5
Humidification Effect on Inactivation of Staphylococcus aureus in an Electrostatic Precipitator A. Zukeran 1 , T. Miura 1 , T. Oku 1 , R. Mano 1 , H. Miyashita 1,4 , R. Wada 2 , J. Sawai 3 , and Y. Ehara 4 1 Department of Electrical and Electronic Engineering, Kanagawa Institute of Technology, Japan 2 Department of Applied Bioscience, Kanagawa Institute of Technology, Japan 3 Department of Nutrition and Life Science, Kanagawa Institute of Technology, Japan 4 Department of Electrical and Electronic Engineering, Tokyo City University, Japan Abstract—This study is aimed at inactivating microorganisms collected by a two-stage type electrostatic precipitator. The experimental system consisted of a discharging section and an electrostatic section. The discharging section consisted of a wire and plates. The electrostatic section had a parallel-plates configuration. A bacterial culture of Staphylococcus aureus, as a model of airborne microorganisms, was put on the surface of grounded plate electrodes in the discharging and electrostatic sections. Negative DC high voltage was applied to the discharging section to generate negative corona discharge for inactivation. DC -5 kV was applied to the electrostatic section, and reactive oxygen species (ROS) generated by the discharging section was used for inactivation. The applied voltage to the discharging section was controlled between DC -8.5 kV and -9.5 kV to adjust ozone concentration to approximately 1ppm, which was one of ROS. The gas flow velocity in the experimental system was 0.5 m/s. The relative humidity (RH) in the gas was controlled between 5% and 95% using a humidifier. The result showed that inactivation effect in the discharging section was greater than that in the electrostatic section. Inactivation effect was improved by humidification. Effects both discharging and electrostatic sections are significantly improved by humidification. The survival decreased with increasing relative humidity; it is desirable to increase RH to 60% or higher by humidification. Keywords—Inactivation, electrostatic precipitator, Staphylococcus aureus, corona discharge, humidification I. I NTRODUCTION Electrostatic Precipitators (ESPs) have been extensively used for the cleaning of industrial process flue gases, com- bustion flue gases and ventilation flue gases for road tunnels, etc. A home air cleaner is also one application of ESP. Such air cleaners must be capable of eliminating and inactivating airborne microorganisms to improve indoor air quality. It is known that microorganisms are inactivated by non-thermal plasma [1], [2]. An ESP using corona discharge is expected to be effective for such purposes. Botvinnik et al. reported an experimental result carried out to investigate an elimination effect of Serratia marcescens in the air using ESP [3]. The microorganism concentration was measured using the fifth stage of an Anderson six- stage impactor. As a result, colonies on the Petri dishes decreased with ESP-operation time. Takimoto et al. suggested a bacteria collection system using negative ions and ozone with mist formation in an ESP [4]. They reported that airborne microorganisms were collected on a collection electrode and collected microorganisms were inactivated in the ESP. As for the effects of corona discharge, several experiments were carried out. Mizuno et al. showed the case of sterilizing S. cerevisiae and B. subtilis spores on an electric filter using DC corona discharge [5]. Okubo et al. also showed an inactivation effect on E. coli by corona discharge plasma jet [6]. Tanimura suggested that negative ions and ozone generated by corona Corresponding author: Akinori Zukeran e-mail address: [email protected] Presented at the 3rd ISNPEDADM 2015 (New electrical technologies for environment), in October 2015 discharge are effective for sterilizing E. coli [7]. Timoshkin et al. reported inactivation effects of negative and positive corona discharge [8]. The inactivation mechanism of corona discharge was also studied. Mizuno et al. reported that φX174 phage was inactivated as a result of the degradation of coat protein [9]. Ohshima et al. showed that the cell-surface and DNA of S. epidermidis on a plate electrode was damaged due to corona discharge [10]. There are many literatures describing the inactivation with ozone gas. It is known that survival ratios of B. subtilis and S. aureus are proportional to CT [ppm·min], which is the product of ozone concentration C and exposure time T [11], [12]. It was reported to need 50 or 60ppm·min at the ozone concentration between 60 and 65% for inactivating S. aureus [12], [13]. The aim of this study is to investigate the inactivation characteristic, and to improve the effect of inactivating mi- croorganisms collected on a plate electrode in an ESP. The influence of the location of collection, ozone concentration, elapsed time and relative humidity (RH) on inactivation of microorganisms was experimentally investigated. The ESP had a two-stage structure of discharging and electrostatic sections. A bacterial culture of Staphylococcus aureus, which was used as a model of airborne microorganisms, was applied to the surface of grounded plate electrodes in the discharging and electrostatic sections. Negative DC high voltages were applied to both sections, and ozone generated by the discharging section was used for inactivation. The applied voltage to the discharging section was controlled to vary ozone concentration between 0.06 and 5ppm. The gas flow velocity was 0.5 m/s. The relative humidity (RH) in the gas was controlled between 5% and 95% using a humidifier. Zukeran et al. 181

