6-170.3December, 2011

High-Efficiency Condensing Gas-Fired Separated Combustion Unit Heaters

320235_6-170.3.indd 1 1/17/12 1:32 PM

Page 2: High-Efficiency Condensing Gas-Fired Separated Combustion …hydronichvac.com/wp-content/uploads/6-170.3-PTC-Effinity.pdf · 2016-10-01 · High-Efficiency Condensing Gas-Fired Separated

6-170.32

INTRODUCTION / TABLE OF CONTENTS

Table of Contents Page

Design Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4

General Performance and Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Field Installed Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Downturn Hood Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Unit Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-11

Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

At 93% thermal efficiency for all model sizes, Modine’s Effinity93 condensing unit heater features the highest efficiency available in North America for commercial and industrial gas-fired unit heaters. This industry leading efficiency is a result of the coupling of our ConservicoreTM secondary heat exchanger technology with our robust tubular primary heat exchanger design. The ConservicoreTM technology features a secondary recuperative heat exchanger fabricated from AL29-4C® stainless steel. This material is superior to other lower grades of stainless steel and aluminum, resulting in outstanding ability to withstand the corrosive environment of condensing gas fired equipment.

Available in eight model sizes with input ranges from 85,000 to 310,000 Btu/Hr, Modine offers application flexibility unmatched in the industry. The separated combustion units draw combustion air from outside to ensure that the unit will always have plenty of fresh, clean air for combustion while increasing the overall heating efficiency. Venting material to be used is PVC, an extremely cost effective vent system.

This catalog describes the design benefits, construction features, performance data, unit selection procedure, and the optional and accessory devices available for the Modine Effinity93 Condensing Unit Heater, model PTC.

WARNING1. Do not locate ANY gas-fired unit in areas where chlorinated,

halogenated, or acidic vapors are present in the atmosphere.

2. Do not install in potentially explosive or flammable atmosphere laden with dust, sawdust, or similar airborne materials.

CAUTIONHeaters are designed for use in heating applications with ambient temperatures between 40°F and 80°F. Heaters should not be used in applications where the heated space temperature is below 40°F. The combination of low space and combustion air temperatures may result in condensate freezing in the secondary heat exchanger and/or condensate drain.

! !

As Modine Manufacturing Company has a continuous product improvement program, it reserves the right to change design and specifications without notice.® AL29-4C is a Registered Trademark of Allegheny Ludlum Corporation. TM Effinity93, Conservicore, and any combination of these names either together or with other words is trademarked by Modine Manufacturing Co.

Table 2.1 - Estimated Annual Fuel Cost Savings Using the Effinity93 Condensing Unit Heater

Figure 2.1 - U.S. Average Heat Load Hours Map

Estimated Annual Savings Against Other Equipment ➀ ➁

Gravity Vented Power VentedDesign Heat Load (Btu/Hr): 120,000 280,000 120,000 280,000

Annual Heat Load Hours

(refer to Figure 2.1)

500 $306 $713 $136 $318

1000 $611 $1,427 $273 $637

1500 $917 $2,140 $409 $955

2000 $1,223 $2,853 $546 $1,274

2500 $1,529 $3,567 $682 $1,592

3000 $1,834 $4,280 $819 $1,911

3500 $2,140 $4,993 $955 $2,229

➀ Based on a natural gas rate of $1.10/Therm. Actual realized savings can vary significantly based on a number of changing factors including, but not limited to, fuel prices, climate, building use or construction, etc.

➁ Compares 93% efficient against 65% seasonal efficient gravity vented and 78% seasonal efficient power vented.

Use 3500 for Alaska and Canada.

320235_6-170.3.indd 2 1/17/12 1:32 PM

Page 3: High-Efficiency Condensing Gas-Fired Separated Combustion …hydronichvac.com/wp-content/uploads/6-170.3-PTC-Effinity.pdf · 2016-10-01 · High-Efficiency Condensing Gas-Fired Separated

6-170.3 3

DESIGN FEATURES

Feature

Cab

inet

and

Air

Mov

er

Aluminized steel cabinet (gauge indicated) 20 ga.

