Product Description
Issue 01
Date 2009-10-28
Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Huawei Technologies Co., Ltd. provides customers with comprehensive technical support and service. For anyassistance, please contact our local office or company headquarters.
Huawei Technologies Co., Ltd.Address: Huawei Industrial Base
Bantian, LonggangShenzhen 518129People's Republic of China
Website: http://www.huawei.com
Email: [email protected]
Copyright © Huawei Technologies Co., Ltd. 2009. All rights reserved.No part of this document may be reproduced or transmitted in any form or by any means without prior writtenconsent of Huawei Technologies Co., Ltd. Trademarks and Permissions
and other Huawei trademarks are the property of Huawei Technologies Co., Ltd.All other trademarks and trade names mentioned in this document are the property of their respective holders. NoticeThe purchased products, services and features are stipulated by the contract made between Huawei and thecustomer. All or part of the products, services and features described in this document may not be within thepurchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information,and recommendations in this document are provided "AS IS" without warranties, guarantees or representationsof any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in thepreparation of this document to ensure accuracy of the contents, but the statements, information, andrecommendations in this document do not constitute a warranty of any kind, express or implied.
Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Contents
About This Document.....................................................................................................................1
1 Product Feature...........................................................................................................................1-11.1 Prominent Security Performance....................................................................................................................1-21.2 Prominent Protection Performance.................................................................................................................1-21.3 Easy Installation..............................................................................................................................................1-21.4 Prominent Monitoring and Maintainability.....................................................................................................1-31.5 Compact and Reliable Structure......................................................................................................................1-4
2 Product Structure........................................................................................................................2-12.1 Appearance and Dimensions...........................................................................................................................2-22.2 Structure..........................................................................................................................................................2-22.3 Power System..................................................................................................................................................2-4
2.3.1 AC PDU.................................................................................................................................................2-62.3.2 AC Single-phase Lightning Protection Bar............................................................................................2-72.3.3 Battery....................................................................................................................................................2-82.3.4 Battery Heater........................................................................................................................................2-92.3.5 Remote power supply.............................................................................................................................2-92.3.6 DC PDU...............................................................................................................................................2-10
2.4 Cable Distribution Device.............................................................................................................................2-102.4.1 MDF.....................................................................................................................................................2-102.4.2 ODF......................................................................................................................................................2-12
2.5 Temperature Control Unit.............................................................................................................................2-132.6 Monitoring System........................................................................................................................................2-14
2.6.1 Monitoring Scheme..............................................................................................................................2-142.6.2 Sensor...................................................................................................................................................2-15
3 System Configuration...............................................................................................................3-13.1 F01S100 cabinet Configured with the MA5610.............................................................................................3-23.2 F01S100 cabinet Configured with the MA5616.............................................................................................3-2
4 System Parameters.....................................................................................................................4-1
5 Environmental Specifications..................................................................................................5-1
6 Standards Compliance..............................................................................................................6-1
F01S100Product Description Contents
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
i
7 Acronyms and Abbreviations..................................................................................................7-1
ContentsF01S100
Product Description
ii Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
Figures
Figure 1-1 The installation of the F01S100 cabinet ............................................................................................1-3Figure 2-1 Appearance and dimensions of the F01S100 cabinet.........................................................................2-2Figure 2-2 Structure of the F01S100 cabinet.......................................................................................................2-3Figure 2-3 Power distribution scheme of the F01S100 cabinet...........................................................................2-5Figure 2-4 Appearance of battery.........................................................................................................................2-8Figure 2-5 Appearance of the MDF in the F01S100 cabinet.............................................................................2-11Figure 2-6 Appearance of the ODF in the F01S100 cabinet..............................................................................2-13Figure 2-7 Monitoring scheme of the F01S100 cabinet.....................................................................................2-14Figure 2-8 Appearance of the door status sensor...............................................................................................2-15
F01S100Product Description Figures
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
iii
Tables
Table 2-1 Structure of the F01S100 cabinet (configured with the AC-powered MA5610/MA5616).................2-4Table 2-2 Structure of the F01S100 cabinet (configured with the DC-powered MA5610/MA5616).................2-4Table 2-3 Specifications of the lightning arrester................................................................................................2-6Table 2-4 Technical specifications of the maintenance socket............................................................................2-7Table 2-5 Technical specifications of the AC single-phase lightning protection bar...........................................2-7Table 2-6 Technical specifications of battery.......................................................................................................2-8Table 2-7 Technical specifications of the battery heater......................................................................................2-9Table 2-8 Technical specifications of the remote power supply........................................................................2-10Table 2-9 Specifications of the MDF in the F01S100 cabinet...........................................................................2-11Table 2-10 Specifications of the ODF................................................................................................................2-13Table 2-11 Technical parameters of the heat dissipation fan.............................................................................2-14Table 3-1 Number of subscribers supported by the F01S100 cabinet in different configurations.......................3-2Table 3-2 Number of subscribers supported by the F01S100 cabinet in different configurations.......................3-2Table 4-1 Dimensions of the F01S100 cabinet....................................................................................................4-1Table 4-2 Weight of the F01S100 cabinet............................................................................................................4-1Table 4-3 Power of the F01S100 cabinet.............................................................................................................4-1Table 5-1 Environment specifications of the F01S100 cabinet............................................................................5-1Table 6-1 Standards compliance of the F01S100 cabinet....................................................................................6-1
F01S100Product Description Tables
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
v
About This Document
OverviewThe F01S100 cabinet can hold the MA5610 and MA5616. The F01S100 cabinet is a small-capacity device that can provide the LAN, POTS, ADSL2+, and VDSL2 services for thesubscriber.
