• Heating • ERLQ-CV3 1
• Outdoor Unit • ERLQ-CV3
TABLE OF CONTENTSERLQ-CV3
1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Capacity and Power input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Cooling Capacity Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Heating Capacity Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Certification Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
5 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6 Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
7 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
8 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
Wiring Diagrams - Single Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
9 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Sound Power Spectrum Quiet Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Sound Pressure Spectrum - Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Sound Pressure Spectrum - Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
10 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Installation Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
11 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
• Outdoor Unit • ERLQ-CV3
1
2
1 Features
door Uni ting Q-CV3 kin Alth
Out Hea ERL Dai • Outdoor unit extracts heat from the outdoor air, even at -25°C • Inverter controlled swing compressorGuaranteed operation down
to -25°C
Inverter
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
CONNECTABLE INDOOR UNITS
2-1 Capacity and Power inputEHBH04CB3V/ERLQ004CV3
EHBH08CB9W/ERLQ006CV3
EHBH08CB3V/ERLQ006CV3
EHBH08CB9W/ERLQ008CV3
EHBH08CB3V/ERLQ008CV3
EHBH11CB3V/ERLQ011CV3
Heating capacity Min. kW 1.80 (1) -
Nom. kW 4.40 (1) / 4.03 (2)
6.00 (1) / 5.67 (2) 7.40 (1) / 6.89 (2) 11.2 (1) / 11.0 (2)
Max. kW 5.12 (1) / 4.90 (2)
8.35 (1) / 7.95 (2) 10.0 (1) / 9.53 (2) 8.60 (3) / 8.60 (4)
Power input Heating Nom. kW 0.870 (1) / 1.13 (2)
1.27 (1) / 1.59 (2) 1.66 (1) / 2.01 (2) 2.43 (1) / 3.10 (2)
Max. kW - 3.13 (3) / 4.10 (4)
COP 5.04 (1) / 3.58 (2)
4.74 (1) / 3.56 (2) 4.45 (1) / 3.42 (2) 4.60 (1) / 2.75 (3) / 3.55 (2) /
2.10 (4)
Pump Nominal ESP unit Heating kPa 53.0 (5) / 56.0 (6)
45.0 (5) / 48.0 (6) 33.0 (5) / 38.0 (6) 37.0 (7) / 39.0 (8)
Water side Heat exchanger
Water flow rate Heating Nom. l/min 12.6 (5) / 11.6 (6)
17.2 (5) / 16.3 (6) 21.2 (5) / 19.8 (6) 32.1 (7) / 31.5 (8)
General Supplier/Manufacturer details
Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Name or trademark Daikin Europe N.V.
Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater
No
Low-temperature heat pump No
Supplementary heater integrated
Yes
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 40.0 41.0
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 61.0 62.0 64.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating general Air to water unit Rated airflow (outdoor)
m³/h 2,700 2,820 5,400
Brine/water to water unit
Rated water/brine flow
m³/h 0.00 -
Other Capacity control Inverter
Cdh (Degradation heating) 1.00
Pck (Crankcase heater mode)
kW 0.00 0.055
Poff (Off mode) kW 0.0080 0.055
Psb (Standby mode) kW 0.0080 0.055
Pto (Thermostat off) kW 0.0060 0.0070 0.0080 0.057
Integrated supplementary heater
NOx emission mg/kWh
0.00
Psup kW 3.00 9.00 3.00 9.00 3.00
Type of energy input Electrical
• Heating • ERLQ-CV3 3
• Outdoor Unit • ERLQ-CV3
2
4
2 Specifications
Space heating Average climate water outlet 55°C
General SCOP 3.20 3.22 3.23 3.09
Annual energy consumption
kWh 2,356 3,369 4,064 6,260
Annual energy consumption (GCV)
Gj 8.48 12.1 14.6 22.6
ηs (Seasonal space heating efficiency)
% 125 126 120
Prated at -10°C
kW 3.70 5.30 6.40 9.99
Seasonal space heating eff. class
A++ A+
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.00
COPd 2.03 2.02 1.98 1.99
Pdh kW 3.36 4.50 5.47 8.83
PERd % 81.2 80.8 79.2 79.6
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00 0.990 1.00
COPd 3.08 3.17 3.24
Pdh kW 2.00 4.43 3.43 5.28
PERd % 123 127 130
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.990 0.950
COPd 4.27 4.20 4.31
Pdh kW 2.77 3.51 3.50 4.47
PERd % 171 168 172
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.990 0.930
COPd 6.33 5.82 6.41
Pdh kW 2.65 3.28 5.37
PERd % 253 233 256
Tol (temperature operating limit)
COPd 1.80 1.74 1.66 1.79
Pdh kW 3.76 4.62 6.18 9.08
PERd % 72.0 69.6 66.4 71.6
TOL °C -10.0
WTOL °C 55.0
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.00 0.680 0.220 0.910
Tbiv (bivalent temperature)
COPd 1.80 1.74 1.66 1.99
Pdh kW 3.76 5.09 6.18 8.83
PERd % 72.0 69.6 66.4 79.6
Tbiv °C -10.0 -9.00 -10.0 -7.00
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Cold climate water outlet 55°C
General Annual energy consumption
kWh 2,133 2,306 3,088 6,740
Annual energy consumption (GCV)
Gj 7.68 8.30 11.1 24.3
ηs (Seasonal space heating efficiency)
% 107 110 95.0
Prated at -22°C
kW 2.39 2.60 3.56 6.99
Warm climate water outlet 55°C
General Annual energy consumption
kWh 1,168 1,491 1,904 2,630
Annual energy consumption (GCV)
Gj 4.20 5.37 6.85 9.47
ηs (Seasonal space heating efficiency)
% 186 182 178 125
Prated at 2°C
kW 4.27 5.30 6.59 7.58
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 5
• Outdoor Unit • ERLQ-CV3
2
6
2 Specifications
Space heating Average climate water outlet 35°C
General SCOP 4.52 4.29 4.34 3.98
Annual energy consumption
kWh 1,980 2,540 3,489 5,380
Annual energy consumption (GCV)
Gj 7.13 9.14 12.6 19.4
ηs (Seasonal space heating efficiency)
% 178 169 171 156
Prated at -10°C
kW 4.40 5.34 7.40 11.2
Seasonal space heating eff. class
A++
A Condition (-7°CDB/-8°CWB)
COPd 3.01 2.69 2.63
Pdh kW 4.01 4.72 6.68 8.88
PERd % 120 108 105
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00 0.990 1.00
COPd 4.41 4.24 4.05
Pdh kW 2.40 3.90 6.03
PERd % 176 170 162
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.980 1.00 0.940
COPd 5.85 5.75 6.77
Pdh kW 1.70 2.59 5.74
PERd % 234 230 271
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.980 0.920
COPd 7.71 7.27 8.97
Pdh kW 2.04 2.61 6.50
PERd % 308 291 359
Tol (temperature operating limit)
COPd 2.61 2.29 2.34
Pdh kW 4.36 4.70 6.81 8.76
PERd % 104 91.6 93.6
TOL °C -10.0
WTOL °C 35.0
G Condition (-15°CDB/-)
COPd 0.00 -
Pdh kW 0.00 -
PERd % 0.00 -
Tbiv (bivalent temperature)
COPd 2.61 2.47 2.82
Pdh kW 4.36 4.93 7.14 9.09
PERd % 104 98.8 113
Tbiv °C -10.0 -8.00 -5.00
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.040 0.640 0.590 2.44
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Cold climate water outlet 35°C
General Annual energy consumption
kWh 1,450 2,040 2,480 6,430
ηs (Seasonal space heating efficiency)
% 151 153 151 148
Prated at -22°C
kW 2.28 3.25 3.89 10.3
Qhe Annual energy consumption (GCV)
Gj 5.20 7.34 8.91 23.1
Warm climate water outlet 35°C
General Annual energy consumption
kWh 905 1,270 1,570 1,950
Annual energy consumption (GCV)
Gj 3.26 4.56 5.67 7.02
ηs (Seasonal space heating efficiency)
% 269 259 251 192
Prated at 2°C
kW 4.81 6.40 7.68 9.06
Domestic hot water heating
General Function to fix water heating during off peak hours
Yes -
Average climate ηwh (water heating efficiency)
% -
Cold climate ηwh (water heating efficiency)
% -
Warm climate ηwh (water heating efficiency)
% -
CONNECTABLE INDOOR UNITS
2-2 Capacity and Power inputEHBH11CB9W/ERLQ011CV3
EHBH16CB3V/ERLQ014CV3
EHBH16CB9W/ERLQ014CV3
EHBH16CB3V/ERLQ016CV3
EHBH16CB9W/ERLQ016CV3
Heating capacity Nom. kW 11.2 / 11.0 14.5 / 13.6 16.0 / 15.2
Max. kW 8.60 / 8.60 10.6 / 10.8 11.4 / 10.9
Power input Heating Nom. kW 2.43 / 3.10 3.37 / 4.10 3.76 / 4.66
Max. kW 3.13 / 4.10 4.00 / 5.19 4.32 / 5.22
COP 4.60 / 2.75 / 3.55 / 2.10
4.30 / 2.65 / 3.32 / 2.08 4.25 / 2.64 / 3.26 / 2.09
Pump Nominal ESP unit Heating kPa 37.0 / 39.0 49.0 / 57.0 33.0 / 42.0
Water side Heat exchanger
Water flow rate Heating Nom. l/min 32.1 / 31.5 41.6 / 39.0 45.9 / 43.6
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 7
• Outdoor Unit • ERLQ-CV3
2
8
2 Specifications
General Supplier/Manufacturer details
Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Name or trademark Daikin Europe N.V.
Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater No
Low-temperature heat pump No
Supplementary heater integrated
Yes
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 41.0 44.0
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 64.0 66.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating general Air to water unit Rated airflow (outdoor)
m³/h 5,400
Other Capacity control Inverter
Cdh (Degradation heating) 1.00
Pck (Crankcase heater mode)
kW 0.055
Poff (Off mode) kW 0.055
Psb (Standby mode) kW 0.055
Pto (Thermostat off) kW 0.057
Integrated supplementary heater
NOx emission mg/kWh 0.00
Psup kW 9.00 3.00 9.00 3.00 9.00
Type of energy input Electrical
Space heating Average climate water outlet 55°C
General SCOP 3.09 3.16 3.06
Annual energy consumption
kWh 6,260 7,900 8,970
Annual energy consumption (GCV)
Gj 22.6 28.4 32.3
ηs (Seasonal space heating efficiency)
% 120 123 119
Prated at -10°C
kW 9.99 12.7 13.9
Seasonal space heating eff. class
A+
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.00
COPd 1.99 1.76 1.78
Pdh kW 8.83 9.97 12.2
PERd % 79.6 70.4 71.2
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00
COPd 3.24 3.55 3.12
Pdh kW 5.28 6.76 7.61
PERd % 130 142 125
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Average climate water outlet 55°C
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.950 1.00
COPd 4.31 4.22 4.40
Pdh kW 4.47 4.66 4.83
PERd % 172 169 176
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.930 0.940 0.930
COPd 6.41 5.44 6.36
Pdh kW 5.37 5.26 5.38
PERd % 256 218 254
Tol (temperature operating limit)
COPd 1.79 1.75 1.71
Pdh kW 9.08 12.2 13.3
PERd % 71.6 70.0 68.4
TOL °C -10.0
WTOL °C 55.0
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.910 0.550 0.580
Tbiv (bivalent temperature)
COPd 1.99 1.92 1.78
Pdh kW 8.83 11.0 12.2
PERd % 79.6 76.8 71.2
Tbiv °C -7.00 -6.00 -7.00
Cold climate water outlet 55°C
General Annual energy consumption
kWh 6,740 7,870 8,580
Annual energy consumption (GCV)
Gj 24.3 28.3 30.9
ηs (Seasonal space heating efficiency)
% 95.0 95.5 98.3
Prated at -22°C
kW 6.99 8.15 9.12
Warm climate water outlet 55°C
General Annual energy consumption
kWh 2,630 3,270 3,420
Annual energy consumption (GCV)
Gj 9.47 11.8 12.3
ηs (Seasonal space heating efficiency)
% 125 135 136
Prated at 2°C
kW 7.58 9.84 10.3
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 9
• Outdoor Unit • ERLQ-CV3
2
10
2 Specifications
Space heating Average climate water outlet 35°C
General SCOP 3.98 3.90 3.80
Annual energy consumption
kWh 5,380 7,250 8,270
Annual energy consumption (GCV)
Gj 19.4 26.1 29.8
ηs (Seasonal space heating efficiency)
% 156 153 149
Prated at -10°C
kW 11.2 14.5 16.0
Seasonal space heating eff. class
A++ A+
A Condition (-7°CDB/-8°CWB)
COPd 2.63 2.33
Pdh kW 8.88 10.7 12.4
PERd % 105 93.2
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00
COPd 4.05 4.07 3.74
Pdh kW 6.03 7.71 8.62
PERd % 162 163 150
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.940 1.00 0.940
COPd 6.77 5.71 6.77
Pdh kW 5.74 5.05 5.74
PERd % 271 228 271
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.920 0.930 0.920
COPd 8.97 6.71 8.97
Pdh kW 6.50 5.16 6.50
PERd % 359 268 359
Tol (temperature operating limit)
COPd 2.34 2.60 2.05
Pdh kW 8.76 12.6 11.7
PERd % 93.6 104 82.0
TOL °C -10.0
WTOL °C 35.0
Tbiv (bivalent temperature)
COPd 2.82 2.83 2.56
Pdh kW 9.09 11.6 12.1
PERd % 113 102
Tbiv °C -5.00 -4.00
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 2.44 1.93 4.35
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Notes
(1) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
(2) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
(3) Tamb 35°C - LWE 7°C (DT=5°C)
(4) Tamb 35°C - LWE 18°C (DT=5°C)
(5) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
(6) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
(7) Contains fluorinated greenhouse gases
(8) Condition 3: heating Ta DB -7°C (RH85%) - LWC 35°C
Condition 4: heating Ta DB -7°C (RH85%) - LWC 45°C
Space heating Cold climate water outlet 35°C
General Annual energy consumption
kWh 6,430 8,170 9,050
ηs (Seasonal space heating efficiency)
% 148 141 137
Prated at -22°C
kW 10.3 12.3 13.3
Qhe Annual energy consumption (GCV)
Gj 23.1 29.4 32.6
Warm climate water outlet 35°C
General Annual energy consumption
kWh 1,950 2,350 2,480
Annual energy consumption (GCV)
Gj 7.02 8.46 8.92
ηs (Seasonal space heating efficiency)
% 192 199
Prated at 2°C
kW 9.06 10.9 11.4
Domestic hot water heating
Average climate ηwh (water heating efficiency)
% -
Cold climate ηwh (water heating efficiency)
% -
Warm climate ηwh (water heating efficiency)
% -
CONNECTABLE INDOOR UNITS
2-3 Capacity and Power inputEHBX04CB3V/ERLQ004CV3
EHBX08CB3V/ERLQ006CV3
EHBX08CB9W/ERLQ006CV3
EHBX08CB3V/ERLQ008CV3
EHBX08CB9W/ERLQ008CV3
EHBX11CB3V/ERLQ011CV3
Heating capacity Min. kW 1.80 (1) -
Nom. kW 4.40 (1) / 4.03 (2)
6.00 (1) / 5.67 (2) 7.40 (1) / 6.89 (2) 11.2 (1) / 11.0 (2)
Max. kW 5.12 (1) / 4.90 (2)
8.35 (1) / 7.95 (2) 10.0 (1) / 9.53 (2) 8.60 (3) / 8.60 (4)
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 11
• Outdoor Unit • ERLQ-CV3
2
12
2 Specifications
Cooling capacity Min. kW 2.00 (1) / 2.00 (2)
2.50 (1) / 2.50 (2) -
Nom. kW 4.08 (1) / 4.17 (2)
5.88 (1) / 4.84 (2) 6.20 (1) / 5.36 (2) 12.1 (1) / 11.7 (2)
Power input Heating Nom. kW 0.870 (1) / 1.13 (2)
1.27 (1) / 1.59 (2) 1.66 (1) / 2.01 (2) 2.43 (1) / 3.10 (2)
Max. kW - 3.13 (3) / 4.10 (4)
Cooling Nom. kW 0.900 (1) / 1.80 (2)
1.51 (1) / 2.07 (2) 1.64 (1) / 2.34 (2) 3.05 (1) / 4.31 (2)
COP 5.04 (1) / 3.58 (2)
4.74 (1) / 3.56 (2) 4.45 (1) / 3.42 (2) 4.60 (1) / 2.75 (3) / 3.55 (2) /
2.10 (4)
EER 4.55 (1) / 2.32 (2)
3.89 (1) / 2.34 (2) 3.79 (1) / 2.29 (2) 3.98 (1) / 2.72 (2)
Pump Nominal ESP unit Cooling kPa 55.0 (3) / 47.0 (4)
55.0 (3) / 39.0 (4) 50.0 (3) / 38.0 (4) 33.0 (5) / 3.00 (6)
Heating kPa 53.0 (5) / 56.0 (6)
45.0 (5) / 48.0 (6) 33.0 (5) / 38.0 (6) 37.0 (7) / 39.0 (8)
Water side Heat exchanger
Water flow rate Cooling Nom. l/min 12.0 (3) / 14.3 (4)
13.9 (3) / 19.4 (4) 15.4 (3) / 19.7 (4) 33.6 (5) / 43.1 (6)
Heating Nom. l/min 12.6 (5) / 11.6 (6)
17.2 (5) / 16.3 (6) 21.2 (5) / 19.8 (6) 32.1 (7) / 31.5 (8)
General Supplier/Manufacturer details
Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Name or trademark Daikin Europe N.V.
Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater No
Low-temperature heat pump No
Supplementary heater integrated
Yes
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 40.0 41.0
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 61.0 62.0 64.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating general Air to water unit Rated airflow (outdoor)
m³/h 2,700 2,820 5,400
Brine/water to water unit
Rated water/brine flow
m³/h - 0.00 - 0.00 -
Other Capacity control Inverter
Cdh (Degradation heating) 1.00
Pck (Crankcase heater mode)
kW 0.00 0.055
Poff (Off mode) kW 0.0080 0.055
Psb (Standby mode) kW 0.0080 0.055
Pto (Thermostat off) kW 0.0060 0.0070 0.0080 0.057
Integrated supplementary heater
NOx emission mg/kWh 0.00
Psup kW 3.00 9.00 3.00 9.00 3.00
Type of energy input Electrical
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Average climate water outlet 55°C
General SCOP 3.20 3.22 3.23 3.09
Annual energy consumption
kWh 2,356 3,369 4,064 6,260
Annual energy consumption (GCV)
Gj 8.48 12.1 14.6 22.6
ηs (Seasonal space heating efficiency)
% 125 126 120
Prated at -10°C
kW 3.70 5.30 6.40 9.99
Seasonal space heating eff. class
A++ A+
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.00
COPd 2.03 2.02 1.98 1.99
Pdh kW 3.36 4.50 5.47 8.83
PERd % 81.2 80.8 79.2 79.6
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00 0.990 1.00
COPd 3.08 3.17 3.24
Pdh kW 2.00 4.43 3.43 5.28
PERd % 123 127 130
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.990 0.950
COPd 4.27 4.20 4.31
Pdh kW 2.77 3.51 3.50 4.47
PERd % 171 168 172
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.990 0.930
COPd 6.33 5.82 6.41
Pdh kW 2.65 3.28 5.37
PERd % 253 233 256
Tol (temperature operating limit)
COPd 1.80 1.74 1.66 1.79
Pdh kW 3.76 4.62 6.18 9.08
PERd % 72.0 69.6 66.4 71.6
TOL °C -10.0
WTOL °C 55.0
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.00 0.680 0.220 0.910
Tbiv (bivalent temperature)
COPd 1.80 1.74 1.66 1.99
Pdh kW 3.76 5.09 6.18 8.83
PERd % 72.0 69.6 66.4 79.6
Tbiv °C -10.0 -9.00 -10.0 -7.00
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 13
• Outdoor Unit • ERLQ-CV3
2
14
2 Specifications
Space heating Cold climate water outlet 55°C
General Annual energy consumption
kWh 2,133 2,306 3,088 6,740
Annual energy consumption (GCV)
Gj 7.68 8.30 11.1 24.3
ηs (Seasonal space heating efficiency)
% 107 110 95.0
Prated at -22°C
kW 2.39 2.60 3.56 6.99
Warm climate water outlet 55°C
General Annual energy consumption
kWh 1,168 1,491 1,904 2,630
Annual energy consumption (GCV)
Gj 4.20 5.37 6.85 9.47
ηs (Seasonal space heating efficiency)
% 186 182 178 125
Prated at 2°C
kW 4.27 5.30 6.59 7.58
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Average climate water outlet 35°C
General SCOP 4.52 4.29 4.34 3.98
Annual energy consumption
kWh 1,980 2,540 3,489 5,380
Annual energy consumption (GCV)
Gj 7.13 9.14 12.6 19.4
ηs (Seasonal space heating efficiency)
% 178 169 171 156
Prated at -10°C
kW 4.40 5.34 7.40 11.2
Seasonal space heating eff. class
A++
A Condition (-7°CDB/-8°CWB)
COPd 3.01 2.69 2.63
Pdh kW 4.01 4.72 6.68 8.88
PERd % 120 108 105
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00 0.990 1.00
COPd 4.41 4.24 4.05
Pdh kW 2.40 3.90 6.03
PERd % 176 170 162
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.980 1.00 0.940
COPd 5.85 5.75 6.77
Pdh kW 1.70 2.59 5.74
PERd % 234 230 271
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.980 0.920
COPd 7.71 7.27 8.97
Pdh kW 39.2 2.61 6.50
PERd % 308 291 359
Tol (temperature operating limit)
COPd 2.61 2.29 2.34
Pdh kW 4.36 4.70 6.81 8.76
PERd % 104 91.6 93.6
TOL °C -10.0
WTOL °C 35.0
G Condition (-15°CDB/-)
COPd 0.00 -
Pdh kW 0.00 -
PERd % 0.00 -
Tbiv (bivalent temperature)
COPd 2.61 2.47 2.82
Pdh kW 4.36 4.93 7.14 9.09
PERd % 104 98.8 113
Tbiv °C -10.0 -8.00 -5.00
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.040 0.640 0.590 2.44
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 15
• Outdoor Unit • ERLQ-CV3
2
16
2 Specifications
Space heating Cold climate water outlet 35°C
General Annual energy consumption
kWh 1,450 2,040 2,480 6,430
ηs (Seasonal space heating efficiency)
% 151 153 151 148
Prated at -22°C
kW 2.28 3.25 3.89 10.3
Qhe Annual energy consumption (GCV)
Gj 5.20 7.34 8.91 23.1
Warm climate water outlet 35°C
General Annual energy consumption
kWh 905 1,270 1,570 1,950
Annual energy consumption (GCV)
Gj 3.26 4.56 5.67 7.02
ηs (Seasonal space heating efficiency)
% 269 259 251 192
Prated at 2°C
kW 4.81 6.40 7.68 9.06
Domestic hot water heating
General Function to fix water heating during off peak hours
Yes -
Average climate ηwh (water heating efficiency)
% -
Cold climate ηwh (water heating efficiency)
% -
Warm climate ηwh (water heating efficiency)
% -
CONNECTABLE INDOOR UNITS
2-4 Capacity and Power inputEHBX11CB9W/ERLQ011CV3
EHBX16CB3V/ERLQ014CV3
EHBX16CB9W/ERLQ014CV3
EHBX16CB9W/ERLQ016CV3
EHBX16CB3V/ERLQ016CV3
Heating capacity Nom. kW 11.2 / 11.0 14.5 / 13.6 16.0 / 15.2
Max. kW 8.60 / 8.60 10.6 / 10.8 11.4 / 10.9
Cooling capacity Nom. kW 12.1 / 11.7 12.7 / 12.6 13.8 / 13.1
Power input Heating Nom. kW 2.43 / 3.10 3.37 / 4.10 3.76 / 4.66
Max. kW 3.13 / 4.10 4.00 / 5.19 4.32 / 5.22
Cooling Nom. kW 3.05 / 4.31 3.21 / 5.08 3.74 / 5.73
COP 4.60 / 2.75 / 3.55 / 2.10
4.30 / 2.65 / 3.32 / 2.08 4.25 / 2.64 / 3.26 / 2.09
EER 3.98 / 2.72 3.96 / 2.47 3.69 / 2.29
Pump Nominal ESP unit Cooling kPa 33.0 / 3.00 64.0 / 32.0 61.0 / 23.0
Heating kPa 37.0 / 39.0 49.0 / 57.0 33.0 / 42.0
Water side Heat exchanger
Water flow rate Cooling Nom. l/min 33.6 / 43.1 36.0 / 46.0 37.6 / 48.0
Heating Nom. l/min 32.1 / 31.5 41.6 / 39.0 45.9 / 43.6
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
General Supplier/Manufacturer details
Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Name or trademark Daikin Europe N.V.
Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater No
Low-temperature heat pump No
Supplementary heater integrated
Yes
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 41.0 44.0
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 64.0 66.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating general Air to water unit Rated airflow (outdoor)
m³/h 5,400
Other Capacity control Inverter
Cdh (Degradation heating) 1.00
Pck (Crankcase heater mode)
kW 0.055
Poff (Off mode) kW 0.055
Psb (Standby mode) kW 0.055
Pto (Thermostat off) kW 0.057
Integrated supplementary heater
NOx emission mg/kWh
0.00
Psup kW 9.00 3.00 9.00 3.00
Type of energy input Electrical
Space heating Average climate water outlet 55°C
General SCOP 3.09 3.16 3.06
Annual energy consumption
kWh 6,260 7,900 8,970
Annual energy consumption (GCV)
Gj 22.6 28.4 32.3
ηs (Seasonal space heating efficiency)
% 120 123 119
Prated at -10°C
kW 9.99 12.7 13.9
Seasonal space heating eff. class
A+
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.00
COPd 1.99 1.76 1.78
Pdh kW 8.83 9.97 12.2
PERd % 79.6 70.4 71.2
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00
COPd 3.24 3.55 3.12
Pdh kW 5.28 6.76 7.61
PERd % 130 142 125
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 17
• Outdoor Unit • ERLQ-CV3
2
18
2 Specifications
Space heating Average climate water outlet 55°C
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.950 1.00
COPd 4.31 4.22 4.40
Pdh kW 4.47 4.66 4.83
PERd % 172 169 176
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.930 0.940 0.930
COPd 6.41 5.44 6.36
Pdh kW 5.37 5.26 5.38
PERd % 256 218 254
Tol (temperature operating limit)
COPd 1.79 1.75 1.71
Pdh kW 9.08 12.2 13.3
PERd % 71.6 70.0 68.4
TOL °C -10.0
WTOL °C 55.0
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.910 0.550 0.580
Tbiv (bivalent temperature)
COPd 1.99 1.92 1.78
Pdh kW 8.83 11.0 12.2
PERd % 79.6 76.8 71.2
Tbiv °C -7.00 -6.00 -7.00
Cold climate water outlet 55°C
General Annual energy consumption
kWh 6,740 7,870 8,580
Annual energy consumption (GCV)
Gj 24.3 28.3 30.9
ηs (Seasonal space heating efficiency)
% 95.0 95.5 98.3
Prated at -22°C
kW 6.99 8.15 9.12
Warm climate water outlet 55°C
General Annual energy consumption
kWh 2,630 3,270 3,420
Annual energy consumption (GCV)
Gj 9.47 11.8 12.3
ηs (Seasonal space heating efficiency)
% 125 135 136
Prated at 2°C
kW 7.58 9.84 10.3
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Average climate water outlet 35°C
General SCOP 3.98 3.90 3.80
Annual energy consumption
kWh 5,380 7,250 8,270
Annual energy consumption (GCV)
Gj 19.4 26.1 29.8
ηs (Seasonal space heating efficiency)
% 156 153 149
Prated at -10°C
kW 11.2 14.5 16.0
Seasonal space heating eff. class
A++ A+
A Condition (-7°CDB/-8°CWB)
COPd 2.63 2.33
Pdh kW 8.88 10.7 12.4
PERd % 105 93.2
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00
COPd 4.05 4.07 3.74
Pdh kW 6.03 7.71 8.62
PERd % 162 163 150
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.940 1.00 0.940
COPd 6.77 5.71 6.77
Pdh kW 5.74 5.05 5.74
PERd % 271 228 271
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.920 0.930 0.920
COPd 8.97 6.71 8.97
Pdh kW 6.50 5.16 6.50
PERd % 359 268 359
Tol (temperature operating limit)
COPd 2.34 2.60 2.05
Pdh kW 8.76 12.6 11.7
PERd % 93.6 104 82.0
TOL °C -10.0
WTOL °C 35.0
Tbiv (bivalent temperature)
COPd 2.82 2.83 2.56
Pdh kW 9.09 11.6 12.1
PERd % 113 102
Tbiv °C -5.00 -4.00
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 2.44 1.93 4.35
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 19
• Outdoor Unit • ERLQ-CV3
2
20
2 Specifications
Notes
(1) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
(2) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
(3) Tamb 35°C - LWE 7°C (DT=5°C)
(4) Tamb 35°C - LWE 18°C (DT=5°C)
(5) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
(6) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
(7) Contains fluorinated greenhouse gases
(8) Condition 3: heating Ta DB -7°C (RH85%) - LWC 35°C
Condition 4: heating Ta DB -7°C (RH85%) - LWC 45°C
Cold climate water outlet 35°C
General Annual energy consumption
kWh 6,430 8,170 9,050
ηs (Seasonal space heating efficiency)
% 148 141 137
Prated at -22°C
kW 10.3 12.3 13.3
Qhe Annual energy consumption (GCV)
Gj 23.1 29.4 32.6
Warm climate water outlet 35°C
General Annual energy consumption
kWh 1,950 2,350 2,480
Annual energy consumption (GCV)
Gj 7.02 8.46 8.92
ηs (Seasonal space heating efficiency)
% 192 199
Prated at 2°C
kW 9.06 10.9 11.4
Domestic hot water heating
Average climate ηwh (water heating efficiency)
% -
Cold climate ηwh (water heating efficiency)
% -
Warm climate ηwh (water heating efficiency)
% -
CONNECTABLE INDOOR UNITS
2-5 Capacity and Power input
EHVH04S18CB3V/
ERLQ004CV3
EHVH08S26CB9W/
ERLQ006CV3
EHVH08S18CB3V/
ERLQ006CV3
EHVH08S18CB3V/
ERLQ008CV3
EHVH08S26CB9W/
ERLQ008CV3
EHVH11S18CB3V/
ERLQ011CV3
Heating capacity Min. kW 1.80 (1) -
Nom. kW 4.40 (1) / 4.03 (2)
6.00 (1) / 5.67 (2) 7.40 (1) / 6.89 (2) 11.2 (1) / 11.0 (2)
Max. kW 5.12 (1) / 4.90 (2)
8.35 (1) / 7.95 (2) 10.0 (1) / 9.53 (2) 8.60 (3) / 8.60 (4)
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Power input Heating Nom. kW 0.870 (1) / 1.13 (2)
1.27 (1) / 1.59 (2) 1.66 (1) / 2.01 (2) 2.43 (1) / 3.10 (2)
Max. kW - 3.13 (3) / 4.10 (4)
COP 5.04 (1) / 3.58 (2)
4.74 (1) / 3.56 (2) 4.45 (1) / 3.42 (2) 4.60 (1) / 2.75 (3) / 3.55 (2) /
2.10 (4)
Tank Name Stainless steel domestic hot
water tank 180 l
- Stainless steel domestic hot
water tank 180 l
Pump Nominal ESP unit Heating kPa 53.0 (5) / 56.0 (6)
45.0 (5) / 47.0 (6) 33.0 (5) / 37.0 (6) 34.2 (7) / 35.9 (8)
Water side Heat exchanger
Water flow rate Heating Nom. l/min 12.6 (5) / 11.6 (6)
17.2 (5) / 16.3 (6) 21.2 (5) / 19.8 (6) 32.1 (7) / 31.5 (8)
General Supplier/Manufacturer details
Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Name or trademark Daikin Europe N.V.
Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater Yes
Low-temperature heat pump No
Supplementary heater integrated
Yes
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 42.0
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 61.0 62.0 64.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating general Air to water unit Rated airflow (outdoor)
m³/h 2,700 2,820 5,400
Brine/water to water unit
Rated water/brine flow
m³/h - 0.00 -
Other Capacity control Inverter
Cdh (Degradation heating) 1.00
Pck (Crankcase heater mode)
kW 0.00 0.055
Poff (Off mode) kW 0.0080 0.055
Psb (Standby mode) kW 0.0080 0.055
Pto (Thermostat off) kW 0.0060 0.0070 0.0080 0.057
Integrated supplementary heater
NOx emission mg/kWh 0.00
Psup kW 3.00 9.00 3.00
Type of energy input Electrical
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 21
• Outdoor Unit • ERLQ-CV3
2
22
2 Specifications
Space heating Average climate water outlet 55°C
General SCOP 3.20 3.22 3.23 3.09
Annual energy consumption
kWh 2,356 3,369 4,064 6,260
Annual energy consumption (GCV)
Gj 8.48 12.1 14.6 22.6
ηs (Seasonal space heating efficiency)
% 125 126 120
Prated at -10°C
kW 3.70 5.30 6.40 9.99
Seasonal space heating eff. class
A++ A+
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.00
COPd 2.03 2.02 1.98 1.99
Pdh kW 3.36 4.50 5.47 8.83
PERd % 81.2 80.8 79.2 79.6
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00 0.990 1.00
COPd 3.08 3.17 3.24
Pdh kW 2.00 4.43 3.43 5.28
PERd % 123 127 130
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.990 0.950
COPd 4.27 4.20 4.31
Pdh kW 2.77 3.51 3.50 4.47
PERd % 171 168 172
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.990 0.930
COPd 6.33 5.82 6.41
Pdh kW 2.65 3.28 5.37
PERd % 253 233 256
Tol (temperature operating limit)
COPd 1.80 1.74 1.66 1.79
Pdh kW 3.76 4.62 6.18 9.08
PERd % 72.0 69.6 66.4 71.6
TOL °C -10.0
WTOL °C 55.0
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.00 0.680 0.220 0.910
Tbiv (bivalent temperature)
COPd 1.80 1.74 1.66 1.99
Pdh kW 3.76 5.09 6.18 8.83
PERd % 72.0 69.6 66.4 79.6
Tbiv °C -10.0 -9.00 -10.0 -7.00
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Cold climate water outlet 55°C
General Annual energy consumption
kWh 2,133 2,306 3,088 6,740
Annual energy consumption (GCV)
Gj 7.68 8.30 11.1 24.3
ηs (Seasonal space heating efficiency)
% 107 110 95.0
Prated at -22°C
kW 2.39 2.60 3.56 6.99
Warm climate water outlet 55°C
General Annual energy consumption
kWh 1,168 1,491 1,904 2,630
Annual energy consumption (GCV)
Gj 4.20 5.37 6.85 9.47
ηs (Seasonal space heating efficiency)
% 186 182 178 125
Prated at 2°C
kW 4.27 5.30 6.59 7.58
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 23
• Outdoor Unit • ERLQ-CV3
2
24
2 Specifications
Space heating Average climate water outlet 35°C
General SCOP 4.52 4.29 4.34 3.98
Annual energy consumption
kWh 1,980 2,540 3,489 5,380
Annual energy consumption (GCV)
Gj 7.13 9.14 12.6 19.4
ηs (Seasonal space heating efficiency)
% 178 169 171 156
Prated at -10°C
kW 4.40 5.34 7.40 11.2
Seasonal space heating eff. class
A++
A Condition (-7°CDB/-8°CWB)
COPd 3.01 2.69 2.63
Pdh kW 4.01 4.72 6.68 8.88
PERd % 120 108 105
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00 0.990 1.00
COPd 4.41 4.24 4.05
Pdh kW 2.40 3.90 6.03
PERd % 176 170 162
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.980 1.00 0.940
COPd 5.85 5.75 6.77
Pdh kW 1.70 2.59 5.74
PERd % 234 230 271
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.980 0.920
COPd 7.71 7.27 8.97
Pdh kW 39.2 2.61 6.50
PERd % 308 291 359
Tol (temperature operating limit)
COPd 2.61 2.29 2.34
Pdh kW 4.36 4.70 6.81 8.76
PERd % 104 91.6 93.6
TOL °C -10.0
WTOL °C 35.0
G Condition (-15°CDB/-)
COPd 0.00 -
Pdh kW 0.00 -
PERd % 0.00 -
Tbiv (bivalent temperature)
COPd 2.61 2.47 2.82
Pdh kW 4.36 4.93 7.14 9.09
PERd % 104 98.8 113
Tbiv °C -10.0 -8.00 -5.00
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.040 0.640 0.590 2.44
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Cold climate water outlet 35°C
General Annual energy consumption
kWh - 6,430
ηs (Seasonal space heating efficiency)
% - 148
Prated at -22°C
kW - 10.3
Qhe Annual energy consumption (GCV)
Gj - 23.1
Warm climate water outlet 35°C
General Annual energy consumption
kWh - 1,950
Annual energy consumption (GCV)
Gj - 7.02
ηs (Seasonal space heating efficiency)
% - 192
Prated at 2°C
kW - 9.06
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 25
• Outdoor Unit • ERLQ-CV3
2
26
2 Specifications
Domestic hot water heating
General Declared load profile L XL L XL L
Function to fix water heating during off peak hours
Yes
Average climate AEC (Annual electricity consumption)
kWh 1,084 1,871 1,194 1,871 1,170
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 95.0 90.0 86.4 90.0 87.4
Qelec (Daily electricity consumption)
kWh 4.93 8.50 5.43 8.50 5.32
Qfuel (Daily fuel consumption)
kWh 0.00
Water heating energy efficiency class
A
Cold climate AEC (Annual electricity consumption)
kWh 1,221 2,037 1,332 2,037 1,340
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 84.0 83.0 77.5 83.0 76.6
Qelec (Daily electricity consumption)
kWh 5.55 9.26 6.05 9.26 6.08
Qfuel (Daily fuel consumption)
kWh 0.00
Warm climate AEC (Annual electricity consumption)
kWh 966 1,784 1,123 1,784 1,110
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 106 94.0 91.8 94.0 92.3
Qelec (Daily electricity consumption)
kWh 4.39 8.11 5.10 8.11 5.04
Qfuel (Daily fuel consumption)
kWh - 0.00
CONNECTABLE INDOOR UNITS
2-6 Capacity and Power inputEHVH11S26CB9W/
ERLQ011CV3EHVH16S18CB3V/
ERLQ014CV3EHVH16S26CB9W/
ERLQ014CV3EHVH16S18CB3V/
ERLQ016CV3EHVH16S26CB9W/
ERLQ016CV3
Heating capacity Nom. kW 11.2 / 11.0 14.5 / 13.6 16.0 / 15.2
Max. kW 8.60 / 8.60 10.6 / 10.8 11.4 / 10.9
Power input Heating Nom. kW 2.43 / 3.10 3.37 / 4.10 3.76 / 4.66
Max. kW 3.13 / 4.10 4.00 / 5.19 4.32 / 5.22
COP 4.60 / 2.75 / 3.55 / 2.10
4.30 / 2.65 / 3.32 / 2.08 4.25 / 2.64 / 3.26 / 2.09
Tank Name Stainless steel domestic hot
water tank 260 l
Stainless steel domestic hot
water tank 180 l
Stainless steel domestic hot
water tank 260 l
Stainless steel domestic hot
water tank 180 l
Stainless steel domestic hot
water tank 260 l
Pump Nominal ESP unit Heating kPa 34.2 / 35.9 43.2 / 51.2 26.8 / 36.3
Water side Heat exchanger
Water flow rate Heating Nom. l/min 32.1 / 31.5 41.6 / 39.0 45.9 / 43.6
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
General Supplier/Manufacturer details
Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Name or trademark Daikin Europe N.V.
Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater Yes
Low-temperature heat pump No
Supplementary heater integrated Yes
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 42.0 44.0
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 64.0 66.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating general Air to water unit Rated airflow (outdoor)
m³/h 5,400
Other Capacity control Inverter
Cdh (Degradation heating) 1.00
Pck (Crankcase heater mode)
kW 0.055
Poff (Off mode) kW 0.055
Psb (Standby mode) kW 0.055
Pto (Thermostat off) kW 0.057
Integrated supplementary heater
NOx emission mg/kWh 0.00
Psup kW 9.00 3.00 9.00 3.00 9.00
Type of energy input Electrical
Space heating Average climate water outlet 55°C
General SCOP 3.09 3.16 3.06
Annual energy consumption
kWh 6,260 7,900 8,970
Annual energy consumption (GCV)
Gj 22.6 28.4 32.3
ηs (Seasonal space heating efficiency)
% 120 123 119
Prated at -10°C
kW 9.99 12.7 13.9
Seasonal space heating eff. class
A+
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.00
COPd 1.99 1.76 1.78
Pdh kW 8.83 9.97 12.2
PERd % 79.6 70.4 71.2
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00
COPd 3.24 3.55 3.12
Pdh kW 5.28 6.76 7.61
PERd % 130 142 125
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.950 1.00
COPd 4.31 4.22 4.40
Pdh kW 4.47 4.66 4.83
PERd % 172 169 176
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 27
• Outdoor Unit • ERLQ-CV3
2
28
2 Specifications
Space heating Average climate water outlet 55°C
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.930 0.940 0.930
COPd 6.41 5.44 6.36
Pdh kW 5.37 5.26 5.38
PERd % 256 218 254
Tol (temperature operating limit)
COPd 1.79 1.75 1.71
Pdh kW 9.08 12.2 13.3
PERd % 71.6 70.0 68.4
TOL °C -10.0
WTOL °C 55.0
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.910 0.550 0.580
Tbiv (bivalent temperature)
COPd 1.99 1.92 1.78
Pdh kW 8.83 11.0 12.2
PERd % 79.6 76.8 71.2
Tbiv °C -7.00 -6.00 -7.00
Cold climate water outlet 55°C
General Annual energy consumption
kWh 6,740 7,870 8,580
Annual energy consumption (GCV)
Gj 24.3 28.3 30.9
ηs (Seasonal space heating efficiency)
% 95.0 95.5 98.3
Prated at -22°C
kW 6.99 8.15 9.12
Warm climate water outlet 55°C
General Annual energy consumption
kWh 2,630 3,270 3,420
Annual energy consumption (GCV)
Gj 9.47 11.8 12.3
ηs (Seasonal space heating efficiency)
% 125 135 136
Prated at 2°C
kW 7.58 9.84 10.3
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Average climate water outlet 35°C
General SCOP 3.98 3.90 3.80
Annual energy consumption
kWh 5,380 7,250 8,270
Annual energy consumption (GCV)
Gj 19.4 26.1 29.8
ηs (Seasonal space heating efficiency)
% 156 153 149
Prated at -10°C
kW 11.2 14.5 16.0
Seasonal space heating eff. class
A++ A+
A Condition (-7°CDB/-8°CWB)
COPd 2.63 2.33
Pdh kW 8.88 10.7 12.4
PERd % 105 93.2
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00
COPd 4.05 4.07 3.74
Pdh kW 6.03 7.71 8.62
PERd % 162 163 150
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.940 1.00 0.940
COPd 6.77 5.71 6.77
Pdh kW 5.74 5.05 5.74
PERd % 271 228 271
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.920 0.930 0.920
COPd 8.97 6.71 8.97
Pdh kW 6.50 5.16 6.50
PERd % 359 268 359
Tol (temperature operating limit)
COPd 2.34 2.60 2.05
Pdh kW 8.76 12.6 11.7
PERd % 93.6 104 82.0
TOL °C -10.0
WTOL °C 35.0
Tbiv (bivalent temperature)
COPd 2.82 2.83 2.56
Pdh kW 9.09 11.6 12.1
PERd % 113 102
Tbiv °C -5.00 -4.00
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 2.44 1.93 4.35
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 29
• Outdoor Unit • ERLQ-CV3
2
30
2 Specifications
Space heating Cold climate water outlet 35°C
General Annual energy consumption
kWh 6,430 8,170 9,050
ηs (Seasonal space heating efficiency)
% 148 141 137
Prated at -22°C
kW 10.3 12.3 13.3
Qhe Annual energy consumption (GCV)
Gj 23.1 29.4 32.6
Warm climate water outlet 35°C
General Annual energy consumption
kWh 1,950 2,350 2,480
Annual energy consumption (GCV)
Gj 7.02 8.46 8.92
ηs (Seasonal space heating efficiency)
% 192 199
Prated at 2°C
kW 9.06 10.9 11.4
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Notes
(1) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
(2) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
(3) Tamb 35°C - LWE 7°C (DT=5°C)
(4) Tamb 35°C - LWE 18°C (DT=5°C)
(5) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
(6) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
(7) Contains fluorinated greenhouse gases
(8) Condition 3: heating Ta DB -7°C (RH85%) - LWC 35°C
Condition 4: heating Ta DB -7°C (RH85%) - LWC 45°C
Domestic hot water heating
General Declared load profile XL L XL L XL
Function to fix water heating during off peak hours
Yes
Average climate AEC (Annual electricity consumption)
kWh 1,720 1,170 1,720 1,170 1,720
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 97.7 87.4 97.7 87.4 97.7
Qelec (Daily electricity consumption)
kWh 7.83 5.32 7.83 5.32 7.83
Qfuel (Daily fuel consumption)
kWh 0.00
Water heating energy efficiency class
A
Cold climate AEC (Annual electricity consumption)
kWh 1,980 1,340 1,980 1,340 1,980
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 85.1 76.6 85.1 76.6 85.1
Qelec (Daily electricity consumption)
kWh 8.99 6.08 8.99 6.08 8.99
Qfuel (Daily fuel consumption)
kWh 0.00
Warm climate AEC (Annual electricity consumption)
kWh 1,630 1,110 1,630 1,110 1,630
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 103 92.3 103 92.3 103
Qelec (Daily electricity consumption)
kWh 7.40 5.04 7.40 5.04 7.40
Qfuel (Daily fuel consumption)
kWh 0.00
CONNECTABLE INDOOR UNITS
2-7 Capacity and Power input EHVH04S18CB3VF/ERLQ004CV3 EHVH08S18CB3VF/ERLQ006CV3 EHVH08S18CB3VF/ERLQ008CV3
Heating capacity Min. kW 1.80 (1)
Nom. kW 4.40 (1) / 4.03 (2) 6.00 (1) / 5.67 (2) 7.40 (1) / 6.89 (2)
Max. kW 5.12 (1) / 4.90 (2) 8.35 (1) / 7.95 (2) 10.0 (1) / 9.53 (2)
Power input Heating Nom. kW 0.870 (1) / 1.13 (2) 1.27 (1) / 1.59 (2) 1.66 (1) / 2.01 (2)
COP 5.04 (1) / 3.58 (2) 4.74 (1) / 3.56 (2) 4.45 (1) / 3.42 (2)
Tank Name Stainless steel domestic hot water tank 180 l
-
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 31
• Outdoor Unit • ERLQ-CV3
2
32
2 Specifications
Pump Nominal ESP unit Heating kPa 53.0 (3) / 56.0 (4) 45.0 (3) / 47.0 (4) 33.0 (3) / 37.0 (4)
Water side Heat exchanger
Water flow rate Heating Nom. l/min 12.6 (3) / 11.6 (4) 17.2 (3) / 16.3 (4) 21.2 (3) / 19.8 (4)
General Supplier/Manufacturer details
Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Name or trademark Daikin Europe N.V.
Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater Yes
Low-temperature heat pump No
Supplementary heater integrated
Yes
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 42.0
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 61.0 62.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating general Air to water unit Rated airflow (outdoor)
m³/h 2,700 2,820
Brine/water to water unit
Rated water/brine flow m³/h - 0.00
Other Capacity control Inverter
Cdh (Degradation heating) 1.00
Pck (Crankcase heater mode)
kW 0.00
Poff (Off mode) kW 0.0080
Psb (Standby mode) kW 0.0080
Pto (Thermostat off) kW 0.0060 0.0070 0.0080
Integrated supplementary heater
NOx emission mg/kWh
0.00
Psup kW 3.00
Type of energy input Electrical
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Average climate water outlet 55°C
General SCOP 3.20 3.22 3.23
Annual energy consumption
kWh 2,356 3,369 4,064
Annual energy consumption (GCV)
Gj 8.48 12.1 14.6
ηs (Seasonal space heating efficiency)
% 125 126
Prated at -10°C
kW 3.70 5.30 6.40
Seasonal space heating eff. class
A++
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.00
COPd 2.03 2.02 1.98
Pdh kW 3.36 4.50 5.47
PERd % 81.2 80.8 79.2
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00 0.990 1.00
COPd 3.08 3.17
Pdh kW 2.00 4.43 3.43
PERd % 123 127
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.990
COPd 4.27 4.20
Pdh kW 2.77 3.51 3.50
PERd % 171 168
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.990
COPd 6.33 5.82
Pdh kW 2.65 3.28
PERd % 253 233
Tol (temperature operating limit)
COPd 1.80 1.74 1.66
Pdh kW 3.76 4.62 6.18
PERd % 72.0 69.6 66.4
TOL °C -10.0
WTOL °C 55.0
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.00 0.680 0.220
Tbiv (bivalent temperature)
COPd 1.80 1.74 1.66
Pdh kW 3.76 5.09 6.18
PERd % 72.0 69.6 66.4
Tbiv °C -10.0 -9.00 -10.0
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 33
• Outdoor Unit • ERLQ-CV3
2
34
2 Specifications
Space heating Cold climate water outlet 55°C
General Annual energy consumption
kWh 2,133 2,306 3,088
Annual energy consumption (GCV)
Gj 7.68 8.30 11.1
ηs (Seasonal space heating efficiency)
% 107 110
Prated at -22°C
kW 2.39 2.60 3.56
Warm climate water outlet 55°C
General Annual energy consumption
kWh 1,168 1,491 1,904
Annual energy consumption (GCV)
Gj 4.20 5.37 6.85
ηs (Seasonal space heating efficiency)
% 186 182 178
Prated at 2°C
kW 4.27 5.30 6.59
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Average climate water outlet 35°C
General SCOP 4.52 4.29 4.34
Annual energy consumption
kWh 1,980 2,540 3,489
Annual energy consumption (GCV)
Gj 7.13 9.14 12.6
ηs (Seasonal space heating efficiency)
% 178 169 171
Prated at -10°C
kW 4.40 5.34 7.40
Seasonal space heating eff. class
A++
A Condition (-7°CDB/-8°CWB)
COPd 3.01 2.69
Pdh kW 4.01 4.72 6.68
PERd % 120 108
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00 0.990 1.00
COPd 4.41 4.24
Pdh kW 2.40 3.90
PERd % 176 170
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.980 1.00
COPd 5.85 5.75
Pdh kW 1.70 2.59
PERd % 234 230
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.980
COPd 7.71 7.27
Pdh kW 39.2 2.61
PERd % 308 291
Tol (temperature operating limit)
COPd 2.61 2.29
Pdh kW 4.36 4.70 6.81
PERd % 104 91.6
TOL °C -10.0
WTOL °C 35.0
G Condition (-15°CDB/-)
COPd 0.00
Pdh kW 0.00
PERd % 0.00
Tbiv (bivalent temperature)
COPd 2.61 2.47
Pdh kW 4.36 4.93 7.14
PERd % 104 98.8
Tbiv °C -10.0 -8.00
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.040 0.640 0.590
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 35
• Outdoor Unit • ERLQ-CV3
2
36
2 Specifications
Notes
(1) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
(2) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
(3) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
(4) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
Tamb 35°C - LWE 7°C (DT=5°C)
Tamb 35°C - LWE 18°C (DT=5°C)
Contains fluorinated greenhouse gases
Space heating Cold climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Qhe Annual energy consumption (GCV)
Gj -
Warm climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Domestic hot water heating
General Declared load profile L
Function to fix water heating during off peak hours
Yes
Average climate AEC (Annual electricity consumption)
kWh 1,084 1,194
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 95.0 86.4
Qelec (Daily electricity consumption)
kWh 4.93 5.43
Qfuel (Daily fuel consumption)
kWh 0.00
Water heating energy efficiency class
A
Cold climate AEC (Annual electricity consumption)
kWh 1,221 1,332
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 84.0 77.5
Qelec (Daily electricity consumption)
kWh 5.55 6.05
Qfuel (Daily fuel consumption)
kWh 0.00
Warm climate AEC (Annual electricity consumption)
kWh 966 1,123
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 106 91.8
Qelec (Daily electricity consumption)
kWh 4.39 5.10
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
CONNECTABLE INDOOR UNITS
2-8 Capacity and Power input
EHVX04S18CB3V/
ERLQ004CV3
EHVX08S18CB3V/
ERLQ006CV3
EHVX08S26CB9W/
ERLQ006CV3
EHVX08S18CB3V/
ERLQ008CV3
EHVX08S26CB9W/
ERLQ008CV3
EHVX11S18CB3V/
ERLQ011CV3
Heating capacity Min. kW 1.80 (1) -
Nom. kW 4.40 (1) / 4.03 (2)
6.00 (1) / 5.67 (2) 7.40 (1) / 6.89 (2) 11.2 (1) / 11.0 (2)
Max. kW 5.12 (1) / 4.90 (2)
8.35 (1) / 7.95 (2) 10.0 (1) / 9.53 (2) 8.60 (3) / 8.60 (4)
Cooling capacity Min. kW 2.00 (1) / 2.00 (2)
2.50 (1) / 2.50 (2) -
Nom. kW 4.08 (1) / 4.17 (2)
5.88 (1) / 4.84 (2) 6.20 (1) / 5.36 (2) 12.1 (1) / 11.7 (2)
Power input Heating Nom. kW 0.870 (1) / 1.13 (2)
1.27 (1) / 1.59 (2) 1.66 (1) / 2.01 (2) 2.43 (1) / 3.10 (2)
Max. kW - 3.13 (3) / 4.10 (4)
Cooling Nom. kW 0.900 (1) / 1.80 (2)
1.51 (1) / 2.07 (2) 1.64 (1) / 2.34 (2) 3.05 (1) / 4.31 (2)
COP 5.04 (1) / 3.58 (2)
4.74 (1) / 3.56 (2) 4.45 (1) / 3.42 (2) 4.60 (1) / 2.75 (3) / 3.55 (2) /
2.10 (4)
EER 4.55 (1) / 2.32 (2)
3.89 (1) / 2.34 (2) 3.79 (1) / 2.29 (2) 3.98 (1) / 2.72 (2)
Tank Name - Stainless steel domestic hot
water tank 180 l
Pump Nominal ESP unit Cooling kPa 54.0 (3) / 47.0 (4)
54.0 (3) / 38.0 (4) 50.0 (3) / 37.0 (4) 29.8 (5) / 1.30 (6)
Heating kPa 53.0 (5) / 56.0 (6)
45.0 (5) / 47.0 (6) 33.0 (5) / 37.0 (6) 34.2 (7) / 35.9 (8)
Water side Heat exchanger
Water flow rate Cooling Nom. l/min 12.0 (3) / 14.3 (4)
13.9 (3) / 19.4 (4) 15.4 (3) / 19.7 (4) 33.6 (5) / 43.1 (6)
Heating Nom. l/min 12.6 (5) / 11.6 (6)
17.2 (5) / 16.3 (6) 21.2 (5) / 19.8 (6) 32.1 (7) / 31.5 (8)
General Supplier/Manufacturer details
Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Name or trademark Daikin Europe N.V.
Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater Yes
Low-temperature heat pump No
Supplementary heater integrated
Yes
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 42.0
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 61.0 62.0 64.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
• Heating • ERLQ-CV3 37
• Outdoor Unit • ERLQ-CV3
2
38
2 Specifications
Space heating general Air to water unit Rated airflow (outdoor)
m³/h 2,700 2,820 5,400
Brine/water to water unit
Rated water/brine flow
m³/h - 0.00 -
Other Capacity control Inverter
Cdh (Degradation heating) 1.00
Pck (Crankcase heater mode)
kW 0.00 0.055
Poff (Off mode) kW 0.0080 0.055
Psb (Standby mode) kW 0.0080 0.055
Pto (Thermostat off) kW 0.0060 0.0070 0.0080 0.057
Integrated supplementary heater
NOx emission mg/kWh
0.00
Psup kW 3.00 9.00 3.00 9.00 3.00
Type of energy input Electrical
Space heating Average climate water outlet 55°C
General SCOP 3.20 3.22 3.23 3.09
Annual energy consumption
kWh 2,356 3,369 4,064 6,260
Annual energy consumption (GCV)
Gj 8.48 12.1 14.6 22.6
ηs (Seasonal space heating efficiency)
% 125 126 120
Prated at -10°C
kW 3.70 5.30 6.40 9.99
Seasonal space heating eff. class
A++ A+
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.00
COPd 2.03 2.02 1.98 1.99
Pdh kW 3.36 4.50 5.47 8.83
PERd % 81.2 80.8 79.2 79.6
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00 0.990 1.00
COPd 3.08 3.17 3.24
Pdh kW 2.00 4.43 3.43 5.28
PERd % 123 127 130
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.990 0.950
COPd 4.27 4.20 4.31
Pdh kW 2.77 3.51 3.50 4.47
PERd % 171 168 172
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.990 0.930
COPd 6.33 5.82 6.41
Pdh kW 2.65 3.28 5.37
PERd % 253 233 256
Tol (temperature operating limit)
COPd 1.80 1.74 1.66 1.79
Pdh kW 3.76 4.62 6.18 9.08
PERd % 72.0 69.6 66.4 71.6
TOL °C -10.0
WTOL °C 55.0
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Average climate water outlet 55°C
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.00 0.680 0.220 0.910
Tbiv (bivalent temperature)
COPd 1.80 1.74 1.66 1.99
Pdh kW 3.76 5.09 6.18 8.83
PERd % 72.0 69.6 66.4 79.6
Tbiv °C -10.0 -9.00 -10.0 -7.00
Cold climate water outlet 55°C
General Annual energy consumption
kWh 2,133 2,306 3,088 6,740
Annual energy consumption (GCV)
Gj 7.68 8.30 11.1 24.3
ηs (Seasonal space heating efficiency)
% 107 110 95.0
Prated at -22°C
kW 2.39 2.60 3.56 6.99
Warm climate water outlet 55°C
General Annual energy consumption
kWh 1,168 1,491 1,904 2,630
Annual energy consumption (GCV)
Gj 4.20 5.37 6.85 9.47
ηs (Seasonal space heating efficiency)
% 186 182 178 125
Prated at 2°C
kW 4.27 5.30 6.59 7.58
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 39
• Outdoor Unit • ERLQ-CV3
2
40
2 Specifications
Space heating Average climate water outlet 35°C
General SCOP 4.52 4.29 4.34 3.98
Annual energy consumption
kWh 1,980 2,540 3,489 5,380
Annual energy consumption (GCV)
Gj 7.13 9.14 12.6 19.4
ηs (Seasonal space heating efficiency)
% 178 169 171 156
Prated at -10°C
kW 4.40 5.34 7.40 11.2
Seasonal space heating eff. class
A++
A Condition (-7°CDB/-8°CWB)
COPd 3.01 2.69 2.63
Pdh kW 4.01 4.72 6.68 8.88
PERd % 120 108 105
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00 0.990 1.00
COPd 4.41 4.24 4.05
Pdh kW 2.40 3.90 6.03
PERd % 176 170 162
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.980 1.00 0.940
COPd 5.85 5.75 6.77
Pdh kW 1.70 2.59 5.74
PERd % 234 230 271
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.980 0.920
COPd 7.71 7.27 8.97
Pdh kW 39.2 2.61 6.50
PERd % 308 291 359
Tol (temperature operating limit)
COPd 2.61 2.29 2.34
Pdh kW 4.36 4.70 6.81 8.76
PERd % 104 91.6 93.6
TOL °C -10.0
WTOL °C 35.0
G Condition (-15°CDB/-)
COPd 0.00 -
Pdh kW 0.00 -
PERd % 0.00 -
Tbiv (bivalent temperature)
COPd 2.61 2.47 2.82
Pdh kW 4.36 4.93 7.14 9.09
PERd % 104 98.8 113
Tbiv °C -10.0 -8.00 -5.00
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.040 0.640 0.590 2.44
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Cold climate water outlet 35°C
General Annual energy consumption
kWh - 6,430
ηs (Seasonal space heating efficiency)
% - 148
Prated at -22°C
kW - 10.3
Qhe Annual energy consumption (GCV)
Gj - 23.1
Warm climate water outlet 35°C
General Annual energy consumption
kWh - 1,950
Annual energy consumption (GCV)
Gj - 7.02
ηs (Seasonal space heating efficiency)
% - 192
Prated at 2°C
kW - 9.06
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 41
• Outdoor Unit • ERLQ-CV3
2
42
2 Specifications
Domestic hot water heating
General Declared load profile L XL L XL L
Function to fix water heating during off peak hours
Yes
Average climate AEC (Annual electricity consumption)
kWh 1,084 1,194 1,871 1,194 1,871 1,170
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 95.0 86.4 90.0 86.4 90.0 87.4
Qelec (Daily electricity consumption)
kWh 4.93 5.43 8.50 5.43 8.50 5.32
Qfuel (Daily fuel consumption)
kWh 0.00
Water heating energy efficiency class
A
Cold climate AEC (Annual electricity consumption)
kWh 1,221 1,332 2,037 1,332 2,037 1,340
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 84.0 77.5 83.0 77.5 83.0 76.6
Qelec (Daily electricity consumption)
kWh 5.55 6.05 9.26 6.05 9.26 6.08
Qfuel (Daily fuel consumption)
kWh 0.00
Warm climate AEC (Annual electricity consumption)
kWh 966 1,123 1,784 1,123 1,784 1,110
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 106 91.8 94.0 91.8 94.0 92.3
Qelec (Daily electricity consumption)
kWh 4.39 5.10 8.11 5.10 8.11 5.04
Qfuel (Daily fuel consumption)
kWh - 0.00
CONNECTABLE INDOOR UNITS
2-9 Capacity and Power inputEHVX11S26CB9W/
ERLQ011CV3EHVX16S18CB3V/
ERLQ014CV3EHVX16S26CB9W/
ERLQ014CV3EHVX16S18CB3V/
ERLQ016CV3EHVX16S26CB9W/
ERLQ016CV3
Heating capacity Nom. kW 11.2 / 11.0 14.5 / 13.6 16.0 / 15.2
Max. kW 8.60 / 8.60 10.6 / 10.8 11.4 / 10.9
Cooling capacity Nom. kW 12.1 / 11.7 12.7 / 12.6 13.8 / 13.1
Power input Heating Nom. kW 2.43 / 3.10 3.37 / 4.10 3.76 / 4.66
Max. kW 3.13 / 4.10 4.00 / 5.19 4.32 / 5.22
Cooling Nom. kW 3.05 / 4.31 3.21 / 5.08 3.74 / 5.73
COP 4.60 / 2.75 / 3.55 / 2.10
4.30 / 2.65 / 3.32 / 2.08 4.25 / 2.64 / 3.26 / 2.09
EER 3.98 / 2.72 3.96 / 2.47 3.69 / 2.29
Tank Name Stainless steel domestic hot
water tank 260 l
Stainless steel domestic hot
water tank 180 l
Stainless steel domestic hot
water tank 260 l
Stainless steel domestic hot
water tank 180 l
Stainless steel domestic hot
water tank 260 l
Pump Nominal ESP unit Cooling kPa 29.8 / 1.30 59.2 / 27.2 55.0 / 18.8
Heating kPa 34.2 / 35.9 43.2 / 51.2 26.8 / 36.3
Water side Heat exchanger
Water flow rate Cooling Nom. l/min 33.6 / 43.1 36.0 / 46.0 37.6 / 48.0
Heating Nom. l/min 32.1 / 31.5 41.6 / 39.0 45.9 / 43.6
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
General Supplier/Manufacturer details
Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Name or trademark Daikin Europe N.V.
Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater Yes
Low-temperature heat pump No
Supplementary heater integrated
Yes
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 42.0 44.0
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 64.0 66.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating general Air to water unit Rated airflow (outdoor)
m³/h 5,400
Other Capacity control Inverter
Cdh (Degradation heating) 1.00
Pck (Crankcase heater mode)
kW 0.055
Poff (Off mode) kW 0.055
Psb (Standby mode) kW 0.055
Pto (Thermostat off) kW 0.057
Integrated supplementary heater
NOx emission mg/kWh 0.00
Psup kW 9.00 3.00 9.00 3.00 9.00
Type of energy input Electrical
Space heating Average climate water outlet 55°C
General SCOP 3.09 3.16 3.06
Annual energy consumption
kWh 6,260 7,900 8,970
Annual energy consumption (GCV)
Gj 22.6 28.4 32.3
ηs (Seasonal space heating efficiency)
% 120 123 119
Prated at -10°C
kW 9.99 12.7 13.9
Seasonal space heating eff. class
A+
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.00
COPd 1.99 1.76 1.78
Pdh kW 8.83 9.97 12.2
PERd % 79.6 70.4 71.2
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00
COPd 3.24 3.55 3.12
Pdh kW 5.28 6.76 7.61
PERd % 130 142 125
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 43
• Outdoor Unit • ERLQ-CV3
2
44
2 Specifications
Space heating Average climate water outlet 55°C
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.950 1.00
COPd 4.31 4.22 4.40
Pdh kW 4.47 4.66 4.83
PERd % 172 169 176
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.930 0.940 0.930
COPd 6.41 5.44 6.36
Pdh kW 5.37 5.26 5.38
PERd % 256 218 254
Tol (temperature operating limit)
COPd 1.79 1.75 1.71
Pdh kW 9.08 12.2 13.3
PERd % 71.6 70.0 68.4
TOL °C -10.0
WTOL °C 55.0
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.910 0.550 0.580
Tbiv (bivalent temperature)
COPd 1.99 1.92 1.78
Pdh kW 8.83 11.0 12.2
PERd % 79.6 76.8 71.2
Tbiv °C -7.00 -6.00 -7.00
Cold climate water outlet 55°C
General Annual energy consumption
kWh 6,740 7,870 8,580
Annual energy consumption (GCV)
Gj 24.3 28.3 30.9
ηs (Seasonal space heating efficiency)
% 95.0 95.5 98.3
Prated at -22°C
kW 6.99 8.15 9.12
Warm climate water outlet 55°C
General Annual energy consumption
kWh 2,630 3,270 3,420
Annual energy consumption (GCV)
Gj 9.47 11.8 12.3
ηs (Seasonal space heating efficiency)
% 125 135 136
Prated at 2°C
kW 7.58 9.84 10.3
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Average climate water outlet 35°C
General SCOP 3.98 3.90 3.80
Annual energy consumption
kWh 5,380 7,250 8,270
Annual energy consumption (GCV)
Gj 19.4 26.1 29.8
ηs (Seasonal space heating efficiency)
% 156 153 149
Prated at -10°C
kW 11.2 14.5 16.0
Seasonal space heating eff. class
A++ A+
A Condition (-7°CDB/-8°CWB)
COPd 2.63 2.33
Pdh kW 8.88 10.7 12.4
PERd % 105 93.2
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00
COPd 4.05 4.07 3.74
Pdh kW 6.03 7.71 8.62
PERd % 162 163 150
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.940 1.00 0.940
COPd 6.77 5.71 6.77
Pdh kW 5.74 5.05 5.74
PERd % 271 228 271
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.920 0.930 0.920
COPd 8.97 6.71 8.97
Pdh kW 6.50 5.16 6.50
PERd % 359 268 359
Tol (temperature operating limit)
COPd 2.34 2.60 2.05
Pdh kW 8.76 12.6 11.7
PERd % 93.6 104 82.0
TOL °C -10.0
WTOL °C 35.0
Tbiv (bivalent temperature)
COPd 2.82 2.83 2.56
Pdh kW 9.09 11.6 12.1
PERd % 113 102
Tbiv °C -5.00 -4.00
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 2.44 1.93 4.35
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 45
• Outdoor Unit • ERLQ-CV3
2
46
2 Specifications
Space heating Cold climate water outlet 35°C
General Annual energy consumption
kWh 6,430 8,170 9,050
ηs (Seasonal space heating efficiency)
% 148 141 137
Prated at -22°C
kW 10.3 12.3 13.3
Qhe Annual energy consumption (GCV)
Gj 23.1 29.4 32.6
Warm climate water outlet 35°C
General Annual energy consumption
kWh 1,950 2,350 2,480
Annual energy consumption (GCV)
Gj 7.02 8.46 8.92
ηs (Seasonal space heating efficiency)
% 192 199
Prated at 2°C
kW 9.06 10.9 11.4
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Notes
(1) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
(2) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
(3) Tamb 35°C - LWE 7°C (DT=5°C)
(4) Tamb 35°C - LWE 18°C (DT=5°C)
(5) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
(6) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
(7) Contains fluorinated greenhouse gases
(8) Condition 3: heating Ta DB -7°C (RH85%) - LWC 35°C
Condition 4: heating Ta DB -7°C (RH85%) - LWC 45°C
Domestic hot water heating
General Declared load profile XL L XL L XL
Function to fix water heating during off peak hours
Yes
Average climate AEC (Annual electricity consumption)
kWh 1,720 1,170 1,720 1,170 1,720
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 97.7 87.4 97.7 87.4 97.7
Qelec (Daily electricity consumption)
kWh 7.83 5.32 7.83 5.32 7.83
Qfuel (Daily fuel consumption)
kWh 0.00
Water heating energy efficiency class
A
Cold climate AEC (Annual electricity consumption)
kWh 1,980 1,340 1,980 1,340 1,980
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 85.1 76.6 85.1 76.6 85.1
Qelec (Daily electricity consumption)
kWh 8.99 6.08 8.99 6.08 8.99
Qfuel (Daily fuel consumption)
kWh 0.00
Warm climate AEC (Annual electricity consumption)
kWh 1,630 1,110 1,630 1,110 1,630
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 103 92.3 103 92.3 103
Qelec (Daily electricity consumption)
kWh 7.40 5.04 7.40 5.04 7.40
Qfuel (Daily fuel consumption)
kWh 0.00
CONNECTABLE INDOOR UNITS
2-10 Capacity and Power inputEHSXB04P30B/ERLQ004CV3
EHSXB08P30B/ERLQ006CV3
EHSXB08P50B/ERLQ006CV3
EHSXB08P30B/ERLQ008CV3
EHSXB08P50B/ERLQ008CV3
EHSXB16P50B/ERLQ011CV3
Indoor unit EHSXB04P30BA
EHSXB08P30BA
EHSXB08P50BA
EHSXB08P30BA
EHSXB08P50BA
EHSXB16P50BA
Outdoor unit ERLQ004CAV3
ERLQ006CAV3 ERLQ008CAV3 ERLQ011CAV3
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 47
• Outdoor Unit • ERLQ-CV3
2
48
2 Specifications
Heating capacity Min. kW 1.80 (1) / 1.81 (2) -
Nom. kW 4.26 (3) / 3.47 (4) / 4.53 (1) /
3.98 (2)
5.14 (3) / 4.60 (4) / 6.06 (1) / 5.78 (2)
5.53 (3) / 5.51 (4) / 7.78 (1) / 7.27 (2)
5.95 (1) / 7.74 (2) / 11.80 (3) /
10.40 (4)
Max. kW 4.90 (1) / 5.12 (2)
8.35 (1) / 7.95 (2) 10.02 (1) / 9.53 (2) 11.38 (3) / 11.00 (4)
Cooling capacity Min. kW 2.0 (5) / 2.1 (6) 2.5 (5) / 2.6 (6)
Nom. kW 4.4 (5) / 4.0 (6) 5.2 (5) / 4.6 (6) 15.1 (5) / 11.7 (6)
Max. kW 5.9 (5) / 4.5 (6) 7.3 (5) / 5.5 (6) 8.4 (5) / 6.4 (6) 15.1 (5) / 11.7 (6)
Power input Heating Nom. kW 0.87 (5) / 1.04 (6) / 1.49 (3) /
0.85 (4)
1.30 (5) / 1.58 (6) / 1.88 (3) / 1.26 (4)
1.69 (5) / 2.04 (6) / 1.98 (3) / 1.56 (4)
2.57 (5) / 3.13 (6) / 2.43 (1) /
2.35 (2)
Max. kW 1.12 (5) / 1.44 (6)
1.99 (5) / 2.32 (6) 2.54 (5) / 2.96 (6) 2.64 (5) / 3.25 (6)
Cooling Nom. kW 1.05 (5) / 1.41 (6)
1.43 (5) / 1.85 (6) 4.55 (5) / 4.30 (6)
Max. kW 1.86 (5) / 2.04 (6)
2.27 (5) / 2.51 (6) 2.89 (5) / 3.20 (6) 4.53 (5) / 4.31 (6)
COP 5.23 (5) / 3.84 (6) / 2.85 (3) /
4.07 (4)
4.65 (5) / 3.66 (6) / 2.73 (3) / 3.64 (4)
4.60 (5) / 3.57 (6) / 2.78 (3) / 3.54 (4)
4.38 (5) / 3.32 (6) / 2.45 (1) /
3.29 (2)
EER 4.21 (5) / 2.85 (6)
3.65 (5) / 2.51 (6) 3.32 (5) / 2.72 (6)
Pump Type Grundfos UPM3 25-75 CHBL
Nominal ESP unit Cooling kPa 45.0 (7) / 48.0 (8)
44.0 (7) / 46.0 (8) -
Heating kPa 46.0 (9) / 48.0 (10)
40.0 (9) / 41.0 (10) 37.0 (9) / 36.0 (10) -
Water side Heat exchanger
Water flow rate Cooling Nom. l/min 12.7 (7) / 11.5 (8)
12.9 (7) / 13.3 (8) 43.3 (7) / 33.5 (8)
Heating Nom. l/min 13.0 (9) / 11.3 (10)
17.4 (9) / 16.6 (10) 22.3 (9) / 20.8 (10) 33.8 (9) / 29.8 (10)
General Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater Yes
Low-temperature heat pump No
Supplementary heater integrated No
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 39
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 61 62 64
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating general Air to water unit Rated airflow (outdoor)
m³/h 2,700 2,820 -
Other Capacity control Inverter
Cdh (Degradation heating) 0.9
Pck (Crankcase heater mode)
kW 0.000
Poff (Off mode) kW 0.011 0.012 0.050
Psb (Standby mode) kW 0.011 0.012 0.050
Pto (Thermostat off) kW 0.043 0.048 0.105
Integrated supplementary heater
Psup kW 9.0
Type of energy input Electrical
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Average climate water outlet 55°C
General Annual energy consumption
kWh 2,934 3,828 4,725 6,345
ηs (Seasonal space heating efficiency)
% 132 126 128
Prated at -10°C
kW 5 6 8 10
Seasonal space heating eff. class
A++
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 2.03 2.09 2.10 1.94
Pdh kW 4.2 5.3 5.4 9.0
PERd % 81.2 83.6 84.0 77.6
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 3.31 3.13 3.25 3.30
Pdh kW 2.6 3.1 3.9 5.4
PERd % 132.4 125.2 130.0 132.0
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0 0.9
COPd 4.43 4.09 4.42 4.26
Pdh kW 1.8 2.1 2.6 4.6
PERd % 177.2 163.6 176.8 170.4
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 6.55 5.99 6.30
Pdh kW 2.2 2.0 5.5
PERd % 262.0 239.6 252.0
Tol (temperature operating limit)
COPd 1.64 1.79 1.78
Pdh kW 4.1 5.1 9.1
PERd % 65.6 71.6 71.2
TOL °C -10
WTOL °C 55
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.7 0.9 2.4 1.0
Tbiv (bivalent temperature)
COPd 2.03 2.09 2.36 1.94
Pdh kW 4.2 5.3 5.8 9.0
PERd % 81.2 83.6 94.4 77.6
Tbiv °C -7 -4 -7
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 49
• Outdoor Unit • ERLQ-CV3
2
50
2 Specifications
Space heating Cold climate water outlet 55°C
