Hot water monitoring system

Kristján Guðmundur Birgisson

Final thesis for B.Sc. degree

Keilir Institute of Technology

University of Iceland

School of Engineering and Natural Sciences

Page 2: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 3: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

Hot water monitoring system

Kristján Guðmundur Birgisson

24 ECTS thesis submitted in partial fulfilment of a Baccalaureus Scientiarum degree in Mechatronic Engineering Technology

Advisors Burkni Pálsson

Guðmundur Borgþórsson

Keilir Institute of Technology

University of Iceland

School of Engineering and Natural Sciences

Reykjanesbær, September 2015

Page 4: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

Hot water monitoring system 24 ECTS thesis submitted in partial fulfilment of a Baccalaureus Scientiarum degree in Mechatronic Engineering Technology Copyright © 2015 Kristján Guðmundur Birgisson All rights reserved Keilir Institute of Technology School of Engineering and Natural Sciences University of Iceland Grænásbraut 910 235 Reykjanesbær Sími: 578 4000 Bibliographic information: Kristján Guðmundur Birgisson, 2015, Hot water monitoring system, BSc thesis, Keilir Institute of Technology, University of Iceland, pp. 92. Printing: Háskólaprent ehf., Fálkagata 2, 107 Reykjavík Reykjanesbær, September 2015

Page 5: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

v

Abstract

One of the main uses of geothermal water is for heating. About 98% of buildings in

Iceland use geothermal water for heat. In residence buildings, a flow control frame

distributes the water between the potable water and heating. In the entire flow control

frame there are optical gauges that have to be read manually, which is not optimal way for

the homeowner to check his usage.

This project is to set up a way to monitor the hot water usage by implementing electronic

sensors to measure temperature, flow and pressure. The sensors are connected to a

microcontroller that send the values from the sensors to a database via the internet. A

website will display the values that are stored in the database with charts and gauges.

To test the concept of using electronic sensors and controller, a closed system was

constructed, to have control of the flow, temperature and pressure. Simulated malfunctions

were used to test the system. The system successfully detected the malfunctions and a led

light lit up to indicate what type of problem occurred.

A prototype of the monitoring system was installed into a real flow control frame in a

residential house. The system runs autonomously by sending values at even intervals to a

database that displays the readings on a website for the user of the system to monitor the

hot water usage.

Page 6: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 7: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

vii

Útdráttur

Eitt af aðalnotagildum jarðvarmans er til kyndingar. Á Íslandi er jarðvarmi notaður til

upphitunar á um það bil 98% af húsum. Í íbúðar húsum er flæði heitavatnsins stjórnað í

sérhönnuðum röraramma (kallað grindin). Í grind þessari fer fram deiling á notkun vatnsins

annars vegar til húsahitunar og hins vegar til neyslu á vatninu (þvotta og fleira). Í

flæðirammanum eru skynjarar, sem þarf að lesa af til að fylgjast með notkuninni sem er

ekki ákjósanleg leið.

Verkefnið fjallar um að koma upp eftirlitskerfi fyrir notkunina á heitu vatni og nýtingu

þess með því að setja rafmagns skynjara í mælagrindina sem mæla á hita, flæði og þrýsting

á vökvanum. Skynjararnir eru tengdir örtölvu, ásamt búnaði til að gefa viðvörunarljós ef

ekki er allt eðlilegt, sem sendir svo gögnin yfir til gagnagruns í gegnum internetið. Vefsíða

er síðan notuð til þess að sýna gildin sem geymd eru í gagnagrunninum með línuriti og

skífumálum.

Til að prófa hugmyndina, við að nota rafmagns skynjara og örtölvu, var smíðað lokað kerfi

til þess að hafa betri stjórn á flæðinu, hitanum og þrýstingum til prófunar. Bilanir voru

framkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði

góðum árangri að skynja bilanirnar og að kveikja á ljósi til þess að gefa til kynna hvaða

bilun var um að ræða.

Frumgerð af eftirlitskerfinu var komið fyrir á raunverulegu heitavatns kerfi í íbúðar

húsnæði. Kerfið sendir gögn með jöfnu tímabili til gagnagruns sem er síðan sýnt á vefsíðu

þar sem notandi kerfisins getur fylgst með notkuninni á heitavatninu og nýtingu þess.

Page 8: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 9: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

ix

Table of Contents

List of figures ...................................................................................................................... xi

List of Tables ..................................................................................................................... xiii

Abbreviations ..................................................................................................................... xv

Acknowledgements .......................................................................................................... xvii

1 Introduction ..................................................................................................................... 1 1.1 Water monitoring systems ....................................................................................... 2

1.2 Solution ................................................................................................................... 3

2 Background ..................................................................................................................... 5 2.1 Embedded systems .................................................................................................. 5

2.1.1 Microcontrollers ............................................................................................. 6 2.1.2 Processors ...................................................................................................... 7 2.1.3 How processors works ................................................................................... 7

2.2 Information distribution and holding ...................................................................... 9

2.2.1 Database ......................................................................................................... 9 2.2.2 Distribution .................................................................................................. 10

2.3 Water monitoring systems ..................................................................................... 11

3 Analysis .......................................................................................................................... 15 3.1 Controller Systems ................................................................................................ 16

3.2 Sensors................................................................................................................... 18 3.2.1 Temperature sensors .................................................................................... 18 3.2.2 Pressure sensor ............................................................................................. 21 3.2.3 Flow sensor .................................................................................................. 23

4 Build ............................................................................................................................... 25 4.1 Measurements ........................................................................................................ 25

4.2 Prototype ............................................................................................................... 27 4.3 Programming ......................................................................................................... 28

4.3.1 Arduino Yún ................................................................................................ 29 4.3.2 Database and Website .................................................................................. 31

4.4 Cost ........................................................................................................................ 32

5 Result .............................................................................................................................. 35 5.1 Alarm System ........................................................................................................ 36 5.2 Testing the system ................................................................................................. 37

6 Addition ......................................................................................................................... 41 6.1 Setting up the Sensors ........................................................................................... 42

6.1.1 Adding the sensors to the heat frame ........................................................... 44 6.2 Connections from sensors to Arduino Yún ........................................................... 45

Page 10: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

x

6.3 Database and Webpage .......................................................................................... 46 6.3.1 Database ....................................................................................................... 46 6.3.2 Calculation from the database ..................................................................... 47 6.3.3 Webpage ...................................................................................................... 49

6.4 The working of the system ..................................................................................... 52 6.5 Cost after addition to project .................................................................................. 53

7 Conclusion ...................................................................................................................... 55

8 Discussion ....................................................................................................................... 57 8.1 First test .................................................................................................................. 57

8.2 Second test ............................................................................................................. 57

9 Future Work .................................................................................................................. 59

Reference ............................................................................................................................. 61

Appendix A: Specification of Arduino Ýun Development Board .................................. 63

Appendix B: Arduino Yún electrical schematic .............................................................. 65

Appendix C: Specification of the DS18B20 temperature sensor ................................... 67

Appendix D: Specification of the flow sensor .................................................................. 69

Appendix E: Specification of the pressure sensor ........................................................... 71

Appendix: Time Schedules ................................................................................................ 73

Page 11: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

xi

List of figures

Figure 1 Hot Water Supply System for the Greater Reykjavík Area .................................... 1

Figure 2 Examples of Embedded Systems ............................................................................ 5

Figure 3 Basic Structure and Block Diagram of a Microcontroller ...................................... 6

Figure 4 Main Hardware Components of a Processor ........................................................... 8

Figure 5 Basic Platform for a Working Website ................................................................. 11

Figure 6 Flow Controller Frame from HS Veitur HF .......................................................... 12

Figure 7 PIN Layout For DS18B20 Temperature Sensor ................................................... 20

Figure 8 Multiple DS18B20 Temperature Sensors Connected to the Same Data Line ...... 21

Figure 9 Multiple DS18B20 Temperature Sensors Connected to the Same Data Line

with Pins One and Three Shorted ..................................................................... 21

Figure 10 Explanation of Magnetic Flow ............................................................................ 23

Figure 11 The Closed System that Tests the Chosen Equipment and Idea ......................... 27

Figure 12 Communication Between Both Processors ......................................................... 29

Figure 13 Input and Output Pins from the Arduino Yún ..................................................... 30

Figure 14 Values from the Sensors to MySQL Database .................................................... 31

Figure 15 Graphical Visualization of the Data from the Database Shown in Website. ...... 32

Figure 16 Values from the Sensors Shown in Webpage ..................................................... 35

Figure 17 Work Diagram for the Values from the Sensors to the Database and from

the Database to the Webpage ............................................................................ 36

Figure 18 Water Temperature Anomaly .............................................................................. 37

Figure 19 Yellow Warning Light Turns On when the Temperature in not within the

Limit Range ...................................................................................................... 37

Figure 20 Pressure in the System Falls Down ..................................................................... 38

Figure 21 Green Warning Light Turns On when the Pressure in not within the Limit

Range ................................................................................................................ 38

Page 12: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

xii

Figure 22 Flow in the System Falls Down .......................................................................... 39

Figure 23 Red Warning Light Turns On when the Flow in not within the Limit Range .... 39

Figure 24 Before Implementing Cross Fittings in to the Flow Controller Frame A)

Figure on Right Shows Where the Water Enters Into the Frame. B)

Figure on Left Shows When the Water Enters the Snow Melting System

and Exits the Frame .......................................................................................... 42

Figure 25 After Implementing Cross Fittings to the Flow Controller Frame. A) Left.