This document describes the product feature, product structure, system configuration,systemparameters,environmental specifications,standards compliance and acronyms andabbreviations of the F01S100 cabinet.
Related VersionThe following table lists the product version related to this document.
Product Name Version
MA5610/MA5616 V800R307
Intended AudienceThe intended audience of this document is:
l Network planning engineers
l Installation and commissioning engineers
l Field maintenance engineers
l Network monitoring engineers
l System maintenance engineers
l Data configuration engineers
l Application developers
F01S100Product Description About This Document
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
1
OrganizationThe F01S100 cabinetis an indoor and front access cabinet of a small capacity. The followingtable lists the contents of the document.
Chapter... Describes...
1 Product Feature The security performance, protection performance,installation method, and structure of the F01S100 cabinet.
2 Product Structure The appearance, structure, and parameters of the F01S100cabinet, and the functions of the components.
3 System Configuration The configuration of the F01S100 cabinet.
4 System Parameters The dimensions, weight, power consumption, configurationand environmental parameters of the F01S100 cabinet.
5 EnvironmentalSpecifications
The environmental parameters of the F01S100 cabinet.
6 Standards Compliance The standards that the F01S100 cabinet complies with interms of environment, structure, power system, and lightingprotection.
7 Acronyms andAbbreviations
The acronyms and abbreviations used in this document.
Conventions
Symbol Conventions
The following symbols may be found in this document. They are defined as follows.
Symbol Description
Indicates a hazard with a high level of risk which, if notavoided, will result in death or serious injury.
Indicates a hazard with a medium or low level of risk which,if not avoided, could result in minor or moderate injury.
Indicates a potentially hazardous situation that, if notavoided, could cause equipment damage, data loss, andperformance degradation, or unexpected results.
Indicates a tip that may help you solve a problem or saveyour time.
About This DocumentF01S100
Product Description
2 Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
Symbol Description
Provides additional information to emphasize orsupplement important points of the main text.
General Conventions
Convention Description
Times New Roman Normal paragraphs are in Times New Roman.
Boldface Names of files, directories, folders, and users are inboldface. For example, log in as user root.
Italic Book titles are in italics.
Courier New Terminal display is in Courier New.
Command Conventions
Convention Description
Boldface The keywords of a command line are in boldface.
Italic Command arguments are in italic.
[ ] Items (keywords or arguments) in square brackets [ ] areoptional.
{ x | y | ... } Alternative items are grouped in braces and separated byvertical bars. One is selected.
[ x | y | ... ] Optional alternative items are grouped in square bracketsand separated by vertical bars. One or none is selected.
{ x | y | ... } * Alternative items are grouped in braces and separated byvertical bars. A minimum of one or a maximum of all canbe selected.
GUI Conventions
Convention Description
Boldface Buttons, menus, parameters, tabs, window, and dialog titlesare in boldface. For example, click OK.
> Multi-level menus are in boldface and separated by the ">"signs. For example, choose File > Create > Folder.
F01S100Product Description About This Document
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
3
Keyboard OperationFormat Description
Key Press the key. For example, press Enter and press Tab.
Key 1+Key 2 Press the keys concurrently. For example, pressing Ctrl+Alt+A means the three keys should be pressedconcurrently.
Key 1, Key 2 Press the keys in turn. For example, pressing Alt, A meansthe two keys should be pressed in turn.
Mouse OperationAction Description
Click Select and release the primary mouse button withoutmoving the pointer.
Double-click Press the primary mouse button twice continuously andquickly without moving the pointer.
Drag Press and hold the primary mouse button and move thepointer to a certain position.
Update HistoryUpdates between document versions are cumulative. Therefore, the latest document versioncontains all updates made to previous versions.
Updates in Issue 01 (2009-10-28)This is the first release.
About This DocumentF01S100
Product Description
4 Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
1 Product Feature
About This Chapter
This topic describes the security performance, protection performance, installation method,monitoring, maintenance, and structure of the F01S100 cabinet.
1.1 Prominent Security PerformanceThe F01S100 cabinet features prominent security performance to comply with the internationalsafety standards.
1.2 Prominent Protection PerformanceThe F01S100 cabinet features prominent protection performance to meet the requirements ofthe outdoor or the indoor environment that does not have any protection.