Baked-on polyester powder paint for durability and corrosion resistence •

Adjustable air-deflector blades •

Fans engineered for quiet operation •

Totally enclosed fan motors for maximum durability •

Fingerproof fan guard (standard on size 110 and smaller) O

Hea

t Ex

chan

ger

and

Bur

ner

93% thermally efficient •

Aluminized steel primary heat exchanger (409 stainless steel optional) •

Tubular heat exchanger for superior durability •

In-shot burner on each heat exchanger tube for reliable performance, ease of serviceability and low sound level on flame ignition/extinction

Modine ConservicoreTM technology on secondary recuperative heat exchanger with AL29-4C® stainless steel material as standard

Con

trols

ETL certification for residential (size 110 and smaller only), commercial, and industrial use in the US and Canada •

Factory-installed power exhauster •

Controls for natural gas (propane optional) •

Single stage gas controls •

High limit safety controls for both the heated air and flue gas temperature •

Condensate drain overflow switch to verify proper condensate drainage •

Differential pressure switch for proof of venting •

Direct spark ignition with continuous retry control system •

Contractor Convenience Package featuring a condensate pump convenience outlet, unit on/off switch, heater function status indicator lights, and external terminals for thermostat wiring

Gas control step down transformer with 24V gas controls •

Fan delay timer •

Table 3.1 - Standard Features and Factory Options ➀

➀ • = Standard, O = Option. See page 6 for Field Installed Accessories.

Figure 3.1 - Effinity93 (model PTC) Figure 3.2 - Modine ConservicoreTM Heat Exchanger

SECONDARY HEAT

EXCHANGER

PRIMARYHEAT

EXCHANGER

POWER EXHAUSTER

320235_6-170.3.indd 3 1/17/12 1:32 PM

Page 4: High-Efficiency Condensing Gas-Fired Separated Combustion …hydronichvac.com/wp-content/uploads/6-170.3-PTC-Effinity.pdf · 2016-10-01 · High-Efficiency Condensing Gas-Fired Separated

4 6-170.3

DESIGN FEATURES

Figure 4.1 - Factory Mounted Standard Features

➆ Flame Roll Out Switch (size 110 and smaller only) (hidden)Flame roll out switches are mounted near the burners and will shut off the gas supply in the event of an unsafe flame roll out condition.

➇ Direct Spark IgniterProvides spark for direct ignition of the burners.

➈ High Limit Switches One limit control is mounted in the air stream and will shut

off the gas supply in the event of overheating. The other limit control is mounted on the power exhauster housing and will shut off the gas supply in the event of overheating flue gas temperatures.

➉ Condensate Drain Overflow Switch Shuts down gas controls if condensate is not properly

draining from the unit.

Gas Pipe Connection Easy access to factory installed gas pipe connection stubbed

to outside of unit casing.

Condensate Drain Connection Easy access to factory installed condensate drain pipe

connection stubbed to outside of unit casing.

Combustion Air Inlet Pipe ConnectionSimple connection for combustion air inlet piping.

Vent Pipe Connection Simple Fernco® rubber boot connection for PVC vent system.

Fan Guard Propeller units may be equiped with an optional finger proof fan

guard (standard on size 110 and smaller) for added protection. If ordered, the finger proof fan guard is installed at the factory in place of the standard fan guard.

Contractor Convenience Package External junction box features simple connection of supply

power wiring internally, thermostat wiring to terminals externally, an On/Off switch, a single 115V outlet for connection of an external condensate pump, and status indicator lights to display the operational state of the unit.

Horizontal Air Deflector Blades (hidden)Factory mounted on the discharge of the unit, the blades can be adjusted to provide horizontal (up and down) delivery control of the heated air. Vertical deflector blades are available as a field installed accessory.

➀ Power Exhauster All units are supplied with a round vent pipe and combustion

air inlet pipe connections.

➁ Pressure Switch An automatic reset vent pressure switch is supplied on all

units and is designed to prevent operation of the main burner in the event there is restricted venting of flue products. This restriction may occur due to an improper vent diameter, long vent runs, un-approved vent terminal, high winds, high negative pressure within space, etc. After the cause of the restriction has been corrected, the pressure switch will reset automatically.

➂ Control Step Down Transformer The control step down transformer is located in the electrical

junction box. The transformer is used to step down from 115V to 24V for the gas controls, fan delay relay, field supplied motor starter, etc. An additional field installed transformer is required if the supply voltage is 208V, 230V, 460V, or 575V. To determine the control transformer supplied as well as any required accessory transformers, refer to Table 5.2.

➃ Integrated Direct Spark Control Board The integrated direct spark ignition control combines all

furnace control functions. The integrated board provides digital control of the air mover, inducer, ignition, gas valve and flame sense as well as monitoring the safety circuit at all times. The board includes LED diagnostics for trouble shooting and a fused power supply. Ignition control is 100% shut-off with continuous retry.

➄ Flame Sensor Remote flame sensor verifies ignition of all burners,

monitors the flame signal and communicates with the integrated circuit board.

➅ Single Stage Gas ValveThe main gas valve is factory installed on the unit heater gas train. The main gas valve provides regulator, main gas, and manual shutoff functions. The valve is redundant and provides 100% shut off. Natural gas is Control Code 11, propane gas is Control Code 21.

