Upload
sutton
View
33
Download
0
Embed Size (px)
DESCRIPTION
Hospital Central Gas Supply Systems. Simplex MMR. - Small cottage hospitals, veterinaries, dentists, third source of supply etc. - Suitable when automatic change over is not a demand - Connections for 3 high pressure hoses - Gaslarm C44 - 27-30 m3/h - CE-marked according to EN737-3. - PowerPoint PPT Presentation
Citation preview
© GCE Group
Date / Name
Hospital Central Gas Supply Systems
© GCE Group
Date / Name
- Small cottage hospitals, veterinaries, dentists, third source of supply etc.
- Suitable when automatic change over is not a demand
- Connections for 3 high pressure hoses
- Gaslarm C44
- 27-30 m3/h
- CE-marked according to EN737-3
Simplex MMR
© GCE Group
Date / Name
- Small to intermediate sized hospitals, Large hospitals for N20
- (Medical Breathing) O2, Air, N2O, CO2, N2 and Argon.
- 25 Nm3/h (O2), 17 Nm3/h (N2O)
- Gas Cylinders/ Cylinder Bundles
Manifold MC25
© GCE Group
Date / Name
- 2-stage control
- Semiautomatic Manifold
- Service without interruption of the gas flow
- Gas Alarm C44
- Slave panels: Gas Alarm C44, Connect from Relays
- CE-marked according to: EN737-3
Manifold MC25
© GCE Group
Date / Name
- Intermediate to large sized hospitals
- (Medical Breathing) O2, Air, N20
- 90 m3/h (O2)
- Gas Cylinders/ Cylinder Bundles
- CE-marked according to: EN737-3
Manifold MM90 Auto & Semiauto
© GCE Group
Date / Name
- LOX backup
- Automatic Change of Operating side, Automatic Manifold
- Service without interruption of the gas flow
Manifold MM90 Auto
© GCE Group
Date / Name
- LOX-backup
- Manual Change of Operating side, Semiautomatic Manifold
- Service without interruption of the gas flow
Manifold MM90 Semiauto
© GCE Group
Date / Name
- For all medical gases
- Inlet from LOX-tank and from Manifold
- Service and repair without interrupting the flow
- Sometimes one for every building
- Normal operation, use only one regulator, one for backup
- 80 Nm3/h (with dP2<0,3 bar)
- Adjustable outlet pressure (P2=3-7 bar)
- Inlet and outlet 22 mm (Int.)
- CE-marked according to: EN737-3
Stabilizer MC80
© GCE Group
Date / Name
- Same basic design and outer appearance as MC80 Stabilizer
- Service and repair without interrupting the flow
- Suitable for double LOX- systems
- Normal operation, use only one regulator
- 150 Nm3/h (with dP2<0,3 bar)
- Variable outlet pressure, (P2=3-7 bar)
- Inlet and outlet 35 mm (Int.)- CE-marked according to: EN737-3
Stabilizer MC150
© GCE Group
Date / Name
- Gas alarm intended for Manifolds (MM90, MC25 and Simplex MMR) and Pressure Watch
- Backup battery (30 min)
- Mute (15 min) /Test button
- Alarm signal according to EN475.
- Optical and audible signal
- Adjustable audible signal
- 4 Channels = 4 alarm points
- EMC Approved
- CE-marked according to EN737-3,
SIS HB370, EN60601
Gas Alarm C44
© GCE Group
Date / Name
IN-SIGNAL:- Pressure switches, contact gauges,
relays or any other type of switch (e.g. light switch)
OUT-SIGNAL: - Connection by relays
1. Can be connected to a PC (PLC). Using the PC as a slave panel
2. To another Gas Alarm C44
Gas Alarm C44
© GCE Group
Date / Name
-Can send the signal a long distance
- Connect the transmitters directly to PLC (PC).
- For local alarm; connect PLC to Gas Alarm C44
- 4-20 mA is the signal that most used in hospitals for other alarms
- Specially designed for usage with high pressure oxygen
- Accuracy 1% of FS better accuracy than Pressure Switches
- Can be fitted to all products (MM90, MC25, Simplex MMR, Line regulators, Pressure Watch)
- Pressure port G1/4”
- 0-16 bar, 0-25 bar and 0-250 bar versions
- CE-marked
4-20 mA Alarm System
© GCE Group
Date / Name
- 100% steel.
- Gas-specific connection to all kind of cylinders
- Length: 1250 or 2000 mm
- Product life 5 years
- Maximum allowed operating pressure 230 bar
- Pressure tested at 345 bar
- Safety wire
- O2, N20, Air, CO2, Nitrogen
- CE-marked according to: ISO 2196, EN13221
High Pressure Hoses
© GCE Group
Date / Name
- Evacuates if the pressure exceeds 6,8 bar
- Evacuates 130 m3/h
- 2 models, one is intended to be mounted immediately after Simplex MMR
- CE-marked according to EN737-3
Medical Piping System - Safety Valve for pipe system
© GCE Group
Date / Name
- Safety and service reasons
- Service free
- Can be locked
- Degreased for oxygen service
- PN 40 class
- DN10, 15, 25, 32 and 40
Medical Piping System - Shut-off Valves
© GCE Group
Date / Name
- For safety and service reasons
- Usually outside every ward. In some wards outside every room.
- Exposed installation / Recessed installation
- Pipes turning
- 1-5 valves
- Sealed front
- Pressure and leak tested
- Service free valves
- CE-marked according to EN737-3
Emergency Shut-Off Valve Box
© GCE Group
Date / Name
- Exposed / Recessed /Bed head (Panel) Installation
- Service valve- Quick Coupling
- Gas specific (MINI parts can be mixed up)
- O2, N20, Air, Vacuum, Gas exhaust, Instrumental Air, N2, CO2
- CE-marked according to EN737-3, EN737-1, ISO9170-1, SS8752430
Gas Outlets Nordic (MC70 and MINI)
© GCE Group
Date / Name
- Exposed / Recessed /Bed head (Panel) Installation
- Service valve
- Quick Coupling
- Gas specific
- O2, N20, Air, Air 8 bar, Vacuum, N2, CO2
- CE-marked according to EN737-3, EN737-1,
NFS 90.116
Gas Outlets Afnor
© GCE Group
Date / Name
- Exposed / Recessed /Bed head (Panel) Installation
- Service valve
- Quick Coupling
- Gas specific
- O2, N20, Air, Air 8 bar, Vacuum, N2, CO2
- CE-marked according to EN737-3, EN737-1
Gas Outlets DIN