Upload
rika-juwita-manurung
View
248
Download
0
Embed Size (px)
Citation preview
7/27/2019 hrc fuse.pdf
1/44
FusegearDIN-type HRC-fuse links, 2...1600 AgG- and aM- types
Low Voltage Switches
7/27/2019 hrc fuse.pdf
2/44
. . . . . . . . . . . . . . . . . . . . . . .
000aM
63A
OFAA
1
1
00aM
100A
OFAA
1 1a
M
250A
OFAA
2aM
400A
OFAA
OFAA
3aM
500A
4aM
800A
OFAA
0aM
160A
OFAF
1
. . . . . . . . . . . . . . . . . . . . . . .
00gG
160A
OFAF
1
1
0gG
160A
OFAF
1
1gG
315A
OFAF
1 2
gG
315A
OFAA
3gG
400A
OFAA 4gG
800A
OFAA
1
000 00 0 1 2 3 4
2...100 125...160 6...250 16...355 25...500 250...800 400...1250
2...63 80...125 6...200 16...250 32...500 250...500 500...1250
2...125 16...250 160...400 315...630
DIN-size
OFAF_H_ / ln[A] / 500 V
OFAA_GG_ / ln[A] / 690 V
OFAA_H__/ ln[A] / 690 V
DIN-type HRC fuse links, gGOFAF_H_, OFAA_GG_ and OFAA_H_
HRC-fuse links gG2...1600 A
DIN-size
OFAF_AM_ / ln[A] / 500 V
OFAM_AM / ln[A] / 690 V
OFAA_AM_ / ln[A] / 690 V
000 00 0 1 2 3 4
2...160 80...160 6...200 16...315 35...500 250...800 400...1250
2...160 50...250 125...400 315...800
2...63 80...160 50...250 125...400 315...500 500...1000
DIN-type HRC fuse links aMOFAF_AM_, OFAM_AM_ and OFAA_AM_
7/27/2019 hrc fuse.pdf
3/44
3
1SCC317001C0201
HRC-fuse links gG, aM
OFAF_
OFAA_
OFAM_
. . . . . . . .
. . . . . . . .
OFAA
4a/aM
1000A
Contents:
Features .............................................................................................................................. 4-5
Technical data ...........................................................................................................................6
Ordering information
gG-types, for overload and short circuit protection
500 V, gG, universal fuses OFAF_H_ .................................................................... 7-8690 V, gG, universal fuses OFAA_GG_ ............................................................... 9-10
690 V, gG, universal fuses OFAA_H_ ......................................................................11
690 V, gG, for demanding industrial evironment OFAA_H_-H20 ............................12
aM-types, for short circuit protection in motor circuits
500 V, aM, OFAF_AM_ ...................................................................................... 13-14
690 V, aM, OFAM_AM_ ...........................................................................................15
690 V, aM, OFAA_AM_ ............................................................................................16
690 V, aM, for demanding industrial evironment OFAM_AM_-H20 ........................17
Accessories .....................................................................................................................18
Time-current characteristicsgG-types
500 V, gG, OFAF_H_ ...............................................................................................19
690 V, gG, OFAA_GG_ ............................................................................................20
690 V, gG, OFAA_H_, OFAA_H_-H20 .....................................................................21
aM-types
500 V, aM, OFAF_AM_ ............................................................................................22690 V, aM, OFAM_AM_, OFAM_AM_-H20 ..............................................................23
690 V, aM, OFAA_AM_ ............................................................................................24
Cut-off current characteristics
gG-types
500 V, gG, OFAF_H_ ...............................................................................................25
690 V, gG, OFAA_GG_ ...................................................................................... 26-27
690 V, gG, OFAA_H_, OFAA_H_-H20 .....................................................................28
aM-types
500 V, aM, OFAF_AM_ ............................................................................................29
690 V, aM, OFAM_AM_, OFAM_AM_-H20 ..............................................................30
690 V, aM, OFAA_AM_............................................................................................31
I2t characteristicsgG-types
500 V, gG, OFAF_H_ ...............................................................................................32
690 V, gG, OFAA_GG_ ............................................................................................33690 V, gG, OFAA_H_, OFAA_H_-H20 .....................................................................34
aM-types
500 V, aM, OFAF_AM_ ............................................................................................35
690 V, aM, OFAM_AM_, OFAM_AM_-H20 ..............................................................36
690 V, aM, OFAA_AM_............................................................................................37
Dimension drawings......................................................................................................... 38-39
Fuse monitor, connecting digram ........................................................................................39
Index .......................................................................................................................... 40-43
OFAA
4a/gG
1000A
OFAA 5/gG 1600A
4a 5
500...1250
500...1250 1000...1600
and aM
4a
500...1250
500... 1000
7/27/2019 hrc fuse.pdf
4/44
4
1SCC317001C0201
Fuse links - Safety,reliability and economy
Dual indication of blown fuse
ABBs gG fuse links have proven themselves to be suitable for a number of applications,
from over-current and short-circuit protection of lines to short-circuit protection of
semiconductor and other equipment as well as protection of DC circuits. For motor
protection, we recommend to use aM fuse links. The aM fuse links give economical and
reliable protection. ABB fuse links for demanding industrial environments are available to
be used in the protection of general as well as motor applications.
The fuse links limit the unlimited prospective short circuit
current to cut-off current. When the low operating energy
and cut-off current given in this brochure are used, cables
and equipment can be specied without over-dimensioning.For example in the range of low short circuit, the low peak
let-through energy protects the overload relay from burning,
while during a short circuit the extremely fast operating
fuse link protects the contactor contacts from welding and
reduces the short-circuit forces in lines and equipment.
The optional electronic fuse monitor enhances theprotection and control of the circuitry. The fuse monitor
provides status indications and control impulses in case
of operated fuse link. The fuse helps protect three-phase
motors for single-phase operation.
000aM
100A
OFAF
DIN-type HRC-fuse link range
2...1600 A, 500 V and 690 V
1aM
315
A
OFAF
OFAA
4a/gG
1000A 000gG
100A
OFAF
1gG
315A
OFAF
1gG
315
A
OFAF
Superior current limiting capability
The dual indicating DIN-type fuse links incorporate the top
and center indication system and are available for most
common sizes up to 630 A. The center indicator and the wide
windows on the front cover of ABB switch fuses enhance theservice speed and safety level.
7/27/2019 hrc fuse.pdf
5/44
5
1SCC317001C0201
New fuse links
The DIN 0 size fuse links for current range 6...250 A The DIN 5 size fuse links up to 1600 A
0gG
160A
OFAA
OFAA
5/gG 1250A
OFAA 5/gG 1600A
Reliable protection
Discrimination
The perfect t for the OS-switch fuses and fuse monitors
minimize the need for space in the switchboard.
The DIN 0 size fuse link saves space together with the
OS-switch fuse.
The new size 5 fuse links are developed to widen the
0aM
160A
OFAF
0gG
6A
OFAA
Discrimination, (i.e. selectivity), is one of the most important
features of the fuse links contributing to the reliability and
availability of an electrical network. In case of a fault, only the
affected part of the network is isolated. At the same time, the
system is able to allow normal currents in the rest of the network
ABB fuse links are, in most cases, selective for consecutive
fuses in the ratio of 1:1.6. In some cases the same range of
ABB fuses are selective with a ratio up to 1:1.25.
ABB fuse links guarantee maximum protection against all
faults. The higher the voltage, the better the protection
that can be achieved with the fuse link. The fused system
provides, according to IEC 60947-4-1, type 2 coordination
class up to 690 V, in which the equipment needs to be
operational even after a short circuit. The fast operation
contributes to economical protection for semiconductors.
The oversize fuse links allow exibility in the short-circuit
protection of distribution and motor circuits, which enables
the optimal use of fuse switches.
scope of main switch and motor protection switch
fuses. Use the switch fuse size OS1250 and size 5 fuse
links to achieve a motor rating of 1000 kW by 690 V .
7/27/2019 hrc fuse.pdf
6/44
6
1SCC317001C0201
HRC Fuse links, DIN-type
Technical data
Applications:
gG- fuse links for general installation and industrial applications
500 V / 690 V, OFAF_H_ / OFAA_GG_
- Low power loss- Dual indication up to 630 A
690 V, OFAA_H_ ja OFAA_H_-H20
- for industrial applications, see coordination tables:www.abb.com/Low Voltage products/Software tools/Coordination tables for motor protection
- H20 -types for demanding industrial applications, silver coating 20m
aM-fuse links for motor protection
500 V / 690 V, OFAF_AM_ / OFAA_AM_
- Low power loss
- Dual indication up to 630 A
690 V, OFAM_AM_
- Optimum dimensioning 400 V...690 V for motor protection in industrial applications, see coordination tables:www.abb.com/Low Voltage products/Software tools/Coordination tables for motor protection
- H20 -types for demanding industrial applications, silver coating 20m
Standards:
EN/IEC 60269-1-2, DIN
VDE 0636, DIN 43620 SFS 6000-8-801 (801.473.2) /2000
SFS 6000-801/2007
Approvals:
Lloyds Register of Shipping
DNV
BV
RoHs certicate:
All fuse links are environment friendly and fulll the requirements by RoHs.
Technical data according to EN/IEC 60269The fuse links are tested to the following short circuit ratings:
Size 000 00 0 1 2 3 4
Max. current rating, AC 500 V A 100 160 250 355 500 800 1250
690 V A 80 125 160 250 355 500 1000
Max. current rating, DC, 250 V A 100 160 500 800
time constant
7/27/2019 hrc fuse.pdf
7/44
7
HRC Fuse links, DIN-type, gG
Ordering information
1SCC317001C0201
00gG
160A
OFAF
0gG
160A
OFAF
1gG
315A
OFAF
HRC fuse links, gG, universal fuses OFAF_H_, 500 VThe type code includes one fuse link, the delivery batch is according to the column.Dual indication.
IEC- Rated Power loss Type Order number Delivery- Weight/size current batch unit
In
[A] Ph
[W] [pcs] [kg]
000 2 3.9 OFAF000H2 1SCA022627R0230 9 0.124 1.5 OFAF000H4 1SCA022627R0310 9 0.126 1.6 OFAF000H6 1SCA022627R0400 9 0.1210 1.1 OFAF000H10 1SCA022627R0580 9 0.1216 1.8 OFAF000H16 1SCA022627R0660 9 0.1220 2.4 OFAF000H20 1SCA022627R0740 9 0.1225 2.4 OFAF000H25 1SCA022627R0820 9 0.1232 2.7 OFAF000H32 1SCA022627R0910 9 0.1235 3.0 OFAF000H35 1SCA022627R1040 9 0.1240 3.4 OFAF000H40 1SCA022627R1120 9 0.1250 3.9 OFAF000H50 1SCA022627R1210 9 0.1263 4.7 OFAF000H63 1SCA022627R1390 9 0.1280 5.7 OFAF000H80 1SCA022627R1470 9 0.12100 6.7 OFAF000H100 1SCA022627R1550 9 0.12
00 125 8.4 OFAF00H125 1SCA022627R1630 3 0.18160 10.6 OFAF00H160 1SCA022627R1710 3 0.18
0 6 1.8 OFAF0H6 1SCA022627R1800 3 0.2110 1.5 OFAF0H10 1SCA022627R1980 3 0.2116 2.5 OFAF0H16 1SCA022627R2010 3 0.2120 3.5 OFAF0H20 1SCA022627R2100 3 0.2125 3.5 OFAF0H25 1SCA022627R2280 3 0.2132 3.2 OFAF0H32 1SCA022627R2360 3 0.2135 3.5 OFAF0H35 1SCA022627R2440 3 0.2140 4.2 OFAF0H40 1SCA022627R2520 3 0.2150 5.1 OFAF0H50 1SCA022627R2610 3 0.2163 6.2 OFAF0H63 1SCA022627R2790 3 0.2180 7.1 OFAF0H80 1SCA022627R2870 3 0.21100 8.7 OFAF0H100 1SCA022627R2950 3 0.21125 11.0 OFAF0H125 1SCA022627R3090 3 0.21160 11.7 OFAF0H160 1SCA022627R3170 3 0.21200 15.0 OFAF0H200 1SCA022629R5140 3 0.30224 16.2 OFAF0H224 1SCA022629R5220 3 0.30250 17.8 OFAF0H250 1SCA022629R5310 3 0.30
1 16 2.5 OFAF1H16 1SCA022627R3250 3 0.2820 3.5 OFAF1H20 1SCA022627R3330 3 0.2825 3.3 OFAF1H25 1SCA022627R3410 3 0.2832 3.2 OFAF1H32 1SCA022627R3500 3 0.2835 3.5 OFAF1H35 1SCA022627R3680 3 0.2840 4.2 OFAF1H40 1SCA022627R3760 3 0.2850 5.1 OFAF1H50 1SCA022627R3840 3 0.2863 6.2 OFAF1H63 1SCA022627R3920 3 0.2880 7.1 OFAF1H80 1SCA022627R4060 3 0.28100 8.7 OFAF1H100 1SCA022627R4140 3 0.28125 11.0 OFAF1H125 1SCA022627R4220 3 0.40160 11.7 OFAF1H160 1SCA022627R4310 3 0.40200 14.5 OFAF1H200 1SCA022627R4490 3 0.40224 15.9 OFAF1H224 1SCA022627R4570 3 0.40250 19.7 OFAF1H250 1SCA022627R4650 3 0.40
315 26.0 OFAF1H315 1SCA022627R4730 3 0.40355 26.4 OFAF1H355 1SCA022701R4520 3 0.40
OFAF000H_
S01350A
OFAF0H_
S01352A
OFAF1H_
S01353A
OFAF00H_
S01351A
7/27/2019 hrc fuse.pdf
8/44
8
HRC Fuse links, DIN-type, gG
Ordering information
1SCC317001C0201
OFAF
3gG
630A
4gG
1250A
OFAF
OFAF
4a/gG
1250A
2gG
400A
OFAF
HRC fuse links, gG, universal fuses OFAF_H_, 500VThe type code includes one fuse link, the delivery batch is according to the column.Dual indication on fuse link sizes 2 and 3 up to 630 A.
