Hunter Bldg Test 2008

  • Upload
    liu-leo

  • View
    219

  • Download
    0

Embed Size (px)

Citation preview

  • 8/8/2019 Hunter Bldg Test 2008

    1/70

    ABSG Consulting Inc. 14607 San Pedro Avenue, Suite 215 San Antonio, TX 78232 USA

    Tel: 210-495-5195 Fax: 210-495-5134

    www.absconsulting.com

    1

    Hunter Building and Manufacturing

    Standard BuildingFull Scale Explosive Testing

    Prepared For:

    Hunter Buildings and Manufacturing

    Houston, TX

    Final Report

    Project Number 1749999

    Prepared By:

    Ben Harrison, P.E.

    Darrell Barker, P.E.

    Jerry Collinsworth

    July 9, 2008

  • 8/8/2019 Hunter Bldg Test 2008

    2/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    i

    Executive Summary

    ABS Consulting conducted two full scale field tests utilizing 1,250 pounds of ANFO explosive

    on a standard 8 psi, 200 msec Heavy Response Hunter blast resistant modular building. The

    purpose of the explosive testing was to determine performance of the building at the upper limitof Medium Response (Test I) and the upper limit of High Response (Test II). Testing consisted

    of the detonation of a 1,250 lbANFO charge at a range of 100 feet for Test I and 75 feet for Test II.

    The ANFO charge was placed on the door side of the building for Test I and the opposite wall

    for Test II. Peak side-on pressures were 9.7 psi for Test I and 17.4 psi for Test II.

    Test I - Medium Response

    Performance of the structure in Test I was consistent with ASCE Medium Response. While

    primary components exhibited some plastic deformation, structural integrity was not

    compromised. Test I resulted in a peak wall panel deformation of 6.3 inches which corresponds

    to 6 degrees of support rotation, consistent with ASCE Medium Response limits for steel plates.Material strain data was not collected during the test but post-test evaluation of the response

    indicated peak strains on the order of 4% which is also consistent with the selected design strain

    limit for ASCE Medium Response. Peak wall accelerations were approximately 400 g. Peakbuilding sliding varied between 2 and 3 inches with a peak sliding acceleration of approximately

    25g. Tipping was not observed.

    An instrumented Hybrid III 50th percentile male car crash dummy was placed in the building for

    Test I with the back of the Hybrid IIIs chair placed against the reflected wall. The peak

    acceleration measured in the Hybrid III was 8 g. This acceleration is due to overall building

    movement with some decoupling provided by the chair. Although the Hybrid III was situated

    directly against the reflected wall only of the peak kinematic building acceleration wastransmitted to the Hybrid III. Relatively light damage was observed inside the building. Interior

    furnishings and suspended items were dislodged. Acoustical ceiling tiles were down in some

    sections of the building. The main ceiling grid components remained intact, but some of the

    ceiling grid cross members were dislodged. Items placed on shelves were dislodged. Two fireextinguishers located on the blast wall came free from the mounting brackets.

    Blast doors manufactured by Booth Industries were installed on the reflected wall facing theblast in Test I. Door latches were damaged during the test. One door rebounded open during the

    test and the other door was jammed in the opening; therefore, the doors were found to be Intact

    but Inoperable. There was no apparent structural deformation of the door beams. Hunter hasbeen manufacturing and installing its own blast doors which have been analyzed in separate

    evaluation and testing.

  • 8/8/2019 Hunter Bldg Test 2008

    3/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    ii

    Test II - High Response

    Test II resulted in approximately 17.5 inches of deformation on the wall facing the blast as

    integrated from the reflected wall accelerometer. Peak measured acceleration on the wall was onthe order of 2,000 g. Post-test evaluation indicated peak strains on the order of 10% which is

    below the 15% value used for design. The peak wall deformation of 17.5 inches corresponds toa support rotation of 17 degrees. This response exceeds the ASCE support rotation limits forHigh Response for plates (12 degrees); however, damage to the structure was less than the

    qualitative building damage description for High Response in the ASCE guideline. While

    significant deformation occurred, the primary components were not at incipient collapse andwere not in danger of collapsing under environment loads (wind, etc.) as described by the ASCE

    guideline for High response. Interior objects from the reflected wall including the desk, shelf,

    cabinets and drywall had significant movement. The high debris velocity was evidenced by

    penetrating impacts of desk coping into the veneer of the interior doors. The instrumenteddummy was not used for this test.

    Both Booth blast doors on the rear face of the building, away from the charge, rebounded openduring Test II; however, the latches on the doors were damaged in Test I and thus did not have

    the restraining capacity of an undamaged door.

    Pressures were measured inside the building and were 3.7 psi during Test I and 4.5 psi during

    Test II. Interior pressures did not appear to be the result of blast infiltration into the building but

    may be attributed to the deformation of structural components. Sliding during Test II variedfrom 13-20 inches at the corners. Tipping was not observed in the high speed video.

    Analysis of Results

    Post-test modeling of the structure revealed that it was more flexible than predicted in theoriginal building analysis due to eave strut deformation. A revised model was prepared whichbetter matched the test results. This model results in greater wall deformation and support

    rotation than the original analysis for the same strain value.

    For Test I, the observed deflections were consistent with strain and rotation limits for Medium

    Response in the ASCE guideline.

    For Test II, deformations were less than High Response based on strain limits but observed

    deformations were greater than High Response for support rotation limits. Thus if the design is

    based on strain limits, deflections at maximum capacity will be greater than observed in the test.

    If the design is based on support rotation, response at maximum capacity will be less thanobserved in the test.

    Designing to the ASCE Building Damage descriptions in Table 5.B utilizing stain limits for thewall panels can be an appropriate approach; however, design based on support rotation limits is a

    more common approach. In either approach, it is important for the user to understand the

    deformations associated with the design and determine which is appropriate for the intended use.

  • 8/8/2019 Hunter Bldg Test 2008

    4/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    iii

    The utilization of support rotations is incorporated in blast design as a simplified measure ofdamage. However, with the advent of more powerful computing and modeling techniques more

    sophisticated measures of damage may be utilized. This includes the use of plastic strain, rather

    than support rotation response criteria. Plastic strains occur as a component is deformed beyondits elastic capacity. The amount of deformation required to cause a given amount of plastic

    strain is a function of several variables, many of which can be non-linear. Examples of variablesthat affect the level of plasticity and deformation a component can withstand include the materialproperties, level of fixity provided at the component supports and the stability of the cross-

    section.

    Using strain limits, a revised structural model based on the test, and incorporating clearingeffects, the free-field blast capacity at the limit of High Response is consistent with the 8 psi

    value. For a design based on ASCE support rotation limit criteria and including clearing, the

    free-field blast capacity at High Response is 7.3 psi with the short wall facing the blast and 8.0psi with the long wall facing the blast.

    Using strain limits, with the revised structural model based on the test and incorporating clearingeffects, the free-field blast capacity at the limit of Medium response is consistent with the 5.6 psi

    value. For a design based on ASCE support rotation limit criteria and including clearing, the

    free-field blast capacity at Medium Response is 5.9 psi, which is consistent with the design

    value.

    When selecting the appropriate response level and design criteria, vulnerability of occupants to

    debris and dislodged objects should be considered in addition to the response of structuralcomponents. Assessment of vulnerability was beyond the scope of this test program.

    If the Booth blast doors are used, at least one should be facing away from a potential blast.