Humidification Effect on Inactivation of Staphylococcus …...Botvinnik et al. reported an experimental result carried out to investigate an elimination effect of Serratia marcescens

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

  • Humidification Effect on Inactivation of Staphylococcus aureus in anElectrostatic Precipitator

    A. Zukeran1, T. Miura1, T. Oku1, R. Mano1, H. Miyashita1,4, R. Wada2, J. Sawai3, and Y. Ehara41Department of Electrical and Electronic Engineering, Kanagawa Institute of Technology, Japan

    2Department of Applied Bioscience, Kanagawa Institute of Technology, Japan3Department of Nutrition and Life Science, Kanagawa Institute of Technology, Japan4Department of Electrical and Electronic Engineering, Tokyo City University, Japan

    Abstract—This study is aimed at inactivating microorganisms collected by a two-stage type electrostatic precipitator. Theexperimental system consisted of a discharging section and an electrostatic section. The discharging section consisted of a wireand plates. The electrostatic section had a parallel-plates configuration. A bacterial culture of Staphylococcus aureus, as a model ofairborne microorganisms, was put on the surface of grounded plate electrodes in the discharging and electrostatic sections. NegativeDC high voltage was applied to the discharging section to generate negative corona discharge for inactivation. DC -5 kV was appliedto the electrostatic section, and reactive oxygen species (ROS) generated by the discharging section was used for inactivation.The applied voltage to the discharging section was controlled between DC -8.5 kV and -9.5 kV to adjust ozone concentration toapproximately 1ppm, which was one of ROS. The gas flow velocity in the experimental system was 0.5 m/s. The relative humidity(RH) in the gas was controlled between 5% and 95% using a humidifier.

    The result showed that inactivation effect in the discharging section was greater than that in the electrostatic section. Inactivationeffect was improved by humidification. Effects both discharging and electrostatic sections are significantly improved by humidification.The survival decreased with increasing relative humidity; it is desirable to increase RH to 60% or higher by humidification.

    Keywords—Inactivation, electrostatic precipitator, Staphylococcus aureus, corona discharge, humidification

    I. INTRODUCTION

    Electrostatic Precipitators (ESPs) have been extensivelyused for the cleaning of industrial process flue gases, com-bustion flue gases and ventilation flue gases for road tunnels,etc. A home air cleaner is also one application of ESP. Suchair cleaners must be capable of eliminating and inactivatingairborne microorganisms to improve indoor air quality. It isknown that microorganisms are inactivated by non-thermalplasma [1], [2]. An ESP using corona discharge is expectedto be effective for such purposes.

    Botvinnik et al. reported an experimental result carried outto investigate an elimination effect of Serratia marcescensin the air using ESP [3]. The microorganism concentrationwas measured using the fifth stage of an Anderson six-stage impactor. As a result, colonies on the Petri dishesdecreased with ESP-operation time. Takimoto et al. suggesteda bacteria collection system using negative ions and ozonewith mist formation in an ESP [4]. They reported that airbornemicroorganisms were collected on a collection electrode andcollected microorganisms were inactivated in the ESP. Asfor the effects of corona discharge, several experiments werecarried out. Mizuno et al. showed the case of sterilizing S.cerevisiae and B. subtilis spores on an electric filter using DCcorona discharge [5]. Okubo et al. also showed an inactivationeffect on E. coli by corona discharge plasma jet [6]. Tanimurasuggested that negative ions and ozone generated by corona

    Corresponding author: Akinori Zukerane-mail address: [email protected]

    Presented at the 3rd ISNPEDADM 2015 (New electrical technologies forenvironment), in October 2015

    discharge are effective for sterilizing E. coli [7]. Timoshkin etal. reported inactivation effects of negative and positive coronadischarge [8]. The inactivation mechanism of corona dischargewas also studied. Mizuno et al. reported that φX174 phage wasinactivated as a result of the degradation of coat protein [9].Ohshima et al. showed that the cell-surface and DNA of S.epidermidis on a plate electrode was damaged due to coronadischarge [10].