IEC- Rated Power loss Type Order number Delivery- Weight/size current batch unit
In
[A] Ph
[W] [pcs] [kg]
2 25 3.3 OFAF2H25 1SCA115948R1001 3 0.4235 3.5 OFAF2H35 1SCA022627R4810 3 0.4240 5.1 OFAF2H40 1SCA022627R4900 3 0.4250 6.0 OFAF2H50 1SCA022627R5030 3 0.4263 7.1 OFAF2H63 1SCA022627R5110 3 0.4280 8.6 OFAF2H80 1SCA022627R5200 3 0.42100 10.6 OFAF2H100 1SCA022627R5380 3 0.42125 11.9 OFAF2H125 1SCA022627R5460 3 0.42160 14.0 OFAF2H160 1SCA022627R5540 3 0.42200 15.4 OFAF2H200 1SCA022627R5620 3 0.42224 19.1 OFAF2H224 1SCA022627R5710 3 0.42250 22.5 OFAF2H250 1SCA022627R5890 3 0.42300 24.0 OFAF2H300 1SCA022627R5970 3 0.63315 26.2 OFAF2H315 1SCA022627R6010 3 0.63
355 27.5 OFAF2H355 1SCA022627R6190 3 0.63400 30.2 OFAF2H400 1SCA022627R6270 3 0.63425 33.0 OFAF2H425 1SCA022706R3900 3 0.63500 44.0 OFAF2H500 1SCA022701R4610 3 0.63
3 250 17.9 OFAF3H250 1SCA022627R6350 1 0.63300 20.0 OFAF3H300 1SCA022627R6430 1 0.63315 22.4 OFAF3H315 1SCA022627R6510 1 0.63355 23.5 OFAF3H355 1SCA022627R6600 1 0.63400 30.1 OFAF3H400 1SCA022627R6780 1 0.63425 33.0 OFAF3H425 1SCA022627R6860 1 1.00450 36.0 OFAF3H450 1SCA022627R6940 1 1.00500 44.0 OFAF3H500 1SCA022627R7080 1 1.00630 47.5 OFAF3H630 1SCA022627R7160 1 1.00800 56.9 OFAF3H800 1SCA022627R7240 1 0.90
4 400 31.0 OFAF4H400 1SCA022627R7320 1 2.00500 35.0 OFAF4H500 1SCA022627R7410 1 2.00630 44.0 OFAF4H630 1SCA022627R7590 1 2.00800 70.0 OFAF4H800 1SCA022627R7670 1 2.001000 85.0 OFAF4H1000 1SCA022627R7750 1 2.001250 93.0 OFAF4H1250 1SCA022627R7830 1 2.00
4a 500 33.0 OFAF4AH500 1SCA022637R3980 1 2.00630 43.0 OFAF4AH630 1SCA022637R4010 1 2.00800 58.0 OFAF4AH800 1SCA022637R4100 1 2.001000 71.0 OFAF4AH1000 1SCA022637R4280 1 2.001250 85.0 OFAF4AH1250 1SCA022637R4360 1 2.00
5 12501) 78 OFAA5GG1250 1SCA112680R1001 1 3.2016001) 111 OFAA5GG1600 1SCA112681R1001 1 4.20
OFAF2H_
S01354A
OFAF4H_
S01362A
OFAF4AH_
S01356A
OFAF3H_
S013
55A
OFAA5GG1250
OFAA5GG1600
S04110
OFAA
5/gG 1250A
OFAA 5/gG 1600A
S04112
1) Un
690 V
7/27/2019 hrc fuse.pdf
9/44
9
HRC Fuse links, DIN-type, gG
Ordering information
1SCC317001C0201
000gG
63A
OFAA
00gG
100A
OFAA
0gG
160A
OFAA
1gG
200A
OFAA
HRC fuse links, gG, universal fuses OFAA_GG_, 690VThe type code includes one fuse link, the delivery batch is according to the column.Dual indication.
IEC- Rated Power loss Type Order number Delivery- Weight/size current batch unit
In
[A] Ph
[W] [pcs] [kg]
000 2 3.9 OFAA000GG2 1SCA022661R8250 9 0.124 1.5 OFAA000GG4 1SCA022661R8330 9 0.126 1.6 OFAA000GG6 1SCA022661R8410 9 0.1210 1.1 OFAA000GG10 1SCA022661R8500 9 0.1216 1.8 OFAA000GG16 1SCA022661R8680 9 0.1220 2.4 OFAA000GG20 1SCA022661R8760 9 0.1225 2.4 OFAA000GG25 1SCA022661R8840 9 0.1232 2.7 OFAA000GG32 1SCA022661R8920 9 0.1235 3.0 OFAA000GG35 1SCA022661R9060 9 0.1240 3.4 OFAA000GG40 1SCA022661R9140 9 0.1250 3.9 OFAA000GG50 1SCA022661R9220 9 0.1263 4.7 OFAA000GG63 1SCA022661R9310 9 0.12
00 80 5.7 OFAA00GG80 1SCA022700R9440 3 0.18
100 6.7 OFAA00GG100 1SCA022700R9520 3 0.18125 8.4 OFAA00GG125 1SCA022724R0610 3 0.18
0 6 1.8 OFAA0GG6 1SCA022703R1290 3 0.2110 1.5 OFAA0GG10 1SCA022703R1370 3 0.2116 2.5 OFAA0GG16 1SCA022703R1450 3 0.2120 3.5 OFAA0GG20 1SCA022703R1530 3 0.2125 3.5 OFAA0GG25 1SCA022703R1610 3 0.2132 3.2 OFAA0GG32 1SCA022703R1700 3 0.2135 3.5 OFAA0GG35 1SCA022703R1880 3 0.2140 4.2 OFAA0GG40 1SCA022703R1960 3 0.2150 5.1 OFAA0GG50 1SCA022703R2000 3 0.2163 6.2 OFAA0GG63 1SCA022703R2180 3 0.2180 7.1 OFAA0GG80 1SCA022703R2260 3 0.21100 8.7 OFAA0GG100 1SCA022703R2340 3 0.21125 11.0 OFAA0GG125 1SCA022703R2420 3 0.21160 11.7 OFAA0GG160 1SCA022703R2510 3 0.21
1 16 2.5 OFAA1GG16 1SCA022703R2690 3 0.28
20 3.5 OFAA1GG20 1SCA022703R2770 3 0.2825 3.3 OFAA1GG25 1SCA022703R2850 3 0.2832 3.2 OFAA1GG32 1SCA022703R2930 3 0.2835 3.5 OFAA1GG35 1SCA022703R3070 3 0.2840 4.2 OFAA1GG40 1SCA022703R3150 3 0.2850 5.1 OFAA1GG50 1SCA022700R9610 3 0.2863 6.2 OFAA1GG63 1SCA022700R9790 3 0.2880 7.1 OFAA1GG80 1SCA022700R9870 3 0.28100 8.7 OFAA1GG100 1SCA022700R9950 3 0.28125 11.0 OFAA1GG125 1SCA022701R0020 3 0.40160 11.7 OFAA1GG160 1SCA022701R0110 3 0.40200 14.5 OFAA1GG200 1SCA022701R0290 3 0.40250 17.8 OFAA1GG250 1SCA022701R0370 3 0.40
OFAA000GG_
S01572A
OFAA0GG_
S01568A
OFAA1GG_
S01569A
OFAA00GG_
S01567A
7/27/2019 hrc fuse.pdf
10/44
10
HRC Fuse links, DIN-type, gG
Ordering information
1SCC317001C0201
2gG
315A
OFAA
3gG
400A
OFAA
4gG
800A
OFAA
OFAA
4a/gG
1000A
HRC fuse links, gG, universal fuses OFAA_GG_, 690VThe type code includes one fuse link, the delivery batch is according to the column.Dual indication on fuse link sizes 2 and 3.
IEC- Rated Power loss Type Order number Delivery- Weight/size current batch unit
In
[A] Ph
[W] [pcs] [kg]
2 32 3.2 OFAA2GG32 1SCA022703R3230 3 0.4235 3.5 OFAA2GG35 1SCA022703R3310 3 0.4240 5.1 OFAA2GG40 1SCA022703R3400 3 0.4250 6.0 OFAA2GG50 1SCA022703R3580 3 0.4263 7.1 OFAA2GG63 1SCA022703R3660 3 0.4280 8.6 OFAA2GG80 1SCA022703R3740 3 0.42100 10.6 OFAA2GG100 1SCA022703R3820 3 0.42125 11.9 OFAA2GG125 1SCA022701R0450 3 0.42160 14.0 OFAA2GG160 1SCA022701R0530 3 0.42200 15.4 OFAA2GG200 1SCA022701R0610 3 0.42224 19.1 OFAA2GG224 1SCA022703R3910 3 0.42250 22.5 OFAA2GG250 1SCA022701R0700 3 0.42300 24.0 OFAA2GG300 1SCA022703R4040 3 0.63315 26.2 OFAA2GG315 1SCA022701R0880 3 0.63
355 27.0 OFAA2GG355 1SCA022701R0960 3 0.63
3 250 17.9 OFAA3GG250 1SCA022703R4120 1 0.63300 21.0 OFAA3GG300 1SCA022703R4210 1 0.63315 22.4 OFAA3GG315 1SCA022701R1000 1 0.63355 23.5 OFAA3GG355 1SCA022701R1180 1 0.63400 30.1 OFAA3GG400 1SCA022701R1260 1 0.63425 33.0 OFAA3GG425 1SCA022706R4030 1 1.00500 44.0 OFAA3GG500 1SCA022701R1340 1 1.00
4 500 35.0 OFAA4GG500 1SCA022701R1420 1 2.00630 44.0 OFAA4GG630 1SCA022701R1510 1 2.00800 70.0 OFAA4GG800 1SCA022701R1690 1 2.001000 85.0 OFAA4GG1000 1SCA112679R1001 1 2.00
4a 500 33.0 OFAA4AGG500 1SCA022660R9770 1 2.00630 43.0 OFAA4AGG630 1SCA022660R9850 1 2.00800 58.0 OFAA4AGG800 1SCA022660R9930 1 2.001000 71.0 OFAA4AGG1000 1SCA022699R6360 1 2.00
5 1250 78 OFAA5GG1250 1SCA112680R1001 1 3.201600 111 OFAA5GG1600 1SCA112681R1001 1 4.20
OFAA2GG_
S01570A
OFAA4GG_
S01574A
OFAA4AGG_
S01571A
OFAA3GG_
S0
1573A
OFAA5GG1250
OFAA5GG1600
S04110
OFAA
5/gG 1250A
OFAA 5/gG 1600A
S04112
7/27/2019 hrc fuse.pdf
11/44
11
HRC Fuse links, DIN-type, gG
Ordering information
1SCC317001C0201
OFAA
00/gG
125A
OFAA
1/gG
250A
OFAA
2/gG
400A
OFAA
3/gG
630A
HRC fuse links, gG, universal fuses OFAA_H_, 690VThe type code includes one fuse link, the delivery batch is according to the column.Indication on the top of fuse link.
IEC- Rated Rated Power Type Order number Delivery- Weight/size current voltage loss batch unit
In
[A] Un[V] P
h[W] [pcs] [kg]
00 2 690 1.3 OFAA00H2 1SCA022041R3630 30 0.164 690 1.4 OFAA00H4 1SCA022028R5700 30 0.166 690 1.4 OFAA00H6 1SCA022007R3940 30 0.1610 690 2.7 OFAA00H10 1SCA022007R4080 30 0.1616 690 3 OFAA00H16 1SCA022007R4160 30 0.1620 690 3.2 OFAA00H20 1SCA022007R4240 30 0.1625 690 3.9 OFAA00H25 1SCA022007R4320 30 0.1632 690 4.5 OFAA00H32 1SCA022208R7050 30 0.1635 690 4.9 OFAA00H35 1SCA022007R4410 30 0.1640 690 5.3 OFAA00H40 1SCA022261R7200 30 0.1650 690 6.9 OFAA00H50 1SCA022007R4590 30 0.1663 690 8.6 OFAA00H63 1SCA022007R4670 30 0.1680 690 9.2 OFAA00H80 1SCA022007R4750 30 0.16100 690 9.6 OFAA00H100 1SCA022007R4830 30 0.16
125 500 10.6 OFAA00H125 1SCA022078R4290 30 0.16
1 16 690 1.9 OFAA1H16 1SCA022023R9510 3 0.4920 690 3.1 OFAA1H20 1SCA022023R9690 3 0.4925 690 3.9 OFAA1H25 1SCA022023R9770 3 0.4932 690 4.6 OFAA1H32 1SCA022197R1420 3 0.4935 690 5 OFAA1H35 1SCA022007R4910 3 0.4940 690 6.3 OFAA1H40 1SCA022197R1690 3 0.4950 690 7.1 OFAA1H50 1SCA022007R5050 3 0.4963 690 8.5 OFAA1H63 1SCA022007R5130 3 0.4980 690 9.4 OFAA1H80 1SCA022007R5210 3 0.49100 690 14 OFAA1H100 1SCA022007R5300 3 0.49125 690 19 OFAA1H125 1SCA022007R5480 3 0.49160 690 20 OFAA1H160 1SCA022007R5560 3 0.49200 690 22.5 OFAA1H200 1SCA022007R5640 3 0.49250 500 23 OFAA1H250 1SCA022007R5720 3 0.49
2 160 690 21 OFAA2H160 1SCA022007R5810 3 0.67200 690 23 OFAA2H200 1SCA022007R5990 3 0.67250 690 25.5 OFAA2H250 1SCA022007R6020 3 0.67315 690 31.5 OFAA2H315 1SCA022007R6110 3 0.67400 500 34 OFAA2H400 1SCA022007R6290 3 0.67
3 315 690 30.5 OFAA3H315 1SCA022007R6370 3 0.97400 690 41.5 OFAA3H400 1SCA022007R6450 3 0.97500 690 45 OFAA3H500 1SCA022007R6530 3 0.97630 500 48 OFAA3H630 1SCA022007R6610 3 0.97
OFAA00H_
S00404A
OFAA2H_
S00406A
OFAA3H_
S00407A
OFAA1H_
S00405A
7/27/2019 hrc fuse.pdf
12/44
12
HRC Fuse links, DIN-type, gG
Ordering information
1SCC317001C0201
OFAA
00/gG
125A
OFAA
1/gG
250A
OFAA
2/gG
400A
OFAA
3/gG
630A
HRC fuse links, gG, OFAA_H_-H20, industrial fuses, 690VIndustrial fuses with 20 m silver coating for demanding industrial environment.The type code includes one fuse link, the delivery batch is according to the column.