    /

  • 8/8/2019 Hunter Bldg Test 2008

    5/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    iv

    Executive Summary......................................................................................................................... i

    List of Figures................................................................................................................................. v

    List of Tables ................................................................................................................................ vii1. Purpose.................................................................................................................................... 1

    2. Building Layout and Construction.......................................................................................... 13. Test Configurations................................................................................................................. 33.1. Explosive Charge Siting ................................................................................................. 4

    3.2. Instrumentation ............................................................................................................... 5

    3.3. Test I Configuration...................................................................................................... 10

    3.3.1. Range and Explosive Charge................................................................................ 103.3.2. Building Instrumentation Placement..................................................................... 12

    3.4. Test II Configuration..................................................................................................... 17

    3.4.1. Range and Explosive Charge................................................................................ 173.4.2. Building Instrumentation Placement..................................................................... 18

    4. Test I Results......................................................................................................................... 22

    4.1. Free Field and Applied Pressures ................................................................................. 224.2. Observed Damage......................................................................................................... 27

    4.3. Structural Response Measurements .............................................................................. 38

    4.3.1. Sliding and Tipping............................................................................................... 39

    4.3.2. Wall Panel............................................................................................................. 404.3.3. Roof Joists............................................................................................................. 42

    5. Test II Results ....................................................................................................................... 43

    5.1. Free Field and Applied Pressures ................................................................................. 435.2. Observed Damage......................................................................................................... 48

    5.3. Structural Response Measurements .............................................................................. 555.3.1. Sliding and Tipping Response .............................................................................. 56

    5.3.2. Wall Panel Response............................................................................................. 57

    5.3.3. End Wall Eave Strut Response ............................................................................. 596. Summary............................................................................................................................... 60

  • 8/8/2019 Hunter Bldg Test 2008

    6/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    v

    List of Figures

    Figure 1. Hunter Building Floor Plan ............................................................................................ 1

    Figure 2. Hunter Building Exterior Elevations .............................................................................. 2Figure 3. Test Building Framing Plans and Framing Elevations................................................... 3

    Figure 5. PCB 102A07 Pressure Transducer ................................................................................. 5Figure 6. Typical Reflected Pressure Gauge Mount...................................................................... 6Figure 7. PCB 350B23 Shock Accelerometer ............................................................................... 6

    Figure 8. Wall Typical Accelerometer Mount............................................................................... 7

    Figure 9. Sliding and Tipping Accelerometer Mount.................................................................... 7Figure 10. HYBRID III 50th Percentile Male Crash Test Dummy................................................ 8

    Figure 11. Yokogawa DL750 Oscilloscope................................................................................... 9

    Figure 12. Instrumentation Bunker................................................................................................ 9Figure 13. Concrete Footing and Spray Paint Marker ................................................................. 10

    Figure 14. Test I - Range Layout................................................................................................. 11

    Figure 15. Test I - Skirted Building............................................................................................. 11

    Figure 16. Test I - Explosive Charge........................................................................................... 12Figure 17. Test I - Building Layout Relative to Explosive Charge ............................................. 13

    Figure 18. Test I - Reflected Wall Instrumentation (Elevation 2) ............................................... 13

    Figure 19. Test I - Rear Wall Instrumentation (Elevation 1)....................................................... 14Figure 20. Test I - Sidewall Instrumentation (Elevation 3) ......................................................... 14

    Figure 21. Test I - Roof Instrumentation ..................................................................................... 15

    Figure 22. Test I - Instrumented Hybrid III Placement ............................................................... 16Figure 23. Test I - Interior Cameras and Instrumentation ........................................................... 16

    Figure 24. Test II - Explosive Charge.......................................................................................... 17

    Figure 25. Test II - Unskirted Building ....................................................................................... 18

    Figure 26. Test II - Range Layout................................................................................................ 18

    Figure 27. Test II - Building Layout Relative to Explosive Charge............................................ 19Figure 28. Test II - Reflected Wall Instrumentation (Elevation 1).............................................. 19

    Figure 29. Test II - Rear Wall Instrumentation (Elevation 2)...................................................... 20

    Figure 30. Test II - Sidewall Instrumentation (Elevation 3)........................................................ 20

    Figure 31. Test II - Roof Instrumentation.................................................................................... 21Figure 32. Test II - Interior Cameras and Instrumentation .......................................................... 21

    Figure 33. Test I Crater................................................................................................................ 22

    Figure 34. Test I - Free-Field Pressure Time History.................................................................. 23Figure 35. Test I - Reflected Wall Pressure Time History #1 ...................................................... 24

    Figure 36. Test I - Reflected Wall Pressure Time History #2 ...................................................... 24

    Figure 37. Test I- Applied Roof Pressure Time History.............................................................. 25Figure 38. Test I - Applied Rear Wall Pressure History.............................................................. 25

    Figure 39. Test I - Interior Pressure Time History (Occupied Volume)...................................... 26

    Figure 40. Test I - Interior Pressure Time History (Plenum)....................................................... 26

    Figure 41. Test I - Reflected Wall Damage (Weld Cracks Spray Painted Magenta) .................. 28Figure 42. Test I - Rear Wall Damage......................................................................................... 28

    Figure 43. Test I - Roof Damage ................................................................................................. 29

    Figure 44. Test I - Passive Building Sliding Measurements........................................................ 30Figure 45. Test I - Damage to HVAC: (a) Exterior and (b) Interior........................................... 31

  • 8/8/2019 Hunter Bldg Test 2008

    7/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    vi

    Figure 46. Test I - Booth Blast Door Response: (a) Leftmost Door and (b) Rightmost Door ... 32Figure 47. Test I - Booth Door Latch Damage: (a) Pre-Test and (b) Post-Test ......................... 32

    Figure 48. Test I - HYBRID III: (a) Pre-Test and (b) Post-Test................................................. 33

    Figure 49. Test I - HYBRID III Measured Accelerations ........................................................... 34Figure 50. Test I - Mannequin: (a) Pre-Test and (b) Post-Test.................................................. 35

    Figure 51. Test I - Building Interior: (a) Pre-Test and (b) Post-Test Damage............................ 35Figure 52. Test I - Cabinet Movement on Reflected Wall........................................................... 36Figure 53. Test I - Lavatory Fixtures: (a) Pre-Test and (b) Post-Test Damage.......................... 36

    Figure 54. Test I - Interior Wall Damage: (a) Drywall Pulling Away and (b) Metal Stud

    Damage ................................................................................................................................. 37

    Figure 55. Test I - Fire Extinguisher Throw................................................................................ 38Figure 56. Test I Measured Sliding Time History .................................................................... 39

    Figure 57. Test I - Measured Tipping Time History.................................................................... 40

    Figure 58. Test I - Total Wall Panel Response Time History (Includes Sliding)........................ 41Figure 59. Test I - Relative Wall Panel Response Time History................................................. 41

    Figure 60. Test I - Roof Joist Response Time History ................................................................ 42

    Figure 61. Test II Crater............................................................................................................... 43Figure 62. Test II - Free-Field Pressure Time History................................................................. 44

    Figure 63. Test II - Reflected Wall Pressure Time History #1.................................................... 45

    Figure 64. Test II - Reflected Wall Pressure Time History #2.................................................... 45

    Figure 65. Test II - Applied Roof Pressure Time History ........................................................... 46Figure 66. Test II - Applied Rear Wall Applied Pressure Time History ..................................... 46

    Figure 67. Test II - Interior Pressure Time History (Occupied Volume) .................................... 47

    Figure 68. Test II - Interior Pressure Time History (Plenum) ..................................................... 47Figure 69. Test II - High Speed Video Capture of Peak Wall Panel Response........................... 48

    Figure 70. Test II - Reflected Wall Damage................................................................................ 49Figure 71. Test II - End Wall Damage......................................................................................... 49

    Figure 72. Test II - Roof Deck Damage ...................................................................................... 50

    Figure 73. Test II - Floor Deck Damage...................................................................................... 50Figure 74. Test II - Passive Building Sliding Measurements ...................................................... 51

    Figure 75. Test II - Damage to HVAC: (a) Exterior and (b) Interior ......................................... 52

    Figure 76. Test II - Damage to HVAC Duct................................................................................ 52Figure 77. Test II - Office Room: (a) Pre-Test and (b) Post- Test............................................. 53

    Figure 78. Test II - Desk Debris Impacts: (a) Door Scarring and (b) With Impacting Debris ... 53

    Figure 79. Test II - Central Work Room: (a) Pre-Test and (b) Post Test ................................... 54

    Figure 80. Test II - Interior Debris............................................................................................... 54Figure 81. Test II - Light Fixture Damage................................................................................... 55

    Figure 82. Test II - Measured Sliding Time History ................................................................... 56

    Figure 83. Test II - Measured Tipping Time History .................................................................. 57Figure 84. Test II - Total Wall Panel Response Time History (Includes Sliding)....................... 58

    Figure 85. Test II - Relative Wall Panel Response Time History ............................................... 58

    Figure 86. Test II - End Wall Eave Strut Response Time History .............................................. 59

  • 8/8/2019 Hunter Bldg Test 2008

    8/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    vii

    List of Tables

    Table 1. Test Structure Component Cut List ................................................................................. 2Table 2. ASCE Response Range Descriptions .............................................................................. 4

    Table 3. Test I - Deformation Limits............................................................................................. 4Table 4. Test II - Deformation Limits............................................................................................ 5Table 5. Test I - Measured and Applied Load Summary............................................................. 23

    Table 6. Test I - Measured Response Summary .......................................................................... 39

    Table 7. Test II - Measured and Applied Load Summary ........................................................... 44Table 8. Test II - Measured Response Summary......................................................................... 55

  • 8/8/2019 Hunter Bldg Test 2008

    9/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    1

    1. Purpose

    Hunter Buildings and Manufacturing LLC. (Hunter) manufactures blast resistant portable

    buildings for the petroleum and chemical process industries. The purpose of a blast resistantmodular building is to provide increased protection to occupants over that which would be

    provided by portable trailers of conventional construction.