General Annual energy consumption
kWh 3,069 4,008 4,575 8,185
ηs (Seasonal space heating efficiency)
% 110 104 109 101
Prated at -22°C
kW 4 5 9
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 2.30 2.47 2.41 1.98
Pdh kW 2.2 2.6 3.2 5.2
PERd % 92.0 98.8 96.4 79.2
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0 0.9 1.0
COPd 3.75 3.26 3.69 3.25
Pdh kW 1.4 2.0 2.4 3.2
PERd % 150.0 130.4 147.6 130.0
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.9
COPd 5.92 4.42 5.58 5.50
Pdh kW 1.6 2.6 3.2 5.2
PERd % 236.8 176.8 223.2 220.0
D Condition (12°CDB/11°CWB)
COPd 8.65 5.54 7.79 7.56
Pdh kW 1.6 3.0 3.6 6.1
PERd % 346.0 221.6 311.6 302.4
Tol (temperature operating limit)
COPd 0.89 1.05 0.98 1.22
Pdh kW 0.8 1.0 1.2 5.7
PERd % 35.6 42.0 39.2 48.8
TOL °C -20
WTOL °C 55
G Condition (-15°CDB/-)
COPd 1.25 1.42 1.33 1.51
Pdh kW 2.9 3.6 4.3 7.1
PERd % 50.0 56.8 53.2 60.4
Tbiv (bivalent temperature)
COPd 1.25 1.42 1.33 1.51
Pdh kW 2.9 3.6 4.3 7.1
PERd % 50.0 56.8 53.2 60.4
Tbiv °C -15
Rated heat output supplementary capacity
Psup (at Tdesign -22°C)
kW 3.5 4.4 5.2 3.4
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Warm climate water outlet 55°C
General Annual energy consumption
kWh 1,174 1,901 1,932 2,637
ηs (Seasonal space heating efficiency)
% 186 149 176 146
Prated at 2°C
kW 4 5 7 8
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 2.11 2.29 2.15 1.82
Pdh kW 4.3 5.5 6.6 7.6
PERd % 84.4 91.6 86.0 72.8
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0
COPd 3.76 3.41 3.70 3.07
Pdh kW 2.8 3.5 4.2 4.9
PERd % 150.4 136.4 148.0 122.8
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 7.26 4.86 6.52 5.88
Pdh kW 1.6 2.9 3.5 5.4
PERd % 290.4 194.4 260.8 235.2
Tbiv (bivalent temperature)
COPd 2.11 2.29 2.15 1.82
Pdh kW 4.3 5.5 6.6 7.6
PERd % 84.4 91.6 86.0 72.8
Tbiv °C 2
Average climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Cold climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Qhe Annual energy consumption (GCV)
Gj -
Warm climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 51
• Outdoor Unit • ERLQ-CV3
2
52
2 Specifications
Domestic hot water heating
General Declared load profile L XL L XL
Function to fix water heating during off peak hours
Yes
Average climate AEC (Annual electricity consumption)
kWh 1,063 1,148 1,654 1,256 1,797 2,158
ηwh (water heating efficiency)
% 103 98 108 90 99 84
Qelec (Daily electricity consumption)
kWh 4.753 5.138 7.453 5.630 8.105 9.681
Water heating energy efficiency class
A
Cold climate AEC (Annual electricity consumption)
kWh 1,221 1,263 1,858 1,387 2,200 2,394
ηwh (water heating efficiency)
% 92 89 95 80 76
Qelec (Daily electricity consumption)
kWh 5.473 5.653 8.379 6.226 10.000 10.755
Warm climate AEC (Annual electricity consumption)
kWh 948 1,068 1,510 1,138 1,696 1,921
ηwh (water heating efficiency)
% 120 107 117 100 106 95
Qelec (Daily electricity consumption)
kWh 4.229 4.763 6.796 5.091 8.000 8.600
CONNECTABLE INDOOR UNITS
2-11 Capacity and Power input EHSXB16P50B/ERLQ014CV3 EHSXB16P50B/ERLQ016CV3
Indoor unit EHSXB16P50BA
Outdoor unit ERLQ014CAV3 ERLQ016CAV3
Heating capacity Nom. kW 14.81 / 13.73 / 8.28 / 9.57 15.34 / 14.86 / 8.04 / 10.05
Max. kW 14.55 / 13.59 16.10 / 15.22
Cooling capacity Min. kW 2.5 / 2.6 -
Nom. kW 16.1 / 12.6 16.8 / 13.1
Max. kW 16.1 / 12.6 16.8 / 13.1
Power input Heating Nom. kW 3.42 / 4.07 / 3.17 / 2.93
Max. kW 3.43 / 4.22 3.83 / 4.71
Cooling Nom. kW 5.44 / 5.10 6.18 / 5.72
Max. kW 5.42 / 5.09 6.15 / 5.74
COP 4.27 / 3.34 / 2.58 / 3.22 4.10 / 3.22 / 2.44 / 3.15
EER 2.96 / 2.47 2.72 / 2.29
Pump Type Grundfos UPM3 25-75 CHBL
Water side Heat exchanger
Water flow rate Cooling Nom. l/min 46.0 / 36.1 48.1 / 37.5
Heating Nom. l/min 42.4 / 39.4 44.0 / 42.6
General Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater Yes
Low-temperature heat pump No
Supplementary heater integrated No
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 39
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 64 66
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating general Other Capacity control Inverter
Cdh (Degradation heating) 0.9
Pck (Crankcase heater mode)
kW 0.000
Poff (Off mode) kW 0.050
Psb (Standby mode) kW 0.050
Pto (Thermostat off) kW 0.105
Integrated supplementary heater
Psup kW 9.0
Type of energy input Electrical
Space heating Average climate water outlet 55°C
General Annual energy consumption
kWh 7,654 8,978
ηs (Seasonal space heating efficiency)
% 130 127
Prated at -10°C
kW 12 14
Seasonal space heating eff. class
A++
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 1.92 1.85
Pdh kW 10.9 12.6
PERd % 76.8 74.0
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 3.30 3.19
Pdh kW 6.6 7.8
PERd % 132.0 127.6
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0
COPd 4.34 4.47
Pdh kW 4.6 4.9
PERd % 173.6 178.8
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 6.45 6.52
Pdh kW 5.5 5.4
PERd % 258.0 260.8
Tol (temperature operating limit)
COPd 1.63 1.57
Pdh kW 9.8 11.2
PERd % 65.2 62.8
TOL °C -10
WTOL °C 55
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 2.5 3.0
Tbiv (bivalent temperature)
COPd 1.92 1.84
Pdh kW 10.9 12.6
PERd % 76.8 73.6
Tbiv °C -7
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 53
• Outdoor Unit • ERLQ-CV3
2
54
2 Specifications
Space heating Cold climate water outlet 55°C
General Annual energy consumption
kWh 9,676 10,405
ηs (Seasonal space heating efficiency)
% 101
Prated at -22°C
kW 10 11
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 2.04 2.05
Pdh kW 6.2 6.6
PERd % 81.6 82.0
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 3.20 3.19
Pdh kW 3.8 4.0
PERd % 128.0 127.6
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.9
COPd 5.50
Pdh kW 5.2
PERd % 220.0
D Condition (12°CDB/11°CWB)
COPd 7.56
Pdh kW 6.1
PERd % 302.4
Tol (temperature operating limit)
COPd 1.13 1.08
Pdh kW 6.4 6.8
PERd % 45.2 43.2
TOL °C -20
WTOL °C 55
G Condition (-15°CDB/-)
COPd 1.50 1.42
Pdh kW 8.4 8.9
PERd % 60.0 56.8
Tbiv (bivalent temperature)
COPd 1.50 1.42
Pdh kW 8.4 8.9
PERd % 60.0 56.8
Tbiv °C -15
Rated heat output supplementary capacity
Psup (at Tdesign -22°C)
kW 4.6 4.9
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Warm climate water outlet 55°C
General Annual energy consumption
kWh 3,282 3,429
ηs (Seasonal space heating efficiency)
% 153 154
Prated at 2°C
kW 10
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 1.90 1.78
Pdh kW 9.8 10.3
PERd % 76.0 71.2
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0
COPd 3.22 3.25
Pdh kW 6.3 6.6
PERd % 128.8 130.0
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 5.88
Pdh kW 5.4
PERd % 235.2
Tbiv (bivalent temperature)
COPd 1.90 1.78
Pdh kW 9.8 10.3
PERd % 76.0 71.2
Tbiv °C 2
Average climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Cold climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Qhe Annual energy consumption (GCV)
Gj -
Warm climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 55
• Outdoor Unit • ERLQ-CV3
2
56
2 Specifications
Notes
(1) EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB
(2) EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB
(3) EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB
(4) EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB
(5) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
(6) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
(7) Tamb 35°C - LWE 18°C (DT=5°C)
(8) Tamb 35°C - LWE 7°C (DT=5°C)
(9) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
(10) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
Domestic hot water heating
General Declared load profile XL
Function to fix water heating during off peak hours
Yes
Average climate AEC (Annual electricity consumption)
kWh 2,158
ηwh (water heating efficiency)
% 84
Qelec (Daily electricity consumption)
kWh 9.681
Water heating energy efficiency class
A
Cold climate AEC (Annual electricity consumption)
kWh 2,394
ηwh (water heating efficiency)
% 76
Qelec (Daily electricity consumption)
kWh 10.755
Warm climate AEC (Annual electricity consumption)
kWh 1,921
ηwh (water heating efficiency)
% 95
Qelec (Daily electricity consumption)
kWh 8.600
CONNECTABLE INDOOR UNITS
2-12 Capacity and Power inputEHSH04P30B/ERLQ004CV3
EHSH08P30B/ERLQ006CV3
EHSH08P50B/ERLQ006CV3
EHSH08P30B/ERLQ008CV3
EHSH08P50B/ERLQ008CV3
EHSH16P50B/ERLQ011CV3
Indoor unit EHSH04P30BA
EHSH08P30BA
EHSH08P50BA
EHSH08P30BA
EHSH08P50BA
EHSH16P50BA
Outdoor unit ERLQ004CAV3
ERLQ006CAV3 ERLQ008CAV3 ERLQ011CAV3
Heating capacity Min. kW 1.80 (1) / 1.81 (2) -
Nom. kW 4.26 (3) / 3.47 (4) / 4.53 (1) /
3.98 (2)
5.14 (3) / 4.60 (4) / 6.06 (1) / 5.78 (2)
5.53 (3) / 5.51 (4) / 7.78 (1) / 7.27 (2)
5.95 (1) / 7.74 (2) / 11.80 (3) /
10.40 (4)
Max. kW 4.90 (1) / 5.12 (2)
8.35 (1) / 7.95 (2) 10.02 (1) / 9.53 (2) 11.38 (3) / 11.00 (4)
Power input Heating Nom. kW 0.87 (5) / 1.04 (6) / 1.49 (3) /
0.85 (4)
1.30 (5) / 1.58 (6) / 1.88 (3) / 1.26 (4)
1.69 (5) / 2.04 (6) / 1.98 (3) / 1.56 (4)
2.57 (5) / 3.13 (6) / 2.43 (1) /
2.35 (2)
Max. kW 1.12 (5) / 1.44 (6)
1.99 (5) / 2.32 (6) 2.54 (5) / 2.96 (6) 2.64 (5) / 3.25 (6)
COP 5.23 (5) / 3.84 (6) / 2.85 (3) /
4.07 (4)
4.65 (5) / 3.66 (6) / 2.73 (3) / 3.64 (4)
4.60 (5) / 3.57 (6) / 2.78 (3) / 3.54 (4)
4.38 (5) / 3.32 (6) / 2.45 (1) /
3.29 (2)
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Pump Type Grundfos UPM3 25-75 CHBL
Nominal ESP unit Heating kPa 46.0 (7) / 48.0 (8)
40.0 (7) / 41.0 (8) 37.0 (7) / 36.0 (8) -
Water side Heat exchanger
Water flow rate Heating Nom. l/min 13.0 (7) / 11.3 (8)
17.4 (7) / 16.6 (8) 22.3 (7) / 20.8 (8) 33.8 (7) / 29.8 (8)
General Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater
Yes
Low-temperature heat pump No
Supplementary heater integrated
No
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 39
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 61 62 64
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating general Air to water unit Rated airflow (outdoor)
m³/h 2,700 2,820 -
Other Capacity control Inverter
Cdh (Degradation heating) 0.9
Pck (Crankcase heater mode)
kW 0.000
Poff (Off mode) kW 0.011 0.012 0.050
Psb (Standby mode)
kW 0.011 0.012 0.050
Pto (Thermostat off) kW 0.043 0.048 0.105
Integrated supplementary heater
Psup kW 9.0
Type of energy input Electrical
Space heating Average climate water outlet 55°C
General Annual energy consumption
kWh 2,934 3,828 4,725 6,345
ηs (Seasonal space heating efficiency)
% 130 125 127 125
Prated at -10°C
kW 5 6 8 10
Seasonal space heating eff. class
A++
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 2.03 2.09 2.10 1.94
Pdh kW 4.2 5.3 5.4 9.0
PERd % 81.2 83.6 84.0 77.6
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 3.31 3.13 3.25 3.30
Pdh kW 2.6 3.1 3.9 5.4
PERd % 132.4 125.2 130.0 132.0
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 57
• Outdoor Unit • ERLQ-CV3
2
58
2 Specifications
Space heating Average climate water outlet 55°C
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0 0.9
COPd 4.43 4.09 4.42 4.26
Pdh kW 1.8 2.1 2.6 4.6
PERd % 177.2 163.6 176.8 170.4
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 6.55 5.99 6.30
Pdh kW 2.2 2.0 5.5
PERd % 262.0 239.6 252.0
Tol (temperature operating limit)
COPd 1.64 1.79 1.78
Pdh kW 4.1 5.1 9.1
PERd % 65.6 71.6 71.2
TOL °C -10
WTOL °C 55
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.7 0.9 2.4 1.0
Tbiv (bivalent temperature)
COPd 2.03 2.09 2.36 1.94
Pdh kW 4.2 5.3 5.8 9.0
PERd % 81.2 83.6 94.4 77.6
Tbiv °C -7 -4 -7
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Cold climate water outlet 55°C
General Annual energy consumption
kWh 3,069 4,008 4,575 8,185
ηs (Seasonal space heating efficiency)
% 109 103 109 100
Prated at -22°C
kW 4 5 9
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 2.30 2.47 2.41 1.98
Pdh kW 2.2 2.6 3.2 5.2
PERd % 92.0 98.8 96.4 79.2
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0 0.9 1.0
COPd 3.75 3.26 3.69 3.25
Pdh kW 1.4 2.0 2.4 3.2
PERd % 150.0 130.4 147.6 130.0
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.9
COPd 5.92 4.42 5.58 5.50
Pdh kW 1.6 2.6 3.2 5.2
PERd % 236.8 176.8 223.2 220.0
D Condition (12°CDB/11°CWB)
COPd 8.65 5.54 7.79 7.56
Pdh kW 1.6 3.0 3.6 6.1
PERd % 346.0 221.6 311.6 302.4
Tol (temperature operating limit)
COPd 0.89 1.05 0.98 1.22
Pdh kW 0.8 1.0 1.2 5.7
PERd % 35.6 42.0 39.2 48.8
TOL °C -20
WTOL °C 55 1 55
G Condition (-15°CDB/-)
COPd 1.25 1.42 1.33 1.51
Pdh kW 2.9 3.6 4.3 7.1
PERd % 50.0 56.8 53.2 60.4
Tbiv (bivalent temperature)
COPd 1.25 1.42 1.33 1.51
Pdh kW 2.9 3.6 4.3 7.1
PERd % 50.0 56.8 53.2 60.4
Tbiv °C -15
Rated heat output supplementary capacity
Psup (at Tdesign -22°C)
kW 3.5 4.4 5.2 3.4
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 59
• Outdoor Unit • ERLQ-CV3
2
60
2 Specifications
Space heating Warm climate water outlet 55°C
General Annual energy consumption
kWh 1,174 1,901 1,932 2,637
ηs (Seasonal space heating efficiency)
% 179 145 171 135
Prated at 2°C
kW 4 5 7 8
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 2.11 2.29 2.15 1.82
Pdh kW 4.3 5.5 6.6 7.6
PERd % 84.4 91.6 86.0 72.8
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0
COPd 3.76 3.41 3.70 3.07
Pdh kW 2.8 3.5 4.2 4.9
PERd % 150.4 136.4 148.0 122.8
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 7.26 4.86 6.52 5.88
Pdh kW 1.6 2.9 3.5 5.4
PERd % 290.4 194.4 260.8 235.2
Tbiv (bivalent temperature)
COPd 2.11 2.29 2.15 1.82
Pdh kW 4.3 5.5 6.6 7.6
PERd % 84.4 91.6 86.0 72.8
Tbiv °C 2
Average climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Cold climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Qhe Annual energy consumption (GCV)
Gj -
Warm climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Domestic hot water heating
General Declared load profile L XL L XL
Function to fix water heating during off peak hours
Yes
Average climate AEC (Annual electricity consumption)
kWh 1,063 1,148 1,747 1,256 1,866 2,187
ηwh (water heating efficiency)
% 103 98 102 90 96 83
Qelec (Daily electricity consumption)
kWh 4.753 5.138 7.866 5.630 8.409 9.811
Water heating energy efficiency class
A
Cold climate AEC (Annual electricity consumption)
kWh 1,221 1,263 1,954 1,387 2,104 2,435
ηwh (water heating efficiency)
% 92 89 91 80 84 74
Qelec (Daily electricity consumption)
kWh 5.473 5.653 9.000 6.226 9.496 10.938
Warm climate AEC (Annual electricity consumption)
kWh 948 1,068 1,559 1,138 1,727 1,956
ηwh (water heating efficiency)
% 120 107 115 100 104 93
Qelec (Daily electricity consumption)
kWh 4.229 4.763 7.014 5.091 8.000 8.760
CONNECTABLE INDOOR UNITS
2-13 Capacity and Power input EHSH16P50B/ERLQ014CV3 EHSH16P50B/ERLQ016CV3
Indoor unit EHSH16P50BA
Outdoor unit ERLQ014CAV3 ERLQ016CAV3
Heating capacity Nom. kW 8.28 / 9.57 / 14.81 / 13.73 15.34 / 14.86 / 8.04 / 10.05
Max. kW 14.55 / 13.59 16.10 / 15.22
Power input Heating Nom. kW 3.42 / 4.07 / 3.17 / 2.93 3.42 / 4.07 / 3.17 / 2.93
Max. kW 3.43 / 4.22 3.83 / 4.71
COP 4.27 / 3.34 / 2.58 / 3.22 4.10 / 3.22 / 2.44 / 3.15
Pump Type Grundfos UPM3 25-75 CHBL
Water side Heat exchanger
Water flow rate Heating Nom. l/min 42.4 / 39.4 44.0 / 42.6
General Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater Yes
Low-temperature heat pump No
Supplementary heater integrated
No
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 39
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 64 66
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 61
• Outdoor Unit • ERLQ-CV3
2
62
2 Specifications
Space heating general Other Capacity control Inverter
Cdh (Degradation heating) 0.9
Pck (Crankcase heater mode)
kW 0.000
Poff (Off mode) kW 0.050
Psb (Standby mode) kW 0.050
Pto (Thermostat off) kW 0.105
Integrated supplementary heater
Psup kW 9.0
Type of energy input Electrical
Space heating Average climate water outlet 55°C
General Annual energy consumption
kWh 7,654 8,978
ηs (Seasonal space heating efficiency)
% 126 125
Prated at -10°C
kW 12 14
Seasonal space heating eff. class
A++
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 1.92 1.85
Pdh kW 10.9 12.6
PERd % 76.8 74.0
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 3.30 3.19
Pdh kW 6.6 7.8
PERd % 132.0 127.6
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0
COPd 4.34 4.47
Pdh kW 4.6 4.9
PERd % 173.6 178.8
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 6.45 6.52
Pdh kW 5.5 5.4
PERd % 258.0 260.8
Tol (temperature operating limit)
COPd 1.63 1.57
Pdh kW 9.8 11.2
PERd % 65.2 62.8
TOL °C -10
WTOL °C 55
