1. PCDS Introduction 2

2. Product Code Instruction 3

2.1. PGDS: Power Generatrix Distribution System 3

2.2. PCSM: Power Controlling System Module 3

2.3. PDUM: Power Distribution Unit Module 4

3. Input Style 4

4. PCSM Introduction 5

4.1. No PCSM 5

4.2. Master Circuit Breaker Module 5

4.3. NPM Module Introduction 6

4.4. CPDU Module Introduction 7

4.5. Digital AC Amperemeter Module Introduction 8

5. PDUM Introduction 8

6. Installation Chart 11

7. Wire Terminal Connection Box Chart 11

8. Main Specifications Introduction 12

POWER CONTROLLING DISTRIBUTION SYSTEM

PC

DS

CATALOGUE

1

PGDS

PCDS - Power Controlling Distribution System

PCSM

PDUM PDUM

All Clever s PCDS products are manufactured by environmental protection materials and components, accord with the regulations of European Union RoHS directive, and we had passed test of .

,

S SG

All rights reserved. Contents are subject to change without prior notice. The pictures are for indication only, subject to the final product.

Page 3: PCDS Lehmann_sz

2

PCDSPCDS

Power Controlling Distribution System, PCDS for short, was designed and developed by Clever

company in 2001.

PCDS is formed by Power Generatrix Distribution System (PGDS), Power Controlling System

Module (PCSM) and Power Distribution Unit Module (PDUM).

PCDS Characteristics

1. PGDS general wiring, the max load can reach 3 32A;

2. PCSM has master air circuit breaker function, can automatically alarm when overload,

CPDU (Computer Monitor Power Distribute Unit) and NPM (Network Power Manager)

function, etc.

3. PDUM has different standard sockets all over the world;

4. PCDS can change and add the PDUM in uninterrupted operation;

5. PCDS can be matched with different PCSM and PDUM according to customers'

different technical requirement;

6. Each PCDS can be configured 6 group PDUM at most according to customers'

technical requirement;

7. Power input connecting terminal box is convenient for customers to mount and debug

on job site;

8. PCDS is vertically mounted in cabinet and the mounting method is very easy, which

can save space to the utmost extent.

1. PCDS Introduction

Page 4: PCDS Lehmann_sz

2. Product Code Instruction

POWER CONTROLLING DISTRIBUTION SYSTEM

3

PC A 1 2 A 2 A 2 0 B

PG A 1 2 B 2 A 0 6 W

2.1. PGDS: Power Generatrix Distribution System

2.2. PCSM: Power Controlling System Module

Code:

Code:

case color (B: black)

output (0: multi-type)

controlling function (2: circuit breaker & CPDU)

output current (A: 32A)

output voltage (2: 220V)

input current (A: 32A)

input voltage (2: 220V)

input method (1: single input)

output standard (A: standard configuration)

module type (PC: power controlling system module)

case color (W: white)

output quantity (6: 6 groups PDUM)

controlling function (0: no PCSM)

output current (A: 16A)

output voltage (2: 220V)

input current (B: 32A)

input voltage (2: 220V)

input method (1: w )ire terminal connection box input

output standard (A: standard configuration)

module type (PG: power generatrix distribution system )

PC

DS

Page 5: PCDS Lehmann_sz

2.3. PDUM: Power Distribution Unit Module

3. Input Style

4

PCDSPCDS

PD A 1 2 A 2 A 2 5 B

Code:

Single input Double input Wire terminal connection box input

case color (B: black)

output quantity (5: 5 output units)

controlling function (2: fuse & indicator)

output current (A: 16A)

output voltage (2: 220V)

input current (A: 16A)

input voltage (2: 220V)

input method (1: single input)

output standard (A: IEC320 C13)

module type (PD: power controlling system module)

Page 6: PCDS Lehmann_sz

4. PCSM Introduction

5

POWER CONTROLLING DISTRIBUTION SYSTEM

4.1. No PCSM

No PCSM

No PCSM

No PCSM

4.2. Master Circuit Breaker Module

Master Circuit Breaker Module

PC

DS

Page 7: PCDS Lehmann_sz

6

PCDSPCDS

Network Power Manager (NPM) which is developed and produced by Clever, is the world-advance new generation

network managing power distribution and monitoring device.

The governor can monitor, control and manage many pieces of equipments through LAN or WAN in the cabinet of

data room located all over the world.