    Hunter Buildings contracted ABSG Consulting Inc (ABS Consulting) to perform two full scale

    tests utilizing 1,250 pounds of ANFO. The purpose of the explosive testing was to test the

    design and manufacturing of Hunter Buildings standard building at the upper limit of MediumResponse and the upper limit of High Response as defined by the American Society of Civil

    Engineers (ASCE)Design of Blast Resistant Buildings in Petrochemical Facilities.[i]

    2. Building Layout and Construction

    The Hunter standard building utilized in the test measured 40 feet by 12 feet in plan and had an

    eave height of 11 feet. A floor plan of the tested building is shown below in Figure 1 and

    exterior elevations are provided in Figure 2. The building was constructed with the componentsshown in the framing plans and elevations in Figure 3 and specified in the cut list presented in

    Table 1. Blast doors were manufactured by Booth Industries.

    Figure 1. Hunter Building Floor Plan

    i ASCE, Design of Blast Resistant Buildings in Petrochemical Facilities, Task Committee on Blast Resistant

    Design, American Society of Civil Engineers, NY, NY, 1997.

  • 8/8/2019 Hunter Bldg Test 2008

    10/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    2

    Figure 2. Hunter Building Exterior Elevations

    Table 1. Test Structure Component Cut ListItem DimensionsTolerance No. of Pieces

    CL1 HSS 6 x 6 x .625 A500B 11'-2" +0/-.125 4

    CL2 HSS 6 x 6 x .500 A500B 10'-0" +0/-.125 7

    B1 HSS 6 x 6 x .500 A500B 39'-0" +0/-.125 2

    B2 HSS 6 x 6 x .500 A500B 11-0" +0/-.125 2

    R1 HSS 6 x 6 x .500 A500B 39'-0" +0/-.125 2

    R2 HSS 6 x 6 x .500 A500B 11'-0" +0/-.125 2

    W1 HSS 6 x 6 x .500 A500B 3-0 +0/-.125 0

    D1 HSS 6 x 6 x .500 A500B 3-1 1/2 +0/-.125 2

    FJ1 HSS 6 x 2 x .3125 A500B 11'-0" +0/-.125 21

    RJ1 C 6 x 13# A-36 11'-0" +0/-.125 19

    RA1 Angle 2" x 2" x 1/8" A-36 39' +0/-.125 12

    HRS 10 GA 17

    HRS 12 GA 872" x 240"

    84" x 120"

    A1011-36

    Description

    A1011-36

  • 8/8/2019 Hunter Bldg Test 2008

    11/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    3

    Figure 3. Test Building Framing Plans and Framing Elevations

    3. Test Configurations

    ABS Consulting tested a single standard Hunter Building two times. The building was not

    manufactured specifically for this test but was pulled from the rental fleet at random. Therefore,

    the building was representative of dimension, material, and fabrication of Hunters fleet ofbuildings and was not manufactured with the knowledge that it was for testing.

    The purpose of Test I was to test the building at the upper limit of Medium Response in order tovalidate analysis methods and building response mechanisms. The purpose of Test II was to

    determine potential failure mechanisms at the upper limits of capacity. Therefore, the building

    was sited at a standoff predicted to cause a wall panel deformation at the upper limit of High

    Response.

    The following sections describe the instrumentation and instrumentation placement utilized to

    achieve the goals for each test.

  • 8/8/2019 Hunter Bldg Test 2008

    12/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    4

    3.1.Explosive Charge SitingThe goal of the test program was to perform two full scale high explosive tests utilizing 1,250 lbsof Ammonium Nitrate and Fuel Oil (ANFO). ANFO has a TNT equivalency of 0.82 for both

    pressure and impulse which produces a TNT equivalent charge weight of 1,025 lbs TNT[ii]

    . Thefirst explosive charge was configured to test the upper limit of Medium Response and the secondexperiment, with the charge placed on the opposite side of the structure, was configured to test

    the upper limit of High Response. The design basis response levels are defined by ASCEs 1997

    Design of Blast Resistant Buildings in Petrochemical Facilities[i]

    . Response limits in Table 3were utilized for Test I and response limits in Table 4 were utilized for Test II. These support

    rotation limits are more conservative than the strain limit criteria used for the design. Support

    rotations were used because they are a more conservative approach and are commonly used inthe industry. Table 2 provides ASCEs written descriptions for the ASCE response levels. The

    original design basis utilized these written descriptions and assigned strain limits to each

    response level to quantify the design utilizing a strain limit of 7.5% for Medium Response and a

    strain limit of 15% for High Response. A standoff of 100 ft was chosen for the first test and astandoff of 75 feet was chosen for the second test.

    Table 2. ASCE Response Range DescriptionsResponse Range Description

    Low

    Localized building/component damage. Building can be used,

    however repairs are required to restore integrity of structural envelope.Total cost of repairs is moderate.

    Medium Widespread building/component damage. Building cannot be used

    until repaired. Total cost of repairs is significant.

    High Building/component has lost structural integrity and may collapse due

    to environmental conditions. Total cost of repairs approach

    replacement cost of building

    Table 3. Test I - Deformation Limits

    Test Target Deformation LimitComponent

    (deg) (in)Wall Panel

    *Designed for plasticity only and qualitativedescriptions in Table 2.

    Roof and Floor Deck 6 10 1.2 in

    Roof Joist 6 10 6.9 in

    Floor Joist 6 10 6.9 in

    End Wall Eave and

    Sill Struts

    6 10 6.9in

    Door Column (Low) 2 3 2.1 in*Corrugated panel response criteria were not adopted as they were intended for thin gauge

    (< 1/8-inch) panels. Plasticity limit criteria via FEA were utilized.

    **Design of Columns supporting doors were limited to Low Response in order to aide

    egress.

    ii ConWep, Conventional Weapons Effects Program, Structures Laboratory, U.S. Army Engineer Waterways

    Experiment Station, Vicksberg, Mississippi, V. 2.1.0.8.

  • 8/8/2019 Hunter Bldg Test 2008

    13/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    5

    Table 4. Test II - Deformation Limits

    Test Target Deformation LimitComponent

    (deg) (in)Wall Panel* Designed for plasticity only and qualitative

    descriptions in Table 2.Roof and Floor Deck 12 20 2.5 in

    Roof Joist 12 20 14 in

    Floor Joist 12 20 14 in

    End Wall Eave and

    Sill Struts

    12 20 14 in

    *Corrugated panel response criteria were not adopted as they were intended for thin gauge

    (< 1/8-inch) panels. Plasticity limit criteria via FEA were utilized.

    **Design of Columns supporting doors were limited to Low Response in order to aide

    egress.

    3.2.InstrumentationIn order to measure free-field and applied pressures nine PCB 102A07 pressure transducers, see

    Figure 4, were utilized. These transducers measure pressure in the presence of shock and

    vibration. The pressure probe consists of the Model 112A high sensitivity acceleration

    compensated quartz element and an IC source follower amplifier joined together as aninseparable assembly and can measure pressures up to 50 psi utilizing 5 v output and has a useful

    over range of 100 psi utilizing 10v output.

    Figure 4. PCB 102A07 Pressure Transducer

  • 8/8/2019 Hunter Bldg Test 2008

    14/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    6

    Figure 5. Typical Reflected Pressure Gauge Mount

    Three PCB 350B23 accelerometers, see Figure 6, and one PCB 350B02 accelerometer wereutilized for structural response measurements. The equations of motion are characterized bythree main variables: acceleration, velocity and displacement and these three variables can be

    mathematically derived from the measurements of acceleration. The PCB 350B02

    Accelerometer has a range of 50,000 g and the PCB 350B23 accelerometers have a range of

    10,000 g. The accelerometers are characterized by the following features:

    Fixed voltage sensitivity, regardless of cable type.

    Low-impedance output signal, which can be transmitted over long cables in harshenvironments with virtually no loss in signal quality.

    Two-wire operation with low cost coaxial cable.

    Requires only constant current signal conditioning.