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 2.5 3.0
Tbiv (bivalent temperature)
COPd 1.92 1.84
Pdh kW 10.9 12.6
PERd % 76.8 73.6
Tbiv °C -7
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Cold climate water outlet 55°C
General Annual energy consumption
kWh 9,676 10,405
ηs (Seasonal space heating efficiency)
% 100
Prated at -22°C
kW 10 11
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 2.04 2.05
Pdh kW 6.2 6.6
PERd % 81.6 82.0
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 3.20 3.19
Pdh kW 3.8 4.0
PERd % 128.0 127.6
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.9
COPd 5.50
Pdh kW 5.2
PERd % 220.0
D Condition (12°CDB/11°CWB)
COPd 7.56
Pdh kW 6.1
PERd % 302.4
Tol (temperature operating limit)
COPd 1.13 1.08
Pdh kW 6.4 6.8
PERd % 45.2 43.2
TOL °C -20
WTOL °C 55
G Condition (-15°CDB/-)
COPd 1.50 1.42
Pdh kW 8.4 8.9
PERd % 60.0 56.8
Tbiv (bivalent temperature)
COPd 1.50 1.42
Pdh kW 8.4 8.9
PERd % 60.0 56.8
Tbiv °C -15
Rated heat output supplementary capacity
Psup (at Tdesign -22°C)
kW 4.6 4.9
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 63
• Outdoor Unit • ERLQ-CV3
2
64
2 Specifications
Space heating Warm climate water outlet 55°C
General Annual energy consumption
kWh 3,282 3,429
ηs (Seasonal space heating efficiency)
% 144 145
Prated at 2°C
kW 10
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 1.90 1.78
Pdh kW 9.8 10.3
PERd % 76.0 71.2
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0
COPd 3.22 3.25
Pdh kW 6.3 6.6
PERd % 128.8 130.0
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 5.88
Pdh kW 5.4
PERd % 235.2
Tbiv (bivalent temperature)
COPd 1.90 1.78
Pdh kW 9.8 10.3
PERd % 76.0 71.2
Tbiv °C 2
Average climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Cold climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Qhe Annual energy consumption (GCV)
Gj -
Warm climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Notes
(1) EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB
(2) EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB
(3) EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB
(4) EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB
(5) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
(6) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
(7) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
(8) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
Domestic hot water heating
General Declared load profile XL
Function to fix water heating during off peak hours
Yes
Average climate AEC (Annual electricity consumption)
kWh 2,187
ηwh (water heating efficiency)
% 83
Qelec (Daily electricity consumption)
kWh 9.811
Water heating energy efficiency class
A
Cold climate AEC (Annual electricity consumption)
kWh 2,435
ηwh (water heating efficiency)
% 74
Qelec (Daily electricity consumption)
kWh 10.938
Warm climate AEC (Annual electricity consumption)
kWh 1,956
ηwh (water heating efficiency)
% 93
Qelec (Daily electricity consumption)
kWh 8.760
CONNECTABLE INDOOR UNITS
2-14 Capacity and Power inputEHSX04P30B/ERLQ004CV3
EHSX08P50B/ERLQ006CV3
EHSX08P30B/ERLQ006CV3
EHSX08P30B/ERLQ008CV3
EHSX08P50B/ERLQ008CV3
EHSX16P50B/ERLQ011CV3
Indoor unit EHSX04P30BA
EHSX08P50BA
EHSX08P30BA EHSX08P50BA
EHSX16P50BA
Outdoor unit ERLQ004CAV3
ERLQ006CAV3 ERLQ008CAV3 ERLQ011CAV3
Heating capacity Min. kW 1.80 (1) / 1.81 (2) -
Nom. kW 4.26 (3) / 3.47 (4) / 4.53 (1) /
3.98 (2)
5.14 (3) / 4.60 (4) / 6.06 (1) / 5.78 (2)
5.53 (3) / 5.51 (4) / 7.78 (1) / 7.27 (2)
5.95 (1) / 7.74 (2) / 11.80 (3) /
10.40 (4)
Max. kW 4.90 (1) / 5.12 (2)
8.35 (1) / 7.95 (2) 10.02 (1) / 9.53 (2) 11.38 (3) / 11.00 (4)
Cooling capacity Min. kW 2.0 (5) / 2.1 (6) 2.5 (5) / 2.6 (6)
Nom. kW 4.4 (5) / 4.0 (6) 5.2 (5) / 4.6 (6) 15.1 (5) / 11.7 (6)
Max. kW 5.9 (5) / 4.5 (6) 7.3 (5) / 5.5 (6) 8.4 (5) / 6.4 (6) 15.1 (5) / 11.7 (6)
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 65
• Outdoor Unit • ERLQ-CV3
2
66
2 Specifications
Power input Heating Nom. kW 0.87 (5) / 1.04 (6) / 1.49 (3) /
0.85 (4)
1.30 (5) / 1.58 (6) / 1.88 (3) / 1.26 (4)
1.69 (5) / 2.04 (6) / 1.98 (3) / 1.56 (4)
2.57 (5) / 3.13 (6) / 2.43 (1) /
2.35 (2)
Max. kW 1.12 (5) / 1.44 (6)
1.99 (5) / 2.32 (6) 2.54 (5) / 2.96 (6) 2.64 (5) / 3.25 (6)
Cooling Nom. kW 1.05 (5) / 1.41 (6)
1.43 (5) / 1.85 (6) 4.55 (5) / 4.30 (6)
Max. kW 1.86 (5) / 2.04 (6)
2.27 (5) / 2.51 (6) 2.89 (5) / 3.20 (6) 4.53 (5) / 4.31 (6)
COP 5.23 (5) / 3.84 (6) / 2.85 (3) /
4.07 (4)
4.65 (5) / 3.66 (6) / 2.73 (3) / 3.64 (4)
4.60 (5) / 3.57 (6) / 2.78 (3) / 3.54 (4)
4.38 (5) / 3.32 (6) / 2.45 (1) /
3.29 (2)
EER 4.21 (5) / 2.85 (6)
3.65 (5) / 2.51 (6) 3.32 (5) / 2.72 (6)
Pump Type Grundfos UPM3 25-75 CHBL
Nominal ESP unit Cooling kPa 45.0 (7) / 48.0 (8)
- 44.0 (7) / 46.0 (8) -
Heating kPa 46.0 (9) / 48.0 (10)
40.0 (7) / 41.0 (8)
40.0 (9) / 41.0 (10)
37.0 (9) / 36.0 (10) -
Water side Heat exchanger
Water flow rate Cooling Nom. l/min 12.7 (7) / 11.5 (8)
- 12.9 (7) / 13.3 (8) 43.3 (7) / 33.5 (8)
Heating Nom. l/min 13.0 (9) / 11.3 (10)
17.4 (7) / 16.6 (8)
17.4 (9) / 16.6 (10)
22.3 (9) / 20.8 (10) 33.8 (9) / 29.8 (10)
General Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater Yes
Low-temperature heat pump No
Supplementary heater integrated
No
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 39
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 61 62 64
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating general Air to water unit Rated airflow (outdoor)
m³/h 2,700 2,820 -
Other Capacity control Inverter
Cdh (Degradation heating) 0.9
Pck (Crankcase heater mode)
kW 0.000
Poff (Off mode) kW 0.011 0.012 0.050
Psb (Standby mode) kW 0.011 0.012 0.050
Pto (Thermostat off) kW 0.043 0.048 0.105
Integrated supplementary heater
Psup kW 9.0
Type of energy input Electrical
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Average climate water outlet 55°C
General Annual energy consumption
kWh 2,934 3,828 4,725 6,345
ηs (Seasonal space heating efficiency)
% 132 126 128
Prated at -10°C
kW 5 6 8 10
Seasonal space heating eff. class
A++
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 2.03 2.09 2.10 1.94
Pdh kW 4.2 5.3 5.4 9.0
PERd % 81.2 83.6 84.0 77.6
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 3.31 3.13 3.25 3.30
Pdh kW 2.6 3.1 3.9 5.4
PERd % 132.4 125.2 130.0 132.0
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0 0.9
COPd 4.43 4.09 4.42 4.26
Pdh kW 1.8 2.1 2.6 4.6
PERd % 177.2 163.6 176.8 170.4
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 6.55 5.99 6.30
Pdh kW 2.2 2.0 5.5
PERd % 262.0 239.6 252.0
Tol (temperature operating limit)
COPd 1.64 1.79 1.78
Pdh kW 4.1 5.1 9.1
PERd % 65.6 71.6 71.2
TOL °C -10
WTOL °C 55
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.7 0.9 2.4 1.0
Tbiv (bivalent temperature)
COPd 2.03 2.09 2.36 1.94
Pdh kW 4.2 5.3 5.8 9.0
PERd % 81.2 83.6 94.4 77.6
Tbiv °C -7 -4 -7
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 67
• Outdoor Unit • ERLQ-CV3
2
68
2 Specifications
Space heating Cold climate water outlet 55°C
General Annual energy consumption
kWh 3,069 4,008 4,575 8,185
ηs (Seasonal space heating efficiency)
% 110 103 104 109 100
Prated at -22°C
kW 4 5 9
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 2.30 2.47 2.41 1.98
Pdh kW 2.2 2.6 3.2 5.2
PERd % 92.0 98.8 96.4 79.2
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0 0.9 1.0
COPd 3.75 3.26 3.69 3.25
Pdh kW 1.4 2.0 2.4 3.2
PERd % 150.0 130.4 147.6 130.0
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.9
COPd 5.92 4.42 5.58 5.50
Pdh kW 1.6 2.6 3.2 5.2
PERd % 236.8 176.8 223.2 220.0
D Condition (12°CDB/11°CWB)
COPd 8.65 5.54 7.79 7.56
Pdh kW 1.6 3.0 3.6 6.1
PERd % 346.0 221.6 311.6 302.4
Tol (temperature operating limit)
COPd 0.89 1.05 0.98 1.22
Pdh kW 0.8 1.0 1.2 5.7
PERd % 35.6 42.0 39.2 48.8
TOL °C -20
WTOL °C 55
G Condition (-15°CDB/-)
COPd 1.25 1.42 1.33 1.51
Pdh kW 2.9 3.6 4.3 7.1
PERd % 50.0 56.8 53.2 60.4
Tbiv (bivalent temperature)
COPd 1.25 1.42 1.33 1.51
Pdh kW 2.9 3.6 4.3 7.1
PERd % 50.0 56.8 53.2 60.4
Tbiv °C -15
Rated heat output supplementary capacity
Psup (at Tdesign -22°C)
kW 3.5 4.4 5.2 3.4
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Warm climate water outlet 55°C
General Annual energy consumption
kWh 1,174 1,901 1,932 2,637
ηs (Seasonal space heating efficiency)
% 186 145 149 176 135
Prated at 2°C
kW 4 5 7 8
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 2.11 2.29 2.15 1.82
Pdh kW 4.3 5.5 6.6 7.6
PERd % 84.4 91.6 86.0 72.8
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0
COPd 3.76 3.41 3.70 3.07
Pdh kW 2.8 3.5 4.2 4.9
PERd % 150.4 136.4 148.0 122.8
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 7.26 4.86 6.52 5.88
Pdh kW 1.6 2.9 3.5 5.4
PERd % 290.4 194.4 260.8 235.2
Tbiv (bivalent temperature)
COPd 2.11 2.29 2.15 1.82
Pdh kW 4.3 5.5 6.6 7.6
PERd % 84.4 91.6 86.0 72.8
Tbiv °C 2
Average climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Cold climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Qhe Annual energy consumption (GCV)
Gj -
Warm climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 69
• Outdoor Unit • ERLQ-CV3
2
70
2 Specifications
Domestic hot water heating
General Declared load profile L XL L XL
Function to fix water heating during off peak hours
Yes
Average climate AEC (Annual electricity consumption)
kWh 1,063 1,747 1,148 1,256 1,866 2,187
ηwh (water heating efficiency)
% 103 102 98 90 96 83
Qelec (Daily electricity consumption)
kWh 4.753 7.866 5.138 5.630 8.409 9.811
Water heating energy efficiency class
A
Cold climate AEC (Annual electricity consumption)
kWh 1,221 1,954 1,263 1,387 2,104 2,435
ηwh (water heating efficiency)
% 92 91 89 80 84 74
Qelec (Daily electricity consumption)
kWh 5.473 9.000 5.653 6.226 9.496 10.938
Warm climate AEC (Annual electricity consumption)
kWh 948 1,559 1,068 1,138 1,727 1,956
ηwh (water heating efficiency)
% 120 115 107 100 104 93
Qelec (Daily electricity consumption)
kWh 4.229 7.014 4.763 5.091 8.000 8.760
CONNECTABLE INDOOR UNITS
2-15 Capacity and Power input EHSX16P50B/ERLQ014CV3 EHSH16P50B/ERLQ016CV3
Indoor unit EHSX16P50BA
Outdoor unit ERLQ014CAV3 ERLQ016CAV3
Heating capacity Nom. kW 14.81 / 13.73 / 8.28 / 9.57 15.34 / 14.86 / 8.04 / 10.05
Max. kW 14.55 / 13.59 16.10 / 15.22
Cooling capacity Min. kW 2.5 / 2.6 -
Nom. kW 16.1 / 12.6 16.8 / 13.1
Max. kW 16.1 / 12.6 16.8 / 13.1
Power input Heating Nom. kW 3.42 / 4.07 / 3.17 / 2.93
Max. kW 3.43 / 4.22 3.83 / 4.71
Cooling Nom. kW 5.44 / 5.10 6.18 / 5.72
Max. kW 5.42 / 5.09 6.15 / 5.74
COP 4.27 / 3.34 / 2.58 / 3.22 4.10 / 3.22 / 2.44 / 3.15
EER 2.96 / 2.47 2.72 / 2.29
Pump Type Grundfos UPM3 25-75 CHBL
Water side Heat exchanger
Water flow rate Cooling Nom. l/min 46.0 / 36.1 48.1 / 37.5
Heating Nom. l/min 42.4 / 39.4 44.0 / 42.6
General Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater Yes
Low-temperature heat pump No
Supplementary heater integrated No
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 39
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 64 66
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating general Other Capacity control Inverter
Cdh (Degradation heating) 0.9
Pck (Crankcase heater mode)
kW 0.000
Poff (Off mode) kW 0.050
Psb (Standby mode) kW 0.050
Pto (Thermostat off) kW 0.105
Integrated supplementary heater
Psup kW 9.0
Type of energy input Electrical
Space heating Average climate water outlet 55°C
General Annual energy consumption
kWh 7,654 8,978
ηs (Seasonal space heating efficiency)
% 130 127
Prated at -10°C
kW 12 14
Seasonal space heating eff. class
A++
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 1.92 1.85
Pdh kW 10.9 12.6
PERd % 76.8 74.0
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 3.30 3.19
Pdh kW 6.6 7.8
PERd % 132.0 127.6
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0
COPd 4.34 4.47
Pdh kW 4.6 4.9
PERd % 173.6 178.8
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 6.45 6.52
Pdh kW 5.5 5.4
PERd % 258.0 260.8
Tol (temperature operating limit)
COPd 1.63 1.57
Pdh kW 9.8 11.2
PERd % 65.2 62.8
TOL °C -10
WTOL °C 55
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 2.5 3.0
Tbiv (bivalent temperature)
COPd 1.92 1.84
Pdh kW 10.9 12.6
PERd % 76.8 73.6
Tbiv °C -7
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 71
• Outdoor Unit • ERLQ-CV3
2
72
2 Specifications
Space heating Cold climate water outlet 55°C
General Annual energy consumption
kWh 9,676 10,405
ηs (Seasonal space heating efficiency)
% 101
Prated at -22°C
kW 10 11
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 2.04 2.05
Pdh kW 6.2 6.6
PERd % 81.6 82.0
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 3.20 3.19
Pdh kW 3.8 4.0
PERd % 128.0 127.6
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.9
COPd 5.50
Pdh kW 5.2
PERd % 220.0
D Condition (12°CDB/11°CWB)
COPd 7.56
Pdh kW 6.1
PERd % 302.4
Tol (temperature operating limit)
COPd 1.13 1.08
Pdh kW 6.4 6.8
PERd % 45.2 43.2
TOL °C -20
WTOL °C 55
G Condition (-15°CDB/-)
COPd 1.50 1.42
Pdh kW 8.4 8.9
PERd % 60.0 56.8
Tbiv (bivalent temperature)
COPd 1.50 1.42
Pdh kW 8.4 8.9
PERd % 60.0 56.8
Tbiv °C -15
Rated heat output supplementary capacity
Psup (at Tdesign -22°C)
kW 4.6 4.9
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Warm climate water outlet 55°C
General Annual energy consumption
kWh 3,282 3,429
ηs (Seasonal space heating efficiency)
% 153 154
Prated at 2°C
kW 10
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 1.90 1.78
Pdh kW 9.8 10.3
PERd % 76.0 71.2
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0
COPd 3.22 3.25
Pdh kW 6.3 6.6
PERd % 128.8 130.0
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 5.88
Pdh kW 5.4
PERd % 235.2
Tbiv (bivalent temperature)
COPd 1.90 1.78
Pdh kW 9.8 10.3
PERd % 76.0 71.2
Tbiv °C 2
Average climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Cold climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Qhe Annual energy consumption (GCV)
Gj -
Warm climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 73
• Outdoor Unit • ERLQ-CV3
2
74
2 Specifications
Notes
(1) EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB
(2) EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB
(3) EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB
(4) EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB
(5) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
(6) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
(7) Tamb 35°C - LWE 18°C (DT=5°C)
(8) Tamb 35°C - LWE 7°C (DT=5°C)
(9) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
(10) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
Domestic hot water heating
General Declared load profile XL
Function to fix water heating during off peak hours
Yes
Average climate AEC (Annual electricity consumption)
kWh 2,187
ηwh (water heating efficiency)
% 83
Qelec (Daily electricity consumption)
kWh 9.811
Water heating energy efficiency class
A
Cold climate AEC (Annual electricity consumption)
kWh 2,435
ηwh (water heating efficiency)
% 74
Qelec (Daily electricity consumption)
kWh 10.938
Warm climate AEC (Annual electricity consumption)
kWh 1,956
ηwh (water heating efficiency)
% 93
Qelec (Daily electricity consumption)
kWh 8.760
CONNECTABLE INDOOR UNITS
2-16 Capacity and Power inputEHSHB04P30B/ERLQ004CV3
EHSHB08P30B/ERLQ006CV3
EHSHB08P50B/ERLQ006CV3
EHSHB08P30B/ERLQ008CV3
EHSHB08P50B/ERLQ008CV3
EHSHB16P50B/ERLQ011CV3
Indoor unit EHSHB04P30BA
EHSHB08P30BA
EHSHB08P50BA
EHSHB08P30BA
EHSHB08P50BA
EHSHB16P50BA
Outdoor unit ERLQ004CAV3
ERLQ006CAV3 ERLQ008CAV3 ERLQ011CAV3
Heating capacity Min. kW 1.80 (1) / 1.81 (2) -
Nom. kW 4.26 (3) / 3.47 (4) / 4.53 (1) /
3.98 (2)
5.14 (3) / 4.60 (4) / 6.06 (1) / 5.78 (2)
5.53 (3) / 5.51 (4) / 7.78 (1) / 7.27 (2)
5.95 (1) / 7.74 (2) / 11.80 (3) /
10.40 (4)
Max. kW 4.90 (1) / 5.12 (2)
8.35 (1) / 7.95 (2) 10.02 (1) / 9.53 (2) 11.38 (3) / 11.00 (4)
Power input Heating Nom. kW 0.87 (5) / 1.04 (6) / 1.49 (3) /
0.85 (4)
1.30 (5) / 1.58 (6) / 1.88 (3) / 1.26 (4)
1.69 (5) / 2.04 (6) / 1.98 (3) / 1.56 (4)
2.57 (5) / 3.13 (6) / 2.43 (1) /
2.35 (2)
Max. kW 1.12 (5) / 1.44 (6)
1.99 (5) / 2.32 (6) 2.54 (5) / 2.96 (6) 2.64 (5) / 3.25 (6)
COP 5.23 (5) / 3.84 (6) / 2.85 (3) /
4.07 (4)
4.65 (5) / 3.66 (6) / 2.73 (3) / 3.64 (4)
4.60 (5) / 3.57 (6) / 2.78 (3) / 3.54 (4)
4.38 (5) / 3.32 (6) / 2.45 (1) /
3.29 (2)
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Pump Type Grundfos UPM3 25-75 CHBL
Nominal ESP unit Heating kPa 46.0 (7) / 48.0 (8)
40.0 (7) / 41.0 (8) 37.0 (7) / 36.0 (8) -
