24
HH-TJ-PF-01 External Masonry Cavity Wall, Partial-Fill - Suspended Beam And Block Floor, Insulation Above Slab HH-TJ-PF-02 External Masonry Cavity Wall, Partial-Fill - Suspended In-Situ Concrete Floor, Insulation Below Slab HH-TJ-PF-04 External Masonry Cavity Wall, Partial-Fill - Independent Lintel HH-TJ-PF-03 External Masonry Cavity Wall, Partial-Fill - Concrete Ground Bearing Floor, Insulation Below Slab HH-TJ-PF-07 External Masonry Cavity Wall, Partial-Fill - Jamb HH-TJ-PF-05 External Masonry Cavity Wall, Partial-Fill - Steel Lintel, Perforated Base Plate, (Insulated Soffit) HH-TJ-PF-06 External Masonry Cavity Wall, Partial-Fill - Sill HH-TJ-PF-09 External Masonry Cavity Wall, Partial-Fill - Precast Concrete Separating Floor Between Dwellings HH-TJ-PF-08 External Masonry Cavity Wall, Partial-Fill - Intermediate Timber Floor Within A Dwelling HH-TJ-PF-10 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Gable, Insulation At Ceiling Level, Ventilated Loft HH-TJ-PF-15 External Masonry Cavity Wall, Partial-Fill - Inverted Corner HH-TJ-PF-11 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Gable, Insulation At Rafter Level, Unventilated Rafter Void HH-TJ-PF-12 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Eaves, Insulation At Ceiling Level, Ventilated Loft HH-TJ-PF-14 External Masonry Cavity Wall, Partial-Fill - Normal Corner HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill - Party Wall Between Dwellings HH-TJ-PW-18 Party Wall Masonry, Full Fill - Suspended Concrete Floor, Insulation Below Slab HH-TJ-PW-19 Party Wall Masonry, Full Fill - In-Situ Concrete Ground Bearing Floor, Insulation Below Slab HH-TJ-PW-20 Party Wall Masonry, Full Fill - Roof, Insulation At Ceiling Level, Ventilated Loft HH-TJ-PW-21 Party Wall Masonry, Full Fill - Roof, Insulation At Rafter Level, Unventilated Rafter Void Detail Ref. Detail Title HH-TJ-PF-13 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Eaves, Insulation At Rafter Level, Unventilated Rafter Void HH-TJ-PW-17 Party Wall Masonry, Full Fill - Suspended Beam And Block Floor, Insulation Above Slab HH-TJ-PW-18 Party Wall Masonry, Full Fill - Suspended Concrete Floor, Insulation Below Slab HH-TJ-PW-19 Party Wall Masonry, Full Fill - In-Situ Concrete Ground Bearing Floor, Insulation Below Slab HH-TJ-PW-20 Party Wall Masonry, Full Fill - Roof, Insulation At Ceiling Level, Ventilated Loft HH-TJ-PW-21 Party Wall Masonry, Full Fill - Roof, Insulation At Rafter Level, Unventilated Rafter Void HH-TJ-PF-23 External Masonry Cavity Wall, Partial Fill - Pitched Roof, Eaves - Insulation At Rafter Level, Unventilated Rafter Void HH-TJ-PF-22 External Masonry Cavity Wall, Partial-Fill - Steel Lintel, Open Back (no continuous base plate) DRAWN BY TITLE DATE SCALE CHECKED BY REV.NO. DWG No. Thin Joint Junction Details (partial Fill) INDEX AHR SJB Nov 2012 A N.T.S. REV. DESCRIPTION. DATE. BY. H+H UK Limited Fax +44 (0)1732 887013 Kent, TN15 9HZ. Ightham, Sevenoaks Tel +44 (0)1732 880580 Celcon House Technical Services Dept. E-mail [email protected] These details have been produced for guidance only. It is the responsibility of the building designer to ensure that the details shown are compatible with the overall building design and will satisfy the relevant parts of the Building Regulations applicable before they are adopted into the project design. A 11/2014 SJB HH-TJ-PF-22 & HH-TJ-PF-23 ADDED

HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

HH-TJ-PF-01 External Masonry Cavity Wall, Partial-Fill - Suspended Beam And Block Floor, Insulation Above Slab

