Frequency 5.8GHz
360°
Operating Temperature
Environmental Protection
Rated voltage
3 DIMENSIONIncandescent Lamp : Max. 2000WAC Halogen Lamp : Max. 1000WLV Halogen Lamp : Max. 1000VA / 600WFluorescent Lamp : Max. 900VA / 100µF 25 x (1 x 18W); 12 x (2 x 18W) 15 x (1 x 36W); 7 x ( 2 x 36W) 10 x (1 x 58W); 5 x ( 2 x 58W) Max. 1000VA/600W (uncompensated) LED Lamp : Max. 500VA / 400WEnergy Saving Lamp : Max. 600VA / 400W (include CFL and PL lamp)
0oC to +45oC
DetectionAngle
Adjustable up to Φ14m (H=2.5 - 5m)Adjustable up to Φ10m (H=5.5 - 10m)
DetectionRange
PMSMCS
2.2 Characters of high frequency presence detector
2.2.1 High frequency sensor is able to penetrate non-metallic materials such as wood board, brick wall, glass, etc, but it can not penetrate water and metal. 2.2.2 High frequency presence detector range is less affected by temperature (0°C to +45°C), airflow, wind, etc..2.2.3 The humidity, vibration as well as measurement of moving object can effect the performance of high frequency detector.2.2.4 The detector is more sensitive for movement at different speed which lead to larger detection range and it is less sensitive for movement at same speed, therefore, the detection range could be reduced.2.2.5 The sensor can penetrate non-metallic materials which could false activation of the sensor. Great consideration should be given when choosing the location of detector.
4 INSTALLATION AND WIRING
Time 1 (for lighting): Adjustable from approx. 10sec to 30min, Test &Time 2 (for HVAC): Adjustable from approx. 10sec to 60min
1s.
Auto Off TimeAdjustment
PMSMCS
1 PACKAGE CONTENT
Installation and assembly of electrical equipment mustbe carried out by skilled qualified electricians. Contact a qualified electrician in the event of fault or break down.
TECHNICAL SPECIFICATIONS
TECHNICAL SPECIFICATIONS
INSTRUCTION MANUAL
Please disconnect power completely and read the entire instruction manual carefully before installation.
The high-frequency output of radar module is <1mW; approximatelyjust 0.1% of the transmission power of a mobile telephone or the output of a microwave oven.
The penetration of detector for different materials, please see belowtable:
4.1.2 Helpful tips for installation
Material Penetration Attenuation
PVC & plastic Yes 5% - 10%
Wood Yes 10% - 20%
Glass
Yes, the different thicknesses of glass can result in different attenuation
15% - 30%
Brick
Yes, the brick wall with thickness less than 30cm
No, the brick wall with thickness over 30cm
60% - 70%
100%
100%
100%
Reinforced concrete
Metal
No
No2.1 Features
4.1 Select a proper locationHIGHBAY PRESENCE DETECTOR
FOR 10M HEIGHT MOUNT
Class ⅡIP40 (Flush mount with power box cap SP-96 and European standard junction box) IP54 (Surface mount with junction box JB-41)
PMSMCS: Φ107 x 48mm
Detector with SP-96 power box cap
Detector with JB-41 junction box
Φ107
48
Φ52
33
52
.5
Φ107
Φ107
Φ59
81
33
FIG.2-B
4.1.1 Detection coverage
LuxAdjustment
2 PRODUCT DESCRIPTION
Detector
1
Manual
1 12
Screw Φ3x 16mm
Accessories for optional purchase
IR remotecontroller
FIG.1-B
FIG.1-C
FIG.1-A
A circuit breaker (250VAC, 10A) type C according to EN60898-1 of loadⅠ(CH1) shall be installed in the fixed wiring for protection.A circuit breaker (250VAC, 6A) type C according to EN60898-1 of loadⅡ(CH2) shall be installed in the fixed wiring for protection.Do not mount on conductive surface. Do not open the enclosure frequently.Turn off power when change the light sources.High in-rush current would be caused when bulbs of certain brands burned which might damage the unit permanently.Not suitable to be used with dimmers
CAUTION!
