1
Coal Fired O 2 and Excess Air Input Data Output Data Fuel Analysis Assumptions ( Calculated) Carbon 49.27 Excess Air 10.0% %O 2 Dry 1.95 Sulfur 0.30 (for calculation of O 2 ) Hydrogen 3.42 %O 2 Wet 1.71 Oxygen 11.44 O 2 , Wet 10.00 Nitrogen 0.71 (for calculation of excess air) Difference 0.24 Moisture 29.46 Ash 5.40 % Excess Air 102.7% Total 100.0 Oil Fired O 2 and Excess Air Input Data Output Data Fuel Analysis Assumptions (Calculated) Carbon 87.20 Excess Air 10.0% %O 2 Dry 2.03 Sulfur 0.02 (for calculation of O 2 ) Hydrogen 12.80 %O 2 Wet 1.80 Oxygen 0.00 O 2 , Wet 10.00 Nitrogen 0.00 (for calculation of excess air) Difference 0.22 Moisture 0.01 Ash 0.00 % Excess Air 96.7% Total 100.0 Gas Fired O 2 and Excess Air Input Data Output Data Fuel Analysis Assumptions (Calculated) H 2 0.00 Excess Air 10.0% %O 2 Dry 2.10 H 2 O 0.00 (for calculation of O 2 ) H 2 S 0.00 %O 2 Wet 1.74 CO 0.00 O 2 , Wet 10.00 CO 2 0.00 (for calculation of excess air) Difference 0.36 O 2 0.00 CH 4 90.00 % Excess Air 100.7% C 2 H 6 5.00 C 3 H 8 0.00 N 2 5.00 Other 0.00 Total 100.0 doc9.xlsx http://www.exoeng.com/excessaircalc.htm 1 of 1 23-Sep-14 1:48 PM

Hitung Excess Air

Embed Size (px)

DESCRIPTION

Cara menghitung excess air pada boiler dan perhitungan effisiensinya. Sangat pentng bagi yang membuthkan

Citation preview

Page 1: Hitung Excess Air

Coal Fired O

2 and Excess Air

Input Data Output Data Fuel Analysis Assumptions (Calculated)

Carbon 49.27ExcessAir 10.0% %O

2 Dry 1.95

Sulfur 0.30 (for calculation of O2)

Hydrogen 3.42 %O2 Wet 1.71

Oxygen 11.44 O2, Wet 10.00

Nitrogen 0.71 (for calculation ofexcess air)

Difference 0.24

Moisture 29.46

Ash 5.40 % ExcessAir 102.7%

Total 100.0

Oil Fired O

2 and Excess Air

Input Data Output Data

Fuel Analysis Assumptions (Calculated)

Carbon 87.20ExcessAir 10.0% %O

2 Dry 2.03

Sulfur 0.02 (for calculation of O2)

Hydrogen 12.80 %O2 Wet 1.80

Oxygen 0.00 O2, Wet 10.00

Nitrogen 0.00 (for calculation ofexcess air)

Difference 0.22

Moisture 0.01

Ash 0.00 % ExcessAir 96.7%

Total 100.0

Gas Fired O

2 and Excess Air

Input Data Output Data Fuel Analysis Assumptions (Calculated)

H2 0.00

ExcessAir 10.0% %O

2 Dry 2.10

H2O 0.00 (for calculation of O

2)

H2S 0.00 %O

2 Wet 1.74

CO 0.00 O2, Wet 10.00

CO2 0.00

(for calculation ofexcess air)

Difference 0.36

O2 0.00

CH4 90.00

% ExcessAir 100.7%

C2H

6 5.00

C3H

8 0.00

N2 5.00

Other 0.00

Total 100.0

doc9.xlsx http://www.exoeng.com/excessaircalc.htm