    There are many literatures describing the inactivation withozone gas. It is known that survival ratios of B. subtilis andS. aureus are proportional to CT [ppm·min], which is theproduct of ozone concentration C and exposure time T [11],[12]. It was reported to need 50 or 60ppm·min at the ozoneconcentration between 60 and 65% for inactivating S. aureus[12], [13].

    The aim of this study is to investigate the inactivationcharacteristic, and to improve the effect of inactivating mi-croorganisms collected on a plate electrode in an ESP. Theinfluence of the location of collection, ozone concentration,elapsed time and relative humidity (RH) on inactivation ofmicroorganisms was experimentally investigated. The ESP hada two-stage structure of discharging and electrostatic sections.A bacterial culture of Staphylococcus aureus, which was usedas a model of airborne microorganisms, was applied to thesurface of grounded plate electrodes in the discharging andelectrostatic sections. Negative DC high voltages were appliedto both sections, and ozone generated by the dischargingsection was used for inactivation. The applied voltage to thedischarging section was controlled to vary ozone concentrationbetween 0.06 and 5ppm. The gas flow velocity was 0.5 m/s.The relative humidity (RH) in the gas was controlled between5% and 95% using a humidifier.

    Zukeran et al. 181

  • II. METHODOLOGY

    The schematic diagrams of experimental ESP systems areshown in Fig. 1. Two types of ESPs were used for experiments,and placed in a clean bench. Type A was used to investigate theinfluences of ozone concentration, location of collection andelapsed time. It has a parallel-plate electrode structure com-posed of a high-voltage application electrode (70×160 mm)sandwiched between grounded plate electrodes (70×270 mm)with a gap of 10 mm. The high-voltage application electrodehas a sawtooth edge on its upstream side, while the groundedelectrodes have no such edges. All electrodes are made ofstainless steel with a thickness of 0.8 mm. A solution ofbacterial culture of Staphylococcus aureus (NBRC13276, 104

    CFU) diluted with saline was put at four locations on thesurface of one grounded plate electrode to simulate collectedmicroorganisms. The locations were 6 mm upstream from thetip of the sawtooth edge (Location A1), as well as 40, 80 and120 mm downstream from the tip (Location A2-A4). A controlwas located at 185 mm on the upstream side to except naturaldecrement of the microorganisms. In the preliminary experi-ment, it was obtained that the survival on the control decreasedby approximately 6% for 60 min at RH between 60 and 65%due to natural decrement. The gas flow velocity was adjustedto 0.5 m/s by a fan located on the downstream side of the ESP.The high-voltage application electrode was supplied with DCvoltage to generate negative corona discharge and electrostaticfield. The applied DC voltage was changed between -6.2 kVand -10 kV to vary ozone concentration in the gas flowbetween 0.06ppm and 5ppm. The microorganisms put on thoselocations were inactivated by corona discharge or ozone. Theexperiments were carried out under room temperature andnormal humidity.

    Type B was used to investigate the influence of relativehumidity (RH), location of collection and elapsed time. It hasa two-stage structure of discharging and electrostatic sections.The discharging section has a wire-and-plates configurationcomposed of a high-voltage application wire electrode (φ:0.45 mm, L: 70 mm, SUS304) placed between grounded plateelectrodes (70×270 mm) with a gap of 10 mm. The elec-trostatic section has a parallel-plate electrode structure com-posed of a high-voltage application electrode (70×174 mm)sandwiched between grounded plate electrodes (70×174 mm)with a gap of 10 mm. All plate electrodes are made of stainlesssteel with a thickness of 0.8 mm. Six samples of the bacterialculture (104 CFU) were put on two grounded plate electrodesin the discharging and electrostatic sections. The three samplesin the discharging section were respectively located under thewire electrode as well as at 25 mm upstream and downstreamfrom the wire electrode (Locations B1-B3). The three samplesin the electrostatic section were respectively located at thecenter of the electrode as well as at 43.5 mm upstream anddownstream from the center (Locations B4-B6). The controlwas located at 70 mm upstream from the grounded electrode inthe discharging section. The discharging section was suppliedwith DC voltage of -8.5 to -9.5 kV to generate negativecorona discharge, whereby the discharge current was adjustedto 0.024 mA, which ozone concentration was approximately

    (a) Type A

    (b) Type B

    Fig. 1. Schematic diagram of experimental apparatus.