B) Right ............................................................................................................ 43

Figure 26 Pipe Assembly when the Cross Fittings are Inserted into .................................. 43

Figure 27 Thread Fittings and Insulation for the Temperature Sensor ............................... 44

Figure 28 Sensors Connected to the Flow Controller Frame .............................................. 44

Figure 29 Electrical Box with Arduino Yún and Connection with Sensor with PCB ........ 45

Figure 30 Login Page for the Website ................................................................................ 49

Figure 31 Facebook Login Page .......................................................................................... 50

Figure 32 The Main Web page for the Monitoring System ................................................ 50

Figure 33 Web Page that Displays all the Temperature Measurements ............................. 51

Figure 34 Working of the Monitoring System .................................................................... 52

Figure 35 Appendix B-1 Block Diagram of Arduino Yún .................................................. 65

Figure 36 Appendix B-2 Power Block Diagram ................................................................. 66

Figure 37 Original Time Schedule ...................................................................................... 73

Figure 38 New Time Schedual ............................................................................................ 74

Page 13: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

xiii

List of Tables

Table 1 Incidents that exceed one million krónur ................................................................. 2

Table 2 Difference Between the First Processor to the Latest Model From Intel ................. 7

Table 3 Characteristics of RISK/CISC Instruction Set Architecture .................................... 9

Table 4 Material of Flow Controller Frame from HS Veitur HF ........................................ 12

Table 5 Comparisons of Specifications for the Development Boards................................. 16

Table 6 Comparisons for I/O for the Development Boards................................................. 17

Table 7 Typical Temperature Sensor Characteristics .......................................................... 19

Table 8 Comparisons of Temperature Sensors Models ....................................................... 20

Table 9 Notes and Terminology for Pressure Sensors ........................................................ 22

Table 10 Comparisons of Pressure Sensors Models ............................................................ 23

Table 11 Comparisons of Flow Sensors Models ................................................................. 24

Table 12 Flow Measurements Taken on a Real Controller Flow Frame............................. 25

Table 13 Temperature Measurements ................................................................................. 26

Table 14 Pressure Measurements ........................................................................................ 26

Table 15 Bill of Material ..................................................................................................... 27

Table 16 Cost of Material and Work ................................................................................... 33

Table 17 Calculation of the Temperature for 13 Days of Data Points ................................ 47

Table 18 Calculation of the Pressure for 13 Days of Data Points ....................................... 48

Table 19 Cost after Modifacations of Project ...................................................................... 53

Page 14: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 15: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

xv

Abbreviations

ARM Advanced RISC Machine, Acorn RISC Machine

ADC Analog to Digital Converter

ALU Arithmetic and Logic Unit

BSD Berkeley Software Distribution

CISK Complex Instruction Set Computer

CPU Central Processing Unit

CSS Cascading Style Sheet

DAC Digital to Analog Converter

DBMS Database Management Systems

DSP Digital Signal Processor

EEPROM Electrically Erasable Programmable Read Only Memory

GPU Graphics Processing Unit

HTML Hyper Text Markup Language

I/O Input and Output

IR Instruction Register

ISA Instruction set Architecture.

PCB Printed Circuit Board

PDF Portable Document Format

PHP Hypertext Preprocessor

PLC Programmable Logic Controller

PC Program Counter

RAM Random Access Memory

RISK Reduced Instruction Set Computing

ROM Read Only Memory

Page 16: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

xvi

SSH Secure Shell

UART Universal Asynchronous Receiver/Transmitter

URL Uniform Resource Locator

Page 17: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

xvii

Acknowledgements

I want to thank

Kjartan Birgisson, Sigríður Andrea Ásgeirsdóttir for their help.

Magni Þór Birgisson for his help and use of dataserver and web site storage.

Guðrún Þorbjörg Kristjánsdóttir for help in making figures in this thesis.

Birgir Óskarsson for use of the tank and drill that was used in testing.

Birgir and Guðrún for allowing to implement the monitoring system to their house for

testing.

Orkuveita Reykjavíkur for lending of a regulated flow sensor.

Page 18: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 19: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

1

1 Introduction

One of Iceland´s most valuable resources is its plentiful geothermal water. The hot water

is either used directly or indirectly. In some places hot water is pumped from the ground

into pipes and then flows through pipes towards the customers and their houses. The

other way is to heat cold ground water through geothermal energy plants and used that

through same system pipes to heat houses. These methods are both used in the Reykjavik

area Figure 11.

Figure 1 Hot Water Supply System for the Greater Reykjavík Area

About 98% of houses in Iceland use the hot water for heating2. This kind of heating is

used in all types and kinds of facilities, for example business, department buildings,

administrative buildings, and residential buildings.

Many Icelanders own summerhouses as a second home, that are only used irregularly and

a lot of them are heated with hot water. That means that they are empty for quite some

1 Source: https://www.or.is/vorur-thjonusta/heitt-vatn#hitaveita_a_hofudborgarsvaedinu Accessed:

14.9.2015 2 Source: https://www.hsveitur.is/images/mv_hitamenning.pdf Accsessed: 12.05.2015

Page 20: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

2

time and no one is there to regulate or monitor the use of the hot water or the condition of

the heating system3.

About 90% of all hot water usage is for heating purposes4 and the rest is used for washing,

cleaning and personal hygiene. The main suppliers of hot water are either state or county.

1.1 Water monitoring systems

There are not many water monitoring systems that are generally installed in buildings

other than those installed to the flow controller frame by the supplier. The only two

companies in Iceland that offers a package that includes a water leakage detector is

Securitas5 and Öryggismiðstöðin

6. The water leakage detector is only one sensor, which

means that there could be massive water damage before the sensor indicates leakage.

Mannvirkjastofnun7 announced in the year 2014 that the number of reported water

damages was 7.387. Of 7.387 incidents, 1.442 were not liable and therefore the owner had

to pay for the damages. In 418 incidents, the cost was equal to or exceeded one million

krónur:

Table 1 Incidents that exceed one million krónur

Cost (million Kr) Incedence

4 < 22

3 - 4 24

2 - 3 56

1 - 2 316

The total cost of water damage was close to 2.4 billion krónur. The insurance companies

payed out about 1.7 billion krónur. The average cost of damage that was not liable is

about 430 million krónur. The own risk policy of the insurance company had the home

owners pay over 700 million krónur.

These numbers show how massive the cost can be when dealing with water damages and

how the homeowners had to frequently cover big financial costs. In some instances they

had to abandon their homes for some days because of repairs.

Water monitoring system is needed that can help prevent some of the damages that occur

to homes and buildings.

The audience of this thesis are University students and professional that have at least, a

basic understanding and knowledge of programming and electronic components

3 Source: https://www.vis.is/einstaklingar/forvarnir/fritimi/sumarbustadur/vatnsvarnir/ Accessed: 13.05.2015

4 Source: https://www.or.is/spurningar-og-rad/sparnadarrad/hushitun Accessed: 12.05.2015

5 Source: http://www.securitas.is/Heimavorn/heimavorn.html Accessed: 14.9.2015

6 Source: https://www.oryggi.is/ Accessed: 15.9.2015

7Source: http://www.mbl.is/frettir/innlent/2015/05/21/tjon_vegna_vatnsleka_2_4_milljardar/

Accessed:10.9.2015

Page 21: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

3

1.2 Solution

The main problem with monitoring the flow controller frame is that all the sensors are

optical gauges which means that they have to be read manually. To maintain the flow

system and check if operations are running normal the sensor have to be regularly

monitored and written down to check for anomalies.

In this thesis there will be used another way of monitoring the usage by using electronic

sensors that are connected to a controller. The controller is connected to a database that

will collect and hold all values and then displayed for the user.

Page 22: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 23: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

5

2 Background

The idea was to construct and set up a device that could monitor and measure the usage of

hot water for heating houses. This device would be used to monitor the usage, fluctuations

in flow, heat and pressure, and send the readings to a server. The device will include

sensors located within the hot water pipes and a microcontroller to assemble the readings

and transmit the results. Each step is documented to include what kind of equipment is

needed to accomplish those measurements.

In order to take measurements the sensors are located at strategic points in the heat frame

and they send signal to a microcontroller. The processor´s functions are to interpret and

convert the signals from the sensors to an understandable format.

The measurements are then automatically sent to a database that will store the information.

The information is set up in a table and collected from the server, and the information can

be shown on a website. The website is set up for the user to easily read the information

from the sensors.

2.1 Embedded systems

Embedded systems consist of some sort of controlling mechanism such as a

microcontroller or microprocessor. In other words “A physical system that employs

computer control for a specific purpose, rather than for a general-purpose computation, is

referred to as an embedded system” [1,386].

Figure 2 Examples of Embedded Systems

Page 24: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

6

Figure 28 shows examples of embedded systems as they are used in remote controllers, cd

players/radios, watches and satellites that have a specific purpose for controlling or

monitoring.

The setup for an embedded system must be easily accessible in order to make repairs, for

example, if a part has malfunctioned or the system needs to be replaced by a newer

version.

The purpose for embedded systems for this project is to collect values from multiple

sensors and store them in a database. In order to collect the values the physical system

must be equipped with a processor, I/O ports, analog/digital converter, timer, internal

memory to name a few.

2.1.1 Microcontrollers

“A microcontroller (μC) is a small computer on a single integrated circuit consisting of a

relatively simple central processing unit (CPU) combined with peripheral devices such as

memories, I/O devices and timers” [2,179]. Figure 39 shows a block diagram of the basic

structure for microcontrollers.

The main part is a CPU that is responsible for fetching the instructions and it decodes

them to usable functions so they can be executed. The CPU connects every part of the

microcontroller into a single system.

The memory is split up in two different groups: RAM and ROM memory. The RAM

holds the data that changes during computations. The ROM holds the pre-programmed

instructions for the CPU. Popular choices for ROM memory are EEPROM and Flash

memory as they can be reprogrammed over and over again [1,390].

8 Source: http://www.rrsg.uct.ac.za/courses/EEE3074W/EmbeddedSystems.html Accessed 11.06.2015

9 Source: http://www.circuitstoday.com/basics-of-microcontrollers Accessed 30.5.2015

Figure 3 Basic Structure and Block Diagram of a Microcontroller

Page 25: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

7

For the microcontrollers to work proficiently it can be necessary to have both parallel and

serial interfaces. To make the implementation easier in standard I/O connection the

common practices is to provide several I/O ports for both serial and parallel interfaces

[1,391]. Parallel ports may be configured as inputs or outputs which can help keep the

system smaller when only a few ports are needed. A serial port interface provides UART

capabilities. Double buffering is used in the transmit - and receive paths [1,395].

The counter for microcontroller can be either an internal clock or an external one and is

responsible for the correct sequence of actions the microcontroller must make.

2.1.2 Processors

Since the first microprocessor was released in 197110

, the Intel 4004, there has been a lot

of development in processors. The technology continues to evolve each year which leaves

processors with more capabilities and computing power.

Table 2 Difference Between the First Processor to the Latest Model From Intel

Name 1971 Intel

4004

processor

1982 Intel

286 Processor

1993 Intel

Pentium

processor

2003

Intel

Pentium

M

processor

2012 3rd

gen Intel

core

processor

Initial clock

speed

108 kHz 6 MHz 66 MHz 1.7 GHz 2.9GHz

Transistors 2300 134.000 3.1 million 55

million

1.4

billion

Manufactory

Technology

10 μm 1.5 μm 0.8 μm 90 nm 22 nm

Table 2 shows that the processors have gotten smaller, the number of transistors has

increased exponentially along with the initial clock speed.

2.1.3 How processors works

The CPU executes machine language instructions and coordinates activities of other units

[1,152]. The operations of a processor can be carried out as follows

- Read contents of a given memory location and load them into a processor register

- Read data from one or more processor register

- Perform an arithmetic or logic operation and place the result into a processor register

- Store data from a processor register into a given memory location11

10Source: http://www.intel.com/content/www/us/en/history/history-intel-chips-timeline-poster.html

Accessed 12.6.2015

Page 26: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

8

The main hardware components of the processor should and could be able to perform

these operations as can be seen in Figure 412

. The processor conveys with the memory

with the processor memory interface that moves the data to and from the memory during

read and write operations. The instruction address generator then updates the contents of

the PC when the instructions are fetched. The processor´s general purpose register, is

formed by organization of storage location from the register´s file. All contents

instruction that require computing are sent to the ALU unit and all the results are then

stored in the register file [1,153-154].

