High Resistance Grounding Tech Paper

Embed Size (px)

Citation preview

  • 8/16/2019 High Resistance Grounding Tech Paper

    1/9

    Francis K. Fox, Howard J. Grotts, and Clyde H. Tipton

    IEEE Transactions on Industry and General Applications

    September/October 1965 E

  • 8/16/2019 High Resistance Grounding Tech Paper

    2/9

    Francis K. Fox, Howard J. Grotts, and Clyde H. Tipton

    IEEE Transactions on Industry and General Applications

    September/October 1965

    Approved by the Petroleum Industry Committee for

    presentation at the IEEE Petroleum Industry TechnicalConf., Houston, Tex., September 13-15, 1965.

    Francis K. Fox is with the Central Electric Company, San

    Francisco, Calif.

    Howard J. Grotts is with the Tidewater Oil Company,

    Avon, Calif.

    Clyde H. Tipton is with the Standard Oil Company of 

    California, Richmond, Calif.

    Abstract - A method is described which has been used to

    reduce the difficulties encountered on several old

    delta-ungrounded systems. Data are included which will help

    in applying this to any particular power system. The scheme

    gives an alarm whenever a ground fault occurs, permits every-

    thing to keep running even more assuredly than with an un-

    grounded system, and provides a method for quickly locating

    the fault. Circuit diagrams and photographs of actual equip-

    ment are included, and operating practice is summarized.

      Introduction

    Should electric power systems be grounded and if so, what

    is the best method to use? Much has been written, and many

    heated arguments, not recorded, center about this subject. Be-

    fore describing any one particular scheme, the authors will at-

    tempt to summarize the entire subject as objectively and as

    briefly as possible.

    An ungrounded system is one in which no intentional con-

    nection is made between any part of the system and ground.

    Such a system is nevertheless grounded by the effect of the

    distributed resistance and capacitance (mostly capacitance)which exists between all the conductors (cables, motors, trans-

    formers, etc.) and ground.

    A grounded system is one in which an intentional con-

    nection is made between the power system (preferably at the

    neutral junction) and ground, either directly or through an im-

    pedance.

    Present industrial power system practice seems to indi-

    cate a greater need for some form of system neutral ground-

    ing, as the voltage of the system increases. Many 480-volt sys-

    tems have successfully operated ungrounded for years, but ex-

    perience with the higher voltages has been such that almost all

    12-kV systems are grounded. Between these two voltages area great variety of grounding conditions: Most of the older

    2400-volt systems are ungrounded. Many 6900-volt systems

    are still ungrounded. The best results in grounding 6900- and

    12 000-volt industrial systems have been obtained by ground-

    ing the neutral through a resistor to limit ground-fault current

    to a desirable value, but retaining enough to produce selective

    tripping of breakers. Some 4160-volt systems are solidly neu-

    tral grounded although, for industrial service, there is much

    preference for resistance grounding at this, as well

    as at other voltage levels above 600 volts. Power

    company practice is usually to ground the neutral

    solidly, if available. Many 480-volt industrial sys-

    tems have been solidly grounded. In the last few

    years, many 2400- and 4160-volt systems have been

    resistance grounded with ground-fault immediate

    tripping of breakers or high-voltage motor control-

    lers.

      What determines the best power system? The

    ideal system would be one in which a failure neveroccurred but, even if such a system could be built,

    the cost would be prohibitive. So power systems are

    designed to produce as little trouble as possible.

    The hooker is in defining the word “trouble.”

    First, there is the difficulty of obtaining the money

    with which to build the power system: no one can

    overlook that trouble. Next, recollect all the trouble

    you have experienced from power outages or equip-

    ment failures and what it cost you. You have read or

    heard about other engineers’ troubles; evaluate them

    as they might affect you if those same troubles ap-pear in your plant.

    The next step is devising a system with features

    for protecting against these troubles. However, the

    cost of the various protective features must always

    be balanced against the cost of the troubles.

    Electrical failures occur in many ways, but most

    failures originate as ground faults. In this paper, the

    authors are confining themselves to a brief summary

    of how system neutral grounding may affect the

    trouble which such failures produce.