HH-TJ-PF-02 External Masonry Cavity Wall, Partial-Fill - Suspended In-Situ Concrete Floor, Insulation Below Slab

HH-TJ-PF-04 External Masonry Cavity Wall, Partial-Fill - Independent Lintel

HH-TJ-PF-03 External Masonry Cavity Wall, Partial-Fill - Concrete Ground Bearing Floor, Insulation Below Slab

HH-TJ-PF-07 External Masonry Cavity Wall, Partial-Fill - Jamb

HH-TJ-PF-05 External Masonry Cavity Wall, Partial-Fill - Steel Lintel, Perforated Base Plate, (Insulated Soffit)

HH-TJ-PF-06 External Masonry Cavity Wall, Partial-Fill - Sill

HH-TJ-PF-09 External Masonry Cavity Wall, Partial-Fill - Precast Concrete Separating Floor Between Dwellings

HH-TJ-PF-08 External Masonry Cavity Wall, Partial-Fill - Intermediate Timber Floor Within A Dwelling

HH-TJ-PF-10 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Gable, Insulation At Ceiling Level, Ventilated Loft

HH-TJ-PF-15 External Masonry Cavity Wall, Partial-Fill - Inverted Corner

HH-TJ-PF-11 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Gable, Insulation At Rafter Level, Unventilated Rafter Void

HH-TJ-PF-12 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Eaves, Insulation At Ceiling Level, Ventilated Loft

HH-TJ-PF-14 External Masonry Cavity Wall, Partial-Fill - Normal Corner

HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill - Party Wall Between Dwellings

HH-TJ-PW-18 Party Wall Masonry, Full Fill - Suspended Concrete Floor, Insulation Below Slab

HH-TJ-PW-19 Party Wall Masonry, Full Fill - In-Situ Concrete Ground Bearing Floor, Insulation Below Slab

HH-TJ-PW-20 Party Wall Masonry, Full Fill - Roof, Insulation At Ceiling Level, Ventilated Loft

HH-TJ-PW-21 Party Wall Masonry, Full Fill - Roof, Insulation At Rafter Level, Unventilated Rafter Void

Detail Ref. Detail Title

HH-TJ-PF-13 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Eaves, Insulation At Rafter Level, Unventilated Rafter Void

HH-TJ-PW-17 Party Wall Masonry, Full Fill - Suspended Beam And Block Floor, Insulation Above Slab

HH-TJ-PW-18 Party Wall Masonry, Full Fill - Suspended Concrete Floor, Insulation Below Slab

HH-TJ-PW-19 Party Wall Masonry, Full Fill - In-Situ Concrete Ground Bearing Floor, Insulation Below Slab

HH-TJ-PW-20 Party Wall Masonry, Full Fill - Roof, Insulation At Ceiling Level, Ventilated Loft

HH-TJ-PW-21 Party Wall Masonry, Full Fill - Roof, Insulation At Rafter Level, Unventilated Rafter Void

HH-TJ-PF-23 External Masonry Cavity Wall, Partial Fill - Pitched Roof, Eaves - Insulation At Rafter Level, Unventilated Rafter Void

HH-TJ-PF-22 External Masonry Cavity Wall, Partial-Fill - Steel Lintel, Open Back (no continuous base plate)

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

Thin Joint Junction Details(partial Fill)

INDEX

AHRSJB

Nov 2012 AN.T.S.

REV. DESCRIPTION.DATE. BY.

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

A 11/2014 SJBHH-TJ-PF-22 & HH-TJ-PF-23 ADDED

Page 2: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

ventilated void

wall cavity insulation tocontinue at least 215mm

from top of beam

partial-fill cavitywall insulation

floor insulation to tightly abutwall blockworkdpc

clear cavity Celcon thin joint blocks*to inner leaf, above dpc

dpm

precast beam and block floorwith Celcon Standard infill blocks

Celcon blocks and traditionalmortar below ground

Celcon infill blocks built into wallsto have the same compressivestrength as wall blocks

perimeter insulation to provideminimum resistance of0.8m²K/W

traditional mortar base courseincorporating dpm and dpc

helical cavity tiesface fixed to inner leaf

max. 75mm screed thickness

Celcon foundation blocks

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

External Masonry Cavity Wall,

Partial Fill - Suspended Beam And Block

Floor, Insulation Above Slab

HH-TJ-PF-01

AHRSJB

Nov 2012 1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

C

11/2013 MAX. SCREED THICKNESS NOTEADDED

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBB

SJBA

REV. DESCRIPTION.DATE. BY.