11 [1,153]

12 [1,153]

Figure 4 Main Hardware Components of a

Processor

Page 27: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

9

There are two very different approaches of the design of instruction sets for computers and

that are RISK or CISC instruction set [1, 34]. See Table 313

for difference in

characteristics for both types.

Table 3 Characteristics of RISK/CISC Instruction Set Architecture

RISC CISC

General Very fast, fixed length instruction

decode, high execution rate

Fewer instructions, size of code is

smaller

# of instruction <100 >200

# of address modes 1-2 5-50

Instruction formats average 1-2 3+

Cycles/Instructions ≈1 3-10

Memory access Load/store instructions Most CPU instructions

Registers 32+ 2-16

Control unit Hardwires Microcoded

Instruction decode area(% of

overall die area)

10% >50%

RISC has instructions that fit into a single word and a load/store architecture is used where

all operands are accessed. The number of instructions can exceed over 100 overall and it

takes about one cycle to execute each instruction.

CICS instructions are not constrained to the load/store architecture where arithmetic and

logics operations can be performed on operands in the processor register [1, 74]. The

number of instructions are fewer than 200 and it takes three to ten cycles for one

instruction to complete.

2.2 Information distribution and holding

Distributing and storing information is a key element when building a monitoring system.

The information will be stored in a database and displayed on a website.

2.2.1 Database

A database is a collection of software that can be used in almost all operating systems such

as Windows, OSX, Linux and BSD.

13 [3,8]

Page 28: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

10

DBMS provide more functions to a simple file management:14

Allow concurrency

Control security

Maintain data integrity

Provide for backup and recovery

Control redundancy

Allow data independence

Provide non-procedural query language

Perform automatic query optimization

There are multiple versions of databases available but there will be only overview on

relational type database. “Relation database is a database that treats all of its data as a

collection of relations” [4, 7]. An essential attribute of a relational database is that every

tuple or record must be unique. They are identifying values that are known as key or key

values.

For this project two databases types MySQL and SQLite will be used and explained in

chapter 4.

2.2.2 Distribution

When presenting information from a database there are several things that have to be

considered. Ease of access for the database and the user are the main focus points and also

the way the information is presented. Therefore the three main components for the

distribution are:

Web page setup

Relevant Information

Presentation of information

For the webpage setup there are several programming languages that work together.

HTML is the main building block for the webpage. HTML format tells the computer how

to display the contents on the web page which is plain text with special tags that a web

browser uses to display the information15

. “The syntax and placement of special

instructions (tags) that aren’t displayed, but tells the browser how to display the

documents contents.”[5, 67]. In order to have more control on displaying the information

the CSS is used. CSS can specify the page element of the web page setup, such as the

font, size of the text and keeps it in place throughout the webpage. Figure 5 shows how

the setup is when using JavaScript, PHP, CSS and HTML. JavaScript and PHP control the

action that is displayed, CSS controls where and how it is shown. HTML is the page that

shows the contents.

14 [4, 4]

15 Source: http://www.austincc.edu/hr/profdev/eworkshops/docs/HTML_Basics.pdf Accessed 18.06.2015

Page 29: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

11

For this project there are communications between data server and the HTML website.

The PHP programming language is used for that communication and is open source. PHP

has support for most web servers and all major operating systems.16

PHP has the abilities

to output images, PDF files and Flash videos. JavaScript is used to show the data from the

data server with graphs and gauges. CSS controls where on the web page the graphs and

gauges are and HTML is the webpage that shows the graphs and gauges.

2.3 Water monitoring systems

The standard monitoring systems for buildings that is provided by the utility that supplies

the water to them can be seen in Figure 617

. This setup is owned by HS Veitur HF. The

only sensors that are included are optical gauge sensors and the sensors are read manually.

A worker from the company has to go to every building/structure, read the values and

write them down and this is done at least once every year. Not many customers are known

to go regularly and check the sensors for themselves.

After a company worker has checked the gauges, the company sends a bill that gives

indication to the customer if he has used more or less than estimated water usage for that

fiscal year. This is the only indication to the customer that everything is all right with the

system if the usage is not monitored regularly throughout the year.

16 Source: http://php.net/manual/en/intro-whatcando.php Accessed 18.06.2015

17 Source: http://www.hsveitur.is/english/HSAdvice/HSAdviceFrame.aspx Accessed: 22.6.2015

Figure 5 Basic Platform for a Working Website

Page 30: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

12

Figure 6 Flow Controller Frame from HS Veitur HF

The content of the heat frame in Figure 6 is listed in Table 4.

Table 4 Material of Flow Controller Frame from HS Veitur HF

NR Material

1 Inlet valve hot water

2 Filter

3 Flow meter, sales meter HS Veitur hf

4 Main valve heating system

5 Main valve potable water

6 Pressure meter

7 Pressure control valve, type Danfoss AVD

8 Temperature and pressure meter

9 Non-return valve

10 Flow control valve*

11 Safety valve

Page 31: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

13

*Flow meter valve is a choice to put in, to limit the maximum flow of hot water through

the heating system.

The inlet valve (1) controls whether hot water enters the flow controller frame, and is

usually open except when maintenance is being done on the system. The flow meter (3)

measures the volume of all the water usage in cubic meters. There are then two valves,

one that controls the heating system (4) and then the potable water or drinking water (5).

The potable water is used for domestic uses such as bath, showers and cleaning. The rest

goes to the radiators for heating. The hot water goes through the radiator flow limiting

valve (12) and from there to every radiators that are connected to the system. There is

usually one pressure meter (6), one flow meter (3) and two temperature and pressure

meters in one (8, 15) that are on each flow controller frame. The temperature meters show

the temperature drop from when the water enters the radiators and when it exits them.

Some flow controller frames, have extra input valve for a snow melting system that is

connected between the radiator return valve (13) and drain (18) and uses the excess heat

when the water has gone through the radiators. If the system needs maintenance then the

inlet valve (1) is closed and the filter and drain valve (16) are opened to take the pressure

and water from the system to prevent damages and injuries.

12 Radiator flow limiting valve

13 Radiator return valve

14 Maintenance valve

15 Temperature and pressure meter

16 Filter and drain valve

17 Back pressure valve, type Danfoss AVD

18 Drain

Page 32: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 33: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

15

3 Analysis

During the design process several variables needed to be considered when choosing the

right equipment for this project. The device needs to be compact so it is easily installed

near the heat frame for easy access in order to maintain the device and the heat frame.

It is preferable to have continuous electricity for the device from an electrical outlet, either

battery power source or main house electricity. An external power source can be difficult

to install near the heat frame due to tight spaces. The device´s power consumption is

relatively small as it will not affect the consumer´s electrical bill.

The water temperature from the supplier is usually around 80°C and the pressure is from

two bar to maximum eight bar18

.

Requirements for the temperature sensor:

Needs to be reliable so that error measurements are low over time.

Easily connected to device

Easily installed to heat frame

Maximum temperature range over 100°C.

Requirements for the pressure sensor:

Needs to be reliable so that error measurements are low over time.

Easily connected to device

Easily installed to heat frame

Maximum pressure range over eight bar pressure.

Handle the water temperature in the heat frame.

Requirements for the flow sensor:

Needs to be reliable so that error measurements are low over time.

Needs to handle the flow of water.

Needs to handle the water temperature.

Easily connected to device

Easily installed to heat frame

Requirements for the controller system

Easy in software programming.

Needs to handle the heat from the heat frame.

Can read analog and digital inputs

Can connect to the internet

18 Source: https://www.or.is/spurningar-og-rad/ertu-ad-byggja/tenging-vid-hitaveitu Accessed 22.6.2015

Page 34: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

16

3.1 Controller Systems

A few development boards were examined, in order to choose one that would qualify

according to the stated requirements of this project. The choice was also between buying

a development board and making one from individual parts.

A Linux based development board was chosen as Linux is an open source operating

system that only uses a small amount of memory and is easily programmable. It also has

the ability to be programmed over the internet with an SSH connection.

The four development boards that were looked at are:

Arduino Yún

Beaglebone Black

Intel Galileo

Raspberry Pi

Comparisons of the development boards can be seen on the Table 5 and Table 619

.

Table 5 Comparisons of Specifications for the Development Boards

Arduino Yun Beaglebone

Black Intel Galileo Raspberry Pi

SoC Atheros AR9331 Texas Instruments

AM3358 Intel Quark X1000

Broadcom

BCM2835

CPU MIPS32 24K and

ATmega32U4 ARM Cortex-A8 Intel X1000 ARM1176

Architecture MIPS and AVR ARMv7 i586 ARMv6

Speed 400mhz (AR9331)

and 16mhz

(ATmega)

1ghz 400mhz 700mhz

Memory 64MB (AR9331)

and 2.5KB

(ATmega)

512MB 256MB

256MB (model A)

or 512MB (model

B)

FPU None (Software) Hardware Hardware Hardware

GPU None PowerVR SGX530 None Broadcom

VideoCore IV

Internal

Storage

16MB (AR9331)

and 32KB

(ATmega)

2GB (rev B) or 4GB

(rev C) 8MB None

External

Storage MicroSD (AR9331) MicroSD MicroSD SD card

Networking 10/100Mbit Ethernet

and 802.11b/g/n Wi-

Fi

10/100Mbit Ethernet 10/100Mbit

Ethernet

None (model A) or

10/100Mbit Ethernet

19 [2]

Page 35: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

17

Power Source 5V from USB micro

B connector, or

header pin.

5V from USB mini

B connector, 2.1mm

jack, or header pin.

5V from 2.1mm

jack, or header pin.

5V from USB micro

B connector, or

header pin.

Dimensions 2.7in x 2.1in

(68.6mm x 53.3mm)

3.4in x 2.1in

(86.4mm x 53.3mm)

4.2in x 2.8in

(106.7mm x

71.1mm)

3.4in x 2.2in

(85.6mm x 56mm)

Weight 1.4oz (41g) 1.4oz (40g) 1.8oz (50g) 1.6oz (45g)

Approximate

Price $75

$55 (rev C), $45 (rev

B) $80

$25 (model A), $35

(model B)

Documentation Open source Open source Open source Open source

Table 6 Comparisons for I/O for the Development Boards

Arduino Yun Beaglebone

Black Intel Galileo Raspberry Pi

Digital I/O

Pins 20 65 14 17

Digital I/O

Power 5V 3.3V

3.3V or 5V (switched

with jumper) 3.3V

Analog Input

12 with 10-bit ADC,

0-5V (supports

external reference

input)

7 with 12-bit ADC,

0-1.8V (no external

reference input)

6 with 12-bit ADC,

0-5V (no external

reference input)

None

PWM Output 7 8

6 (limited speeds

prevent fine servo

control)

1

UART 2 (1 wired

to AR9331) 4

2 (1 exposed through

3.5mm jack) 1

SPI 1 2 1 2

I2C 1 2 1 1

USB Host 1 standard A

connector (AR9331)

1 standard A

connector

1 micro AB

connector

1 (Model A) or 2

(Model B) standard

A connector

USB Client 1 micro B

connector (ATmega) 1 mini B connector 1 micro B connector None

Video Output None Micro HDMI None HDMI, Composite

RCA, DSI

Video Input None None None CSI (camera)

Page 36: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

18

Audio Output None Micro HDMI None HDMI, 3.5mm jack

Power Output 3.3V up to 50mA, 5V 3.3V up to 250mA,

5V up to 1A

3.3V up to 800mA,

5V up to 800mA

3.3V up to 50mA, 5V

up to 300-500mA

Other

- All I/O routed to

ATmega processor

unless noted

otherwise.

