HH-TJ-PF-01 External Masonry Cavity Wall, Partial-Fill - Suspended Beam And Block Floor, Insulation Above Slab
HH-TJ-PF-02 External Masonry Cavity Wall, Partial-Fill - Suspended In-Situ Concrete Floor, Insulation Below Slab
HH-TJ-PF-04 External Masonry Cavity Wall, Partial-Fill - Independent Lintel
HH-TJ-PF-03 External Masonry Cavity Wall, Partial-Fill - Concrete Ground Bearing Floor, Insulation Below Slab
HH-TJ-PF-07 External Masonry Cavity Wall, Partial-Fill - Jamb
HH-TJ-PF-05 External Masonry Cavity Wall, Partial-Fill - Steel Lintel, Perforated Base Plate, (Insulated Soffit)
HH-TJ-PF-06 External Masonry Cavity Wall, Partial-Fill - Sill
HH-TJ-PF-09 External Masonry Cavity Wall, Partial-Fill - Precast Concrete Separating Floor Between Dwellings
HH-TJ-PF-08 External Masonry Cavity Wall, Partial-Fill - Intermediate Timber Floor Within A Dwelling
HH-TJ-PF-10 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Gable, Insulation At Ceiling Level, Ventilated Loft
HH-TJ-PF-15 External Masonry Cavity Wall, Partial-Fill - Inverted Corner
HH-TJ-PF-11 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Gable, Insulation At Rafter Level, Unventilated Rafter Void
HH-TJ-PF-12 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Eaves, Insulation At Ceiling Level, Ventilated Loft
HH-TJ-PF-14 External Masonry Cavity Wall, Partial-Fill - Normal Corner
HH-TJ-PF-16 External Masonry Cavity Wall, Partial-Fill - Party Wall Between Dwellings
HH-TJ-PW-18 Party Wall Masonry, Full Fill - Suspended Concrete Floor, Insulation Below Slab
HH-TJ-PW-19 Party Wall Masonry, Full Fill - In-Situ Concrete Ground Bearing Floor, Insulation Below Slab
HH-TJ-PW-20 Party Wall Masonry, Full Fill - Roof, Insulation At Ceiling Level, Ventilated Loft
HH-TJ-PW-21 Party Wall Masonry, Full Fill - Roof, Insulation At Rafter Level, Unventilated Rafter Void
Detail Ref. Detail Title
HH-TJ-PF-13 External Masonry Cavity Wall, Partial-Fill - Pitched Roof, Eaves, Insulation At Rafter Level, Unventilated Rafter Void
HH-TJ-PW-17 Party Wall Masonry, Full Fill - Suspended Beam And Block Floor, Insulation Above Slab
HH-TJ-PW-18 Party Wall Masonry, Full Fill - Suspended Concrete Floor, Insulation Below Slab
HH-TJ-PW-19 Party Wall Masonry, Full Fill - In-Situ Concrete Ground Bearing Floor, Insulation Below Slab
HH-TJ-PW-20 Party Wall Masonry, Full Fill - Roof, Insulation At Ceiling Level, Ventilated Loft
HH-TJ-PW-21 Party Wall Masonry, Full Fill - Roof, Insulation At Rafter Level, Unventilated Rafter Void
HH-TJ-PF-23 External Masonry Cavity Wall, Partial Fill - Pitched Roof, Eaves - Insulation At Rafter Level, Unventilated Rafter Void
HH-TJ-PF-22 External Masonry Cavity Wall, Partial-Fill - Steel Lintel, Open Back (no continuous base plate)
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
Thin Joint Junction Details(partial Fill)
INDEX
AHRSJB
Nov 2012 AN.T.S.
REV. DESCRIPTION.DATE. BY.