14

15

16

17

12

13

11

➁ ➂

➈12

11

15

16

1314

320235_6-170.3.indd 4 1/17/12 1:32 PM

Page 5: High-Efficiency Condensing Gas-Fired Separated Combustion …hydronichvac.com/wp-content/uploads/6-170.3-PTC-Effinity.pdf · 2016-10-01 · High-Efficiency Condensing Gas-Fired Separated

56-170.3

GENERAL PERFORMANCE AND ELECTRICAL DATA

Table 5.1 - Propeller Unit Heater Model PTC General Performance Data

Table 5.2 - Electrical Selection Details - All Models

Table 5.3 - Model PTC Operating Electrical Data ➄

➀ Ratings shown are for elevations up to 2,000 ft. For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea level. (In Canada see rating plate.) Reduction of ratings requires use of a high altitude kit.

➁ Data taken at 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit, and without deflector hoods.

➂ All motors used are produced, rated and tested by reputable manufacturers in accordance with NEMA standards and carry the standard warranty of both the motor manufacturer and Modine. All motors are totally enclosed and all single phase motors have built-in thermal overload protection.

Model Supply Voltage Phase Required Accessory

Transformer ➃Power & Gas Control Circuit

Transformer VoltagesFactory Installed

Transformer

PTC

115 1 none

115V/1ph 115 to 24V

2081 or 3

208V to 115V

230 230V to 115V

4603

460V to 115V

575 575V to 115V

➃ For accessory transformer sizing, refer to Table 5.3.

Amp draw data shown is operating amp draw at incoming power. For units that use a field installed accessory step-down transformer as noted, the amp draw shown is the primary side operating amp draw. For sizing of circuit protection for equipment with transformers, please refer to the National Electric Code.

Model PTC Sizes85 110 135 155/156 180 215 260 310

Btu/Hr Input 85,000 110,000 135,000 155,000 180,000 215,000 260,000 310,000

Btu/Hr Output 79,050 102,300 125,500 144,150 167,400 199,950 241,800 288,300

Condensate Production (Gal./Hr.) 0.5 0.7 1.0 1.1 1.3 1.6 1.9 2.3

Entering Airflow (CFM) @ 70°F 1650 1750 2160 2510/2600 3020 3865 4585 5400

Outlet Velocity (FPM) 619 668 719 835/862 676 699 831 765

Air Temp. Rise (°F) 44 54 54 53/51 51 48 49 49

Max. Mounting Height (Ft.) 13 13 14 17/18 15 17 20 19

Heat Throw (Ft.) @ Max. Mtg Ht 48 46 51 59/62 53 60 70 67

Motor Type PSC PSC PSC PSC PSC PSC PSC PSC

Motor HP 1/8 1/3 1/3 1/3 1/3 1/2 3/4 3/4

Motor RPM 1550 1075 1075 1075 1075 1075 1125 1125

Supply Voltage Power Code Model PTC Sizes

85 110 135 155/156 180 215 260 310

115V1 Phase 01 (115V)

Motor Amps 2.2 4.6 4.6 4.6 4.6 7.0 8.8 8.8

Total Amps 4.5 6.9 6.9 6.9 6.9 9.3 11.1 9.9

Transformer kVA n/a n/a n/a n/a n/a n/a n/a n/a

208V 1 or 3 Phase

01 (115V) with Transformer

208V Total Amps 2.49 3.81 3.81 3.81 3.81 5.14 6.14 5.47

Transformer kVA 1.0 1.0 1.0 1.0 1.0 1.5 1.5 1.5

230V 1 or 3 Phase

01 (115V) with Transformer

230V Total Amps 2.25 3.45 3.45 3.45 3.45 4.65 5.55 4.95

Transformer kVA 1.0 1.0 1.0 1.0 1.0 1.5 1.5 1.5

460V3 Phase

01 (115V) with Transformer

460V Total Amps 1.13 1.73 1.73 1.73 1.73 2.33 2.78 2.48

Transformer kVA 1.0 1.0 1.0 1.0 1.0 1.5 1.5 1.5

575V3 Phase

01 (115V) with Transformer

575V Total Amps 0.9 1.38 1.38 1.38 1.38 1.86 2.22 1.98

Transformer kVA 1.0 1.0 1.0 1.0 1.0 1.5 1.5 1.5

320235_6-170.3.indd 5 1/17/12 1:32 PM

Page 6: High-Efficiency Condensing Gas-Fired Separated Combustion …hydronichvac.com/wp-content/uploads/6-170.3-PTC-Effinity.pdf · 2016-10-01 · High-Efficiency Condensing Gas-Fired Separated