Indication on the top of fuse link.
IEC- Rated Rated Power Type Order number Delivery- Weight/size current voltage loss batch unit
In
[A] Un[V] P
h[W] [pcs] [kg]
00 2 690 1.3 OFAA00H2-H20 1SCA022297R0150 3 0.164 690 1.4 OFAA00H4-H20 1SCA022297R1120 3 0.166 690 1.4 OFAA00H6-H20 1SCA022297R1710 3 0.1610 690 2.7 OFAA00H10-H20 1SCA022296R9310 3 0.1616 690 3 OFAA00H16-H20 1SCA022296R9900 3 0.1620 690 3.2 OFAA00H20-H20 1SCA022297R0310 3 0.1625 690 3.9 OFAA00H25-H20 1SCA022297R0580 3 0.1632 690 4.5 OFAA00H32-H20 1SCA022297R0740 3 0.1635 690 4.9 OFAA00H35-H20 1SCA022297R0910 3 0.1640 690 5.3 OFAA00H40-H20 1SCA022297R1390 3 0.1650 690 6.9 OFAA00H50-H20 1SCA022297R1550 3 0.1663 690 8.6 OFAA00H63-H20 1SCA022297R1980 3 0.1680 690 9.2 OFAA00H80-H20 1SCA022297R2100 3 0.16
100 690 9.6 OFAA00H100-H20 1SCA022296R9570 3 0.16125 500 10.6 OFAA00H125-H20 1SCA022296R9730 3 0.16
1 16 690 1.9 OFAA1H16-H20 1SCA022297R2950 3 0.4920 690 3.1 OFAA1H20-H20 1SCA022297R3330 3 0.4925 690 3.9 OFAA1H25-H20 1SCA022297R3760 3 0.4932 690 4.6 OFAA1H32-H20 1SCA022297R4140 3 0.4935 690 5 OFAA1H35-H20 1SCA022297R4310 3 0.4940 690 6.3 OFAA1H40-H20 1SCA022297R4570 3 0.4950 690 7.1 OFAA1H50-H20 1SCA022297R4730 3 0.4963 690 8.5 OFAA1H63-H20 1SCA022299R4410 3 0.4980 690 9.4 OFAA1H80-H20 1SCA022299R4680 3 0.49100 690 14 OFAA1H100-H20 1SCA022297R2520 3 0.49125 690 19 OFAA1H125-H20 1SCA022297R2790 3 0.49160 690 20 OFAA1H160-H20 1SCA022297R3170 3 0.49200 690 22.5 OFAA1H200-H20 1SCA022297R3500 3 0.49250 500 23 OFAA1H250-H20 1SCA022297R3920 3 0.49
2 160 690 21 OFAA2H160-H20 1SCA022299R4840 3 0.67200 690 23 OFAA2H200-H20 1SCA022299R5060 3 0.67250 690 25.5 OFAA2H250-H20 1SCA022299R5220 3 0.67315 690 31.5 OFAA2H315-H20 1SCA022299R5490 3 0.67400 500 34 OFAA2H400-H20 1SCA022299R5650 3 0.67
3 315 690 30.5 OFAA3H315-H20 1SCA022299R5810 3 0.97400 690 41.5 OFAA3H400-H20 1SCA022299R6030 3 0.97500 690 45 OFAA3H500-H20 1SCA022299R6200 3 0.97630 500 48 OFAA3H630-H20 1SCA022299R6460 3 0.97
OFAA00H_-H20
S00404A
OFAA2H_-H20
S00406A
OFAA3H_-H20
S00407A
OFAA1H_-H20
S00405A
7/27/2019 hrc fuse.pdf
13/44
OFAF000AM_
S01555
A
S01556A
OFAF00AM_
S01557A
OFAF0AM_
OFAF1AM_
S01558A
13
HRC Fuse links, DIN-type, aM
Ordering information
1SCC317001C0201
1aM
315A
OFAF
HRC fuse links for motor protection, aM, OFAF_AM_, 500VThe type code includes one fuse link, the delivery batch is according to the column.Dual indication.
IEC- Rated Power loss Type Order number Delivery- Weight/size current batch unit
In
[A] Ph
[W] [pcs] [kg]
000 2 0.1 OFAF000AM2 1SCA022652R0360 9 0.124 0.2 OFAF000AM4 1SCA022652R0440 9 0.126 0.3 OFAF000AM6 1SCA022652R0520 9 0.1210 0.5 OFAF000AM10 1SCA022652R0610 9 0.1216 0.7 OFAF000AM16 1SCA022652R0790 9 0.1220 0.9 OFAF000AM20 1SCA022652R0870 9 0.1225 1.2 OFAF000AM25 1SCA022652R0950 9 0.1232 1.5 OFAF000AM32 1SCA022652R1090 9 0.1235 1.6 OFAF000AM35 1SCA022697R2510 9 0.1240 1.8 OFAF000AM40 1SCA022652R1170 9 0.1250 2.3 OFAF000AM50 1SCA022697R2690 9 0.1263 2.9 OFAF000AM63 1SCA022697R2770 9 0.1280 3.6 OFAF000AM80 1SCA022697R2850 9 0.12
00 100 5.2 OFAF00AM100 1SCA022697R2930 3 0.18125 6.4 OFAF00AM125 1SCA022697R3070 3 0.18160 7.9 OFAF00AM160 1SCA022697R3150 3 0.18
0 6 0.3 OFAF0AM6 1SCA022697R3230 3 0.2110 0.5 OFAF0AM10 1SCA022697R3310 3 0.2116 0.8 OFAF0AM16 1SCA022697R3400 3 0.2120 1.0 OFAF0AM20 1SCA022697R3580 3 0.2125 1.3 OFAF0AM25 1SCA022697R3660 3 0.2132 1.6 OFAF0AM32 1SCA022697R3740 3 0.2135 1.7 OFAF0AM35 1SCA022697R3820 3 0.2140 2.0 OFAF0AM40 1SCA022697R3910 3 0.2150 2.8 OFAF0AM50 1SCA022697R4040 3 0.2163 3.4 OFAF0AM63 1SCA022697R5610 3 0.2180 4.9 OFAF0AM80 1SCA022697R5950 3 0.21100 6.0 OFAF0AM100 1SCA022697R5790 3 0.21125 7.9 OFAF0AM125 1SCA022697R6090 3 0.21160 10.5 OFAF0AM160 1SCA022697R6170 3 0.21200 11.8 OFAF0AM200 1SCA022697R6250 3 0.21
1 16 1.0 OFAF1AM16 1SCA022697R6330 3 0.2820 1.2 OFAF1AM20 1SCA022697R6410 3 0.2825 1.4 OFAF1AM25 1SCA022697R6500 3 0.2832 1.9 OFAF1AM32 1SCA022697R6680 3 0.2835 2.0 OFAF1AM35 1SCA022697R6760 3 0.2840 2.3 OFAF1AM40 1SCA022697R6840 3 0.2850 2.9 OFAF1AM50 1SCA022697R6920 3 0.2863 3.6 OFAF1AM63 1SCA022697R7060 3 0.2880 4.6 OFAF1AM80 1SCA022697R7140 3 0.28100 5.8 OFAF1AM100 1SCA022697R7220 3 0.28160 10.4 OFAF1AM160 1SCA022697R7490 3 0.30200 14.2 OFAF1AM200 1SCA022697R7570 3 0.30224 16.0 OFAF1AM224 1SCA022697R7650 3 0.30250 17.5 OFAF1AM250 1SCA022697R7730 3 0.30315 22.1 OFAF1AM315 1SCA022697R7810 3 0.30
000aM
100A
OFAF
00aM
160A
OFAF
0aM
160A
OFAF
7/27/2019 hrc fuse.pdf
14/44
OFAF2AM_
OFAF3AM_
OFAF4AM_
OFAF4AAM_
14
HRC Fuse links, DIN-type, aM
Ordering information
1SCC317001C0201
4aM
800A
OFAF
OFAF
4a/aM
1000A
2aM
400A
OFAF
OFAF
3aM
630A
HRC fuse links for motor protection, aM, OFAF_AM_, 500VThe type code includes one fuse link, the delivery batch is according to the column.Dual indication on fuse link sizes 2 and 3 up to 630 A.
IEC- Rated Power loss Type Order number Delivery- Weight/size current batch unit
In
[A] Ph
[W] [pcs] [kg]
2 35 1.8 OFAF2AM35 1SCA022697R8110 3 0.3240 2.1 OFAF2AM40 1SCA022697R8200 3 0.3250 2.7 OFAF2AM50 1SCA022697R8380 3 0.3263 3.4 OFAF2AM63 1SCA022697R8460 3 0.3280 4.4 OFAF2AM80 1SCA022697R8540 3 0.32100 5.5 OFAF2AM100 1SCA022697R8620 3 0.32125 6.4 OFAF2AM125 1SCA022697R8710 3 0.32160 9.3 OFAF2AM160 1SCA022697R8890 3 0.32200 11.3 OFAF2AM200 1SCA022697R8970 3 0.32224 16.0 OFAF2AM224 1SCA022697R9010 3 0.32250 16.8 OFAF2AM250 1SCA022697R9190 3 0.32300 21.0 OFAF2AM300 1SCA022697R9270 3 0.40315 23.1 OFAF2AM315 1SCA022697R9350 3 0.40355 26.0 OFAF2AM355 1SCA022697R9430 3 0.40
400 29.7 OFAF2AM400 1SCA022697R9510 3 0.40500 34.4 OFAF2AM500 1SCA022697R9600 3 0.40
3 250 16.0 OFAF3AM250 1SCA022697R9780 1 0.45300 21.0 OFAF3AM300 1SCA022697R9860 1 0.45315 21.0 OFAF3AM315 1SCA022697R9940 1 0.45355 26.5 OFAF3AM355 1SCA022698R0010 1 0.45400 29.1 OFAF3AM400 1SCA022698R0100 1 0.45425 33.0 OFAF3AM425 1SCA022698R0280 1 0.60450 37.0 OFAF3AN450 1SCA022698R0360 1 0.60500 42.0 OFAF3AM500 1SCA022698R0440 1 0.60630 42.0 OFAF3AM630 1SCA022698R0520 1 0.60800*) 55.0 OFAF3AM800 1SCA022701R4790 1 0.60
4 400 26.0 OFAF4AM400 1SCA022698R0610 1 2.00500 38.0 OFAF4AM500 1SCA022698R0790 1 2.00630 50.0 OFAF4AM630 1SCA022698R0870 1 2.00800 65.0 OFAF4AM800 1SCA022698R0950 1 2.001000 80.0 OFAF4AM1000 1SCA022698R1090 1 2.001250 110.0 OFAF4AM1250 1SCA022698R1170 1 2.00
4a 500 38.0 OFAF4AAM500 1SCA022698R1410 1 2.00630 50.0 OFAF4AAM630 1SCA022698R1680 1 2.00800 65.0 OFAF4AAM800 1SCA022698R1760 1 2.001000 80.0 OFAF4AAM1000 1SCA022698R1840 1 2.001250 110.0 OFAF4AAM1250 1SCA022698R1920 1 2.00
S01559A
S0
1560A
S01998A
S01999A
*) 800 A / 400 V
7/27/2019 hrc fuse.pdf
15/44
15
HRC Fuse links, DIN-type, aM
Ordering information
1SCC317001C0201
HRC fuse links for motor protection, aM, OFAM_AM_, 690VThe type code includes one fuse link, the delivery batch is according to the column.Indication on the top of fuse link. Coordination tables, see the www -address, page 6.