    Figure 6. PCB 350B23 Shock Accelerometer

  • 8/8/2019 Hunter Bldg Test 2008

    15/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    7

    Figure 7. Wall Typical Accelerometer Mount

    Figure 8. Sliding and Tipping Accelerometer Mount

    A HYBRID III 50th Percentile male crash test dummy, representing the average adult male, was

    utilized to measure occupant response. The HYBRID III, see Figure 9, is the most widely used

    dummy in frontal crash and automotive safety restraint testing. The Hybrid IIIs height is 5 feet

    9 inches and weights 172.3 pounds. Originally, the Hybrid III 50th male was developed byGeneral Motors for vehicle safety purposes. It has since been incorporated into the Code of

    Federal Regulations under Title 49, Part 572 subpart E, and is the required dummy in NHTSAsmotor vehicle safety standards. The Hybrid III 50th male features a neck design that simulates

    the human dynamic moment / rotation, flexion, and extension response characteristics of an

    average size adult male. The upper torso has 6 high strength steel ribs with polymer baseddamping material to simulate human chest force-deflection characteristics. The lower torso has a

    curved cylindrical rubber lumbar spine that provide human-like slouch of a seated person. The

  • 8/8/2019 Hunter Bldg Test 2008

    16/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    8

    pelvis is vinyl skin/urethane foam molded over an aluminum casting in the seated position. Theball-jointed femur attachments carry bump stops to reproduce the human leg to hip

    moment/rotation characteristics.

    The Hybrid III was instrumented with three piezo-resistive accelerometers in the head with one

    in the vertical axis and two placed orthogonally in the horizontal plane, front to back and ear toear.

    Figure 9. HYBRID III 50th

    Percentile Male Crash Test Dummy

    Instrumentation measurements were measured utilizing a Yokogawa DL750 Oscilloscope,

    shown in Figure 10. The Oscilloscope is capable of recording up to sixteen channels at high data

    sampling rates (i.e., > 1 MHz). Testing experience indicates that a sampling rate of at least 500KHz or 500 samples per millisecond for shock pressure histories and 300 kHz (or 300 samples

    per millisecond) for acceleration time histories provides adequate fidelity for a structural

    response. This ensures that very short duration peaks in shock pressure and accelerationmeasurements are not missed by the data recording process. In general, a sample rate of 500

    KHz was used to record the test data when the Hybrid III was utilized and 1 MHz otherwise.The Yokogawa scope was placed within a bunker on the side of the building away from the

    charge as shown in Figure 11.

  • 8/8/2019 Hunter Bldg Test 2008

    17/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    9

    Figure 10. Yokogawa DL750 Oscilloscope

    Figure 11. Instrumentation Bunker

    The building was placed on concrete pads in order to more accurately assess the sliding response.

    In addition to utilizing accelerometers to measure sliding, the building position was marked

    using spray paint at each footing location as shown in Figure 12 so that the sliding distance could

    be observed directly.

  • 8/8/2019 Hunter Bldg Test 2008

    18/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    10

    Figure 12. Concrete Footing and Spray Paint Marker

    3.3.Test I ConfigurationThe purpose of Test I was to test the building at the upper limit of Medium Response in order to

    validate modeling methods and building response mechanisms. In order to achieve those goals

    the explosive charge and instrumentation were arranged to produce the desired level of walldamage, to measure the applied loads to the building and the level of structural response.

    3.3.1. Range and Explosive Charge

    The test arena was arranged with two free-field pressure gauges and three high speed cameras as

    shown in Figure 13. Free-field gauge #1 was placed in the shadow of the building from the

    explosive charge and free-field gauge #2 was placed at an identical range to the charge as thebuilding to measure the free-field pressures associated with the applied building loads. The

    explosive charge, Figure 15, was placed at a range of 100 ft from the center of the blastward wall

    of the building. The three high speed cameras were placed further from the explosive chargethan the building so that the structural response could be recorded by the cameras before the

    shockwave arrived at the camera locations.

    For the first test, the building was skirted with 2x12 wood joists along the reflected wall to

    prevent shock from traveling underneath the building. A photo of the skirted building is

    provided in Test I - Skirted Building. By preventing shock from traveling under the building the

    effects of the dynamic roof load on the friction force could be evaluated.

  • 8/8/2019 Hunter Bldg Test 2008

    19/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    11

    Figure 13. Test I - Range Layout

    Figure 14. Test I - Skirted Building

  • 8/8/2019 Hunter Bldg Test 2008

    20/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    12

    Figure 15. Test I - Explosive Charge

    3.3.2. Building Instrumentation Placement

    The building was oriented such that the building elevation holding the two blast doors was facing

    the charge as shown in Figure 16. Figure 16 also shows the numbering of the concrete footingsthe building was placed on for reference to passive sliding measurements. The reflected wall

    was instrumented with two pressure gauges for measuring the applied reflected load, and three

    accelerometers for measuring the wall panel response as well as the sliding and tipping response

    of the building. The reflected wall instrumentation plan is provided below in Figure 17.

  • 8/8/2019 Hunter Bldg Test 2008

    21/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    13

    100 ft

    2

    3

    1

    4

    100 ft

    22

    33

    11

    44

    Figure 16. Test I - Building Layout Relative to Explosive Charge

    Pressure

    Gauge

    Pressure

    Gauge

    Wall Panel

    Accelerometer

    Sliding and TippingAccelerometers

    Pressure

    Gauge

    Pressure

    Gauge

    Wall Panel

    Accelerometer

    Sliding and TippingAccelerometers

    Figure 17. Test I - Reflected Wall Instrumentation (Elevation 2)

    The leeward wall of the building was instrumented with a single pressure gauge to measure theapplied load to the backside of the building. An elevation of the back wall detailing the location

    of the pressure gauge is provided in Figure 18.

  • 8/8/2019 Hunter Bldg Test 2008

    22/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    14

    Pressure

    Gauge

    Pressure

    Gauge

    Figure 18. Test I - Rear Wall Instrumentation (Elevation 1)

    The sidewall of the building opposite of the HVAC equipment was instrumented with a pressuregauge, as shown in Figure 19, in order to measure the applied pressure to the enwall of the

    building.

    Pressure

    Gauge

    Pressure

    Gauge

    Figure 19. Test I - Sidewall Instrumentation (Elevation 3)

    The roof of the building was instrumented with a pressure gauge to measure the applied pressure

    at the center of the roof. An accelerometer was placed at the mid-span of a roof joist so that the

    response of the roof joist to the measured roof load could be evaluated. A detail of the roofinstrumentation plan is provided below in Figure 20.

  • 8/8/2019 Hunter Bldg Test 2008

    23/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    15

    Pressure

    Gauge

    Accelerometer Pressure

    Gauge

    Accelerometer

    Figure 20. Test I - Roof Instrumentation

    Cameras and instruments were also placed within the building to assess the occupant

    environment during structural response to the explosion. Three closed circuit cameras wereplaced inside the building along with an instrumented Hybrid III dummy (see Figure 21), amannequin and two pressure gauges. The Hybrid III was placed in a chair with the back of the

    dummy and chair resting against the reflected wall. A plan showing the location of the cameras

    and instruments is provided in Figure 22. As can be seen in Figure 22, the Hybrid III was placedaway from a column so that it could be impacted by the responding wall panel. One pressure

    gauge was placed in the occupied volume of the building and a second was placed within the

    plenum between the roof and drop ceiling so that any disparity of pressure between these twovolumes within the building could be evaluated.

  • 8/8/2019 Hunter Bldg Test 2008

    24/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    16

    Figure 21. Test I - Instrumented Hybrid III Placement

    Figure 22. Test I - Interior Cameras and Instrumentation

  • 8/8/2019 Hunter Bldg Test 2008

    25/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    17

    3.4.Test II ConfigurationThe purpose of Test II was to test potential building failure mechanisms and damage at the upper

    limits of High Response. In order to achieve those goals the explosive charge and

    instrumentation were arranged to produce the desired level of wall damage, to measure theapplied loads to the building and the level of structural response.

    3.4.1. Range and Explosive Charge

    The test arena was arranged with two free-field pressure gauges and three high speed cameras as

    shown in Figure 25. Free-field gauge #1 was placed in the shadow of the building from the

    explosive charge and free-field gauge #2 was placed at an identical range to the charge as thebuilding to measure the free-field pressures associated with the applied building loads. The

    explosive charge, Figure 23, was placed at a range of 75 ft from the center of the blastward wall

    of the building. The three high speed cameras were placed further from the explosive chargethan the building so that the structural response could be recorded by the cameras before the

    shockwave arrived at the camera locations.

    For the first test, the building was skirted with 2x12 wood joists along the reflected wall to

    prevent shock from traveling underneath the building. By preventing shock from traveling under

    the building the effects of the dynamic roof load on the friction force could be evaluated.

    Figure 23. Test II - Explosive Charge

  • 8/8/2019 Hunter Bldg Test 2008

    26/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    18

    Figure 24. Test II - Unskirted Building

    Figure 25. Test II - Range Layout

    3.4.2. Building Instrumentation Placement

    The building was oriented such that the building elevation holding the two blast doors was facingaway from the charge as shown in Figure 26. Figure 26 also shows the numbering of the

    concrete footings the building was placed on for reference to passive sliding measurements. The

    reflected wall was instrumented with two pressure gauges for measuring the applied reflectedload, and three accelerometers. One accelerometer was placed for measuring the wall panel

  • 8/8/2019 Hunter Bldg Test 2008

    27/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    19

    response and two accelerometers for the sliding and tipping response of the building. Thereflected wall instrumentation plan is provided below in Figure 27.