    For most industrial power systems 2400 volts

    and above, probably the least trouble will be pro-duced if the system neutral is grounded through a

    resistor which will limit ground-fault current to a

    few hundred amperes, but will retain enough cur-

    rent to trip a breaker immediately and remove the

    faulty equipment from the system. This method of 

    grounding has the following advantages:

    1) System overvoltages are reduced both in mag-

    nitude and duration.

    2) Faulty equipment is immediately known.

    3) Damage at the point of fault is negligible.

    4) Hardly any voltage disturbance is noticed on

    the system, and no other loads are affected.

    5) Methods for detecting and removing ground

    faults in modem switchgear with the use of breakers

    (not fuses) and high-voltage motor controllers are

    accurate, sensitive, and economical.

    E-

  • 8/16/2019 High Resistance Grounding Tech Paper

    3/9

    Francis K. Fox, Howard J. Grotts, and Clyde H. Tipton

    IEEE Transactions on Industry and General Applications

    September/October 1965 E

    However, this method has several disadvantages:

    1) No warning precedes the tripping of a breaker or the

    opening of a motor contactor.

    2) Sudden stoppage of a motor, or of all loads on an entire

    circuit, may cause considerable damage to a process plant.

    3) On an old system, adding needed neutral grounding

    equipment and ground-fault relaying is expensive.

    For various reasons, there are many ungrounded 2400- or

    4160-volt systems in operation. These systems are all subject

    to the following possible troubles:

    1) Certain types of ground faults can produce dangeroushigh transient overvoltages throughout the entire system.

    2) These overvoltages can a) produce an immediate fail-

    ure of some other equipment on another feeder resulting in the

    simultaneous tripping of two breakers, or b) weaken other in-

    sulation so that the next failure will take place sooner.

    3) A ground fault sometimes goes unnoticed for days or

    weeks. Even if no dangerous transient overvoltages are pro-

    duced, such a fault usually develops into a phase-to-phase fault

    with consequent increased damage at the point of fault.

    4) It is annoying, time consuming, and sometimes hazard-

    ous to locate the ground fault by switching loads on and off, inorder to remove the faulty equipment from the system.

    High Resistance Grounding System Utilizing Pulsing

    Ground-Fault Detector Apparatus*

    This high-resistance grounding scheme was developed to

    overcome the troubles which are associated with an ungrounded

    system and which have already been described. Briefly, the

    scheme is designed to

    1) Eliminate the high transient overvoltages which can

    appear during arcing ground faults.

    2) Give immediate warning when a ground fault occurs.3) Accomplish this with a minimum of system neutral

    grounding, so that the current at the ground fault will be only

    slightly greater than (but perhaps even less than) the fault cur-

    rent would be if the system were left ungrounded. (In the case

    of a sputtering fault, the ground-fault current in an ungrounded

    system may be increased to several times the bolted-fault value.

    High-resistance grounding will hold the current value to sub-

    stantially the steady-state bolted-fault value.)

    4 Enable the system to continue operation with a single

    line-to-ground fault present, in the same manner as an un-

    grounded system. (The high-resistance grounding circuit is anexcellent damper of high-frequency transient oscillations so

    that, in some cases, the ability to continue operation might be

    enhanced.)

    5) Provide a means for pulsing the current into the ground

    fault, so that it can be traced to the point of fault. This pu

    is accomplished without ever removing the high-resist

    neutral grounding connection.

    6) Provide a means for measuring the system-char

    current so that the proper degree of minimum neutral gro

    ing by high resistance can be accomplished.

    System-charging current is the highly leading power

    tor ground-fault current (on an ungrounded system) requ

    to charge the capacitance of the other two phases to gro

    The component of ground-fault current controlled by

    high-resistance neutral ground must be slightly greater the system charging current. The reason for this, as well

    complete explanation of the nature and causes of system

    ervoltages can be found in the General Electric Indus

    Power Systems Data Book [1].

    Description of System

    Figure 1. illustrates the manner in which groundin

    accomplished. The system neutral is derived by three s

    (3- to 10-kVA) transformers, connected wye-broken delt

    shown. The primary neutral is grounded through a cur

    transformer and ammeter, so that ground fault current cameasured. The secondary neutral is connected to a res

    with taps, so that the proper resistance can be used to co

    the current which will flow into a ground fault. The s

    arrows show the path of the ground-fault current. Notice

    the ground-fault current is equally divided in the three s

    transformers, and that it also circulates through the delta

    ply system. The arrows represent currents which are in ph

    *U. S. patent pending; applied for by F. K. Fox for the

    General Electric Company.