Water side Heat exchanger
Water flow rate Heating Nom. l/min 13.0 (7) / 11.3 (8)
17.4 (7) / 16.6 (8) 22.3 (7) / 20.8 (8) 33.8 (7) / 29.8 (8)
General Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater Yes
Low-temperature heat pump No
Supplementary heater integrated No
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 39
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 61 62 64
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating general Air to water unit Rated airflow (outdoor)
m³/h 2,700 2,820 -
Other Capacity control Inverter
Cdh (Degradation heating) 0.9
Pck (Crankcase heater mode)
kW 0.000
Poff (Off mode) kW 0.011 0.012 0.050
Psb (Standby mode) kW 0.011 0.012 0.050
Pto (Thermostat off) kW 0.043 0.048 0.105
Integrated supplementary heater
Psup kW 9.0
Type of energy input Electrical
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 75
• Outdoor Unit • ERLQ-CV3
2
76
2 Specifications
Space heating Average climate water outlet 55°C
General Annual energy consumption
kWh 2,934 3,828 4,725 6,345
ηs (Seasonal space heating efficiency)
% 130 125 127 125
Prated at -10°C
kW 5 6 8 10
Seasonal space heating eff. class
A++
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 2.03 2.09 2.10 1.94
Pdh kW 4.2 5.3 5.4 9.0
PERd % 81.2 83.6 84.0 77.6
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 3.31 3.13 3.25 3.30
Pdh kW 2.6 3.1 3.9 5.4
PERd % 132.4 125.2 130.0 132.0
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0 0.9
COPd 4.43 4.09 4.42 4.26
Pdh kW 1.8 2.1 2.6 4.6
PERd % 177.2 163.6 176.8 170.4
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 6.55 5.99 6.30
Pdh kW 2.2 2.0 5.5
PERd % 262.0 239.6 252.0
Tol (temperature operating limit)
COPd 1.64 1.79 1.78
Pdh kW 4.1 5.1 9.1
PERd % 65.6 71.6 71.2
TOL °C -10
WTOL °C 55
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.7 0.9 2.4 1.0
Tbiv (bivalent temperature)
COPd 2.03 2.09 2.36 1.94
Pdh kW 4.2 5.3 5.8 9.0
PERd % 81.2 83.6 94.4 77.6
Tbiv °C -7 -4 -7
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Cold climate water outlet 55°C
General Annual energy consumption
kWh 3,069 4,008 4,575 8,185
ηs (Seasonal space heating efficiency)
% 109 103 109 101
Prated at -22°C
kW 4 5 9
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 2.30 2.47 2.41 1.98
Pdh kW 2.2 2.6 3.2 5.2
PERd % 92.0 98.8 96.4 79.2
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0 0.9 1.0
COPd 3.75 3.26 3.69 3.25
Pdh kW 1.4 2.0 2.4 3.2
PERd % 150.0 130.4 147.6 130.0
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.9
COPd 5.92 4.42 5.58 5.50
Pdh kW 1.6 2.6 3.2 5.2
PERd % 236.8 176.8 223.2 220.0
D Condition (12°CDB/11°CWB)
COPd 8.65 5.54 7.79 7.56
Pdh kW 1.6 3.0 3.6 6.1
PERd % 346.0 221.6 311.6 302.4
Tol (temperature operating limit)
COPd 0.89 1.05 0.98 1.22
Pdh kW 0.8 1.0 1.2 5.7
PERd % 35.6 42.0 39.2 48.8
TOL °C -20
WTOL °C 55
G Condition (-15°CDB/-)
COPd 1.25 1.42 1.33 1.51
Pdh kW 2.9 3.6 4.3 7.1
PERd % 50.0 56.8 53.2 60.4
Tbiv (bivalent temperature)
COPd 1.25 1.42 1.33 1.51
Pdh kW 2.9 3.6 4.3 7.1
PERd % 50.0 56.8 53.2 60.4
Tbiv °C -15
Rated heat output supplementary capacity
Psup (at Tdesign -22°C)
kW 3.5 4.4 5.2 3.4
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 77
• Outdoor Unit • ERLQ-CV3
2
78
2 Specifications
Space heating Warm climate water outlet 55°C
General Annual energy consumption
kWh 1,174 1,901 1,932 2,637
ηs (Seasonal space heating efficiency)
% 179 145 171 146
Prated at 2°C
kW 4 5 7 8
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 2.11 2.29 2.15 1.82
Pdh kW 4.3 5.5 6.6 7.6
PERd % 84.4 91.6 86.0 72.8
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0
COPd 3.76 3.41 3.70 3.07
Pdh kW 2.8 3.5 4.2 4.9
PERd % 150.4 136.4 148.0 122.8
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 7.26 4.86 6.52 5.88
Pdh kW 1.6 2.9 3.5 5.4
PERd % 290.4 194.4 260.8 235.2
Tbiv (bivalent temperature)
COPd 2.11 2.29 2.15 1.82
Pdh kW 4.3 5.5 6.6 7.6
PERd % 84.4 91.6 86.0 72.8
Tbiv °C 2
Average climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Cold climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Qhe Annual energy consumption (GCV)
Gj -
Warm climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Domestic hot water heating
General Declared load profile L XL L XL
Function to fix water heating during off peak hours
Yes
Average climate AEC (Annual electricity consumption)
kWh 1,063 1,148 1,654 1,256 1,797 2,158
ηwh (water heating efficiency)
% 103 98 108 90 99 84
Qelec (Daily electricity consumption)
kWh 4.753 5.138 7.453 5.630 8.105 9.681
Water heating energy efficiency class
A
Cold climate AEC (Annual electricity consumption)
kWh 1,221 1,263 1,858 1,387 2,200 2,394
ηwh (water heating efficiency)
% 92 89 95 80 76
Qelec (Daily electricity consumption)
kWh 5.473 5.653 8.379 6.226 10.000 10.755
Warm climate AEC (Annual electricity consumption)
kWh 948 1,068 1,510 1,138 1,696 1,921
ηwh (water heating efficiency)
% 120 107 117 100 106 95
Qelec (Daily electricity consumption)
kWh 4.229 4.763 6.796 5.091 8.000 8.600
CONNECTABLE INDOOR UNITS
2-17 Capacity and Power input EHSHB16P50B/ERLQ014CV3 EHSHB16P50B/ERLQ016CV3
Indoor unit EHSHB16P50BA
Outdoor unit ERLQ014CAV3 ERLQ016CAV3
Heating capacity Nom. kW 14.81 / 13.73 / 8.28 / 9.57 15.34 / 14.86 / 8.04 / 10.05
Max. kW 14.55 / 13.59 16.10 / 15.22
Power input Heating Nom. kW 3.42 / 4.07 / 3.17 / 2.93
Max. kW 3.43 / 4.22 3.83 / 4.71
COP 4.27 / 3.34 / 2.58 / 3.22 4.10 / 3.22 / 2.44 / 3.15
Pump Type Grundfos UPM3 25-75 CHBL
Water side Heat exchanger
Water flow rate Heating Nom. l/min 42.4 / 39.4 44.0 / 42.6
General Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater Yes
Low-temperature heat pump No
Supplementary heater integrated No
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 39
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 64 66
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating general Other Capacity control Inverter
Cdh (Degradation heating) 0.9
Pck (Crankcase heater mode)
kW 0.000
Poff (Off mode) kW 0.050
Psb (Standby mode) kW 0.050
Pto (Thermostat off) kW 0.105
Integrated supplementary heater
Psup kW 9.0
Type of energy input Electrical
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 79
• Outdoor Unit • ERLQ-CV3
2
80
2 Specifications
Space heating Average climate water outlet 55°C
General Annual energy consumption
kWh 7,654 8,978
ηs (Seasonal space heating efficiency)
% 126 125
Prated at -10°C
kW 12 14
Seasonal space heating eff. class
A++
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 1.92 1.85
Pdh kW 10.9 12.6
PERd % 76.8 74.0
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 3.30 3.19
Pdh kW 6.6 7.8
PERd % 132.0 127.6
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0
COPd 4.34 4.47
Pdh kW 4.6 4.9
PERd % 173.6 178.8
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 6.45 6.52
Pdh kW 5.5 5.4
PERd % 258.0 260.8
Tol (temperature operating limit)
COPd 1.63 1.57
Pdh kW 9.8 11.2
PERd % 65.2 62.8
TOL °C -10
WTOL °C 55
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 2.5 3.0
Tbiv (bivalent temperature)
COPd 1.92 1.84
Pdh kW 10.9 12.6
PERd % 76.8 73.6
Tbiv °C -7
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Cold climate water outlet 55°C
General Annual energy consumption
kWh 9,676 10,405
ηs (Seasonal space heating efficiency)
% 100
Prated at -22°C
kW 10 11
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.0
COPd 2.04 2.05
Pdh kW 6.2 6.6
PERd % 81.6 82.0
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 3.20 3.19
Pdh kW 3.8 4.0
PERd % 128.0 127.6
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.9
COPd 5.50
Pdh kW 5.2
PERd % 220.0
D Condition (12°CDB/11°CWB)
COPd 7.56
Pdh kW 6.1
PERd % 302.4
Tol (temperature operating limit)
COPd 1.13 1.08
Pdh kW 6.4 6.8
PERd % 45.2 43.2
TOL °C -20
WTOL °C 55
G Condition (-15°CDB/-)
COPd 1.50 1.42
Pdh kW 8.4 8.9
PERd % 60.0 56.8
Tbiv (bivalent temperature)
COPd 1.50 1.42
Pdh kW 8.4 8.9
PERd % 60.0 56.8
Tbiv °C -15
Rated heat output supplementary capacity
Psup (at Tdesign -22°C)
kW 4.6 4.9
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 81
• Outdoor Unit • ERLQ-CV3
2
82
2 Specifications
Space heating Warm climate water outlet 55°C
General Annual energy consumption
kWh 3,282 3,429
ηs (Seasonal space heating efficiency)
% 144 145
Prated at 2°C
kW 10
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.0
COPd 1.90 1.78
Pdh kW 9.8 10.3
PERd % 76.0 71.2
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
1.0
COPd 3.22 3.25
Pdh kW 6.3 6.6
PERd % 128.8 130.0
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.9
COPd 5.88
Pdh kW 5.4
PERd % 235.2
Tbiv (bivalent temperature)
COPd 1.90 1.78
Pdh kW 9.8 10.3
PERd % 76.0 71.2
Tbiv °C 2
Average climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Cold climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Qhe Annual energy consumption (GCV)
Gj -
Warm climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Notes
(1) EW 30°C; LW 35°C; ambient conditions: 7°CDB/6°CWB
(2) EW 40°C; LW 45°C; ambient conditions: 7°CDB/6°CWB
(3) EW 30°C; LW 35°C; ambient conditions: -7°CDB/-8°CWB
(4) EW 30°C; LW 35°C; ambient conditions: 2°CDB/1°CWB
(5) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
(6) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
(7) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
(8) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
Domestic hot water heating
General Declared load profile XL
Function to fix water heating during off peak hours
Yes
Average climate AEC (Annual electricity consumption)
kWh 2,158
ηwh (water heating efficiency)
% 84
Qelec (Daily electricity consumption)
kWh 9.681
Water heating energy efficiency class
A
Cold climate AEC (Annual electricity consumption)
kWh 2,394
ηwh (water heating efficiency)
% 76
Qelec (Daily electricity consumption)
kWh 10.755
Warm climate AEC (Annual electricity consumption)
kWh 1,921
ηwh (water heating efficiency)
% 95
Qelec (Daily electricity consumption)
kWh 8.600
CONNECTABLE INDOOR UNITS
2-18 Capacity and Power input
EHVZ04S18CB3V/
ERLQ004CV3
EHVZ08S18CB3V/
ERLQ006CV3
EHVZ08S18CB3V/
ERLQ008CV3
EHVZ16S18CB3V/
ERLQ011CV3
EHVZ16S18CB3V/
ERLQ014CV3
EHVZ16S18CB3V/
ERLQ016CV3
Heating capacity Min. kW 1.80 (1) -
Nom. kW 4.40 (1) / 4.03 (2)
6.00 (1) / 5.67 (2)
7.40 (1) / 6.89 (2)
11.2 (1) / 11.0 (2)
14.4 (1) / 13.5 (2)
15.9 (1) / 15.1 (2)
Max. kW 5.12 (1) / 4.90 (2)
8.35 (1) / 7.95 (2)
10.0 (1) / 9.53 (2)
8.60 (3) / 8.60 (4)
10.5 (3) / 10.7 (4)
11.3 (3) / 10.8 (4)
Power input Heating Nom. kW 0.870 (1) / 1.13 (2)
1.27 (1) / 1.59 (2)
1.66 (1) / 2.01 (2)
2.43 (1) / 3.10 (2)
3.39 (1) / 4.12 (2)
3.77 (1) / 4.67 (2)
Max. kW - 3.13 (3) / 4.10 (4)
4.02 (3) / 5.21 (4)
4.33 (3) / 5.22 (4)
COP 5.04 (1) / 3.58 (2)
4.74 (1) / 3.56 (2)
4.45 (1) / 3.42 (2)
4.60 (1) / 2.75 (3) / 3.55 (2) /
2.10 (4)
4.24 (1) / 2.61 (3) / 3.28 (2) /
2.05 (4)
4.22 (1) / 2.61 (3) / 3.23 (2) /
2.07 (4)
Tank Name Stainless steel domestic hot water tank 180 l
Water side Heat exchanger
Water flow rate Heating Nom. l/min 12.6 (5) / 11.6 (6)
17.2 (5) / 16.3 (6)
21.2 (5) / 19.8 (6)
32.1 (1) / 31.5 (1)
41.3 (1) / 38.7 (2)
45.6 (1) / 43.3 (2)
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 83
• Outdoor Unit • ERLQ-CV3
2
84
2 Specifications
General Supplier/Manufacturer details
Name and address Daikin Europe N.V. - Zandvoordestraat 300, 8400 Oostende, Belgium
Name or trademark Daikin Europe N.V.
Product description Air-to-water heat pump Yes
Brine-to-water heat pump No
Heat pump combination heater Yes
Low-temperature heat pump No
Supplementary heater integrated Yes
Water-to-water heat pump No
LW(A) Sound power level (according to EN14825)
Indoor dB(A) 42.0 47.0
LW(A) Sound power level (according to EN14825)
Outdoor dB(A) 61.0 62.0 64.0 66.0
Sound condition Ecodesign and energy label Sound power in heating mode, measured according to the EN12102 under conditions of the EN14825
Space heating general Air to water unit Rated airflow (outdoor) m³/h 2,700 2,820 5,400
Brine/water to water unit
Rated water/brine flow m³/h 0.00
Other Capacity control Inverter
Cdh (Degradation heating) 1.00
Pck (Crankcase heater mode)
kW 0.00 0.055
Poff (Off mode) kW 0.0080 0.055
Psb (Standby mode) kW 0.0080 0.055
Pto (Thermostat off) kW 0.0060 0.0070 0.0080 0.057
Integrated supplementary heater
NOx emission mg/kWh 0.00
Psup kW 3.00
Type of energy input Electrical
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Average climate water outlet 55°C
General SCOP 3.20 3.22 3.23 3.09 3.16 3.06
Annual energy consumption
kWh 2,360 3,370 4,060 6,260 7,900 8,970
Annual energy consumption (GCV)
Gj 8.48 12.1 14.6 22.6 28.4 32.3
ηs (Seasonal space heating efficiency)
% 125 126 120 123 119
Prated at -10°C
kW 3.70 5.30 6.40 9.99 12.7 13.9
Seasonal space heating eff. class
A++ A+
A Condition (-7°CDB/-8°CWB)
Cdh (Degradation heating)
1.00
COPd 2.03 2.02 1.98 1.99 1.76 1.78
Pdh kW 3.36 4.50 5.47 8.83 9.97 12.2
PERd % 81.2 80.8 79.2 79.6 70.4 71.2
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00 0.990 1.00
COPd 3.08 3.17 3.24 3.55 3.12
Pdh kW 2.00 4.43 3.43 5.28 6.76 7.61
PERd % 123 127 130 142 125
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.990 0.950 1.00
COPd 4.27 4.20 4.31 4.22 4.40
Pdh kW 2.77 3.51 3.50 4.47 4.66 4.83
PERd % 171 168 172 169 176
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.990 0.930 0.940 0.930
COPd 6.33 5.82 6.41 5.44 6.36
Pdh kW 2.65 3.28 5.37 5.26 5.38
PERd % 253 233 256 218 254
Tol (temperature operating limit)
COPd 1.80 1.74 1.66 1.79 1.75 1.71
Pdh kW 3.76 4.62 6.18 9.08 12.2 13.3
PERd % 72.0 69.6 66.4 71.6 70.0 68.4
TOL °C -10.0
WTOL °C 55.0
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.00 0.680 0.220 0.910 0.550 0.580
Tbiv (bivalent temperature)
COPd 1.80 1.74 1.66 1.99 1.92 1.78
Pdh kW 3.76 5.09 6.18 8.83 11.0 12.2
PERd % 72.0 69.6 66.4 79.6 76.8 71.2
Tbiv °C -10.0 -9.00 -10.0 -7.00 -6.00 -7.00
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 85
• Outdoor Unit • ERLQ-CV3
2
86
2 Specifications
Space heating Cold climate water outlet 55°C
General Annual energy consumption
kWh 2,130 2,310 3,090 6,740 7,870 8,580
Annual energy consumption (GCV)
Gj 7.68 8.30 11.1 24.3 28.3 30.9
ηs (Seasonal space heating efficiency)
% 107 110 95.0 95.5 98.3
Prated at -22°C
kW 2.39 2.60 3.56 6.99 8.15 9.12
Warm climate water outlet 55°C
General Annual energy consumption
kWh 1,170 1,490 1,900 2,630 3,270 3,420
Annual energy consumption (GCV)
Gj 4.20 5.37 6.85 9.47 11.8 12.3
ηs (Seasonal space heating efficiency)
% 186 182 178 125 135 136
Prated at 2°C
kW 4.27 5.30 6.59 7.58 9.84 10.3
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Space heating Average climate water outlet 35°C
General SCOP 4.52 4.29 4.34 -
Annual energy consumption
kWh 1,980 2,540 3,490 -
Annual energy consumption (GCV)
Gj 7.13 9.14 12.6 -
ηs (Seasonal space heating efficiency)
% 178 169 171 -
Prated at -10°C
kW 4.40 5.34 7.40 -
Seasonal space heating eff. class
A++ -
A Condition (-7°CDB/-8°CWB)
COPd 3.01 2.69 -
Pdh kW 4.01 4.72 6.68 -
PERd % 120 108 -
B Condition (2°CDB/1°CWB)
Cdh (Degradation heating)
1.00 0.990 1.00 -
COPd 4.41 4.24 -
Pdh kW 2.40 3.90 -
PERd % 176 170 -
C Condition (7°CDB/6°CWB)
Cdh (Degradation heating)
0.980 1.00 -
COPd 5.85 5.75 -
Pdh kW 1.70 2.59 -
PERd % 234 230 -
D Condition (12°CDB/11°CWB)
Cdh (Degradation heating)
0.980 -
COPd 7.71 7.27 -
Pdh kW 2.04 2.61 -
PERd % 308 291 -
Tol (temperature operating limit)
COPd 2.61 2.29 -
Pdh kW 4.36 4.70 6.81 -
PERd % 104 91.6 -
TOL °C -10.0 -
WTOL °C 35.0 -
Tbiv (bivalent temperature)
COPd 2.61 2.47 -
Pdh kW 4.36 4.93 7.14 -
PERd % 104 98.8 -
Tbiv °C -10.0 -8.00 -
Rated heat output supplementary capacity
Psup (at Tdesign -10°C)
kW 0.040 0.640 0.590 -
Cold climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Qhe Annual energy consumption (GCV)
Gj -
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3 87
• Outdoor Unit • ERLQ-CV3
2
88
2 Specifications
Notes
(1) Condition 1: cooling Ta 35°C - LWE 18°C (DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
(2) Condition 2: cooling Ta 35°C - LWE 7°C ( DT = 5°C); heating Ta DB/WB 7°C/6°C - LWC 45°C ( DT = 5°C )
(3) Condition 3: heating Ta DB -7°C (RH85%) - LWC 35°C
(4) Condition 4: heating Ta DB -7°C (RH85%) - LWC 45°C
(5) DB/WB 7°C/6°C - LWC 35°C (DT=5°C)
(6) DB/WB 7°C/6°C - LWC 45°C (Dt=5°C)
(7) Capacity must be split up over the additional and main zone. Refer to ESP-data for more details on available head (kPa).