For Ψ values applicable to this detail,see Constructive Details CD0001orLABC Registered ConstructionDetails E5MCPF16 - 21.

LABC NOTE ADDED11.2014 SJBC

Page 3: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

dpmdpcwall cavity insulation to

continue at least 215mmbelow underside of slab

floor insulation to tightly abutwall blockwork

traditional mortar base courseincorporating lapped dpm and dpc

partial-fill cavitywall insulation

clear cavity

helical cavity tiesface fixed to inner leaf

Celcon thin joint blocks*to inner leaf, above dpc

Celcon blocks and traditionalmortar below ground

Celcon foundation blocks

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

External Masonry Cavity Wall,

Partial Fill - Suspended In-Situ Concrete

Floor, Insulation Below Slab

HH-TJ-PF-02

AHRSJB

Nov 2012 1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

C

11/2013 MAX. FLOOR THICKNESS NOTEADDED

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBB

SJBA

REV. DESCRIPTION.DATE. BY.

C 11/2014 SJBMAX. FLOOR THICKNESS NOTEREMOVED. LABC REFERENCEADDED.

For Ψ values applicable to this detail,see Constructive Details CD0002orLABC Registered ConstructionDetails E5MCPF28 - 33.

Page 4: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

dpc

perimeter insulation toprovide minimum resistanceof 0.8m²K/W

Celcon thin joint blocks*to inner leaf, above dpc

partial-fill cavitywall insulation

clear cavity

helical cavity tiesface fixed to inner leaf

dpm

floor insulation to tightly abutwall blockwork

traditional mortar base courseincorporating lapped dpm and dpc

Celcon blocks and traditionalmortar below ground

wall insulation to continueat least 215mm below

underside of slab

Celcon foundation blocks

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

External Masonry Cavity Wall,

Partial Fill - Concrete Ground Bearing

Floor, Insulation Below Slab

HH-TJ-PF-03

AHRSJB

Nov 2012 1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

C

11/2013 MAX. FLOOR THICKNESS NOTEADDED

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBB

SJBA

REV. DESCRIPTION.DATE. BY.

C 11/2014 SJBMAX. FLOOR THICKNESS NOTEREMOVED. LABC REFERENCEADDED.

For Ψ values applicable to this detail,see Constructive Details CD0003orLABC Registered ConstructionDetails E5MCPF22 - 27.

Page 5: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

minimum frameoverlap 30mm

PVC-U cavity closerfully insulated

internal lintel

Celcon thin joint blocks*to inner leaf

partial-fill cavitywall insulation

clear cavity

helical cavity tiesface fixed to inner leaf

external lintel

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

External Masonry Cavity Wall,Partial Fill - Independent Lintel

HH-TJ-PF-04

AHRSJB

Nov 2012 B1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBA

REV. DESCRIPTION.DATE. BY.

11/2014 LABC NOTE ADDED SJBB

For Ψ values applicable to this detail,see Constructive Details CD0004orLABC Registered ConstructionDetails E2MCPF4 - 6.

Page 6: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

insulated steel lintel with perforatedbase plate (equivalent conductivity30W/mK or less)

minimum frameoverlap 30mm

soffit insulation with min.resistance of 0.6m²K/W

Celcon thin joint blocks*to inner leaf

partial-fill cavitywall insulation

clear cavity

helical cavity tiesface fixed to inner leaf

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

HH-TJ-PF-05

AHRSJB

Nov 2012 B1:100 @ A4

External Masonry Cavity Wall,

Partial Fill - Steel Lintel, Perforated

Base Plate, (Insulated Soffit)

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBA

REV. DESCRIPTION.DATE. BY.