    Fig. 1. Diagram of grounding method for system ha

    ungrounded delta power supply of 24UO or 4,160 volts:

    trol and protective circuits not shown.

  • 8/16/2019 High Resistance Grounding Tech Paper

    4/9

    Francis K. Fox, Howard J. Grotts, and Clyde H. Tipton

    IEEE Transactions on Industry and General Applications

    September/October 1965 E

    Corresponding currents in the secondary neutral circulate in the bro-

    ken delta and through the resistor. This method is equivalent to losing

    the delta and grounding the primary neutral through a high resistance.

    Figure 2 presents the actual voltage conditions, both normally and

    with a ground fault on the system. A typical 2400-volt power system

    of around 5000 kVA may require 3 amperes, as shown, at the point of 

    fault. This would produce 1 ampere in each primary and, if the trans-

    former ratio is 20 to 1, a current of 20 amperes through the resistor at

    208 volts. This allows using a low-voltage resistor and pulsing contactor.

    With no ground fault on the system, the voltage at the broken deltais zero. When a ground fault occurs, this voltage increases to a maxi-

    mum of 208 volts, so that the voltage relay VR can give the alarm.

    For the typical system shown, this is equivalent to grounding the

    system neutral through a 460-ohm resistor. The voltage conditions

    shown are for a solid ground fault but, even for a high-resistance fault,

    enough voltage will appear across the resistor to operate the voltage

    relay and sound an alarm. For example, if the entire ground-fault path

    introduced 1000 ohms of resistance, the voltage across the resistor

    would be around 55 volts. Relay VR can be set to pick up at approxi-

    mately 16 volts, which would actually detect and give the alarm, even

    if the incipient ground fault had a resistance of approximate 4000 ohms.

    Locating the Fault

    The operator then initiates a control circuit which causes the puls-

    ing contactor to close approximately 40 times per minute to produce

    current pulses of about a half-second duration. These pulses can be

    traced to the point of fault, with the use of a hook-on ammeter, as

    shown.

    Several actual ground faults have been locate

    this manner. Several ground faults have also been

    liberately placed on systems of different types inder to check the ability of the system to follow t

    pulses to the point of fault.

    On systems involving bare overhead line

    poles, tracing the signal is simple because all the

    current is forced to return through ground. On

    tems involving conduit, tracing the signal is ha

    because the fault current tends to return through

    conduit of the circuit involved. To the extent that

    happens, the return current in the conduit cancel

    the fault current flowing out through the conduct

    the point of fault. Fortunately, even on all con

    systems, this cancelling effect is not 100 percen

    the hook-on ammeter is sensitive enough and if

    insensitive to other local magnetic effects, the

    can be located. The return current divides into str

    unpredictable patterns and appears on conduits

    metal structures not associated with the faulty cir

    Also, these structures very often carry current at

    utable to other causes not associated with the fau

    any case, the definite rhythmic pulse of

    ground-fault current is extremely helpful.

    The signal receiver which has been found m

    useful in tracing the pulsing ground-fault curre

    the hook-on ammeter shown in Figs. 3 and 4.

    device has a split core with a window large enoug

    encircle a 5-inch conduit. The handle is insulated f

    the core so that it can be used safely on power ca

    of 2400- or 4160-volt systems which are not in

  • 8/16/2019 High Resistance Grounding Tech Paper

    5/9

    Francis K. Fox, Howard J. Grotts, and Clyde H. Tipton

    IEEE Transactions on Industry and General Applications

    September/October 1965 E

    duit. Several degrees of sensitivity are provided. The split core

    completely encircles the conduit, or cables in air, thereby ig-

    noring the effect of other local magnetic fields to a great ex-

    tent.