6 6-170.3

ACCESSORIES

Table 6.1 - Field Installed Accessories

Table 6.2 - Field Installed Thermostats

Sing

le-S

tage

Roo

mTh

erm

osta

ts

Description

WHITE-RODGERS 1C20-101 - 1.2 amps @30VAC, 50° -90°F temperature range, 0.15 to 1.2 amps adjustable heat anticipator

WHITE-RODGERS 1C26-101 - Same as 1C20-101 above except adds Heat/Off/Cool and Fan On/Auto switches

HONEYWELL TH5220D1029 digital non-programmable room stat with switching - range 40-90°F

Figure 6.1 - Horizontal Concentric Vent Kit Figure 6.2 - Vertical Concentric Vent Kit

FROM UNIT VENTCONNECTION

TO UNIT COMBUSTION AIR INTAkE CONNECTION

CONCENTRIC VENT ADAPTER

INLET GUARD ASSEMBLY

PVCVENT TERMINAL

(ELBOW)

INLETTERMINAL

VENT TERMINALASSEMBLY

FROM UNIT VENT CONNECTION

TO UNIT COMBUSTION AIRINTAkE CONNECTION

CONCENTRIC VENT ADAPTER

Feature

Cab

inet

and

A

ir M

over

Vertical Deflector Blades - Allows directional discharge air control in the left and right directions.

Downward Air Deflector Hoods - Available in 30°, 60°, and 90° configurations these deflector hoods provide more focused air flow control. Refer to page 7 for further details.

Two-Point Suspension Kits - Converts from 4-point suspension to 2-point suspension.

Fingerproof Fan Guard - Ships installed on unit in place of standard guard (standard on size 110 and smaller).

Con

trols

Natural Gas to Propane Gas Conversion Kit - All required parts to convert a natural gas unit to propane gas.

Energy Saver Thermostats - Mounted high and independent of the room stat, this control turns on the unit heater fan if high temperatures are sensed, forcing the heated air down, reducing stratification and potentially gas usage. SPDT switch, 30°-100° range. 16 amp @ 120V. Honeywell T631A1113.

Single-Stage Room Thermostats - See Table 6.2 for details.

Stepdown Transformers - Used to operate units on 208V, 230V, 460V, or 575V supply voltage. Refer to Tables 5.2 and 5.3 for further selection details.

Con

dens

ate

Han

dlin

g

Condensate Pump - Used for high lift applications of up to 22’ - DiversiTech CP-22

Condensate Pump Suspension Kit - Used to suspend/support pump (DiversiTech CP-22) from heater.

Condensate Treatment - Controls slime growth in pump (DiversiTech CP-22) and downstream drain.

Condensate pH Neutralizing Kit - Reduces acidity of condensate.

Recharge Kit for pH Neutralizing Kit - Aggregate material to recharge the pH Neutralizing kit (once per year or every 2000 hours).

Vent

ing

Horizontal Concentric Vent Kit - Enables horizontal concentric venting. kit consists of one concentric adapter, one vent termination screen, and one inlet guard assembly (See Figure 6.1).

Vertical Concentric Vent Kit - Enables vertical concentric venting. kit consists of one concentric adaptor, one combustion air inlet cap, and two vent pipe terminal screens (See Figure 6.2).

Termination screens for horizontal or vertical, 2-pipe system terminals. Terminals are by others.

320235_6-170.3.indd 6 1/17/12 1:32 PM

Page 7: High-Efficiency Condensing Gas-Fired Separated Combustion …hydronichvac.com/wp-content/uploads/6-170.3-PTC-Effinity.pdf · 2016-10-01 · High-Efficiency Condensing Gas-Fired Separated

76-170.3

PERFORMANCE DATA - DEFLECTOR HOODS

Figure 7.1 - 30°, 60°, & 90° Deflector Hoods

H

SS

MOUNTINGHEIGHT

X Y

YZ

ZX

60 DOWNTURN

30 DOWNTURN

Note:X = Feet from Heater to Start of Floor CoverageY = Feet to End of Floor CoverageZ = Feet to End of Throw

60

30

30 DOWNTURN60 DOWNTURN

Figure 7.2 - 30° & 60° Hood Throw/Floor Coverage

Figure 7.3 - 90° Hood Throw/Floor Coverage

30° HOOD 60° HOOD 90° HOOD

Table 7.1 - Deflector Hood Performance Data

Model Size

Airflow Temp Rise

Mounting Height

Blade Angle

30° Hood 60° Hood 90° Hood

X Y Z X Y Z S(CFM) (°F) (ft) (°) (ft) (ft) (ft) (ft) (ft) (ft) (ft)