IEC- Rated Rated Power Type Order number Delivery- Weight/size current voltage loss batch unit
In
[A] Un
[V] Ph
[W] [pcs] [kg]
00 2 690 0.17 OFAM00AM2 1SCA022640R4960 3 0.164 690 0.35 OFAM00AM4 1SCA022386R2630 3 0.166 690 0.4 OFAM00AM6 1SCA022386R2710 3 0.1610 690 0.72 OFAM00AM10 1SCA022386R2800 3 0.1616 690 1.1 OFAM00AM16 1SCA022323R6520 3 0.1620 690 1.4 OFAM00AM20 1SCA022323R6790 3 0.1625 690 1.6 OFAM00AM25 1SCA022324R2410 3 0.1632 690 2.1 OFAM00AM32 1SCA022324R2680 3 0.1640 690 2.9 OFAM00AM40 1SCA022324R2840 3 0.1650 690 3.7 OFAM00AM50 1SCA022324R2500 3 0.1663 690 4.6 OFAM00AM63 1SCA022324R2760 3 0.1680 690 6.4 OFAM00AM80 1SCA022324R2920 3 0.16100 690 7.7 OFAM00AM100 1SCA022324R8610 3 0.16
125 690 9.1 OFAM00AM125 1SCA022324R8880 3 0.16160 690 12 OFAM00AM160 1SCA022324R9000 3 0.16
1 50 690 2.9 OFAM1AM50 1SCA022194R7390 3 0.4963 690 3.5 OFAM1AM63 1SCA022194R7120 3 0.4980 690 4.7 OFAM1AM80 1SCA022194R6910 3 0.49100 690 6 OFAM1AM100 1SCA022194R6740 3 0.49125 690 7.1 OFAM1AM125 1SCA022194R6580 3 0.49160 690 14.2 OFAM1AM160 1SCA022103R6100 3 0.49200 690 17.7 OFAM1AM200 1SCA022103R6360 3 0.49250 690 18.3 OFAM1AM250 1SCA022103R6520 3 0.49
2 125 690 9.3 OFAM2AM125 1SCA022194R6310 3 0.67160 690 9.8 OFAM2AM160 1SCA022194R6150 3 0.67200 690 12 OFAM2AM200 1SCA022194R5510 3 0.67250 690 16 OFAM2AM250 1SCA022194R5340 3 0.67315 690 25 OFAM2AM315 1SCA022103R0670 3 0.67355 690 26 OFAM2AM355 1SCA022103R0670 3 0.67400 690 30 OFAM2AM400 1SCA022103R0830 3 0.67
3 315 690 21 OFAM3AM315 1SCA022194R4960 3 0.97355 690 25 OFAM3AM355 1SCA022194R4700 3 0.97400 690 29.2 OFAM3AM400 1SCA022194R4530 3 0.97500 690 36 OFAM3AM500 1SCA022103R1050 3 0.97630 690 40 OFAM3AM630 1SCA022103R1210 3 0.97800 500 70 OFAM3AM800 1SCA022655R7360 3 0.97
OFAM
00/aM
160A
OFAM
1/aM
250A
OFAM
2/aM
400A
OFAM
3/aM
800A
OFAM00AM_
S00408A
OFAM1AM_
OFAM2AM_
OFAM3AM_
S00409A
S00410A
S00411A
7/27/2019 hrc fuse.pdf
16/44
16
HRC Fuse links, DIN-type, aM
Ordering information
1SCC317001C0201
HRC fuse links for motor protection, aM, OFAA_AM_, 690VThe type code includes one fuse link, the delivery batch is according to the column.Dual indication on fuse link sizes from 000 up to 3.
IEC- Rated Power loss Type Order number Delivery- Weight/size current batch unit
In
[A] Ph
[W] [pcs] [kg]
000 2 0.1 OFAA000AM2 1SCA022660R7640 9 0.124 0.2 OFAA000AM4 1SCA022660R8020 9 0.126 0.3 OFAA000AM6 1SCA022660R8110 9 0.1210 0.5 OFAA000AM10 1SCA022660R8290 9 0.1216 0.7 OFAA000AM16 1SCA022660R8370 9 0.1220 0.9 OFAA000AM20 1SCA022660R8450 9 0.1225 1.2 OFAA000AM25 1SCA022660R8530 9 0.1232 1.5 OFAA000AM32 1SCA022660R8610 9 0.1235 1.6 OFAA000AM35 1SCA022660R8700 9 0.1240 1.8 OFAA000AM40 1SCA022660R8880 9 0.1250 2.3 OFAA000AM50 1SCA022660R8960 9 0.1263 2.9 OFAA000AM63 1SCA022660R9000 9 0.12
00 80 3.6 OFAA00AM80 1SCA022701R1770 3 0.18
100 5.2 OFAA00AM100 1SCA022701R1850 3 0.18125 7.5 OFAA00AM125 1SCA022701R1930 3 0.18160 OFAM00AM160 1SCA022324R9000 3 0.18
1 50 2.9 OFAA1AM50 1SCA022701R2070 3 0.2863 3.6 OFAA1AM63 1SCA022701R2150 3 0.2880 4.6 OFAA1AM80 1SCA022701R2230 3 0.28100 5.8 OFAA1AM100 1SCA022701R2310 3 0.28125 7.5 OFAA1AM125 1SCA022701R2400 3 0.30160 10.4 OFAA1AM160 1SCA022701R2580 3 0.30200 14.2 OFAA1AM200 1SCA022701R2660 3 0.30250 17.5 OFAA1AM250 1SCA022701R2740 3 0.30
2 125 6.4 OFAA2AM125 1SCA022701R2820 3 0.32160 9.3 OFAA2AM160 1SCA022701R2910 3 0.32200 11.3 OFAA2AM200 1SCA022701R3040 3 0.32250 16.8 OFAA2AM250 1SCA022701R3120 3 0.32315 23.1 OFAA2AM315 1SCA022701R3210 3 0.40355 25.0 OFAA2AM355 1SCA022701R3390 3 0.40
400 29.7 OFAA2AM400 1SCA022701R3470 3 0.403 315 21.0 OFAA3AM315 1SCA022701R3550 1 0.45
355 24.5 OFAA3AM355 1SCA022701R3630 1 0.45400 29.1 OFAA3AM400 1SCA022701R3710 1 0.45500 42.0 OFAA3AM500 1SCA022701R3800 1 0.60
4 500 38.0 OFAA4AM500 1SCA022701R3980 1 2.00630 50.0 OFAA4AM630 1SCA022701R4010 1 2.00800 65.0 OFAA4AM800 1SCA022701R4100 1 2.001000 80.0 OFAA4AM1000 1SCA022776R1000 1 2.00
4a 500 38.0 OFAA4AAM500 1SCA022701R4280 1 2.00630 50.0 OFAA4AAM630 1SCA022701R4360 1 2.00800 65.0 OFAA4AAM800 1SCA022701R4440 1 2.001000 80.0 OFAA4AAM1000 1SCA022703R4550 1 2.00
000aM
63A
OFAA
00aM
100A
OFAA
1aM
250A
OFAA
2aM
400A
OFAA
OFAA
3aM
500A
4aM
800A
OFAA
OFAA
4a/aM
1000A
OFAA000AM_
S0156
1A
S0156
2A
OFAA00AM_
S01563A
OFAA1AM_
S01564A
OFAA2AM_
OFAA3AM_
S01565A
OFAA4AM_
OFAA4AAM_
S020
00A
S02001A
7/27/2019 hrc fuse.pdf
17/44
17
HRC Fuse links, DIN-type, aM
Ordering information
1SCC317001C0201
HRC fuse links for motor protection, aM, OFAM_AM_-H20, industrialfuses, 690VIndustrial fuses with 20 m silver coating for demanding industrial environment.The type code includes one fuse link, the delivery batch is according to the column.Indication on the top of fuse link. Coordination tables, see the www -address, page 6.
IEC- Rated Rated Power Type Order number Delivery- Weight/size current voltage loss batch unit
In
[A] Un
[V] Ph
[W] [pcs] [kg]
00 2 690 0.17 OFAM00AM2-H20 1SCA022640R5000 3 0.164 690 0.35 OFAM00AM4-H20 1SCA022386R7270 3 0.166 690 0.4 OFAM00AM6-H20 1SCA022386R7350 3 0.1610 690 0.72 OFAM00AM10-H20 1SCA022386R7430 3 0.1616 690 1.1 OFAM00AM16-H20 1SCA022339R3460 3 0.1620 690 1.4 OFAM00AM20-H20 1SCA022339R3620 3 0.1625 690 1.6 OFAM00AM25-H20 1SCA022339R3890 3 0.1632 690 2.1 OFAM00AM32-H20 1SCA022339R4010 3 0.1640 690 2.9 OFAM00AM40-H20 1SCA022339R4270 3 0.1650 690 3.7 OFAM00AM50-H20 1SCA022339R4430 3 0.1663 690 4.6 OFAM00AM63-H20 1SCA022339R4600 3 0.16
80 690 6.4 OFAM00AM80-H20 1SCA022339R4860 3 0.16100 690 7.7 OFAM00AM100-H20 1SCA022339R5080 3 0.16125 690 9.1 OFAM00AM125-H20 1SCA022339R5240 3 0.16160 690 12 OFAM00AM160-H20 1SCA022339R5410 3 0.16
1 50 690 2.9 OFAM1AM50-H20 1SCA022299R7600 3 0.4963 690 3.5 OFAM1AM63-H20 1SCA022299R7860 3 0.4980 690 4.7 OFAM1AM80-H20 1SCA022299R8080 3 0.49100 690 6 OFAM1AM100-H20 1SCA022299R6620 3 0.49125 690 7.1 OFAM1AM125-H20 1SCA022299R6890 3 0.49160 690 14.2 OFAM1AM160-H20 1SCA022299R7010 3 0.49200 690 17.7 OFAM1AM200-H20 1SCA022299R7270 3 0.49250 690 18.3 OFAM1AM250-H20 1SCA022299R7430 3 0.49
2 125 690 9.3 OFAM2AM125-H20 1SCA022299R8240 3 0.67160 690 9.8 OFAM2AM160-H20 1SCA022299R8410 3 0.67200 690 12 OFAM2AM200-H20 1SCA022299R8670 3 0.67250 690 16 OFAM2AM250-H20 1SCA022299R8830 3 0.67315 690 25 OFAM2AM315-H20 1SCA022299R9050 3 0.67
355 690 26 OFAM2AM355-H20 1SCA022299R9210 3 0.67400 690 30 OFAM2AM400-H20 1SCA022299R9480 3 0.67
3 315 690 21 OFAM3AM315-H20 1SCA022299R3520 3 0.97355 690 25 OFAM3AM355-H20 1SCA022299R3790 3 0.97400 690 29.2 OFAM3AM400-H20 1SCA022299R3950 3 0.97500 690 36 OFAM3AM500-H20 1SCA022299R4170 3 0.97630 690 40 OFAM3AM630-H20 1SCA022299R4330 3 0.97800 500 70 OFAM3AM800-H20 1SCA022655R7440 3 0.97
OFAM
00/aM
160A
OFAM
1/aM
250A
OFAM
2/aM
400A
OFAM
3/aM
800A
OFAM00AM_-H20
S00408A
OFAM1AM_-H20
OFAM2AM_-H20
OFAM3AM_-H20
S00409A
S00410A
S00411A
7/27/2019 hrc fuse.pdf
18/44
18
HRC Fuse links, DIN-type, aM
Ordering information
1SCC317001C0201
OFM 260OFM 690
OFS 260OFS 690
Fuse replacement handles
REMARK: Fuse size 4a, fuse replacement with the cover of switch fuse OS1250 or fuse base OFAX4.
Suitable for DIN- Description Type Order number Units/ Weight/fuse link size type unit
[pcs] [kg]
000, 00, 0, 1, 2, 3 Compact OFAE504 1SCA022007R6880 1 0.16000, 00, 0, 1, 2, 3 690 V OFAE505 2CMA125276R1000 1 0.80
Electronic fuse monitorSuitable for 1- and 3-phase circuits.