    Physical Equipment

    Several types of power systems have been grounded in

    the manner described. One of the first installations is shown

    in Fig. 5. The power supply consists of a 3750-kVA 3-phase

    2400-volt transformer. Various feeders to a large tank-farm

    area originate in the switchgear in the background. Distribu-

    tion is entirely by bare overhead lines on poles. The groun

    ing equipment at this location is in four separate housin

    consisting of a fused oil switch, a 3-phase oil-immers

    grounding transformer, a relay and control panel, and a s

  • 8/16/2019 High Resistance Grounding Tech Paper

    6/9

    Francis K. Fox, Howard J. Grotts, and Clyde H. Tipton

    IEEE Transactions on Industry and General Applications

    September/October 1965 E

    erator was readily available through three single-pole

    connects. Therefore, the grounding transformer had on

    be a single-phase unit shown at the lower right. Both

    transformer and resistor sections of this equipment meat bolted covers. This 2400-volt system was found to have

    amperes charging current with a 13 000-kVA load. Th

    sistor was set to produce 4.5 amperes into a ground f

    with pulsation to 8.0 amperes while tracking the sign

    locate the fault.

    Operating Experience At Richmond Refinery

    A pulsing ground-fault detector was installed on

    2400-volt system at the Standard Oil Refinery, Richm

    Calif., in December 1963. Its primary function was to the transient overvoltages, during a line-to-ground fau

    the system. Its secondary function was to impress a puls

    the fault current so that a portable signal detector coul

    used to trace the pulse to the grounded conductor.

    The 2.4-kV system consists of three turbine-driven

    erators rated at 5000-kVA each, connected through reac

    ondary resistor.

    At another location, the same scheme has been used ex-

    cept that a spare breaker in a switchgear line-up was substi-

    tuted for the fused oil switch. This is a superior method but,

    tracing easier.

    A more compact single-enclosure construction is shownin Figs. 6 and 7. This installation is on a 4160-volt system

    involving steam turbine-generators having a total capacity of 

    15 000-kVA and two 10 000-kVA transformer sources. The

    fused disconnect switch and three dry-type grounding trans-

    formers are mounted in the left-hand high-voltage section

    which is padlocked closed. The low-voltage resistor, relays

    and controls are all mounted in the right-hand section and are

    readily accessible. Louvres are provided to ventilate the re-

    sistor, which must dissipate approximately 15kW when a solid

    ground fault occurs on the system. Normally, the resistor car-

    ries no current. This 4160-volt system was found to have a

    charging current of approximately 6.4 amperes with a totalload of 20 000-kVA. The resistor is set on the tap to produce

    6.5 amperes into a ground fault. Pulsing to 9.0 amperes is

    utilized when hunting for the fault.

    Similar single-enclosure equipment is presented in Figs.

    8 and 9. This installation also involves 15 000-kVA of steam

    turbine-generation but, in this case, the neutral of each gen-

    of course, the breaker costs more than the fused switch.

    A total of five such installations are set on a resistor tap to

    produce approximately 2.7 amperes into a ground fault, with

    pulsation to 3.5 amperes while hunting for the fault. The puls-

    ing current will probably be increased to make ground-fault

  • 8/16/2019 High Resistance Grounding Tech Paper

    7/9

    Francis K. Fox, Howard J. Grotts, and Clyde H. Tipton

    IEEE Transactions on Industry and General Applications

    September/October 1965 E

    TABLE I

    Values of Actual Tests on 2400-Volt Systems

    kVA

    Total

    Trans- (Motors*

    Motors formers and Charging Charging

    Running Connected Trans- Current Current,

    System hp kVA formers) Measured A/MVA

    Tidewater sub-

    station 1 2700 4142 6842 2.55 0.373Tidewater sub-

    station 2 4500 3000 7500 1.98 0.264

    Tidewater sub-

    station 7A 1900 1500 3400 0.42 0.124

    Tidewater sub-

    station 7B (1) 1900 1500 3400 0.29 0.085

    Tidewater sub-

    station 9 1225 1200 2425 0.34 0.140

    Richmond

    refinery

    2400-

    volt power

    plant 11 525 11 925 23 450 3.6 0.154

    *Assuming 1 hp = 1kVA for motors.

    (1) This substation feeds no 2300-volt motors smaller than 200

    hp, has only 675 feet of RL (5000 volts 3/C) cable total, 2 to 200 hp

    and 1 to 1500 hp motors were running, and 2 to 750 kVA (three 2300/ 

    440-volt) transformers were energized.

    to three separate 2.4-kV busses. Each bus is conne

    through a a reactor to a common synchronizing

    From the three busses, thirteen radial feeders dis

    ute power to load centers throughout the refinery

    10).