85 1650 44

8 59 14 30 41 0 32 43 1710 49 12 29 39 0 29 40 16

12 39 11 26 37 0 26 36 1413 32 10 25 35 0 24 33 14

110 1750 54

8 57 13 29 39 0 30 41 16

10 47 11 27 37 0 28 38 15

12 35 10 25 34 0 24 33 13

13 28 9 23 32 0 22 30 13

135 2160 53

8 60 15 32 44 0 34 47 2410 52 13 31 42 0 32 44 2112 42 12 29 40 0 29 40 1914 30 10 26 36 0 25 34 18

155 2510 53

8 60 14 32 43 0 33 46 2310 51 13 30 42 0 31 43 2112 41 12 28 39 0 28 39 1914 29 10 25 35 0 24 33 1716 8 6 17 26 0 15 21 16

156 2600 51

8 60 19 41 56 0 43 60 2610 51 18 40 55 0 42 57 2312 41 17 38 53 0 40 55 2114 29 15 37 51 0 37 51 2016 8 14 34 48 0 34 47 18

180 3020 51

8 63 16 35 48 0 37 51 2610 55 15 34 46 0 35 48 2312 46 13 32 44 0 32 45 2114 36 12 29 41 0 29 40 20

215 3865 48

8 66 19 41 56 0 43 59 3210 60 18 40 54 0 42 57 2912 53 17 38 53 0 40 54 2614 46 15 36 50 0 37 51 2416 37 14 34 47 0 33 46 23

260 4585 49

8 69 22 45 62 0 48 66 3710 63 21 44 61 0 47 64 3312 57 19 43 59 0 45 62 3014 51 18 42 57 0 43 59 2816 44 17 40 55 0 40 55 2618 35 15 37 52 0 36 50 2520 25 13 33 47 0 31 43 24

310 5400 49

8 68 20 43 58 0 45 62 3410 61 19 42 57 0 44 60 31

12 55 18 40 55 0 42 58 2814 48 17 39 53 0 40 54 2616 40 15 37 51 0 36 50 2418 31 13 34 47 0 32 44 23

Note: Refer to Figures 7.1 through 7.3.

320235_6-170.3.indd 7 1/17/12 1:32 PM

Page 8: High-Efficiency Condensing Gas-Fired Separated Combustion …hydronichvac.com/wp-content/uploads/6-170.3-PTC-Effinity.pdf · 2016-10-01 · High-Efficiency Condensing Gas-Fired Separated

8 6-170.3

UNIT SELECTION

Selection Example ConditionsSelect a unit heater to meet the following conditions:1. Heating output capacity = 166,000 Btu/Hr per design

engineer 2. Heat exchanger = 409 Stainless Steel3. Gas Type = Natural4. Gas Controls = Single Stage5. Supply Voltage: 460V/60Hz/3Ph6. Altitude: 1,000 feet

With the information listed above, the basic model, using the information in this catalog and the Model Nomenclature shown on page 11, can be selected as shown:

1. Determine the Model and Input Rating (MBH): Using the Heating output capacity, the Furnace Input Rating

is determined from Table 6.1. The closest model to 166,000 Btu/Hr output has an Btu/Hr Input rating of 180,000 Btu/Hr so the Furnace Input Rating = 180. The corresponding model for a 180 size, propeller, separated combustion unit heater is PTC. The model and size are a PTC180.

2. Determination of Heat Exchanger Material: From item #2 in the example, the Heat Exchanger required is

409 Stainless Steel. Thus, the Heat Exchanger Material = S from the Model Nomenclature on page 11.

3. Determine the Ignition Type: The Ignition Type = S from the Model Nomenclature on page11

4. Determine Power Code Required: Referring to Table 5.2, it can be seen that the supply

voltage from the example conditions is not available (460V). A transformer kit selected later in this example must be used. In this instance, from Table 5.2 select the 115V/60Hz/1Ph power code (PC) = 01 unit.

5. Determine the control type: From items #4 and #5 in the example conditions, the gas type

is Natural Gas and controls are Single Stage. From note ➅ on page 4, we are directed to use Control Code (CC) 11.

At this point we have a full model number of: PTC180SS01116. Determination of transformer: To operate a 115V/60Hz/1Ph unit on 460V/60Hz/3Ph supply

power a unit step down transformer must be selected. By referring to Table 5.2 we see that a 460V to 115V step down transformer is required. As noted in the footnote for Table 5.2, the size can be determined to be 1.0VA from Table 5.3.

7. Altitude: Since deration of gas fired unit heaters is only required for

units to be installed at 2,000 ft or greater, no high altitude kit is required.