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
A 11/2014 SJBHH-TJ-PF-22 & HH-TJ-PF-23 ADDED
ventilated void
wall cavity insulation tocontinue at least 215mm
from top of beam
partial-fill cavitywall insulation
floor insulation to tightly abutwall blockworkdpc
clear cavity Celcon thin joint blocks*to inner leaf, above dpc
dpm
precast beam and block floorwith Celcon Standard infill blocks
Celcon blocks and traditionalmortar below ground
Celcon infill blocks built into wallsto have the same compressivestrength as wall blocks
perimeter insulation to provideminimum resistance of0.8m²K/W
traditional mortar base courseincorporating dpm and dpc
helical cavity tiesface fixed to inner leaf
max. 75mm screed thickness
Celcon foundation blocks
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Suspended Beam And Block
Floor, Insulation Above Slab
HH-TJ-PF-01
AHRSJB
Nov 2012 1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
C
11/2013 MAX. SCREED THICKNESS NOTEADDED
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBB
SJBA
REV. DESCRIPTION.DATE. BY.
For Ψ values applicable to this detail,see Constructive Details CD0001orLABC Registered ConstructionDetails E5MCPF16 - 21.
LABC NOTE ADDED11.2014 SJBC
dpmdpcwall cavity insulation to
continue at least 215mmbelow underside of slab
floor insulation to tightly abutwall blockwork
traditional mortar base courseincorporating lapped dpm and dpc
partial-fill cavitywall insulation
clear cavity
helical cavity tiesface fixed to inner leaf
Celcon thin joint blocks*to inner leaf, above dpc
Celcon blocks and traditionalmortar below ground
Celcon foundation blocks
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Suspended In-Situ Concrete
Floor, Insulation Below Slab
HH-TJ-PF-02
AHRSJB
Nov 2012 1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
C
11/2013 MAX. FLOOR THICKNESS NOTEADDED
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBB
SJBA
REV. DESCRIPTION.DATE. BY.
C 11/2014 SJBMAX. FLOOR THICKNESS NOTEREMOVED. LABC REFERENCEADDED.
For Ψ values applicable to this detail,see Constructive Details CD0002orLABC Registered ConstructionDetails E5MCPF28 - 33.
dpc
perimeter insulation toprovide minimum resistanceof 0.8m²K/W
Celcon thin joint blocks*to inner leaf, above dpc
partial-fill cavitywall insulation
clear cavity
helical cavity tiesface fixed to inner leaf
dpm
floor insulation to tightly abutwall blockwork
traditional mortar base courseincorporating lapped dpm and dpc
Celcon blocks and traditionalmortar below ground
wall insulation to continueat least 215mm below
underside of slab
Celcon foundation blocks
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Concrete Ground Bearing
Floor, Insulation Below Slab
HH-TJ-PF-03
AHRSJB
Nov 2012 1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
C
11/2013 MAX. FLOOR THICKNESS NOTEADDED
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBB
SJBA
REV. DESCRIPTION.DATE. BY.
C 11/2014 SJBMAX. FLOOR THICKNESS NOTEREMOVED. LABC REFERENCEADDED.
For Ψ values applicable to this detail,see Constructive Details CD0003orLABC Registered ConstructionDetails E5MCPF22 - 27.
minimum frameoverlap 30mm
PVC-U cavity closerfully insulated
internal lintel
Celcon thin joint blocks*to inner leaf
partial-fill cavitywall insulation
clear cavity
helical cavity tiesface fixed to inner leaf
external lintel
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,Partial Fill - Independent Lintel
HH-TJ-PF-04
AHRSJB
Nov 2012 B1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBA
REV. DESCRIPTION.DATE. BY.
11/2014 LABC NOTE ADDED SJBB
For Ψ values applicable to this detail,see Constructive Details CD0004orLABC Registered ConstructionDetails E2MCPF4 - 6.
insulated steel lintel with perforatedbase plate (equivalent conductivity30W/mK or less)
minimum frameoverlap 30mm
soffit insulation with min.resistance of 0.6m²K/W
Celcon thin joint blocks*to inner leaf
partial-fill cavitywall insulation
clear cavity
helical cavity tiesface fixed to inner leaf
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
HH-TJ-PF-05
AHRSJB
Nov 2012 B1:100 @ A4
External Masonry Cavity Wall,
Partial Fill - Steel Lintel, Perforated
Base Plate, (Insulated Soffit)
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBA
REV. DESCRIPTION.DATE. BY.
