0 N/A 10 0 90 0

2 E Restroom 0 N/A 23 0 90 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

3 Office 1 > 3 HRS 118 118 0 20

3 Exam 1 VARIES 124 124 0 20

3 Exam 1 VARIES 100 100 0 20

3 Reception 1 > 3 HRS 108 119 0 20

3 Corridor 0 N/A 83 0 0 0

3 Exam 1 VARIES 120 120 0 20

3 Exam 1 VARIES 99 99 0 20

3 Restroom 0 N/A 24 0 90 0

3 Restroom 0 N/A 24 0 90 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

4 Reception 1 > 3 HRS 253 253 0 20

4 Waiting 4 VARIES 514 427 0 100

4 U Restroom 0 N/A 21 0 90 0

4 Storage 0 N/A 12 12 T/A 0 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

5 Exam 1 VARIES 89 89 0 15

5 Office 1 > 3 HRS 130 130 0 20

5 Corridor 0 N/A 257 127 0 0

5 Exam 1 VARIES 101 101 0 15

5 Exam 1 VARIES 89 89 0 15

5 Exam 1 VARIES 105 105 0 15

5 Waiting 20 VARIES 1229 1229 0 50

BUILDING TOTALS 68 VARIES 7600 6970 630 630

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3

CALCULATIONS BASED ON ASHRAE 62.1 - 2007 TABLE 6-1 - PROCEDURE PROVIDES VENTILATION FOR VARIABLE / INTERMITTENT OCCUPANTS

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

BUILDING VENTILATION CALCULATION

TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / PERSON

PEAK Office 8 1.00 20 20 160 20

PEAK Waiting 47 0.50 15 7.5 352.5 7.5

PEAK Exam Office 13 0.50 15 7.5 97.5 7.5

BUILDING TOTALS 68 610 (630 provided)

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE

CALCULATIONS BASED ON ASHRAE 62.1 - 2007 TABLE 6-1 - PROCEDURE PROVIDES VENTILATION FOR VARIABLE / INTERMITTENT OCCUPANTS

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

22"

22x22,10",-335

22x22,14",-646

8x4,4",10 CFM8x4,4",23 CFM

22x22,10",335 CFM

22x22,10",-243

22x22,14",-646

CEILINGABOVE

RELOCATED

AHU-2

Exam

12

x1

21

8x

12

24

x1

2

ON SLAB

CU-2

ON SLAB

CU-4

ON SLAB

CU-3

ON SLAB

CU-5

ABOVEMEZZANINE

RELOCATED TO

AHU-3

22x22,7",-120

22x22,8",-124

8x4,4",24 CFM

22x22,7",-118 8x4,4",24 CFM

22x22,8",-119

22x22,7"-100

22x22,7",-99

HORIZONTALVERTICAL OREXISTING AHU

MAY CONFIGURE

6x10

12x10

12

x8

8x10

10x12

ABOVEMEZZANINE

EXISTING ON

AHU-4

22x22,10",-253

22x22,12",-427

14x14

10

x1

21

4x

12

ABOVEMEZZANINE

EXISTING ON

AHU-5

HORIZONTALVERTICAL OREXISTING AHU

MAY CONFIGURE

22x22,14",-615

22x22,14",-61522x22,7",-89

22x22,7",-101

22x22,7",-105

22x22,8",-130

22x22,7",129 CFM

22x22,7",-89

22x22,6",89 CFM

22x22,8",-12722x22,6",89 CFM

24

x1

2

16x1220x12

12

x1

61

4x

16

18x16

SPLIT SYSTEM EQUIPMENT SCHEDULEAIR HANDLER MARK: AHU-1,2,5 AHU-3,4UNIT MODEL NUMBER: EXISTING EXISTING

UNIT DIMEN H/W/D: 59.5X26X23.5 44.5X24X23.5

UNIT WEIGHT: 155 111

SUPPLY PLENUM SIZE : 12.02X21.22 12.02X19.22

RETURN PLENUM SIZE : 18.07X21.5 19.5X18.07

SUPPLY FAN CFM / SP : 2000 / .70 800 / .60

SUPPLY FAN H/P : 1 1/4

OUTDOOR AIR CFM: 130 / 130 / 130 120 / 120

UNIT PHASE / HERTZ: * *

UNIT VOLTAGE: * *

HEATER KW: * *

HEATER BREAKER: * *

CONDENSER MARK: CU-1,2,5 CU-3,4NOMINAL A/C TONS : 5 2

UNIT MODEL NUMBER: EXISTING EXISTING

UNIT VOLTAGE: * *

UNIT MCA / BREAKER: * *

UNIT DIMEN H/W/D: 46.4X35.1X38.7 37.2X26.7X30

UNIT WEIGHT: 269 175

TOTAL COOLING BTUH: 58,000 22,800

SENS. COOLING BTUH: 40,000 16,600

LAT. COOLING BTUH: 18,000 6,200

TOTAL HEATING BTUH: 34,120 17,060

SENSIBLE HEAT % 0.69 0.73

SEER: 13 13

THERMOSTAT MODEL: T8411R1002 T8411R1002

NOTES: * EQUIPMENT IS EXISTING,SEE NAME PLATE

DATA FOR EXACT INFORMATION. CLEAN AND CHECK

EQUIPMENT TO INSURE PROPER OPERATION.

SIZE AND INSTALL STAND ALONE DEHUMIDIFICATION

AT THE INDOOR FOUNTAIN AREA.

EXHAUST FAN SCHEDULE

FAN MARK: EF-1MANUFACTURER: NUTONE

MODEL NUMBER: QT-80

FAN TYPE: EXHAUST

FAN CFM: 90

TOTAL PRESSURE: .2

FAN VOLTAGE: 120/1/60

FAN AMPERAGE: .7

FAN DIMEN LWH: 9X9X6

DUCT OUTLET SIZE: 4

DUCT INLET SIZE: 10X10

FAN WEIGHT: 12

NOTES: 1,2

1 = VENT TO EXTERIOR

2 = INTERLOCK WITH LIGHTS

HANDLER DETAILVERTICAL AIR

FMC 401AIR DUCT* FRESH

FMC 1101WIRING

+ CONTROLPIPING

REFRIGERANT

FMC 303AIR HANDLER

FMC 601AIR DUCTSUPPLY

FMC 601RISER DUCT

* RETURN AIR

FMC 307DRAIN

CONDENSATE

* CEILING

FLOOR

STANDAIR HANDLER

DRAWING FOR EXACT CONFIGURATION.* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN

FMC 1101+ CONTROL WIRING

REFRIGERANT PIPING

HORIZONTAL AIR HANDLER DETAIL

FMC 401DUCTAIR

* FRESH

TOP CHORDSUSPEND FROM

1/2 THREADED ROD

FMC 303AIR HANDLER

SUPPLY AIR DUCT FMC 601FMC 601

RETURN DUCT

CONDENSATE DRAIN FMC 307

* ACCESS PANEL FMC 306.3

* CEILING

SWITCH FMC 301.2.3AUX. DRAIN PAN + FLOAT

DRAWING FOR EXACT CONFIGURATION.* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN

WALL

FLOOR

FMC 1101 - MAY ALSO ROUTE BELOW SLABREFRIGERANT PIPING + CONTROL WIRING

GRADEEQUIPMENT SLAB

FMC 301.13FASTENER

FMC 303CONDENSING UNIT

PIPE COVER - MAY MOUNT INTERIOR

CONDENSING UNIT DETAIL

AHU TYPEVERIFY EXISTING

HORIZONTAL -VERTICAL OREXISTING AHU

MAY CONFIGURE

ALONE DEHUMIDIFICATIONAND PROVIDE STAND

FOUNTAIN - CALCULATETHIS AREA CONTAINS A

Page 7: HVAC Designs Book

North

PERMIT SET1/31/2009

DRAWING DATE

New Office Building721 of 22,597Hillsborough County FloridaCorner of Lakewood & OakfieldPrieto Office Building 1st Floor

1 OF 3DRAWING

HVAC

CLASSIFICATION :CONDITIONED SQ. FT.:PROJECT STATE, ZIP:PROJECT ADDRESS:

PROJECT NAME:

SCALE 1/8"=1'-0"R#884 C#959FLORIDA BERS

813-885-2258HVAC Designs

Neil FimbelDesigned By:

HVAC SCHEDULES + DETAILS

x

THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD. SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.

IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND

HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING

HVAC NOTES

BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR

E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE

O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN

S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT

ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN

HVAC SYMBOLS

FMC 603.151 WAY THROW

CEILING REGISTER

FMC 603.152 WAY THROW

CEILING REGISTER

FMC 603.153 WAY THROW

CEILING REGISTER

FMC 603.154 WAY THROW

CEILING REGISTER

FMC 603.15CORNER THROW

CEILING REGISTER

FMC 603.152 WAY THROW

WALL REGISTER

FMC 603.152 WAY THROW

FLOOR REGISTER

AIR FMC 603.15FILTER RETURNFLOOR GRILLE

AIR FMC 603.15FILTER RETURNCEILING GRILLE

AIR FMC 603.15FILTER RETURN

WALL GRILLE

FMC 603.15DIRECT T/ A

WALL GRILLE

FMC SECTION 603DUCTWORKFLEXIBLE

FMC SECTION 603DUCTWORK

RECTANGULAR

SECTION 603BOXES FMC

AIR DISTRIBUTION

FMC SECTION 602PLENUM TRUNK

RETURN AIR

FMC SECTION 602PLENUM TRUNK

SUPPLY AIR

CAP FMC 504ROOF / WALLDRYER VENT

FMC 505 - 506ROOF / WALL CAP

RANGE VENT

ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED

FMC SECTION 606SMOKE DETECTOR

DUCT MOUNTED

FEC 13-613ABOVE FLOOR

THERMOSTAT @ 60"

FMC SECTION 307DRAIN TO GRASS

CONDENSATE

PIPING FMC 1101REFRIGERANT

CONTROL /

FMC SECTION 403EF-1 or as NOTED

EXHAUST FAN

FMC SECTION 306ACCESS PANEL

EQUIPMENT

FMC SECTION 307TO DRYWELLCONDENSATE

FMC SECTION 607FIRE DAMPER

DUCT MOUNTED

FMC 603.15CONTROL DAMPER

AIR VOLUME

303 --- 312FMC SECTIONS

HANDLER ON STANDVERTICAL AIR

FMC 303 -- 312AIR DAMPER

ZONE CONTROL

D

R R

T

DS

FMC 303 -- 312DAMPER

BYPASS AIR

303 -- 312FMC SECTIONS

ON SLABCONDENSING UNIT

ZD

BP

303 --- 312FMC SECTIONS

FROM STRUCTUREHANDLER MOUNTHORIZONTAL AIR

303 -- 312FMC SECTIONS

ROOF MOUNTEDPACKAGE UNIT

303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT

30 CFM T/A1" UNDERCUT DOOR

H

303 -- 312FMC SECTIONS

HANDLERDUCTLESS AIR

= DEVICE NECK SIZE

= BRANCH DUCT SIZE

ADJUSTMENTS= AIRFLOW CFMWalk In Closet

Bedroom

4"

32

8x4

TYPICAL ROOM

DUCTBRANCHTYPICAL

DEVICETYPICAL AIR

D

FMC 603.15DUCTED T/ A

CEILING GRILLE

Lobby

COMPLIES WITH FBC 406.3.3.1NATURALLY VENTILATEDOPEN PARKING GARAGE

COMPLIES WITH FBC 406.3.3.1NATURALLY VENTILATEDOPEN PARKING GARAGE

TYPICAL OPENING x10' HEIGHT

22x22,9",250 CFM

22x22,9",250 CFM

22x22,9",250 CFM

22x22,9",250 CFM

22x22,16",-895 CFM

10x12

TO GUTTER / GRASS AREAPUMP CONDESATE DRAIN

FIRE CAULK PENETRATIONSPIPING UP TO ROOF

DUCT SET TO 105 CFM12x12 OAL,6" FRESH AIR

20x18 20x12

ABOVEON ROOF

CU-1

CEILINGABOVE

AHU-1

12x12,8",-105 CFM

RELIEVE 105 CFMRELIEF AIR DAMPER TODUCT SET BAROMETRIC12x12 OAL,8" RELIEF AIR

FIRST FLOOR

PARKING GARAGE NATURAL VENTILATION CALCULATION

FLOOR CLASSIFICATION OPEN WALL PERIMETER OPEN WALL HEIGHT GROSS OPEN AREA % OF OPENING GROSS PERIMETER RESULT

1 OPEN PARKING 328 10.00 3280 54 597 PASSES

BUILDING TOTALS 597

OPENINGS ARE UNIFORMLY DISTRIBUTED ON ALL 4 WALLS, THE OPENING AREA EXCEEDS THE MINIMUM OF 20% OPENING TO PERIMETER WALL AREA.

CALCULATIONS BASED ON THE 2004 + SUPPLEMENTS FLORIDA MECHANICAL CODE SECTION 403.1, 403.3 AND FLORIDA BUILDING CODE 406.3.3.1

FIRST FLOOR AIR BALANCE SCHEDULEZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM

1 LOBBY 14 0.5 1000 895 105 105X X X X X X X X

FIRST FLOOR TOTALS 14 0.5 1000 895 105 105

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

FIRST FLOOR VENTILATION CALCULATION TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / SQ FOOT

PEAK Reception / Wait 14 0.50 15 7.5 105 7.5

FIRST FLOOR TOTALS 105

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

TRANE EQUIPMENT

AIR HANDLER MARK: AHU-1UNIT MODEL NUMBER: 2TEC3F30A

UNIT DIMEN H/W/D: 46.5X24X23.5

UNIT WEIGHT: 125

SUPPLY PLENUM SIZE : 12.02X19.22

RETURN PLENUM SIZE : 18.07X19.5

SUPPLY FAN CFM / SP : 1000 / .40

SUPPLY FAN H/P : 1/3

OUTDOOR AIR CFM: 105

UNIT PHASE / HERTZ: 1 / 60

UNIT VOLTAGE: 208 / 240

HEATER KW: 3.6 / 4.8

HEATER BREAKER: 25 / 30

CONDENSER MARK: CU-1NOMINAL A/C TONS : 2.5

UNIT MODEL NUMBER: 2TTR3030A

UNIT VOLTAGE: 208/230/ 1 / 60

UNIT MCA / BREAKER: 13 / 20

UNIT DIMEN H/W/D: 38X30.1X33

UNIT WEIGHT: 198

TOTAL COOLING BTUH: 27,600

SENS. COOLING BTUH: 20,400

LAT. COOLING BTUH: 7,200

TOTAL HEATING BTUH: 17,060

SENSIBLE HEAT % 0.74

SEER: 13

THERMOSTAT MODEL: T8411R1002

NOTES: ALTERNATE BRAND EQUIPMENT WITH

EQUAL PERFORMANCE ARE ACCEPTABLE.