- Real-time support

with programmable

real-time units.

- Mini-PCI Express

slot.

- Real-time clock

with optional battery.

- Hardware

compatibility with

most Arduino

Leonardo compatible

shields.

- Many pins have

multiple functions

such as I2S audio,

CAN bus, etc.

- Mixed compatibility

with Arduino shields.

Regarding a controller system, it was decided to choose a development board instead of

setting up the embedded system from scratch, in order to save time and make testing easier

The development board that was chosen was the Arduino Yún. It has two processors

Atheros AR9331 and ATmega32U4. The first is Linux based and the second one uses the

Arduino software that is open source. It is easy to program and has a strong programming

debug capabilities. It is the only development board that has internal Wi-Fi connection

and can read 5V analog inputs without extra equipment or circuitry. It can support

external reference inputs and has 5V digital power. All I/O ports are routed to the

ATmega processor, which leaves the AR9331 processor to work simultaneously with the

ATmega.

3.2 Sensors

The analyses of the different types of sensors are shown in the beginning of the chapter

and those qualifications were used to make a decision of which sensors were chosen. The

specifications were compared for different sensors and then a sensor was chosen that could

fulfil the requirements and by the score they received. The sensors that were chosen for

this project did not need complicated circuitry to connect with the chosen controller

system.

The sensors were also chosen to test the idea of measuring changes in the heat frame. The

cost of the sensors was also a factor and was kept as low as possible. The chosen sensors

do not necessarily represent what sensors would be used in real applications.

3.2.1 Temperature sensors

There were several different sensors that could fulfil the requirements. Comparisons of

temperature sensors can be seen in Table 7

Page 37: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

19

Table 7 Typical Temperature Sensor Characteristics

Typical Characteristics

Thermistors General Purpose

Resistance Temperature

Device Thermocouples

Semiconductor Temperature

Sensors

Temperature Range

-55°C to +125°C

-200°C to 850°C

-600°C to +2000°C

-50°C to +150°C

Linearity ex Fairly linear Fairly linear Best

Sensitivity High Low Medium Highest

Response Time

Fast Slow Fast to slow (depends on construction)

Slow

Excitation of power

Needed Needed Not Needed Needed

Long-Term Stability

Low High High Medium

Self-heating Yes Yes No Yes

Cost Low

Low (film)

High (wire wound)

Moderate to High

(depends on construction)

Low to Moderate

According to Table 7 the Semiconductor and Thermistors sensors are the best choices

since the temperature range is closest to the requirements. The Semiconductor sensors are

the better choice since they have better sensitivity, and linearity. They also have better

long term stability and that is a crucial requirement in order to make the need of

maintenance low. The response time is not required to be fast since the change in water

temperature after it goes through the radiator system and exits takes time and depends on

how many radiators are connected and how big the system is.

Page 38: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

20

Table 8 Comparisons of Temperature Sensors Models

Temperature sensors

Model Tmp3620

DS18B2021

W1701 switch +

b25 thermistor22

Voltage input (V) 2.7 - 5.5 3 - 5.5 12

Output 10mV/°C Binary 277.2 - 0.0619 k-ohm

Accuracy ±2% ± 0.5°C ±0.1°C

Digital/Analog Analog Digital Analog

Temperature range (°C)

-40 to +125 -55 to +125 +20 to +90

Extra

Waterproof Waterproof

Cost (dollars) 1.50 1.65 3.99

The selected sensor was the DS18B20 which is accurate and also within the temperature

range of this project. The sensor does not need complicated circuitry to connect to the

controller. The sensor comes in a waterproof casing and has accuracy of a half a degree.

It has the best accuracy and cost ratio.

This temperature sensor has the ability to have multiple

sensors connected on the same data line to the controller.

Each sensor has a unique serial number that the controller

reads and can identify which sensor is sending the data.

The sensor has three pins see Figure 7:

GND

DQ

VDD

20 Source: https://www.sparkfun.com/products/10988 Accessed 15.5.2015

21 Source: http://www.ebay.com/itm/1pcs-Waterproof-DS18B20-Digital-Thermal-Probe-or-Sensor-

/201335507714?pt=LH_DefaultDomain_0&hash=item2ee0880b02 Accessed 15.5.2015 22

http://www.ebay.com/itm/New-20-90-Precision-Temperature-Difference-Adjustable-Control-Switch-DC-

12V/111450300007?_trksid=p2047675.c100005.m1851&_trkparms=aid%3D222007%26algo%3DSIC.MB

E%26ao%3D1%26asc%3D32022%26meid%3D86349e6d7d0d457d93f91e268713b536%26pid%3D100005

%26rk%3D1%26rkt%3D6%26sd%3D251722971921&rt=nc Accessed 15.5.2015

Figure 7 PIN Layout For

DS18B20 Temperature Sensor

Page 39: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

21

The VDD is connected to the power either three volts or five volts, DQ is the data line

which sends the temperature readings to the controller and GD is the ground wire. There

needs to be 4,7 Kohm pull up resistor shorted between the VDD line and DQ line.

There are two ways of connecting the ds18b20 sensors to the controller. One way can be

seen in Figure 823

that is called normal power mode or connect pin one and three to the

ground, which is called parasite power mode see Figure 924

.

For best uses of the sensor the normal power mode works best and ensures that all data

from the sensors can be delivered to the controller.

3.2.2 Pressure sensor

Pressures sensors can be categorized depending on the characteristics of individual

projects. The best way to choose a pressure sensor is to define its use and compare it to

the definition in Table 925

23 Source: http://www.tweaking4all.com/hardware/arduino/arduino-ds18b20-temperature-sensor/ Accessed:

29.8.2015 24

See reference 16 25

[7, 11 - 12]

Figure 8 Multiple DS18B20 Temperature Sensors Connected to the

Same Data Line

Figure 9 Multiple DS18B20 Temperature Sensors Connected to the

Same Data Line with Pins One and Three Shorted

Page 40: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

22

Table 9 Notes and Terminology for Pressure Sensors

Sensor Categories

Definition

Pressure Sensor

Refer to a basic device that includes a diaphragm, bellows, or bourdon tube that is in contact with the process fluid and strain or deflection measuring devices but not with the circuitry needed to convert strain-produced resistance changes to a change in electrical current, or the equivalent devices in other form of pressure-measuring apparatus

Pressure Transducer

Includes the functions of the sensor and in addition, a signal processor or means for converting the change in pressure to a change in electrical, hydraulic, pneumatic, or optical quantity that can be quantified over a range of values

Pressure Switch Is equivalent to a pressure transducer except that the change in pressure is converted to a bistable quantity that is either ‘on’ or ‘off’

Pressure Transmitter Is a pressure transducer to which are added power supply, temperature compensation, and output signal conditioning so that a signal can be transmitted to a remote pressure indicator or process controller

Pressure Gauge Is a generic term that denotes a device that measures pressure, which might include manometers, dead weight testers, mechanical gauges, and any other direct means for measuring pressure.

According to Table 9 the chosen sensor categories are pressure transducer and pressure

transmitter which has the means to convert the change in pressure to a change in electrical

quantity that can be quantified over range of values. The sensor measures the pressure and

then sends electrical change to the controller. Then the controller calculates the electrical

signal to a pressure value that can be read.

Page 41: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

23

Table 10 Comparisons of Pressure Sensors Models

Pressure Sensor

Model HK1100C26 HK1100C27 HK1100C28

Input voltage (V) 5 6 7

Output (V) 0.5 to 4.5 0.5 to 4.5 0.5 to 4.5

Accuracy ±1.5% ±1% ±1.5%

Digital/Analog Analog Analog Analog

Work range (MPa) 0 to 1.2 0 to 0.5 0 to 0.8

Extra Water-, dustproof Water-, dustproof Water-, dustproof

Cost (dollars) 11.49 14.39 16.50

Table 10 shows the pressure sensors that fulfil the requirements for measuring the pressure

inside the heat frame. The pressure sensors that were inspected are all in the same model

family and the only difference is work range. The chosen pressure sensor is HK1100C

pressure transmitter that has working range from 0 – 1.2 MPa.

3.2.3 Flow sensor

A flow sensor measures flow of liquid or gas regardless of type. The flow meter is

designed so that a wheel is inside a tube with a magnet that gives pulses when the magnet

goes past the coil as seen in Figure 1029

.

26 http://www.ebay.com/itm/G1-4-inch-5V-0-1-2-MPa-Pressure-Transducer-Sensor-Oil-Fuel-Diesel-Gas-

Water-Air-/321801631422?pt=LH_DefaultDomain_0&hash=item4aecdf36be Accessed 15.5.2015 27

http://www.ebay.com/itm/G1-4-inch-5V-0-0-5-MPa-Pressure-Transducer-Sensor-Oil-Fuel-Diesel-Gas-

Water-Air-/311233888623?pt=LH_DefaultDomain_0&hash=item4876fc416f Accessed 15.5.2015 28

http://www.ebay.com/itm/G1-4-inch-5V-0-0-8-MPa-Pressure-Transducer-Sensor-Oil-Fuel-Diesel-Gas-

Water-

Air/251773562411?_trksid=p2047675.c100005.m1851&_trkparms=aid%3D222007%26algo%3DSIC.MBE

%26ao%3D1%26asc%3D32022%26meid%3D5656f653e244403b9f7b73933a54b337%26pid%3D100005%

26rk%3D2%26rkt%3D6%26sd%3D311233888623&rt=nc Accessed 15.5.2015 29

Source: http://www.cyberphysics.co.uk/Q&A/KS4/magnetism/EMI/Q1.html Accessed 8.7.2015

Figure 10 Explanation of Magnetic Flow

Page 42: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

24

Table 11 Comparisons of Flow Sensors Models

Flow Sensors

Model YF-520130 SEN-HZ43WB31 YF-DN5032

Sensor Hall Hall Hall

Input voltage (V) 5 to 18 3 to 18 5

Accuracy ±10% ±2% ±3%

Temperature (°C) -25 to 80 -25 to 80 < 80

Max pressure (MPa)

2 1.75 1.75

Digital/Analog Analog Analog Analog

Work range (L/min)

1 to 30 1 to 30 10 to 200

Cost ( dollars) 5.98 12.88 24.80

The chosen sensor is SEN-HZ43WB because it was the best to fit the requirements it can

handle the pressure inside the flow controller frame, the housing is made out of copper and

is the most accurate. The working voltage is between three volts and eighteen volts and

the chosen controller sends five volts.