B 11/2014 SJBMAX. LINTEL HEIGHT NOTEREMOVED. LINTEL BASEPLATEADDED. LABC REFERENCE ADDED
For Ψ values applicable to this detail,see Constructive Details CD0005orLABC Registered ConstructionDetails E1MCPF4 - 6.
minimum frameoverlap 30mm
Aircrete blocks to inner leaf
insulated steel lintel, no continuousbase plate. max. steel thickness 3.0mm
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Steel Lintel, Open Back
(no continuous base plate)
HH-TJ-PF-22
AHRSJB
Nov 2014 1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
REV. DESCRIPTION.DATE. BY.
0
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
For Ψ values applicable to this detail,see LABC Registered ConstructionDetails E2MCPF7 - 9.
minimum frameoverlap 30mm
Celcon thin joint blocks*to inner leaf
partial-fill cavitywall insulation
PVC-U cavity closer,fully insulated
clear cavity
helical cavity tiesface fixed to inner leaf
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Sill
HH-TJ-PF-06
AHRSJB
Nov 2012 B1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBA
REV. DESCRIPTION.DATE. BY.
11/2014 LABC NOTE ADDED SJBB
For Ψ values applicable to this detail,see Constructive Details CD0006orLABC Registered ConstructionDetails E3MCPF4 - 6.
Celcon thin joint blocks*to inner leaf
PVC-U cavity closer,fully insulated
minimum frameoverlap 30mm
clear cavity
helical cavity tiesface fixed to inner leaf
partial-fill cavitywall insulation
300mm max.
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,Partial Fill - Jamb
HH-TJ-PF-07
AHRSJB
Nov 2012 B1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBA
REV. DESCRIPTION.DATE. BY.
11/2014 LABC NOTE ADDED SJBB
For Ψ values applicable to this detail,see Constructive Details CD0007orLABC Registered ConstructionDetails E4MCPF4 - 6.
timber floor joists may be built intoinner block leaf or supported onjoist hangers
partial-fill cavitywall insulation
Celcon thin joint blocks*to inner leaf
clear cavity
helical cavity tiesface fixed to inner leaf
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Intermediate Timber FloorWithin A Dwelling
HH-TJ-PF-08
AHRSJB
Nov 2012 B1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBA
REV. DESCRIPTION.DATE. BY.
11/2014 LABC NOTE ADDED SJBB
For Ψ values applicable to this detail,see Constructive Details CD0008orLABC Registered ConstructionDetails E6MCPF4 - 6.
clear cavity
proprietary fire stop precast concreteplank floor
concrete screed
ceiling void
partial-fill cavitywall insulation
Celcon thin joint blocks*to inner leaf
dpm
traditional mortarbase course
helical cavity tiesface fixed to inner leaf
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Precast Concrete Separating
Floor Between Dwellings
HH-TJ-PF-09
AHRSJB
Nov 2012 B1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBA
REV. DESCRIPTION.DATE. BY.
11/2014PROPRIETARY FIRE STOP NOTEREVISED. LABC NOTE ADDED.
SJBB
For Ψ values applicable to this detail,see Constructive Details CD0009orLABC Registered ConstructionDetails E7MCPF4 - 6.
clear cavity
minimum 200mmwall insulation above
ceiling insulation
Celcon thin joint blocks*to inner leaf
partial-fill cavitywall insulation
ceilinginsulation
pack compressible insulationbetween last truss and wall
helical cavity tiesface fixed to inner leaf
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Pitched Roof, Gable -
Insulation At Ceiling Level, Ventilated Loft
HH-TJ-PF-10
AHRSJB
Nov 2012 B1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBA
REV. DESCRIPTION.DATE. BY.
For Ψ values applicable to this detail,see Constructive Details CD0010orLABC Registered ConstructionDetails E12MCPF4 - 6.
