Transformer Differential Protection Relay Protection Technology made simple Application The MRDT4 is a protection relay which uses the latest Dual-Core-Processor Technology to provide precise and re- liable protective functions and is very easy to operate. Its various protective functions are specifically tailored to the protection of two winding trans- formers and offers in addition to that various overcurrent backup protec- tion functions. All inclusive: All protection features without extra charge Parameter setting and evaluation software Disturbance record analysis software Two stages transformer differen- tial protection Stabilized tripping characteristic, transients and C.T. saturation (temporarily restraint) Various selectable transformer groups Disturbance recorder 120 s non volatile, 32 samples per cycles Event recorder 300 events Last 50 non volatile Additional highlights Inrush Thermal replica Four stages external protection Plausibility checks Adaptive parameter sets Status display Masking of unused functions Commissioning support (forcing and disarming relays) Comprehensive measured values and statistics THD (total harmonic distortion) Current phasors and angles RMS and fundamental IRIG-B00X Time accuracy of ±1ms All time synchronization formats (IRIG-B000 ... B007) 36 UTC Time Zones Transmission of up to 18 synchro- nized control commands Temperature protection Buchholz (sudden pressure), ext. oil temperature, and aux. tem- perature protection via digital input Parameter setting support by software Copy parameter sets Compare parameter sets Setting files are up and down convertible (across versions) Supervision Current transformer supervision Circuit breaker failure protection Trip circuit supervision Cold load pickup Switch onto fault HighPROTEC MRDT4 C.T. missmatch correction Autom. magnitude and phase compensation Zero sequence removal High set element (unrestraint) Two stages ground differential protection Three point slope characteristic High set element (non-restraint) Four stages (Backup Protection) Overcurrent/short-circuit protection (non-directional) Earth fault protection (non-directional) Tripping characteristics: DEFT ANSI: NINV, VINV, EINV IEC: NINV, VINV, LINV, EINV Thermal Flat, IT, I2T, I4T Two stages unbalanced load protection Supervision by definite time or tripping characteristic

HighPROTEC Protection Technology made simple · Protection Technology made simple ... • Cold load pickup • Switch onto fault HighPROTEC ... inrush detection with evaluation of

Embed Size (px)

Citation preview

Transformer Differential Protection Relay

Protection Technologymade simple

ApplicationThe MRDT4 is a protection relay which uses the latest Dual-Core-Processor Technology to provide precise and re-liable protective functions and is very easy to operate. Its various protective functions are specifically tailored to the protection of two winding trans-formers and offers in addition to that various overcurrent backup protec-tion functions.

All inclusive:All protection features without •

extra chargeParameter setting and •

evaluation softwareDisturbance record analysis•

software

two stages transformer differen-tial protection

Stabilized tripping characteristic, • transients and C.T. saturation (temporarily restraint)

Various selectable transformer • groups

Disturbance recorder120 s non volatile,•

32 samples per cycles event recorder

300 events• Last 50 non volatile•

Additional highlightsInrush• Thermal replica• Four stages external protection• Plausibility checks• Adaptive parameter sets• Status display• Masking of unused functions• Commissioning support (forcing •

and disarming relays)

comprehensive measured values and statistics

THD (total harmonic distortion)• Current phasors and angles• RMS and fundamental•

iriG-B00XTime accuracy of ±1ms• All time synchronization •

formats (IRIG-B000 ... B007)36 UTC Time Zones• Transmission of up to 18 synchro- •

nized control commands

temperature protectionBuchholz (sudden pressure), ext. •

oil temperature, and aux. tem- perature protection via digital input

Parameter setting support by software

Copy parameter sets• Compare parameter sets• Setting files are up and down •

convertible (across versions)

supervisionCurrent transformer supervision• Circuit breaker failure protection• Trip circuit supervision• Cold load pickup• Switch onto fault•