1.3 Easy InstallationThe F01S100 cabinet can be installed on the wall, on a pole, or on a concrete pedestal.
1.4 Prominent Monitoring and MaintainabilityThe structure of the F01S100 cabinet meets the requirements of real-time monitoring and easymaintenance.
1.5 Compact and Reliable StructureThe compact design of the F01S100 cabinet facilitates the installation of the F01S100 cabinetand ensures that the F01S100 cabinet runs reliably.
F01S100Product Description 1 Product Feature
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
1-1
1.1 Prominent Security PerformanceThe F01S100 cabinet features prominent security performance to comply with the internationalsafety standards.
l The F01S100 cabinet features prominent protection performance and anti-attackperformance.
l The F01S100 cabinet uses the HW-2802A lock to secure the cabinet door and serve as ananti-theft measure.
1.2 Prominent Protection PerformanceThe F01S100 cabinet features prominent protection performance to meet the requirements ofthe outdoor or the indoor environment that does not have any protection.
l When the F01S100 cabinet is configured with the MA5610/MA5616 (device that uses theforced air cooling mode for heat dissipation), the F01S100 cabinet provides the IPprotection rating of the integrated device reaches IP55 ("IP" refers to InternationalProtection. The first number "5" refers to the class for preventing the solid particle fromentering the device. That is, the cabinet cannot completely prevent dust from entering thedevice, but the amount of dust that enters the cabinet does not damage the device. Thesecond number "5" refers to the class for preventing water from entering the cabinet. Thatis, the water sprayed from different directions to the cabinet does not damage the device.).
l The built-in lightning arrester in the AC PDU or AC single-phase lightning protection barprotects the AC power supply.
l The built-in external line protection unit (optional) and the service boards provide 2-levelprotection for the service ports and meet the requirements of the K-45 protection index.
1.3 Easy InstallationThe F01S100 cabinet can be installed on the wall, on a pole, or on a concrete pedestal.
The F01S100 cabinet can be easily installed.l The F01S100 cabinet has firm mounting brackets on its top and thus can be hoisted in a
safe and reliable way.l The F01S100 cabinet provides a marking-off plate. During the installation, you can use the
marking-off plate to determine the installation position of the cabinet. As a result, you needto carry the cabinet only once.
l The wall mounting installation parts of the F01S100 cabinet enable you to install theF01S100 cabinet on the wall that has the surface differences smaller than 10 mm. Thislowers the risk of installing the cabinet.
Figure 1-1 shows the installation of the F01S100 cabinet
1 Product FeatureF01S100
Product Description
1-2 Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
Figure 1-1 The installation of the F01S100 cabinet
1.4 Prominent Monitoring and MaintainabilityThe structure of the F01S100 cabinet meets the requirements of real-time monitoring and easymaintenance.
F01S100Product Description 1 Product Feature
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
1-3
l The F01S100 cabinet monitors the states of the internal ambient temperature, door status,lightning arrester (optional), heat dissipation fan (optional), and major alarms of the remotepower supply in real time to support the remote alarming function.
l The F01S100 cabinet (configured with AC-powered MA5610/MA5616) provides an ACpower socket to supply power to the maintenance terminal and implement on-sitemaintenance.
1.5 Compact and Reliable StructureThe compact design of the F01S100 cabinet facilitates the installation of the F01S100 cabinetand ensures that the F01S100 cabinet runs reliably.
l When the F01S100 cabinet configured with the AC-powered MA5610/MA5616, itintegrates the AC-powered MA5610/MA5616, main distribution frame (MDF), opticaldistribution frame (ODF), AC PDU, battery (optional), battery heater (optional) andenhanced heat dissipation module (optional). The F01S100 cabinet can be installed quicklyon site to meet the requirement for quick deployment.
l When the F01S100 cabinet configured with the DC-powered MA5610/MA5616, itintegrates the DC-powered MA5610/MA5616, MDF, ODF, remote power supply, DCPDU and enhanced heat dissipation module (optional). The F01S100 cabinet can beinstalled quickly on site to meet the requirement for quick deployment.
l The ventilation design of the F01S100 cabinet can ensure that the F01S100 cabinet runsreliably in the outdoor or indoor environment when the F01S100 cabinet is not configuredwith any air conditioner.
1 Product FeatureF01S100
Product Description
1-4 Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
2 Product Structure
About This Chapter
This topic describes the appearance, structure, component function, and related technicalparameter of the F01S100 cabinet.
2.1 Appearance and DimensionsThis topic shows the appearance and dimensions of the F01S100 cabinet.
2.2 StructureThis topic describes the structure of the F01S100 cabinet when it is configured with differentdevices.
2.3 Power SystemThe F01S100 cabinet uses the optional AC PDU or AC single-phase lightning protection bar tosupport the AC-powered MA5616/MA5610. It can also use the remote power supply to supportthe DC-powered MA5616/MA5610.