11/2014 SJBB LABC NOTE ADDED
partial-fill cavitywall insulation
clear cavity
100mm minimum
breathable roofmembrane
helical cavity tiesface fixed to inner leaf
pack compressible insulationbetween last rafter and wall
insulation under rafters(optional)
min. 150mm rafters void fullyfilled with insulation
Celcon thin joint blocks*to inner leaf
fill this void with insulationhaving a max. λ of 0.04W/mK
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
HH-TJ-PF-11
AHRSJB
Nov 2012 1:100 @ A4
External Masonry Cavity Wall,Partial Fill - Pitched Roof, Gable - Insulation
At Rafter Level, Unventilated Rafter Void
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
C
11/2013 RAFTERS INSULATION THICKNESSNOTE ADDED
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBB
SJBA
REV. DESCRIPTION.DATE. BY.
11/2014 SJBC LABC NOTE ADDED
For Ψ values applicable to this detail,see Constructive Details CD0011orLABC Registered ConstructionDetails E13MCPF4 - 6.
Celcon thin joint blocks*inner leaf
ceiling insulationbetween and overroof trusses
ventilated loft
partial-fill cavitywall insulation
clear cavity
helical cavity tiesface fixed to inner leaf
min. 50mm insulationbetween wall plate
and vent
proprietary ventilatorbetween rafters
insulation to entirely filleaves gap between wall
insulation andceiling insulation
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
HH-TJ-PF-12
AHRSJB
Nov 2012 1:100 @ A4
External Masonry Cavity Wall,Partial Fill - Pitched Roof, Eaves - Insulation
At Ceiling Level, Ventilated Loft
THIN JOINT
A 11/2013 SJBWALL PLATE INSULATION COVERNOTE MOVED
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
REV. DESCRIPTION.DATE. BY.
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints C
BLOCK FORMATS NOTE REVISED09.2014 SJBB
11/2014 SJBC LABC NOTE ADDED
For Ψ values applicable to this detail,see Constructive Details CD0012orLABC Registered ConstructionDetails E10MCPF4 - 6.
partial-fill cavitywall insulation
Celcon thin joint blocks*to inner leaf
breathable roofmembrane
insulation to entirely filleaves gap betweenwall insulation and
ceiling insulation
insulation underrafters (optional)
150mm min. rafters with insulationof max. λ = 0.040W/mk between,to sloping ceiling section
clear cavity
helical cavity tiesface fixed to inner leaf
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
HH-TJ-PF-13
AHRSJB
Nov 2012 1:100 @ A4
External Masonry Cavity Wall,Partial Fill - Pitched Roof, Eaves - Insulation
At Rafter Level, Unventilated Rafter Void
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
B
A 11/2013 SJBRAFTERS INSULATION NOWSHOWN AS 150mm.
REV. DESCRIPTION.DATE. BY.
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBB
For Ψ values applicable to this detail,see Constructive Details CD0013
150mm rafters with insulationof λ = 0.044W/mk between,to sloping ceiling section
proprietary fire stop (if required),max λ ≤ 0.044W/mK
50mm insulation under
rafters, max λ = 0.022W/mK
Aircrete blocks to inner leaf
insulation to entirely filleaves gap betweenwall insulation and
ceiling insulation
clear cavity
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,
Partial Fill - Pitched Roof, Eaves, Insulated
At Rafter Level, Unventilated Rafter Void
HH-TJ-PF-23
AHRSJB
Nov 2014 1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
REV. DESCRIPTION.DATE. BY.
0
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
For Ψ values applicable to this detail,see LABC Registered ConstructionDetails E11MCPF4 - 6.
Celcon thin joint blocks*to inner leaf
clear cavity
Partial-fillwall insulation
helical cavity tiesface fixed to inner leaf
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
HH-TJ-PF-14
AHRSJB
Nov 2012 1:100 @ A4
External Masonry Cavity Wall,Partial Fill - Normal Corner
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
REV. DESCRIPTION.DATE. BY.
B
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBA
LABC NOTE ADDED11.2014 SJBB
For Ψ values applicable to this detail,see Constructive Details CD0014orLABC Registered ConstructionDetails E16MCPF4 - 6.
partial-fillcavity insulation
clear cavity
Celcon thin joint blocks*to inner leaf
helical cavity tiesface fixed to inner leaf
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
HH-TJ-PF-15
AHRSJB
Nov 2012 1:100 @ A4
External Masonry Cavity Wall,Partial Fill - Inverted Corner
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
REV. DESCRIPTION.DATE. BY.