    Prior to installing the pulsing ground detector

    neutrals of the generators were connected throu

    resistor to ground. A 10/5-ampere current transfo

    on the grounded line was connected to a recor

    ammeter and an alarm panel. When the alarm soun

    it was the signal for a long tedious search forgrounded conductor. First, each bus section wit

    generator had to be separated from the grounding

    tem to determine which bus section contained the f

    After this had been established, feeders were p

    leled and loads switched from one bus to the oth

    order to determine which feeder contained the gro

    fault. Next, the faulted feeder was paralleled

    sectionalized until, finally, after several hour

    switching and various manipulations, the locatio

    the ground fault was narrowed down to a comp

    tively short section of line supplying perhaps fivsix motors. The motors were then shut down, one

    time, until the fault cleared The entire operation, f

    start to finish, many times required as many as e

    hours.

    There have been two ground faults on the 2.4

    system since the pulsing ground detector was insta

    The first one occurred on August 7, 1964 about

    P.M. The operating crew had witnessed a demon

    tion of the use of the Pulsator but this was the

    “real thing.” It required only 28 minutes from the

    the alarm sounded to find and shut down the fa

    motor. The elapsed time could have been consably less but, in this case, the fault happened to b

    the No. 13 feeder, the last feeder to be checked,

    was located quite a distance from the power plant

    the end of the feeder.

    The second ground fault occurred at 6:00 A

    January 4, 1965. The operating crew at the power p

    had not been on duty when the previous ground

    developed. Therefore, this was also a “first” for th

    In 18 minutes, the fault was traced to a forced-d

    fan motor on the No. 6 station service feeder.

    Thus far, the authors’ experience with the pu

    ground detector has been extremely satisfactory

    two ground faults at the Richmond Standard Oil

    finery were located in minutes, rather than hou

    was not necessary to shut down any motor-dr

    equipment while searching for the fault; and equ

    important, the hazard associated with hasty sw

    ing was avoided.

  • 8/16/2019 High Resistance Grounding Tech Paper

    8/9

    Francis K. Fox, Howard J. Grotts, and Clyde H. Tipton

    IEEE Transactions on Industry and General Applications

    September/October 1965

    Operating Experience at Avon Refinery

    The Tidewater Oil Company, Avon California Refinery, has

    eight 2400-volt 3-phase delta systems. Each system is inde-

    pendent of the others and is fed by its own 2400-volt substa-

    tion. Each substation is located at a load center. Many of these

    systems are now provided with the high-resistance grounding

    scheme, with ground-fault alarms and the pulsing signal to fault,

    as described in this paper. A red alarm light is provided above

    each substation and an annunciator alarm panel has been in-

    stalled in the refinery electric shop. When a ground fault takesplace, both the substation alarm light and the electric-shop an-

    nunciator panel will light up. So far, this alarm system has

    worked satisfactorily.

    Prior to the installation of this high-resistance grounding

    scheme, every time a “dreaded” ground fault arose, a great many

    hours were required to isolate, locate, and repair the fault. On

    a few occasions, the ground faults did not have to be tracked

    down because the trouble was actually multiple simultaneous

    failures.

    The first grounding system was placed in operation on

    October 24, 1962. The other grounding systems were installedin 1963. All the grounding systems have been in service for

    about 1 1/2 years.

    Four ground faults have occurred on systems involving

    open-wire lines since these systems have been in operation.

    The first one appeared when a potential transformer on the

    2300-volt side of a 2300/440-volt 3-phase transformer bank 

    went to ground. This transformer bank is fed from an open-wire

    overhead line by way of a pole riser from the main 2400-volt

    substation switchgear through lead-covered cable in conduit

    to the overhead line, then from the overhead line by way of 

    lead-covered cable in conduit to the transformer. The pulsing

    current was 3 and 3.8 amperes. The faulty circuit was readilyfound at the substation. It was then a matter of checking for the

    pulse current at each pole riser fed from the overhead-line cir-

    cuit until the faulty riser and the trouble was found. All in all,

    the actual “tracking down” took an hour or two. The second

    ground fault occurred when the terminal box for a 2300-volt

    800-hp motor filled with rain water. This motor was also fed

    from an overhead line in much the same manner as was the

    case with the first fault. Trouble 3 took place on the primary

    side of a poIe-mounted series lighting transformer. Both faults

    2 and 3 were tracked down with little difficulty. Trouble 4, also

    found very quickly, was a ground fault in a current transformer

    in one of the switch houses.

