Reversible Chillers and Heat Pumps - LEW SERIES 40 - 420 kW

HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

���������� ���

���

Reversible Chillers and Heat Pumps - LEW SERIES

40 - 420 kW

Page 2: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 2 of 56 RG66006951‐Rev.01 

 

Page 3: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 3 of 56 RG66006951‐Rev.01 

 

 

 Contents 

CONTENTS ...................................................................................................................................................... 3 

1  GENERAL DESCRIPTION .................................................................................................................. 5 

1.1  LEW UNITS .............................................................................................................................................. 5 1.1.1  PRODUCT CONFIGURATIONS .................................................................................................................. 5 1.1.2  CONFIGURATION AND ACCESSORIES .................................................................................................... 6 1.1.3  FIELD OF APPLICATION ........................................................................................................................... 7 1.1.4  PRODUCT INNOVATION ......................................................................................................................... 10 1.2  STRUCTURE ............................................................................................................................................. 10 1.3  COOLING CIRCUIT ................................................................................................................................ 10 1.3.1  COMPRESSORS ...................................................................................................................................... 11 1.3.2  HEAT EXCHANGERS ............................................................................................................................... 11 1.3.3  DE-SUPERHEATER FOR PARTIAL HEAT RECOVERY (OPTIONAL) ........................................................ 12 1.3.4  UTILITY AND DISSIPATION SIDE CYCLE INVERSION VALVES (OPTIONAL) ...................................... 12 1.3.5  ELECTRONICALLY CONTROLLED ELECTRIC EXPANSION VALVE ......................................................... 13 1.3.6  OTHER COOLING COMPONENTS ........................................................................................................... 14 1.4  ELECTRIC PANEL .................................................................................................................................... 18 1.4.1  CONTROL MICROPROCESSOR ............................................................................................................... 18 

2  MAIN UNITS TECHNICAL DATA ................................................................................................. 19 

2.1  PERFORMANCE OF LEW C, D, H, W HEAT PUMP UNITS ............................................................ 25 2.2  NOISE EMISSION .................................................................................................................................. 28 2.3  OVERALL DIMENSIONS AND WEIGHT OF THE MAIN UNITS ........................................................ 28 2.4  OVERALL DRAWINGS OF THE MAIN UNITS ..................................................................................... 30 

3  TECHNICAL DATA OF OPTIONAL HYDRONIC MODULES ............................................. 39 

3.1  CHARACTERISTIC CURVES OF THE HYDRAULIC PUMPS ASSOCIATED TO THE UNITS ........... 39 3.2  OVERALL DIMENSIONS AND WEIGHT OF OPTIONAL HYDRONIC MODULES ............................ 45 3.3  OVERALL DRAWINGS OF OPTIONAL HYDRONIC MODULES ......................................................... 46 

4  INSTALLATION .................................................................................................................................... 50 

4.1  INSTALLATION CLEARANCE REQUIREMENTS .................................................................................. 50 4.2  VOLUME OF WATER IN THE SYSTEM ................................................................................................. 50 

5  OPERATING LIMITS .......................................................................................................................... 52 

5.1  WORKING LIMITS ................................................................................................................................. 53 5.2  WATER FLOW TO EVAPORATOR ......................................................................................................... 53 

6  CALIBRATION OF CONTROL DEVICES ................................................................................... 54 

Page 4: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 4 of 56 RG66006951‐Rev.01 

 

 

Declaration of conformity

The declaration of conformity is attached to each machine

Page 5: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 5 of 56 RG66006951‐Rev.01 

 

 

1 General description 

1.1 LEW units LEW reversible water chillers and heat pumps are air or process fluid conditioning units, designed for both domestic and industrial use and in operation 24 hours a day. They cover a thermal output range from 40 to 429 kW, guaranteeing a high level thermodynamic performance and a wide range of configuration possibilities, both in accessories and cooling circuit.  LEW machines have been built in a fully faired framework to make the assembly extremely silent. They can therefore be installed  in open environments without needing  to be closed off. The all‐new new rounded‐off shape enhances their appearance.    The  exclusive  use  of  R410A  refrigerant  and  of  high‐quality  components  in  the  chiller,  hydraulic  and electrical parts makes the LEW units state‐of‐the‐art chillers in terms of efficiency, reliability and emitted sound output.  

1.1.1 Product configurations The series of LEW models consists in a wide range of products, meeting all system needs:  LEW C water chillers‐cold water only LEW D water chillers‐cold water only (interlocked by Dry‐Cooler or Evaporative turret) LEW H water heat pumps‐chiller side reversible water LEW W water ‐ water only heating heat pumps  All the above‐mentioned versions are available  in sizes referred to  in the table below. The sizes of the LEW units are expressed in the X‐coordinates of the table in terms of rated cooling capacity [kW], obtained in conditions with chilled water produced at 7°C and  combined with  the evaporative  turret with dissipation  circuit water at 29°  inlet and 35° outlet.   Table I ‐ Table summarising the range of LEW products by size and Efficiency Pack:  

Sizes:  040  050  060  070  080  090  110  130  140  160  180  200  210  240  280  310  340  370  420  480 

Efficiency Pack 1 

F1  F1  F1  F1  F1  F1  F2  F2  F2  F2  F2                   

Efficiency Pack 2 

F1  F1  F1  F1  F1  F1  F2  F2  F2  F2  F2                   

Efficiency Pack 3 

                          F3  F3           

Efficiency Pack 4 

                F3  F3  F3  F3  F3  F3  F3  F3  F3  F3  F3  F3 

 The  first  column of Table  I  shows  the available  "Efficiency Packs". These determine  the  configuration of  the  cooling circuit. For  further details  see paragraph 1.3  “Cooling circuit”. For example,  the  size  “LEW 2 090” develops a 90 kW chiller output and is implemented with Efficiency Pack 2 (two compressors, one cooling circuit). The dimensions of the "Frames" of the units are listed in the cells, by means of reference symbols F1 F2 F3 (with increasing dimensions); all the information  concerning  the weight of  the machines and  the dimensions  corresponding  to each  frame  is available  in paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof set‐up, covering the compressor and outer panelling with soundproof material.   The LEW units are identified with the following symbol:  

LEW 072  CS      

1 2 3 4 5

Page 6: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 6 of 56 RG66006951‐Rev.01 

 

  1 ‐ Identification symbol of Hiref Model (e.g.: “LEW” unit) 2 ‐ Unit sizes expressed in rated chilling output x10 [kW] (e.g.: 70 kW) 3 ‐ Efficiency Pack: cooling circuit and compressor layout (e.g.: Efficiency Pack 2) 4 ‐ Machine version (e.g.: “C”, Chiller) 5 ‐ Machine execution (e.g.: “S” soundproofing not available)   

1.1.2 Configuration and accessories  

List of standard features R410A refrigerant

Scroll compressors

Galvanised and painted sheet-metal structure

Flow switch included

Brazed plate heat exchangers

Second set point on utility side that can be activated from an external input

  

List of options Version CMP-1

Chiller condensed with well or mains water C

Chiller condensed with water from a dry-cooler or evaporative tower D

Reversible heat pump H

Non-reversible heat pump (hot only) W

Execution CMP0

standard S

low-noise L

1 - Electric power supply CMP1

400/3/50 + N 0

400/3/50 + Motor circuit breakers 2

2 - control microprocessor and expansion device CMP2

base + electronic expansion valve 0

base + mechanical expansion valve A

programmable (LCD display 8x22) + electronic expansion valve B

programmable (LCD display 8x22) + mechanical expansion valve C

3 - Partial heat recovery (mandatory condensation control) CMP3

absent 0

de-superheater (40% Pf recovered under normal circumstances) D Not available if Field 4 = 0

4 - Flow rate modulation on source side CMP4

absent 0

condens. control with 0-10V modulated output signal P Not available if Field 2 = 0,A

5 - Flow rate modulation on utility circuit CMP5

absent 0

6 - Remote communication CMP6

absent 0

RS485 serial board (Carel or Modbus protocol) 1

Serial board Lonworks 2 Not available if Field 2 = 0,A

GSM modem kit 3 Not available if Field 2 = 0,A

Ethernet board (SNMP or BACNET protocol) + clock board 4 Not available if Field 2 = 0,A

Ethernet board + clock board + supervision software 5 Not available if Field 2 = 0,A

7 - Vibration isolation CMP7

absent 0

Rubber anti-vibration mounts at unit base G

Spring anti-vibration mounts at unit base M

8 - Package CMP8

standard 0

Page 7: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 7 of 56 RG66006951‐Rev.01 

 

wooden cage 1

wooden cage 2

9 - Remote control CMP9

absent 0

Simplified remote control panel 1

Remote display for standard microprocessor 2 Not available if Field 2 = B,C

Remote display for programmable microprocessor 3 Not available if Field 2 = 0,A

10 - External insulated hydraulic module separated from the main unit CMP10

No hydraulic module 0

LP utility pump + LP dissipation 1

LP utility pump + modulating LP dissipation 2 Not available if Field 2 = 0,A

LP utility pump + HP dissipation 3

LP utility pump + modulating HP dissipation 4 Not available if Field 2 = 0,A

HP utility pump + LP dissipation 5

HP utility pump + modulating LP dissipation 6 Not available if Field 2 = 0,A

HP utility pump + HP dissipation 7

HP utility pump + modulating HP dissipation 8 Not available if Field 2 = 0,A

List of accessories Shunt condensers A

Soft-starter kit B

Service kit (probe kit for quick diagnostics) C Not available if Field 2 = 0,A

Clock board D Not available if Field 2 = 0,A

ON-OFF status of compressors E

Remote contact for (step-based= power limitation F Not available if Field 2 = 0,A

Configurable digital alarms board G Not available if Field 2 = 0,A

Pressure gauges H Not available if Field 2 = 0,A

G - Four Vic-Taulic joints for quick water IN-OUT connection I

Filter cut-off kit (solenoid and cock on liquid line) L

Outdoor temperature sensor for set-point compensation M Not available if Field 2 = 0,A

Dissipation side water temp. probe for Version = "H" or "W" N Not available if Field 10 = 1.2

  

1.1.3 Field of application LEW units are designed for cooling‐heating water and solutions containing up to 30% glycol (percentage by weight)  in civil,  industrial  and  technological  air‐conditioning  systems.  The  units  cannot  operate  outdoors,  as  the  metalwork provides an IP43 insulation. Please contact the technical office for these applications.  

LEW series units must be used within the operating limits shown in this document or the warranty required by the sales contract will be voided.

 LEW multifunction machines have 4 water connections associated with two different water circuits for 2‐pipe systems: Circuit 1, production of cold or hot water for utility; Circuit 2, production of hot or cold water for dissipation in opposition to the utility;  Accordingly, the multifunction units have 2 heat exchangers: Plate heat exchanger 1 with both evaporation and condensation function, intended for the utility circuit; Plate heat exchanger 2 with both evaporation and condensation function, intended for the dissipation circuit;      Cooling LEW machine: view of the water connections and of the thermodynamic circuit For the correct direction of the connections, always refer to the dimensional drawing attached with the documentation.   

Page 8: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 8 of 56 RG66006951‐Rev.01 

 

           LEW  C machines  are  designed  for  cold‐only  production:  in  the utility  circuit  only  the  production  of  chilled water  is envisaged. The  LEW H machines are  reversible heat pumps:  in  the utility  circuit hot water and  chilled water  can be produced alternatively.  The following points briefly illustrate the operating functions of the LEW C, D, H, W units:  Chilling LEW C, D, H units in “Chiller” mode cool the water to cool down the environment on the utility side, thereby dissipating condensation heat with the water cooled by the dissipation heat exchanger.  

 Heating LEW H, W units in “Heat Pump” mode heat the water in the condenser to heat the utility side, thereby dissipating the evaporation cooling capacity by means of the water which is heated in the dissipation heat exchanger. In other words, a certain amount of heat  is drawn  from a  thermal  source and  is  then  transferred  to  the utility after  it has  reached a sufficient thermal level that is suitable for its needs. 