B
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBA
LABC NOTE ADDED11.2014 SJBB
For Ψ values applicable to this detail,see Constructive Details CD0015orLABC Registered ConstructionDetails E17MCPF4 - 6.
full fill mineral wool cavity wallinsulation, density up to 40kg/m³
partial-fill cavitywall insulation
clear cavity
Celcon thin joint blocks*to inner leaf
8mm parge coat may be omitted(subject to Robust Detail requirements)
cavity width min. 75mmup to 100mm max.
(subject to Robust Detailrequirements)
2 x 100mm thin joint leaves*to separating wall above dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)
helical cavity tiesface fixed to inner leaf
separating wall ties to beAncon Staifix HRT4 ORClan PWT4
proprietary insulated fire stopif required
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
External Masonry Cavity Wall,Partial Fill - Party Wall Between Dwellings
HH-TJ-PF-16
AHRSJB
Nov 2012 1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
REV. DESCRIPTION.DATE. BY.
B
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBA
11/2014PROPRIETARY FIRE STOP NOTEREVISED. LABC NOTE ADDED.
SJBB
For Ψ values applicable to this detail,see Constructive Details CD0016orLABC Registered ConstructionDetails E18MCPF7 - 10.
ventilated void
floor insulation to tightly abutwall blockwork
full fill mineral wool cavity wall insulation,density up to 40kg/m³
precast beam and block floorwith Celcon Standard infill blocks
minimum 225mm
dpmdpm
2 x 100mm thin joint leaves*to separating wall above dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)
insulation to continue at least 215mmbelow top of beams
Celcon blocks and traditionalmortar below dpc
cavity width min. 75mmup to 100mm max.
(subject to Robust Detailrequirements)
traditional mortar base courseincorporating dpm and dpc
8mm parge coat may be omitted(subject to Robust Detail requirements)
separating wall ties to beAncon Staifix HRT4 OR Clan PWT4
Celcon infill block built into wallsto have the same compressivestrength as wall blocks
max. 75mm screed thickness
perimeter insulation to provideminimum resistance of 0.8m²K/W
Celcon foundation blocks
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
Party Wall Masonry, Full Fill -
Suspended Beam And Block Floor,
Insulation Above Slab
HH-TJ-PW-17
AHRSJB
Nov 2012 1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
C
A 11/2013 SJBMAX. SCREED THICKNESS NOTEADDED
REV. DESCRIPTION.DATE. BY.
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBB
For Ψ values applicable to this detail,see Constructive Details CD0017orLABC Registered ConstructionDetails P1PCFF1 - 2.
LABC NOTE ADDED11.2014 SJBC
dpm
n,
floor insulation to tightly abutwall blockwork
insulation to continueat least 215mm belowunderside of slab
full fill mineral wool cavity wall
insulation, density up to 40kg/m³
2 x 100mm thin joint leaves*to separating wall above dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)
dpm
cavity width min. 75mmup to 100mm max.
(subject to Robust Detailrequirements)
8mm parge coat may be omitted(subject to Robust Detail
Requirement)
Celcon blocks and traditionalmortar below ground
traditional mortar base courseincorporating lapped dpm and dpc
separating wall ties to be AnconStaifix HRT4 or Clan PWT4separating wall ties to be AnconStaifix HRT4 or Clan PWT4
Celcon foundation blocks
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
Party Wall Masonry, Full Fill -
Suspended Concrete Floor,
Insulation Below Slab
HH-TJ-PW-18
AHRSJB
Nov 2012 1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
C
A 11/2013 SJBMAX. FLOOR THICKNESS NOTEADDED
REV. DESCRIPTION.DATE. BY.
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBB
C 11/2014 SJBMAX. FLOOR THICKNESS NOTEREMOVED. LABC REFERENCEADDED.
For Ψ values applicable to this detail,see Constructive Details CD0018orLABC Registered ConstructionDetails P1PCFF3 - 4.
dpmfloor insulation to tightly abutwall blockwork
2 x 100mm thin joint leaves*to separating wall above dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)
full fill mineral wool cavity wall
insulation, density up to 40kg/m³
dpm
cavity width min. 75mmup to 100mm max.