SUBMIT PERFORMANCE DATA FOR APPROVAL.

FMC 1101+ CONTROL WIRING

REFRIGERANT PIPING

HORIZONTAL AIR HANDLER DETAIL

FMC 401DUCTAIR

* FRESH

TOP CHORDSUSPEND FROM

1/2 THREADED ROD

FMC 303AIR HANDLER

SUPPLY AIR DUCT FMC 601FMC 601

RETURN DUCT

CONDENSATE DRAIN FMC 307

* ACCESS PANEL FMC 306.3

* CEILING

SWITCH FMC 301.2.3AUX. DRAIN PAN + FLOAT

DRAWING FOR EXACT CONFIGURATION.* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN

ROOFTOP CONDENSING UNIT DETAIL

CONNECTIONCURB

CURB

CONNECTIONEQUIPMENT

FMC 303EQUIPMENTROOFTOP

MEMBERTRUSS

CONNECT TO

ROOF

CURB

@ 18" O.C.3/8 BOLT

JOISTCURB

EQUIPMENTROOFTOP

O.C.@ 18""

OR ANGLE1/4" PLATESCREWS

3/8"

MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOADMECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD

Page 8: HVAC Designs Book

North

PERMIT SET1/31/2009

DRAWING DATE

New Office Building10,938 of 22,597Hillsborough County FloridaCorner of Lakewood & OakfieldPrieto Office Building 2nd Floor

2 OF 3DRAWING

HVAC

CLASSIFICATION :CONDITIONED SQ. FT.:PROJECT STATE, ZIP:PROJECT ADDRESS:

PROJECT NAME:

SCALE 1/8"=1'-0"R#884 C#959FLORIDA BERS

813-885-2258HVAC Designs

Neil FimbelDesigned By:

HVAC SCHEDULES + DETAILS

x

THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD. SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.

IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND

HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING

HVAC NOTES

BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR

E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE

O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN

S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT

ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN

HVAC SYMBOLS

FMC 603.151 WAY THROW

CEILING REGISTER

FMC 603.152 WAY THROW

CEILING REGISTER

FMC 603.153 WAY THROW

CEILING REGISTER

FMC 603.154 WAY THROW

CEILING REGISTER

FMC 603.15CORNER THROW

CEILING REGISTER

FMC 603.152 WAY THROW

WALL REGISTER

FMC 603.152 WAY THROW

FLOOR REGISTER

AIR FMC 603.15FILTER RETURNFLOOR GRILLE

AIR FMC 603.15FILTER RETURNCEILING GRILLE

AIR FMC 603.15FILTER RETURN

WALL GRILLE

FMC 603.15DIRECT T/ A

WALL GRILLE

FMC SECTION 603DUCTWORKFLEXIBLE

FMC SECTION 603DUCTWORK

RECTANGULAR

SECTION 603BOXES FMC

AIR DISTRIBUTION

FMC SECTION 602PLENUM TRUNK

RETURN AIR

FMC SECTION 602PLENUM TRUNK

SUPPLY AIR

CAP FMC 504ROOF / WALLDRYER VENT

FMC 505 - 506ROOF / WALL CAP

RANGE VENT

ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED

FMC SECTION 606SMOKE DETECTOR

DUCT MOUNTED

FEC 13-613ABOVE FLOOR

THERMOSTAT @ 60"

FMC SECTION 307DRAIN TO GRASS

CONDENSATE

PIPING FMC 1101REFRIGERANT

CONTROL /

FMC SECTION 403EF-1 or as NOTED

EXHAUST FAN

FMC SECTION 306ACCESS PANEL

EQUIPMENT

FMC SECTION 307TO DRYWELLCONDENSATE

FMC SECTION 607FIRE DAMPER

DUCT MOUNTED

FMC 603.15CONTROL DAMPER

AIR VOLUME

303 --- 312FMC SECTIONS

HANDLER ON STANDVERTICAL AIR

FMC 303 -- 312AIR DAMPER

ZONE CONTROL

D

R R

T

DS

FMC 303 -- 312DAMPER

BYPASS AIR

303 -- 312FMC SECTIONS

ON SLABCONDENSING UNIT

ZD

BP

303 --- 312FMC SECTIONS

FROM STRUCTUREHANDLER MOUNTHORIZONTAL AIR

303 -- 312FMC SECTIONS

ROOF MOUNTEDPACKAGE UNIT

303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT

30 CFM T/A1" UNDERCUT DOOR

H

303 -- 312FMC SECTIONS

HANDLERDUCTLESS AIR

= DEVICE NECK SIZE

= BRANCH DUCT SIZE

ADJUSTMENTS= AIRFLOW CFMWalk In Closet

Bedroom

4"

32

8x4

TYPICAL ROOM

DUCTBRANCHTYPICAL

DEVICETYPICAL AIR

D

FMC 603.15DUCTED T/ A

CEILING GRILLE

Unit 2 H

Restroom

Unit 2 G

Unit 2 F

Infusion

Pharmacy Cold

Restroom

Exam 2

Exam 1

Lab

Restroom

Exam 3

Exam 4

Exam 5

Server

CorridorFiles

Storage

Phone

Dr Off 4

Dr Off 2

Admin

Billing

Lunch

F Office

Conference

Storage

Unit 2 C Unit 2 B

Restroom

Unit 2 A

Restroom

22x22,8",164 CFM22x22,8",164 CFM

22x22,8",164 CFM 22x22,8",164 CFM

22x22,8",164 CFM22x22,8",164 CFM

SCHEDULE FOR CFMSEE AIR BALANCEFRESH AIR INTAKE12x12 LOUVER + 9"