 

DISSIPATION

UTILITY

Page 9: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 9 of 56 RG66006951‐Rev.01 

 

Air‐conditioning applications often need to be able to dispose of heat to heat up domestic hot water or for post‐heating control  in air treatment  facilities where an autonomous Temperature and humidity control will be  implemented. The heat required can be drawn from the condensing section of the thermodynamic unit, which is at a higher temperature. If  only  part  of  the  heat  is  drawn,  a  de‐superheater  sends  gas‐sensitive  heat  to  the delivery  pipe  towards  the  third thermal source at a higher temperature.  

  Upon  specific demand, all  cold‐only units of  the  LEW  series  can be equipped with a de‐superheater  for partial heat recovery. The available  thermal output  that can be used  for domestic hot water,  for example, depends on  the unit's operating conditions.  

         Layout of partial heat recovery circuit  

         

Page 10: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 10 of 56 RG66006951‐Rev.01 

 

 

1.1.4 Product innovation LEW units provide excellent  thermodynamic performance and maximum  flexibility of use  thanks  to constant product research.  The  joint  application of  scroll  compressors,  advanced  control  systems  and R410A  refrigerant  gas  achieves compact circuits and high COPs. The possibility of keeping the evaporator on the  inside allows you not to add glycol to the water  in the system, with clear  advantages  in  terms  of  thermodynamic  performance,  preservation  from  corrosion  and  respect  for  the environment.  It  also makes  it  possible  for  all  the  components  requiring maintenance  to  be  installed  in  an  easily accessible space. Chiller units can be applied even when no dissipation source other  than air  is available: a water Dry‐Cooler provides thermal exchange with the atmosphere while maintaining a compact‐sized circuit. For large buildings, air‐conditioning can be implemented as the floors/zones are sold or rented by installing a LEW unit for each  floor  in a small size technical room, thus spreading the  investment over time. The overall dimensions of the units (less than 90 cm depth in the higher output sizes) make them easy to be installed since they fit through any door.   The main innovations which this product presents are summarised in the following list:  Option of using water without glycol in the utility circuit Heat pump mode with chiller side cycle inversion Option of even heat pump versions using condensation control  Electronically controlled electric expansion valve High COP (Coefficient of performance) of thermodynamic cycle Reduced refrigerant load  Option of applying chiller mode even when air is used as dissipation source It occupies less space on the floor‐plan (specific powers up to 153 kW/m2) Innovative aesthetic features and full safety since units are completely closed No noise on the outside, less noise on the inside due to dual‐soundproofing in low‐noise versions. 

1.2 Structure All LEW series units have the load bearing base and panelling in galvanised sheet metal painted with polyester powders and  polymerised  in  the  oven  at  180°C.  The  unit  has  an  attractive  design  and when  closed  all  the  components  are inaccessible.  This,  along with  the  extensive  use  of  soundproofing material  inside  the  compartment  and  around  the compressors (available for the low‐noise version), reduces sound to exceptionally low levels (Lp < 67 dB‐A @1 metre for bigger sizes).  The  hydraulic/chiller  connections  are  envisioned  on  the  right  side, when  looking  at  the  electrical  control  board,  to reduce the technical space required for installation. All the panels are removable (except for the one on the right, upon which all the hydraulic connections are fitted) making the unit fully accessible even though routine maintenance only needs accessing from the front. 

1.3 Cooling circuit The  cooling  circuit  is manufactured  in our  factory, with  top brand  components  and operators  trained,  according  to Directive 97/23, on all the brazing operations.   The range can be configured  in the cooling circuit mode (Efficiency Pack) which, depending on the size, can be a dual compressor on a double circuit (Efficiency Pack 1) for a highly redundant system, dual compressor (tandem) on single circuit (Efficiency Pack 2) for greater efficiency in partial loads, three compressors (trio) on single circuit (Efficiency Pack 3) combining economical implementation and partial load efficiency and four compressors (two tandems) on a double circuit (Efficiency Pack 4) for a system which is both redundant and efficient with the reduced load.            

Page 11: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 11 of 56 RG66006951‐Rev.01 

 

Table II – List and graphical representation of the layout of the components in four Efficiency Packs:  

         

Efficiency Pack ONE:Efficiency Pack ONE:

Efficiency Pack TWO:Efficiency Pack TWO:

Efficiency Pack THREE:Efficiency Pack THREE:

Efficiency Pack FOUR:Efficiency Pack FOUR:Efficiency Pack FOUR:

   Solutions with more than one circuit provide the utmost reliability thanks to redundancy, while those with more than one compressor on a circuit provide partial loads with ideal efficiency, also thanks to increased heat exchange surfaces. 

1.3.1 Compressors Only top international brand Scroll compressors are used on LEW units. Scroll compressors, up to a power output of 182 kW for single circuit, are the best solution in terms of reliability and efficiency. They also provide the lowest amount of sound  emissions.  Process  optimisation,  along with  a  carefully  selected  intrinsic  volumetric  compression  ratio  (RVI), clearly  improves  the  isentropic compression performance and  reduces energy  losses. The use of a  scroll compressor allows  low  viscosity  oils  to  be  used.  This,  in  comparison  to  higher  viscosity  oils,  reduces  thermal  resistance  at  the evaporator.  It  also  increases  the  evaporation  temperature  by more  than  1.5°C  (EER  increases  by more  than  5.5%) compared to other solutions. Compressor  motors  are  protected  against  overheating,  overloads  and  high  delivery  gas  temperatures.  They  are mounted on rubber anti‐vibration mounts, complete with oil charge and  inserted  in a soundproof compartment with sound‐absorbing  material.  Also  complete  with  automatic  oil  heater  to  prevent  the  oil  from  being  diluted  by  the refrigerant when the compressor stops.  

  NOTE:  Scroll  compressors,  like  all  air‐tight  compressors,  are  classified  as  pressurised  containers.  The  low  pressure section, referred to by the PS on the data plate, complies with PED CE 97/23. 

1.3.2 Heat exchangers Only brazed plate heat exchangers are used, made of austenitic  stainless  steel AISI 316, with AISI 316L connections. These feature a reduced carbon content that favours brazing operations. The brazed plate heat exchanger represents the  state‐of‐the‐art  in  terms  of  thermal  exchange  efficiency  and  allows  a  strong  reduction  of  the  refrigerant  load compared to standard solutions. The high level of turbulence generated by internal plate corrugation, along with plate smoothness, makes  it difficult for dirt to accumulate or for  limescale to build up on the condenser circuit. These heat exchangers also make  it possible  to use R410A  fluid which,  thanks  to  the high‐level  thermal conductivity of  its  liquid phase and to its azeotropic behaviour, enhances thermal exchange during evaporation. The performances are improved over other methane‐derivative fluids of the HFC group.  

Page 12: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 12 of 56 RG66006951‐Rev.01 

 

  NOTE: due  to thermal  insulation  the data plate  (in compliance with PED CE 97/23)  is not  legible. However,  the serial number  of  the  heat  exchanger  and  the  declaration  of  conformity  are  both  recorded  during  production  and  are  an integral part of Hiref's archive.  

1.3.3 De-superheater for partial heat recovery (optional) The option of partial heat recovery  is  implemented with a braze‐welded plate heat exchanger placed  in series on the finned pack condenser and its size limits pressure drops on the refrigerant side to a minimum.  All machines configured with heat recovery use as per standard modulating condensation control. To prevent a lack of balance  in  the  cooling  circuit,  if  the water  temperature  is  too  low when  the  recovery  starts,  the hydraulic  recovery circuit is implemented as indicated in the following figure: a low water temperature at recovery would cause a drop in the condensation temperature and therefore an insufficient pressure jump on the expansion valve with the ensuing risk of the safety devices being triggered. 

                   The bulb of  the  3‐way mixer  valve  is placed  at  the de‐superheater  exchanger  inlet, which by mixing  the hot water produced with colder water from the tank allows you to  limit the time needed for the system to reach full operating capacity to a  few moments. A buffer tank must be placed between the unit and the utility since the demand  for hot water and its availability are not simultaneous, because it needs the compressors to be running. It should be pointed out that the heat recovery output is linked to the dispensed cooling output and that, therefore, in partial load situations it is also reduced just the same; this aspect must be taken into consideration for the dimensions of  the buffer  tank.  The partial heat  recovery option  is  supplied only with  the de‐superheater  exchanger.  The other components of the circuit laid out in the previous figure are not included in the supply.  

1.3.4 Utility and dissipation side cycle inversion valves (optional) When LEW H reversible chillers switch from chiller to heat pump, and vice versa, they perform two cycle inversions: one on the coolant circuit and one on the water circuit. The inversion valve of the water‐side cycle switches from position A to position B and vice versa by means of an electrical driver without changing  the direction of  travel  for  the outside utilities. This allows you  to  invert  the direction of  the  flow  in  the heat exchangers, keeping  them against  the  flow  in relation to the refrigerant fluid in every operating mode. The water‐side cycle inversion valve is an optional component.   

TANK 

DIVERTER RECIRCULATION PUMP  H

EAT 

Page 13: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 13 of 56 RG66006951‐Rev.01 

 

  

      Refrigerant side cycle inversion valve       Heat‐transfer fluid side cycle inversion valve  

        

1.3.5 Electronically controlled electric expansion valve The electronically controlled valve with external equalisation and built‐in MOP function is managed by the software and therefore makes cooling circuit operation very efficient, stabilising and decreasing the power absorbed by the system when a sudden thermal load variation occurs. The shutter in the central part of the valve can always slide vertically with an ample stroke allowing variation of the degree of opening of the orifice of the fluid passage. Using this valve reduces compressor  energy  consumption  when  the  surrounding  conditions  bring  the  pressure  difference  between  the evaporator and the air conditioner below 5 bar, thus improving performance.  

Page 14: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 14 of 56 RG66006951‐Rev.01 

 

 

1.3.6 Other cooling components ‐ Molecular sieve filter dryer ‐ Sight glass with humidity indicator ‐ One‐way valves (only reversible heat pump) ‐ Liquid receiver marked in compliance with EC Directive 97/23 PED (only reversible heat pumps or units with remote 

condenser) ‐ High and low pressure switches Schrader valves for control and/or maintenance 

Page 15: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 15 of 56 RG66006951‐Rev.01 

 

  Diagram of the dual‐circuit cold‐only version (please note: this is a standard layout, refer to the layout enclosed with the unit). To consult the layouts, please refer to the symbols in the following table.   

  

Page 16: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 16 of 56 RG66006951‐Rev.01 

 

 Diagram of  the dual‐circuit  reversible heat pump  version  (please note:  this  is  a  standard  layout,  refer  to  the  layout enclosed with the unit).   

    

Page 17: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 17 of 56 RG66006951‐Rev.01 

 

 Reference table for numbering used in layouts  

   

Page 18: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 18 of 56 RG66006951‐Rev.01 

 

 

1.4 Electric panel The electric panel  is built and wired  in accordance with standard EN 60204‐1. The electric panel  is accessed from the front of the machine. Before it can be accessed, the unit must be disconnected from the power supply using the main switch, which  functions  as  a  door‐lock. All  the  remote  controls  are  implemented with  low  voltage  signals  at  24  V, powered by an isolation transformer positioned inside the control board. All the control boards have an air circulation system with auxiliary fans.   The position of the main switch makes wiring operations in the work site easier. This avoids several difficult operations as well as having to twist the power cords. All the utilities are protected against surges and short  circuits. The  circuit breaker  set‐up  can be  configured  for  any  load  (optional). Thermal protection, however,  is carried out by thermistor chains. These are set  in the windings of each electric motor and are controlled by onboard electronics.   All machines are standard‐equipped with a phase sequence relay which  inhibits compressor operation  if the phase sequence is not carried out: only one direction of rotation is possible for scroll compressors, as well as for the screw  and Rotary  compressors.   The unit  is  rated  IP43 which makes  it  suitable  for outdoor  installation. The  control board with the open panel maintains an  IP20 rating.  Inside the electrical control board of the Basic control there are two manual selectors to enable remote switching on‐off, seasonal changeover (only heat pumps) and to select local or remote control: remote consents are implemented by very low voltage contacts placed on the terminal board. 