B 11/2014 SJBMAX. LINTEL HEIGHT NOTEREMOVED. LINTEL BASEPLATEADDED. LABC REFERENCE ADDED

For Ψ values applicable to this detail,see Constructive Details CD0005orLABC Registered ConstructionDetails E1MCPF4 - 6.

Page 7: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

minimum frameoverlap 30mm

Aircrete blocks to inner leaf

insulated steel lintel, no continuousbase plate. max. steel thickness 3.0mm

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

External Masonry Cavity Wall,

Partial Fill - Steel Lintel, Open Back

(no continuous base plate)

HH-TJ-PF-22

AHRSJB

Nov 2014 1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

REV. DESCRIPTION.DATE. BY.

0

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

For Ψ values applicable to this detail,see LABC Registered ConstructionDetails E2MCPF7 - 9.

Page 8: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

minimum frameoverlap 30mm

Celcon thin joint blocks*to inner leaf

partial-fill cavitywall insulation

PVC-U cavity closer,fully insulated

clear cavity

helical cavity tiesface fixed to inner leaf

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

External Masonry Cavity Wall,

Partial Fill - Sill

HH-TJ-PF-06

AHRSJB

Nov 2012 B1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBA

REV. DESCRIPTION.DATE. BY.

11/2014 LABC NOTE ADDED SJBB

For Ψ values applicable to this detail,see Constructive Details CD0006orLABC Registered ConstructionDetails E3MCPF4 - 6.

Page 9: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

Celcon thin joint blocks*to inner leaf

PVC-U cavity closer,fully insulated

minimum frameoverlap 30mm

clear cavity

helical cavity tiesface fixed to inner leaf

partial-fill cavitywall insulation

300mm max.

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

External Masonry Cavity Wall,Partial Fill - Jamb

HH-TJ-PF-07

AHRSJB

Nov 2012 B1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBA

REV. DESCRIPTION.DATE. BY.

11/2014 LABC NOTE ADDED SJBB

For Ψ values applicable to this detail,see Constructive Details CD0007orLABC Registered ConstructionDetails E4MCPF4 - 6.

Page 10: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

timber floor joists may be built intoinner block leaf or supported onjoist hangers

partial-fill cavitywall insulation

Celcon thin joint blocks*to inner leaf

clear cavity

helical cavity tiesface fixed to inner leaf

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

External Masonry Cavity Wall,

Partial Fill - Intermediate Timber FloorWithin A Dwelling

HH-TJ-PF-08

AHRSJB

Nov 2012 B1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBA

REV. DESCRIPTION.DATE. BY.

11/2014 LABC NOTE ADDED SJBB

For Ψ values applicable to this detail,see Constructive Details CD0008orLABC Registered ConstructionDetails E6MCPF4 - 6.

Page 11: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

clear cavity

proprietary fire stop precast concreteplank floor

concrete screed

ceiling void

partial-fill cavitywall insulation

Celcon thin joint blocks*to inner leaf

dpm

traditional mortarbase course

helical cavity tiesface fixed to inner leaf

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

External Masonry Cavity Wall,

Partial Fill - Precast Concrete Separating

Floor Between Dwellings

HH-TJ-PF-09

AHRSJB

Nov 2012 B1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBA

REV. DESCRIPTION.DATE. BY.

11/2014PROPRIETARY FIRE STOP NOTEREVISED. LABC NOTE ADDED.

SJBB

For Ψ values applicable to this detail,see Constructive Details CD0009orLABC Registered ConstructionDetails E7MCPF4 - 6.

Page 12: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

clear cavity

minimum 200mmwall insulation above

ceiling insulation

Celcon thin joint blocks*to inner leaf

partial-fill cavitywall insulation

ceilinginsulation

pack compressible insulationbetween last truss and wall

helical cavity tiesface fixed to inner leaf

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

External Masonry Cavity Wall,

Partial Fill - Pitched Roof, Gable -

Insulation At Ceiling Level, Ventilated Loft

HH-TJ-PF-10

AHRSJB

Nov 2012 B1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBA

REV. DESCRIPTION.DATE. BY.

For Ψ values applicable to this detail,see Constructive Details CD0010orLABC Registered ConstructionDetails E12MCPF4 - 6.

