    HCMCPC

    SPECIFICATION

    TERMINATION KIT FOR 0.6/1KV 3x95+1x50mm2 or3x50+1x25mm2 CABLE

    I. SCOPE :

    This specification covers the supply of outdoor terminations withaccessories for 0.6/1KV - 3x95+1x50mm2 or 3x50+1x25mm2 cable.

    II. STANDARD OF MANUFACTURE AND TEST :

    VDE 0278 : Power cable accessories with rated voltage up to 30KV.

    III. DESCRIPTION :

    1. The termination shall be of outdoor, heat or cold shrink type used tomake the cable termination for underground cable 0.6/1KV.

    2. Technical characteristics of cable :

    - Insulation of cable : XLPE- Voltage rating : 0.6/1KV- Core size :

    + 3x95 + 1x50 mm2

    + 3x50 + 1x25 mm2

    - Conductor material : Copper

    - Armour : Steel wires- Outside diameter of cable 3x95 + 1x50 mm2 : 43mm- Outside diameter of cable 3x50 + 1x25 mm2 : 37mm

    3. Technical requirement :

    - AC withstand voltage : 4KV AC for 15 minute between eachconductor and other conductor.

    - Impulse voltage withstand :+ 10 positive impulses : 8KV+ 10 negative impulses : 8KV

    - Load cycling : According to VDE 0278- DC voltage withstand : 15KV for 5 minutes.

    4. Accessories :

    Description 3x95 + 1x50 3x50 + 1x25

    Copper crimp lugs forcopper conductor

    + 3 for conductor of95mm2+ 1 for conductor of50mm2

    + 3 for conductor of50mm2+ 1 for conductor of25mm2

    IV. TESTING REQUIREMENT :

    1. Type testing items :

    /var/www/apps/conversion/tmp/scratch_1/138238355.rtf 1/4

  • 7/28/2019 HOP DAU CAP ha the.rtf

    2/3

    HCMCPC

    SPECIFICATION

    TERMINATION KIT FOR 0.6/1KV 3x95+1x50mm2 or3x50+1x25mm2 CABLE

    - AC voltage withstand test.- Loading cycle test.- Impulse voltage withstand test.- Thermal short circuit test.- DC voltage withstand test.

    2. Requirements :

    In order to ensure the quality of supplied goods , in case of bid winning ,the Tenderer shall supply copies of type test report met the following

    requirements:

    Type test report shall be approved by an lawful, reputable, independenttesting laboratory with the following content :

    - Testing sample : The same as the supplied item (manufacturer,original country, manufactures code as specified in tender document).

    - Testing items : Including testing items as specified in SectionIV.1 of this specification.

    - Testing values shall be corresponding values as stated in Section IIIof this specification. If in section III, there are no corresponding values,

    testing values will be selected according to the standard specified insection II of this specification.

    V. REQUIREMENT OF TENDER TECHNICAL DOCUMENT :

    - Technical description, data sheets, catalogues and other materialsubmitted with the quotation must enable the buyers engineers tothoroughly evaluate the proposals as to its compliance with the inquiryspecifications.

    - Minimum requirements :

    + Detailed summary of deviations to inquiry specification+ Completed inquiry data sheet expressed at section VI+ Catalogues containing outline dimensions, electrical data and

    installation details+ Certificate of quality management.

    - The proposal bidding has Type Test Report which meets the requirementsas specified in item IV 2.b will be preferable .

    VI. DATA SHEET :

    No

    DESCRIPTION UNITREQUIREME

    TENDERED

    /var/www/apps/conversion/tmp/scratch_1/138238355.rtf 2/4

  • 7/28/2019 HOP DAU CAP ha the.rtf

    3/3

    HCMCPC

    SPECIFICATION

    TERMINATION KIT FOR 0.6/1KV 3x95+1x50mm2 or3x50+1x25mm2 CABLE

    NTS

    1. Item No.

    2.

    DC voltage withstand for 5min.

    KV 15

    15.

    Accessories :

    - 3 copper crimp lugs forconductor of 95mm2 and 1copper crimp lug forconductor of 50mm2.

    Yes

    - 3 copper crimp lugs forconductor of 50mm2 and 1copper crimp lug forconductor of 25mm2.

    Yes

    /var/www/apps/conversion/tmp/scratch_1/138238355.rtf 3/4