1.4.1 Control microprocessor LEW series units have two different microprocessor control levels: ‐ Basic – Carel µChiller ‐ Advanced – Carel series pCO  The latter, in addition to the functions described below, can customise the software to meet all system requests. These include cascade management of the units with step‐control or cascade logic. The microprocessor on board the unit controls the various operating parameters with an electric panel keypad; 

‐ Compressor connection/disconnection to maintain the set‐point of the chiller inlet water T; ‐ Alarm management: High / low pressure;  Antifreeze / Flow switch;  Pump alarm ‐ Alarm signals ‐ Display of operating parameters ‐ Evaporator anti‐freeze protection ‐ Control of maximum number of compressor starts ‐ RS232, RS485 serial output control (optional) ‐ Incorrect phase sequence (not viewed on display, prevents the compressor from starting) 

 As for remote communication, the controls can be connected to advanced BMS systems. The HSD (HiRef Software Department) structure is capable of assisting customers in integration operations. System interconnectivity capabilities are summarised below: ‐ Available serial ports 

‐ RS232 ‐ RS485 ‐ Ethernet (“HiWeb” board) 

‐ GSM Modem:  with prepaid card and relative antenna on board the machine for autonomous two‐way control of alarms and/or set‐point variations 

‐ Protocols ‐ Carel     [Built‐In] ‐ Modbus® [Built In with Advanced controls] ‐ Modbus® [With external gateway with Basic controls] ‐ LonWorks® [Dedicated serial board to be requested when ordering the machine] ‐ BACnet™ [With external gateway] ‐ TCP‐IP  [With external gateway] ‐ TREND® [Dedicated serial board to be requested when ordering the machine] 

 (ref. Microprocessor control manual for further details)  

Page 19: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 19 of 56 RG66006951‐Rev.01 

 

 

2 Main units technical data 

 The following chapter provides the technical data for the LEW unit. Performance values are accurately reported and can be interpolated to know specific operating conditions.   Table I – Technical data of LEW chillers in standard operating conditions  

RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7°C; 15/30°C 

 Efficiency pack  1  2  1  2  1  2  1  2  1  2 

LEW CS / CL     41  42  51  52  61  62  71  72  81  82 Cooling capacity  kW  51.9  51.1  60.2  60.1  69.1  69.2  77.9  77.9  89.1  89.1 

Rated absorbed power  kW  9.3  8.7  11.2  11.2  12.4  12.4  14.3  14.3  15.9  15.9 

Evaporator‐side pressure drops  kPa  38  37  51  51  40  40  50  50  39  39 

Evaporator‐side flow rate  l/h  8933  8791  10360 10344 11888 11897 13406  15326  15330  15326 

Condenser pressure drops  kPa  7  7  9  9  12  12  15  15  18  18 

Condenser‐side flow rate  l/h  3483  3402  4062  4057  4637  4639  5246  5972  5974  5972 

Electrical power supply  V/ph/Hz  400 ‐ 3N ‐ 50Hz 

Scroll compressors / cooling circuits  No.  2/2  2/1  2/2  2/1  2/2  2/1  2/2  2/1  2/2  2/1 

Victaulic hydraulic connections  inches  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2 

Height  mm  1594  1594  1594  1594  1594  1594  1594  1594  1594  1594 

Length  mm  1174  1174  1174  1174  1174  1174  1174  1174  1174  1174 

Depth  mm  772  772  772  772  772  772  772  772  772  772 

Maximum current (FLA)  A  30.0  30.0  37.0  37.0  40.0  40.0  46.0  46.0  50.0  50.0 

Booster current (LRA)  A  111.0  111.0  156.0  156.0  157.0  157.0  164.0  164.0  176.0  176.0 

LRA with soft‐starter kit  A  73.0  73.0  83.0  83.0  102.0  102.0  107.0  107.0  117.0  117.0 

EER     5.75  6.05  5.46  5.45  5.72  5.73  5.54  5.54  5.76  5.76 

Refrigerant load   kg  6  5  6  5  6  6  7  7  7  7 

 

RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7°C; 15/30°C 

 Efficiency pack  1  2  1  2  1  2  1  2  4 

LEW CS / CL     91  92  111  112  131  132  141  142  144 

Cooling capacity  kW  99.3  99.3  118.9  118.9  135.6  135.5  157.2  157.3  156.9 

Rated absorbed power  kW  18.0  18.0  21.3  21.3  24.6  24.6  27.9  27.9  28.8 

Evaporator‐side pressure drops  kPa  48  48  39  39  50  50  47  47  47 

Evaporator‐side flow rate  l/h  17075 17077 20448 20454 23326 23309  27039  27061  26983

Condenser pressure drops  kPa  22  22  30  30  38  38  19  19  19 

Condenser‐side flow rate  l/h  6674  6675  7978  7980  9118  9112  10532  10538  10563

Electrical power supply  V/ph/Hz 400 ‐ 3N ‐ 50Hz 

Scroll compressors / cooling circuits  No.  2  /  2  2  /  1  2  /  2  2  /  1  2  /  2  2  /  1  2  /  2  2  /  1  4  /  2 

Victaulic hydraulic connections  inches  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2 

Height  mm  1594  1594  1594  1594  1594  1594  1594  1594  1854 

Length  mm  1174  1174  1674  1674  1674  1674  1674  1674  2374 

Depth  mm  772  772  772  772  772  772  772  772  772 

Maximum current (FLA)  A  61.0  61.0  70.0  71.0  79.0  79.0  91.0  91.0  92.0 

Booster current (LRA)  A  203.0  203.0  238.0  275.0  244.0  244.0  289.0  289.0  197.0 

LRA with soft‐starter kit  A  137.0  137.0  176.0  210.0  182.0  182.0  224.0  224.0  140.0 

EER     5.60  5.60  5.71  5.71  5.58  5.58  5.73  5.74  5.54 

Refrigerant load   kg  8  8  12  12  13  12  15  13  15 

 

Page 20: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 20 of 56 RG66006951‐Rev.01 

 

  

RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7°C; 15/30°C 

 Efficiency pack  1  2  4  1  2  3  4  4 

LEW CS / CL     161  162  164  181  182  184  204  214 

Cooling capacity  kW  174.9  175.1  176.2  204.5  204.8  198.9  219.1  235.1 

Rated absorbed power  kW  32.1  32.1  31.9  37.9  37.9  36.4  39.3  42.7 

Evaporator‐side pressure drops  kPa  51  51  52  54  54  51  51  57 

Evaporator‐side flow rate  l/h  30076 30113 30302 35180 35218 34211  37680  40444

Condenser pressure drops  kPa  23  23  23  30  31  29  28  33 

Condenser‐side flow rate  l/h  11771 11783 11838 13788 13803 13386  14703  15805

Electrical power supply  V/ph/Hz 400 ‐ 3N ‐ 50Hz 

Scroll compressors / cooling circuits  No.  2  /  2  2  /  1  4  /  2  2  /  2  2  /  1  4  /  2  4  /  2  4  /  2 

Victaulic hydraulic connections  inches  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2 

Height  mm  1594  1594  1854  1594  1594  1854  1854  1854 

Length  mm  1674  1674  2374  1674  1674  2374  2374  2374 

Depth  mm  772  772  772  772  772  877  877  877 

Maximum current (FLA)  A  102.0  102.0  100.0  116.0  116.0  122.0  132.0  142.0 

Booster current (LRA)  A  298.0  298.0  211.0  361.0  361.0  250.0  321.0  328.0 

LRA with soft‐starter kit  A  233.0  233.0  152.0  278.0  278.0  184.0  256.0  263.0 

EER     5.53  5.54  5.59  5.46  5.47  5.54  5.64  5.55 

Refrigerant load   kg  15  15  15  16  15  22  22  22 

 

RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7°C; 15/30°C 

 Efficiency pack  3  4  3  4  4  4  4  4  4 

LEW CS / CL     243  244  283  284  314  344  374  424  484 

Cooling capacity  kW  267.9  279.0  313.0  316.4  349.7  377.4  410.6  453.5  520.7 

Rated absorbed power  kW  47.8  47.9  56.4  56.3  64.7  70.4  74.5  81.6  92.5 

Evaporator‐side pressure drops  kPa  51  55  40  41  49  56  54  56  53 

Evaporator‐side flow rate  l/h  46080 47979 53828 54419 60144 64905  70623  78003  89412

Condenser pressure drops  kPa  21  23  28  28  35  36  33  33  39 

Condenser‐side flow rate  l/h  17961 18601 21017 21207 23571 25469  27652  30446  35016

Electrical power supply  V/ph/Hz 400 ‐ 3N ‐ 50Hz 

Scroll compressors / cooling circuits  No.  3  /  1  4  /  2  3  /  1  4  /  2  4  /  2  4  /  2  4  /  2  4  /  2  4 / 2 

Victaulic hydraulic connections  inches  2 1/2  2 1/2  3  3  3  3  3  3  3 

Height  mm  1854  1854  1854  1854  1854  1854  1854  1854  1854 

Length  mm  2374  2374  2374  2374  2374  2374  2374  2374  2374 

Depth  mm  877 877 877 877 877 877  877  877  877

Maximum current (FLA)  A  153.0  159.0  174.0  182.0  204.0  218.0  232.0  281.0  302.0 

Booster current (LRA)  A  336.0  301.0  401.0  355.0  374.0  437.0  442.0  490.0  525.0 

LRA with soft‐starter kit  A  271.0  239.0  318.0  290.0  309.0  354.0  359.0  420.0  454.0 

EER     5.68  5.86  5.68  5.75  5.49  5.41  5.57  5.60  5.63 

Refrigerant load   kg  21  30  28  35  35  35  40  40  40 

          

Page 21: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 21 of 56 RG66006951‐Rev.01 

 

   

RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7°C; 40/45°C 30% glyc. 

 Efficiency pack  1  2  1  2  1  2  1  2  1  2 

LEW DS / DL     41  42  51  52  61  62  71  72  81  82 Cooling capacity  kW  43.06  43.06  50.6  50.6  57.9  57.8  65.7  65.8  75.5  75.5 

Rated absorbed power  kW  12.8  12.8  15.2  15.2  16.8  16.8  19.5  19.5  21.5  21.5 

Evaporator‐side pressure drops  kPa  27  27  37  37  30  30  37  37  29  29 

Evaporator‐side flow rate  l/h  7407  7311  8700  8702  9953  9946  11306  11316  12982  12970 

Condenser pressure drops  kPa  51  51  71  71  55  55  71  71  53  53 

Condenser‐side flow rate  l/h  10871 10650 12807 12811 14541 14534 16582  16595  18877  18865 

Electrical power supply  V/ph/Hz  400 ‐ 3N ‐ 50Hz 

Scroll compressors / cooling circuits  No.  2  /  2  2  /  1  2  /  2  2  /  1  2  /  2  2  /  1  2  /  2  2  /  1  2  /  2  2  /  1 

Victaulic hydraulic connections  inches  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2 

Height  mm  1594  1594  1594  1594  1594  1594  1594  1594  1594  1594 

Length  mm  1174  1174  1174  1174  1174  1174  1174  1174  1174  1174 

Depth  mm  772  772  772  772  772  772  772  772  772  772 

Maximum current (FLA)  A  30.0  30.0  37.0  37.0  40.0  40.0  46.0  46.0  50.0  50.0 

Booster current (LRA)  A  111.0  111.0  156.0  156.0  157.0  157.0  164.0  164.0  176.0  176.0 

LRA with soft‐starter kit  A  73.0  73.0  83.0  83.0  102.0  102.0  107.0  107.0  117.0  117.0 

EER     3.36  3.36  3.33  3.33  3.45  3.44  3.37  3.37  3.51  3.51 

ESEER     5.61  6.04  5.39  5.78  5.73  6.11  5.59  6.01  5.89  6.25 

Refrigerant load   kg  4  4  4  5  5  5  5  6  7  7 

  

RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7°C; 40/45°C 30% glyc. 