    1ppm. The electrostatic section was supplied with DC voltageof -5 kV to form an electrostatic field. RH was controlledbetween 5% and 95% by a heating type humidifier with pure ortap water. The gas temperature was between 20◦C and 30◦C.

    The operating time was a maximum of 8 hours. Afterthe operation, S. aureus on the electrode was wiped usingRASPER CHECKTM, which was a wiping swab, and thenincubated for 24 hours. The survival η defined as Eq. (1), orthe survival ratio log(N/N0) were calculated from the colonycounts.

    η =N

    N0× 100 [%] (1)

    where N and N0 are the colony counts at each location onthe grounded electrodes and the control, respectively.

    III. RESULTS AND DISCUSSION

    A. Influence of ozone concentration and elapsed time

    Influence of ozone concentration and elapsed time wasmeasured using the type-A apparatus. The relationship be-tween survival and ozone concentration for an operating timeof 1 hour is shown in Fig. 2. A survival ratio less than100% means inactivation, while a ratio greater than 100%means an increased number of microorganisms. Survival atLocation A1 was 78% at an ozone concentration of 0.06ppm,which decreased with increasing ozone concentration, to beeventually stabilized at the levels between 12% and 21%.Survivals at Locations A2, A3 and A4 were between 126%and 136% at an ozone concentration of 0.06ppm, which tendedto decrease with increasing ozone concentration. However, thevalue was between 59% and 95% within the range from 3ppm

    182 International Journal of Plasma Environmental Science & Technology, Vol.10, No.2, DECEMBER 2016

  • Fig. 2. The relationship between survival and ozone concentration (Apparatus:type A. Operation time; 1 hour).

    Fig. 3. The influence of elapsed time on survival at ozone concentration of1ppm (Apparatus: type A).

    to 5ppm and the inactivation effect was barely improved withincreasing ozone concentration by 1 hour operation.

    The influence of the elapsed time on the survival at an ozoneconcentration of 1ppm is shown in Fig. 3. The survival atLocation A1 tended to decrease with time, reaching 12% at8 h. The survivals on Location A2, A3 and A4 decreased withtime, which reached between 30% and 35% at 8 h.

    These results demonstrate that the inactivation effect in thedischarging section is greater than in the electrostatic sectiondue to radicals other than ozone, and it takes more than 8 hoursto inactivate microorganisms on the electrode by ozone witha concentration of 1ppm.

    B. Effect of humidification

    Inactivation effect of corona discharge was confirmed inFigs. 2 and 3. However, it is necessary to more quickly inac-tivate microorganisms. Therefore, the effect of humidificationon inactivation was investigated using the type-B apparatus atan ozone concentration of 1ppm, and for 60 min. The relation-ship between survival and elapsed time for the six locationswith RH between 20 and 75% is shown in Fig. 4. This is theresult obtained without the humidifier. In Fig. 4(a), the survivalat Location B1 in the discharging section at elapsed time of

    (a) Discharging section

    (b) Electrostatic section

    Fig. 4. The influence of elapsed time on survival at six locations withRH between 5% and 75% (Apparatus: type B. Ozone concentration: 1ppm.Without humidifier).

    60 min was 98%, which barely changed for 60 min, becauseradicals barely reach the upstream side of the wire electrode.The survivals at B2 and B3 gradually decreased with time,reaching 28% and 33% at 60 min. In Fig. 4(b), the survivalsat B4, B5 and B6 in the electrostatic section were greater than100% for 30 min after the operation began. Corona dischargemay also have enhancement effect of microorganism. Furtherstudy is needed to investigate this phenomena. In elapsed timebetween 30 and 60 min, the survivals tended to decrease,reaching 82%. However, this result indicates that it is difficultto quickly inactivate microorganisms by only ozone, as hasalready been shown in Fig. 2.