Can be mounted at height up to 10m, it is ideal for using in the building of high ceiling, such as warehouse, gymnasium, etc.High sensitivity for detecting the slightest movement.Sensitivity will not be changed no matter the movement is across ortowards to the detector. Powerful circuit design to control all kinds of lamps.A light detecting sensor is built-in for setting the desired light level to switch on the controlled lighting automatically at the right timingto maximize energy savings and save more of your electricity expense. Various mounting methods, including ceiling flush mounted with spring clips SP-96 power box cap directly or combined with the existing European standard junction box and ceiling surface mounted with the JB-41 junction box.Except the provided Lux values, the ambient light level can be read-in either by IR or knob as the threshold for switching on / off the loads for more flexible application.
Load< 1mW Approx. 1000mW
HD-611Fi / HD-611AFi
HIGHBAY PRESENCE DETECTOR FOR 10M HEIGHT MOUNT
FIG.2-A
2.5
- 5m
5.5
- 10
m
Φ14m
Φ10m 4.3.2 PMSMCS controls staircase timer switch (Time1 should be set to ) (See. FIG.6)1s.
4.3 Wiring
4.4 Installation procedure
To secure the correct wiring, please re-check it carefully after wiring.
NOTE
4.1.3 When mounting the detector on ceiling
FIG.3
B 4m (at A < 30cm)B 1m (at A 30cm)
A
Detector
<< <
B
Please keep the detector at least 4m (B) away from the wall of wooden, glass or brick material which thickness is less than 30cm (A) or 1m (B) away from the wall which thickness is over 30cm (A). Also, users can adjust Meter knob to decrease the sensitivity and coverage, which can avoid false triggering when people passing through outsidethe wall.
4.1.4 The water-flow in water pipes would be possible to trigger the HF detector. It is recommended to keep the detector away from the waterpipe as the following guidelines to avoid nuisance triggering.
FIG.4
Water pipes(Dia. Φ10cm)
2m<2m<
Water pipes(Dia. Φ10cm)
Water pipes(Dia. Φ10cm) <
Water pipes(Dia. Φ10cm)
1m< 1m<
<
<
<
4.4.1 Flush mount with European standard junction box
4.4.1.1 Take off decorative frame of PMSMCS, then take the detector head apart from power box by unscrew its 4pcs non-dropping screws (See FIG.9).
FIG.10
4.4.1.2 Pull out AC power cables from European standard junction box then strip off 6 - 8mm of cable sheathing for wiring (See FIG.10 ).
FIG.9
Non-droppingscrew
Power box
Decorativeframe
Detector head
6 - 8mm
30 - 35mm
6 - 8mm
30 - 35mm
4.4.2 Flush mount with power box cap SP-96 4.4.2.1 To install detector, please drill a hole with diameter of 65mm on ceiling board and keep the power cable out- side. Please strip off 6 - 8mm of cable sheathing for wiring (See FIG.12).
FIG.12
4.4.2.4 Close up detector’s two spring clips and insert detector into the drilled hole on ceiling (See FIG.14).
4.4.2.5 Restore the power supply.
4.4.1.3 Fix the power box into European standard junction box with 2pcs screws (See FIG.11).
4.4.1.4 Fix the detector head on power box by inserting its four non-dropping screws into the corresponding screw holes, then cover up the decorative frame (See FIG.9).4.4.1.5 Restore the power supply.
Φ=65
Drill a hole with Φ=65mm on theceiling
4.4.2.2 Use screwdriver to break the rubber gasket on SP-96, then feed cables through it (See FIG.13).4.4.2.3 Please refer to illustration of FIG.5 - FIG.8 for correct wiring and then screw the SP-96 tightly.