 Efficiency pack  1  2  1  2  1  2  1  2  4 

LEW DS / DL     91  92  111  112  131  132  141  142  144 

Cooling capacity  kW  83.7  83.8  101.5  101.4  115.3  115.5  132.8  132.9  133.5 

Rated absorbed power  kW  24.6  24.6  28.7  28.7  33.4  33.4  38.1  38.1  38.7 

Evaporator‐side pressure drops  kPa  35  35  30  30  37  37  35  35  35 

Evaporator‐side flow rate  l/h  14400 14421 17451 17448 19833 19864  22848  22867  22957

Condenser pressure drops  kPa  67  67  55  55  71  71  65  65  67 

Condenser‐side flow rate  l/h  21078 21098 25347 25338 28945 28973  33277  33292  33520

Electrical power supply  V/ph/Hz 400 ‐ 3N ‐ 50Hz 

Scroll compressors / cooling circuits  No.  2  /  2  2  /  1  2  /  2  2  /  1  2  /  2  2  /  1  2  /  2  2  /  1  4  /  2 

Victaulic hydraulic connections  inches  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2 

Height  mm  1594  1594  1594  1594  1594  1594  1594  1594  1854 

Length  mm  1174  1174  1674  1674  1674  1674  1674  1674  2374 

Depth  mm  772  772  772  772  772  772  772  772  772 

Maximum current (FLA)  A  61.0  61.0  70.0  71.0  79.0  79.0  91.0  91.0  92.0 

Booster current (LRA)  A  203.0  203.0  238.0  275.0  244.0  244.0  289.0  289.0  197.0 

LRA with soft‐starter kit  A  137.0  137.0  176.0  210.0  182.0  182.0  224.0  224.0  140.0 

EER     3.40  3.41  3.54  3.53  3.45  3.46  3.49  3.49  3.45 

ESEER     5.81  6.25  6.05  6.48  6.00  6.43  5.90  6.17  6.09 

Refrigerant load   kg  7  7  13  12  13  12  15  13  15 

 

Page 22: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 22 of 56 RG66006951‐Rev.01 

 

 

RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7°C; 40/45°C 30% glyc. 

 Efficiency pack  1  2  4  1  2  3  4  4 

LEW DS / DL     161  162  164  181  182  184  204  214 

Cooling capacity  kW  149.4  149.5  150  175  174.9  169.6  187  201.2 

Rated absorbed power  kW  42.6  42.6  75.1  50  50  48.6  52.7  57.3 

Evaporator‐side pressure drops  kPa  38  38  38  40  40  38  38  43 

Evaporator‐side flow rate  l/h  25700 25712 25806 30104 30078 29178  32165  34601

Condenser pressure drops  kPa  57  57  59  64  64  60  60  70 

Condenser‐side flow rate  l/h  37388 37403 37539 43812 43775 42476  46666  50309

Electrical power supply  V/ph/Hz 400 ‐ 3N ‐ 50Hz 

Scroll compressors / cooling circuits  No.  2  /  2  2  /  1  4  /  2  2  /  2  2  /  1  4  /  2  4  /  2  4  /  2 

Victaulic hydraulic connections  inches  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2 

Height  mm  1594  1594  1854  1594  1594  1854  1854  1854 

Length  mm  1674  1674  2374  1674  1674  2374  2374  2374 

Depth  mm  772  772  772  772  772  877  877  877 

Maximum current (FLA)  A  102.0  102.0  100.0  116.0  116.0  122.0  132.0  142.0 

Booster current (LRA)  A  298.0  298.0  211.0  361.0  361.0  250.0  321.0  328.0 

LRA with soft‐starter kit  A  233.0  233.0  152.0  278.0  278.0  184.0  256.0  263.0 

EER     3.51  3.51  2.00  3.50  3.50  3.49  3.55  3.51 

ESEER     5.80  6.17  6.24  5.84  6.29  6.33  6.46  6.44 

Refrigerant load   kg  15  13  15  16  15  22  24  27 

  

RATED TECHNICAL DATA OF LEW WATER CHILLERS@ 12/7°C; 40/45°C 30% glyc. 

 Efficiency pack  3  4  3  4  4  4  4  4  4 

LEW DS / DL     243  244  283  284  314  344  374  424  484 

Cooling capacity  kW  231.8  240.2  266.2  269.4  298.3  321.4  349.1  386.7  442.05 

Rated absorbed power  kW  63.6  65.6  75.2  75.9  86.3  93.3  100.4  109.2  126.57 

Evaporator‐side pressure drops  kPa  23  24  29  31  37  42  40  42  39 

Evaporator‐side flow rate  l/h  39864 41306 45790 46344 51312 55284  60038  66514  75914 

Condenser pressure drops  kPa  42  45  55  56  70  66  65  63  72 

Condenser‐side flow rate  l/h  57517 59548 66463 67235 74861 80719  87499  96550  105646

Electrical power supply  V/ph/Hz 400 ‐ 3N ‐ 50Hz 

Scroll compressors / cooling circuits  No.  3  /  1  4  /  2  3  /  1  4  /  2  4  /  2  4  /  2  4  /  2  4  /  2  4 / 2 

Victaulic hydraulic connections  inches  2 1/2  2 1/2  3  3  3  3  3  3  3 

Height  mm  1854  1854  1854  1854  1854  1854  1854  1854  1854 

Length  mm  2374  2374  2374  2374  2374  2374  2374  2374  2374 

Depth  mm  877 877 877 877 877 877  877  877  877

Maximum current (FLA)  A  153.0  159.0  174.0  182.0  204.0  218.0  232.0  281.0  302.0 

Booster current (LRA)  A  336.0  301.0  401.0  355.0  374.0  437.0  442.0  490.0  525.0 

LRA with soft‐starter kit  A  271.0  239.0  318.0  290.0  309.0  354.0  359.0  420.0  454.0 

EER     3.64  3.66  3.54  3.55  3.46  3.44  3.48  3.54  3.22 

ESEER     6.37  6.62  6.34  6.21  6.15  6.13  6.20  6.45  6.56 

Refrigerant load   kg  28  30  28  31  31  31  31  31  31 

 

Page 23: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 23 of 56 RG66006951‐Rev.01 

 

  Table II – Technical data of LEW heat pumps in standard operating conditions  

RATED TECHNICAL DATA OF LEW HEAT PUMPS @ 15/10°C; 40/45°C 

 Efficiency pack  1  2  1  2  1  2  1  2  1  2 

LEW HS / HL – LEW WS / WL     41  42  51  52  61  62  71  72  81  82 Cooling capacity  kW  43.31  42.7  50.85  50.86  58.19  58.13  66.09  66.14  75.74  75.81 

Utility side pressure drops  kPa  26  25  36  36  36  36  35  35  27  27 

Heat sink pressure drops  kPa  39  38  55  55  41  41  54  54  41  41 

Heating capacity  kW  60.17  59  70.91  70.9  80.5  80.52  91.69  91.72  104.38  104.38 

Rated absorbed power  kW  12.8  12.13  15.29  15.3  16.85  16.85  19.46  19.47  21.42  21.43 

Evaporator‐side pressure drops  kPa  47  45  65  65  49  49  64  64  49  49 

Evaporator‐side flow rate  l/h  10350 10148 12196 12194 13846 13850 15770  15775  17953  17953 

Condenser pressure drops  kPa  32  31  44  44  44  44  43  43  33  33 

Condenser‐side flow rate  l/h  8258  8166  9698  9695  11093 11096 12591  12594  14454  14451 

Electrical power supply  V/ph/Hz  400 ‐ 3N ‐ 50Hz 

Scroll compressors / cooling circuits  No.  2/2  2/1  2/2  2/1  2/2  2/1  2/2  2/1  2/2  2/1 

Victaulic hydraulic connections  inches  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2 

Height  mm  1594  1594  1594  1594  1594  1594  1594  1594  1594  1594 

Length  mm  1174  1174  1174  1174  1174  1174  1174  1174  1174  1174 

Depth  mm  772  772  772  772  772  772  772  772  772  772 

Maximum current (FLA)  A  30.0  30.0  37.0  37.0  40.0  40.0  46.0  46.0  50.0  50.0 

Booster current (LRA)  A  111.0  111.0  156.0  156.0  157.0  157.0  164.0  164.0  176.0  176.0 

LRA with soft‐starter kit  A  73.0  73.0  83.0  83.0  102.0  102.0  107.0  107.0  117.0  117.0 

COP     4.79  4.93  4.63  4.63  4.76  4.76  4.71  4.71  4.94  4.93 

ESEER     5.61  6.04  5.39  5.78  5.73  6.11  5.59  6.01  5.89  6.25 

H version refrigerant load   kg  8  6  8  7  8  7  9  8  10  9 

W version refrigerant charge  kg  5  4  5  4  5  4  7  6  7  6 

  

RATED TECHNICAL DATA OF LEW HEAT PUMPS @ 15/10°C; 40/45°C 

 Efficiency pack  1  2  1  2  1  2  1  2  4 

LEW HS / HL – LEW WS / WL     91  92  111  112  131  132  141  142  144 

Cooling capacity  kW  84.19  84.3  102.02 101.96 116.12 116.09  133.77  133.65  134.19

Utility side pressure drops  kPa  34  34  30  30  36  36  34  34  34 

Heat sink pressure drops  kPa  51  51  42  42  54  54  50  50  51 

Heating capacity  kW  116.87 116.89 140.29 140.31 160.24 160.28  184.3  184.18  185.49

Rated absorbed power  kW  24.42  24.4  28.56  28.55  33.19  33.16  37.89  37.87  38.71 

Evaporator‐side pressure drops  kPa  61  61  50  50  64  64  60  59  61 

Evaporator‐side flow rate  l/h  20102  20105  24129  24134  27561  27568  31699  31679  31904 

Condenser pressure drops  kPa  42  42  36  37  44  44  42  42  42 

Condenser‐side flow rate  l/h  16112  16118  19463  19469  22138  22150  25507  25491  25579 

Electrical power supply  V/ph/Hz 400 ‐ 3N ‐ 50Hz 

Scroll compressors / cooling circuits  No.  2  /  2  2  /  1  2  /  2  2  /  1  2  /  2  2  /  1  2  /  2  2  /  1  4  /  2 

Victaulic hydraulic connections  inches  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2 

Height  mm  1594  1594  1594  1594  1594  1594  1594  1594  1854 

Length  mm  1174  1174  1674  1674  1674  1674  1674  1674  2374 

Depth  mm  772  772  772  772  772  772  772  772  772 

Maximum current (FLA)  A  61.0  61.0  70.0  71.0  79.0  79.0  91.0  91.0  92.0 

Booster current (LRA)  A  203.0  203.0  238.0  275.0  244.0  244.0  289.0  289.0  197.0 

LRA with soft‐starter kit  A  137.0  137.0  176.0  210.0  182.0  182.0  224.0  224.0  140.0 

COP     4.79  4.79  4.95  4.95  4.81  4.82  4.86  4.86  4.79 

ESEER     5.81  6.25  6.05  6.48  6.00  6.43  5.90  6.17  6.09 

H version refrigerant charge   kg  13  12  22  21  22  21  22  21  41 

W version refrigerant charge  kg  7  6  10  9  12  10  12  12  24 

   

Page 24: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 24 of 56 RG66006951‐Rev.01 

 

  

RATED TECHNICAL DATA OF LEW HEAT PUMPS @ 15/10°C; 40/45°C 

 Efficiency pack  1  2  4  1  2  3  4  4 

LEW HS / HL – LEW WS / WL     161  162  164  181  182  184  204  214 

Cooling capacity  kW  149.21 149.37 149.82 177.59 177.67  172.56  187.01  204.32

Utility side pressure drops  kPa  38  38  38  33  33  32  37  35 

Heat sink pressure drops  kPa  56  56  57  49  49  47  56  53 

Heating capacity  kW  206.27 206.31 207.12 244.39 244.28  237.95  257.95  281.31

Rated absorbed power  kW  42.83  42.82  43.08  49.94  49.95  48.24  52.89  57 

Evaporator‐side pressure drops  kPa  66  66  67  58  58  56  66  63 

Evaporator‐side flow rate  l/h  35479  35485  35624  42035  42016  40928  44368  48385 

Condenser pressure drops  kPa  46  46  46  41  41  40  45  43 

Condenser‐side flow rate  l/h  28481  28488  28584  33875  33855  33046  35727  39071 

Electrical power supply  V/ph/Hz 400 ‐ 3N ‐ 50Hz 

Scroll compressors / cooling circuits  No.  2  /  2  2  /  1  4  /  2  2  /  2  2  /  1  4  /  2  4  /  2  4  /  2 

Victaulic hydraulic connections  inches  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2  2 1/2 