    75 ft

    2

    3

    1

    4

    75 ft75 ft

    22

    33

    11

    44

    Figure 26. Test II - Building Layout Relative to Explosive Charge

    Pressure

    Gauge

    Wall Panel

    Accelerometer

    Sliding and Tipping

    Accelerometers

    Pressure

    Gauge

    Pressure

    Gauge

    Wall Panel

    Accelerometer

    Sliding and Tipping

    Accelerometers

    Pressure

    Gauge

    Figure 27. Test II - Reflected Wall Instrumentation (Elevation 1)

  • 8/8/2019 Hunter Bldg Test 2008

    28/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    20

    The leeward wall of the building was instrumented with a single pressure gauge to measure theapplied load to the backside of the building. An elevation of the back wall detailing the location

    of the pressure gauge is provided in Figure 28.

    Pressure

    Gauge

    Pressure

    Gauge

    Figure 28. Test II - Rear Wall Instrumentation (Elevation 2)

    The sidewall of the building opposite of the HVAC equipment was instrumented with a pressure

    gauge and accelerometer, as shown in Figure 28. The pressure gauge measured the applied loadto the side wall and the accelerometer measured the flexural response of the eave strut.

    Pressure

    Gauge

    Accelerometer

    Pressure

    Gauge

    Pressure

    Gauge

    Accelerometer

    Figure 29. Test II - Sidewall Instrumentation (Elevation 3)

    The roof of the building was instrumented with a pressure gauge to measure the applied pressure

    at the center of the roof as shown in the detail of the roof instrumentation plan provided below in

    Figure 30.

  • 8/8/2019 Hunter Bldg Test 2008

    29/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    21

    Pressure

    Gauge

    Pressure

    Gauge

    Figure 30. Test II - Roof Instrumentation

    Cameras and instruments were also placed within the building to assess the occupant

    environment during structural response to the explosion. Three closed circuit cameras wereplaced inside the building along with a mannequin and two pressure gauges. The Hybrid III was

    not utilized for Test II due to the potential to damage the Hybrid III and instrumentation. A plan

    showing the location of the cameras and instruments is provided in Figure 31. One pressure

    gauge was placed in the occupied volume of the building and a second was placed within theplenum between the roof and drop ceiling so that any disparity of pressure between these two

    volumes within the building could be evaluated. The mannequin was situated against the desk

    along the reflected wall.

    Figure 31. Test II - Interior Cameras and Instrumentation

  • 8/8/2019 Hunter Bldg Test 2008

    30/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    22

    4. Test I Results

    The first explosive test produced the crater shown below in Figure 32. The crater had an inner

    diameter of 7 feet, an outer diameter of 15 feet and a depth of 38 inches. A summary of the blast

    loading, observed pressure and structural response are provided in the following sections.

    Figure 32. Test I Crater

    4.1.Free Field and Applied PressuresThe measured free-field and applied pressures are summarized below in Table 5 with the

    associated time histories in Figure 33 through Figure 39. The free-field and reflected peakpressures compared well to the theoretical values for 1,250 lbsANFO at 100 feet. The endwallpressure gauge failed and did not record a good trace. Of interest are the interior pressure

    histories in Figure 38 and Figure 39. Peak pressures in the occupied volume peaked at 4 psi and

    the plenum pressures were on the order of 1 psi. The interior pressures are not the result ofshock infiltrating the structure through openings. Instead they are a result of pressure waves

    transmitted into the structure from deformation of the buildings surfaces (walls and roof).

  • 8/8/2019 Hunter Bldg Test 2008

    31/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    23

    Table 5. Test I - Measured and Applied Load Summary

    Peak Positive PhaseGauge

    Pressure

    (psi)

    Impulse

    (psi*msec)

    PressureTime History

    Free Field 9.6 51 Figure 33

    Reflected Wall #1 24.0 154 Figure 34Reflected Wall #2 25.5 153 Figure 35

    Roof 7.0 30 Figure 36

    Rear Wall 3.0 59 Figure 37

    Side Wall Gauge Failure

    Interior Pressure

    (Occupied Volume)

    3.7 22 Figure 38

    Interior Pressure(Plenum)

    0.8 71 Figure 39

    Time (msec)

    Pressure(psi)

    Im

    pulse(psi-msec)

    -40 -20 0 20 40 60 80 100 120-5 -20

    0 0

    5 20

    10 40

    15 60Raw DataFiltered Data (3.5-250hz)Impulse

    Figure 33. Test I - Free-Field Pressure Time History

  • 8/8/2019 Hunter Bldg Test 2008

    32/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    24

    Time (msec)

    Pressure(psi)

    Impulse(psi-msec)

    -60 -40 -20 0 20 40 60 80 100 120 140-15 -60

    -5 -20

    5 20

    15 60

    25 100

    35 140Raw DataFiltered Data (2.7-1000hz)Impulse

    Figure 34. Test I - Reflected Wall Pressure Time History #1

    Time (msec)

    Pressure(psi)

    Impulse(psi-mse

    c)

    -75 -50 -25 0 25 50 75 100 125 150 175-30 -120

    -20 -80

    -10 -40

    0 0

    10 40

    20 80

    30 120

    40 160Raw DataFiltered Data (4-500hz)Impulse

    Figure 35. Test I - Reflected Wall Pressure Time History #2

  • 8/8/2019 Hunter Bldg Test 2008

    33/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    25

    Time (msec)

    Pressure(psi)

    Impulse(psi-msec

    )

    -100 -75 -50 -25 0 25 50 75 100 125 150-4 -30

    -2 -15

    0 0

    2 15

    4 30

    6 45

    8 60Raw DataFiltered Data (1500hz)Impulse

    Figure 36. Test I- Applied Roof Pressure Time History

    Time (msec)

    Pressure(ps

    i)

    Impulse(psi-m

    sec)

    -75 -50 -25 0 25 50 75 100 125 150 175

    -15 -45

    -10 -30

    -5 -15

    0 0

    5 15

    10 30

    15 45

    20 60

    Raw DataFiltered Data (1.1-1000hz)Impulse

    Figure 37. Test I - Applied Rear Wall Pressure History

  • 8/8/2019 Hunter Bldg Test 2008

    34/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    26

    Time (msec)

    Pressure(psi)

    Impulse(psi-msec)

    -25 0 25 50 75 100 125 150 175 200 225-7.5 -24

    -5 -16

    -2.5 -8

    0 0

    2.5 8

    5 16

    7.5 24

    10 32

    Raw DataFiltered Data (5.5-500hz)Impulse

    Figure 38. Test I - Interior Pressure Time History (Occupied Volume)

    Time (msec)

    Pressure(ps

    i)

    Impulse(psi-msec)

    -75 -50 -25 0 25 50 75 100 125 150 175

    -2 -10

    -1 -5

    0 0

    1 5

    2 10

    3 15

    4 20

    5 25Raw DataFiltered Data (1200hz)Impulse

    Figure 39. Test I - Interior Pressure Time History (Plenum)

  • 8/8/2019 Hunter Bldg Test 2008

    35/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    27

    4.2.Observed DamageDamage to the Hunter Standard Building is characterized by the permanent deformation of

    structural components such as wall panels and roof joists, sliding and tipping of the building, and

    displacement of internal fixtures.

    After Test I a permanent deflection of the reflected wall was measured to be between 3 and 4inches depending upon the location of the measurement. Reflected wall damage is shown in

    Figure 40. Cracking of the wall panel supporting overhead welds along the top of the panel wereobserved and are highlighted by magenta paint in Figure 40. A total of five cracks, all on the

    tension face of the panel, were observed with lengths of 1 inch, 13 inches, and 3.5 inches. The

    total length of cracking was measured to be 34 inches. It is suspected, but not confirmed, thatthe cause of the cracking was improper fit up of the panel prior to welding. The suspected fit-up

    issue would be caused by the panel sitting on the bottom tube and too large of a gap existing

    between the top of the panel and the top tube. In this condition, the toe of the weld on the panelwould be insufficient. It is important to note that the weld cracks did not lead to any structural

    failure or increased wall panel response when subjected to the test blast loading.

    No permanent deformations of the side-wall or rear wall panels was visible and fieldmeasurements showed no permanent damage to these building surfaces. Figure 41 shows the

    lack of damage to the rear wall after Test I.