FIG.11
FIG.13
FIG.14
Case 2: Manual on switching (Lux settings is invalid):If the lighting is under off mode, it can be manually switched on.If the lighting is switched on manually by pressing ( 1sec) thepush button (activate the manual on mode), it keeps on while the detector is triggered constantly, and it turns off when no movement detected and the switch off delay time elapsed, andthe detector backs to the last setting mode before entering intomanual on mode. If the device is in the manual on mode, the second press on the push button activates the manual off mode.
Case 1: Manual off switching (Lux settings is invalid):If the lighting is under on mode, it can be manually switched off. If the lighting is switched off manually by pressing ( 1sec) thepush button (activate the manual off mode), it keeps off even thedetector is triggered. If the room is vacant for a longer period (switch off delay time elapsed), the manual off status (= manual off mode) is deactivated, then the detector backs to the last setting mode before entering into manual off mode. If the device is in the manual off mode, the second press on the push button activates the manual on mode.
4.2 Function
4.2.1.1 Terminal of R and push button (N.O.) can be series connected to enable nianucolly on/off control on load. (case 1: on → off; case 2: off → on). While pressing push button ( 1sec):Please note, this function is invalid when the lighting (detector) is in the On 8hrs & Off 8hrs conditions set by IR remote control.
4.2.1 The function of R terminal
According to the changeable ambient light level, detector canpostpone load’s delay time of turning on and off to avoid load’sunnecessarily switching due to rapid ambient light change:Ambient light level changes from bright to dark: If the ambient light level keeps be lower than the preset Lux value for10sec, the light will be automatically switched on after 10sec.(LED will be on 10sec for indication)Ambient light level changes from dark to bright: If the ambient light level continuously exceeds the switch off Lux value for 5min, there are different reactions according to the time setting value.Time setting 5min, the light will be automatically switched offafter 5min.Time setting < 5min, the light will be automatically switched offwhen the set time reached if no movement is detected during the5min. But if there is movement detected within the 5min, the time will be reset upon detection and until 5min later, the light is switched off.
<
4.2.2 Ambient light appraisal
4.3.1 PMSMCS for standard application (See. FIG.5)
4.3.4 PMSMCS controls staircase timer switch (Time should be set to ) (See. FIG.8)
4.3.3 PMSMCS For standard application (See. FIG.7)
FIG.5
FIG.7
FIG.8
1s.
Φ=65Power cable
Spring clips
PMSMCS
R
N N L L’
R
Load
Pushbutton(N.O.)
N
L
PMSMCS
R
N N L L’
R
Load
N
L
D2 D1
A1 A2
SupplyVoltage
Contactor
Fan
Heater
M
ManualSwitch
Pushbutton(N.O.)
R
N N L L’
R
Load
Staircase timer
Pushbutton(N.O.)
Pushbutton(N.O.)
N
L
PMSMCS
LN
OUTIN
μ
FIG.6
R R D2 D1
N N L L’
Load
Staircase timer
Pushbutton(N.O.)
Pushbutton(N.O.)
N
L
LN
OUTIN
μ
Load for HVAC Power supply
PMSMCSCable entry
Power box capSP-96
Non-droppingscrew
Rubber gasket
LoadⅠ(L’) for Lighting: µ
230V~±10% 50/60Hz
PMSMCS
Adjustable from approx. 10Lux to (∞) and“ ” (learning range: 10Lux - 2000Lux)
1 4 2
Junction box JB-41
Non-droppingscrew Φ3×15mm
Wood screw Φ4 × 25.4mm
1
Power boxcap SP-96
Rubberwasher
Pattern
Item
Quantity
Accessories supplied
Item
Quantity
<
<
<
Installationheight
Detection range
H=4 - 5m
H=2.5 - 3.5m
H=5.5 - 10m
Φ14m
Φ14m Φ2m
Φ10m
Meter knob set “+” Meter knob set “-”
An additional function of manually switching on / off the controlledload is feasible by connecting to a push button switch.IR remote control is available for easy and quick settings
5.1 Setting of Meter, Lux and Time knobs
Knob(Ex-factorysetting)
Function Knob setting
Delay off time forlighting
Time1
15m
5m
10s30m
Test1s.
