Upload
others
View
12
Download
0
Embed Size (px)
Citation preview
High Voltage Testing and Engineering Commission
Fachkommission für Hochspannungsfragen
Cable testing
Proof of proper assembly and installation of the cable systems is the primary consideration
when carrying out on-site voltage testing of high-voltage cable connections.
The on-site AC voltage testing technology for high-voltage cables that is now used throughout
the world was developed jointly by the Swiss Federal Institute of Technology Zurich (ETH) and
FKH, and was introduced by FKH in the 1980s. It is based on the series resonance principle
with a tuneable frequency. Various other diagnostic methods, including partial discharge (PD)
measurements in particular, are offered in addition to voltage testing.
High-voltage series-resonant testing of cable systems
Prior to commissioning a new cable system, or after the completion of major conversion work
on an existing system, voltage testing is recommended before starting to operate the system.
The aim is to exclude the following faults in particular:
Assembly errors in cable terminations or joints
Damage to the cable sheath or the semiconding screen
In compliance with CENELEC HD 632 and in divergence from IEC 60840 and/or 62067, FKH
recommends that a higher test voltage should be applied to cables, but for a reduced testing
duration. This recommendation is based on FKH's lengthy experience of testing.
Recommended test procedure depending on the system voltage
In the test circuit, an inductance L with a high quality factor is connected in series to the test ca-
pacitance Cx of the object. Under resonance conditions, a voltage UP builds up over the test ob-
ject that is considerably greater than the voltage UT of the supply transformer. The test frequency
is obtained with the following formula:
Thanks to its modular inductances, the test system can be configured for a sufficiently high test
frequency to ensure that voltage transformers do not reach magnetic saturation; this eliminates
the need to remove them for the test.
Diagram of a series-resonant system
U / U0 Utest Utest/ U0 Test
duration
45 / 26 kV 57 kV 2.2 15 min
60 / 36 kV 80 kV 2.2 15 min
110 / 64 kV 140 kV 2.2 15 min
132 / 76 kV 167 kV 2.2 15 min
150 / 87 kV 190 kV 2.2 15 min
220 / 127 kV 254 kV 2.0 15 min
275 / 160 kV 320 kV 2.0 15 min
380 / 220 kV 400 kV 1.8 15 min
totCLf
=
2
1
Series-resonant systems are virtually the only possible high-voltage sources for AC voltage tests
on lengthy XLPE- and EPR-insulated cable sections with typical capacitance values (conductor /
to screen) of 0.1 to 0.5 µF per km. This restriction is due to the high charging current IC and/or the
high reactive power Q. Oil cable systems can also be tested according to this principle.
Advantages over other methods
Power supply required is low
Voltage at the test object is sinusoidal and free of
harmonics
Minimal energy release at the fault location in case of
test object breakdown
If the inductances are connected in parallel, the
frequency can be increased so that voltage transform-
ers can be included in the testing
Additional cable connections and other equipment
connected via switchgear can also be included in the
testing
Concept for integral testing of complete systems
Partial discharge measurement and other diagnostic methods
A partial discharge measurement is recommended as an additional measure for important cable sections and higher voltage levels. This involves specific inspections of the cable termi-nations and joints in order to identify insulation faults. In this way, it is possible to detect flaws that have not yet caused an immediate breakdown, but which harbour the risk of an unex-pected insulation failure.
FKH uses the following partial discharge test methods and coupling types: :
Conventional, via a coupling capacitor
With partial discharge sensors integrated into the fittings (joints, terminations)
Via current sensors on the cable shielding
With acoustic emission sensors
For oil-insulated cables and in the medium-
voltage grid, FKH also performs C-tgδ mea-
surements as well as measurements of the
polarisation and depolarisation currents
(PDC).
The modern partial discharge measure-
ment instruments used by FKH allow syn-
chronous measurements at different points.
To capture all partial discharges simultane-
ously, fibre-optic (OWG) connections must
be installed between all the sensors in
advance.
High-voltage resonance test on a 275 kV
cable connection
Partial discharge level during a voltage test
Cable testing system in outdoor switchgear
Series resonance system on an offshore
wind power converter platform with test ca-
ble adapters
Complete experimental setup for cable testing
with partial discharge measurement in the
gallery of a hydroelectric power plant
FKH Head Office
Hagenholzstrasse 81
8050 Zurich
FKH Insulating Oil Laboratory
4658 Däniken
FKH Experimental Station
4658 Däniken
Phone: +41 62 288 77 99
Fax: +41 62 288 77 90
Phone: +41 44 253 62 62
Fax: +41 44 253 62 60
Phone: +41 62 288 77 95
Fax: +41 62 288 77 94
www.fkh.ch / [email protected]
HIGH VOLTAGE TESTING AND ENGINEERING COMMISSION
@ FKH-2021-01