  • 8/8/2019 Hunter Bldg Test 2008

    36/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    28

    Figure 40. Test I - Reflected Wall Damage (Weld Cracks Spray Painted Magenta)

    Figure 41. Test I - Rear Wall Damage

  • 8/8/2019 Hunter Bldg Test 2008

    37/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    29

    The roof of the building sustained little damage as shown in Figure 42. There was no visible or

    measurable permanent deformation to the roof joists. Roof panel deformations were measured

    between 3/8 and 5/8 inches.

    Figure 42. Test I - Roof Damage

    Sliding of the building was measured actively utilizing an accelerometer and passively by spraypainting around the building base plates. After the first test the building slid between two and

    three inches as shown in Figure 43.

  • 8/8/2019 Hunter Bldg Test 2008

    38/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    30

    Figure 43. Test I - Passive Building Sliding Measurements

    1

    2

    3

    4

    1

    2

    3

    4

  • 8/8/2019 Hunter Bldg Test 2008

    39/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    31

    The HVAC unit on the end wall of the building was damaged by the test and is shown in its posttest condition in Figure 44. The interior view of the HVAC shows that the air intake filter is still

    in place. In addition no blowout of any of the ducts inside the building was observed.

    Figure 44. Test I - Damage to HVAC: (a) Exterior and (b) Interior

    The test building was fitted with doors provided by Booth Industries. Both doors were Intact butInoperable after the test as show in Figure 45. The doors were inoperable due to damage to the

    latch plate on the door as shown in Figure 46. The rightmost door into the work room was blownopen during the negative phase of the explosion. The leftmost door in Figure 45 could not be

    opened manually or with the application of force by sledge hammer. No permanent bending of

    the door leaf was observed nor measured.

    (a) (b)

  • 8/8/2019 Hunter Bldg Test 2008

    40/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    32

    Figure 45. Test I - Booth Blast Door Response: (a) Leftmost Door and (b) Rightmost Door

    Figure 46. Test I - Booth Door Latch Damage: (a) Pre-Test and (b) Post-Test

    (a) (b)

  • 8/8/2019 Hunter Bldg Test 2008

    41/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    33

    Simulated occupants, the Hybrid III and Mannequin, were moved by the explosion but were still

    in their places. The Hybrid III, which was situated against the reflected wall, had obviously been

    rotated slightly forward about the hips as shown in Figure 47. In the post test condition theHybrid IIIs feet are no longer pressed against the bathroom wall but are placed firmly to the

    floor. In addition, the right arm of the Hybrid III was found to be resting against the chair andthe Hybrid IIIs torso had been rotated forward. Measurements from the Hybrid IIIaccelerometers are presented in Figure 48. The peak acceleration was from front to back on the

    Hybrid III and measured approximately 8 g. For comparison, the peak acceleration of the

    building from sliding was measured to be approximately 25 g. Although the Hybrid III was

    situated directly against the reflected wall only of the peak kinematic building accelerationwas transmitted to the Hybrid III. Peak vertical acceleration measured in the Hybrid III was

    approximately 2 g.

    Figure 47. Test I - HYBRID III: (a) Pre-Test and (b) Post-Test

    (a) (b)

  • 8/8/2019 Hunter Bldg Test 2008

    42/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    34

    Time (msec)

    Acceleration(g)

    0 5 10 15 20 25 30 35 40 45 50 55 60 65-12.5

    -10

    -7.5

    -5

    -2.5

    0

    2.5

    5

    7.5

    10Raw Data_Dummy 01 (Front and Back)Raw Data_Dummy 02 (Left and Right)Raw Data_Dummy 03 (Up and Down)

    Figure 48. Test I - HYBRID III Measured Accelerations

    The mannequin was placed at the desk situated along the rear wall of the building as shown in

    Figure 49. The mannequin was held in place by a bungee cord around the waist of themannequin and fastened to the chair. The bungee cord is visible in Figure 49. After the test, the

    mannequin was still in place in the chair. The mannequin was impacted by folders and books

    that were placed along the shelf above the desk as wall as some of the framing for the acoustic

    ceiling.

  • 8/8/2019 Hunter Bldg Test 2008

    43/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    35

    Figure 49. Test I - Mannequin: (a) Pre-Test and (b) Post-Test

    The damage to the interior of the building is summarized in Figure 50 through Figure 54. The

    main work room is shown in Figure 50. Ceiling tiles and framing for the ceiling tiles were found

    on the floor. All overhead fluorescent light fixtures were still in place as was the overhead

    drywall insulation above the acoustic ceiling. The books placed on the shelf along the back wall

    were thrown to the floor. The cabinet on the blastward wall was moved approximately 6 inchesaway from the reflected wall as highlighted in Figure 51.

    Figure 50. Test I - Building Interior: (a) Pre-Test and (b) Post-Test Damage

    (a) (b)

    (a) (b)

  • 8/8/2019 Hunter Bldg Test 2008

    44/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    36

    Figure 51. Test I - Cabinet Movement on Reflected Wall

    The porcelain bathroom fixtures were shattered by the shock to the building, see Figure 52. The

    sink had fallen to the floor from its mount and shattered as had the toilet. Several large shards of

    porcelain from the sink and toilet were observed.

    Figure 52. Test I - Lavatory Fixtures: (a) Pre-Test and (b) Post-Test Damage

    The interior metal stud wall was impacted by the responding reflected wall and the steel studs

    were bent inward permanently. Evidence of this damage, see Figure 53, could be seen aroundlight switches and plugs. A section of the interior wall panel was removed to reveal the damage

    to the interior metal studs.

    (a) (b)

  • 8/8/2019 Hunter Bldg Test 2008

    45/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    37

    Figure 53. Test I - Interior Wall Damage: (a) Drywall Pulling Away and (b) Metal Stud

    Damage

    Two fire extinguishers were mounted to the blastward wall and both were thrown across the

    building to the opposite wall. One fire extinguisher which was located in the end work room is

    shown in Figure 54.

    (a) (b)

  • 8/8/2019 Hunter Bldg Test 2008

    46/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    38

    Figure 54. Test I - Fire Extinguisher Throw

    4.3.Structural Response MeasurementsAs discussed in Section 3.3.2, the building was instrument to active record structuralaccelerations of sliding and tipping, the reflected wall panel and roof joist. The acceleration data

    was filtered and integrated twice to produce displacement time histories. The wall panelaccelerometers recorded the kinematic sliding of the building in addition to the flexural responseof the wall panel. Therefore, the sliding response had to be subtracted from the wall panel

    response in order to obtain the wall panel relative displacement time history. A summary of the

    active response measurements are provided below in Table 6. The wall panel and building

    response compared well to pretest predictions as evidenced by the 6 degree rotation of thereflected wall panel. The roof joist response was low, about 1 degree of support rotation. The

    sliding response was recorded in building corner 1, see Figure 16. The recorded sliding response

    of 1.7 inches compared well with the passive measurement at this corner of 2 inches.

  • 8/8/2019 Hunter Bldg Test 2008

    47/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    39

    Table 6. Test I - Measured Response Summary

    Measured ResponseComponent

    max (in) (deg)Wall Panel

    6.3 in 6.0

    Roof Joist 1.2 in 1.0

    Sliding* 1.7 in -

    Tipping**

    -* Sliding passive response measurements presented in Figure 43.** Tipping data is incomplete due to loss of signal during the test.

    4.3.1. Sliding and Tipping

    The sliding and tipping measurements experienced some drift of the signal at later times and the

    tipping accelerometer measurements experienced a loss of signal for about 20 msec. The

    acceleration and integrated sliding data are presented below in Figure 55. This data compared

    well to the passive sliding measurement of the same building corner as was instrumented. Peak

    sliding accelerations were on the order of 100 gs. The active tipping acceleration measurementscould not be evaluated due to loss of the signal as shown in Figure 56.

    Time (msec)

    Acc

    eleration(in/msec^2)andVelocity(in/msec)

    Displacement(in)

    -12 -4 4 12 20 28 36 44-0.3 -10

    -0.24 -8

    -0.18 -6

    -0.12 -4

    -0.06 -2

    0 0

    0.06 2

    0.12 4

    0.18 6

    0.24 8

    0.3 10Raw Acceleration DataFiltered Acceleration DataVelocityDisplacement

    Figure 55. Test I Measured Sliding Time History

  • 8/8/2019 Hunter Bldg Test 2008

    48/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    40

    Time (msec)

    Acceleration(in/msec^2)andVelocity(in/msec)

    Displacement(in)

    -12 -4 4 12 20 28 36 44-0.25 -60

    -0.2 -30

    -0.15 0

    -0.1 30

    -0.05 60

    0 90

    0.05 120

    0.1 150

    0.15 180

    0.2 210Raw Data_1st halfRaw Data_2nd halfFiltered Data (1000hz)velocity

    displacement

    Figure 56. Test I - Measured Tipping Time History

    4.3.2. Wall Panel

    The wall panel acceleration time history and integrated data is presented below in Figure 57.