15m
5m
10s30m
Test1s.
Time
Set the light valuefor switchingon load
Set the sensitivity of detector
+-
6 TROUBLE SHOOTING
7.1 It is strongly recommended to purchase our high quality IR remote controller IR-11H for easy and safe setting operations on PMSMCS.
7.2 Push button function:
When PMSMCS works abnormally, please check assumptive problems and suggested solutions in below table that will hopefully to solve your problem.
Problem Possible cause Suggested solution
1. Detector is nuisance triggered.
2. Wired incorrectly.
1. Keep away from detection coverage to avoid activating detector while doing the test.2. Make sure load and wires are connected correctly.
LED does not turn on
1. No power is supplied.2. Incorrect wiring.
1. Switch on the power.
2. Connect the load referring to the wiring diagrams (See FIG.5 - FIG.8 ).
Nuisance triggered
Lighting devicedoes notturn off
Lighting devicedoes notturn on
1. Wired incorrectly.
2. Malfunctioned load.
1. Refer to wiring diagrams for correct connection.2. Replace the disabled load with a new one.
1. Reflective metallic materials.
2. Vibration of installation surface.
1. Check if the sensor is aiming toward any reflective metallic materials.2. Check if the detector is mounted on the vibrational surface.
NO. A B The distancebetween A and B
1
2
3
4
41
60
70
85
41
60
70
85
41mm
60mm
70mm
85mm
FIG.15-B
4.4.3.2 To feed AC power cables through the side of junction box, please use the cutting pliers to break the cable entry knockouts on the side of junction box, then insert cables into junction box and feed through it. Strip off 6 - 8mm of cable sheathing for wiring (See FIG.16).
4.4.3.3 Choose proper knockouts to fix the junction box JB-41 on the surface of ceiling board with 2pcs wood screws attached with rubber washer (See FIG.17).
5.3. Walk test (Lux is invalid)
4.4.3.4 Insert 4pcs non-dropping screws to the corresponding screw holes on detector’s fixing plate, and those 4pcs screws will not drop off to provide convenience to the subsequent installations (See FIG.18).
FIG.15-A
A
Konckouts
Knockouts
85
85
70
70
60
60
41
41
857060
41
B
85
706041
FIG.16
FIG.17
FIG.18
Non-droppingscrew
Non-droppingscrew
85
70
70
60
60
41
41
Rubberwasher
Earthterminal
4.4.3.6 Cover up the detector’s decorative frame and restore the power supply.
FIG.19
4.4.3.5 Refer to wiring diagrams for correct wiring connection (See FIG.5 - FIG.8). There is a square hole in the fixing plate, when you put the fixing plate into the junction box, please fit the fillister to the junction box’s protrusion (See FIG.19), then fix the detector head on the power box following FIG.9 and assemble them with the attached 4pcs non-dropping screws.
Non-droppingscrew
8570
6041
Square hole
Protrusion
Set delayoff time forHVAC
Time2
30m
60m
15m
10s
Range:Adjustable from approx. 10sec to 60min
10
100300
2000
FIG.21
The purpose of conducting the walk test is to check and adjust the detection coverage.
Test procedures:
5.3.1 Tester must be within the detection coverage.5.3.2 Switch the power on.5.3.3 The detector takes approx. 30sec to warm up with load and LED keeps on, then turn off after warming up time.5.3.4 Walk from outside across or toward to the detection coverage until LED and load turn on for 2sec (See FIG.21).5.3.5 Adjusting Meter knob for desired detection range.
FIG.22
IR-11H
3.28.0218406110100
Range: Adjustable from “-” (approx. Φ4m) to “+” (approx. Φ14m). Refer to 4.1.1.
Meter
Lux Range : Adjustable from approx. 10Lux to “ ” (∞). (learn): The actual ambient light level (10Lux - 2000Lux) can be read in.