Height  mm  1594  1594  1854  1594  1594  1854  1854  1854 

Length  mm  1674  1674  2374  1674  1674  2374  2374  2374 

Depth  mm  772  772  772  772  772  877  877  877 

Maximum current (FLA)  A  102.0  102.0  100.0  116.0  116.0  122.0  132.0  142.0 

Booster current (LRA)  A  298.0  298.0  211.0  361.0  361.0  250.0  321.0  328.0 

LRA with soft‐starter kit  A  233.0  233.0  152.0  278.0  278.0  184.0  256.0  263.0 

COP     4.78  4.79  4.78  4.90  4.89  4.94  4.85  4.92 

ESEER     5.80  6.17  6.24  5.84  6.29  6.33  6.46  6.44 

H version refrigerant charge   kg  25  22  41  31  28  42  42  43 

W version refrigerant charge  kg  13  12  25  15  13  25  25  27 

  

RATED TECHNICAL DATA OF LEW HEAT PUMPS @ 15/10°C; 40/45°C 

 Efficiency pack  3  4  3  4  4  4  4  4  4 

LEW HS / HL – LEW WS / WL     243  244  283  284  314  344  374  424  484 

Cooling capacity  kW  232.74 241.14 267.41 270.57 300.02 326.54  354.46  393.07  450.32 

Utility side pressure drops  kPa  38  25  29  30  36  35  34  33  35 

Heat sink pressure drops  kPa  57  33  41  43  53  51  51  50  55 

Heating capacity  kW  318.09 329.52 367.31 371.69 413.83 451.62  487.71  538.48  617.22 

Rated absorbed power  kW  63.37  65.38  75.13  75.62  85.81  93.13  100.44  109.69  126.84 

Evaporator‐side pressure drops  kPa  67  39  49  51  63  61  60  58  63 

Evaporator‐side flow rate  l/h  54711  56677  63178  63930  71179  83886  83886  92618  107266

Condenser pressure drops  kPa  47  30  36  37  44  43  42  41  42 

Condenser‐side flow rate  l/h  44356  45994  50902  51573  57157  67474  67474  74696  85417 

Electrical power supply  V/ph/Hz 400 ‐ 3N ‐ 50Hz 

Scroll compressors / cooling circuits  No.  3  /  1  4  /  2  3  /  1  4  /  2  4  /  2  4  /  2  4  /  2  4  /  2  4 / 2 

Victaulic hydraulic connections  inches  2 1/2  2 1/2  3  3  3  3  3  3  3 

Height  mm  1854  1854  1854  1854  1854  1854  1854  1854  1854 

Length  mm  2374  2374  2374  2374  2374  2374  2374  2374  2374 

Depth  mm  877 877 877 877 877 877  877  877  877

Maximum current (FLA)  A  153.0  159.0  174.0  182.0  204.0  218.0  232.0  281.0  302.0 

Booster current (LRA)  A  336.0  301.0  401.0  355.0  374.0  437.0  442.0  490.0  525.0 

LRA with soft‐starter kit  A  271.0  239.0  318.0  290.0  309.0  354.0  359.0  420.0  454.0 

COP     4.97  5.12  4.93  4.95  4.81  4.84  4.85  4.91  4.87 

ESEER     6.37  6.62  6.34  6.21  6.15  6.13  6.20  6.45  6.56 

H version refrigerant charge   kg  41  44  43  53  55  55  55  55  55 

W version refrigerant charge  kg  25  28  25  28  31  31  31  31  31 

 

Page 25: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 25 of 56 RG66006951‐Rev.01 

 

 

2.1 Performance of LEW C, D, H, W heat pump units All the data in the paragraph refers to ΔT = 5°C on the evaporation and condensation side. Pf = chiller power [kW] ;    Pa = absorbed power [kW]. In order to calculate the thermodynamic EER and COP factors, take the Pf / Pa ratio. The performance was calculated with different glycol percentages in a solution, even though from a thermodynamic point of view, with up to 30% of glycol in a solution, there is a minor performance drop: nonetheless refer to paragraph 4.1 “Use of glycol solutions” for further information.  Table III: performance of LEW C D H units with cold water production mode.   

    LEW C  LEW D  LEW H 

  Tcond [°C] 

10/30  15/30  20/30  30/35  35/40  40/45  10/30  15/30  20/30 

Size Tev [°C] 

Pf  Pa  Pf  Pa  Pf  Pa  Pf  Pa  Pf  Pa  Pf  Pa  Pf  Pa  Pf  Pa  Pf  Pa 

LEW 041/2 

20/15  66.8  9.4  66.5  9.5  66.1  9.6  61.6  10  58.5  11.0  55.7  13  65.9  8.6  66.5  9.5  65.2  8.9 

15/10  57.4  9.3  57.1  9.4  56.8  9.5  52.8 9.9 50.0 11.0 47.1 12.1 56.5  8.5  56.2  8.7 56.1 8.9

10/5  49  9.1  48.7  9.2  48.4  9.3  45.5 10.5 43.0 11.6 40.5 12.6 49.0  9.1  48.7  9.2 48.4 9.3

LEW 051/2 

20/15  77.9  11.5  77.6  11.7  77  11.8  72.8 13.2 69.1 14.3 65.3 15.6 78.1  11.5  77.6  11.7 77.1 11.8

15/10  66.7  11.2  66.3  11.4  66  11.5  62.4 12.8 59.2 14.1 55.9 15.3 66.7  11.2  66.3  11.4 66.0 11.5

10/5  56.5  11  56.22  11.1  55.8  11.2  53 12.5 50.4 13.8 47.7 15 56.5  11.0  56.2  11.1 55.8 11.2

LEW 061/2 

20/15  89  12.6  88.7  12.7  87.8  12.9  83.7 14.2 79.3 15.6 74.8 17.1 89.8  12.4  89.2  12.5 88.7 12.7

15/10  76.4  12.4  76.2  12.5  75.5  12.7  71.8 14 67.9 15.5 64 16.9 76.9  12.2  76.7  12.3 75.9 12.5

10/5  65.2  12.1  64.9  12.3  64.4  12.5  61.2 13.7 57.8 15.2 54.4 16.6 65.6  11.9  65.3  12.1 64.7 12.3

LEW 071/2 

20/15  99.7  14.4  99  14.6  98.5  14.8  94.1 16.3 89.6 17.9 84.5 19.7 100.4  14.1  99.8  14.3 99.3 14.6

15/10  85.8  14.3  85.3  14.4  84.9  14.6  81 16.1 76.9 17.8 72.7 19.5 86.6  14.1  86.1  14.2 85.5 14.4

10/5  73.7  14  73.2  14.2  72.6  14.4  69.3 15.9 65.7 17.6 62.1 19.3 74.3  13.8  73.8  14 73.1 14.2

LEW 081/2 

20/15  114.4  16.2  113.8  16.4  112.7  16.7  108.7 18 103.2 19.7 97.3 21.7 116.1  15.7  115.6  15.9 144.8 16.1

15/10  98.5  15.8  97.8  16.1  97.1  16.3  93.4 17.6 88.4 19.5 83.4 21.4 100.0  15.2  99.3  15.5 98.3 15.8

10/5  83.9  15.6  83.6  15.7  83  16  79.8 17.3 75.4 19.3 71 21.3 85.1  15.2  84.8  15.3 83.9 15.7

LEW 091/2 

20/15  128.4  18  127.4  18.3  126.4  18.5  121.6 20.2 115.5 22.2 108.9 24.6 130.3  17.4  129.8  17.6 128.7 17.9

15/10  109.8  17.9  109.1  18.1  108.3  18.5  104.1 20 98.6 22.2 93 24.4 111.8  17.3  111.1  17.5 109.9 18.0

10/5  93.6  17.8  93  18  92  18.3  88.4 19.9 83.7 22.1 78.9 24.3 95.3  17.2  94.7  17.4 93.3 17.8

LEW 111/2 

20/15  153.3  21.5  152.1  21.8  151.3  22.2  146.7 23.5 139.3 26.0 131.1 28.8 157.1  20.4  156.2  20.6 155.2 20.9

15/10  131.7  21.2  130.6  21.5  129.4  21.9  125.8 23.3 119.1 26.0 112.4 28.6 135.3  19.9  134.2  20.3 132.2 20.9

10/5  112.3  20.9  111.4  21.3  110.7  21.6  107.1 23 101.3 25.7 95.4 28.4 115.3  19.6  114.4  20.1 113.0 20.6

LEW 131/2 

20/15  174.2  25  172.8  25.4  171.5  25.8  166.8 27.3 158.3 30.2 149.1 33.4 178.8  23.7  178  24 176.6 24.3

15/10  149.7  24.5  148.8  24.9  147.6  25.3  143.2 26.9 135.5 30.1 127.8 33.2 153.8  23.0  152.9  23.5 150.8 24.1

10/5  128  24.1  126.9  24.5  125.9  25  122 26.7 115.4 29.9 108.8 33 131.8  22.6  130.7  23.1 128.8 23.8

LEW 141/2 

20/15  201.8  28.1  201.1  28.4  199.3  28.9  191.6 31.4 180.0 34.5 171.4 38.1 204.8  27.3  203.7  27.6 202.4 28.0

15/10  173.8  27.7  172.7  28  171.6  28.6  164.6 31 155.9 34.5 147.1 37.9 176.3  26.9  175.2  27.2 173.5 27.9

10/5  148.6  27.4  147.7  27.7  146.6  28.2  140.7 30.7 132.9 34.2 125.1 37.7 150.4  26.6  149.5  26.9 148.0 27.5

LEW 144 

20/15  201.1  29  199.9  29.4  198.2  29.9  190.7 32.4 181.4 35.7 171.5 39.2 203.4  28.1  202.4  28.4 201.4 28.9

15/10  173.1  28.6  172.5  29  171  29.5  164.3 32 156.0 35.4 147.6 38.7 175.2  27.7  174.6  28.1 172.6 28.7

10/5  148.4  28.23  147.3  28.7  146.5  29  140.6 31.5 133.2 34.9 125.8 38.2 150.4  27.3  149.3  27.8 148.1 28.2

LEW 161/2 

20/15  224.7  32  224  32.4  222.1  33  214.9 35.3 204.4 38.8 193.1 42.7 228.2  31.0  227.3  31.3 225.6 31.8

15/10  193.6  31.7  224.7  32.2  190.8  32.7  184.7 35 175.1 38.7 165.4 42.4 164.1  30.6  195.3  31.1 167.8 31.8

10/5  165.4  27.4  164.4  32  163.2  32.4  157.8 34.8 149.2 38.6 140.5 42.3 167.6  26.3  166.6  30.8 164.9 31.4

LEW 164 

20/15  226.4  32.6  225.1  33  223.6  33.5  216.2 35.8 234.2 43.9 193.7 43.2 229.6  31.6  228.5  31.9 227.1 32.4

15/10  195.1  31.8  193.7  32.3  192.2  32.8  185.6 35.1 175.9 38.9 166.1 42.7 198.0  30.7  196.6  31.2 194.5 31.9

10/5  166.3  31.3  165.3  31.7  164.4  32  158.5 34.6 149.9 38.5 141.2 42.4 168.9  30.1  167.9  30.5 166.4 31.0

LEW 181/2 

20/15  263.3  38  261.3  38.6  258.9  39.4  251.6 41.7 238.9 45.9 225.3 50.4 272.0  36.0  270.5  36.5 269.0 37.0

15/10  226.5  37.6  224.7  38.2  222.6  38.9  216.4 41.2 204.9 45.6 193.3 49.9 234.6  35.4  232.9  36.1 228.9 37.1

10/5  193.6  37.2  192.4  37.7  190.5  38.4  185.2 40.7 175.0 45.1 164.7 49.4 200.2  35.1  199.1  35.7 195.6 36.7

LEW 184 

20/15  256.9  36.3  255.3  36.7  253.6  37.4  246.3 39.8 234.2 43.9 220.8 48.5 266.4  34.3  265.2  34.7 263.3 35.2

15/10  220.5  36  219.1  36.5  217.5  37.2  210.5 39.5 199.6 43.6 188.4 48.3 228.4  34.2  227.2  34.6 225.4 35.1