30 Source: http://www.ebay.com/itm/1-30L-min-1-2MPa-1-2-Hall-Effect-Flowmeter-Control-Water-Flow-

Sensor-Arduino-/161129523876 Accessed 15.5.2015 31

Source: http://www.ebay.com/itm/SEN-HZ43WB-G3-4-Male-1-30L-min-Water-Flow-Hall-Effect-

Sensor-Switch-Flowmeter-/291179227359?pt=LH_DefaultDomain_3&hash=item43cba268df Accessed

15.5.2015 32

Source: http://www.ebay.com/itm/Hall-effect-water-Flow-Counter-Sensor-DC3-18V-2-DN50-

/121685535933?pt=LH_DefaultDomain_0&hash=item1c5505ecbd Accessed 15.5.2015

Page 43: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

25

4 Build

A closed system was built to test the equipment in an easy and secure way. That was done

in order to be able to check the system and adapt when needed.

To be able to test the closed system, measurements were taken from a live system. The

measurements were taken from a 234 m2 house in order to get real data on water usage.

Then the measurements were duplicated and malfunctions were inserted to the closed

system.

Three led lights, each with different colour, are used to show which failure has happened

within the closed system.

Temperature is under or over the given range

Flow is under or over the given range

Pressure is too low or too high.

4.1 Measurements

The measurements were taken from the heat frame six times with 30 minutes intervals in

order to find the average usage. Pressure, temperature and flow measurements were taken

from the heat frame through the sensors that are already in place from the company that

supplies the water.

Table 12 Flow Measurements Taken on a Real Controller Flow Frame

Flow

0.0001 0.001 0.01 0.1 m3

1. Measurement 7.5 6.7 8.7 2.5 0.34445

2. Measurement 7.5 0.8 3 3.2 0.35155

3. Measurement 8 8.9 9 3.4 0.4397

4. Measurement 9.2 1.9 3.1 4.1 0.44382

5. Measurement 4.1 8.3 7.8 4.4 0.52671

6. Measurement 6.1 5.5 2.5 5 0.53111

Table 12 shows those measurements from the flowmeter which is connected to the water

intake to the heat frame. The measurement entries in the table show the change from each

measurement and how many m3 of water have been pumped into the house. A simple

calculation using the figures in Table 12 shows that 0.037332 m3 of water flows into the

Page 44: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

26

house every half hour or 0.074 m3 (74 L/Hour) hour. About 90% of hot water is used for

space heating and 10% used for other means33

.

Table 13 Temperature Measurements

Table 13 shows the temperature readings in the heat frame when the water enters the

house and when it exits the house. The temperature holds steady through the

measurements at each end but has a 39°C drop in temperature from entering the house and

exiting.

Table 14 Pressure Measurements

Table 14 shows the pressure in the heat frame to be steady at four bars. Pressure

measurements were taken when only radiators where active and everything else was shut

off. When a faucet was turned on the pressure fell down but these measurements are only

to test the radiator system water usage.

33 Source https://www.hsveitur.is/images/mv_hitamenning.pdf Accessed: 20.04.2015

Temperature (°C)

Temp in Temp out

1. Measurement 69 30

2. Measurement 69 30

3. Measurement 69 30

4. Measurement 68.9 30

5. Measurement 69 30

6. Measurement 69 30

Pressure (bar)

Pressure in

1. Measurement 4

2. Measurement 4

3. Measurement 4

4. Measurement 4

5. Measurement 4

6. Measurement 4

Page 45: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

27

4.2 Prototype

A closed system was built to test the idea and equipment that was chosen in chapter 3.

Figure 11 The Closed System that Tests the Chosen Equipment and Idea

Table 15 Bill of Material

To test the equipment safely a closed

system was built (see Figure 11 and Table

15 for the material list). Controlling the

flow, temperature and pressure of the

system is crucial for a test of the equipment

and to see if it works. A pressure tank was

used (5) that could withstand the pressure

which is in a regular heat frame. The tank

can withstand pressure up to ten bars and

the measurement shows that it only needs to

handle four bars. There are six holes in the

tank which makes it perfect to hold all the

electronic sensors for the test and extra non

electronic sensors that were used to test the

output value of the electronic sensors.

Water pump (2) was used to simulate water

circulation and the drill (1) was used for

turning the water pump to control the speed

of the water flow.

No Part

1 Drill and drill holder

2 Water pump

3 Pressure gauge

4 DS18S20 temperature sensor

5 2.5 gallon tank

6 Breadboard connected to Yún

7 Arduino Yún

8 SEN flow sensor

9 HK pressure sensor

10 Power supply for Yún

11 Flowmeter from Orkuveitu

Reykjavíkur

12 Exit nozzle

Page 46: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

28

An accurate flow meter (11) was borrowed from Orkuveita Reykjavíkur. That is the

company that supplies all houses with water in the greater Reykjavík area. This flow meter

was used for comparison of the output value from the SEN flow sensor (8).

A pressure gauge (3) was used to compare the output value from the HK pressure sensor

(9).

All the electronic sensors were connected to the Arduino Yún (7). The Arduino Yún was

connected to a database and sent the results from the sensors to that database. The values

from the database were then sent to a webpage that showed the values from each sensor.

A regular garden hose was used to connect the exits and nozzle (12) that were connected

to the tank and accessories.

4.3 Programming

The programming was done in several different programming languages. Each language

has a specific purpose and all interact differently which will be explained along with the

communication between programming languages. Also the analyses on the values from

the sensors to the Arduino Yún that sends them to a database and then the results are

shown on a website.

The programming languages that are used in this project are:

C/C++

Python

PHP

HTML

CSS

JavaScript

SQL

The following programming languages are used to make the system work as whole. This

programming chapter can be divided into two categories, first the microcontroller

programming and the second one for the database and website.

C is used to program the Arduino Yún to read the signals from the sensors. The values are

then calculated from the results and sent to the Linux core in the Arduino Yún.

Python is used to program the Arduino Yún´s Linux side to send the data to a database

which was installed in the Arduino Yún. It is also used to send the data to a web server

through the internet connection in the Arduino Yún.

PHP is the programming language that receives and reads the data from Python and sends

and writes it into the SQL database. It also reads and sends the values from the database

to a web server.

HTML and HTML5 are the programming languages that are used to build websites.

Page 47: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

29

CSS is the building block for website designing and can control the appearance of the

website.

JavaScript is a programming language which is used to display the data from the database

graphically, as for example as line charts, pie charts and gauges.

MySQL software was set up on a web server that holds all the data from the Arduino Yún.

SQLite software was set up on the Arduino Yún as a precaution if the internet connection

would fail. Then the data from the Arduino Yún would not be lost, and the data would be

kept intact until the connection would be restored. Then the data would be safely sent to

the MySQL data server.

4.3.1 Arduino Yún

The first steps to program the Arduino Yún included downloading the software that was

designed for the Arduino Yún microcomputer. The software is “Arduino Yún Software

(IDE)” 34

.

To program the Arduino Yún, an older version of the software was required, the IDE 1.5.3

that was made for the Arduino Yún.

The Arduino Yún can connect to the internet by Wi-Fi, so programming the Arduino Yún

does not require it to be plugged into a computer but it must be connected through the

same internet network. The Atmega32U4 processor is programmed with the IDE software.

This processor controls the I/O ports of the microcontroller.

The ATmega processor is not directly connected to the internet interface and the SD

reader. To link both the ATmega and the AR 9331 processors a “BRIGDE” library is used

as seen in Figure 12.35

34 Source: http://www.arduino.cc/en/Main/Software[Online] Accessed: 30.04.2015

35

Source http://www.arduino.cc/en/Guide/ArduinoYun Accessed 30.04.2015

Figure 12 Communication Between Both Processors

Page 48: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

30

The Bridge library code from the ATmega is translated to Python and vice versa. Its

purpose is to run programs on both sides, if and when the Arduino Yún asks for it. It also

shares the readings from the Arduino Yún sensors through the internet to the database. If

the readings fluctuate more than normal the database sends signals to the controllers in

order to turn on warning signals

The Arduino designers have developed the software “Open Wrt-Yun” which can program

the AR 9331 processor and connect through the internet with SSH connection that allows

the programmers who uses this, monitor and change the activity of the processor.

The I/O pins of the Arduino Yún breadboard can be seen in Figure 1336

.

There are three ways to power up the device. One is using a micro power plug that

connects to an electrical outlet. Another way is through power pins Vin with five volts

DC and GND. Because the Arduino Yún does not have a built-in power regulator caution

36 Guðrún Þorbjörg Kristjánsdóttir adapted this figure from the Arduino Yún breadboard Source:

https://www.arduino.cc/en/Main/ArduinoBoardYun Accessed 30.04.2015

Figure 13 Input and Output Pins from the Arduino Yún

Page 49: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

31

must be taken when using this method so the board does not get damaged. The third way

is to use PoE, by getting the power straight from the Internet LAN cable 37

.

4.3.2 Database and Website

There are two different databases used in this project, MySQL for the data server and

SQLite for the Arduino Yún. The same principle is used for both but more details will be

put into the MySQL since that server is used for both receiving data from the Arduino Yún

and sending it to the web site.

The connection between the Arduino Yún and the server is through the internet and the

PHP programming which is used for retrieving data from the Arduino Yún and JavaScript

for visualization on the website.

For this project an Apache38

http server project is used to host the website. That is mainly

to keep down cost as it is open source and compatible with Linux operating system.

The setup for the MySQL database was used as a simple table for holding all the

information that the Arduino Yún sends and the website receives. The table holds the

information from all three sensors and a timestamp, for when the values from the Arduino

Yún are sent. Four columns are used to keep the values from the sensors separated for

better handling of data.

Figure 14 shows how the data is kept in the database. The first column is used for a

timestamp to know when each value is gathered to the database. It shows that every new

entry is at a seven second interval and the flow is at zero which means that the drill was

not in operation and the temperature and pressure are at normal values.

For every entry in the server’s database the server forwards the data to the website. The

inspiration for the website set up is from http://fermentationriot.com/arduinopid.php. It

uses open source Google script to display the values from the Arduino Yún that uses

JavaScript and PHP languages that work together to show the information graphically.

37 Source: https://www.arduino.cc/en/Main/ArduinoBoardYun?from=Products.ArduinoYUN

Accessed 25.08.2015 38

Source: http://httpd.apache.org/ Accessed 2.06.2015

Figure 14 Values from the Sensors to MySQL Database

Page 50: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

32

The web page uses line chart and gauges for every sensor as can be seen in Figure 1539

.