    The peak acceleration of the wall panel including sliding was recorded to be approximately 400gs, which compares well to the theoretical peak acceleration. The accelerometer recorded boththe wall panel response and kinematic sliding. Therefore, in order to properly assess the panel

    displacement time history, the sliding response must be subtracted. The relative wall panel

    displacement time history is presented in Figure 58. The peak recorded wall displacement

    relative to the supporting structural members was 6.3 inches. This displacement corresponds to asupport rotation of 6 degrees. The design limit for medium response was 6 degrees; therefore,

    the response correlated well to the pre-test prediction.

  • 8/8/2019 Hunter Bldg Test 2008

    49/70

  • 8/8/2019 Hunter Bldg Test 2008

    50/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    42

    4.3.3. Roof Joists

    The roof joist measured response time history is presented below in Figure 59. The peak roof

    joist acceleration was approximately 160 gs. The peak displacement as integrated from the

    acceleration time history was 1.2 inches which corresponds to a support rotation of 1 degree.

    Time (msec)

    Acceleration(in/msec

    ^2)andVelocity(in/msec)

    Displacement(in)

    -7.5 -2.5 2.5 7.5 12.5 17.5 22.5 27.5 32.5-0.48 -15

    -0.32 -10

    -0.16 -5

    0 0

    0.16 5

    0.32 10

    0.48 15

    0.64 20Raw Acceleration DataFiltered Acceleration DataVelocityDisplacement

    Figure 59. Test I - Roof Joist Response Time History

  • 8/8/2019 Hunter Bldg Test 2008

    51/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    43

    5. Test II Results

    The second explosive test produced the crater shown below in Figure 60. The crater had an innerdiameter of 7 feet, an outer diameter of 15 feet and a depth of 41 inches. A summary of the blast

    loading, observed pressure and structural response are provided in the following sections.

    Figure 60. Test II Crater

    5.1.Free Field and Applied PressuresThe measured free-field and applied pressures are summarized below in Table 7 with the

    associated time histories in Figure 61 through Figure 67. The free-field and reflected peakpressures were higher than the theoretical values for 1,250 lbsANFO at 75 feet but not

    unreasonably so. The endwall pressure gauge failed and did not record a good trace. Of interest

    are the interior pressure histories in Figure 66 and Figure 67. Peak pressures in the occupiedvolume peaked at 4.5 psi and the plenum pressures were on the order of 1.5 psi. The interior

    pressures are not the result of shock infiltrating the structure through openings. Instead they are

    a result of pressure waves transmitted into the structure from deformation of the buildings

    surfaces (walls and roof).

  • 8/8/2019 Hunter Bldg Test 2008

    52/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    44

    Table 7. Test II - Measured and Applied Load Summary

    Peak Positive PhaseGauge

    Pressure

    (psi)

    Impulse

    (psi*msec)

    PressureTime History

    Free Field 23.5 62 Figure 61

    Reflected Wall #1 77.9 248 Figure 62Reflected Wall #2 67.1 313 Figure 63

    Roof 8.8 32 Figure 64

    Rear Wall 5.5 70 Figure 65

    Side Wall Gauge Failure

    Interior Pressure

    (Occupied Volume)

    4.5 39 Figure 66

    Interior Pressure(Occupied Volume)

    1.4 24 Figure 67

    Time (msec)

    Pressure(psi)

    Im

    pulse(psi-msec)

    -40 -20 0 20 40 60 80 100-10 -20

    0 0

    10 20

    20 40

    30 60

    40 80Raw DataFiltered Data (6-2500hz)Impulse

    Figure 61. Test II - Free-Field Pressure Time History

  • 8/8/2019 Hunter Bldg Test 2008

    53/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    45

    Time (msec)

    Pressure(psi)

    Impulse(psi-msec

    )

    -4 -2 0 2 4 6 8 10 12 14-100 -0.8

    -50 -0.4

    0 0

    50 0.4

    100 0.8

    150 1.2

    200 1.6

    250 2

    300 2.4Raw DataImpulse

    Figure 62. Test II - Reflected Wall Pressure Time History #1

    Time (msec)

    Pressure(psi)

    Impulse(psi-msec

    )

    -10 -5 0 5 10 15 20-50 -400

    0 0

    50 400

    100 800

    150 1200Raw DataImpulse

    Figure 63. Test II - Reflected Wall Pressure Time History #2

  • 8/8/2019 Hunter Bldg Test 2008

    54/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    46

    Time (msec)

    Pressure(psi)

    Impulse(psi-msec

    )

    -40 -20 0 20 40 60 80 100 120-10 -30

    -5 -15

    0 0

    5 15

    10 30

    15 45Raw DataFiltered Data (500hz)Impulse

    Figure 64. Test II - Applied Roof Pressure Time History

    Time (msec)

    Pressure(ps

    i)

    Impulse(psi-msec)

    -50 -25 0 25 50 75 100 125 150 175 200

    -10 -80

    -7.5 -60

    -5 -40

    -2.5 -20

    0 0

    2.5 20

    5 40

    7.5 60

    10 80Raw DataFiltered Data (2.7-900hz)Impulse

    Figure 65. Test II - Applied Rear Wall Applied Pressure Time History

  • 8/8/2019 Hunter Bldg Test 2008

    55/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    47

    Time (msec)

    Pressure(psi)

    Impulse(psi-mse

    c)

    -20 0 20 40 60 80 100 120 140 160 180-15 -120

    -10 -80

    -5 -40

    0 0

    5 40

    10 80

    Raw DataFiltered Data (4-1000hz)Impulse

    Figure 66. Test II - Interior Pressure Time History (Occupied Volume)

    Time (msec)

    Pressure(psi)

    Impulse(psi-msec

    )

    -50 -25 0 25 50 75 100 125 150 175 200 225 250

    -2 -20

    -1.5 -15

    -1 -10

    -0.5 -5

    0 0

    0.5 5

    1 10

    1.5 15

    2 20

    2.5 25

    3 30Raw DataFiltered Data (2.5-750hz)Impulse

    Figure 67. Test II - Interior Pressure Time History (Plenum)

  • 8/8/2019 Hunter Bldg Test 2008

    56/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    48

    5.2.Observed DamageDuring the second test the wall panels were pressed inward and developed in-plane tensile

    membrane forces. This is evidenced in the high speed video image in Figure 68. The supportingHSS Eave Strut is bent between the columns from the panel tensile reaction. Unfolding and

    flattening of the corrugations can also be seen. The post test condition of the reflected wall panelis shown in Figure 69. The panels were found to be pulled outward approximately 5 inches in

    the middle with permanent inward deflections of approximately 8 inches to either side of theoutward panel bulge. No cracking of the reflected wall panel welds was observed after the

    second test. Although significant demand was placed on the HSS eave strut at the peak wall

    panel response as shown in Figure 68, no permanent downward deflection of the eave strut waspresent after the test.

    The side wall panel was buckled and had a permanent inward deformation of 5/16 inches asshown in Figure 70.

    Figure 68. Test II - High Speed Video Capture of Peak Wall Panel Response

  • 8/8/2019 Hunter Bldg Test 2008

    57/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    49

    Figure 69. Test II - Reflected Wall Damage

    Figure 70. Test II - End Wall Damage

    Damage to the roof deck and roof joists after Test II, shown in Figure 71, was not measurablydifferent that that which was observed after Test I. Photographs of the underside of the buildingwere taken during the load out of the building and floor deck damage was observed as shown in

    Figure 72. This is not unexpected since the building was not skirted for the second test and a gap

    varying between 6 and 10 inches was present between the building and the ground thus allowingshock to get underneath the building during the second test.

  • 8/8/2019 Hunter Bldg Test 2008

    58/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    50

    Figure 71. Test II - Roof Deck Damage

    Figure 72. Test II - Floor Deck Damage

    Sliding of the building was measured actively utilizing an accelerometer and passively by spraypainting around the building base plates. After the second test the building slid between thirteen

    and twenty inches as shown in Figure 73.

  • 8/8/2019 Hunter Bldg Test 2008

    59/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    51

    Figure 73. Test II - Passive Building Sliding Measurements

    1

    2

    3

    4

    1

    2

    3

    4

  • 8/8/2019 Hunter Bldg Test 2008

    60/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    52

    The HVAC unit was heavily damaged by the second test as evidenced in Figure 74. The airreturn intake was blown into the work room at the end of the structure; the exterior unit was

    heavily bent with the blower cover no longer attached to the unit. There was also evidence of

    HVAC duct bulging inside the building, as shown in Figure 75. However, it is not clear whetherthe damage was caused by shock inside the duct or blast response of the roof.