11/2014 SJBB LABC NOTE ADDED

Page 13: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

partial-fill cavitywall insulation

clear cavity

100mm minimum

breathable roofmembrane

helical cavity tiesface fixed to inner leaf

pack compressible insulationbetween last rafter and wall

insulation under rafters(optional)

min. 150mm rafters void fullyfilled with insulation

Celcon thin joint blocks*to inner leaf

fill this void with insulationhaving a max. λ of 0.04W/mK

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

HH-TJ-PF-11

AHRSJB

Nov 2012 1:100 @ A4

External Masonry Cavity Wall,Partial Fill - Pitched Roof, Gable - Insulation

At Rafter Level, Unventilated Rafter Void

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

C

11/2013 RAFTERS INSULATION THICKNESSNOTE ADDED

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBB

SJBA

REV. DESCRIPTION.DATE. BY.

11/2014 SJBC LABC NOTE ADDED

For Ψ values applicable to this detail,see Constructive Details CD0011orLABC Registered ConstructionDetails E13MCPF4 - 6.

Page 14: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

Celcon thin joint blocks*inner leaf

ceiling insulationbetween and overroof trusses

ventilated loft

partial-fill cavitywall insulation

clear cavity

helical cavity tiesface fixed to inner leaf

min. 50mm insulationbetween wall plate

and vent

proprietary ventilatorbetween rafters

insulation to entirely filleaves gap between wall

insulation andceiling insulation

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

HH-TJ-PF-12

AHRSJB

Nov 2012 1:100 @ A4

External Masonry Cavity Wall,Partial Fill - Pitched Roof, Eaves - Insulation

At Ceiling Level, Ventilated Loft

THIN JOINT

A 11/2013 SJBWALL PLATE INSULATION COVERNOTE MOVED

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

REV. DESCRIPTION.DATE. BY.

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints C

BLOCK FORMATS NOTE REVISED09.2014 SJBB

11/2014 SJBC LABC NOTE ADDED

For Ψ values applicable to this detail,see Constructive Details CD0012orLABC Registered ConstructionDetails E10MCPF4 - 6.

Page 15: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

partial-fill cavitywall insulation

Celcon thin joint blocks*to inner leaf

breathable roofmembrane

insulation to entirely filleaves gap betweenwall insulation and

ceiling insulation

insulation underrafters (optional)

150mm min. rafters with insulationof max. λ = 0.040W/mk between,to sloping ceiling section

clear cavity

helical cavity tiesface fixed to inner leaf

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

HH-TJ-PF-13

AHRSJB

Nov 2012 1:100 @ A4

External Masonry Cavity Wall,Partial Fill - Pitched Roof, Eaves - Insulation

At Rafter Level, Unventilated Rafter Void

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

B

A 11/2013 SJBRAFTERS INSULATION NOWSHOWN AS 150mm.

REV. DESCRIPTION.DATE. BY.

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBB

For Ψ values applicable to this detail,see Constructive Details CD0013

Page 16: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

150mm rafters with insulationof λ = 0.044W/mk between,to sloping ceiling section

proprietary fire stop (if required),max λ ≤ 0.044W/mK

50mm insulation under

rafters, max λ = 0.022W/mK

Aircrete blocks to inner leaf

insulation to entirely filleaves gap betweenwall insulation and

ceiling insulation

clear cavity

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

External Masonry Cavity Wall,

Partial Fill - Pitched Roof, Eaves, Insulated

At Rafter Level, Unventilated Rafter Void

HH-TJ-PF-23

AHRSJB

Nov 2014 1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

REV. DESCRIPTION.DATE. BY.

0

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

For Ψ values applicable to this detail,see LABC Registered ConstructionDetails E11MCPF4 - 6.

Page 17: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

Celcon thin joint blocks*to inner leaf

clear cavity

Partial-fillwall insulation

helical cavity tiesface fixed to inner leaf

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

HH-TJ-PF-14

AHRSJB

Nov 2012 1:100 @ A4

External Masonry Cavity Wall,Partial Fill - Normal Corner

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

REV. DESCRIPTION.DATE. BY.

B

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBA

LABC NOTE ADDED11.2014 SJBB

For Ψ values applicable to this detail,see Constructive Details CD0014orLABC Registered ConstructionDetails E16MCPF4 - 6.