TYPICAL

10' SEPERATION REQUIREDEXHAUST AIR EQUAL TO FRESH AIR

TYPICAL

10' SEPERATION

22x22,14",-880 CFM

8x4,4",14 CFM

DUCT12x12,9" T/A

TYPICAL

TO ROOFPIPE CHASE

TYPICAL

SECOND FLOOR

18x20 20x12

T/ACFM106

CEILINGABOVE

AHU-1

EF-1VTE

12

x8

12

x1

28

x1

2

NOTEDUNLESSTYPICAL

FLOORABOVE 3rd

CURBON ROOF

CU-1

TYPICAL

T/ACFM147

CEILINGABOVE

AHU-2

FLOORABOVE 3rd

CURBON ROOF

CU-2

22x22,16",-1040 CFM18x20

22x22,8",198 CFM22x22,8",198 CFM

22x22,8",198 CFM22x22,8",198 CFM

22x22,8",198 CFM22x22,8",198 CFM

8x4,4",13 CFM

20x12

12

x8

14

x1

28

x1

2

T/ACFM126

CEILINGABOVE

AHU-3

FLOORABOVE 3rd

CURBON ROOF

CU-3

Restroom

22x22,16",-860 CFM

22x22,8",164 CFM22x22,8",164 CFM

22x22,8",164 CFM

22x22,8",164 CFM

22x22,8",164 CFM

8x4,4",14 CFM

22x22,8",164 CFM

20x12

12x8

12x12

8x12

18x20

Corridor

22x22,8",195 CFM22x22,10",278 CFM

22x22,6",90 CFM

22x22,5",75 CFM

22x22,6",103 CFM

10x6,6",100 CFM8x4,4",19 CFM

Restroom

22x22,5",75 CFM

22x22,9",-184 CFM

22x22,9",-195 CFM

Dr Off 122x22,12",-278 CFM22x22,8",184 CFM

10x6,5",63 CFM

HIGH WALL12x12 T/A

Restroom

22x22,9",-183 CFM

22x22,6",-75 CFM

Dr Off 3

22x22,7",-90 CFM

22x22,6",-75 CFM

8x4,4",19 CFM

18x2020x12

8x12

12x12

12x12

14

x1

2

CEILINGABOVE

AHU-4

FLOORABOVE 3rd

CURBON ROOF

CU-4

22x22,10",307 CFM

8x4,4",14 CFM

8x4,4",11 CFM

22x22,10",289 CFM

22x22,10",289 CFM

22x22,10",289 CFM

Restroom

EF-2VTE

EF-2VTE

EF-2VTE

EF-2VTE

EF-2VTE

EF-2VTE

22x22,9",-192 CFM

22x22,14",-868 CFM

CEILINGABOVE

AHU-5

20

x1

21

8x

20

16

x1

2

FLOORABOVE 3rd

CURBON ROOF

CU-5

22x22,5",65 CFM

22x22,4",28 CFM

22x22,4",28 CFM

22x22,8",165 CFM

SR-82,8",165 CFM

22x22,8",165 CFM

22x22,8",165 CFM

22x22,8",165 CFM

8x4,4",54 CFM

Restroom

22x22,14",-860 CFM

FLOORABOVE 3rd

CURBON ROOF

CU-6

CEILINGABOVE

AHU-6

Recep / Wait

18

x2

02

0x

12

10

x1

2

22x22,5",81 CFM

22x22,9",213 CFM

EF-2VTE

22x22,9",213 CFM

22x22,9",213 CFM

10x6,6",92 CFM

22x22,6",91 CFM

22x22,9",223 CFM 22x22,5",63 CFM

10x6,5",66 CFM

8x4,4",43 CFM

Restroom

22x22,14",-640 CFM

8x4,4",51 CFM

22x22,7",-78 CFM

22x22,9",249 CFMP Infusion

12x12,6",-66 CFM

8x4,4",20 CFM

22x22,10",-300 CFM

10

' S

EP

ER

AT

ION

22x22,10",-223 CFM

22x22,6",-63 CFM

22x22,10",-252 CFM

22x22,6",-63 CFM

22x22,6",-65 CFM

22x22,5",65 CFM

22x22,5",63 CFM

22x22,9",252 CFM

FLOORABOVE 3rd

CURBON ROOF

CU-7

CEILINGABOVE

AHU-7

21x12 18x21

8x

12

12

x1

4

16

x1

01

6x

12

18

x1

2

18

x1

4

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,16",-1060 CFM

Restroom8x4,4",13 CFM

T/ACFM127

EF-1VTE

NOTEDUNLESSTYPICAL

FLOORABOVE 3rd

CURBON ROOF

CU-8

CEILINGABOVE

AHU-8

20

x1

2

12x8 12x12 8x12

18

x2

0

CEILINGABOVE

AHU-9

FLOORABOVE 3rd

CURBON ROOF

CU-9

Restroom

22x22,9",231 CFM

22x22,9",231 CFM

22x22,9",231 CFM

22x22,9",231 CFM

22x22,9",231 CFM

22x22,9",231 CFM

T/ACFM148

22x22,16",-1240 CFM

8x4,4",12 CFM 18

x2

02

0x

12

10x1216x1210x12

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

T/ACFM107

22x22,16",-1080 CFM

8x4,4",13 CFM

FLOORABOVE 3rd

CURBON ROOF

CU-10

CEILINGABOVE

AHU-10

20x12

12x8 12x12 8x12

18x20

TRANE SPLIT SYSTEM EQUIPMENT SCHEDULE

AIR HANDLER MARK: AHU-1,3,6 AHU-2,4,5,8,10 AHU-7 AHU-9UNIT MODEL NUMBER: 2TEC3F30A 2TEC3F36A 2TEC3F60A 2TEC3F42A

UNIT DIMEN H/W/D: 46.5X24X23.5 46.5X24X23.5 59.5X26X23.5 53.25X26X23.5

UNIT WEIGHT: 125 125 155 150

SUPPLY PLENUM SIZE : 12.02X19.22 12.02X19.22 12.02X21.22 12.02X21.22

RETURN PLENUM SIZE : 18.07X19.5 18.07X19.5 18.07X21.5 18.07X21.5

SUPPLY FAN CFM / SP : 1000 / .40 1200 / .40 2000 / .40 1400 / .40

SUPPLY FAN H/P : 1/3 1/3 1 1/2

OUTDOOR AIR CFM: 120/140/140 160/120/140/140/120 250 160

UNIT PHASE / HERTZ: 1 / 60 1 / 60 1 / 60 1 / 60

UNIT VOLTAGE: 208 / 240 208 / 240 208 / 240 208 / 240

HEATER KW: 3.6 / 4.8 3.6 / 4.8 7.2 / 9.6 3.6 / 4.8

HEATER BREAKER: 25 / 30 25 / 30 50 / 60 25 / 30

CONDENSER MARK: CU-1,3,6 CU-2,4,5,8,10 CU-7 CU-9NOMINAL A/C TONS : 2.5 3 5 3.5

UNIT MODEL NUMBER: 2TTR3030A 2TTR3036A 2TTR3060A 2TTR3042A

UNIT VOLTAGE: 208/230/ 1 / 60 208/230/ 1 / 60 208/230/ 1 / 60 208/230/ 1 / 60

UNIT MCA / BREAKER: 13 / 20 18 / 30 32 / 50 21 / 35

UNIT DIMEN H/W/D: 38X30.1X33 38X30.1X33 46.4X35.1X38.7 38.4X35.1X38.7

UNIT WEIGHT: 198 194 269 250

TOTAL COOLING BTUH: 27,600 34,200 58,000 41,000

SENS. COOLING BTUH: 20,400 25,400 40,000 29,800

LAT. COOLING BTUH: 7,200 8,800 18,000 11,200

TOTAL HEATING BTUH: 17,060 17,060 34,120 17,060

SENSIBLE HEAT % 0.74 0.74 0.69 0.73

SEER: 13 13 13.5 13.5

THERMOSTAT MODEL: T8411R1002 T8411R1002 T8411R1002 T8411R1002

NOTES: ALTERNATE BRAND EQUIPMENT WITH EQUAL PERFORMANCE ARE ACCEPTABLE.

SUBMIT PERFORMANCE DATA FOR APPROVAL.