10/5  187.5  35.8  186.7  36.2  185.1  36.9  179.3 39.2 169.5 43.5 159.8 48.1 194.3  34  193.8  34.4 192.4 34.9

LEW 204 

20/15  282.7  39.4  280.5  40.1  278.3  40.7  270.4 43.2 256.9 47.7 242.5 52.7 288.5  37.6  286.8  38.1 285.3 38.7

15/10  242.2  39  240.8  39.6  238.5  40.4  231.8 42.8 219.3 47.7 206.8 52.5 247.6  40.0  246.2  40.6 242.7 41.2

10/5  206.5  38.6  205.2  39.2  203.5  39.8  197.1 42.4 186.6 47.3 176 52.2 211.2  36.7  209.9  37.4 207.1 38.3

LEW 214 

20/15  303.4  43  302.3  43.5  299.4  44.3  290.9 47 275.6 51.9 260.8 57.3 315.1  40.7  313.2  41.2 311.7 41.8

15/10  260.9  42.3  259.2  42.9  256.7  43.7  249.7 46.4 236.3 51.7 222.8 57 270.5  39.9  269  40.6 264.2 41.7

10/5  222.7  47  221.3  42.4  219  43.2  212.6 46 200.8 51.4 189 56.8 230.6  44.3  229.4  40.1 225.2 41.2

LEW 243 

20/15  344.1  47.7  356  49.5  339.5  49.2  332.3 52.7 316.1 57.9 298.5 63.7 353.9  45.8  352.4  46.3 350.2 47.0

15/10  295.9  47.4  294.2  48  292  48.8  285.8 52.3 271.0 57.9 256.1 63.4 305.0  45.3  303.4  46 299.1 47.1

10/5  252.7  47  251.3  47.6  249.4  48.4  244.2 51.9 231.1 57.5 218 63 260.7  44.9  259.4  45.6 255.6 46.7

Page 26: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 26 of 56 RG66006951‐Rev.01 

 

LEW 244 

20/15  358.8  48.7  402.9  57.6  353.6  50.4  344.8 54 327.5 59.6 309.1 65.9 370.3  46.9  368.1  47.4 365.3 48.1

15/10  308.2  47.8  307  48.4  304  49.3  296.7 53.1 281.1 59.3 265.5 65.4 318.0  45.6  317  46.3 311.7 47.5

10/5  263.8  47  262  47.6  259.5  48.6  253.5 52.5 239.8 58.8 226 65 272.5  44.8  270.8  45.5 266.2 46.8

LEW 283 

20/15  400.7  56.6  445.4  65.6  394.9  58.5  381.8 62.8 362.6 69.1 341.8 76 408.6  53.9  406.5  54.7 403.6 55.6

15/10  345.3  56.1  343.2  56.8  340.4  57.9  328.9 62.1 311.4 68.6 293.8 75.1 352.5  53.4  350.4  54.2 346.0 55.7

10/5  295.7  55.4  293.9  56.2  291.5  57.1  281.5 61.3 266.2 67.9 250.8 74.4 301.8  52.7  300  53.6 296.2 54.9

LEW 284 

20/15  405.9  56.7  480  71.4  399.2  58.6  386.9 62.7 367.9 69.0 347 76.1 413.7  54.3  411.4  54.9 408.9 55.9

15/10  350.1  55.9  347.4  56.8  344.2  57.8  333.3 62 315.5 68.8 297.7 75.6 357.5  53.2  354.8  54.2 349.9 55.6

10/5  298.5  55.4  297.2  56.1  294.4  57.2  284.8 61.3 269.3 68.3 253.8 75.2 304.8  52.8  303.5  53.6 299.3 55.1

LEW 314 

20/15  448.7  64.6  521.5  76.7  441.5  66.8  428.4 71.4 407.1 78.5 384.1 86.3 457.0  61.8  454.6  62.6 451.9 63.7

15/10  386.5  64.1  383.6  65  381.1  66.2  368.3 70.9 349.1 78.4 329.9 85.8 394.1  61.2  391.2  62.2 387.0 63.8

10/5  330.7  63.8  328.7  64.5  325.6  65.7  314.9 70.4 297.9 77.9 280.9 85.3 337.4  60.9  335.4  61.7 330.8 63.3

LEW 344 

20/15  482.4  70.3  480  71.4  475.7  72.7  460.9 77.6 438.0 85.4 414.3 93.9 498.8  66.9  496.9  67.9 492.9 69.0

15/10  416.6  69.8  414  70.7  410.2  72  397.8 76.9 376.6 85.0 355.3 93.1 430.4  66.2  428  67.3 420.9 69.1

10/5  357.1  69.1  355  69.9  351.6  71.2  340 76 321.3 84.2 302.5 92.4 368.1  65.8  366.2  66.7 360.2 68.5

LEW 374 

20/15  524.7  75.8  521.5  76.7  518  78.2  500.5 83.8 474.7 92.4 448.2 101.6 541.9  72.2  538.1  73.1 534.9 74.3

15/10  453.6  74.9  450.1  76.1  446.6  77.3  432 82.9 408.4 91.7 384.8 100.4 467.6  71.0  464.3  72.4 457.5 74.1

10/5  388.4  74  385.4  75.1  382.3  76.3  369.2 81.9 349.3 90.7 329.3 99.4 400.3  70.5  397.5  71.7 391.6 73.4

LEW 424 

20/15  578.5  84.6  574.1  85.8  568.8  87.2  550.3 93 522.4 101.8 492.9 111.8 599.9  81.1  597.8  82.1 592.5 83.4

15/10  498.8  82.1  496.1  83.3  491.4  84.7  475.5 90.4 450.5 100.0 425.4 109.6 517.8  78.5  515.5  79.8 506.2 81.7

10/5  428.3  79.6  426.4  80.6  423.2  82  407.9 88 385.8 98.0 363.6 107.9 444.5  76.1  443  77.2 435.9 79.1

LEW 484 

20/15  657.9  92.9  654.7  94.3  650.5  96.0  628.3 103.7 596.5 115.0 560.6 128.1 685.6  88.2  683.5  89.3 677.8 90.9

15/10  571.7  91.9  568.8  93.3  564.9  95.0  545.5 102.3 515.9 113.9 485.3 126.8 594.5  87.4  592.6  88.5 588.0 90.0

10/5  494.5  90.8  490.9  92.1  486.4  93.8  468.9 101.1 443.8 112.5 416.7 125.3 512.1  86.5  510.2  87.6 507.6 88.9

  In the heat pump performance calculation, in 5/0 evaporator conditions, a 10% glycol mixture was used on the dissipation side; in 0/‐5 conditions, a 25% glycol mixture was used.     Table IV: performance of LEW H W units in heat pump mode.  

    LEW H  ‐ LEW W 

  Tcond [°C] 

30/35  40/45  50/55 

Size  Tev [°C]  Pf  Pa  Pf  Pa  Pf  Pa 

LEW 041/2 

15/10  63.9  10.7  60.2  12.8  55.3  14.9 

10/5  54.5  9.9 51.75 12.4 49 14.9 

5/0  47.2  9.8 45.2 12.4 43.2 15 

0/‐5  40.6  9.8 39.25 12.45 37.9 15.1 

LEW 051/2 

15/10  75  12.8 70.9 15.3 66.5 18.4 

10/5  65.3  12.5 62.25 15.4 59.2 18.3 

5/0  56.4  12.2 54.4 15.15 52.4 18.1 

0/‐5  48.2  11.9 47.15 14.9 46.1 17.9 

LEW 061/2 

15/10  85.5  14 80.5 16.9 75.3 20.5 

10/5  74.6  13.7 70.65 17 66.7 20.3 

5/0  64.6  13.4 61.7 16.75 58.8 20.1 

0/‐5  55.4  13.1 53.45 16.45 51.5 19.8 

LEW 071/2 

15/10  96.8  16.1 91.7 19.5 86.2 23.7 

10/5  84.8  15.9 80.65 19.7 76.5 23.5 

5/0  73.9  15.6 70.75 19.45 67.6 23.3 

0/‐5  63.7  15.3 61.6 19.15 59.5 23 

LEW 081/2 

15/10  110.8  17.6 104.4 21.4 97.5 26.4 

10/5  96.7  17.3 91.65 21.85 86.6 26.4 

5/0  84  17 80.3 21.65 76.6 26.3 

0/‐5  72.2  16.9 69.8 21.55 67.4 26.2 

LEW 091/2 

15/10  123.5  20 116.9 24.4 109.6 30 

10/5  107.9  19.9 102.55 25 97.2 30.1 

5/0  93.6  19.8 89.75 25 85.9 30.2 

0/‐5  80.5  19.7 77.95 25 75.4 30.3 

LEW 111/2 

15/10  148.6  23.3 140.3 28.6 131.6 35.3 

10/5  129.7  23 123.15 29.15 116.6 35.3 

5/0  112.5  22.9 107.75 29.15 103 35.4 

0/‐5  96.7  22.8 93.5 29.05 90.3 35.3 

LEW 131/2 15/10  169.4  26.9 160.3 33.2 150.7 41.2 

10/5  148.2  26.6 140.95 33.9 133.7 41.2 

Page 27: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 27 of 56 RG66006951‐Rev.01 

 