Page 18: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

partial-fillcavity insulation

clear cavity

Celcon thin joint blocks*to inner leaf

helical cavity tiesface fixed to inner leaf

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

HH-TJ-PF-15

AHRSJB

Nov 2012 1:100 @ A4

External Masonry Cavity Wall,Partial Fill - Inverted Corner

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

REV. DESCRIPTION.DATE. BY.

B

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBA

LABC NOTE ADDED11.2014 SJBB

For Ψ values applicable to this detail,see Constructive Details CD0015orLABC Registered ConstructionDetails E17MCPF4 - 6.

Page 19: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

full fill mineral wool cavity wallinsulation, density up to 40kg/m³

partial-fill cavitywall insulation

clear cavity

Celcon thin joint blocks*to inner leaf

8mm parge coat may be omitted(subject to Robust Detail requirements)

cavity width min. 75mmup to 100mm max.

(subject to Robust Detailrequirements)

2 x 100mm thin joint leaves*to separating wall above dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)

helical cavity tiesface fixed to inner leaf

separating wall ties to beAncon Staifix HRT4 ORClan PWT4

proprietary insulated fire stopif required

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

External Masonry Cavity Wall,Partial Fill - Party Wall Between Dwellings

HH-TJ-PF-16

AHRSJB

Nov 2012 1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

REV. DESCRIPTION.DATE. BY.

B

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBA

11/2014PROPRIETARY FIRE STOP NOTEREVISED. LABC NOTE ADDED.

SJBB

For Ψ values applicable to this detail,see Constructive Details CD0016orLABC Registered ConstructionDetails E18MCPF7 - 10.

Page 20: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

ventilated void

floor insulation to tightly abutwall blockwork

full fill mineral wool cavity wall insulation,density up to 40kg/m³

precast beam and block floorwith Celcon Standard infill blocks

minimum 225mm

dpmdpm

2 x 100mm thin joint leaves*to separating wall above dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)

insulation to continue at least 215mmbelow top of beams

Celcon blocks and traditionalmortar below dpc

cavity width min. 75mmup to 100mm max.

(subject to Robust Detailrequirements)

traditional mortar base courseincorporating dpm and dpc

8mm parge coat may be omitted(subject to Robust Detail requirements)

separating wall ties to beAncon Staifix HRT4 OR Clan PWT4

Celcon infill block built into wallsto have the same compressivestrength as wall blocks

max. 75mm screed thickness

perimeter insulation to provideminimum resistance of 0.8m²K/W

Celcon foundation blocks

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

Party Wall Masonry, Full Fill -

Suspended Beam And Block Floor,

Insulation Above Slab

HH-TJ-PW-17

AHRSJB

Nov 2012 1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

C

A 11/2013 SJBMAX. SCREED THICKNESS NOTEADDED

REV. DESCRIPTION.DATE. BY.

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBB

For Ψ values applicable to this detail,see Constructive Details CD0017orLABC Registered ConstructionDetails P1PCFF1 - 2.

LABC NOTE ADDED11.2014 SJBC

Page 21: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

dpm

n,

floor insulation to tightly abutwall blockwork

insulation to continueat least 215mm belowunderside of slab

full fill mineral wool cavity wall

insulation, density up to 40kg/m³

2 x 100mm thin joint leaves*to separating wall above dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)

dpm

cavity width min. 75mmup to 100mm max.

(subject to Robust Detailrequirements)

8mm parge coat may be omitted(subject to Robust Detail

Requirement)

Celcon blocks and traditionalmortar below ground

traditional mortar base courseincorporating lapped dpm and dpc

separating wall ties to be AnconStaifix HRT4 or Clan PWT4separating wall ties to be AnconStaifix HRT4 or Clan PWT4

Celcon foundation blocks

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

Party Wall Masonry, Full Fill -

Suspended Concrete Floor,

Insulation Below Slab

HH-TJ-PW-18

AHRSJB

Nov 2012 1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

C

A 11/2013 SJBMAX. FLOOR THICKNESS NOTEADDED

REV. DESCRIPTION.DATE. BY.