2.4 Cable Distribution DeviceThe F01S100 cabinet is configured with the built-in MDF and ODF. The MDF is used to connectthe internal subscriber cable and the external subscriber cable. The ODF is used to connect theoptical fiber and the optical communication device.
2.5 Temperature Control UnitThis topic provides the technical parameters of the built-in temperature control unit used in theF01S100 cabinet.
2.6 Monitoring SystemThis topic describes the monitoring scheme and the built-in sensors of the F01S100 cabinet.
F01S100Product Description 2 Product Structure
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
2-1
2.1 Appearance and DimensionsThis topic shows the appearance and dimensions of the F01S100 cabinet.
Figure 2-1 shows the appearance and dimensions of the F01S100 cabinet.
Figure 2-1 Appearance and dimensions of the F01S100 cabinet
2.2 StructureThis topic describes the structure of the F01S100 cabinet when it is configured with differentdevices.
2 Product StructureF01S100
Product Description
2-2 Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
NOTE
The F01S100 cabinet provides a space of 4 U for installing devices and can be configured with the followingdevices:
l One AC-powered MA5610/MA5616. During installation, the AC-powered MA5610/MA5616 mustbe installed at the outermost 2 U position to facilitate heat dissipation and future maintenance.
l One DC-powered MA5610/MA5616 + one remote power supply + one DC PDU. During installation,the DC-powered MA5610/MA5616 must be installed at the outermost 2 U position to facilitate heatdissipation and future maintenance; the DC PDU must be installed at the inmost 1 U position.
Figure 2-2 shows the structure of the F01S100 cabinet. The advantages of the F01S100cabinet structure are as follows:l The F01S100 cabinet can be installed and maintained from its front. Cables and boards can
be installed or removed easily.l The low-noise design is excellent. The noise is lowered to 35 dBA at nights, which is as
quiet as in a library.l The F01S100 cabinet provides the excellent cabling management function.
l The F01S100 cabinet supports up to 256 narrowband lines, which is the largest capacityfor the products of the same type in the industry.
Figure 2-2 Structure of the F01S100 cabinet
Configured with the AC-powered MA5610/MA5616
Table 2-1 shows the structure of the F01S100 cabinet configured with the AC-poweredMA5610/MA5616.
F01S100Product Description 2 Product Structure
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
2-3
Table 2-1 Structure of the F01S100 cabinet (configured with the AC-powered MA5610/MA5616)
Item Component Name
Service device One AC-powered MA5610/MA5616
Power system l AC PDU
l Battery (optional)
l Battery Heater (optional)
Cabledistributiondevice
l MDF
l ODF
Temperaturecontrol unit
Enhanced heat dissipation module (optional)
Monitoringsystem
Sensor (optional)
Configured with the DC-powered MA5610/MA5616Table 2-2 shows the structure of the F01S100 cabinet configured with the DC-poweredMA5610/MA5616.
Table 2-2 Structure of the F01S100 cabinet (configured with the DC-powered MA5610/MA5616)
Item Component Name
Service device One DC-powered MA5610/MA5616
Power system Remote power supply / DC PDU
Cabledistributiondevice
l MDF
l ODF
Temperaturecontrol unit
Enhanced heat dissipation module (optional)
Monitoringsystem
Sensor (optional)
2.3 Power SystemThe F01S100 cabinet uses the optional AC PDU or AC single-phase lightning protection bar tosupport the AC-powered MA5616/MA5610. It can also use the remote power supply to supportthe DC-powered MA5616/MA5610.
Figure 2-3 shows the power distribution scheme of the F01S100 cabinet
2 Product StructureF01S100
Product Description
2-4 Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
Figure 2-3 Power distribution scheme of the F01S100 cabinet
2.3.1 AC PDUThis topic describes the power distribution scheme and the related technical specifications ofthe built-in AC PDU (optional) in the F01S100 cabinet.
2.3.2 AC Single-phase Lightning Protection BarThis topic describes the power distribution scheme and the related technical specifications ofthe built-in AC single-phase lightning protection bar (optional) in the F01S100 cabinet.
2.3.3 Battery
F01S100Product Description 2 Product Structure
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
2-5
When the F01S100 cabinet is configured with the AC-powered MA5610/MA5616, batteries canbe selected as the backup power supply.
2.3.4 Battery HeaterThis topic describes the technical specifications of the battery heater used in the F01S100cabinet.
2.3.5 Remote power supplyWhen configured with the DC-powered MA5610/MA5616, the F01S100 cabinet uses the remotepower supply as its DC power input.
2.3.6 DC PDUThis topic describes technical specifications of the built-in DC PDU in the F01S100 cabinet.
2.3.1 AC PDUThis topic describes the power distribution scheme and the related technical specifications ofthe built-in AC PDU (optional) in the F01S100 cabinet.
The AC PDU consists of the lightning arrester, maintenance socket, and MCB.
Lightning Arrester
The lightning arrester protects the 220 V single-phase power system against the surge voltagecaused by the lightning. Table 2-3 lists the technical specifications of the lightning arrester.