EXHAUST FAN SCHEDULE

FAN MARK: EF-1 EF-2

MANUFACTURER: NUTONE NUTONE

MODEL NUMBER: QT-150 QT-110

FAN TYPE: EXHAUST EXHAUST

FAN CFM: 140 92.85

TOTAL PRESSURE: .25 .25

FAN VOLTAGE: 120/1/60 120/1/60

FAN AMPERAGE: 1.0 .7

FAN DIMEN LWH: 14X10X9 9X9X6

DUCT OUTLET SIZE: 3.25X10 TO 7 4

DUCT INLET SIZE: 15X11 10X10

FAN WEIGHT: 14 12

NOTES: 1,2 1,2

1 = VENT TO EXTERIOR

2 = INTERLOCK WITH LIGHTS

SECOND FLOOR VENTILATION CALCULATION TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / SQ FOOT

PEAK Conference 10 VARIES 20 19.75 197.5 19.75

PEAK Office 56 1.00 20 20 1120 20

PEAK Reception / Wait 23 0.50 15 7.5 172.5 7.5

SECOND FLOOR TOTALS 89 1490

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

SECOND FLOOR AIR BALANCE SCHEDULEZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

1 Unit 2 A 6 > 3 HRS 986 880 0 120

1 Restroom 0 N/A 14 0 120 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

2 Unit 2 B 8 > 3 HRS 1187 1040 0 160

2 Restroom 0 N/A 13 0 160 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

3 Unit 2 C 7 > 3 HRS 986 860 0 120

3 Restroom 0 N/A 14 0 120 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

4 Server 0 N/A 100 100 T/A 0 0

4 Dr Off 4 1 > 3 HRS 75 75 0 20

4 Dr Off 3 1 > 3 HRS 75 75 0 20

4 Restroom 0 N/A 19 0 96 0

4 Dr Off 2 1 > 3 HRS 184 184 0 20

4 Restroom 0 N/A 63 0 96 0

4 Dr Off 1 1 > 3 HRS 195 195 0 20

4 Admin 1 > 3 HRS 90 90 0 20

4 Billing 1 > 3 HRS 278 278 0 20

4 F Office 0 N/A 18 0 0 0

4 Corridor 0 N/A 103 183 0 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

5 Lunch 4 < 3 HRS 307 192 0 40

5 Restroom 0 N/A 14 0 95 0

5 Conference 10 < 3 HRS 868 868 0 120

5 Storage 0 N/A 11 0 0 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

6 Files 0 N/A 28 0 0 0

6 Storage 0 N/A 28 0 0 0

6 Recep / Wait 10 VARIES 825 860 0 140

6 Restroom 0 N/A 54 0 95 0

6 Phone 0 N/A 65 0 0 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

7 Infusion 9 VARIES 640 640 0 90

7 Restroom 0 N/A 43 0 96 0

7 Pharmacy 1 > 3 HRS 249 300 0 20

7 Cold 0 N/A 51 0 0 0

7 P Infusion 1 > 3 HRS 66 66 0 20

7 Restroom 0 N/A 20 0 96 0

7 Exam 2 1 > 3 HRS 223 223 0 20

7 Exam 1 1 > 3 HRS 63 63 0 20

7 Lab 1 > 3 HRS 92 0 0 20

7 Restroom 0 N/A 92 0 96 0

7 Exam 3 1 > 3 HRS 252 252 0 20

7 Exam 4 1 > 3 HRS 63 63 0 20

7 Exam 5 1 > 3 HRS 65 65 0 20

7 Corridor 0 N/A 81 78 0 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

8 Unit 2 F 7 > 3 HRS 1187 1060 0 140

8 Restroom 0 N/A 13 0 140 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

9 Unit 2 F 8 > 3 HRS 1388 1240 0 160

9 Restroom 0 N/A 12 0 160 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

10 Unit 2 F 6 > 3 HRS 1187 1080 0 120

10 Restroom 0 N/A 13 0 120 0

SECOND FLOOR TOTALS 89 VARIES 12400 10910 1490 1490

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

ROOFTOP CONDENSING UNIT DETAIL

CONNECTIONCURB

CURB

CONNECTIONEQUIPMENT

FMC 303EQUIPMENTROOFTOP

MEMBERTRUSS

CONNECT TO

ROOF

CURB

@ 18" O.C.3/8 BOLT

JOISTCURB

EQUIPMENTROOFTOP

O.C.@ 18""ANGLE

ORPLATE

1/4"SCREWS

3/8"

LOADMECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WINDLOADMECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND

1101CONTROL WIRING FMCREFRIGERANT PIPING +

HORIZONTAL AIR HANDLER DETAIL

FMC 401DUCTAIR

* FRESH

TOP CHORDSUSPEND FROM

1/2 THREADED ROD

FMC 303AIR HANDLER

SUPPLY AIR DUCT FMC 601FMC 601

RETURN DUCT

CONDENSATE DRAIN FMC 307

* ACCESS PANEL FMC 306.3

* CEILING

SWITCH FMC 301.2.3AUX. DRAIN PAN + FLOAT

DRAWING FOR EXACT CONFIGURATION.* = OPTIONAL ITEM, SEE HVAC FLOOR PLAN

LOBBY BELOWPIPING UP FROM

Page 9: HVAC Designs Book

North

PERMIT SET1/31/2009

DRAWING DATE

New Office Building10,938 of 22,597Hillsborough County FloridaCorner of Lakewood & OakfieldPrieto Office Building 2nd Floor

3 OF 3DRAWING

HVAC

CLASSIFICATION :CONDITIONED SQ. FT.:PROJECT STATE, ZIP:PROJECT ADDRESS:

PROJECT NAME:

SCALE 1/8"=1'-0"R#884 C#959FLORIDA BERS

813-885-2258HVAC Designs

Neil FimbelDesigned By:

HVAC SCHEDULES + DETAILS

x

THIS DESIGN IS FOR PEAK LOAD CONDITIONS ONLY, CONSIDER USING STAGED COOLING EQUIPMENT OR STAND ALONE DEHUMIDIFICATION FOR PART LOAD. SEE "TOTAL BUILDING LOAD SUMMARY" FORM, FIELD INSPECT BUILDING ENVELOPE DURING CONSTRUCTION, BE SURE THE BUILDING MATCHES THE FORM. IS BASED ON MANUAL J HEAT LOAD CALCULATIONS, FOR DETAILED BUILDING ENVELOPE INFORMATION (INSULATING VALUES, WINDOW ENERGY VALUES) HVAC CONTRACTOR SHOULD RED LINE SKETCH ANY CHANGES IN HVAC WORK AND SUBMIT AS BUILT DRAWING TO THE ORIGINAL DESIGNER. THIS DRAWING SUBMISSION, ANY MODIFICATIONS TO THE BUILDING OR BUILDING COMPONENTS DURING CONSTRUCTION MUST BE COMMUNICATED TO THE DESIGNER.10) THIS DIAGRAM, HEAT LOAD CALCULATIONS, AND FLORIDA ENERGY CALCULATIONS WERE BASED ON THE ARCHITECTURAL PLANS PROVIDED FOR PERMIT TO ACHIEVE ACCEPTABLE INTERIOR HUMIDITY LEVELS DURING PART LOAD CONDITIONS, A/C CONTRACTOR TO DISCUSS THIS WITH THE BUILDING OWNER. MULTISTAGE CONDENSING UNITS OR STAND ALONE DE-HUMIDIFICATION IS REQUIRED FOR ALL STRUCTURES LOCATED IN SUB-TROPIC ENVIRONMENTS STAND ALONE DEHUMIDIFICATION + HUMIDISTAT, PLUS ANY INFORMATION NOT SHOWN ON THE HVAC DRAWINGS OR MANUAL J HEAT LOAD CALCULATIONS. OF INTERNAL AND EXTERNAL SHADING DEVICES, INTERIOR HEAT AND MOISTURE PRODUCING APPLIANCES, ENTERTAINING LARGE AMOUNTS OF PEOPLE, CONDITIONS, INDOOR AIR QUALITY, HEALTH PROBLEMS, COMBUSTION AIR SAFETY, ALLOWABLE SWINGS IN TEMPERATURE AND HUMIDITY, ZONING, USE TO THE BUILDING OWNER FOR REVIEW AND APPROVAL. INSTALLING CONTRACTOR WILL CONDUCT A BUILDING OWNER INTERVIEW TO DISCUSS DESIGN 9) INSTALLING CONTRACTOR MUST PROVIDE A COPY OF THE HVAC HEAT LOAD CALCULATIONS, FLORIDA ENERGY CALCULATIONS, AND A HVAC DRAWING 6' OF THE ACCESS PANEL WITH ATTIC LIGHT. SEE SECTION 610 OF THE FLORIDA ENERGY CODE FOR FULL COMPLIANCE DESCRIPTION. PROPERLY. POST A NOTICE ON THE ELECTRICAL PANEL INDICATING TO THE HOMEOWNER THE AIR HANDLER IS LOCATED IN THE ATTIC SPACE WITHIN 8) ATTIC MOUNTED EQUIPMENT (RESIDENTIAL) MUST CONTAIN A DEVICE TO ALERT THE HOMEOWNER IF THE CONDENSATE DRAIN LINE IS NOT WORKING INTERIOR DOORS + A MEANS FOR AIR TRANSFER, RELIEF, OR AIR RETURN. PRESSURE DIFFERENTIALS NOT TO EXCEED .01 INCH W.G. (30 CFM / 30" DOOR). 7) PROVIDE A BALANCED RETURN AIR SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 601.4. ALL CLOSEABLE ROOMS REQUIRE 1" UNDERCUT ON FOR BOTH CONDENSATE DRAINS AND REFRIGERANT PIPING PER FMC 305. SIZE REFRIGERANT PIPING PER THE MANUFACTURERS RECOMMENDATIONS. EXTEND CONDENSATE DRAIN DISCHARGE A MINIMUM OF 12" FROM EXTERIOR WALL TO GRASS (OR OTHER APPROVED METHOD), PROVIDE PIPING SUPPORTS 6) PROVIDE A CONDENSATE DRAIN SYSTEM PER THE FLORIDA MECHANICAL CODE SECTION 307 AND A REFRIGERANT PIPING SYSTEM PER FMC SECTION 1107. PROVIDE BRANCH DUCT VOLUME DAMPERS AT ALL BRANCH DUCT TO TRUNKLINE CONNECTIONS FOR AIR BALANCING, PROVIDE ACCESS TO DAMPERS. PROVIDE FIELD FABRICATED REGISTER BOXES WITH SIDE TAP COLLAR IN AREAS WHERE THE FLEXIBLE DUCT ELBOW WON'T MAINTAIN 1 DUCT RADIUS DIA. LINE RADIUS OF 1 DUCT DIAMETER MINIMUM, EXTEND A FEW INCHES BEYOND THE COLLAR FLANGE BEFORE THE ELBOW, DO NOT COMPRESS THE DUCT. DUCTWORK PER UL-181 (STRAP DUCT INNER CORE + VAPOR SEAL, VAPOR SEAL DUCT OUTER JACKET). FLEXIBLE DUCT ELBOWS MUST MAINTAIN A CENTER ONE AIR DUCT - CONSTRUCT AND SUSPEND DUCTWORK FROM THE BUILDING STRUCTURE PER THE FLORIDA MECHANICAL CODE CHAPTER 6. SEAL ALL EQUAL TO KNAUF 1 1/2" R-6 - FABRICATE, REINFORCE, AND INSTALL PER SMACNA STANDARDS. FLEXIBLE DUCTWORK EQUAL TO ATCO 36 SERIES R-6 CLASS 5) ALL DUCT DIMENSIONS SHOWN ARE CLEAR INTERIOR DUCT DIMENSIONS. ADD 3" TO LISTED SIZE FOR EXTERIOR DIMENSIONS. FIBERGLASS DUCT BOARD MAY BE REQUIRED FOR EQUIPMENT SUSPENDED FROM ATTIC TRUSSES AND FOR EXTERIOR EQUIPMENT MOUNTED ABOVE GRADE LEVEL. MEANS FOR WIND RESISTANCE ON ALL EXTERIOR MOUNTED EQUIPMENT (INCLUDING ROOF AND WALL CAPS) PER SECTION FMC 301.13. ENGINEER SEAL 4) MECHANICAL INSTALLER TO FIELD VERIFY CLEARANCES AND ACCESSIBILITY PRIOR TO FABRICATION OR INSTALLATION OF ANY HVAC WORK. PROVIDE A THE PRODUCT INSTALLATION INSTRUCTIONS. ALTERNATE BRAND EQUIPMENT MUST BE OF EQUAL PERFORMANCE AND CONSTRUCTION QUALITY. GENERAL CONTRACTOR *PROTECT THE STRUCTURE PER FMC 302. FABRICATE AND INSTALL HVAC SYSTEMS PER THE FLORIDA MECHANICAL CODE AND 3) COORDINATE LOCATION FOR ALL HVAC COMPONENTS INCLUDING EQUIPMENT, FANS, AIR DEVICES, PIPING, AND BUILDING PENETRATIONS WITH THE THE VENTILATION CALCULATIONS AND THE BUILDING AIR BALANCE SCHEDULE. PERFORM A TEST AND AIR BALANCE TO ACHIEVE THE VALUES LISTED. INFILTRATION AS SHOWN ON THE HVAC HEAT LOAD CALCULATIONS. COMMERCIAL BUILDINGS MUST HAVE MECHANICALLY INDUCED FRESH AIR PER THE REQUIRED IF THE CALCULATED MINIMUM OUTDOOR AIR REQUIRED EXCEEDS THE OUTDOOR AIR THAT ENTERS THE BUILDING NATURALLY DUE TO 2) PROVIDE ACCEPTABLE INDOOR AIR QUALITY PER THE FLORIDA MECHANICAL CODE SECTION 403.3. MECHANICALLY INDUCED OUTDOOR AIR IS ONLY THIS DRAWING COMPLIES WITH THE 2005, 2006, AND 2007 CODE SUPPLEMENTS AND "BLUE PAGES" RELEASED MID 2007. 1) HVAC INSTALLATION MUST COMPLY WITH THE 2004 FLORIDA BUILDING, ENERGY, AND MECHANICAL CODES. OBTAIN REQUIRED PERMITS + INSPECTIONS.

