Test Procedures for Fire Fighting System Project Name : Site Name : Room Name : Date :  Fire Panel MRP-2002 Test Sheet  System Trouble Test  Power Supply Test Mains Test (AC 220 v.) Disconnect the 220 AC volt  Green AC Power LED LABLE OFF  The LCD Display will indicate AC FAULT  Yellow Trouble LED LABLE ON  Internal Buzzer Sound Press ACK/STEP Button to mute internal buzzer Battery Test Disconnect the Battery  Green AC Power LED ON  The LCD Display will indicate NO BATTERY  Yellow Trouble LED ON  Internal Buzzer Sound Press ACK/STEP Button to mute internal buzzer  Earth Fault Test Connect any cable to a steel conduit  Green AC Power LED ON  Yellow System Trouble LED ON  Internal Buzzer Sound Press ACK/STEP Button to mute internal buzzer

HPCO2 Test Sheet

Embed Size (px)

Citation preview

Page 1: HPCO2 Test Sheet

8/6/2019 HPCO2 Test Sheet

http://slidepdf.com/reader/full/hpco2-test-sheet 1/6

Test Procedures for Fire Fighting SystemProject Name :

Site Name :

Room Name :

Date :

 Fire Panel MRP-2002 Test Sheet

 System Trouble Test

 Power Supply Test

Mains Test (AC 220 v.)

Disconnect the 220 AC volt

  Green AC Power LED LABLE OFF

  The LCD Display will indicate AC FAULT

  Yellow Trouble LED LABLE ON

  Internal Buzzer Sound

Press ACK/STEP Button to mute internal buzzer

Battery Test

Disconnect the Battery

  Green AC Power LED ON

  The LCD Display will indicate NO BATTERY

  Yellow Trouble LED ON

  Internal Buzzer Sound

Press ACK/STEP Button to mute internal buzzer

  Earth Fault Test

Connect any cable to a steel conduit

  Green AC Power LED ON

  Yellow System Trouble LED ON  Internal Buzzer Sound

Press ACK/STEP Button to mute internal buzzer

Page 2: HPCO2 Test Sheet

8/6/2019 HPCO2 Test Sheet

http://slidepdf.com/reader/full/hpco2-test-sheet 2/6

 

  Initiating Zones Trouble Test

Disconnect any detector from its base, disconnect any wire from zone 1 or 2

  Green AC Power LED ON

  The LCD Display will indicate OPEN FAULT(Open 2- wire smoke)

  Yellow Trouble LED ON

  Internal Buzzer Sound

Press ACK/STEP Button to mute internal buzzer

  Manual Release Trouble Test

Disconnect Manual Release from zone 3

  Green AC Power LED ON

  LCD Display will indicate OPEN FAULT (Open Rel)

  Yellow Trouble LED ON

  Internal Buzzer Sound

Press ACK/STEP Button to mute internal buzzer

  Abort Release SW Trouble Test

Disconnect Manual Release from zone 4

  Green AC Power LED ON  LCD Display will indicate OPEN FAULT (Open Abort Rel SW)

  Yellow Trouble LED ON

  Internal Buzzer Sound

Press ACK/STEP Button to mute internal buzzer

  Notification Appliance Trouble Test

Disconnect the Bell or Siren from its base, disconnect any wire from O/P 1&2

  Green AC Power LED ON

  LCD Display will indicate OPEN FAULT (Open NAC 1&2)

  Yellow Trouble LED ON  Internal Buzzer Sound

Press ACK/STEP Button to mute internal buzzer

Page 3: HPCO2 Test Sheet

8/6/2019 HPCO2 Test Sheet

http://slidepdf.com/reader/full/hpco2-test-sheet 3/6

  Releasing Circuits Trouble Test

Disconnect any wire from O/P 3&4

  Green AC Power LED ON

  LCD Display will indicate OPEN FAULT (Open NAC 3&4)

  Yellow Trouble LED ON

  Circuit Trouble LED ON

  Internal Buzzer Sound

Press ACK/STEP Button to mute internal buzzer

--------------------------------------------------------------  System Alarm & Releasing Test

Disconnect the Electric Actuator from the cylinder valve

  Test Zone 1 or Zone 2 (Alarm Test)

Test any Detector from zone 1 or zone 2 using recommended test magnet

  Green AC Power LED ON

  LCD Display will indicate ALARM 2-Wire Smoke

  Internal Buzzer Sound

  1-st Alarm Notification Circuit Activated (BELL) O/P1

Press ACK/STEP Button to mute internal buzzer

Press Alarm Silence Button to Silence the Bell

Press Rest Button to Rest the system

  Test Zone 1 and Zone 2 (Releasing Test)

Test any Detector from zone 1 and zone 2 using recommended test magnet

  Green AC Power LED ON

  LCD Display will indicate ALARM 2-Wire Smoke

  Internal Buzzer Sound

  1-st Alarm Notification Circuit Activated (BELL) O/P1  2-nd Alarm Notification Circuit Activated (SIREN) O/P2

  Releasing Circuit Activated After The Delay Time O/P3

  Check the operation of the Electric Actuator.

Press ACK/STEP Button to mute internal buzzer

Press Alarm Silence Button to Silence the Bell and the Siren

Press Rest Button to Rest the system

Page 4: HPCO2 Test Sheet

8/6/2019 HPCO2 Test Sheet

http://slidepdf.com/reader/full/hpco2-test-sheet 4/6

  Test Zone 1 and Zone 2 (Releasing Test with Abort)

Test any Detector from zone 1 and zone 2 using recommended test magnet

  Green AC Power LED ON

  LCD Display will indicate ALARM 2-Wire Smok

  Internal Buzzer Sound

  1-st Alarm Notification Circuit Activated (BELL) O/P1

  2-nd Alarm Notification Circuit Activated (SIREN) O/P2

  Press and Hold the Abort switch for 2 sec.

  Releasing Circuit Activated After The Delay Time (FROM 30Sec to 20MIN)

  Check the operation of the Electric Actuator.

Press ACK/STEP Button to mute internal buzzer

Press Alarm Silence Button to Silence the Bell and the Siren

Press Rest Button to Rest the system

  Manual Release Test (Releasing Test)

Push In and Pull Down the manual gas release

  Green AC Power LED ON

  Internal Buzzer Sound

  2-nd Alarm Notification Circuit Activated (SIREN) O/P2

  Releasing Circuit Activated Immediately O/P3

Press ACK/STEP Button to mute internal buzzer

Press Alarm Silence Button to Silence the Bell

Press Rest Button to Rest the system

-------------------------------------------------------------------------------------------  

Page 5: HPCO2 Test Sheet

8/6/2019 HPCO2 Test Sheet

http://slidepdf.com/reader/full/hpco2-test-sheet 5/6

  Pipes Pneumatically Test Sheet

Refer to NFPA2001 to test the

6-3.2.1 High Pressures system

All piping from the carbon dioxide supply to the nozzle shall be subjected to a

minimum pressure of 600 psig (4137 Kpa). The leakage during a 2-mintee period

shall not exceed a pressure drop of 10 percent

Duration:

Start time: Pressure bar

End time: Pressure bar

----------------------------------------------

---------------------------------------------  

Signatures:

Owner Representative.

Consultant Representative.

Contractor Representative.

Supplier Representative.