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBB

C 11/2014 SJBMAX. FLOOR THICKNESS NOTEREMOVED. LABC REFERENCEADDED.

For Ψ values applicable to this detail,see Constructive Details CD0018orLABC Registered ConstructionDetails P1PCFF3 - 4.

Page 22: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

dpmfloor insulation to tightly abutwall blockwork

2 x 100mm thin joint leaves*to separating wall above dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)

full fill mineral wool cavity wall

insulation, density up to 40kg/m³

dpm

cavity width min. 75mmup to 100mm max.

(subject to Robust Detailrequirements)

8mm parge coat may be omitted(subject to Robust Detail

Requirement)

Celcon blocks and traditionalmortar below ground

separating wall ties to be AnconStaifix HRT4 or Clan PWT4

insulation to continue at least215mm below underside of slab

traditional mortar base courseincorporating lapped dpm and dpc

perimeter insulation to provideminimum resistance of 0.8m²K/W

Celcon foundation blocks

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

Party Wall Masonry, Full Fill -

In-situ Concrete Ground Bearing Floor,

Insulation Below Slab

HH-TJ-PW-19

AHRSJB

Nov 2012 1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

C

A 11/2013MAX. FLOOR THICKNESS NOTEADDED

BY.

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014B

SJB

SJB

REV. DESCRIPTION.DATE.

C 11/2014 SJBMAX. FLOOR THICKNESS NOTEREMOVED. LABC REFERENCEADDED.

For Ψ values applicable to this detail,see Constructive Details CD0019orLABC Registered ConstructionDetails P1PCFF5 - 6.

Page 23: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

ceiling insulation

pack compressible insulationbetween last rafter and wall

full fill mineral woolcavity wall insulation,density up to40kg/m³

2 x 100mm thin joint leaves*to separating wall above dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)

cavity width min. 75mmup to 100mm max.

(subject to Robust Detailrequirements)

minimum 200mm wallinsulation above ceiling

insulation

separating wall ties to be AnconStaifix HRT4 or Clan PWT4

8mm parge coat may be omitted(subject to Robust Detail

requirements)

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

Party Wall Masonry, Full Fill -

Roof, Insulated At Ceiling Level,

Ventilated Loft

HH-TJ-PW-20

AHRSJB

Nov 2012 1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

REV. DESCRIPTION.DATE. BY.

B

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014 SJBA

LABC NOTE ADDED11.2014 SJBB

For Ψ values applicable to this detail,see Constructive Details CD0020orLABC Registered ConstructionDetails P4PCFF1 - 2.

Page 24: HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill

breathable roofmembrane

minimum 100mminsulation

2 x 100mm thin joint leaves*to separating wall:

Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)

Celcon Super Strength (8.7N/mm²)

insulation under rafters(optional)

separating wall ties to be AnconStaifix HRT4 or Clan PWT4

cavity width min. 75mm, up to 100mm max.(subject to Robust Detail requirements)

min. 150mm rafters void fullyfilled with insulation

pack compressible insulationbetween last rafter and wall

8mm parge coat may be omitted(subject to Robust Detail requirements)

full fill mineral wool cavitywall insulation, density upto 40kg/m³

DRAWN BY

TITLE

DATE SCALE

CHECKED BY

REV.NO.

DWG No.

Party Wall Masonry, Full Fill -

Roof, Insulated At Rafter Level,

Unventilated Rafter Void

HH-TJ-PW-21

AHRSJB

Nov 2012 1:100 @ A4

THIN JOINT

H+H UK Limited

Fax +44 (0)1732 887013

Kent, TN15 9HZ.Ightham, Sevenoaks

Tel +44 (0)1732 880580

Celcon HouseTechnical Services Dept.

E-mail [email protected]

These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.

A 11/2013 SJBRAFTERS INSULATION THICKNESSNOTE ADDED

REV. DESCRIPTION.DATE. BY.

C

* Thin joint block formats are:Plus = 630mm x 215mm

Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm

in 2mm Celfix mortar joints

BLOCK FORMATS NOTE REVISED09.2014B SJB

LABC NOTE ADDED11.2014 SJBC

For Ψ values applicable to this detail,see Constructive Details CD0021orLABC Registered ConstructionDetails P5PCFF1 - 2.