Range: Adjustable from approx. 10sec to 30minTest : Test mode (Load and red LED will be 2sec on, 2sec off) : Short impulse mode for staircase timer switch control (Load will be 1sec on, 9sec off)
1s
Learning procedure:
5.2 Lux learining function with knob
10
100300
2000
10
100300
2000
10
100300
2000
10
100300
2000
10
100300
2000
Adjust knob to” “ from other position
Adjust knob toother positionfrom ” “
1sec after, goesback to ” “
FIG.20-A
FIG.20-B
FIG.20-C
W
LED and load off
Detector switches to AUTO mode
W
LED and load keep on 5sec(the actual light level range is 10 - 2000Lux)
LED flashes slowly for 25sec & Load is off
W
LED flashes quickly for 5sec & Load is off (the actual light level range is out of 10 - 2000Lux)
W
5.2.1 Adjust the knob to “ ” when the ambient light level matches with the desired value (See FIG.20-A).5.2.2 When the knob is set to “ ” originally, it should be adjusted to other position more than 1sec, then goes back to “ ” (See FIG.20-B). 5.2.3 Then the load is off. LED starts to flash slowly indicating entering into learning mode. Learning will be completed within 25 seconds. Afterwards, the LED and load will keep on 5sec or LED flash quickly for 5sec and load is off to confirm successful learning (See FIG.20-C).5.2.4 After learning procedure, the detector returns to AUTO mode with LED and load being off.
5 OPERATION AND FUNCTION
4.4.3 Surface mount with junction box JB-41
4.4.3.1 There are 4 pairs of knockouts with various distances from 41mm to 85mm on the junction box JB-41 can be selected for different mounting applications (See FIG.15-A). Select two same figures on both ends for the corresponding distance for fixing (See FIG.15-B).
Cable entryknockout
6 - 8mm
30 - 35mm
7 OPTIONAL ACCESSORY
Due to our policy of continuous improvement we reserve the right to change specification without prior notice.Errors and omissions excepted. These instructions have been carefully checked prior to publication. However, no responsibility can be accepted by E-Matic for any misinterpretation of these instructions.
RoHSConform
Copyright 2014.CAll rights reserved. No reproduction, copy, or transmission of this product may be made without writing permission.
OFF
To lock IR-11H buttons
By pressing “ ” button, IR-11H buttons will be locked and no key function is workable (Except “ ” & “ ”).
By pressing “ ” button, IR-11H buttons will be unlocked. Thereafter, IR remote controller can be used to set presence detector. The default channel is CH1 (LoadⅠ) after unlocking IR-11H.When operating IR-11H to detector under unlock mode, detector will lock automatically 5min after the last operating if “ ” button is not pressed.
Unlock IR-11H buttons
To set loadⅠ(CH1) off for 4hrs or 8hrs
By pressing “ ” button, the load connected to detector will beturned off for 4hrs or 8hrs depending on the incorporated product.Detector will return to auto mode after 4hrs or 8hrs. Or press “ ” button again to exit this “4hrs or 8hrs off mode” during this period, detector will return to auto mode. Or switching off power supply of presence detector for 5sec and re-supply it again to lead detector to auto mode.LoadⅠ(CH1) can be lead to on mode by pressing “ ” button under off mode.ON
OFF
OFF
TESTTest mode
By pressing “ ” button to enter into Test mode, it is confirmed by flashing of detector’s LED for 2sec. Walking through the detection coverage, both loadⅠ(CH1) and detector’s LED turn on 2sec once detector is triggered (Reaction is regardless of Lux value).LoadⅡ(CH2) has no reaction in test mode.
TEST
Button Function
ONBy pressing “ ” button, the load of detector will be turned on for 4hrs or 8hrs depending on the incorporated product. Load will be turned off after 4hrs or 8hrs and return to auto mode. Or press “ ” button again to exit this “4hrs or 8hrs on mode” during this period, detector will return to auto mode. Or switching off power supply of presence detector for 5sec and re-supply it again to lead detector to auto mode.LoadⅠ(CH1) can be lead to off mode by pressing “ ” button under on mode.