4.3. NPM Module Introduction

Monitoring Function

The total load current;

The operating state of NPM system;

The state of temperature/humidity;

The state of smog or water logging;

The state of cabinet door.

Alarming Function

1. User-defined alarm

The Min/Max limiting value of total load current;

The Min/Max limiting value of temperature /humidity.

2. System default alarm

The total load current exceeds rating value;

System goes wrong;

Smog;

Water-logging;

Door opening.

3. Alarming method

The indicator of NPM controlling panel flashes and

the buzzer alarms.

The indicator on the Web interface flashes and the

buzzer alarms.

Automatically send E-mail to system administrator.

SNMP sends alarm information.

Daisy-chain Function

Support NPM daisy-chain and daisy-chain 10pcs NPM at

most by radial link method.

Log Record

Record and save the operation information of NPM, provide

the query and output of records.

User Management

Setting the user rights.

Accessing method

Web, access through IE;

SNMP (V1/V2C/V3), access to control through standard

network working station;

Telnet, SSH, access to control through command

controlling station.

System Support

Multi-user operation system, support software upgrade.

NPM Controlling Module

Page 8: PCDS Lehmann_sz

POWER CONTROLLING DISTRIBUTION SYSTEM

7

Main Functions

1. Through PC, timely monitors the total load current

of PCDS by visiting the hyper terminal.

2. Timely displays the total load current of PCDS

through The digital alternating current ammeter.

3. Timely monitor the load current of 32 pcs CPDU

at most.

4. Rating voltage: 125/250VAC 50/60HZ; Rating load

current: 16A, 32A.

Monitoring Methods

1. The governor can monitor the total load current of

the PCDS through the digital alternating current

ammeter on CPDU panel.

2. The governor can monitor the load current of PCDS

on the PC's interface through the hyper terminal.

4.4. CPDU Module Introduction

Computer Monitored Power Distribution Unit - CPDU

CPDU module is a kind of PCSM (Power Controlling System Module) which can timely monitor the total load current

of the PCDS through PC's hyper terminal when the PC (or other equipments with serial port) is connected with RJ45

port based on the telecom technology of the computer's serial port.

Circuit Breaker+CPDU Controlling Module

Contents Be Monitored And Displayed

1. Address code (can be set by the governor)

2. Load current value (display the timely load current)

3. State of the load current (Normal or Abnormal)

4. Date (can be modified)

5. Time (can be modified)

6. The overload alarm value (can be modified)

Connection

1. CPDU can be connected to PC with RS-232 or

RS485 serial port.

2. When the load current of several CPDU is to be

monitored through a PC at the same time, a hub

can be applied.

3. Please refer to the above connecting method

when CPDU is connected with other equipments

with serial port.

PC

DS

Page 9: PCDS Lehmann_sz

PDA12A2A25B PDC12A2A24B PDB12A2A23W

5. PDUM Introduction

8

PCDSPCDS

4.5. Digital AC Amperemeter Module Introduction

Circuit Breaker+Digital AC Amperemeter Controlling Module

AC 16A/32AMax. Input

Full measurement

Accuracy

Resolution

Frequency range

Digit display

Display

Overload alarm

Power supply

AC 16A/32A

1.0%+1Digit

100mA (<10A)

50/60Hz

2

Red LED

125/250VAC

AC 3 16/32A

AC 16A/32A

alarm, LED flashesL1, L2 and L3 light

alarm, LED flashes

3-Phase Electricity

Performance index MB3306A MB3307A

Page 10: PCDS Lehmann_sz

POWER CONTROLLING DISTRIBUTION SYSTEM

9

PC

DS

PDF11A1A15W PDL12A2A24B

PDM12A2A24B PDH12A2A24B PDI12A2A24B

PDG11A1A25W

Page 11: PCDS Lehmann_sz

10

PCDSPCDS

PDJ12A2A24B PDD12A2A14BPDE12A2A24B

PDN12A2A23B PDK12A2A23B PDB12A2A23W

Page 12: PCDS Lehmann_sz

7. Wire Terminal Connection Box Chart

POWER CONTROLLING DISTRIBUTION SYSTEM

11

6. Installation Chart

1 2 3 4

PC

DS

Page 13: PCDS Lehmann_sz

12

PCDSPCDS

8. Main Specifications Introduction

Page 14: PCDS Lehmann_sz

13

POWER CONTROLLING DISTRIBUTION SYSTEM

PC