5/0  128.7  26.4 123.45 33.75 118.2 41.1 

0/‐5  110.8  26.2 107.3 33.5 103.8 40.8 

LEW 141/2 

15/10  194.9  31 184.3 37.9 172.4 46.5 

10/5  170.5  30.8 161.65 38.65 152.8 46.5 

5/0  148.1  30.5 141.55 38.45 135 46.4 

0/‐5  127.6  30.2 123.05 38.1 118.5 46 

LEW 144 

15/10  195.6  32 185.5 38.7 174.1 47.1 

10/5  171.4  31.5 162.9 39.1 154.4 46.7 

5/0  149.2  31 142.85 38.65 136.5 46.3 

0/‐5  128.7  30.5 124.3 38.1 119.9 45.7 

LEW 161/2 

15/10  218.6  35.3 206.3 42.8 192.5 52.1 

10/5  191.2  35.1 181 43.65 170.8 52.2 

5/0  166.2  34.8 158.65 43.5 151.1 52.2 

0/‐5  143.3  34.5 138.1 43.25 132.9 52 

LEW 164 

15/10  219.8  35.4 207.1 43.1 193.9 53 

10/5  192.2  34.9 182.1 43.95 172 53 

5/0  166.7  34.4 159.45 43.65 152.2 52.9 

0/‐5  143.5  33.9 138.8 43.3 134.1 52.7 

LEW 181/2 

15/10  259.1  41.2 244.4 49.9 227.7 60.7 

10/5  226.9  40.8 214.4 50.6 201.9 60.4 

5/0  197.2  40.2 187.85 50.2 178.5 60.2 

0/‐5  169.9  39.7 163.45 49.7 157 59.7 

LEW 184 

15/10  252  39.6 238 48.2 222.7 59.3 

10/5  219.5  39.3 208.35 49.35 197.2 59.4 

5/0  190.2  39 182 49.35 173.8 59.7 

0/‐5  163.6  39 158.05 49.45 152.5 59.9 

LEW 204 

15/10  272.9  43.1 258 52.9 241.7 65.2 

10/5  238.5  42.8 226.45 54 214.4 65.2 

5/0  206.6  42.6 197.9 54 189.2 65.4 

0/‐5  177.5  42.4 171.75 53.95 166 65.5 

LEW 214 

15/10  297.5  46.4 281.3 57 263.7 70.5 

10/5  259.9  46 246.8 58.3 233.7 70.6 

5/0  225.5  45.7 215.85 58.15 206.2 70.6 

0/‐5  193.8  45.5 187.4 58 181 70.5 

LEW 243 

15/10  337  52.3 318.1 63.4 296.4 77.3 

10/5  294.9  51.9 278.65 64.5 262.4 77.1 

5/0  256.4  51.5 243.95 64.2 231.5 76.9 

0/‐5  221.2  51 212.2 63.65 203.2 76.3 

LEW 244 

15/10  348.7  53.1 329.5 65.4 309 81.2 

10/5  304.9  52.5 289.25 66.8 273.6 81.1 

5/0  264.6  51.9 253.1 66.5 241.6 81.1 

0/‐5  228  51.6 220.05 66.1 212.1 80.6 

LEW 283 

15/10  389.7  62 367.3 75.1 342.4 91.3 

10/5  341.5  61.3 322.7 76.05 303.9 90.8 

5/0  297.2  60.5 283.05 75.45 268.9 90.4 

0/‐5  256.7  59.7 246.8 74.7 236.9 89.7 

LEW 284 

15/10  393.9  62 371.7 75.6 348 92.9 

10/5  344.8  61.3 326.65 77.05 308.5 92.8 

5/0  299.4  60.8 286.1 76.65 272.8 92.5 

0/‐5  258.8  60.3 249.2 76.05 239.6 91.8 

LEW 314 

15/10  437.6  70.9 413.8 85.8 386.3 104.3 

10/5  383.7  70.4 363.35 87.5 343 104.6 

5/0  334.6  69.7 319.15 87.2 303.7 104.7 

0/‐5  288.5  69 278.05 86.6 267.6 104.2 

LEW 344 

15/10  477.7  76.9 451.6 93.1 420.6 113.2 

10/5  418.8  76.1 395.9 94.55 373 113 

5/0  364.7  75.3 346.7 93.9 328.7 112.5 

0/‐5  315.7  74.4 301.75 92.95 287.8 111.5 

LEW 374 

15/10  517.2  82.9 487.7 100.4 454.8 122.2 

10/5  453.3  81.9 428.55 101.7 403.8 121.5 

5/0  394.8  80.9 376.1 100.85 357.4 120.8 

0/‐5  341  79.7 328 99.8 315 119.9 

LEW 424 

15/10  571.4  90.7 538.5 109.7 505.6 134.7 

10/5  499.8  88.1 474.35 109.7 448.9 131.3 

5/0  435.8  85.9 416.45 106.7 397.1 127.5 

0/‐5  377.5  84 363.95 104.1 350.4 124.2 

LEW 484 

15/10  655.3  102.5 617.2 126.8 578.1 157.9 

10/5  576.3  101.2 546.1 125.3 514.8 156.5 

5/0  502.2  99.7 479.0 124.1 456.6 155.4 

0/‐5  438.0  98.5 421.7 122.8 406.9 154.8 

 

Page 28: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 28 of 56 RG66006951‐Rev.01 

 

2.2 Noise emission Table V: sound emissions for LEW ‐ Lw models: Sound power ‐ Lp: Sound pressure   

 Sizes:  040  050  060  070  080  090  110  130  140  160  180  200  210  240  280  310  340  370  420  484 

Lw [db(A)] 

Standard Version 

72  72  73  73  74  76  76  77  80  80  81  81  81  82  82  82  83  83  83  86 

Low‐Noise Version 

68  68  69  69  70  72  72  73  76  76  77  77  77  78  78  78  79  79  79  82 

Lp [db(A)] @ 10 m 

Standard Version 

44  44  45  45  46  48  48  49  52  52  53  53  53  54  54  54  55  55  55  58 

Low‐Noise Version 

40  40  41  41  42  44  44  45  48  48  49  49  49  50  50  50  51  51  51  54 

Lp [db(A)] @ 5 m 

Standard Version 

50  50  51  51  52  54  54  55  58  58  59  59  59  60  60  60  61  61  61  64 

Low‐Noise Version 

46  46  47  47  48  50  50  51  54  54  55  55  55  56  56  56  57  57  57  60 

 

2.3 Overall dimensions and weight of the main units The LEW product range consists of different frames. The overall drawings of the LEW models are reported in the following paragraph. They can be referred to by consulting the identification codes reported in the tables in this paragraph. The tables below report the weights, reference drawings and overall dimensions of all the LEW models.   Table VI: weight and reference drawings of the main units of the LEW range with reference to their frames  

  CS ‐ Chiller DS  Dry Cooler 

Chiller HS – Heat Pump  WS – Hot only 

Frame  Model Weight [kg] 

Overall Drawing 

Weight [kg] 

Overall Drawing 

Weight [kg] 

Overall Drawing 

Weight [kg] 

Overall Drawing 

F1 

LEW 041  370  HF64000737  370  HF64000737  415  HF64000737  370  HF64000614 

LEW 042  360 HF64000737  360 HF64000737 385 HF64000737 360 HF64000614 

LEW 051  430 HF64000737  430 HF64000737 475 HF64000737 430 HF64000614 

LEW 052  420  HF64000737  420  HF64000737  445  HF64000737  420  HF64000614 

LEW 061  440 HF64000737  447 HF64000737 502 HF64000737 447 HF64000614 

LEW 062  430 HF64000737  437 HF64000737 467 HF64000737 437 HF64000614 

LEW 071  450 HF64000737  457 HF64000737 512 HF64000737 457 HF64000614 

LEW 072  440 HF64000737  447 HF64000737 482 HF64000737 447 HF64000614 

LEW 081  470 HF64000737  485 HF64000737 530 HF64000737 485 HF64000614 

LEW 082  460 HF64000737  475 HF64000737 510 HF64000737 475 HF64000614 

LEW 091  510 HF64000737  525 HF64000737 575 HF64000737 525 HF64000614 

LEW 092  490 HF64000737  505 HF64000737 540 HF64000737 505 HF64000614 

F2 

LEW 111  560 HF64000592  585 HF64000592 645 HF64000592 585 HF64000608 

LEW 112  550 HF64000592  575 HF64000592 605 HF64000592 575 HF64000608 

LEW 131  570 HF64000592  595 HF64000592 660 HF64000592 595 HF64000608 

LEW 132  560 HF64000592  585 HF64000592 625 HF64000592 585 HF64000608 

LEW 141  630 HF64000592  650 HF64000592 720 HF64000592 650 HF64000608 

LEW 142  615 HF64000592  635 HF64000592 685 HF64000592 635 HF64000608 

LEW 161  670 HF64000592  705 HF64000592 775 HF64000592 705 HF64000608 

LEW 162  650 HF64000592  685 HF64000592 740 HF64000592 685 HF64000608 

LEW 181  710 HF64000592  750 HF64000592 825 HF64000592 750 HF64000608 

LEW 182  690 HF64000592  730 HF64000592 780 HF64000592 730 HF64000608 

F3 

LEW 144  720 HF64000581  740 HF64000581 830 HF64000581 740 HF64001344 

LEW 164  740 HF64000581  775 HF64000581 865 HF64000581 775 HF64001344 

LEW 184  850 HF64000581  890 HF64000581 985 HF64000581 890 HF64001344 

LEW 204  870 HF64000581  915 HF64000581 1110 HF64000581 915 HF64001344 

LEW 214  920 HF64000581  965 HF64000581 1065 HF64000581 965 HF64001344 

LEW 243  950 HF64000581  1060 HF64000609 1120 HF64000609 1060 HF64000627 

LEW 244  980 HF64000581  1090 HF64000609 1270 HF64000609 1090 HF64000627 

LEW 283  1050  HF64000803  1120 HF64000609 1180 HF64000609 1120 HF64000627 

LEW 284  1090  HF64000803  1260 HF64000609 1340 HF64000609 1260 HF64000627 

LEW 314  1250  HF64000803  1330 HF64000609 1420 HF64000609 1330 HF64000627 

LEW 344  1290  HF64000803  1380 HF64000609 1470 HF64000609 1380 HF64000627 

LEW 374  1330  HF64000803  1440 HF64000609 1540 HF64000609 1440 HF64000627 

LEW 424  1410  HF64000803  1530 HF64000609 1650 HF64000609 1530 HF64000627 

LEW 484  1510  HF64000803  1520 HF64000609 1710 HF64000609 1710 HF64000627 

Page 29: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 29 of 56 RG66006951‐Rev.01 

 

  Table VII: overall dimensions of the frames of the main units (F_)   

Frame of the main unit 

Height (H)  Width (L)  Depth (D) 

F1  1594  1174  772 

F2  1594  1644 772

F3  1854  2374  877 

 

Page 30: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 30 of 56 RG66006951‐Rev.01 

 

 

2.4 Overall drawings of the main units  HF64000737 overall drawing  

              

Page 31: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 31 of 56 RG66006951‐Rev.01 

 

HF64000614 overall drawing   

          

Page 32: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 32 of 56 RG66006951‐Rev.01 

 

HF64000592 overall drawing   

              

Page 33: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 33 of 56 RG66006951‐Rev.01 

 

HF64000608 overall drawing   

         

Page 34: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 34 of 56 RG66006951‐Rev.01 

 

HF64000581 overall drawing  

           

Page 35: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 35 of 56 RG66006951‐Rev.01 

 

HF64000609 overall drawing   

             

Page 36: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 36 of 56 RG66006951‐Rev.01 

 

HF64001344 overall drawing  

    

Page 37: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 37 of 56 RG66006951‐Rev.01 

 

HF64000803 overall drawing   

              

Page 38: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 38 of 56 RG66006951‐Rev.01 

 

HF64000627 overall drawing   

           

Page 39: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 39 of 56 RG66006951‐Rev.01 

 

 

3 Technical data of optional hydronic modules 

  Hydronic modules, recommended as an optional feature for LEW units, bring together, in just a single, compact and silent solution, the main components of the primary circuit of the hydraulic system served by LEW machines. Each hydraulic module contains both circuits: 

‐ ON/OFF hydraulic pump ‐ Blade‐type flow switch to prevent ice from forming, which is caused by the evaporation of the refrigerant in the 

plate heat exchanger. (LEW C D units have a flow switch on the utility side, LEW W H units have a flow switch both on the utility and the source side) 

‐ Expansion vessel to manage changes in volume affecting the amount of water contained in the LEW unit and the module itself 

‐ Safety valve (set to 3 bar as standard)  The module has its own electric panel, which powers the pumps, protects them with motor overload protections and receives the consent from the LEW units. The power is not supplied by the LEW unit, but directly by the external line. The module is insulated to reduce the sound emissions of the pumps.        

3.1 Characteristic curves of the hydraulic pumps associated to the units The graphics displayed in this paragraph show the useful head (net with the internal losses of the units) of the HP pumps and LP pumps in the optional hydronic module.   At the nominal flow rates listed in this chapter in Tables I and II, the low‐pressure LP pumps provide 60 kPa of useful head on the utility side and 70 kPa on the dissipation side. The high‐pressure HP pumps provide a useful head equal to 140 kPa for both hydraulic circuits.     Useful head for LEW 041, 042 pumps on utility side      Useful head for LEW 051, 052 pumps on utility side 

    Useful head for  LEW 061, 062, 071, 072 pumps on utility side    Useful head for LEW 081, 082 pumps on utility side 

 

Page 40: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 40 of 56 RG66006951‐Rev.01 

 

   Useful head for LEW 091, 092 pumps on utility side      Useful head for LEW 111, 112, 131, 132 pumps on utility side 

   Useful head for LEW 141, 142, 144 pumps on utility side    Useful head for LEW 161, 162, 164 pumps on utility side 

    Useful head for  LEW 181; 182; 184 pumps on utility side    Useful head for LEW 204 pumps on utility side 

    Useful head for LEW 214 pumps on utility side      Useful head for LEW 243, 244 pumps on utility side 

     

Page 41: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 41 of 56 RG66006951‐Rev.01 

 

Useful head for LEW 283, 284 pumps on utility side      Useful head for LEW 314 pumps on utility side 

    Useful head for  LEW 344 pumps on utility side      Useful head for LEW 374 pumps on utility side 

    Useful head for  LEW 424 pumps on utility side      Useful head for LEW 484 pumps on utility side 

    Useful head for LEW 041, 042 pumps on dissipation side    Useful head for LEW 051, 052 pumps on dissipation side 

  

Page 42: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 42 of 56 RG66006951‐Rev.01 

 

  Useful head for LEW 061, 062 pumps on dissipation side    Useful head for LEW 071, 072 pumps on dissipation side 

    Useful head for LEW 081, 082 pumps on dissipation side    Useful head for LEW 091, 092 pumps on dissipation side 

    Useful head for LEW 111, 112 pumps on dissipation side    Useful head for LEW 131, 132 pumps on dissipation side 

    Useful head for LEW 141, 142 pumps on dissipation side    Useful head for LEW 144 pumps on dissipation side 

  

Page 43: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 43 of 56 RG66006951‐Rev.01 

 

   Useful head for LEW 161, 162, 164 pumps on dissipation side    Useful head for LEW 181, 182, 184 pumps on dissipation side 

    Useful head for LEW 204 pumps on dissipation side      Useful head for LEW 214 pumps on dissipation side 

    Useful head for LEW 243 pumps on dissipation side      Useful head for LEW 244, 283, 284 pumps on dissipation side 

    Useful head for LEW 314 pumps on dissipation side      Useful head for LEW 344 pumps on dissipation side 

 

Page 44: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 44 of 56 RG66006951‐Rev.01 

 

   Useful head for LEW 374 pumps on dissipation side    Useful head for LEW 424 pumps on dissipation side 

  Useful head for LEW 484 pumps on dissipation side 

  

Page 45: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 45 of 56 RG66006951‐Rev.01 

 

 

3.2 Overall dimensions and weight of optional hydronic modules The tables below list the weights, reference drawings and overall dimensions of all optional hydronic modules. The overall drawings of the optional modules are reported in the following paragraph. They can be referred to by consulting the identification codes reported the tables in this paragraph.   Table VIII: weight and reference drawings of optional modules with reference to the dimensions of the relative main unit and whether or not there is a water side cycle inversion valve.  