    A fault-tracking experience which proved more difficult

    was on an all-conduit lead-jacketed cable system with parallel

    feeders serving a crude unit. The pulse intensities used for this

    substation are 3 and 4 amperes. The fault was in

    high-voltage terminal box of a lighting transformer. With

    ground current dividing between the two parallel feeders,

    a resulting pulse current in each feeder of 1 1/2 and 2

    peres, and with much of the signal cancelled out by re

    current on the conduit, it was not possible for company

    sonnel to pick up the pulse with the nonhook-on-type si

    receiver used. By a method of elimination, the trouble

    narrowed down and the pulse was picked up in the con

    feeding the faulty transformer.

    System-Charging Current Data

    Actual charging current seems to vary from one sy

    to another. An actual test must be made on each system

    that the lowest current tap of the resistor can be used.

    test can most conveniently be made after the grounding

    tem is installed; therefore, an estimated charging current

    be ascertained at the time the equipment is purchased.

    estimated charging current should be on the “high side.”

    resistor tap must later be selected so that the ground cu

    is slightly above the actual measured charging current2400-volt systems having an operating load of 15 000-k

    and less, it has not been the authors’ experience to find a ch

    ing current over 4 amperes. The one 4-kV system te

    showed a charging current of 6.4 amperes with an opera

    load of approximately 20 000 kVA.

    The following values have been derived from the

    presented in the table:

    1) Overhead open-wire lines apparently have very

    effect on charging current unless they are many thousan

    feet in length.

    2) VL or shielded cable appears to have the most e

    (in the order of 0.4 A/1000 ft for 2400 volts and 0.7 A/10for 4-kV systems).

    3) Non-shielded cables in conduit, transformers, and

    tors also have some effect, in the order of:

    Non-shielded cables .05 for 2400 V in Amps per 100

      In conduit .08 for 4160 V in Amps per 100

    Transformers 0.3 for 2400 V in Amps per 1000

      .05 for 4160 V in Amps per 1000

    Motors .05 to .10 for 2400 V Motors in Amps per 1000

     .07 to .12 for 4000 V Motors in Amps per 1000

    4) Aerial cable approximates the value of cable in

    duct.

    5) It is very important to include values for surge cap

    tors connected to the motor terminals or at switchgear bu

    E-8

  • 8/16/2019 High Resistance Grounding Tech Paper

    9/9

    Francis K. Fox, Howard J. Grotts, and Clyde H. Tipton

    IEEE Transactions on Industry and General Applications

    September/October 1965

    This equipment will add about 0.75 amperes at 2400 volts or

    1.3 amperes at 4160 volts, for each set of surge capacitors used.

    6) The authors wish to point out that these values were

    derived from limited test data and, therefore, are only approxi-

    mate. It should also be realized that capacitance values will

    vary considerably with the wide ranges of cable, wire, motor,

    and transformer sizes installed in the typical refinery.

    7) The authors have noted recent published test data [3]

    wherein system-charging current of several 2400-volt mining

    power systems was found to be in the order of 1.0 A/MVA of 

    system capacity. This is much greater than the current foundon any systems with which the authors have worked and is

    probably caused by the extensive use of lead-covered or

    shielded cables used in underground mining operations and

    also by the extensive use of surge capacitors at the terminals of 

    large 2300-volt motors.

    References

    (1) Industrial Power Systems Data Book. Schenectady, N.

    Y.: General Electric Company, Sec 0.220 and App. C.

    (2) D. L. Beeman, Power Systems Handbook. New York:

    McGraw Hill, 1955.

    (3) W. R. Duffy, “How the Anaconda Company protects

    its system against ground faults,” Indus. Power Sys., March

    1964.

    (4) “Grounding of Industrial Power Systems,” AIEE Spe-

    cial Publ. 953 (Green Book), October 1956, editorially re-

    vised on September, 1960.

    E-9