Table 2-3 Specifications of the lightning arrester
Item Value
Rated voltage 220 VAC
Maximum continuous running voltage(Uc)
380 VAC
Rated discharge current (In) 20 kA (8/20 μs)
Maximum discharge current (Imax) 40 kA (8/20 μs)
Protection rating (Up) l < 1.5kV (8/20 μs, 5 kA)
l < 1.8kV (8/20 μs, 15 kA)
Response time ≤ 25 ns
Dimensions 100 mm x 65 mm x 72 mm
Environment for usage l Temperature: –40°C to +70°C
l Relative humidity: ≤ 95%
Maintenance Socket
The maintenance socket is connected to the maintenance terminal to facilitate the on-sitemaintenance. Table 2-4 lists the technical specifications of the maintenance socket.
2 Product StructureF01S100
Product Description
2-6 Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
Table 2-4 Technical specifications of the maintenance socket
Item Value
220 VAC power supply 220 VAC/3 A
MCB
The MCB controls the external AC input.
2.3.2 AC Single-phase Lightning Protection BarThis topic describes the power distribution scheme and the related technical specifications ofthe built-in AC single-phase lightning protection bar (optional) in the F01S100 cabinet.
Table 2-5 lists the technical specifications of the AC single-phase lightning protection bar usedin the F01S100 cabinet.
Table 2-5 Technical specifications of the AC single-phase lightning protection bar
Item Value
Rated working voltage 250 VAC
Maximum continuous running voltage (Uc) 385 VAC
Working frequency 47 Hz to 63 Hz
Rated working current 8 A
Fuse current 8 A
Fuse type Slow-blow
Protection mode L-N, L-PE, and N-PE
Rated through-current capacity (In) 5 kA (8/20 μs)
Maximum discharge current (Imax) 15 kA (8/20 μs)
Voltage protection rating (Up) 1500 V (8/20 us)
LED for improper grounding Off: normalRed and on: An alarm is generated.
LED for polarity reversal Off: normalYellow and on: An alarm is generated.
LED for lightning protection Off: normalRed and on: The lightning protection fails.
Type of socket hole Versatile
Number of socket holes 3 bits
F01S100Product Description 2 Product Structure
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
2-7
Item Value
Shell protection rating IP20
Flame retardant rating 94-V0
Response time Ta ≤ 25 ns
Cable specifications With a diameter of 8 mm and a length of 2 m
Working temperature –40°C to +70°C
Storage temperature –40°C to +85°C
Relative humidity 5% to 95%
Dimensions (W x D x H) 288 mm x 58 mm x 46 mm
2.3.3 BatteryWhen the F01S100 cabinet is configured with the AC-powered MA5610/MA5616, batteries canbe selected as the backup power supply.
The AC-powered MA5610/MA5616 provides the interface for batteries.
NOTE
When the F01S100 cabinet is configured with the AC-powered MA5610/MA5616, a set (four batteries)of 12 Ah batteries can be selected as the backup power supply.
Figure 2-4 shows appearance of battery.
Figure 2-4 Appearance of battery
Table 2-6 lists the technical specifications of the batteries used in the F01S100 cabinet.
Table 2-6 Technical specifications of battery
Item Value
Rate working voltage (when configuredwith four batteries)
–48 VDC
2 Product StructureF01S100
Product Description
2-8 Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
Item Value
Rated capacity 12 Ah
Floating charging voltage of the battery set –54 VDC
Maximum charging current 3.6 A
Voltage of a single battery –12 VDC
Working temperature range –15°C to +50°C
Dimensions of a single battery (W x D x H) 151 mm x 100 mm x 98 mm
Weight of a single battery 3.83 kg
2.3.4 Battery HeaterThis topic describes the technical specifications of the battery heater used in the F01S100cabinet.
NOTE
Two battery heaters must be configured when the F01S100 cabinet is used in the area where the ambienttemperature is below 0°C.
Table 2-7 lists the technical specifications of the battery heater used in the F01S100 cabinet.
Table 2-7 Technical specifications of the battery heater
Item Value
Rated voltage 220 VAC
Voltage range 150 VAC to 300 VAC
Rated heating power 70 W
Insulation resistance The insulation resistance between the heaterleading power cable and the heater shell mustbe greater than 10 megohms.
Working environment The heater can work reliably in theenvironment with relative humidity of 5% to95%.
Dimensions (L x W x D) 180 mm x 125 mm x 2 mm
2.3.5 Remote power supplyWhen configured with the DC-powered MA5610/MA5616, the F01S100 cabinet uses the remotepower supply as its DC power input.
Table 2-8 lists the technical specifications of the remote power supply used in the F01S100cabinet.