  Optional hydronic module with pumps 

Model Optional 

module frame Weight [kg] Overall Drawing 

LEW 041  M1  391  HF64000799 

LEW 042  M1 391 HF64000799

LEW 051  M1 400 HF64000799

LEW 052  M1 400 HF64000799

LEW 061  M1 400 HF64000799

LEW 062  M1 400 HF64000799

LEW 071  M1 395 HF64000799

LEW 072  M1 395 HF64000799

LEW 081  M1 395 HF64000799

LEW 082  M1 395 HF64000799

LEW 091  M1 399 HF64000799

LEW 092  M1 399 HF64000799

LEW 111  M1 399 HF64000799

LEW 112  M1 399 HF64000799

LEW 131  M1 412 HF64000799

LEW 132  M1 412 HF64000799

LEW 141  M1 412 HF64000799

LEW 142  M1 412 HF64000799

LEW 161  M1 433 HF64000799

LEW 162  M1 433 HF64000799

LEW 181  M1 543 HF64000799

LEW 182  M1 543 HF64000799

LEW 144  M3 423 HF64000906

LEW 164  M3 433 HF64000906

LEW 184  M3 543 HF64000906

LEW 204  M3 559 HF64000906

LEW 214  M3 559 HF64000906

LEW 243  M3 576 HF64000908

LEW 244  M3 587 HF64000908

LEW 283  M3 587 HF64000908

LEW 284  M3 587 HF64000908

LEW 314  M3 614 HF64000908

LEW 344  M3 614 HF64000908

LEW 374  M3 626 HF64000908

LEW 424  M3 626 HF64000908

LEW 484  M3 626 HF64000908

  Table VII: overall dimensions of the frames of the main units (F_) and optional hydraulic modules (M_) used in the LEW range  

Optional module frame 

Height (H)  Width (L)  Depth (D) 

M1  1594 1174  772 

M2  1594 1644 772

M3  1854 1644 877

M4  1854 2374  877 

  

Page 46: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 46 of 56 RG66006951‐Rev.01 

 

3.3 Overall drawings of optional hydronic modules  HF64000799 overall drawing    

               

Page 47: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 47 of 56 RG66006951‐Rev.01 

 

HF64000906 overall drawing    

              

Page 48: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 48 of 56 RG66006951‐Rev.01 

 

HF64000908 overall drawing for LEW C units  

                

Page 49: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 49 of 56 RG66006951‐Rev.01 

 

HF64000908 overall drawing for LEW D W H units  

                 

Page 50: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 50 of 56 RG66006951‐Rev.01 

 

 

4 Installation 

4.1 Installation clearance requirements The hydraulic connections are all foreseen on the right side of the unit, when looking at the front panel. This way the back of the unit can be against the wall. It is essential to ensure the following service spaces:  ‐ rear side: min. 0  m ‐ electric panel side: at least 1 m to guarantee access for inspections and/or for maintenance of cooling components ‐ right side: 1 m to be able to connect the hydraulic piping properly ‐ top side: min. 1  m ‐ left side: 0.5 m  

  These distances refer to standard versions of LEW units; the same considerations apply to the optional hydronic modules.  

When installing the unit, for safety purposes, make sure that the room temperature does not exceed 50°C (with unit on or off).

 

4.2 Volume of water in the system  The ON/OFF‐type compressors work intermittently, since the cooling power required by the utility is not generally the same as that supplied by the compressor. In systems containing little water, in which the thermal inertia is low, verify that the water content of the delivery section (to users) satisfies the equation below:

NsSh

CcV

V = water content in user section [m3] Sh = specific heat of fluid [J/(kg/°C)] e.g. 2090 [J/(kg/°C)] for water = density of fluid [kg/m3] e.g. 1000 [kg/m3] for water D = minimum time between 2 compressor restarts [s] e.g. 120 [s] DT = admissible differential on water T [°C] e.g. 4 [°C] Cc = Cooling Capacity [W] Ns = N° of capacity control steps

Page 51: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 51 of 56 RG66006951‐Rev.01 

 

A standard feature of LEW units is a device to control the water flow rate (blade-type flow switch supplied). Any tampering with this device will immediately invalidate the warranty. We recommend installing a metal net filter on the water inlet piping.

Warning: Never perform hydraulic connection operations with open flames near or inside the unit.

Inertial Tank Ts °C

Inlet water T  

Outlet water T 

Page 52: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 52 of 56 RG66006951‐Rev.01 

 

 

5 Operating limits 

  This paragraph reports a list of operating limits for the LEW chillers relating to the water outlet temperature on the utility side and water inlet temperature at the dissipation exchanger. Applications with water T exceeding the limits indicated they must run with R134a refrigerant (available upon request). You can contact your local Agent for related details.   Operating range of LEW units in cooling mode and heat pump mode:  

  Water can be produced at temperatures below 5°C (up to ‐10°C) using glycol solutions. This lowers the freezing point as shown in the following table:  

Minimum temperature of produced water 

5 °C  2°C ‐1 °C ‐5°C ‐10 °C 

Percentage in weight of ethylene glycol 

0 %  10 % 15% 25 % 30 % 

Freezing temperature of mixture 

0 °C  ‐4 °C ‐ 8 °C ‐14 °C ‐18 °C 

 If  the water produced  is below  0°C,  a  special  insulation needs  to be  applied  to  the  cold pipes  to prevent  ice  from forming. This is why applications with temperatures produced below 0°C must be considered as special applications.    The useful head supplied by the pump, at the same volumetric water flow, depends on the glycol percentage as shown in the following table:  

Percentage in weight of ethylene glycol 

0 %  10 % 15% 25 % 30 % 

Reduction percentage of useful flow rate 

0 %  ‐5 % ‐8 % ‐12 % ‐15 % 

 Performance loss of the thermodynamic circuit is negligible up to concentrations of 30% glycol, in weight.  

Page 53: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 53 of 56 RG66006951‐Rev.01 

 

The machines' performance can be calculated with the selection software. 

5.1 Working limits ‐ Heat transfer fluid: water or mixture of water and max 30% glycol antifreeze ‐ Maximum water side pressure:    = 3 bar ‐ Maximum pressure on high pressure   side    = 45 bar‐r (**) ‐ Maximum ambient T        =  45 °C ‐ Minimum ambient T= ‐10 °C ‐ Maximum pressure on low pressure side   = 29 bar‐r (*) ‐ Power supply voltage:       = +/‐ 10% compared to plate voltage ‐ Maximum storage T       = + 50 °C ‐ Minimum storage Temp          = ‐ 20  °C (limit set by on‐board electronics)  (*) this value can only be reached during storage and determines the saturation pressure of 30 bar‐r of the refrigerant on the low pressure side of the circuit (value which determines its limits). (**) for units with power outputs higher than 140 kW per circuit, a second pressure switch sets the threshold to 40.5 bar. 

5.2 Water flow to evaporator The nominal flow rate is based on a temperature differential of 5° C between inlet and outlet water, in relation to the cooling capacity provided at the nominal water (12/7 °C) temperatures.  The maximum allowable flow rate is associated with a temperature differential of 3 °C. Higher flow rates cause unacceptable drops in pressure.  The minimum allowable flow rate is achieved with a temperature differential of 8 °C. Lower flow rates may result in low evaporation temperatures, which could trigger the safety devices and stop the unit. They may also cause an incorrect distribution or heat transfer in a non‐turbulent or not fully turbulent flow.   

Page 54: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 54 of 56 RG66006951‐Rev.01 

 

 

6 Calibration of control devices 

  All the control devices are set and tested in the factory before the unit is dispatched. However, after the unit has been in service for a reasonable period of time you can perform a check on the operating and safety devices. The calibration values are reported in Tables I and II.  

All the servicing operations performed on the control equipment are considered as extraordinary maintenance and must be carried out EXCLUSIVELY BY QUALIFIED PERSONNEL: incorrect calibration values can cause serious damage to the unit and serious injury to people.

 Many of the functioning parameters and calibrations of the control systems that affect the integrity of the unit are set by the microprocessor control and are protected by passwords.   Table I ‐ Calibration of control devices  

Control device  Set Point °C  Differential °C 

Service thermostat ‐ C  12  2 

Service thermostat ‐ H  40  2 

  Table II ‐ Calibration of safety devices  

Control device Unit of 

measurement Switching it on  Differential  Resetting 

Antifreeze thermostat  °C  +4  2  Automatic 

Maximum pressure switch cat. IV PED 

bar  40.5  ‐  Manual 

Low pressure safety valve cat. IV PED 

bar  29.0  ‐0 / +10%  ‐ 

Minimum pressure switch  bar  1.5  1.0  Automatic 

Modulating condensation control [optional] 

bar  18  10  ‐ 

Time between two start‐ups of the same compressor 

s  480  ‐  ‐ 

Flow switch alarm delay  s  20  ‐  ‐ 

Low pressure alarm delay  s  1  ‐  ‐ 

  Calibration of the maximum pressure switch The high pressure switch stops the compressor when delivery pressure exceeds the calibration value. For power outputs greater than 140 kW per circuit (namely LER162 in single circuit and LEW304 in dual circuit) there are two maximum pressure switches, one set at 40.5 bar and the other at 45 bar. For smaller sizes, there is just one pressure switch set to 45 bar. 

Page 55: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

  

Page 55 of 56 RG66006951‐Rev.01 

 

Attention: do not modify the calibration of the maximum pressure switch. Should the latter fail to work, rising pressure causes the high pressure safety valve to open.

The high pressure switch must be reset manually; this is possible only when the pressure drops below the value indicated by the set differential (see Table II).  Calibration of the minimum pressure switch The low pressure switch stops the compressor when the intake pressure falls below the set value for more than 120 seconds.  It is reset automatically only when the pressure rises above the value indicated by the set differential (see Table II).  Calibration of the service thermostat function This function starts and stops the compressors according to the water temperature reading at the chiller unit inlet [water returning from the system].  Refer to the section of the document on the microprocessor control for further details.  Calibration of the antifreeze thermostat function The antifreeze probe is located at the evaporator outlet and stops the compressor if the water temperature drops below the preset limit. Together with the flow switch and low pressure switch, this device protects the evaporator from the risk of freezing as a result of faults in the water circuit. Refer to the microprocessor control manual for further details  Calibration of the anti‐recycle timer function The timer function prevents excessively frequent compressor starts and stops. It imposes a minimum time lapse of 480 seconds between two successive starts. Refer to the microprocessor control manual for further details. 

Never change the delay time set by the manufacturer: incorrect values could cause serious damage to the unit.

 

Page 56: HF61G00027 LEW-0-PD-GB-06 HIREF · paragraph 2.3 "Overall dimensions and weight". All sizes of the LEW series can be implemented with the standard "S" set‐up or the "L" soundproof

40010 Bentivoglio (BO)Via Romagnoli 12/aTel. 051/8908111Fax. 051/8908122

www.galletti.itAzienda certificata UNI EN ISO 9001 e OHSAS 18001