To set loadⅠ(CH1) on for 4hrs or 8hrs
ON
ON
OFF
Button Function
To reset settings on presence detectorBy pressing “ ” button aiming to the detector, all settings on presence detector will go back to potentiometers’ settings, and all MEMO data will be deleted.
1. Set the desired Lux and time values on one detector by using IR remote controller.2. Then by pressing “ ” button for approx. 3sec aiming to above detector, the Lux and time settings of this detector will be saved into this IR remote controller confirmed by detector’s LED flashing.3. By pressing “ ” button again for approx. 1sec aiming to a new detector, the saved settings can be duplicated to the new detector. 4. Transfer the settings to detectors desired by repeating above last step. If no data is saved in IR remote controller, detector has no reaction after press “ ” button. 5. Battery removed for more than 5sec or “ ” button is pressed, all the data in IR remote controller will be deleted.
By pressing corresponding button, the selected light level threshold is set to presence detector for switching on the connected load. LoadⅡ(CH2) is independent of Lux value.
To adjust Lux value
The previous setting values can be stored and duplicated to other detector
10Lux
2000Lux
~
MEMO
MEMO
MEMO
MEMO
To read-in the actual ambient light levelActual ambient light level can be read-in as threshold for switching the connected load, if the provided Lux values do not match user's requirement. The steps are as below: Press “ ” button till detector's red LED flashing to enter into learning mode, learning time is 10sec. Then the actual ambient light level is read-in confirmed by both load and LED turn on for 5sec to indicate IR-11H learning successfully and then turn off. Afterwards, it returns to Auto mode.Note: If the ambient light level is out of the range of 10 - 2000Lux, detector will learn for 10sec, then LED flashes quickly for 5sec to indicate IR-11H learning is failed, and the alternative of 10Lux or 2000Lux value will be stored depending on under 10Lux or above2000Lux value.
1Min.
60Min.
~
By pressing “ ” button to enter into short impulse mode, it is confirmed by flashing of detector’s LED for 2sec. LoadⅠ(CH1) will be on 1sec and off 9sec when detector detects movement. Detector acts depending on movement and the pre-set Lux value under short impulse mode.
Short impulse mode for loadⅠ(CH1)
Time2
Time1By pressing “ ” to set the delay off time value of loadⅠ(CH1), and “ ” to set the delay off time value of loadⅡ(CH2). “ ” is invalid if the detector has only one load.
Time2
Time2
Time1
Select load for time setting
Time setting for Time / Time1 or Time2By pressing “ ” “ ” to select the load desired to set the delay off time value. Either “ ” or “ ” is pressed, LED flashes 2sec, and then press the corresponding time value button to set it, which is confirmed by detector’s LED flashing for 2sec.
Time2
Time2
Time1
Time1
8 TROUBLE SHOOTING OF IR-11HWhen remote controller IR-11H works abnormally, please check assumptive problems and suggested solutions in following chart that hopefully solve your problem.
Problem Suggested solution Possible cause
Detector fails to receive signal
Fail to transmit signal
1. Exceed the transmission range.
2. Low battery power.3. Detector works abnormally.
1. Low battery power.2. Press two or more buttons once.
In locked mode.
1. Operate within transmission range, and ensure IR-11H aims directly to the detector.2. Replace a new battery.3. Check the trouble of detector, then refer the TROUBLE SHOOTING of detector manual for reparing.
1. Replace battery.2. Press one button once.
Unlock IR-11H.
No signal
Button Function
+SEN
SEN
-
By pressing “ ” “ ” buttons to set the sensitivity of sensor. Each time the user presses the button, the sensitivity of sensor would increase or decrease 10% with indication of red LEDflashing. By pressing “ ” button to increase the sensitivity of sensor.By pressing “ ” button to decrease the sensitivity of sensor.When the sensitivity of sensor is at its highest or lowest level which is confirmed by red LED keeping on for approx. 2sec.
+SEN
+SEN
SEN
-
SEN
-
Adjustment on sensitivity of detector