F01S100Product Description 2 Product Structure
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
2-9
Table 2-8 Technical specifications of the remote power supply
Item Value
Input rated voltage 340 VDC (+/-170 VDC)
Input voltage range 285 VDC to 348 VDC
Output rated voltage –48 VDC
Output voltage range –40 VDC to –57 VDC
Cooling method Forced air cooling
Working temperature range -40℃ to +70℃
Storage temperature range -40℃ to +80℃
Weight 2.5 kg
Dimensions (W x D x H) 445 mm x 230 mm x 44.5 mm
2.3.6 DC PDUThis topic describes technical specifications of the built-in DC PDU in the F01S100 cabinet.
The DC PDU consists of the MCB. The MCB controls the -48 VDC output of the remote powersupply.
2.4 Cable Distribution DeviceThe F01S100 cabinet is configured with the built-in MDF and ODF. The MDF is used to connectthe internal subscriber cable and the external subscriber cable. The ODF is used to connect theoptical fiber and the optical communication device.
2.4.1 MDFThis topic describes the specifications of the built-in MDF in the F01S100 cabinet.
2.4.2 ODFThis topic provides the appearance of the built-in ODF in the F01S100 cabinet and describesthe capacity specifications of the ODF.
2.4.1 MDFThis topic describes the specifications of the built-in MDF in the F01S100 cabinet.
l The 16-pair exchange side terminal blocks are installed to be connected with the internalcables of the MDF and the jumper cables. The exchange side terminal blocks are also usedfor tests and open circuits.
l The 10-pair cable side terminal blocks are installed to be connected with the external cablesof the MDF and the jumper cables. The protective unit (optional) installed in the cable sideterminal block provides the overvoltage protection and generates alarms.
2 Product StructureF01S100
Product Description
2-10 Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
l The harness, which consists of the connector, subscriber cable, and terminal block, providesconnections between the service boards and the MDF.
Figure 2-5 shows the appearance of the MDF in the F01S100 cabinet.
Figure 2-5 Appearance of the MDF in the F01S100 cabinet
Table 2-9 lists the specifications of the MDF.
Table 2-9 Specifications of the MDF in the F01S100 cabinet
Item Value
Type of theexchange sideterminal block
JPX658-STO-236XD (White)
F01S100Product Description 2 Product Structure
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
2-11
Item Value
Height of theexchange sideterminal block
12 mm
Type of the cableside terminal block
l JPX658-FA8-239XB (White)
l JPX658-FA8-239XH (Yellow)
l JPX658-BLK2-E10VB (White)
l JPX658-BLK2-E10VH (Yellow)
Height of the cableside terminal block
l JPX658-FA8-239XB (15 mm)
l JPX658-FA8-239XH (15 mm)
l JPX658-BLK2-E10VB (13 mm)
l JPX658-BLK2-E10VH (13 mm)
Type of theprotective unit
l JPX658-FA9-280J
l JPX658-FA10-97
l JPX658-SPD2-G400T
Type of the SPL l JPX658-VPS3-Y600-VDSL2
l JPX658-VPS3-E270A-VDSL2
l JPX658-VPS3-E270B-VDSL2
l JPX658-VPS3-E320-VDSL2
Height of the MDF 680 mm, which can be adjusted flexibly.
2.4.2 ODFThis topic provides the appearance of the built-in ODF in the F01S100 cabinet and describesthe capacity specifications of the ODF.
The ODF is used to connect the optical fiber and the optical communication device. The ODFcan perform the following functions:
l Fasten and protect optical fibers.
l Protect the cores of the peeled optical fibers.
l Distribute optical fibers.
l Adjust optical fibers.
l Store optical fibers.
Figure 2-6 shows the appearance of the ODF in the F01S100 cabinet.
2 Product StructureF01S100
Product Description
2-12 Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
Figure 2-6 Appearance of the ODF in the F01S100 cabinet
Table 2-10 lists the specifications of the built-in ODF in the F01S100 cabinet.
Table 2-10 Specifications of the ODF
ODF Type Port Type Capacity
ODF (simple) FC/PC 6 adapters (default configuration: 2adapters)
2.5 Temperature Control UnitThis topic provides the technical parameters of the built-in temperature control unit used in theF01S100 cabinet.
The F01S100 cabinet uses the heat exchanger mounted on the cabinet wall for heat dissipation.Besides, the cabinet can also be configured with a enhanced heat dissipation module to furtherimprove the heat dissipation performance and to meet the requirement of the environment witha temperature higher than 45°C (When the solar radiation intensity is 1120 W/m2, the highestenvironment temperature is 50°C).
The enhanced heat dissipation consists of two heat dissipation fans. Table 2-11 describes thetechnical parameters of the heat dissipation fan.
F01S100Product Description 2 Product Structure
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
2-13
Table 2-11 Technical parameters of the heat dissipation fan
Item Value
Rated voltage -48 VDC
Running voltage –28 VDC to –54 VDC
Input current 0.17 A
Running power 8.16 W
Rotating speed 3700 rpm
Wind volume 81.97 CFM
Dimensions 92 mm x 92 mm x 25.4 mm
2.6 Monitoring SystemThis topic describes the monitoring scheme and the built-in sensors of the F01S100 cabinet.
2.6.1 Monitoring SchemeThe service chassis installed in the F01S100 cabinet monitors the environment and keycomponents of the cabinet.2.6.2 SensorThis topic provides the appearances of the built-in sensors in the F01S100 cabinet and providesthe information about the functions of the sensors.