100 data points are shown in each line chart which cover 700 seconds or 11.6 minutes and

the latest value is shown in the gauges. The drill was stopped and therefore the flow show

zero L/Hour. The tank is airtight and holds the pressure steady at three bar and water

temperature at nineteen degrees.

In real life application, the data points would be every half hour since the change in the

flow controller frame is slow.

4.4 Cost

The cost is summed up with all the material that was bought to test the idea of monitoring

the flow, pressure and temperature of water. The material is the controller, sensors and

wire connections that is used.

Table 16 show all the material that was bought and the work that was involved with

setting up the closed system and programming for the controller, database and website.

39 Source: stjani.strumpur.net/test.php Accessed 18.05.2015

Figure 15 Graphical Visualization of the Data from the Database Shown in Website.

Page 51: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

33

Table 16 Cost of Material and Work

Name Cost/pcs Nb of pcs Total cost (dollors)

BB400 breadboard 3,96 1 3,96

Jumper Wires 5 1 5

Arduino Yún 70,30 1 70,3

Sparkfun resistor kit 11,95 1 11,95

DS18B20 Temperature Sensor

8,50 1 8,5

SEN-HZ43WB flow sensor 16,91 1 16,91

HK1100C pressure sensor 13,41 1 13,41

Work 54,33 180 9779,4

Total cost 9909

Page 52: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 53: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

35

5 Result

Experiments were made on the closed system (see chapter 4.2) and the results of the

measurements can be seen below. Since this is a closed system, a drill was used to

circulate the water and therefore actual water usage quantity cannot be achieved but close

enough. The heat, flow and pressure take precedence within the closed system.

The measurements show even temperature in the closed system, so it circulates the same

water and no outside water entered the system. The pressure was almost constant as the

drill was locked at the same speed.

The flow shows fluctuations since the water pump and drill have frictions and cannot keep

the flow speed constant. A real heat frame usage has a more constant flow.

The webpage in Figure 16 shows values from all sensor in real time and how the user

would see when the webpage would be entered.

Figure 16 Values from the Sensors Shown in Webpage

Page 54: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

36

5.1 Alarm System

The main purpose of the system is to make a warning system for the heat frame. In case

of a malfunction there have to be indicators to show what has gone wrong. For that

purpose, three led lights were used on the breadboard that the Arduino Yún controls. They

are to light up in case of major anomalies. The anomalies are set as extremes, outside

ordinary fluctuations that have been calculated for the system. The user of the system

would get different lights for different malfunctions, so it would be easier to recognize and

fix problems.

Figure 17 shows the work progress of the equipment when the values from the sensors are

sent to the Arduino Yún. The Arduino Yún checks if the values are within acceptable

limits and if it is not a light would be turned on to indicate the problem. The Arduino Yún

tries to connect to the internet and send the data to a SQL database. To back up the values

from the sensors an SD card is used to store the data if connection fails. The SD card

holds all the information and when the Arduino Yún connects to the database, it sends all

the information from since the connection failed and to the time it connected again. The

SQL server forwards the data to the webpage and displays it as graphs and gauges see

Figure 16.

Malfunctions have independent colours of light to show the user which malfunction has

occurred.

If flow anomaly occurs then the red led light is turned on;

If pressure anomaly occurs then the green led light is turned on;

If temperature anomaly occurs then the yellow led light is turned on;

Figure 17 Work Diagram for the Values from the Sensors to the Database and from the Database to

the Webpage

Page 55: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

37

5.2 Testing the system

The equipment was tested on the closed system in such a way that malfunctions were

introduced to the system to simulate what could happen to a real heat frame system. By

changing the temperature, increase/decrease flow and pressure values in the heat frame.

The first test of the equipment was to change the water temperature so that the water

temperature would go over the limit see Figure 18. For testing purposes the temperature

limit is set at 40°C. The malfunction was simulated by pouring hot water into the tank.

Figure 18 Water Temperature Anomaly

When the temperature changed, the values in the webpage changed immediately and the

temperature went over 40°C and the yellow light got turned on, see Figure 19.

Figure 19 Yellow Warning Light Turns On when the Temperature in not within the Limit Range

Page 56: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

38

The second test was to let the pressure within the closed system malfunction. For security

reasons the pressure was made to decrease instead of increase. That situation was

simulated by loosening a screw on the tank. The pressure immediately fell as seen on

Figure 20

Figure 20 Pressure in the System Falls Down

After the pressure fell to zero, the green led light turned on see Figure 21.

Figure 21 Green Warning Light Turns On when the Pressure in not within the Limit Range

Page 57: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

39

The third test was to make a flow failure. To make a flow failure is possible by making

the drill stop or go on full speed. In this test, the drill was stopped and therefore the water

flow stopped.

Figure 22 Flow in the System Falls Down

When the drill was stopped the water flow stopped as seen in Figure 22. When the flow

stopped, the red light turned on see Figure 23.

Figure 23 Red Warning Light Turns On when the Flow in not within the Limit Range

Page 58: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

40

Malfunctions that were simulated in the trials, are just a few of the possibilities that could

happen within the water controller frame system. If a pipeline or an intersection in the

pipeline starts to leak and the leakage is not noticed early enough then it could slowly

build up to massive damages.

If hot water is leaking slowly then the possibilities of damages are:

Water damage to any surface that the water leaks on to or in to

Steam damage to the surroundings of the leak

Mold can start to grow in the surroundings

Corrosion can cause the pipeline to break

When hot water leaks it can damage all that it touches, e.g., if the floor has carpets or tiles

then the section that the water leaks to may need replacement. The steam from the water

can ruin objects made from wood or water absorbent material, electrical items, and lead to

rusting of iron. A water leak can lead to mold growth within 24 – 48 hours40

. Mold can

cause severe damages to a house, be a major health risk factor and cause a high repair bill.

Houses that have a high risk factor of leak damages are houses that are empty for a long

time such as summerhouses which are used mostly during the summer and left alone in the

winter.

To see indication of a leak the pressure in the system would be lower than normal and or

flow increase.

If water temperature increases in the flow controller system, it could mean one or more of

the following:

Radiator/s are turned too high

Radiator valves have malfunctioned

A faucet is opened and is letting hot water through

A pipe is leaking or broken

If water temperature is too high then there is a possibility that the flow in the heat

controller system is high. It could lead to severe burns if too hot water goes through the

potable water pipeline. If these matters are not monitored then it could lead to injuries and

an excessively high water bill for the consumer.

The conclusion is that if the flow controller system is not properly maintained and

monitored regularly it could lead to severe damages to housing, people’s health and to a

very high repair bill to fix what was damaged or replaced.

40 Source: http://www.epa.gov/mold/moldguide.html Accessed: 13.9.2015

Page 59: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

41

6 Addition

The closed system test was successful. The next step was to implement it on a regular

flow controller frame in an ordinary house. A permission was granted to implement it on

a 234 m2 single family home. The house has fifteen radiators and snow melting system for

the entrance and drive way. It was decided to add heat sensors where hot water enters the

flow controller frame, before and after the snow melting system. Pressure sensors were

installed where the water comes in to the heat frame and before snow melting system.

Flow sensor was to be added where the water exits the heat frame.

Temperature measurements are taken:

When the water enters the heat frame from the supplier.

Before the water enters the snow melting system.

After the water leaves the snow melting system and heat frame.

These measurements show the temperature change when the water enters the heat frame

and goes through the radiators before it enters the snow melting system. Then it shows the

temperature change when the water leaves the system and the change when it exits the

snow melting system.

Pressure measurements are taken:

When the water enters the heat frame from the supplier.

After the water enters the snow melting system.

These measurements show the pressure changes when the water enters the heat frame and

when it leaves the system.

Flow measurements are taken when the water leaves the heat frame.

These measurements show the flow of water that leaves the system.

The closed system was disassembled and the sensors removed to be used again. The heat

frame was analysed and it was decided to use cross pipe fittings at points in the heat frame

where every sensors was to be installed.

Two additional temperature- and one pressure sensors were added to the system.

For some reason the flow sensor malfunctioned during the installation and through out this

test, flow measurements will be at zero.

Page 60: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

42

6.1 Setting up the Sensors

To set up the sensors in the heat frame several changes had to be made. To insert the cross

fittings in to the flow controller frame the old piping had to be taken apart and

reassembled.

Figure 24 shows how the heat frame looked before the cross fittings were placed. Figure

24 A) shows the pipeline in the flow controller frame where the water enters into the

system from the water supplier and a pressure gauge on the bottom pipeline that shows

four bar pressure. On the top pipeline is volume flow controller and external temperature

sensors that measure the temperature on the pipeline and shows little over 40°C.

Figure 24 B) shows the pipeline in the middle where the water enters the snow melting

system and exits the frame to the drain. The second temperature sensor that is in the frame

shows the temperature of the water when it has circulated through the radiators. Two

black pipes go into the floor that show where the water enters the snow melting system (on

left) and exits (on right). The wheel in the middle of the pipes is used for shorting over the

snow melting system and straight to the drain. Bottom pipeline on the left is for the cold

water.

Figure 24 Before Implementing Cross Fittings in to the Flow Controller Frame

A) Figure on Right Shows Where the Water Enters Into the Frame. B) Figure

on Left Shows When the Water Enters the Snow Melting System and Exits the

Frame

Page 61: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

43

Figure 25 shows the change after the cross fittings had been inserted to the frame. Four

cross fittings were used that could hold six sensors. Figure 25 A) displays the cross fitting

that will hold one temperature – and pressure sensor to get measurements when the hot

water enters the frame system. Figure 25 B) displays three cross fittings and one flow

sensor. From the temperature sensor on the left the first cross fitting has a place for one

sensor and is connected to the drain valve. The second cross fitting has a place for one

sensor and is connected to the snow melting system. The last cross fitting has a place for

two sensors and is connected to the flow sensor see Figure 26.

After the cross fittings were inserted and the pipes were inserted to the flow controller

system the flow of water was turned on to check for leaks.

Figure 25 After Implementing Cross Fittings to the Flow Controller Frame.

A) Left. B) Right

Figure 26 Pipe Assembly when the Cross Fittings are Inserted into

Page 62: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

44

6.1.1 Adding the sensors to the heat frame

As there were no leaks found in the new instalment to the frame the sensors were added.

The flow sensor was added when the pipe was assembled (see Figure 26) and no changes

were needed for the sensor. The flow sensor has male port thread G3/4 of inch and was

connected to the cross fittings.

The pressure sensor needed adjustments to be able to fit into the cross fittings since it

thread is G1/4 and needed G1/4 female to G3/4 male fittings to be able to connect to the

cross fittings.

The temperature sensor needed more implementation to be able to connect to the cross

fittings. The temperature sensor did not have thread housing so it needed to be installed

and waterproofed.

Figure 27 shows how a thread housing with insulation is implemented to the temperature

sensor. The middle part is the insulation that prevents the water to flow through the

housing. The thread fitting goes from G1/4 male to G3/4 male. After all three

temperature sensor had the thread housing fitted, they were connected to the flow

controller frame.