Selection Example

320235_6-170.3.indd 8 1/17/12 1:32 PM

Page 9: High-Efficiency Condensing Gas-Fired Separated Combustion …hydronichvac.com/wp-content/uploads/6-170.3-PTC-Effinity.pdf · 2016-10-01 · High-Efficiency Condensing Gas-Fired Separated

96-170.3

DIMENSIONAL DATA

Table 9.1 - Dimensions (inches)

Figure 9.1 - Dimensional Drawings - Model PTC

Table 9.2 - Clearances to Combustible MaterialsUnit Side Clearance To Recommended

Combustible Materials Service ClearanceTop and Bottom 6" 6"

Access Side 6" 18"

Non-Access Side 6" 18"

Rear 18" 18"

Vent Connector 6" 6"

ADJUSTABLELOUVERS

(4) 3/8"-16 MTG HOLES

CONDENSATE DRAIN3/4" PVC

GASCONN.

COMBUSTION AIR INLET

VENTOUTLET

FAN

KNOCKOUTS FOR SUPPLY POWER WIRING

CONDUIT ENTRANCE

ACCESSPANEL

B

C

R (APPROX.) D (OPENING)

E(OPENING)

I

J

KL

H

F

G

M

A Q (MINIMUM DISTANCE TO WALL)

3.56 14.90 N P

Models PTC 85 PTC110 PTC135 PTC155/156 PTC180 PTC 215 PTC260 PTC310A 35.53 35.53 35.53 35.53 42.53 42.53 42.53 42.53

B 20.31 20.31 23.06 23.06 25.81 31.31 31.31 39.56

C 22.05 22.05 22.05 22.05 22.05 22.05 22.05 22.05

D 22.52 22.52 22.52 22.52 29.52 29.52 29.52 29.52

E 18.42 18.42 21.18 21.18 23.93 29.43 29.43 37.68

F 4.50 4.50 4.50 4.50 4.50 4.50 4.50 4.50

G 7.98 7.98 7.98 7.98 7.98 7.47 7.47 8.12

H 10.27 10.27 10.18 10.18 10.36 9.86 9.86 9.79

I 1.32 1.32 2.15 2.15 1.73 1.63 1.63 1.88

J 6.73 6.73 8.09 8.09 9.47 6.72 6.72 10.84

K 8.74 8.74 8.45 8.45 9.82 12.58 12.58 16.19

L 12.13 12.13 12.95 13.45 14.92 17.58 17.58 22.19

M 3.86 3.86 3.48 3.98 3.98 3.72 3.72 4.62

N 1.54 1.54 1.54 1.54 3.97 3.97 3.97 3.97

P 22.03 22.03 22.03 22.03 26.60 26.60 26.60 26.60

Q 45.83 45.83 45.83 45.83 45.83 45.83 46.83 46.83

R 33.83 33.83 33.83 33.83 33.83 33.83 34.83 34.83

Combustion Air Inlet Pipe 3 3 3 4 4 4 4 6

Vent Outlet Pipe 3 3 3 4 4 4 4 4

Gas Connection 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4

Fan Diameter 18 18 20 20 22 24 24 26

Approx. Shipping Weight (lbs.) 125 128 165 165 215 265 265 310

320235_6-170.3.indd 9 1/17/12 1:32 PM

Page 10: High-Efficiency Condensing Gas-Fired Separated Combustion …hydronichvac.com/wp-content/uploads/6-170.3-PTC-Effinity.pdf · 2016-10-01 · High-Efficiency Condensing Gas-Fired Separated

10 6-170.3

SPECIFICATIONS - ALL MODELS

General

A. StandardsAll unit(s) shall include:

A.2. ETL design certification for use in both the US and Canada to the ANSI Z83.8 - latest revision, standard for “Gas Unit Heater and Gas-Fired Duct Furnaces” for safe operation, construction, and performance.

B. Mechanical ConfigurationB.3. Condensing furnace section with 93% minimum

efficiency provided by an indirect-fired tubular heat exchanger with individually fired tubes coupled to a secondary recuperative heat exchanger for maximum heat recovery.

C. Venting/Combustion Air ArrangementC.4. The unit shall be separated combustion. The venting

shall be a power exhausted arrangement with a separate combustion air intake pipe connection to allow for fresh combustion air from outside the conditioned space. The unit shall be tested to insure proper ignition when the unit is subjected to 40 mile per hour wind velocities. The unit shall also include a factory mounted differential pressure switch designed to prevent main burner ignition until positive venting has been proven.

Venting shall be Schedule 40 PVC. For Canadian installations, all vent pipe and components must be approved to ULC S636.

D. Unit CasingD.1. The unit heater(s) casing shall be constructed of not

less than 20 gauge aluminized steel with minimization of exposed fasteners.

D.2. All exterior casing parts casing parts shall be cleaned of all oils and a phosphate coating applied prior to painting. The exterior casing parts shall then be painted with an electrostatically applied baked-on gray-green polyester powder paint (7-mil thickness) for corrosion resistance.