2.6.1 Monitoring SchemeThe service chassis installed in the F01S100 cabinet monitors the environment and keycomponents of the cabinet.
Figure 2-7 shows the monitoring scheme of the F01S100 cabinet.
Figure 2-7 Monitoring scheme of the F01S100 cabinet
2 Product StructureF01S100
Product Description
2-14 Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
2.6.2 SensorThis topic provides the appearances of the built-in sensors in the F01S100 cabinet and providesthe information about the functions of the sensors.
Door status sensorThe door status sensor uses the door status switch as the probe. The door status switch consistsof two built-in parts. The spring clips of the door status switch attract each other due toelectromagnetic interaction. The door status switch monitors the status of the cabinet door, andoutputs the dry contact output signals that do not have polarity.
Figure 2-8 shows the appearance of the door status sensor.
Figure 2-8 Appearance of the door status sensor
F01S100Product Description 2 Product Structure
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
2-15
3 System Configuration
About This Chapter
This topic provides the number of subscribers supported by the F01S100 cabinet.
3.1 F01S100 cabinet Configured with the MA5610This topic provides the number of subscribers supported by the F01S100 cabinet when it isconfigured with the MA5610.
3.2 F01S100 cabinet Configured with the MA5616This topic provides the number of subscribers supported by the F01S100 cabinet when it isconfigured with the MA5616.
F01S100Product Description 3 System Configuration
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
3-1
3.1 F01S100 cabinet Configured with the MA5610This topic provides the number of subscribers supported by the F01S100 cabinet when it isconfigured with the MA5610.
Table 3-1 lists the number of subscribers supported by the F01S100 cabinet in differentconfigurations.
Table 3-1 Number of subscribers supported by the F01S100 cabinet in different configurations
Configuration Maximum Number ofSubscribers
One MA5610 (configured with four ASPB boards) 256 POTS
One MA5610 (configured with three EIUA boards +one ASPB board)
48 LAN + 64 POTS
One MA5610 (configured with two EIUA boards +two ASPB boards)
32 LAN + 128 POTS
One MA5610 (configured with one EIUA board +three ASPB boards)
16 LAN + 192 POTS
NOTE
l The ASPB board is the 64-channel narrowband service board that provides the POTS service.
l The EIUA board is the 16-channel Ethernet access board that provides the LAN service.
In Table 3-1, the number of subscribers is counted when the cabinet is configured with the device provided byHuawei. For details of the device, see the MA5610 Hardware Description.
3.2 F01S100 cabinet Configured with the MA5616This topic provides the number of subscribers supported by the F01S100 cabinet when it isconfigured with the MA5616.
Table 3-2 lists the number of subscribers supported by the F01S100 cabinet in differentconfigurations.
Table 3-2 Number of subscribers supported by the F01S100 cabinet in different configurations
Configuration Maximum Number ofSubscribers
One MA5616 (configured with four ASPB boards) 256 POTS
One MA5616 (configured with four ADLE boards) 128 ADSL2+
One MA5616 (configured with one ASPB board +three ADLE boards)
64 POTS + 96 ADSL2+
3 System ConfigurationF01S100
Product Description
3-2 Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
Configuration Maximum Number ofSubscribers
One MA5616 (configured with four VDSE/VDSH/VDTH boards)
96 VDSL2
One MA5616 (configured with two ASPB boards +two VDSE/VDSH boards)
128 POTS + 48 VDSL2
NOTE
l The ASPB board is the 64-channel narrowband service board that provides the POTS service.
l The ADLE board is the 32-channel ADSL2+ service board with a built-in splitter. It provides the ADSL2+services.
l The VDSE board is the 24-channel VDSL2 service board with a built-in splitter. It provides the VDSL2service.
l The VDSH board is the 24-channel VDSL2 service board without a built-in splitter. It provides the VDSL2service.
l The VDTH board is the 24-channel VDSL2 service board without a built-in splitter. It provides the VDSL2service.
l The VDGE board is the 16-channel VDSL2 service board with a built-in splitter. It provides the VDSL2service.
In Table 3-2, the number of subscribers is counted when the cabinet is configured with the device provided byHuawei. For details of the device, see the MA5616 Hardware Description.
F01S100Product Description 3 System Configuration
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
3-3
4 System Parameters
This topic provides the parameters of the F01S100 cabinet.
Table 4-1 lists the dimensions of the F01S100 cabinet.
Table 4-1 Dimensions of the F01S100 cabinet
Item Dimensions (W x D x H)
F01S100 cabinet (without battery compartment) 720 mm x 250 mm x 830 mm
F01S100 cabinet (with battery compartment) 720 mm x 250 mm x 1030 mm
Table 4-2 lists the weight of the F01S100 cabinet.