Figure 27 Thread Fittings and Insulation for the Temperature

Sensor

Figure 28 Sensors Connected to the Flow Controller Frame

Page 63: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

45

Figure 28 show how the sensors are connected to the flow controller frame and one place

left for a pressure sensor in the cross fitting after the snow melting system.

6.2 Connections from sensors to Arduino Yún

The next step of connecting the sensors to the Arduino Yún controller was to make a more

permanent set up. Since there are no shelves see Figure 28 there was a need to make the

set up attached to the wall. For easy implementation an electrical box was used to keep

the controller and connections in one place see Figure 29.

For better connection a PCB was used and multiple screw terminal blocks as can be seen

in Figure 29. Holes were drilled into the sides of the box for the sensor wires and power

wire for the controller. The screw terminal blocks were used to hold the wires and prevent

the wires to loosen and loose connection to the Arduino Yún and for easier maintenance of

sensors. One terminal block is not connected and is for installation of LCD screen that the

user can see on the lid of the box. Three led lights are in the middle of the PCB that have

the same functions as in chapter 5 but malfunctions were not implemented on the system

since the close controlled test showed they worked.

Figure 29 Electrical Box with

Arduino Yún and Connection with

Sensor with PCB

Page 64: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

46

The sensor connection to the terminal blocks in the box, six terminal blocks on the left of

the PCB are.

From top to bottom:

Temperature sensor from the beginning of the frame

Temperature sensor from the end of the frame

Temperature sensor before the snow melt

Pressure sensor from the beginning of the frame

Pressure sensor before the snow melt

Flow sensor from the end of the frame

The unique ability of the temperature sensor they are connected to the same I/O port of the

Arduino Yún. The pressure sensor are connected to a separate port and same for the flow

sensor.

The box is attached to the wall with a strong adhesive double sided Velcro strap for easy

installation of the box.

6.3 Database and Webpage

The setup for the database was changed to a relational one to be able to have better

handling of the data and user of the system. Changes were made to the web page and a

login page which is controlled by Facebook login was added. It was decided to use

Facebook login as is free to use from the developers of Facebook41

. It is secure and easy

to use.

6.3.1 Database

Two tables were added to the database to make it a relational database:

Table one contains:

Id – The user id number

email – The user email to be able to contact the user

name – The name of the user 1

address – To know the address of the user

sizeOfHouse – To know the size of the house

countOfRadiators – To know the numbers of radiators in the house

snowMelt – To know if there is a snow melt system

facebookId – So the user can log in and see his values

41 Source: https://developers.facebook.com/docs/facebook-login Accessed: 28.08.2015

Page 65: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

47

Table two contains:

Time – Stamps the date and time when values are inserted to the database

UserId – The same id number as in table one

Temperature1 – Holds the values from temperature sensor

Temperature2 – Holds the values from temperature sensor

Temperature3 – Holds the values from temperature sensor

Pressure1 – Holds the values from pressure sensor

Pressure2 – Holds the values from pressure sensor

Flow – Holds the values from flow sensor

The two tables are linked by the same id number. The id number tells the system who the

user is and what values from the sensors to show. When the user logs in to the website he

is redirected to a Facebook login page. Each Facebook user has a unique identification

number and that number is registered to the database. The database compares the

Facebook number to the registered number and if it is the same then the user continues to

the main webpage.

The main webpage contains three flowcharts for each type of measurements and six

gauges to see the newest values that is inserted to the database. The first entry to the

database is 15:58:31 29.8.2015 that is used for comparisons of data from the monitoring

system.

For testing purposes, every entry into the database is eleven seconds apart to get viable

data from the flow controlling frame system, to see the fluctuation of temperature and

pressure.

6.3.2 Calculation from the database

Calculations of the temperature and pressure were made to establish the usage of water

from the time the first entry was made 29.8.2015 and to 11.9.2015 or thirteen days of data

which is about 4254 data points from every sensor.

Table 17 Calculation of the Temperature for 13 Days of Data Points

Temperature enters the flow controller

frame (°C)

Temperature before de-icing system (°C)

Temperature when leaving the flow

controller frame (°C)

Max temperature 78.25 33.81 18.38

Average temperature 74.41 27.59 16.29

Min temperature 71.69 25.94 14.19

Standard deviation 0.76 0.38 0.83

Page 66: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

48

The calculation from the temperature data in Table 17 shows that the temperature

fluctuates. When the hot water enters the flow control frame it has average temperature

74.41 °C and when it has circulated through the radiator system is has dropped to 46.82 °C

on average. After the water goes through the de-icing, it has dropped another 11.30 °C on

average. The water has a 58.12 °C temperature change on average when entering the flow

controlling frame and leaving.

The temperature when the water enters the frame has a 6.56 °C temperature difference

from max to min. The standard deviation shows that the temperature is mostly around

74.41 °C ± 0.76 °C during the thirteen days and the water usage is steady and does not

fluctuate much.

The temperature before de-icing has 7.87 °C difference from max to min that shows that

there are more changes in temperature when the water has circulated through the radiators.

The standard deviation shows that the temperature fluctuates less than the water that enters

the frame but has higher spikes.

The temperature when the water has gone through de-icing has a 4.19 °C temperature

difference from max and min, which is the lowest difference in the system. It has the most

fluctuation as it is dependent on the outside temperature.

Table 18 Calculation of the Pressure for 13 Days of Data Points

Pressure entert the flow controller frame (Bar)

Pressure before de-icing system (Bar)

Max pressure 4.78 3.49

Average pressure 3.78 2.86

Min pressure 1.36 1.49

Standard deviation 0.12 0.09

The calculation from the pressure in Table 18 shows that the fluctuation between the

sensors is not high. The pressure when the water enters the flow controller frame is on

average 3.78 Bar. The pressure drops 0.92 Bar on average when the water has circulated

through the radiator system.

When the water enters the flow controller frame there is a 3.42 Bar difference in pressure

in max and min measurements. The standard deviation shows that the pressure is close to

the 3.78 Bar most of the time. The pressure drops significantly because the potable water

system is connected parallel with the radiator system and therefore has influence on the

pressure when a faucet is opened.

When the water has circulated through the radiator system there is a 2 Bar difference in

max and min measurements. The standard deviations shows that the fluctuation in

pressure after the radiator system is small and hold on average 2.86 Bar most of the time.

Page 67: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

49

At 15:15:30 13.9.2015 the timing of data point entry to the database was changed from

eleven seconds interval to every 20 minutes since the changes in measurements are small

and consistent.

6.3.3 Webpage

The webpage has the function of showing the data from the database in an understandable

and readable format such as graphs, gauges and lists. Several changes were made to the

website. The website has the same front page that shows three graphs and six gauges.

Five extra pages were added so now the website has:

Login page

Main page

Displays only temperature measurements in more detail

Displays only pressure measurements in more detail

Shows all the temperature values in a list

Shows all the pressure values in a list

When entering the website URL stjani.strumpur.net the webpage redirects to

stjani.stumpur.net/login.php and a line appears that says “Login with Facebook” in blue

hyperlink text see Figure 3042

Figure 30 Login Page for the Website

When the text is clicked, another redirection is to a Facebook login page see Figure 31.

42 Source: stjani.strumpur.net/login.php Accessed: 13.9.2015

Page 68: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

50

Figure 31 Facebook Login Page

When the Facebook login page appears, it requests the Facebook username and password.

If the Facebook id number is the same as is in the database then another redirection is

made to the main web page.

Figure 32 The Main Web page for the Monitoring System

The main web page has the same overall look as in test one of this project, but there are

small differences. The name has changed from “Eftirlitskerfi Ofna” see Figure 15 to “Hot

Water Monitoring system” and two extra buttons are in the top left corner. They are “Heat

Temp” and “Pressure”. They redirect to more detailed visualization of the named

measurements.

When the “Heat Temp” button is clicked then a new web page appears that shows the

temperature measurements.

Page 69: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

51

Figure 33 Web Page that Displays all the Temperature Measurements

Figure 33 shows three graphs which displays the temperature measurements from all the

sensor on a separate graphs for more detailed information. The top graph shows the water

temperature when the water enters the flow controller frame. The graph in the middle

shows the water temperature when the water has circulated the radiator system. The graph

on the bottom shows the water temperature when the water has gone through the de-icing

system and is leaving the flow controller frame and into the drain. To the right of every

graph are two text boxes that show “Max Temp:” and “Min Temp” of every graph to show

the corresponding max and min value.

In the top left corner of the web page there are three buttons. One to redirect to the home

page, redirect to the temperature list that shows every value from the database in a list and

a submit button. The submit button works with the two input text boxes that show “From”

and “To”. They have the function to allow the user to choose a specific date to see the

values from one date to another. Precautions were made by only showing max 15.000

data points in a graph for saving time of displaying the data. If the timeframe that was

chosen were is too big then the web page could not handle displaying all the data and

crash or would take long time to display the data to the graph.

The pressure page has the same function as the temperature page and shows only the

pressure measurements in two graphs since there are only two sensors.

There is a security measures in the web page that only lets the user that logged in to see

that specific data. If multiple users were using this system then no one could see each

other values and usage. Another is if a user is not logged in and tried to go directly to a

page for example in Figure 33 then the user would be redirected to the login page see

Figure 30.

Page 70: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

52

6.4 The working of the system

The main working of the monitoring system is to measure data from the flow controller

frame system Figure 3443

. The sensors are strategically position at the frame to measure

valuable data that shows the difference in temperature and pressure when the water flows

through the system. The sensors are connected to the Arduino Yún controller which

calculates the signals from the sensors to know values such as Celsius, Bars and L/hours if

the flow sensor were operational. The Arduino Yún is connected to the data server

through the internet and sends all the data from the sensors. The data base then collects all

the data and inserts the data to a table that isolates the values for better handling. The data

server than sends the data from the sensors to a web site for display.

43 Assambled by Guðrún Þ. Kristjánsdóttir with flow control frame from HS Veitur and Arduino Yún from

Arduino developers.

Figure 34 Working of the Monitoring System

Page 71: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

53

6.5 Cost after addition to project

The cost after project addition does not include the cost in chapter 4.4. Added were two

temperature sensors and one pressure sensor that were installed, with the sensors that were

already acquired, to the flow controller frame. To install the sensors to the frame, then

made were changes to the frame so that the sensors could be installed.

Table 19 Cost after Modifacations of Project

Name Cost/pcs Nb of pcs Total cost

1/2" cross fittings 3,03 2 6,06

3/4" cross fittings 4,35 3 13,05

3/4" to 1/2" fittings 1,16 6 6,96

3/4" bolt thread 1,13 3 3,39

1/2" bolt thread 0,9 9 8,1

1/2" knee fittings 1,08 2 2,16

1/2" to 1/4" cylenders 0,8 8 6,4

UNIONAR 1/2" 3,34 2 6,68

Valve 1/2" 0,74 2 1,48

Electrical Box 23,28 1 23,28

electrical wire tubes 1,12 3 3,36

Heat sink insulation 21,14 1 21,14

Valve for sensor 4,14 3 12,42

DS18B20 Temperature Sensor

8,50 2 17

HK1100C pressure sensor 13,41 1 13,41

Work 54,33 270 14669,1

Total cost

14813,99

The cost of this project is total cost from Table 16 and Table 19 and that is 24722 dollars,

which includes all material and work hours that went to the completion of this project.