Rated voltage Type Order number Units/ Weight/[Vac] type unit
[pcs] [kg]
100260 OFM260 1SCA022459R8560 1 0.14380690 OFM690 1SCA022459R8480 1 0.14
120260 OFS260 1SCA022716R0180 1 0.14
380690 OFS690 1SCA022715R9920 1 0.14
Crimp terminals for connecting fuse monitor to the switch fuse type OS_
Suitable for Flat terminal Type Order number Units/ Weight/switch fuse size [mm] type unit
[pcs] [kg]
OS-switch fuse 2.8 - 0.8 OFMZX2 1SCA022475R9910 6 0.01
HRC fuse links, Accessories
Ordering Information
UNLO
CK/FR
II001
0-31
I
UNLO
CK/FRII
0010-31
I
OFAE5 0 5
6 9 0
V
14
13
22
21
OFAE 504
S00370A
S00371A
OFAE 505
OFMZX_
S00908A
S00954A
S01982A
1) The connection diagram on page 39
Power circuit
Connection wire no:s 1, 3, 5 Double insulated 0.75 mm2 Cu, length 60 cmConnection wire no:s 2, 4, 6 0.75 mm2 Cu, length 60 cmRated voltage OF_ 260 100/120 Vac ... 260 VacRated voltage OF_ 690 380 Vac ... 690 VacVoltage tolerance -10% ... +10%Power consumption < 3 VA
Rated frequency 50 / 60 HzMeasuring impedance > 1000 /VImpulse test voltage (1.2 / 50 s) 9.8 kV
Phase to phase / Supply to load
Output terminals (Auxiliary contacts)
Terminals OFM 13-14 (NO), 21-22 (NC)Wire section: OFS 11-14 (NO), 21-22 (NC)
Flexible Cu 1,5 mm2
Rigid Cu 2,5 mm2
Rated current Ie
4A / 250Vac / AC13A / 250Vac / AC152A / 24Vdc / DC13
Rated voltage / max. breaking voltage 250 Vac / 440 VacRated breaking capacity 2000 VAContact material Cadmium free
Characteristics
Specied ambient air temperature range -25...+55 CTransport and storage temperature range -40...+70 COperating time < 2 secOvervoltage category / Pollution severity III / 3 IEC 60947-1Dielectric test voltage:
Power circuit/output terminals 5 kVrms / 1min 50Hz
EMC (OFM):EmissionConducted emission EN 55022 (1994) Class BRadiated emission EN 55022 (1994) Class BHarmonic currents emissions EN 61000-3-2 (1995) Class AImmunity
Electrostatic discharge (ESD) EN 61000-4-2 (1995) Criteria B (Contact/Air) Level 2/3RF Radiated eld EN 61000-4-3 (1996) Criteria A Level 3Electrical fast transient (EFT) EN 61000-4-4 (1995) Criteria B Level 3RF Electromagnetic conducted EN 61000-4-6 (1996) Criteria A Level 3RF Electromagnetic eld (GSM) ENV 50204 (1995) Criteria A
Magnetic eld immunityContinuous EN 61000-4-8 (1993) Level 5Pulse 1.2 / 50 s EN 61000-4-9 (1993) Level 5
Housing Self-extinguish thermoplast with V-0 behaviorin accordance with UL 94
Degree of protection: IP 20Weight 140 g
Technical data1)
7/27/2019 hrc fuse.pdf
19/44
19
1SCC317001C0201
Time-current characteristics, 500 V, gG- fuse links OFAF_H_, sizes 000...4/4a
HRC fuse links gG
Time-current characteristics
210
-2
10-1
3 4 5
2A
4A
6A
10A
16A
20A
32A
40A
63A
100A
200A
250A
355A
315A
425A
500A
800A
1250A
25A
35A
50A
80
A
125A
160A
224A
400A
450A
630A
1000A
300A
1
Rated current In/A
Pre-arcingtime
ts/
s
Prospective current Ip/A
1 2 104 6 8 10 101010
10
103
102
10
S07026
4
7/27/2019 hrc fuse.pdf
20/44
20
1SCC317001C0201
Time-current characteristics, 690 V, gG- fuse links OFAA_GG_, sizes 000...5
HRC fuse links gG
Time-current characteristics
Rated current In/A
Pre-arcingtime
ts/s
10
2
10-2
10-1
102
103
104
10 10
3
10
4
10
5
2
A
4
A
6
A
10A
16A
20A
32A
40A
63A
100A
200A
250A
355
A
315A
425
A
500
A
800
A
25A
35A
50A
80A
125A
160
A
224
A
400A
450A
630A
1000A
300
A
1
10
Prospective current Ip/A
1 2 4 6 8
S07027
1250
A
1600
A
7/27/2019 hrc fuse.pdf
21/44
21
1SCC317001C0201
HRC fuse links gG
Time-current characteristics
Time-current characteristics, 690 V, gG- fuse links OFAA_H_ and OFAA_H_-H20, sizes 00...3
Rated current In/A
Pre-arcingtimet
s/s
Prospective current lp/A
S01311B
7/27/2019 hrc fuse.pdf
22/44
22
1SCC317001C0201
HRC fuse links aM
Time-current characteristics
Time-current characteristics, 500 V, aM- fuse links OFAF_AM_, sizes 000...3
Rated current In/A
Pre-arcingtime
ts/
s
Prospective current Ip/A
10-2
10-1
102
102
10 103
104
105
6A
10A
16A
20A
32A
40A
63A
100A
200A
250A
400A
355A
500A
800A
(400V)
25A
35A
50A
80A
125A
160A
224A
450A
630A
315A
1
10
4A
S07028
7/27/2019 hrc fuse.pdf
23/44
23
1SCC317001C0201
HRC fuse links aM
Time-current characteristics
Time-current characteristics, 690 V, aM-fuse links OFAM_ AM- and OFAM_AM_-H20, sizes 00...3
S01313A
Rated current In/A
Pre-arcingtimets/s
Prospective current lp/A
7/27/2019 hrc fuse.pdf
24/44
24
1SCC317001C0201
HRC fuse links aM
Time-current characteristics
Time-current characteristics, 690 V, aM- fuse links OFAA_AM_, sizes 000...3
Rated current In/A
Pre-arcingtime
ts/
s
10-2
10-1
102
102
10 103
104
105
6A
10A
16A
20A
32A
40A
63A
100A
200A
250A
400A
355A
500A
25A
35A
50A
80A
125A
160A
224A
450A
315A
1
10
4A
Prospective current Ip/A
S07029
7/27/2019 hrc fuse.pdf
25/44
25
1SCC317001C0201
HRC fuse links gG
Cut-off current characteristics
Current limitation, 500 V, gG- fuse links OFAF_H_, sizes 000...4/4a
10
3
10
2
102
103
104
105
10 6
10
4
10
5
10
6
2 A
4 A
6 A10 A
16 A
20 A
25 A
32 A
40 A
63 A
100 A
160 A
224 A
300 A
355 A
425 A
500 A
800 A
1250 A
35 A
50 A
80 A
125 A
200 A
250 A
315 A
400 A
450 A
630 A
1000 A
i s=
2.3
I p
S07030
Prospective current Ip (r.m.s.) kA
Cut-offcurrent(peak)limitedbyfuselinkic/kA(asymmetrica
lshort-circuit)
7/27/2019 hrc fuse.pdf
26/44
26
1SCC317001C0201
HRC fuse links gG
Cut-off current characteristics
Current limitation, 690 V, gG- fuse links OFAA_GG_, sizes 000...4/4a
103
102
102
103
104
105
106
104
105
106
2 A
4 A
6 A
10 A
16 A
20 A
25 A
32 A
40 A
63 A
100 A
160 A
224 A
300 A
355 A
425 A
500 A
800 A
35 A
50 A
80 A
125 A
200 A
250 A
315 A
400 A
450 A
630 A
1000 A
S07031
I s=
2.3
I p
Prospective current Ip (r.m.s.) kA
Cut-offcurrent(peak)limitedbyfuselinkic/kA(asymmetricalshort-circuit)
7/27/2019 hrc fuse.pdf
27/44
27
1SCC317001C0201
HRC fuse links gG
Cut-off current characteristics
Current limitation, 690 V, gG- fuse links OFAA_GG_, size 5
Prospective current Ip (r.m.s.) kA
1600 A1250 A
i s=2
.3I p
S07032
Cut-offcurrent(pe
ak)limitedbyfuselinkic/kA(asym
metricalshort-circuit)
7/27/2019 hrc fuse.pdf
28/44
28
1SCC317001C0201
HRC fuse links gG
Cut-off current characteristics
Current limitation, 690 V, gG- fuse links OFAA_H_ and OFAA_H_-H20, sizes 00...3
Ip
= Prospective current
iS
= Maximum value ofcurrent (peak)
idc
= Value of DC-component
ic
= Cut-off current (peak)limited by fuse link
K = Correction factor
Prospective current Ip (r.m.s.) kA
Cut-offcurrent(pe
ak)limitedbyfuselinkic/kA(asymmetricalshort-circuit)
Current peak without fuse
S01312B
7/27/2019 hrc fuse.pdf
29/44
29
1SCC317001C0201
HRC fuse links aM
Cut-off current characteristics
Current limitation, 500 V, aM- fuse links OFAF_AM_, sizes 000...3
102
10
102
10 3
10 4
10 5
10 6
103
104
105
106
32 A
6 A4 A
10 A20 A
40 A
16 A
25 A
63 A
100 A
160 A
224 A315 A400 A
500 A
35 A50 A80 A
125 A
200 A
250 A
355 A450 A
630 A800 A (400 V)
l s=2.3I p
Prospective current Ip (r.m.s.) kA
S07033
Cut-offcurrent(pe
ak)limitedbyfuselinkic/kA(asym
metricalshort-circuit)
7/27/2019 hrc fuse.pdf
30/44
30
1SCC317001C0201
HRC fuse links aM
Cut-off current characteristics
Current limitation, 690 V, aM-fuse links OFAM_AM_ and OFAM_AM_-H20, sizes 00...3
S01314A
Prospective current Ip (r.m.s.) kA
Current peak without fuse
Ip
= Prospective current
iS
= Maximum value ofcurrent (peak)
idc
= Value of DC-component
ic
= Cut-off current (peak)limited by fuse link
K = Correction factor
Cut-offcurrent(pe
ak)limitedbyfuselinkic/kA(asym
metricalshort-circuit)
7/27/2019 hrc fuse.pdf
31/44
31
1SCC317001C0201
HRC fuse links aM
Cut-off current characteristics
Current limitation, 690 V, aM- fuse links OFAA_AM_, sizes 000...3
Prospective current Ip (r.m.s.) kA
102
10
102
103
104
105
10 6
103
104
105
106
32 A
6 A
4 A
10 A
20 A
40 A
16 A
25 A
63 A
100 A
160 A
224 A
315 A
400 A
500 A
35 A
50 A
80 A
125 A
200 A
250 A
355 A450 A
i s=
2.3
l p
S07034
Cut-offcurrent(peak)limitedbyfuselinkic/kA(asym
metricalshort-circuit)
7/27/2019 hrc fuse.pdf
32/44
32
1SCC317001C0201
HRC Fuse links, gG
I2t characteristics
I2t characteristics, 500 V, gG- fuse links OFAF_H_, sizes 000...4/4a
4
3
2
5
6
7
10
10
10
10
10
10
10
203050
1
23
5
200300
500
2 0003 0005 000
20 00030 000
50 000
200 000300 000
500 000
2 000 0003 000 000
5 000 000
S07035
gG, 500 V
I2t/[A2s]
2 4 403532252016106 50 63 80 100 125 160 200 224 500425400355300315
250 800630 10 00 12 50
operating-I2t
pre-arcing-I2t
Discrimination
B2
> A1
+ B1
S07036
A1
B1
B2
operating-I2t
pre-arcing-I2t
7/27/2019 hrc fuse.pdf
33/44
33
1SCC317001C0201
HRC Fuse links, gG
I2t characteristics
I2t characteristics, 690 V, gG- fuse links OFAA_GG_, sizes 000...5
Discrimination
B2
> A1
+ B1
S07036
A1
B1
B2
operating-I2t
pre-arcing-I2t
104
103
102
105
106
107
10
2030
50
1
23
5
200300
500
2 0003 000
5 000
20 00030 000
50 000
200 000300 000500 000
2 000 000
3 000 000
5 000 000
S
07038
gG, 690 V 2 4 403532252016106 50 63 80 100 125 160 200 224 450425400355300315250 630500 800 1000