Table 4-2 Weight of the F01S100 cabinet
Item Weight
F01S100 cabinet (without battery compartment, fully-loaded)
57 kg
F01S100 cabinet (fully-loaded, with batterycompartment, fully-loaded)
84 kg
Table 4-3 lists the power of the F01S100 cabinet.
Table 4-3 Power of the F01S100 cabinet
Item Value
Maximum power of the F01S100 cabinet (configured with the AC-poweredMA5610/MA5616)
187.6 W
Maximum power of the F01S100 cabinet (configured with the DC-poweredMA5610/MA5616)
250 W
F01S100Product Description 4 System Parameters
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
4-1
5 Environmental Specifications
This topic describes the environmental specifications for the storage, transportation, and runningof the cabinet.
Table 5-1 lists the environment specifications for the storage, transportation, and running of theF01S100 cabinet.
Table 5-1 Environment specifications of the F01S100 cabinet
Environment Item Value
Storage Solar radiation intensity ≤1120 W/m2
Temperature –45°C to +45°C
Relative humidity 8% to 100%
Air pressure 70 kPa to 106 kPa
Transportation Solar radiation intensity ≤1120 W/m2
Temperature –40°C to +70°C
Relative humidity (without muchvariation in temperature)
95% (+45°C)
Relative humidity (with much variation intemperature: air/air)
95% (-40°C to +30°C)
Air pressure ≥ 70 kPa
Running Solar radiation intensity ≤1120 W/m2
Temperature (when the F01S100 cabinetis configured with one MA5610/MA5616,without the enhanced heat dissipationmodule and )
–33°C to +45°C
Temperature (when the F01S100 cabinetis configured with one MA5610/MA5616,with the enhanced heat dissipation moduleand )
–33°C to +50°C
F01S100Product Description 5 Environmental Specifications
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
5-1
Environment Item Value
Relative humidity 8% to 100%
Air pressure 70 kPa to 106 kPa
5 Environmental SpecificationsF01S100
Product Description
5-2 Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
6 Standards Compliance
This topic provides the standards that the F01S100 cabinet complies with in terms of theenvironment, structure, power system and lightning proof.
Table 6-1 provides the standards compliance of the F01S100 cabinet.
Table 6-1 Standards compliance of the F01S100 cabinet
Item Standards Compliance Class
Running environment ETSI EN 300 019-1-4:Environmental conditionsand environmental test fortelecommunicationsequipment; Part 1-4:Classification ofenvironmental conditions;Stationary use at non-weather protected locations
Class 4.1E Non-weatherprotected locations-extended
Transportation environment ETSI 300 019 – 1 - 2:Environmental conditionsand environmental test fortelecommunicationsequipment; Part 1-2:Classification ofenvironmental conditions;Transportation
Class 2.2 Publictransportation
Storage environment ETSI EN 300 019–1–1 Class 1.3E
Safety IEC 60950–1/ IEC 60065:Safety of information oftechnology equipment
Necessary
Protection IEC 60950-22: Degrees ofprotection provided byenclosures (IP code)
IP55
Noise ETSI EN 300 753 1997-10 Class 4.1 Rural
F01S100Product Description 6 Standards Compliance
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
6-1
Structure IEC 297_1 (2,3): Cabinetsand Pitches of racks structure
-
MDF K.45: Resistibility oftelecommunicationequipment installed in theaccess and trunk networks toovervoltage and overcurrent
-
YD 694-2004 -
Lightning proof ITU-T K.45: Performancerequirement for surgeprotective device connectedto low-voltage distributionsystems oftelecommunication stations/sites
Necessary
Grounding ETSI EN 300 253: Earthingand bonding oftelecommunicationequipment intelecommunication centers
Necessary
6 Standards ComplianceF01S100
Product Description
6-2 Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
Issue 01 (2009-10-28)
7 Acronyms and Abbreviations
A
AC Alternating current
ADSL Asymmetrical digital subscriber line
ADSL2+ Asymmetrical digital subscriber line 2 plus
D
DC Direct current
E
EMC Electro magnetic compatibility
EMU Environment monitoring unit
EN End node
ETS European Telecommunication Standard
ETSI European Telecommunications Standards Institute
F
FE Fast Ethernet
G
GE Gigabit Ethernet
I
IDC Internet data center
F01S100Product Description 7 Acronyms and Abbreviations
Issue 01 (2009-10-28) Huawei Proprietary and ConfidentialCopyright © Huawei Technologies Co., Ltd.
7-1
IEC International Electrotechnical Commission
IEEE Institute of Electrical and Electronics Engineers
IP Internet protocol
ITU-T International Telecommunication Union - TelecommunicationStandardization Sector
L
LAN Local area network
M
MDF Main distribution frame
O
ODF Optical distribution frame
P
POTS Plain old telephone service
PSTN Public switched telephone network
V
VDSL Very high speed digital subscriber line
VDSL2 Very high speed digital subscriber line 2
7 Acronyms and AbbreviationsF01S100