    The relationship between survival and elapsed time for thesix locations with RH between 75% and 95% is shown inFig. 5. This is the result obtained using the humidifier withpure water. In Fig. 5(a), the result at Location B1 on theupstream side of the wire electrode in the discharging sectionsignificantly fluctuated, whereas the survivals at B2 and B3immediately decreased after the operation began. The survivalsat B2 and B3 reached 27% and 11% after 10 minutes ofoperation, while those without the humidifier were 81% after10 minutes of operation as shown in Fig. 4(a). In Fig. 5(b),

    Zukeran et al. 183

  • (a) Discharging section

    (b) Electrostatic section

    Fig. 5. The influence of elapsed time on survival at six locations with RHbetween 75% and 95% (Apparatus: type B. Ozone concentration: 1ppm. Usinghumidifier with pure water).

    the survivals at any locations in the electrostatic section alsosignificantly decreased with time. The survivals at B4, B5 andB6 achieved the levels between 16% and 23% after 10 minutesof operation, while the values achieved without the humidifierwere between 122% and 170% at the same operation time asshown in Fig. 4(b).

    From these results, it is clear that the inactivation effectsboth discharging and electrostatic sections are significantlyimproved by humidification. This is most likely due to thefact that the ROS is held in the moisture on microorganisms’surface.

    C. Characteristic of inactivation effect in relation to RH

    The survival ratio as a function of RH in the dischargingsection is shown in Fig. 6. Pure water was used for hu-midification with RH greater than 75%, the operation timewas 60 minutes, and the discharge current was adjusted to0.024 mA which the ozone concentration was 1ppm. Thesurvival ratio at Location B1 was almost constant when RHwas between 5% and 60%, which increased at RH greaterthan 60%. The reason for this increase needs to be studiedin the future. The ratios at Location B2 and B3 at RH less

    Fig. 6. Survival ratio as a function of relative humidity in the dischargingsection (Apparatus: type A. Ozone concentration: 1ppm. Operating time: 1 h).

    Fig. 7. Survival ratio as a function of relative humidity in the electrostaticsection (Apparatus: type A. Ozone concentration: 1ppm. Operating time: 1 h).

    than 60% barely changed. However, those at RH greater than60% decreased with increasing RH. Survivals decreased bythree orders of magnitude at RH greater than 85%, which isa significant improvement in inactivation effect.

    The survival ratio as a function of RH in the electrostaticsection is shown in Fig. 7. The experimental condition is thesame with Fig. 6. No significant decrease in the survival ratiowas observed at RH less than 60%, while the ratio at anylocation decreased when RH was greater than 60%. Some dataobtained at RH of 85% or greater were lower than the initiallevel by two or more orders of magnitude.

    These results show that RH should desirably be increasedto 60% or higher by humidification to improve the inactivationeffect, and to 85% or higher to achieve high values.

    In practical applications of this system, tap water is morereadily available than pure water for humidification. Thus,the effect of tap water was confirmed. The comparison ofinactivation effect between pure water and tap water is shownin Fig. 8. This is the result obtained using the type-B apparatusat ozone concentration of 1ppm for 1 hour operation, withRH between 75% and 95%. The values indicated are averageratios, and the error bar represents the standard deviation. InFig. 8(a), the survival ratio obtained with humidification by tapwater at each location in the discharging section is equal to or

    184 International Journal of Plasma Environmental Science & Technology, Vol.10, No.2, DECEMBER 2016

  • (a) Discharging section

    (b) Electrostatic section

    Fig. 8. The comparison of inactivation effect between pure water and tapwater (Apparatus: type B. Ozone concentration: 1ppm. Operating time: 1 h.RH: 75%-95%. Using humidifier with pure or tap water).

    lower than that by pure water. In Fig. 8(b), the survival ratioobtained with humidification by tap water at each locationin the electrostatic section is also lower than that by purewater. These results show that tap water can be similarly usedinstead of pure water to improve the inactivation effect byhumidification.

    IV. CONCLUSIONIn this study, we investigated the influence of the location

    of collection, ozone concentration, elapsed time and relativehumidity (RH) on inactivation of microorganisms collected onelectrodes in an ESP. Results are follows:

    1) Inactivation effect in the discharging section is greaterthan that in the electrostatic section due to radicals otherthan ozone.