I2t/[A2s]
108
20 000 00030 000 000
50 000 000
1250 1600
operating-I2t
pre-arcing-I2t
7/27/2019 hrc fuse.pdf
34/44
34
1SCC317001C0201
HRC Fuse links, gG
I2t characteristics
I2t characteristics, 690 V, gG- fuse links OFAA_H_ and OFAA_H_-H20, sizes 00...3
Discrimination
B2
> A1
+ B1
S07036
A1
B1
B2
operating-I2t
pre-arcing-I2t
1
10
100
1 000
10 000
100 000
1 000 000
00H4
00H6
00H10
00
,1H16
00
,1H20
00
,1H25
00
,1H32
00
,1H40
00
,1H50
00
,1H63
00
,1H80
00
,1H100
00
H125
1H125
1,
2H160
1,
2H200
1H250
2H250
2,
3H315
2H400
3H400
3H500
3H630
S07
039
x)x) x) x)
Un690V
IEC 60269-2-1
x)Un500V
I2t/[A2s]
operating-I2t
pre-arcing-I2t
7/27/2019 hrc fuse.pdf
35/44
35
1SCC317001C0201
I2t characteristics, 500 V, aM- fuse links OFAF_AM_, sizes 000...3
HRC Fuse links, aM
I2t characteristics
Discrimination
B2
> A1
+ B1
S07036
A1
B1
B2
operating-I2t
pre-arcing-I2t
10 2
10 3
10 4
10 6
10 7
10 5
10
20
30
50
200
300
500
2 0003 000
5 000
20 000
30 000
50 000
200 000
300 000
500 000
2 000 0003 000 000
5 000 000
aM, 500 V 4 403532252016106 50 63 80 100 125 160 200 224 500450400355 800(400V)250 630315
S07040
I2t/[A2s]
operating-I2t
pre-arcing-I2t
7/27/2019 hrc fuse.pdf
36/44
36
1SCC317001C0201
HRC Fuse links, aM
I2t characteristics
I2t characteristics, 690 V, aM-fuse links OFAM_AM_ and OFAM_AM_-H20, sizes 00...3
Discrimination
B2
> A1
+ B1
S07036
A1
B1
B2
operating-I2t
pre-arcing-I2t
1
10
100
1 000
10 000
100 000
1 000 000
00aM16
00aM20
00aM25
00aM32
00aM40
00aM50
00aM63
00aM80
00aM100
00aM125
00aM160
operating-I2t, 690V
operating-I2t, 500V
operating-I2
t, 400V
pre-arcing-I2t, Ip100kA
00aM4
00aM6
00aM10
S07041
I2t/[A2s]
1
10
100
1000
10000
100000
1 000000
1aM50
1aM63
1aM80
1aM100
1aM125
1aM160
1aM200
1aM250
2aM125
2aM160
2aM200
2aM250
2aM315
2aM355
2aM400
3aM315
3aM355
3aM400
3aM500
3aM630
500V3aM800
S07042
operating-I2t Un690V
pre-arcing-I2t Ip100kA
I2t/[A2s]
7/27/2019 hrc fuse.pdf
37/44
37
1SCC317001C0201
I2t characteristics, 690 V, aM- fuse links OFAA_AM_, sizes 000...3
HRC Fuse links, aM
I2t characteristics
Discrimination
B2
> A1
+ B1
S07036
A1
B1
B2
operating-I2t
pre-arcing-I2t
102
103
104
106
107
105
10
20
30
50
200
300
500
2 000
3 000
5 000
20 000
30 000
50 000
200 000
300 000
500 000
2 000 000
3 000 000
5 000 000
aM, 690 V 4 6 40353225201610 50 63 80 100 125 160 200 224 500400355315250 450
I2t/[A2s]
S07043
operating-I2t
pre-arcing-I2t
7/27/2019 hrc fuse.pdf
38/44
38
1SCC317001C0201
gG- and aM- fuse links
OFAF_H_
OFAA_GG_OFAF_AM_
OFAA_AM_
HRC Fuse links gG, aM
Dimension drawings
gG- and aM- fuse links
OFAA_H_
OFAA_H_-H20
OFAM_AM_
OFAM_AM_-H20
aed
OFA_ 000OFA_ 00OFA_ 0OFA_ 1OFA_ 2OFA_ 3
h
S07044
OFA_ 4
d ae
h
OFA_ 4a
d ae
h
OFA_ 3( -400A)OFA_ 1
cf
b
g
cf
b
OFA_ 000OFA_ 00OFA_ 0
OFA_ 2
g
OFA_ 3
(425-800A)
b
cf
g
OFA_4_
b
cf
g
Fuse link cbaIEC-size
gd fe h
OFA_000_OFA_00_OFA_0_6-160OFA_0_200-250OFA_1_16-100OFA_1_125-315OFA_2_35-250OFA_2_300-500OFA_3_250-400OFA_3_425-800OFA_4_OFA_4A_
000000011223344a
7979
125125135135150150150150200200
49,55066666868686868686888
5252,866,866,870,870,872,372,372,372,3
8585
666666666688
353535354040484860608585
151515201520202626334949
20,829,529,539,529,539,539,5
5151708989
52,559,559,559,564,5
667272
83,586
119119
d
e
fa
e
a
fd
b
g c
cg
b
S07045
Fuse link cbaIEC-size
gd fe
OFA_00_OFA_1_OFA_2_OFA_3_
00123
79135150150
4865,565,565,5
35404860
52747474
6666
30495772
59627084,5
7/27/2019 hrc fuse.pdf
39/44
39
1SCC317001C0201
HRC Fuse links, fuse monitor
Dimension drawings, connecting diagram
gG- fuse links, OFAA5GG1600
S04116
241,3
235
171,4
146
88,9 95,3
273,1
88,9
A
B
D
C
OFAA5GG1200
OFAA5GG1600
A
15,9
15,9
B
60,3
69,8
C
76,2
88,9
D
11,1
12,7
Fuse monitor
OFS
Fuse monitor, connecting diagram
OFM
105
89,5
103,5
63
3753
65
30
33,5
4,5
S00967A
14
13
672,64
1003,94
1285,04
30,12
1164,57
80,31
4,5DIA0,18
120,47
31,61,24
21 22 11 14
M00013
L1L2
L3
N
PE
2L1
2N
21
22
13
14
13
14
95
96
97
98
21
22
31
32
43
44
53
54
1
2
1 3 5
2 4 6
1 3 5
2 4 6
A1
A2
F1
K1
F2
Q1
M1 MU1
V1 W1
3~
F10
1 3 5
2 64
1 3 5
2 64
13
14
21
22
14
13
22
21
S00965A
22
21
14
11
OFM OFS
7/27/2019 hrc fuse.pdf
40/44
Index
40
1SCC317001C0201
Type Order number Page Description
OFAA000AM10 1SCA022660R8290 16 HRC fuse link, aM
OFAA000AM16 1SCA022660R8370 16 HRC fuse link, aM
OFAA000AM2 1SCA022660R7640 16 HRC fuse link, aMOFAA000AM20 1SCA022660R8450 16 HRC fuse link, aM
OFAA000AM25 1SCA022660R8530 16 HRC fuse link, aM
OFAA000AM32 1SCA022660R8610 16 HRC fuse link, aM
OFAA000AM35 1SCA022660R8700 16 HRC fuse link, aM
OFAA000AM4 1SCA022660R8020 16 HRC fuse link, aM
OFAA000AM40 1SCA022660R8880 16 HRC fuse link, aM
OFAA000AM50 1SCA022660R8960 16 HRC fuse link, aM
OFAA000AM6 1SCA022660R8110 16 HRC fuse link, aM
OFAA000AM63 1SCA022660R9000 16 HRC fuse link, aM
OFAA000GG10 1SCA022661R8500 9 HRC fuse link, gG
OFAA000GG16 1SCA022661R8680 9 HRC fuse link, gG
OFAA000GG2 1SCA022661R8250 9 HRC fuse link, gG
OFAA000GG20 1SCA022661R8760 9 HRC fuse link, gG
OFAA000GG25 1SCA022661R8840 9 HRC fuse link, gG
OFAA000GG32 1SCA022661R8920 9 HRC fuse link, gGOFAA000GG35 1SCA022661R9060 9 HRC fuse link, gG
OFAA000GG4 1SCA022661R8330 9 HRC fuse link, gG
OFAA000GG40 1SCA022661R9140 9 HRC fuse link, gG
OFAA000GG50 1SCA022661R9220 9 HRC fuse link, gG
OFAA000GG6 1SCA022661R8410 9 HRC fuse link, gG
OFAA000GG63 1SCA022661R9310 9 HRC fuse link, gG
OFAA00AM100 1SCA022701R1850 16 HRC fuse link, aM
OFAA00AM125 1SCA022701R1930 16 HRC fuse link, aM
OFAA00AM80 1SCA022701R1770 16 HRC fuse link, aM
OFAA00GG100 1SCA022700R9520 9 HRC fuse link, gG
OFAA00GG125 1SCA022724R0610 9 HRC fuse link, gG
OFAA00GG80 1SCA022700R9440 9 HRC fuse link, gG
OFAA00H10 1SCA022007R4080 11 HRC fuse link, gG
OFAA00H100 1SCA022007R4830 11 HRC fuse link, gG
OFAA00H100-H20 1SCA022296R9570 12 HRC fuse l ink, gGOFAA00H10-H20 1SCA022296R9310 12 HRC fuse link, gG
OFAA00H125 1SCA022078R4290 11 HRC fuse link, gG
OFAA00H125-H20 1SCA022296R9730 12 HRC fuse l ink, gG
OFAA00H16 1SCA022007R4160 11 HRC fuse link, gG
OFAA00H16-H20 1SCA022296R9900 12 HRC fuse l ink, gG
OFAA00H2 1SCA022041R3630 11 HRC fuse link, gG
OFAA00H20 1SCA022007R4240 11 HRC fuse link, gG
OFAA00H20-H20 1SCA022297R0310 12 HRC fuse l ink, gG
OFAA00H25 1SCA022007R4320 11 HRC fuse link, gG
OFAA00H25-H20 1SCA022297R0580 12 HRC fuse l ink, gG
OFAA00H2-H20 1SCA022297R0150 12 HRC fuse link, gG
OFAA00H32 1SCA022208R7050 11 HRC fuse link, gG
OFAA00H32-H20 1SCA022297R0740 12 HRC fuse l ink, gG
OFAA00H35 1SCA022007R4410 11 HRC fuse link, gG
OFAA00H35-H20 1SCA022297R0910 12 HRC fuse l ink, gGOFAA00H4 1SCA022028R5700 11 HRC fuse link, gG
OFAA00H40 1SCA022261R7200 11 HRC fuse link, gG
OFAA00H40-H20 1SCA022297R1390 12 HRC fuse l ink, gG
OFAA00H4-H20 1SCA022297R1120 12 HRC fuse link, gG
OFAA00H50 1SCA022007R4590 11 HRC fuse link, gG
OFAA00H50-H20 1SCA022297R1550 12 HRC fuse link, gG
OFAA00H6 1SCA022007R3940 11 HRC fuse link, gG
OFAA00H63 1SCA022007R4670 11 HRC fuse link, gG
OFAA00H63-H20 1SCA022297R1980 12 HRC fuse l ink, gG
OFAA00H6-H20 1SCA022297R1710 12 HRC fuse link, gG
OFAA00H80 1SCA022007R4750 11 HRC fuse link, gG
OFAA00H80-H20 1SCA022297R2100 12 HRC fuse l ink, gG
OFAA0GG10 1SCA022703R1370 9 HRC fuse link, gG
OFAA0GG100 1SCA022703R2340 9 HRC fuse link, gG
OFAA0GG125 1SCA022703R2420 9 HRC fuse link, gGOFAA0GG16 1SCA022703R1450 9 HRC fuse link, gG
OFAA0GG160 1SCA022703R2510 9 HRC fuse link, gG
OFAA0GG20 1SCA022703R1530 9 HRC fuse link, gG
OFAA0GG25 1SCA022703R1610 9 HRC fuse link, gG
Type Order number Page Description
OFAA0GG32 1SCA022703R1700 9 HRC fuse link, gG
OFAA0GG35 1SCA022703R1880 9 HRC fuse link, gG
OFAA0GG40 1SCA022703R1960 9 HRC fuse link, gGOFAA0GG50 1SCA022703R2000 9 HRC fuse link, gG
OFAA0GG6 1SCA022703R1290 9 HRC fuse link, gG
OFAA0GG63 1SCA022703R2180 9 HRC fuse link, gG
OFAA0GG80 1SCA022703R2260 9 HRC fuse link, gG
OFAA1AM100 1SCA022701R2310 16 HRC fuse link, aM
OFAA1AM125 1SCA022701R2400 16 HRC fuse link, aM
OFAA1AM160 1SCA022701R2580 16 HRC fuse link, aM
OFAA1AM200 1SCA022701R2660 16 HRC fuse link, aM
OFAA1AM250 1SCA022701R2740 16 HRC fuse link, aM
OFAA1AM50 1SCA022701R2070 16 HRC fuse link, aM
OFAA1AM63 1SCA022701R2150 16 HRC fuse link, aM
OFAA1AM80 1SCA022701R2230 16 HRC fuse link, aM
OFAA1GG100 1SCA022700R9950 9 HRC fuse link, gG
OFAA1GG125 1SCA022701R0020 9 HRC fuse link, gG
OFAA1GG16 1SCA022703R2690 9 HRC fuse link, gGOFAA1GG160 1SCA022701R0110 9 HRC fuse link, gG
OFAA1GG20 1SCA022703R2770 9 HRC fuse link, gG
OFAA1GG200 1SCA022701R0290 9 HRC fuse link, gG
OFAA1GG25 1SCA022703R2850 9 HRC fuse link, gG
OFAA1GG250 1SCA022701R0370 9 HRC fuse link, gG
OFAA1GG32 1SCA022703R2930 9 HRC fuse link, gG
OFAA1GG35 1SCA022703R3070 9 HRC fuse link, gG
OFAA1GG40 1SCA022703R3150 9 HRC fuse link, gG
OFAA1GG50 1SCA022700R9610 9 HRC fuse link, gG
OFAA1GG63 1SCA022700R9790 9 HRC fuse link, gG
OFAA1GG80 1SCA022700R9870 9 HRC fuse link, gG