    Figure 74. Test II - Damage to HVAC: (a) Exterior and (b) Interior

    Figure 75. Test II - Damage to HVAC Duct

    Although there was no failure of the reflected wall the damage to the interior of the building was

    heavy and a significant amount of interior debris was generated from the High Response of the

    reflected wall. Figure 76 through Figure 80 detail the level, energy and hazardous nature of the

    interior debris. In Figure 76 the damage to the end office is highlighted by the severedisplacement of the interior metal stud wall, throw of the gypsum wall sheathing and

    fragmentation and throw of the book shelf and desk. The desk edging was thrown at a high force

  • 8/8/2019 Hunter Bldg Test 2008

    61/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    53

    impacting the office hallway door and penetrating the door as shown in Figure 77. Furtherevidence of debris impacts on the back wall surfaces was also evident.

    Figure 76. Test II - Office Room: (a) Pre-Test and (b) Post- Test

    Figure 77. Test II - Desk Debris Impacts: (a) Door Scarring and (b) With Impacting

    Debris

  • 8/8/2019 Hunter Bldg Test 2008

    62/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    54

    The bathroom of the building was moved between 2 and 3 feet towards the back of the structureand into the hallway as shown in Figure 78. In Figure 79 debris from the reflected wall and

    ceiling can be seen on the sink and cabinet located in the rear of the work room. Part of the

    reflected wall desk top is also visible in Figure 79 having been thrown to the rear of the building.

    Figure 78. Test II - Central Work Room: (a) Pre-Test and (b) Post Test

    Figure 79. Test II - Interior Debris

  • 8/8/2019 Hunter Bldg Test 2008

    63/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    55

    Overhead light fixtures were found to be mostly intact with just a few fixtures dangling but still

    at the level of the drop ceiling as shown in Figure 80.

    Figure 80. Test II - Light Fixture Damage

    5.3.Structural Response MeasurementsAs discussed in Section 3.4.2, the building was instrumented to actively record structuralaccelerations of sliding and tipping, the reflected wall panel and end wall eave strut. The

    acceleration data was filtered and integrated twice to produce displacement time histories. The

    wall panel accelerometers recorded the kinematic sliding of the building as well as the flexuralresponse of the wall panel. Therefore, the sliding response had to be subtracted from the wall

    panel response in order to obtain the wall panel relative displacement time history. A summary

    of the active response measurements are provided below in Table 8. The wall panel response

    exceeded the pretest prediction of 12.75 inches by 40%. The eave strut response was moderate,about 3 degrees of support rotation. The sliding response was recorded in building corner 4, see

    Figure 26. The recorded sliding response, using the passive marking of the supporting concrete

    pad, was 14 inches. A direct comparison to the active sliding accelerometer measurements couldnot be made due to the signal drift of the accelerometer data at the time scale necessary to

    produce the peak sliding response.

    Table 8. Test II - Measured Response Summary

    Measured ResponseComponent

    max (in) (deg)Wall Panel

    17.5 in 16.2

    Eave Strut 3.9 in 3.4Sliding

    *-

    Tipping* -

    *Accelerometer data drifted therefore data was not reliable at time

    necessary to integrate peak response for sliding or tipping. See

    Section 5.2 Figure 73 for passive sliding measurements.

  • 8/8/2019 Hunter Bldg Test 2008

    64/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    56

    5.3.1. Sliding and Tipping Response

    The sliding and tipping measurements experienced some drift of the signal at later times

    preventing the active measurement of sliding and tipping at time scales necessary for peak

    kinematic building movement. However, the data was sufficient in the time scale of peak wallpanel response, about 20 msec. The acceleration and integrated sliding data is presented below

    in Figure 55. Peak sliding accelerations were on the order of 25 gs. The active tippingacceleration measurements could not be evaluated due to loss of the signal as shown in Figure

    56.

    Time (msec)

    Accele

    ration(in/msec^2)andVelo

    city(in/msec)

    Displacement(in)

    -5 0 5 10 15 20 25 30 35 40-0.3 -6

    -0.25 -5

    -0.2 -4

    -0.15 -3

    -0.1 -2

    -0.05 -1

    0 0

    0.05 1

    0.1 2

    0.15 3

    0.2 4

    0.25 5

    0.3 6Raw Acceleration DataFiltered Acceleration DataVelocityDisplacement

    Figure 81. Test II - Measured Sliding Time History

  • 8/8/2019 Hunter Bldg Test 2008

    65/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    57

    Time (msec)

    Acceleration(in/msec^2)andVelocity(in/msec)

    Displacement(in)

    -3 0 3 6 9 12 15 18-0.4 -4

    -0.3 -3

    -0.2 -2

    -0.1 -1

    0 0

    0.1 1

    0.2 2

    0.3 3

    0.4 4

    0.5 5Raw Acceleration DataFiltered Acceleration DataVelocityDisplacement

    Figure 82. Test II - Measured Tipping Time History

    5.3.2. Wall Panel Response

    The wall panel acceleration time history and integrated data is presented below in Figure 83.

    The peak acceleration of the wall panel including sliding was recorded to be approximately

    2,000 gs. The accelerometer recorded both the wall panel response and kinematic sliding.Therefore, in order to properly assess the panel displacement time history, the sliding response

    must be subtracted. The relative wall panel displacement time history is presented in Figure 84.

    The peak recorded wall displacement relative to the supporting structural members was 17.5inches. The wall panel response exceeded the pretest prediction due to eave strut deformation

    that was more pronounced in the test. The structural model was revised to incorporate this

    flexibility and better matched the test. This revised model was used to predict strains occurringin the wall panels during the tests and to revise the blast capacity calculation for strain and for

    support rotation.

  • 8/8/2019 Hunter Bldg Test 2008

    66/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    58

    Time (msec)

    Acceleration(in/msec^2)andVelocity(in/msec)

    Displacement(in)

    -5 0 5 10 15 20 25 30 35 40 45-2 -20

    -1.5 -15

    -1 -10

    -0.5 -5

    0 0

    0.5 5

    1 10

    1.5 15

    2 20

    Raw Acceleration DataFiltered Acceleration DataVelocityDisplacement

    Figure 83. Test II - Total Wall Panel Response Time History (Includes Sliding)

    -40

    -30

    -20

    -10

    0

    10

    20

    30

    0 5 10 15 20 25 30 35

    Time (msec)

    Displacement(in)

    Wall Panel Displacement

    Figure 84. Test II - Relative Wall Panel Response Time History

  • 8/8/2019 Hunter Bldg Test 2008

    67/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    59

    5.3.3. End Wall Eave Strut Response

    The end wall eave strut measured response time history is presented below in Figure 85. The

    peak eave strut acceleration was approximately 1,500 gs. The peak displacement as integrated

    from the acceleration time history was 3.9 inches which corresponds to a support rotation of 3degrees.

    Time (msec)

    Acceleration(in/msec^2

    )andVelocity(in/msec)

    Displacement(in)

    0 2 4 6 8 10 12 14 16 18 20-5.6 -5.6

    -4.8 -4.8

    -4 -4

    -3.2 -3.2

    -2.4 -2.4

    -1.6 -1.6-0.8 -0.8

    0 0

    0.8 0.8

    1.6 1.6

    2.4 2.4

    3.2 3.2

    4 4Raw Acceleration DataFiltered Acceleration DataVelocityDisplacement

    Figure 85. Test II - End Wall Eave Strut Response Time History

  • 8/8/2019 Hunter Bldg Test 2008

    68/70

    Standard Building Full Scale Explosive Testing, Final Report July 9, 2008

    Hunter Buildings and Manufacturing Project No. 174999

    60

    6. Summary

    ABS Consulting conducted two full scale field tests utilizing 1,250 pounds of ANFO explosiveon a standard 8 psi, 200 msec Heavy Response Hunter blast resistant modular building. The

    purpose of the explosive testing was to determine performance of the building at the upper limit

    of Medium Response (Test I) and the upper limit of High Response (Test II). Testing consistedof the detonation of a 1,250 lbANFO charge at a range of 100 feet for Test I and 75 feet for Test II.

    The ANFO charge was placed on the door side of the building for Test I and the opposite wall

    for Test II. Peak side-on pressures were 9.7 psi for Test I and 17.4 psi for Test II.

    Test I - Medium Response

    Performance of the structure in Test I was consistent with ASCE Medium Response. Whileprimary components exhibited some plastic deformation, structural integrity was not

    compromised