IS BASED ON MANUAL D - DON'T EXCEED 3/1 ASPECT RATIO FOR ALTERNATE DUCT SIZES. A 1" UNDERCUT @ DOOR = ONLY 30 CFM OF RELIEF AIR. COMMERCIAL HVAC LOADS" FOR HEATING CFM VALUES. ALTERNATE AIR DEVICE SIZES MUST EQUAL FREE AREA OF LISTED SIZE. THE DUCT SYSTEM DESIGN ROOM AIR DEVICE SIZES, CFM VALUES, AND BRANCH DUCT SIZES ARE SHOWN PER ROOM BASED ON COOLING SEASON. SEE THE "RHVAC RESIDENTIAL AND

HVAC SYMBOL, HVAC CONTRACTOR SHOULD REFERENCE CODE BOOK PRIOR TO INSTALLATION. THIS DIAGRAM COMPLIES WITH FBC 106.3.5 PLAN REVIEW. SHOWN IS GENERAL IN NATURE; FIELD CONDITIONS WILL DICTATE EXACT CONFIGURATION OF THE HVAC SYSTEM. CODE SECTIONS ARE LISTED FOR EACH THIS HVAC DRAWING IS NOT INTENDED TO SHOW EXACT DETAIL OF EVERY ITEM REQUIRED TO MEET CODE REQUIREMENTS. THE PROPOSED DUCT ROUTING

HVAC NOTES

BD = BAROMETRIC DAMPERBP = BYPASS DAMPERAHU = AIR HANDLING UNITAFF = ABOVE FINISH FLOOR

E/A = EXHAUST AIRDH = DE-HUMIDIFIERCU = CONDENSING UNITCFM = CUBIC FEET / MINUTE

O/A = OUTSIDE AIRMUA = MAKE UP AIRFPM = FEET PER MINUTEEF = EXHAUST FAN

S/A = SUPPLY AIRRTU = ROOFTOP UNITR/A = RETURN AIRPKG = PACKAGE UNIT

ZD = ZONE DAMPERVTE = VENT TO EXTERIORT/A = TRANSFER AIRSF = SUPPLY FAN

HVAC SYMBOLS

FMC 603.151 WAY THROW

CEILING REGISTER

FMC 603.152 WAY THROW

CEILING REGISTER

FMC 603.153 WAY THROW

CEILING REGISTER

FMC 603.154 WAY THROW

CEILING REGISTER

FMC 603.15CORNER THROW

CEILING REGISTER

FMC 603.152 WAY THROW

WALL REGISTER

FMC 603.152 WAY THROW

FLOOR REGISTER

AIR FMC 603.15FILTER RETURNFLOOR GRILLE

AIR FMC 603.15FILTER RETURNCEILING GRILLE

AIR FMC 603.15FILTER RETURN

WALL GRILLE

FMC 603.15DIRECT T/ A

WALL GRILLE

FMC SECTION 603DUCTWORKFLEXIBLE

FMC SECTION 603DUCTWORK

RECTANGULAR

SECTION 603BOXES FMC

AIR DISTRIBUTION

FMC SECTION 602PLENUM TRUNK

RETURN AIR

FMC SECTION 602PLENUM TRUNK

SUPPLY AIR

CAP FMC 504ROOF / WALLDRYER VENT

FMC 505 - 506ROOF / WALL CAP

RANGE VENT

ABOVE FLOORHUMIDISTAT @ 60"WALL MOUNTED

FMC SECTION 606SMOKE DETECTOR

DUCT MOUNTED

FEC 13-613ABOVE FLOOR

THERMOSTAT @ 60"

FMC SECTION 307DRAIN TO GRASS

CONDENSATE

PIPING FMC 1101REFRIGERANT

CONTROL /

FMC SECTION 403EF-1 or as NOTED

EXHAUST FAN

FMC SECTION 306ACCESS PANEL

EQUIPMENT

FMC SECTION 307TO DRYWELLCONDENSATE

FMC SECTION 607FIRE DAMPER

DUCT MOUNTED

FMC 603.15CONTROL DAMPER

AIR VOLUME

303 --- 312FMC SECTIONS

HANDLER ON STANDVERTICAL AIR

FMC 303 -- 312AIR DAMPER

ZONE CONTROL

D

R R

T

DS

FMC 303 -- 312DAMPER

BYPASS AIR

303 -- 312FMC SECTIONS

ON SLABCONDENSING UNIT

ZD

BP

303 --- 312FMC SECTIONS

FROM STRUCTUREHANDLER MOUNTHORIZONTAL AIR

303 -- 312FMC SECTIONS

ROOF MOUNTEDPACKAGE UNIT

303 -- 312FMC SECTIONSSLAB MOUNTEDPACKAGE UNIT

30 CFM T/A1" UNDERCUT DOOR

H

303 -- 312FMC SECTIONS

HANDLERDUCTLESS AIR

= DEVICE NECK SIZE

= BRANCH DUCT SIZE

ADJUSTMENTS= AIRFLOW CFMWalk In Closet

Bedroom

4"

32

8x4

TYPICAL ROOM

DUCTBRANCHTYPICAL

DEVICETYPICAL AIR

D

FMC 603.15DUCTED T/ A

CEILING GRILLE

Restroom

Unit 3 G

Restroom

Unit 3 F

Unit 3 Esouth

Unit 3 DeastUnit 3 Dwest

Restroom

Restroom

Restroom

Unit 3 AUnit 3 BUnit 3 C

Unit 3 Enorth

THIRD FLOOR

22x22,8",198 CFM22x22,8",198 CFM

Restroom

T/A DUCT12x12,9"TYPICAL

T/ACFM106

EXHAUST AIR EQUAL TO FRESH AIRTYPICAL

22x22,16",-1080 CFM

T/ACFM148

T/ACFM125

T/ACFM107

T/ACFM147

T/ACFM127

22x22,198 CFM22x22,198 CFM

22x22,198 CFM 22x22,198 CFM

8x4,4",14 CFM

22x22,8",198 CFM22x22,8",198 CFM

22x22,8",198 CFM22x22,8",198 CFM

22x22,8",198 CFM22x22,8",198 CFM

8x4,4",12 CFM

22x22,16",-1040 CFM

EF-1VTE

NOTEDUNLESSTYPICAL

TO GUTTER / GRASSCONDENSATE DRAIN

TYPICAL

ON ROOF

RTU-1ON ROOF

RTU-2

22x22,8",197 CFM22x22,8",197 CFM

22x22,8",197 CFM

22x22,8",197 CFM

22x22,8",197 CFM

22x22,8",197 CFM

8x4,4",15 CFM

22x22,16",-1060 CFM

ON ROOF

RTU-3

18

x1

6

18

x1

6

18

x1

6

22x14 22x14 22x14

12

x1

21

2x

12

12

x1

21

2x

12

12

x1

21

2x

12

22x22,9",267 CFM

22x22,9",267 CFM

22x22,9",267 CFM22x22,9",267 CFM

22x22,9",267 CFM 22x22,9",267 CFM

22x22,18",-1400 CFM

ON ROOF

RTU-4

22x14

18

x1

61

2x

14

12

x1

4

ON ROOF

RTU-5

22x22,9",267 CFM

22x22,9",267 CFM

22x22,9",267 CFM

22x22,9",267 CFM

22x22,9",267 CFM

22x22,18",-1400 CFM

22x22,9",267 CFM

22x14

18

x1

61

2x

14

8x14 16x14

RELIEF / TYPICAL OF 4 ZONESGRILLE -- FOR INTERIOR AIR PRESSURERELIEF AIR DAMPER + 12x12 RELIEF AIRTYPICAL 12x12 LOUVER + BAROMETRIC