    2) Inactivation effects in the discharging and the electro-static sections are significantly improved by humidifica-tion.

    3) The survival decreased with increasing relative humid-ity; it is desirable to increase RH to 60% or higher byhumidification.

    4) Tap water can be used instead of pure water to improveinactivation effect by humidification.

    ACKNOWLEDGMENT

    The authors wish to thank Iori Kobayashi for valuablecomments and discussions.

    REFERENCES[1] A. Mizuno, Y. Yamazaki, H. Ito, and H. Yoshida, “AC energized

    ferroelectric pellet bed gas cleaner,” IEEE Transactions on IndustryApplications, vol. 28, pp. 535–540, 1992.

    [2] M. J. Gallagher, A. Gutsol, A. Fridman, G. Friedman, andA. Dolgopolsky, “Non-thermal plasma applications in air sterilization,”in IEEE International Conference on Plasma Science, 2004, p. 198.

    [3] I. Botvinnik, C. E. Taylor, and G. Snyder, “High-efficiency portableelectrostatic air cleaner with insulated electrodes (January 2007),” IEEETransactions on Industry Applications, vol. 44, pp. 512–516, 2008.

    [4] A. Takimoto, Y. Tada, H. Onishi, K. Nagaura, and A. Kosaka, “Fineparticle and bacteria collection system by negative ions and ozone withmist formation (in Japanese),” Transactions of the Japan Society ofRefrigerating and Air Conditioning Engineers, vol. 29, pp. 23–30, 2012.

    [5] L. Tun, K. Takashima, S. Katsura, and A. Mizuno, “Recovery offiltration efficiency and sterilization effect of polypropylene (PP)electret filter by recharging with DC corona discharge (in Japanese),”Journal of the Institute of Electrostatics Japan, vol. 29, pp. 130–136,2005.

    [6] K. Yoshida, T. Hibino, N. Saeki, and M. Okubo, “Sterilizationdevice using corona discharge plasma jet at atmospheric pressure (inJapanese),” Journal of the Institute of Electrostatics Japan, vol. 32, pp.90–91, 2008.

    [7] Y. Tanimura and J. Hirotsuji, “Production of negative ions and ozoneby corona discharge and their application to sterilization (in Japanese),”Journal of the Institute of Electrostatics Japan, vol. 22, pp. 212–214,1998.

    [8] I. V. Timoshkin, M. MacLean, M. P. Wilson, M. J. Given, S. J.MacGregor, T. Wang, and J. G. Anderson, “Bactericidal effect ofcorona discharges in atmospheric air,” IEEE Transactions on PlasmaScience, vol. 40, pp. 2322–2333, 2012.

    [9] Y. Tanaka, H. Yasuda, H. Kurita, K. Takashima, and A. Mizuno,“Analysis of the inactivation mechanism of bacteriophage φX174 byatmospheric pressure discharge plasma,” IEEE Transactions on IndustryApplications, vol. 50, pp. 1397–1401, 2014.

    [10] T. Tanino, A. Miyazaki, T. Furuhashi, and T. Ohshima, “Eliminationof airborne microorganism by corona discharge plasma and analysis ofmicroorganism inactivation mechanism trapped on grounded electrode(in Japanese),” Journal of the Institute of Electrostatics Japan, vol. 39,pp. 2–8, 2015.

    [11] N. Kosaka, F. Kadowaki, and S. Okuda, “Sterilization of Bacillus subtilisusing ozone (in Japanese),” Tokyu Sharyo Technical Review, vol. 48, pp.53–58, 2015.

    [12] S. Fukunaga, M. Yamashita, T. Suzuki, Y. Suzuki, R. Takahashi, andT. Shimoyama, “Characterisitics of the bactericidal effect of ozone gason pathogenic bacteria in hospital (in Japanese),” Journal of Antibacte-rial and Antifungal Agents, vol. 27, pp. 359–367, 1999.

    [13] H. Anzai, M. Kurokawa, and T. Ono, “Study of indoor sterilization withozone (in Japanese),” The Journal of Practical Pharmacy, vol. 41, pp.217–221, 1990.

    Zukeran et al. 185