D.3. The unit shall be furnished with horizontal air deflectors. The deflectors are adjustable to provide for horizontal directional airflow control (up or down).

E. Furnace SectionE.1.e. The primary heat exchanger(s) shall be made of

18 gauge aluminized steel (opt 409 stainless steel) tubes and headers. Each heat exchanger tube shall be individually and directly flame-fired. The heat exchanger tube shall be crimped to allow for thermal expansion and contraction. The flue collector box shall be made of 20 gauge AL29-4C stainless steel.

The thermal efficiency of the unit(s) shall be a minimum of 93% efficient for all air flow ranges through the use of a secondary recuperative heat exchanger. The secondary heat exchanger shall be constructed of AL29-4C stainless steel to withstand the corrosive environment of condensing gas fired equipment.

E.3.a. The burner(s) shall be in-shot type, directly firing each heat exchanger tube individually and is designed for good lighting characteristics without noise of extinction for both natural and propane gas.

E.5. The ignition controller(s) shall be 100% shut-off with continuous retry.

E.6. The gas pressure shall be between 6-7" W.C for natural gas (opt the gas pressure shall be 11-14" W.C. for propane gas).

E.7.a. The solid state ignition system shall directly light the gas by means of a direct spark igniter each time the thermostat calls for heat.

E.8. The unit gas controls shall be provided with the following:

E.8.d. Single-stage gas controls with a single-stage combination gas control, an ignition control, and a single-stage low voltage thermostat. The unit fires at 100% full fire based on a call for heat from a room thermostat.

E.9. An automatic reset high limit switch mounted in the air stream to shut off the gas supply in the event of overheating.

E.9.a. An automatic reset high limit switch mounted on the power exhauster housing to shut off the gas supply in the event of overheating flue gas temperatures.

E.9.b. A condensate drain line overflow switch that senses if the condensate line is clogged and shuts the unit heater down.

E.10. A time delay relay that delays the start of the air mover to allow the heat exchanger a warm-up period after a call for heat. The time delay relay shall also continue the air mover operation after the thermostat has been satisfied to remove any residual heat on the heat exchanger.

E.11. The unit shall be orificed for up to 2000' elevation above sea level (opt the unit shall be orificed for _____ elevation above sea level).

F. ElectricalF.1. All electrical components shall carry UL, ETL, or CSA

listing.F.2. Low voltage terminal board.

F.3. A single 115V to 24V step down transformer shall be provided for all unit controls.

G. Air MoverG.1. The motor horsepower shall be ____.

G.2. The motor shall be factory wired.

G.3. The motor shall be controlled by a time delay relay.

G.4. Propeller models shall meet the following requirements.

G.4.a. The motor type shall be Single-speed, totally enclosed (TE)

G.5.b. The motor shall be rated for 115V/60Hz/1Ph.

Note: Specifications below are extracted from a master gas-fired unit heater specification and therefore certain numbered sections have been intentionally omitted.

320235_6-170.3.indd 10 1/17/12 1:32 PM

Page 11: High-Efficiency Condensing Gas-Fired Separated Combustion …hydronichvac.com/wp-content/uploads/6-170.3-PTC-Effinity.pdf · 2016-10-01 · High-Efficiency Condensing Gas-Fired Separated

116-170.3

H. MountingH.1. The unit shall be equipped with tapped holes to accept

3/8-16 threaded rod for suspension.

H.3. Units to have 4 suspension points.

J. AccessoriesThe following field installed accessory control devices shall be provided with the unit:

J.1. A 1-50 psi gas pressure regulator to reduce the inlet gas pressure for the operating controls.

J.2. A clear plastic thermostat guard with two keys for room thermostats.

J.4. Pipe Hanger Adapter kit to facilitate threaded pipe suspension.

J.7. Vertical Deflector kit to enables side distribution of airflow.

J.12. Propane conversion kit for converting natural gas units to propane gas.

J.18. 30° non-velocity generating downward air deflector hood constructed of 20 ga. cold rolled steel with baked-on gray-green polyester powder paint.

J.19. 60° non-velocity generating downward air deflector hood constructed of 20 ga. cold rolled steel with baked-on gray-green polyester powder paint.

J.20. 90° non-velocity generating downward air deflector hood constructed of 20 ga. cold rolled steel with baked-on gray-green polyester powder paint.

J21. A 208V to 115V step down shall be provided for operation of the 115V unit.

J.22. A 230V to 115V step down shall be provided for operation of the 115V unit.

J.23 A 460V to 115V step down shall be provided for operation of the 115V unit.

J.24. A 575V to 115V step down shall be provided for operation of the 115V unit.