ROOFTOP EQUIPMENTFRESH AIR INTAKE @

TYPICAL

22x22,9",267 CFM

22x22,9",267 CFM

22x22,9",267 CFM

22x22,9",267 CFM

22x22,9",267 CFM

22x22,18",-1400 CFM

22x22,9",267 CFM

ON ROOF

RTU-6

22x14

18x16 12x14

8x14

16x14

22x22,9",267 CFM

22x22,9",267 CFM

22x22,9",267 CFM

22x22,9",267 CFM

22x22,9",267 CFM

22x22,9",267 CFM

22x22,18",-1400 CFM

ON ROOF

RTU-7

22x14

18x16 12x1412x14

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM 22x22,8",198 CFM

22x22,198 CFM

22x22,16",-1060 CFM

8x4,4",13 CFM

22

x1

4

12x1218x1612x12

ON ROOF

RTU-8

22x22,9",265 CFM

22x22,9",265 CFM

22x22,9",265 CFM 22x22,9",265 CFM

22x22,18",-1440 CFM

22x22,9",265 CFM

22x22,9",265 CFM

8x4,4",13 CFM

22x14

12x1412x14 18x16

ON ROOF

RTU-9

8x4,4",13 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,8",198 CFM

22x22,16",-1080CFM

Unit 3 H

22

x1

4

12x1218x1612x12

ON ROOF

RTU-10

SECOND FLOORSSPLIT SYSTEMS SERVE FIRST AND

CONDENSING UNIT ON ROOF ABOVETYPICAL CURB MOUNTED

ROOFTOP EQUIPMENT SCHEDULE PACKAGE UNIT MARK: RTU-1,2,3,8,10 RTU-4,5,6,7,9UNIT MANUFACTURER: TRANE TRANE

UNIT MODEL NUMBER: THC033A3 THC043A3

NOMINAL A/C TONS : 3 4

UNIT CONFIGURATION: DOWNFLOW DOWNFLOW

UNIT DIMEN H/W/D: 37X45X70 37X45X70

UNIT WEIGHT: 627 669

SUPPLY PLENUM SIZE : 17X15 17X15

RETURN PLENUM SIZE : 23X14 23X14

SUPPLY FAN CFM / SP : 1200 / .4 1600 / .4

SUPPLY FAN H/P : 1 1

OUTDOOR AIR CFM: 120/160/140/140/120 200/200/200/200/160

UNIT PHASE / HERTZ: 3/60 3/60

UNIT VOLTAGE: 208/230 208/230

UNIT MCA: 19.9 22.6

UNIT MAX BREAKER: 30 35

HEATER KW: 4.5/6 9/12

HEATER MCA: 21.9/24.3 37.5/42.4

HEATER BREAKER: 25/25 40/45

TOTAL COOLING BTUH: 38,000 49,800

SENS. COOLING BTUH: 28,800 39,400

LAT. COOLING BTUH: 9,200 10,400

TOTAL HEATING BTUH: 20,472 40,944

SENS. HEAT % 0.76 0.79

COOLING EFFICIENCY: 13 13

THERMOSTAT MODEL: T8411R1002 T8411R1002

NOTES: ALTERNATE BRAND EQUIPMENT WITH

EQUAL PERFORMANCE ARE ACCEPTABLE.

SUBMIT PERFORMANCE DATA FOR APPROVAL.

EXHAUST FAN SCHEDULE FAN MARK: EF-1MANUFACTURER: NUTONE

MODEL NUMBER: QT-150

FAN TYPE: EXHAUST

FAN CFM: 140

TOTAL PRESSURE: .25

FAN VOLTAGE: 120/1/60

FAN AMPERAGE: 1.0

FAN DIMEN LWH: 14X10X9

DUCT OUTLET SIZE: 3.25X10 TO 7

DUCT INLET SIZE: 15X11

FAN WEIGHT: 14

NOTES: 1,2

1 = VENT TO EXTERIOR

2 = INTERLOCK WITH LIGHTS

THIRD FLOOR AIR BALANCE SCHEDULEZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

1 Unit 3 A 6 > 3 HRS 1186 1080 0 120

1 Restroom 0 N/A 14 0 120 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

2 Unit 3 B 8 > 3 HRS 1188 1040 0 160

2 Restroom 0 N/A 12 0 160 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

3 Unit 3 C 7 > 3 HRS 1185 1060 0 140

3 Restroom 0 N/A 15 0 140 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM

4 Unit 3 Deast 10 > 3 HRS 1600 1400 200 200X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM

5 Unit 3 Dwest 10 > 3 HRS 1600 1400 200 200X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM

6 Unit 3 Enorth 10 > 3 HRS 1600 1400 200 200X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM RELIEF AIR CFM FRESH AIR CFM

7 Unit 3 Esouth 10 > 3 HRS 1600 1400 200 200X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

8 Unit 3 F 7 > 3 HRS 1187 1060 0 140

8 Restroom 0 N/A 13 0 140 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

9 Unit 3 G 8 > 3 HRS 1587 1440 0 160

9 Restroom 0 N/A 13 0 160 0X X X X X X X X

ZONE ROOM NAME OCCUPANTS DURATION SUPPLY AIR CFM RETURN AIR CFM EXHAUST AIR CFM FRESH AIR CFM

10 Unit 3 H 6 > 3 HRS 1187 1080 0 120

10 Restroom 0 N/A 13 0 120 0

THIRD FLOOR TOTALS 82 > 3 HRS 14000 12360 1640 1640

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

THIRD FLOOR VENTILATION CALCULATION TIME CLASSIFICATION OCCUPANTS DURATION MAX. REQ. AIR ADJUSTED AIR TOTAL AIR CFM / SQ FOOT

PEAK Office 82 1.00 20 20 1640 20

THIRD FLOOR TOTALS 82 1640

THIS BUILDING COMPLIES WITH THE 2004 FLORIDA MECHANICAL CODE SECTION 403.1 AND SECTION 403.3 VENTILATION TABLE

THE TEST AND BALANCE CONTRACTOR SHOULD ADJUST THE INTERIOR BUILDING PRESSURE SLIGHTLY POSITIVE ( 4% OF TOTAL CFM )

CURB

ROOFTOP PACKAGE UNIT DETAIL

CONNECTIONCURB

CURB

601FMC

DUCTS/A

601FMC

DUCTR/A

CONNECTIONDUCT

CONNECTIONEQUIPMENT

FMC 303EQUIPMENTROOFTOP

SPAN 3 JOISTS1/4" THK

2" U CHANNEL X

ROOF

@ 18" O.C.3/8 BOLT

JOIST

EQUIPMENTROOFTOP

DUCT @ 8" O.C.SCREWS

1/2"

FMC 601SEALDUCT

CURB

EQUIPMENTROOFTOP

CORNEREACH

ANGLE(1) 1/4x2x2SCREWS(4) 3/8x2

MECHANICALLY FASTEN EQUIPMENT TO CURB FOR UP TO 140 M.P.H. WIND LOADMECHANICALLY FASTEN AND SEAL DUCTS PER FMC SECTIONS 603 AND 604

MECHANICALLY FASTEN CURB TO ROOF STRUCTURE FOR 140 M.P.H. WIND LOAD

DOWN FOR A MAXIMUM OF 140 MPH WINDBOLT AND SCREW SIZES MAY VARY - TIEANGLE PLATE, OR STRAP FOR TIE DOWNA/C CONTRACTOR MAY USE FLAT PLATE,

NOTE: TIE DOWN METHOD MAY VARY