OFAA1H100 1SCA022007R5300 11 HRC fuse link, gG
OFAA1H100-H20 1SCA022297R2520 12 HRC fuse l ink, gG
OFAA1H125 1SCA022007R5480 11 HRC fuse link, gG
OFAA1H125-H20 1SCA022297R2790 12 HRC fuse l ink, gGOFAA1H16 1SCA022023R9510 11 HRC fuse link, gG
OFAA1H160 1SCA022007R5560 11 HRC fuse link, gG
OFAA1H160-H20 1SCA022297R3170 12 HRC fuse l ink, gG
OFAA1H16-H20 1SCA022297R2950 12 HRC fuse link, gG
OFAA1H20 1SCA022023R9690 11 HRC fuse link, gG
OFAA1H200 1SCA022007R5640 11 HRC fuse link, gG
OFAA1H200-H20 1SCA022297R3500 12 HRC fuse l ink, gG
OFAA1H20-H20 1SCA022297R3330 12 HRC fuse link, gG
OFAA1H25 1SCA022023R9770 11 HRC fuse link, gG
OFAA1H250 1SCA022007R5720 11 HRC fuse link, gG
OFAA1H250-H20 1SCA022297R3920 12 HRC fuse link, gG
OFAA1H25-H20 1SCA022297R3760 12 HRC fuse link, gG
OFAA1H32 1SCA022197R1420 11 HRC fuse link, gG
OFAA1H32-H20 1SCA022297R4140 12 HRC fuse link, gG
OFAA1H35 1SCA022007R4910 11 HRC fuse link, gGOFAA1H35-H20 1SCA022297R4310 12 HRC fuse link, gG
OFAA1H40 1SCA022197R1690 11 HRC fuse link, gG
OFAA1H40-H20 1SCA022297R4570 12 HRC fuse link, gG
OFAA1H50 1SCA022007R5050 11 HRC fuse link, gG
OFAA1H50-H20 1SCA022297R4730 12 HRC fuse link, gG
OFAA1H63 1SCA022007R5130 11 HRC fuse link, gG
OFAA1H63-H20 1SCA022299R4410 12 HRC fuse link, gG
OFAA1H80 1SCA022007R5210 11 HRC fuse link, gG
OFAA1H80-H20 1SCA022299R4680 12 HRC fuse link, gG
OFAA2AM125 1SCA022701R2820 16 HRC fuse link, aM
OFAA2AM160 1SCA022701R2910 16 HRC fuse link, aM
OFAA2AM200 1SCA022701R3040 16 HRC fuse link, aM
OFAA2AM250 1SCA022701R3120 16 HRC fuse link, aM
OFAA2AM315 1SCA022701R3210 16 HRC fuse link, aM
OFAA2AM355 1SCA022701R3390 16 HRC fuse link, aMOFAA2AM400 1SCA022701R3470 16 HRC fuse link, aM
OFAA2GG100 1SCA022703R3820 10 HRC fuse link, gG
OFAA2GG125 1SCA022701R0450 10 HRC fuse link, gG
OFAA2GG160 1SCA022701R0530 10 HRC fuse link, gG
7/27/2019 hrc fuse.pdf
41/44
Index
41
1SCC317001C0201
Type Order number Page Description
OFAF000AM25 1SCA022652R0950 13 HRC fuse link, aM
OFAF000AM32 1SCA022652R1090 13 HRC fuse link, aM
OFAF000AM35 1SCA022697R2510 13 HRC fuse link, aMOFAF000AM4 1SCA022652R0440 13 HRC fuse link, aM
OFAF000AM40 1SCA022652R1170 13 HRC fuse link, aM
OFAF000AM50 1SCA022697R2690 13 HRC fuse link, aM
OFAF000AM6 1SCA022652R0520 13 HRC fuse link, aM
OFAF000AM63 1SCA022697R2770 13 HRC fuse link, aM
OFAF000AM80 1SCA022697R2850 13 HRC fuse link, aM
OFAF000H10 1SCA022627R0580 7 HRC fuse link, gG
OFAF000H100 1SCA022627R1550 7 HRC fuse link, gG
OFAF000H16 1SCA022627R0660 7 HRC fuse link, gG
OFAF000H2 1SCA022627R0230 7 HRC fuse link, gG
OFAF000H20 1SCA022627R0740 7 HRC fuse link, gG
OFAF000H25 1SCA022627R0820 7 HRC fuse link, gG
OFAF000H32 1SCA022627R0910 7 HRC fuse link, gG
OFAF000H35 1SCA022627R1040 7 HRC fuse link, gG
OFAF000H4 1SCA022627R0310 7 HRC fuse link, gGOFAF000H40 1SCA022627R1120 7 HRC fuse link, gG
OFAF000H50 1SCA022627R1210 7 HRC fuse link, gG
OFAF000H6 1SCA022627R0400 7 HRC fuse link, gG
OFAF000H63 1SCA022627R1390 7 HRC fuse link, gG
OFAF000H80 1SCA022627R1470 7 HRC fuse link, gG
OFAF00AM100 1SCA022697R2930 13 HRC fuse link, aM
OFAF00AM125 1SCA022697R3070 13 HRC fuse link, aM
OFAF00AM160 1SCA022697R3150 13 HRC fuse link, aM
OFAF00H125 1SCA022627R1630 7 HRC fuse link, gG
OFAF00H160 1SCA022627R1710 7 HRC fuse link, gG
OFAF0AM10 1SCA022697R3310 13 HRC fuse link, aM
OFAF0AM100 1SCA022697R5790 13 HRC fuse link, aM
OFAF0AM125 1SCA022697R6090 13 HRC fuse link, aM
OFAF0AM16 1SCA022697R3400 13 HRC fuse link, aM
OFAF0AM160 1SCA022697R6170 13 HRC fuse link, aMOFAF0AM20 1SCA022697R3580 13 HRC fuse link, aM
OFAF0AM200 1SCA022697R6250 13 HRC fuse link, aM
OFAF0AM25 1SCA022697R3660 13 HRC fuse link, aM
OFAF0AM32 1SCA022697R3740 13 HRC fuse link, aM
OFAF0AM35 1SCA022697R3820 13 HRC fuse link, aM
OFAF0AM40 1SCA022697R3910 13 HRC fuse link, aM
OFAF0AM50 1SCA022697R4040 13 HRC fuse link, aM
OFAF0AM6 1SCA022697R3230 13 HRC fuse link, aM
OFAF0AM63 1SCA022697R5610 13 HRC fuse link, aM
OFAF0AM80 1SCA022697R5950 13 HRC fuse link, aM
OFAF0H10 1SCA022627R1980 7 HRC fuse link, gG
OFAF0H100 1SCA022627R2950 7 HRC fuse link, gG
OFAF0H125 1SCA022627R3090 7 HRC fuse link, gG
OFAF0H16 1SCA022627R2010 7 HRC fuse link, gG
OFAF0H160 1SCA022627R3170 7 HRC fuse link, gGOFAF0H20 1SCA022627R2100 7 HRC fuse link, gG
OFAF0H200 1SCA022629R5140 7 HRC fuse link, gG
OFAF0H224 1SCA022629R5220 7 HRC fuse link, gG
OFAF0H25 1SCA022627R2280 7 HRC fuse link, gG
OFAF0H250 1SCA022629R5310 7 HRC fuse link, gG
OFAF0H32 1SCA022627R2360 7 HRC fuse link, gG
OFAF0H35 1SCA022627R2440 7 HRC fuse link, gG
OFAF0H40 1SCA022627R2520 7 HRC fuse link, gG
OFAF0H50 1SCA022627R2610 7 HRC fuse link, gG
OFAF0H6 1SCA022627R1800 7 HRC fuse link, gG
OFAF0H63 1SCA022627R2790 7 HRC fuse link, gG
OFAF0H80 1SCA022627R2870 7 HRC fuse link, gG
OFAF1AM100 1SCA022697R7220 13 HRC fuse link, aM
OFAF1AM16 1SCA022697R6330 13 HRC fuse link, aM
OFAF1AM160 1SCA022697R7490 13 HRC fuse link, aMOFAF1AM20 1SCA022697R6410 13 HRC fuse link, aM
OFAF1AM200 1SCA022697R7570 13 HRC fuse link, aM
OFAF1AM224 1SCA022697R7650 13 HRC fuse link, aM
OFAF1AM25 1SCA022697R6500 13 HRC fuse link, aM
Type Order number Page Description
OFAA2GG200 1SCA022701R0610 10 HRC fuse link, gG
OFAA2GG224 1SCA022703R3910 10 HRC fuse link, gG
OFAA2GG250 1SCA022701R0700 10 HRC fuse link, gGOFAA2GG300 1SCA022703R4040 10 HRC fuse link, gG
OFAA2GG315 1SCA022701R0880 10 HRC fuse link, gG
OFAA2GG32 1SCA022703R3230 10 HRC fuse link, gG
OFAA2GG35 1SCA022703R3310 10 HRC fuse link, gG
OFAA2GG355 1SCA022701R0960 10 HRC fuse link, gG
OFAA2GG40 1SCA022703R3400 10 HRC fuse link, gG
OFAA2GG50 1SCA022703R3580 10 HRC fuse link, gG
OFAA2GG63 1SCA022703R3660 10 HRC fuse link, gG
OFAA2GG80 1SCA022703R3740 10 HRC fuse link, gG
OFAA2H160 1SCA022007R5810 11 HRC fuse link, gG
OFAA2H160-H20 1SCA022299R4840 12 HRC fuse l ink, gG
OFAA2H200 1SCA022007R5990 11 HRC fuse link, gG
OFAA2H200-H20 1SCA022299R5060 12 HRC fuse l ink, gG
OFAA2H250 1SCA022007R6020 11 HRC fuse link, gG
OFAA2H250-H20 1SCA022299R5220 12 HRC fuse l ink, gGOFAA2H315 1SCA022007R6110 11 HRC fuse link, gG
OFAA2H315-H20 1SCA022299R5490 12 HRC fuse link, gG
OFAA2H400 1SCA022007R6290 11 HRC fuse link, gG
OFAA2H400-H20 1SCA022299R5650 12 HRC fuse link, gG
OFAA3AM315 1SCA022701R3550 16 HRC fuse link, aM
OFAA3AM355 1SCA022701R3630 16 HRC fuse link, aM
OFAA3AM400 1SCA022701R3710 16 HRC fuse link, aM
OFAA3AM500 1SCA022701R3800 16 HRC fuse link, aM
OFAA3GG250 1SCA022703R4120 10 HRC fuse link, gG
OFAA3GG300 1SCA022703R4210 10 HRC fuse link, gG
OFAA3GG315 1SCA022701R1000 10 HRC fuse link, gG
OFAA3GG355 1SCA022701R1180 10 HRC fuse link, gG
OFAA3GG400 1SCA022701R1260 10 HRC fuse link, gG
OFAA3GG425 1SCA022706R4030 10 HRC fuse link, gG
OFAA3GG500 1SCA022701R1340 10 HRC fuse link, gGOFAA3H315 1SCA022007R6370 11 HRC fuse link, gG
OFAA3H315-H20 1SCA022299R5810 12 HRC fuse l ink, gG
OFAA3H400 1SCA022007R6450 11 HRC fuse link, gG
OFAA3H400-H20 1SCA022299R6030 12 HRC fuse l ink, gG
OFAA3H500 1SCA022007R6530 11 HRC fuse link, gG
OFAA3H500-H20 1SCA022299R6200 12 HRC fuse link, gG
OFAA3H630 1SCA022007R6610 11 HRC fuse link, gG
OFAA3H630-H20 1SCA022299R6460 12 HRC fuse link, gG
OFAA4AAM1000 1SCA022703R4550 16 HRC fuse link, aM
OFAA4AAM500 1SCA022701R4280 16 HRC fuse link, aM
OFAA4AAM630 1SCA022701R4360 16 HRC fuse link, aM
OFAA4AAM800 1SCA022701R4440 16 HRC fuse link, aM
OFAA4AGG1000 1SCA022699R6360 10 HRC fuse link, gG
OFAA4AGG500 1SCA022660R9770 10 HRC fuse link, gG
OFAA4AGG630 1SCA022660R9850 10 HRC fuse link, gGOFAA4AGG800 1SCA022660R9930 10 HRC fuse link, gG
OFAA4AM1000 1SCA022776R1000 16 HRC fuse link, aM
OFAA4AM500 1SCA022701R3980 16 HRC fuse link, aM
OFAA4AM630 1SCA022701R4010 16 HRC fuse link, aM
OFAA4AM800 1SCA022701R4100 16 HRC fuse link, aM
OFAA4GG1000 1SCA112679R1001 10 HRC fuse link, gG
OFAA4GG500 1SCA022701R1420 10 HRC fuse link, gG
OFAA4GG630 1SCA022701R1510 10 HRC fuse link, gG
OFAA4GG800 1SCA022701R1690 10 HRC fuse link, gG
OFAA5GG1250 1SCA112680R1001 8 HRC fuse link, gG
OFAA5GG1250 1SCA112680R1001 10 HRC fuse link, gG
OFAA5GG1600 1SCA112681R1001 8 HRC fuse link, gG
OFAA5GG1600 1SCA112681R1001 10 HRC fuse link, gG
OFAE504 1SCA022007R6880 18 Fuse replacement handle
OFAE505 2CMA125276R1000 18 Fuse replacement handleOFAF000AM10 1SCA022652R0610 13 HRC fuse link, aM
OFAF000AM16 1SCA022652R0790 13 HRC fuse link, aM
OFAF000AM2 1SCA022652R0360 13 HRC fuse link, aM
OFAF000AM20 1SCA022652R0870 13 HRC fuse link, aM
7/27/2019 hrc fuse.pdf
42/44
Index
42
1SCC317001C0201
Type Order number Page Description
OFAF3AM800 1SCA022701R4790 14 HRC fuse link, aM
OFAF3AN450 1SCA022698R0360 14 HRC fuse link, aM
OFAF3H250 1SCA022627R6350 8 HRC fuse link, gGOFAF3H300 1SCA022627R6430 8 HRC fuse link, gG
OFAF3H315 1SCA022627R6510 8 HRC fuse link, gG
OFAF3H355 1SCA022627R6600 8 HRC fuse link, gG
OFAF3H400 1SCA022627R6780 8 HRC fuse link, gG
OFAF3H425 1SCA022627R6860 8 HRC fuse link, gG