(subject to Robust Detailrequirements)
8mm parge coat may be omitted(subject to Robust Detail
Requirement)
Celcon blocks and traditionalmortar below ground
separating wall ties to be AnconStaifix HRT4 or Clan PWT4
insulation to continue at least215mm below underside of slab
traditional mortar base courseincorporating lapped dpm and dpc
perimeter insulation to provideminimum resistance of 0.8m²K/W
Celcon foundation blocks
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
Party Wall Masonry, Full Fill -
In-situ Concrete Ground Bearing Floor,
Insulation Below Slab
HH-TJ-PW-19
AHRSJB
Nov 2012 1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
C
A 11/2013MAX. FLOOR THICKNESS NOTEADDED
BY.
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014B
SJB
SJB
REV. DESCRIPTION.DATE.
C 11/2014 SJBMAX. FLOOR THICKNESS NOTEREMOVED. LABC REFERENCEADDED.
For Ψ values applicable to this detail,see Constructive Details CD0019orLABC Registered ConstructionDetails P1PCFF5 - 6.
ceiling insulation
pack compressible insulationbetween last rafter and wall
full fill mineral woolcavity wall insulation,density up to40kg/m³
2 x 100mm thin joint leaves*to separating wall above dpc:Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)Celcon Super Strength (8.7N/mm²)
cavity width min. 75mmup to 100mm max.
(subject to Robust Detailrequirements)
minimum 200mm wallinsulation above ceiling
insulation
separating wall ties to be AnconStaifix HRT4 or Clan PWT4
8mm parge coat may be omitted(subject to Robust Detail
requirements)
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
Party Wall Masonry, Full Fill -
Roof, Insulated At Ceiling Level,
Ventilated Loft
HH-TJ-PW-20
AHRSJB
Nov 2012 1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
REV. DESCRIPTION.DATE. BY.
B
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014 SJBA
LABC NOTE ADDED11.2014 SJBB
For Ψ values applicable to this detail,see Constructive Details CD0020orLABC Registered ConstructionDetails P4PCFF1 - 2.
breathable roofmembrane
minimum 100mminsulation
2 x 100mm thin joint leaves*to separating wall:
Celcon Standard (3.6N/mm²)Celcon High Strength (7.3N/mm²)
Celcon Super Strength (8.7N/mm²)
insulation under rafters(optional)
separating wall ties to be AnconStaifix HRT4 or Clan PWT4
cavity width min. 75mm, up to 100mm max.(subject to Robust Detail requirements)
min. 150mm rafters void fullyfilled with insulation
pack compressible insulationbetween last rafter and wall
8mm parge coat may be omitted(subject to Robust Detail requirements)
full fill mineral wool cavitywall insulation, density upto 40kg/m³
DRAWN BY
TITLE
DATE SCALE
CHECKED BY
REV.NO.
DWG No.
Party Wall Masonry, Full Fill -
Roof, Insulated At Rafter Level,
Unventilated Rafter Void
HH-TJ-PW-21
AHRSJB
Nov 2012 1:100 @ A4
THIN JOINT
H+H UK Limited
Fax +44 (0)1732 887013
Kent, TN15 9HZ.Ightham, Sevenoaks
Tel +44 (0)1732 880580
Celcon HouseTechnical Services Dept.
E-mail [email protected]
These details have been produced for guidance only. It is theresponsibility of the building designer to ensure that the detailsshown are compatible with the overall building design and willsatisfy the relevant parts of the Building Regulations applicablebefore they are adopted into the project design.
A 11/2013 SJBRAFTERS INSULATION THICKNESSNOTE ADDED
REV. DESCRIPTION.DATE. BY.
C
* Thin joint block formats are:Plus = 630mm x 215mm
Jumbo Blok = 630mm x 250mmMultiplate = 630mm x 350mm
in 2mm Celfix mortar joints
BLOCK FORMATS NOTE REVISED09.2014B SJB
LABC NOTE ADDED11.2014 SJBC
For Ψ values applicable to this detail,see Constructive Details CD0021orLABC Registered ConstructionDetails P5PCFF1 - 2.