Page 72: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 73: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

55

7 Conclusion

Sensors and controller were analysed to meet certain requirements to be able to measure

usage of hot water in flow controller frame. The Arduino Yún, was chosen for the best

code debug for prototype testing and internal Ethernet and Wi-Fi module. Sensors for

temperature, pressure and flow were used to measure the usage of hot water inside the

flow controller frame.

The first test with one of each sensor was within a closed system. Failures for each sensor

were simulated to test reaction of each sensor. In each case the warning light lit up to

show what failure had occurred. The website displayed the values from the sensors in real

time. Test on the closed system was successful.

After the first test was successful and showed that the sensors could monitor the water

usage further application was tried. The next step was to install the sensors to a real flow

controller frame. Two temperature sensor were added and one pressure sensor to the

frame. The flow sensor malfunctioned when moved so only the results from the other

sensors were used. One temperature sensors were installed where the water enters the

frame. The second one after the radiator system and the third one after snow melt system

before the water goes to the drain. One pressure sensor was installed at the entrance point

in the frame and another one after the radiator system. The website shows the values from

the sensors in three different ways. Using charts, gauges and table lists. The test of

installing sensors inside the flow frame was successful except the flow sensor. The

prototype monitor system runs autonomously and sends data from the sensors to a

database and then on to a website.

Page 74: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 75: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

57

8 Discussion

The goal of this project was to test the idea of using electronic sensors to measure water

usage where the sensors need to be able to withstand pressure, flow and temperature that

are in the flow controller frame.

8.1 First test

A closed system was constructed to test a monitoring system that uses sensors which are

connected to a controller. The controller sends the sensors data through the internet and to

a database. A website then displays the data.

Malfunctions to the system were simulated and the monitor system responded by lighting

one of three led lights that indicate what malfunctioned as each light has a different colour.

The test was successful in all instances.

8.2 Second test

Thirteen days after installation of the monitoring system in the flow controller frame the

average temperature after the water had circulated the radiators was 27,59 °C (see Table

17). The temperature was considered to be in the higher range and all the radiators were

inspected to see if their settings were set too high. Two radiators in the house had too high

settings and were lowered and the average temperature dropped to 25,69 °C (number

calculated from database).

The monitor system showed that the water temperature was too high after it left the

radiator system. When the radiator settings were adjusted the flow and temperature

decreased which shows correlation between temperature and flow of the water.

Page 76: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 77: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

59

9 Future Work

The result of the tests that show that the usage of a monitoring system is feasible and more

additions to the project can make the system work better.

Here is a list of possible future work:

Making a controller from scratch by using minimum components.

Researching better sensor that do not need any modifications to be installed to a flow

controller system.

Changing the communications from the controller to the database by using phone

network.

Making Android and Apple compatible application to show the data from the

sensors

Change the warning system by sending email and/or calling to notify the user

Make a better website to display the data from the sensors

Add monitoring system to the cold water usage

Page 78: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 79: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

61

Reference

[1] C.Hamacher , Z.Vranesic, S.Zaky, N.Manjikian, Computer Orginazation and

Embedded Systems, NY: McGraw-Hill, 2012.

[2] E. A. Lee and S. A. Seshia, Introduction to Embedded Systems - A Cyber-Physical

Systems Approach, LeeSeshia.org, 2011 [Online]. Available:

http://leeseshia.org/releases/LeeSeshia_DigitalV1_08.pdf

[3] F.Merat, (1996). RISC/CISC Characteristics [Online]. Available:

http://engr.case.edu/merat_francis/eeap282f97/lectures/28_RISC%20&%20PowerPC.pdf

[4] Robbert J. Robbins, (1995) Database Fundamentals [Online]. Available:

http://www.esp.org/db-fund.pdf

[5] O’Reilly,(2000),Web Design in a Nutshell [Online]. Available:

http://www.ntslibrary.com/PDF%20Books/A%20Complete%20Guide%20to%20Web%20

Design.pdf

[6] T. DiCola, 26.09.2014 Embedded Linux Board Comparison [Online]. Available:

https://learn.adafruit.com/downloads/pdf/embedded-linux-board-comparison.pdf

[7] R.L. Shepard , L.H. Thacker (1993) Evaluations of Pressure Sensing Concepts: A

Technology Assessment [Online]. Avilable:

http://web.ornl.gov/info/reports/1993/3445603770391.pdf

Page 80: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 81: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

63

Appendix A: Specification of Arduino

Ýun Development Board

Following information is from Arduino developers acquired at

https://www.arduino.cc/en/Main/ArduinoBoardYun, accessed on 30.04.2015

The Arduino Yún is a microcontroller board based on the Atmega32u4 and the Atheros

AR9331. The Atheros processor supports a Linux distribution based on OpenWrt named

OpenWrt-Yun. The board has built-in Ethernet and WiFi support, a USB-A port, micro-

SD card slot, 20 digital I/O pins ( of which 7 can be used as PWM outputs and 12 as

analog inputs), a 16 MHz crystal oscillator, a micro USB connection, an ICSP header, and

a 3 reset buttons.

Technical specifications of the Arduino Y

AVR Arduino microcontroller

Microcontroller ATmega32U4

Operating Voltage 5V

Input Voltage 5

Digital I/O Pins 20

PWM Channels 7

Analog Input Pins 12

DC Current per I/O Pin 40 mA

DC Current for 3.3V Pin 50 mA

Flash Memory 32 KB (of which 4 KB

used by bootloader)

SRAM 2.5 KB

EEPROM 1 KB

Clock Speed 16 MHz

Linux Microprocessor

Processor Atheros AR9331

Architecture MIPS @400MHz

Operating Voltage 3.3V

Ethernet IEEE 802.3

10/100Mbit/s

WiFi IEEE 802.11b/g/n

USB Type-A 2.0 Host

Card Reader Micro-SD only

RAM 64 MB DDR2

Flash Memory 16 MB

SRAM 2.5 KB

EEPROM 1 KB

Clock Speed 16 MHz

Page 82: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

64

PoE compatible 802.3af card support See Power

Power:

It is recommended to power the board via the micro-USB connection with 5VDC

If you are powering the board though the Vin pin, you must supply a regulated 5VDC.

There is no on-board voltage regulator for higher voltage, which will damage the board.

The Yún is also compatible with PoE power supply but in order to use this feature you

need to mount a PoE module on the board or buy a preassembled board.

Page 83: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

65

Appendix B: Arduino Yún electrical

schematic

Figure 35 Appendix B-1 Block Diagram of Arduino Yún

Page 84: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

66

Figure 36 Appendix B-2 Power Block Diagram

Page 85: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

67

Appendix C: Specification of the

DS18B20 temperature sensor

Features Unique 1-Wire interface requires only one port pin for communication

Multidrop capability simplifies distributed temperature sensing application

Requires no external components

Can be powered from data line. Power supply range is 3.0V to 5.5V

Zero stand by power required

Measures temperatures from -55°C to +125°C

± 0,5°C accuracy from -10°C to +85°C

Temperature is read as a 9-bit digital value

Converts temperature to digital word in 750 ms (max.)

User-definable, non-volatile temperature alarm settings

Alarm search commands identifies and addresses devices whose

temperature is outside of programmed limits (temperature alarm conditions)

Functionally compatible with DS1820 1-Wire digital thermometer

Application include thermostatic controls, industrial systems, consumer

products, thermometers, or any thermally sensitive system

Temperature sensor

Following are excerpts from DS18B20 datasheet

General description

The DS18B20 digital thermometer provides 9-bit temperature readings which

indicate the temperature of the device.

Information is sent to/from the DS18B20 over a 1-Wire interface, so that only

one wire (and ground) needs to be connected from a central microprocessor to

a DS18B20. Power for reading, writing and performing temperature

conversion can be derived from the data line itself with no need for an external

power source.

Because each DS18B20 contains a unique silicon serial number, multiple

DS18B20s can exist on the same 1-Wire bus. This allows for placing

temperature sensors in many different places. Applications where this feature

is useful include HVAC environmental controls, sensing temperatures inside

buildings, equipment or machinery, and process monitoring and control.

Page 86: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 87: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

69

Appendix D: Specification of the

flow sensor

Following are excerpts from SEN-HZ43WB datasheet.

General description

When magnetic material is close with the sensor, its characteristics my vary

In order to avoid particle debris, the sensor must be installed after a filter

The flow sensor installation has to avoid strong vibration and shaking of the

environment, so as not to affect the sensor’s measurements accuracy

Widely used in water industrial field, such as thermostatic water heater, water

purifier, water dispenser, smart card equipment, coffee machine etc.

Wiring: Black: Power Negative, Red: Power Positive, Yellow: Signal

Formula F=8,1 * Q – 3 ±10% 1L Water = 477 HZ ±10%

Specification

Product Name Water Flow Sensor Switch

Model SEN-HZ43WB

Type Hall Effect

Max Switch Current & Voltage 10 mA, DC 3-18V

Working Range 1 - 30 L/min

Male Port Thread Dia (Each End) G3/4

Max. Pressure 1.75Mpa

Insulation Resistance 100M Ohm(Min)

Total Size 60 x 32mm (L*Max.W)

Cable Lenght 34 cm

Main Material Copper

Color Gold Tone, Black

Weight 153g

Page 88: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 89: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

71

Appendix E: Specification of the

pressure sensor

Following are excerpts from HK1100C datasheet.

Features:

Easy removal

Carbon steel connection more firmly

Stainless steel is durable

Sealed waterproof line

Imported chips

Wiring: Red +, Black -, Yellow: output

Specification

Working Voltage 5VDC

Output Voltage 0.5-4.5 VDC

Sensor material Carbon steel alloy

Working Current ≤10 mA

Working Pressure Range 0-1.2 Mpa

The Biggest Pressure 2.4 Mpa

Cable length 19 cm

Destroy Pressure 3 Mpa

Working TEMP. Range 0 - 85°C

Storage Temperature Range 0 - 100°C

Measuring Error ±1.5% FSO

Temperature Range Error ±3.5%FSO

Responce Time ≤2.0 ms

Cycle Life 500.000 pcs

Application non-corrosive gas liquid measurement

Page 90: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for
Page 91: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

73

Appendix: Time Schedules

Figure 37 Original Time Schedule

Page 92: Hot water monitoring system - Heim | Skemmanframkallaðar á lokaða kerfið til þess að reyna virkni eftirlitskerfisins. Eftirlits kerfið náði ... Figure 17 Work Diagram for

74

Figure 38 New Time Schedual