OFAF3H450 1SCA022627R6940 8 HRC fuse link, gG
OFAF3H500 1SCA022627R7080 8 HRC fuse link, gG
OFAF3H630 1SCA022627R7160 8 HRC fuse link, gG
OFAF3H800 1SCA022627R7240 8 HRC fuse link, gG
OFAF4AAM1000 1SCA022698R1840 14 HRC fuse link, aM
OFAF4AAM1250 1SCA022698R1920 14 HRC fuse link, aM
OFAF4AAM500 1SCA022698R1410 14 HRC fuse link, aM
OFAF4AAM630 1SCA022698R1680 14 HRC fuse link, aM
OFAF4AAM800 1SCA022698R1760 14 HRC fuse link, aM
OFAF4AH1000 1SCA022637R4280 8 HRC fuse link, gGOFAF4AH1250 1SCA022637R4360 8 HRC fuse link, gG
OFAF4AH500 1SCA022637R3980 8 HRC fuse link, gG
OFAF4AH630 1SCA022637R4010 8 HRC fuse link, gG
OFAF4AH800 1SCA022637R4100 8 HRC fuse link, gG
OFAF4AM1000 1SCA022698R1090 14 HRC fuse link, aM
OFAF4AM1250 1SCA022698R1170 14 HRC fuse link, aM
OFAF4AM400 1SCA022698R0610 14 HRC fuse link, aM
OFAF4AM500 1SCA022698R0790 14 HRC fuse link, aM
OFAF4AM630 1SCA022698R0870 14 HRC fuse link, aM
OFAF4AM800 1SCA022698R0950 14 HRC fuse link, aM
OFAF4H1000 1SCA022627R7750 8 HRC fuse link, gG
OFAF4H1250 1SCA022627R7830 8 HRC fuse link, gG
OFAF4H400 1SCA022627R7320 8 HRC fuse link, gG
OFAF4H500 1SCA022627R7410 8 HRC fuse link, gG
OFAF4H630 1SCA022627R7590 8 HRC fuse link, gGOFAF4H800 1SCA022627R7670 8 HRC fuse link, gG
OFAM00AM10 1SCA022386R2800 15 HRC fuse link, aM
OFAM00AM100 1SCA022324R8610 15 HRC fuse link, aM
OFAM00AM100-H20 1SCA022339R5080 17 HRC fuse link, aM
OFAM00AM10-H20 1SCA022386R7430 17 HRC fuse link, aM
OFAM00AM125 1SCA022324R8880 15 HRC fuse link, aM
OFAM00AM125-H20 1SCA022339R5240 17 HRC fuse link, aM
OFAM00AM16 1SCA022323R6520 15 HRC fuse link, aM
OFAM00AM160 1SCA022324R9000 15 HRC fuse link, aM
OFAM00AM160 1SCA022324R9000 16 HRC fuse link, aM
OFAM00AM160-H20 1SCA022339R5410 17 HRC fuse link, aM
OFAM00AM16-H20 1SCA022339R3460 17 HRC fuse link, aM
OFAM00AM2 1SCA022640R4960 15 HRC fuse link, aM
OFAM00AM20 1SCA022323R6790 15 HRC fuse link, aM
OFAM00AM20-H20 1SCA022339R3620 17 HRC fuse link, aMOFAM00AM25 1SCA022324R2410 15 HRC fuse link, aM
OFAM00AM25-H20 1SCA022339R3890 17 HRC fuse link, aM
OFAM00AM2-H20 1SCA022640R5000 17 HRC fuse l ink, aM
OFAM00AM32 1SCA022324R2680 15 HRC fuse link, aM
OFAM00AM32-H20 1SCA022339R4010 17 HRC fuse link, aM
OFAM00AM4 1SCA022386R2630 15 HRC fuse link, aM
OFAM00AM40 1SCA022324R2840 15 HRC fuse link, aM
OFAM00AM40-H20 1SCA022339R4270 17 HRC fuse link, aM
OFAM00AM4-H20 1SCA022386R7270 17 HRC fuse link, aM
OFAM00AM50 1SCA022324R2500 15 HRC fuse link, aM
OFAM00AM50-H20 1SCA022339R4430 17 HRC fuse link, aM
OFAM00AM6 1SCA022386R2710 15 HRC fuse link, aM
OFAM00AM63 1SCA022324R2760 15 HRC fuse link, aM
OFAM00AM63-H20 1SCA022339R4600 17 HRC fuse link, aM
OFAM00AM6-H20 1SCA022386R7350 17 HRC fuse link, aMOFAM00AM80 1SCA022324R2920 15 HRC fuse link, aM
OFAM00AM80-H20 1SCA022339R4860 17 HRC fuse link, aM
OFAM1AM100 1SCA022194R6740 15 HRC fuse link, aM
OFAM1AM100-H20 1SCA022299R6620 17 HRC fuse link, aM
Type Order number Page Description
OFAF1AM250 1SCA022697R7730 13 HRC fuse link, aM
OFAF1AM315 1SCA022697R7810 13 HRC fuse link, aM
OFAF1AM32 1SCA022697R6680 13 HRC fuse link, aMOFAF1AM35 1SCA022697R6760 13 HRC fuse link, aM
OFAF1AM40 1SCA022697R6840 13 HRC fuse link, aM
OFAF1AM50 1SCA022697R6920 13 HRC fuse link, aM
OFAF1AM63 1SCA022697R7060 13 HRC fuse link, aM
OFAF1AM80 1SCA022697R7140 13 HRC fuse link, aM
OFAF1H100 1SCA022627R4140 7 HRC fuse link, gG
OFAF1H125 1SCA022627R4220 7 HRC fuse link, gG
OFAF1H16 1SCA022627R3250 7 HRC fuse link, gG
OFAF1H160 1SCA022627R4310 7 HRC fuse link, gG
OFAF1H20 1SCA022627R3330 7 HRC fuse link, gG
OFAF1H200 1SCA022627R4490 7 HRC fuse link, gG
OFAF1H224 1SCA022627R4570 7 HRC fuse link, gG
OFAF1H25 1SCA022627R3410 7 HRC fuse link, gG
OFAF1H250 1SCA022627R4650 7 HRC fuse link, gG
OFAF1H315 1SCA022627R4730 7 HRC fuse link, gGOFAF1H32 1SCA022627R3500 7 HRC fuse link, gG
OFAF1H35 1SCA022627R3680 7 HRC fuse link, gG
OFAF1H355 1SCA022701R4520 7 HRC fuse link, gG
OFAF1H40 1SCA022627R3760 7 HRC fuse link, gG
OFAF1H50 1SCA022627R3840 7 HRC fuse link, gG
OFAF1H63 1SCA022627R3920 7 HRC fuse link, gG
OFAF1H80 1SCA022627R4060 7 HRC fuse link, gG
OFAF2AM100 1SCA022697R8620 14 HRC fuse link, aM
OFAF2AM125 1SCA022697R8710 14 HRC fuse link, aM
OFAF2AM160 1SCA022697R8890 14 HRC fuse link, aM
OFAF2AM200 1SCA022697R8970 14 HRC fuse link, aM
OFAF2AM224 1SCA022697R9010 14 HRC fuse link, aM
OFAF2AM250 1SCA022697R9190 14 HRC fuse link, aM
OFAF2AM300 1SCA022697R9270 14 HRC fuse link, aM
OFAF2AM315 1SCA022697R9350 14 HRC fuse link, aMOFAF2AM35 1SCA022697R8110 14 HRC fuse link, aM
OFAF2AM355 1SCA022697R9430 14 HRC fuse link, aM
OFAF2AM40 1SCA022697R8200 14 HRC fuse link, aM
OFAF2AM400 1SCA022697R9510 14 HRC fuse link, aM
OFAF2AM50 1SCA022697R8380 14 HRC fuse link, aM
OFAF2AM500 1SCA022697R9600 14 HRC fuse link, aM
OFAF2AM63 1SCA022697R8460 14 HRC fuse link, aM
OFAF2AM80 1SCA022697R8540 14 HRC fuse link, aM
OFAF2H100 1SCA022627R5380 8 HRC fuse link, gG
OFAF2H125 1SCA022627R5460 8 HRC fuse link, gG
OFAF2H160 1SCA022627R5540 8 HRC fuse link, gG
OFAF2H200 1SCA022627R5620 8 HRC fuse link, gG
OFAF2H224 1SCA022627R5710 8 HRC fuse link, gG
OFAF2H25 1SCA115948R1001 8 HRC fuse link, gG
OFAF2H250 1SCA022627R5890 8 HRC fuse link, gGOFAF2H300 1SCA022627R5970 8 HRC fuse link, gG
OFAF2H315 1SCA022627R6010 8 HRC fuse link, gG
OFAF2H35 1SCA022627R4810 8 HRC fuse link, gG
OFAF2H355 1SCA022627R6190 8 HRC fuse link, gG
OFAF2H40 1SCA022627R4900 8 HRC fuse link, gG
OFAF2H400 1SCA022627R6270 8 HRC fuse link, gG
OFAF2H425 1SCA022706R3900 8 HRC fuse link, gG
OFAF2H50 1SCA022627R5030 8 HRC fuse link, gG
OFAF2H500 1SCA022701R4610 8 HRC fuse link, gG
OFAF2H63 1SCA022627R5110 8 HRC fuse link, gG
OFAF2H80 1SCA022627R5200 8 HRC fuse link, gG
OFAF3AM250 1SCA022697R9780 14 HRC fuse link, aM
OFAF3AM300 1SCA022697R9860 14 HRC fuse link, aM
OFAF3AM315 1SCA022697R9940 14 HRC fuse link, aM
OFAF3AM355 1SCA022698R0010 14 HRC fuse link, aMOFAF3AM400 1SCA022698R0100 14 HRC fuse link, aM
OFAF3AM425 1SCA022698R0280 14 HRC fuse link, aM
OFAF3AM500 1SCA022698R0440 14 HRC fuse link, aM
OFAF3AM630 1SCA022698R0520 14 HRC fuse link, aM
7/27/2019 hrc fuse.pdf
43/44
Index
43
1SCC317001C0201
Type Order number Page Description
OFAM1AM125 1SCA022194R6580 15 HRC fuse link, aM
OFAM1AM125-H20 1SCA022299R6890 17 HRC fuse link, aM
OFAM1AM160 1SCA022103R6100 15 HRC fuse link, aMOFAM1AM160-H20 1SCA022299R7010 17 HRC fuse link, aM
OFAM1AM200 1SCA022103R6360 15 HRC fuse link, aM
OFAM1AM200-H20 1SCA022299R7270 17 HRC fuse link, aM
OFAM1AM250 1SCA022103R6520 15 HRC fuse link, aM
OFAM1AM250-H20 1SCA022299R7430 17 HRC fuse link, aM
OFAM1AM50 1SCA022194R7390 15 HRC fuse link, aM
OFAM1AM50-H20 1SCA022299R7600 17 HRC fuse l ink, aM
OFAM1AM63 1SCA022194R7120 15 HRC fuse link, aM
OFAM1AM63-H20 1SCA022299R7860 17 HRC fuse l ink, aM
OFAM1AM80 1SCA022194R6910 15 HRC fuse link, aM
OFAM1AM80-H20 1SCA022299R8080 17 HRC fuse l ink, aM
OFAM2AM125 1SCA022194R6310 15 HRC fuse link, aM
OFAM2AM125-H20 1SCA022299R8240 17 HRC fuse link, aM
OFAM2AM160 1SCA022194R6150 15 HRC fuse link, aM
OFAM2AM160-H20 1SCA022299R8410 17 HRC fuse link, aMOFAM2AM200 1SCA022194R5510 15 HRC fuse link, aM
OFAM2AM200-H20 1SCA022299R8670 17 HRC fuse link, aM
OFAM2AM250 1SCA022194R5340 15 HRC fuse link, aM
OFAM2AM250-H20 1SCA022299R8830 17 HRC fuse link, aM
OFAM2AM315 1SCA022103R0670 15 HRC fuse link, aM
OFAM2AM315-H20 1SCA022299R9050 17 HRC fuse link, aM
OFAM2AM355 1SCA022103R0670 15 HRC fuse link, aM
OFAM2AM355-H20 1SCA022299R9210 17 HRC fuse link, aM
OFAM2AM400 1SCA022103R0830 15 HRC fuse link, aM
OFAM2AM400-H20 1SCA022299R9480 17 HRC fuse link, aM
OFAM3AM315 1SCA022194R4960 15 HRC fuse link, aM
OFAM3AM315-H20 1SCA022299R3520 17 HRC fuse link, aM
OFAM3AM355 1SCA022194R4700 15 HRC fuse link, aM
OFAM3AM355-H20 1SCA022299R3790 17 HRC fuse link, aM
OFAM3AM400 1SCA022194R4530 15 HRC fuse link, aMOFAM3AM400-H20 1SCA022299R3950 17 HRC fuse link, aM
OFAM3AM500 1SCA022103R1050 15 HRC fuse link, aM
OFAM3AM500-H20 1SCA022299R4170 17 HRC fuse link, aM
OFAM3AM630 1SCA022103R1210 15 HRC fuse link, aM
OFAM3AM630-H20 1SCA022299R4330 17 HRC fuse link, aM
OFAM3AM800 1SCA022655R7360 15 HRC fuse link, aM
OFAM3AM800-H20 1SCA022655R7440 17 HRC fuse link, aM
OFM260 1SCA022459R8560 18 Electronic fuse monitor
OFM690 1SCA022459R8480 18 Electronic fuse monitor
OFMZX2 1SCA022475R9910 18 Crimp terminal
OFS260 1SCA022716R0180 18 Electronic fuse monitor
OFS690 1SCA022715R9920 18 Electronic fuse monitor
7/27/2019 hrc fuse.pdf
44/44
Contact us
ABB Oy
Low Voltage Switches
P.O. Box 622
FI-65101 Vaasa, Finland
Phone: +358 10 22 11
Fax: +358 10 22 45708
E-Mail: [email protected]
www.abb.com
CatalogueOF1GB
10-04,
1SCC317001C0201The technical data and dimensions are valid at the time of
printing. We reserve the right to subsequent alterations.
ProductedbyA&V
Insin
ritOy/Tekninenviestint,
Vaasa,
Finland