J.29. A horizontal concentric vent kit shall be provided to allow the vent outlet and combustion air inlet pipes to penetrate the building wall through one opening.

J.30. A vertical concentric vent kit shall be provided to allow the vent outlet and combustion air inlet pipes to penetrate the building roof through one opening.

J.31. A 2-point suspension kit to convert the unit from 4-point mounting to 2-point mounting.

J.32. An Energy Saver Thermostat to be mounted high and independent of the room stat to turn on the unit heater fan if high temperatures are sensed, forcing the heated air down to reduce stratification and gas usage.

J.33. A condensate pump for high lift applications of up to 22’. Pump shall include indicator lights to show pump status, internal vibration isolation, a check valve, condensate treatment tablet dispenser, and alarm contacts to shut the unit heater down if the pump becomes inoperable.

J.34. A condensate pump suspension kit to suspend/support the pump (DiversiTech CP-22) from the unit heater.

J.35. Condensate treatment tablets to controls slime growth in pump (DiversiTech CP-22) and downstream drain.

J.36. A condensate pH neutralizing kit to reduce the acidity of condensate. Includes barbed inlet and outlet fittings, mounting brackets and an initial charge of neutralizing aggregate.

J.37. A recharge kit for pH neutralizing kit. Includes sufficient aggregate for a complete recharge of the neutralizing kit.

K. ThermostatsThe unit shall be provided with the following thermostat:

k.2. A single stage room thermostat with a 50°-90°F range.

k.3. A single stage room thermostat with a 50°-90°F range with Heat/Off/Cool and Fan On/Auto switching.

k.4. Honeywell TH5220D1029 digital non-programmable room stat with switching - range 40-90°F.

SPECIFICATIONS - ALL MODELS

Heat Exchanger TypeA - AluminizedS - Stainless Steel

Ignition TypeS - Direct Spark

Control Code Type (refer to page 4)11 - Natural gas, single

stage21 - Propane, single stage

Power Code (refer to page 5)01 - 115V/60Hz/1ph

PTC 215 A S 01 11

Separated Combustion Unit ConfigurationPTC - Propeller Unit, 135-310MBH

Figure 11.1 - Model Number Designations

MBH Input 85 - 85,000 Btu/hr input

110 - 110,000 Btu/hr input135 - 135,000 Btu/hr input

155/156 - 155,000 Btu/hr input 180 - 180,000 Btu/hr input215 - 215,000 Btu/hr input260 - 260,000 Btu/hr input310 - 310,000 Btu/hr input

320235_6-170.3.indd 11 1/17/12 1:32 PM

Page 12: High-Efficiency Condensing Gas-Fired Separated Combustion …hydronichvac.com/wp-content/uploads/6-170.3-PTC-Effinity.pdf · 2016-10-01 · High-Efficiency Condensing Gas-Fired Separated

Products from Modine are designed to provide indoor air-comfort solutions

for commercial, institutional and industrial applications. Whatever your heating,

ventilating and cooling requirements, Modine has the product to satisfy your

needs, including:

• Gas-fired unit heaters

• Gas-fired duct furnaces

• Gas-fired high-intensity infrared heaters

• Gas-fired low-intensity infrared heaters

• Steam/hot water unit heaters

• Steam/hot water cabinet unit heaters

• Steam/hot water commercial fin tube radiation

• Oil-fired unit heaters

• Electric unit heaters

• Indoor gravity and power vented single and multiple duct furnace make-up

air units

• Indoor separated combustion single and multiple duct furnace make-up air units

• Outdoor single and multiple duct furnace make-up air units

• Direct-fired make-up air units

• R410 DX split system air conditioning and heat pump ceiling cassettes

• Chilled water ceiling cassettes

With burner capacities up to 7,862,000 Btu/hr and air-handling capacities

as high as 60,000 CFM, Modine products are compatible with every fuel

type, including:

• Natural or Propane Gas • Steam/Hot Water • Oil • Electric

Specific catalogs and computer-generated heat-loss calculations are available

for each product. Catalogs 75-136 and 75-137 provide details on all Modine

HVAC equipment.

Commercial Products GroupModine Manufacturing Company

1500 DeKoven Avenue

Racine, Wisconsin 53403-2552

Phone: 1.800.828.4328 (HEAT)

Fax: 1.800.204.6011

www.modinehvac.com

© Modine Manufacturing Company 2011

Litho in USA

The Modine brand has been the

industry standard since Arthur B.

Modine invented and patented

the first lightweight, suspended

hydronic unit heater in 1923.

No other manufacturer can

provide the combined application

flexibility, technical expertise and

fast delivery found at Modine.

Consult your local Modine

distributor for help in solving your

indoor air problems.

Distributed By:

320235_6-170.3.indd 12 1/17/12 1:32 PM