HighPROTEC

MRDT4

C.T. missmatch correction• Autom. magnitude and phase •

compensationZero sequence removal• High set element (unrestraint)•

two stages ground differential protection

Three point slope characteristic• High set element (non-restraint)•

Four stages (Backup Protection)Overcurrent/short-circuit •

protection (non-directional)Earth fault protection•

(non-directional)Tripping characteristics: •

DEFT ANSI: NINV, VINV, EINV IEC: NINV, VINV, LINV, EINV Thermal Flat, IT, I2T, I4T

two stages unbalanced load protection

Supervision by definite time or • tripping characteristic

Functional Overview

PrOtective FunctiOns elements Ansi

Transformer differential protection (2 windings), Id>, Id>>, Curve with zero point and two settable slopes and short circuit differential threshold Id>>, voltage ratio between primary and secondary setable, Inrush stabilisation / detection 2 harmonics

2

87T

Restricted earth fault IdE>, IdE>>, characteristics similar to 87T 2 87G (64REF)

I, time overcurrent and short circuit protection (non-directional). Tremendous reset options (instantaneous, definite time, reset characteristics according to IEC and ANSI).

4 50P, 51P

I2>, unbalanced load protection with evaluation of the negative phase sequence currents 2 46

IB, overload protection with thermal replica for transformers IEC60255-8, alarm and trip threshold 1 49T

IH2/In, inrush detection with evaluation of the 2nd harmonic 1 Inrush

IE, earth overcurrent and short circuit protection (non-directional). Tremendous reset options (instantaneous, definite time, reset characteristics according to IEC and ANSI).

4 50N, 51N

ExP, External alarm and trip functions 4

suPervisiOn FunctiOns elements Ansi

CBF, circuit breaker failure protection for both circuit breakers 2 50BF

TCS, trip circuit supervision 1 74TC

CTS, current transformer supervision 1 60L

CLPU, cold load pickup 1

SOTF, switch onto fault 1

Non volatile event recorder up to 120 s with 32 samples per cycles

connections

Fault recorder

Event recorder

Disturbance recorder

Current Max/Min/AvgTHD Current

Current PhasorsSequence Currents

Diff CurrentsHarmonic Currents

Metering

W174TC

W186

W1Inrush

W150

W151

W146

W1 or W2CLPU

W274TC

W286

W2Inrush

W250

W251

W246

W1 or W2SOTF

W150N

W151N

W187N

W250N

W251N

W287N

87T64REF

49

W150BF

W250BF

URTD

inte

rfac

e

Bre

aker

Wea

r (2

elem

ents

)

RTD Prot

IRIG

Com

m In

terf

ace(

s)+P

roto

cols

MRDT4 Typical Configuration

3 3

Winding Side 1 Winding Side 2

Functional overview in Ansi form

current inputs 4 (1 A and 5 A) with automatic short circuitersDigital inputs Switching thresholds adjustable via softwarePower supply Wide range power supplyterminals All terminals plug typeMounting Door mountingtype of enclosure IP54Dimensions of housing 212.7 mm x 173 mm x 209 mm (W x H x D)Weight (max. components) approx. 4 kg

Woodward SEG GmbH & Co. KGKrefelder Weg 47

D - 47906 Kempen

Sales TeamPhone: +49 (0) 21 52 1 45 - 1

Fax.: +49 (0) 21 52 1 45 - 3 54e-mail: [email protected]

ServiceTelefon: +49 (0) 21 52 1 45 - 6 14/3 34

Fax.: +49 (0) 21 52 1 45 - 4 55e-mail: [email protected]

Visit us at www.eps.woodward.com DO

K_FL

Y_M

RDT4

_12.

09_E

N

Enabling Electrical Power Systems Integration

Order form MrDt4

non-directional transformer Differential Protection MrDt4

Digital Inputs

Binary out-put relay Housing Large

display

816

713

B2B2

--

AD

Hardware variant 2Standard 0

Housing and mountingDoor mountingDoor mounting 19“ (flush mounting)

AB

Communication protocolWithout protocolRS485/terminals, Modbus RTU, IEC60870-5-103Modbus TCP, IEC61850 prepared (Hardware interface)/Ethernet 100 MB/RJ45 connectorProfibus-DP, optic fibreProfibus-DP, RS485/D-SUBOptic fiber, Modbus RTU, IEC60870-5-103RS485/D-SUB, Modbus RTU, IEC60870-5-103

ABc

DeFG

Presetting of available menu languagesStandard English/German

The devices can be updated via device front interface (RS232) and PC locally