Space heating Warm climate water outlet 35°C
General ηs (Seasonal space heating efficiency)
% -
Pump Additional Zone Nominal ESP unit (*RLQ*C*)
Heating kPa 52.3 (5) / 55.4 (6)
40.6 (5) / 43.3 (6)
28.3 (5) / 32.7 (6)
26.2 (1) / 28.3 (2)
25.0 (7)
Pump Main Zone Nominal ESP unit (*RLQ*C*)
Heating kPa 48.6 (5) / 51.9 (6)
39.5 (5) / 42.3 (6)
26.4 (5) / 31.2 (6)
18.2 (1) / 20.7 (2)
25.0 (7)
Domestic hot water heating
General Declared load profile L
Function to fix water heating during off peak hours
Yes
Average climate AEC (Annual electricity consumption)
kWh 1,080 1,190 1,170
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 95.0 86.4 87.4
Qelec (Daily electricity consumption)
kWh 4.93 5.43 5.32
Qfuel (Daily fuel consumption)
kWh 0.00
Water heating energy efficiency class
A
Cold climate AEC (Annual electricity consumption)
kWh 1,220 1,330 1,340
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 84.0 77.5 76.6
Qelec (Daily electricity consumption)
kWh 5.55 6.05 6.08
Qfuel (Daily fuel consumption)
kWh 0.00
Warm climate AEC (Annual electricity consumption)
kWh 966 1,120 1,110
AFC (Annual fuel consumption)
Gj 0.00
ηwh (water heating efficiency)
% 106 91.8 92.3
Qelec (Daily electricity consumption)
kWh 4.39 5.10 5.04
Qfuel (Daily fuel consumption)
kWh 0.00
2-19 Technical Specifications ERLQ004CV3 ERLQ006CV3 ERLQ008CV3 ERLQ011CV3 ERLQ014CV3 ERLQ016CV3
Dimensions Unit HeightxWidthxDepth
mm 735x832x307 1,345x900x320
Weight Unit kg 54 56 113
Compressor Quantity 1
Type Hermetically sealed swing compressor Hermetically sealed scroll compressor
CONNECTABLE INDOOR UNITS
• Heating • ERLQ-CV3
3
2
• Outdoor Unit • ERLQ-CV3
2 Specifications
Notes
(1) Operation range domestic hot water (outdoor unit): range increase by support booster heater or backup heater. See separate drawing for operation range.
(2) The sound pressure level is measured via a microphone at a certain distance from the unit. It is a relative value depending on the distance and acoustic environment. Refer to
sound spectrum drawing for more information.
(3) Daikin Altherma inverter controlled compressor starting current always \<= max. running current
(4) Contains fluorinated greenhouse gases
Operation range heating (outdoor unit): range increase by support back-up heater. See separate drawing for operation range.
Condition: Ta DB/WB 7°C/6°C - LWC 35°C (DT = 5°C)
Condition: Ta 35°C - LWE 7°C ( DT = 5°C)
Operation range Cooling Min.~Max. °CDB 10.0~43.0 10.0~46.0
Domestic hot water Min.~Max. °CDB -25 (1)~35 (1) -20 (1)~35 (1)
Refrigerant Type R-410A
GWP 2,087.5
Charge TCO2eq 3.1 3.3 7.1
kg 1.5 1.6 3.4
Control Expansion valve (electronic type)
Sound power level Heating Nom. dBA 61 62 64 (2) 66 (2)
Cooling Nom. dBA 63 64 (3) 66 (3) 69 (3)
Sound pressure level Heating Nom. dBA 48 (2) 49 (2) 51 (4) 52 (4)
Cooling Nom. dBA 48 (2) 49 (2) 50 (2) 50 (4) 52 (4) 54 (4)
2-20 Electrical Specifications ERLQ004CV3 ERLQ006CV3 ERLQ008CV3 ERLQ011CV3 ERLQ014CV3 ERLQ016CV3
Power supply Name/Phase/Frequency/Voltage Hz/V V3/1~/50/230
Current Recommended fuses A 16 20 40
2-19 Technical Specifications ERLQ004CV3 ERLQ006CV3 ERLQ008CV3 ERLQ011CV3 ERLQ014CV3 ERLQ016CV3
• Heating • ERLQ-CV3 89
• Outdoor Unit • ERLQ-CV3
3
90
3 Electrical data3 - 1 Electrical Data
ERLQ004-008CV3Starting current
1 2
1 2
Specifications
Example
Standard On/OFF compressor starting current >> max. running current
Example
Running current [A]
Maximum running current
Time
Daikin Altherma inverter-controlled compressor starting current always max. running current.
Time
Running current [A]
Maximum running current
Example Example
Figure ·A· Starting current
4D094715A
• Heating • ERLQ-CV3
3
4
• Outdoor Unit • ERLQ-CV3
4 Capacity tables4 - 1 Cooling Capacity Tables
∼
• Heating • ERLQ-CV3 91
3
4
• Outdoor Unit • ERLQ-CV3
4 Capacity tables4 - 2 Heating Capacity Tables
∼
• Heating • ERLQ-CV3 93
3
4
• Outdoor Unit • ERLQ-CV3
4 Capacity tables4 - 2 Heating Capacity Tables
ERLQ011-016C
3TW60332-5A
Capacity in function of � eld piping length for inverter
Field piping length (m)
Cooling
Heating
Capacity (%)
NOTE
Capacity drop is at nominal capacity
• Heating • ERLQ-CV3 95
• Outdoor Unit • ERLQ-CV3
4
96
4 Capacity tables4 - 3 Certification Programs
ERLQ004 008CV3
Rated data for certification programmes heating mode
Certification programme Ta [°C] EWC [°C] LWC [°C] HC [kW] COP
Minim
umrequ
iredCO
P
Vivrelec
Minim
umrequ
iredCO
P
NFPA
C
Minim
umrequ
iredCO
P
EHPA
Minim
umrequ
iredCO
P
Ecolab
el
Minim
umrequ
iredCO
P
SEI
Minim
umrequ
iredCO
P
microgene
ratio
n
Minim
umrequ
iredCO
P
SPF(DAB
)
EHPA 10/8 30 35 4,47 5,12Crédit d'impôt, NF PAC 7/6 30 35 4,40 5,04EHPA 2/1 35 3,27 4,02NF PAC, EHPA 7/ 8 35 4,37 2,81SPF 2/1 30 35 3,27 4,02NF PAC 7/6 40 45 4,03 3,58EHPA 7/ 8 45 4,20 2,27NF PAC 7/ 8 45 4,70 2,34EHPA 7/6 47 55 3,71 2,91EHPA 7/ 8 55 3,74 1,80EHPA 10/8 30 35 6,25 5,07Crédit d'impôt, NF PAC 7/6 30 35 6,00 4,74EHPA 2/1 35 4,58 3,66NF PAC, EHPA 7/ 8 35 5,31 2,84SPF 2/1 30 35 4,05 3,88NF PAC 7/6 40 45 5,67 3,56NF PAC 7/ 8 45 5,12 2,22EHPA 7/6 47 55 5,43 2,95EHPA 7/ 8 55 4,47 1,80EHPA 10/8 30 35 7,39 4,75Crédit d'impôt, NF PAC 7/6 30 35 7,40 4,45EHPA 2/1 35 5,80 3,53NF PAC, EHPA 7/ 8 35 5,46 2,71SPF 2/1 30 35 4,56 3,81NF PAC 7/6 40 45 6,89 3,42NF PAC 7/ 8 45 6,13 2,12EHPA 7/6 47 55 6,79 2,87EHPA 7/ 8 55 5,59 1,80
Rated data for certification programmes standby power consumption
Certification programmeNF PAC 7,5WNF PAC 7,5WNF PAC 7,5W
Sound power measurements
Certification programmeRequired setup of unit
for testTa [°C] EW [°C] LW [°C] Mode dBA
Promotelec, Ecolabel, Eurovent Nominal 7/6 30 35 Heating 40
NF PAC, Ecolabel Nominal 7/6 30 35 Heating 42
Symbols
CC= Cooling capacity at maximum operating frequency, measured according to EN 14511.HC= Heating capacity at maximum operating frequency, measured according to EN 14511
COP/EER= Coefficient of Performance/Energy efficiency ratio according to EN 14511.LWE= Leaving water evaporator temperature [°C]LWC= Leaving water condensor temperature [°C]
Ta= Ambient temperature [°C DB/WB]
PI [W]
*RLQ004**RLQ006**RLQ008*
EHVZ04S18CB3V
EHVZ08S18CB3V
1,30Radiator 2,201,60
3,71
Fan coil 2,50 2,701,50
3,002,00 2,10
4,00 3,40 3,20
*RLQ008*
Floor
4,00
3,10
1,30Radiator 2,201,60
3,71
Fan coil 2,50 2,701,50
3,002,00 2,10
4,00 3,40 3,20
*RLQ006*
Floor
4,00
3,10
1,30Radiator 2,201,50 1,60
3,71
Fan coil2,50 2,70
3,10
3,002,00 2,10
4,00 3,40 3,20
*RLQ004*
Floor
4,00
3,10
3D096433
ERLQ004-008CV3
Rated data for certification programmes - heating mode
Certification programme Ta [°C] EWC [°C] LWC [°C] HC [kW] COP
Min
imum
requ
ired
COP
Vivr
elec
Min
imum
requ
ired
COP
NF
PAC
Min
imum
requ
ired
COP
EHPA
Min
imum
requ
ired
COP
Ecol
abel
Min
imum
requ
ired
COP
SEI
Min
imum
requ
ired
COP
mic
roge
nera
tion
Min
imum
requ
ired
COP
SPF
(DAB
)
EHPA 10/8 30 35 4,47 5,12Crédit d'impôt, NF PAC, Microgeneration 7/6 30 35 4,40 5,04EHPA, SEI 2/1 35 3,27 4,02NF PAC, EHPA -7/-8 35 4,37 2,81Ecolabel, SPF 2/1 30 35 3,27 4,02NF PAC 7/6 40 45 4,03 3,58EHPA -7/-8 45 4,20 2,27NF PAC -7/-8 45 4,70 2,34Ecolabel 2/1 40 45 3,97 2,77Danish incentive (< 2013) 2/1 50 55 3,93 2,43Danish incentive (< 2013) -7/-8 50 55 4,20 1,98EHPA 7/6 47 55 3,71 2,91EHPA -7/-8 55 3,74 1,80EHPA 10/8 30 35 6,25 5,07Crédit d'impôt, NF PAC, Microgeneration 7/6 30 35 6,00 4,74EHPA, SEI 2/1 35 4,58 3,66NF PAC, EHPA -7/-8 35 5,31 2,84Ecolabel 2/1 30 35 4,58 3,66SPF 2/1 30 35 4,05 3,88NF PAC 7/6 40 45 5,67 3,56NF PAC -7/-8 45 5,12 2,22Ecolabel 2/1 40 45 5,69 2,81Danish incentive (< 2013) 2/1 50 55 5,27 2,29Danish incentive (< 2013) -7/-8 50 55 4,96 1,86EHPA 7/6 47 55 5,43 2,95EHPA -7/-8 55 4,47 1,80EHPA 10/8 30 35 7,39 4,75Crédit d'impôt, NF PAC, Microgeneration 7/6 30 35 7,40 4,45EHPA, SEI 2/1 35 5,80 3,53NF PAC, EHPA -7/-8 35 5,46 2,71Ecolabel 2/1 30 35 5,80 3,53SPF 2/1 30 35 4,56 3,81NF PAC 7/6 40 45 6,89 3,42NF PAC -7/-8 45 6,13 2,12Ecolabel 2/1 40 45 6,08 2,63Danish incentive (< 2013) 2/1 50 55 5,45 2,27Danish incentive (< 2013) -7/-8 50 55 5,50 1,86EHPA 7/6 47 55 6,79 2,87EHPA -7/-8 55 5,40 1,80
Rated data for certification programmes - cooling mode
Certification programme Ta [°C] EWC [°C] LWC [°C] CC [kW] EER
Min
imum
requ
ired
EER
Vivr
elec
Min
imum
requ
ired
EER
Italy
D1
*RLQ004* Floor Ecolabel, Italy D1 35 23 18 4,08 4,55Fan coil Ecolabel 35 12 7 4,17 2,32
*RLQ006* Floor Ecolabel, Italy D1 35 23 18 5,88 3,89Fan coil Ecolabel 35 12 7 4,84 2,34
*RLQ008* Floor Ecolabel, Italy D1 35 23 18 6,20 3,79Fan coil Ecolabel 35 12 7 5,36 2,29
Rated data for certification programmes - standby power consumption
Certification programmeNF PAC 7,5WNF PAC 7,5WNF PAC 7,5W
Sound power measurements
Certification programmeRequired setup of
unit for testTa [°C] EW [°C] LW [°C] Mode dBA
Promotelec, Ecolabel, Eurovent Nominal 35 12 7 Cooling4042
NF PAC, Ecolabel Nominal 7/6 30 35 Heating4042
SymbolsCC= Cooling capacity at maximum operating frequency, measured according to EN 14511.HC= Heating capacity at maximum operating frequency, measured according to EN 14511
COP/EER= Coefficient of Performance/Energy efficiency ratio according to EN 14511.LWE= Leaving water evaporator temperature [°C]LWC= Leaving water condensor temperature [°C]
Ta= Ambient temperature [°C DB/WB]sCOP = Seasonal coefficient of performance, according to EN14825 and EN14511
EHB(H/X)(04/08)*EHV(H/X)(04/08)*
EHB(H/X)(04/08)*EHV(H/X/Z)(04/08)*
3
*RLQ008*Danish energy agency Average climate - low temperature (35°C) 4,34 3,5
Danish energy agency Average climate - high temperature( 55°C) 3,2 3
*RLQ006**RLQ006*
Danish energy agency Average climate - low temperature (35°C) 4,29 3,5*RLQ008* Danish energy agency Average climate - high temperature( 55°C) 3,22
3,5*RLQ004* Danish energy agency Average climate - high temperature( 55°C) 3,2 3
Rated data for certification programmes - heating mode
Min
imum
requ
ired
COP
DEA
PI [W]Certification programme sCOP
*RLQ004*Danish energy agency Average climate - low temperature (35°C) 4,52
2,20 - - - - -2,20 3,60 - - - -2,20 - - - - -2,20 3,60 - - - -2,20 - - - - -2,20 3,60 - - - -
-- 1,30 - - - - -- 2,20 - - - -
-- - - - - - -
- - -
Radiator
- - - - - -
- -1,50 1,60 - - - - -Fan coil2,50 2,70 - - -
- - 2,60
-- - - - - - 3,71- - - 3,10 - -
3,00 - -2,00 2,10 - - - - -
- - -4,00 3,40 - - - 3,20 -
*RLQ008*
Floor
4,00 - - -
- - 3,10 -
-- 1,30 - - - - -- 2,20 - - - -
-- - - - - - -
-
Radiator
- - - - - -
- -1,50 1,60 - - - - -Fan coil2,50 2,70 - - -
1,50 - 2,60
-- - - - - - 3,71- - - 3,10 - -
3,00 - -2,00 2,10 - - - - -
- - -4,00 3,40 - - - 3,20 -
*RLQ006*
Floor
4,00 - - -
- - 3,10 -
- - -- 1,30 - - - - -
- -- - - - - - -
Radiator
- - - - -
- 2,20 - -
-1,50 - - 2,60 - - -1,50 1,60 - - - -
- - - - - -
3,71
Fan coil
2,50 2,70 - - - - --
- - - 3,10 - -
3,00 - -2,00 2,10 - - - - -
- - -4,00 3,40 - - - 3,20 -
*RLQ004*
Floor
4,00 - - -
- - 3,10 -
3TW60819-3G
• Heating • ERLQ-CV3
3
4
• Outdoor Unit • ERLQ-CV3
4 Capacity tables4 - 3 Certification Programs
ERLQ011 016CV3
Certification programme Ta [°C] EWC [°C] LWC [°C]HC [kW] COP
Minim
umrequ
ired
COP
NFPA
C
Minim
umrequ
ired
COP
EHPA
Minim
umrequ
ired
COP
Ecolab
el
Minim
umrequ
ired
COP
SPF(DAB
)
EHPA 10 35 11,20 4,85NF PAC, EHPA 7/6 30 35 11,20 4,60EHPA 2/1 35 8,56 3,60SPF (DAB) 2/1 30 35 5,71 3,71NF PAC, EHPA 7/ 8 35 8,60 2,75NF PAC 7/6 40 45 11,00 3,55
2/1 45 8,20 2,84NF PAC 7/ 8 45 8,60 2,10EHPA 7/6 47 55 10,76 2,71EHPA 7/ 8 55 8,79 1,74EHPA 10 35 14,30 4,70NF PAC, EHPA 7/6 30 35 14,40 4,24EHPA 2/1 35 10,20 3,35SPF (DAB) 2/1 30 35 5,71 3,71NF PAC, EHPA 7/ 8 35 10,50 2,61NF PAC 7/6 40 45 13,50 3,28
2/1 45 9,90 2,63NF PAC 7/ 8 45 10,70 2,05EHPA 7/6 47 55 13,30 2,71EHPA 7/ 8 55 10,83 1,74EHPA 10 35 15,70 4,50NF PAC, EHPA 7/6 30 35 15,90 4,22EHPA 2/1 35 10,90 3,31SPF (DAB) 2/1 30 35 5,71 3,71NF PAC 7/ 8 35 11,30 2,61NF PAC 7/6 40 45 15,10 3,23
2/1 45 10,80 2,63NF PAC 7/ 8 45 10,80 2,07EHPA 7/6 47 55 15,04 2,80EHPA 7/ 8 55 10,79 1,71
Rated data for certification programmes standby power consumption
Certification programmeNF PAC 22WNF PAC 25WNF PAC 22WNF PAC 25WNF PAC 22WNF PAC 25W
Symbols
CC= Cooling capacity at nominal operating frequency, measured according to EN14511.HC= Heating capacity at nominal operating frequency, measured according to EN14511.
COP/EER= Coefficient of Performance/Energy efficiency ratio according to EN 14511.LWE= Leaving water evaporator temperature [°C]LWC= Leaving water condensor temperature [°C]
Ta= Ambient temperature [°C DB/WB]
*RLQ011C* V3*RLQ011C* W1*RLQ014C* V3*RLQ014C* W1*RLQ016C* V3*RLQ016C* W1
Radiator
2,601,60
2,10
Fan coil2,70
3,103,71
*RLQ016C*
Floor3,40
Radiator
1,60
2,10
Fan coil2,70
3,103,71
*RLQ014C*
Floor3,40
Radiator
2,601,60
2,10
Fan coil2,70
3,103,71
Rated data for certification programmes heating mode
*RLQ011C*
Floor3,40
3D091994
ERLQ011 016CV3
Certification programme Ta [°C] EWC [°C] LWC [°C]HC [kW] COP
Minim
umrequ
iredCO
P
NFPA
C
Minim
umrequ
iredCO
P
EHPA
Minim
umrequ
iredCO
P
Ecolabel
Minim
umrequ
iredCO
P
SPF(DAB
)
EHPA 10 35 11,20 4,85NF PAC, EHPA 7/6 30 35 11,20 4,60EHPA 2/1 35 8,56 3,60Ecolabel 2/1 30 35 8,56 3,60SPF (DAB) 2/1 30 35 5,71 3,71NF PAC, EHPA, Piemonte (Italy) 7/ 8 35 8,60 2,75NF PAC 7/6 40 45 11,00 3,55
2/1 45 8,20 2,84NF PAC 7/ 8 45 8,60 2,10Ecolabel 2/1 40 45 8,20 2,80EHPA 7/6 47 55 10,76 2,71EHPA 7/ 8 55 8,79 1,74EHPA 10 35 14,30 4,70NF PAC, EHPA 7/6 30 35 14,50 4,30EHPA 2/1 35 10,30 3,41Ecolabel 2/1 30 35 10,30 3,41SPF (DAB) 2/1 30 35 5,71 3,71NF PAC, EHPA 7/ 8 35 10,60 2,65Piemonte (Italy) 7/ 8 35 8,60 2,75NF PAC 7/6 40 45 13,60 3,32
2/1 45 10,00 2,67NF PAC 7/ 8 45 10,80 2,08Ecolabel 2/1 40 45 10,00 2,70EHPA 7/6 47 55 13,30 2,71EHPA 7/ 8 55 10,83 1,74EHPA 10 35 15,70 4,50NF PAC, EHPA 7/6 30 35 16,00 4,25EHPA 2/1 35 11,10 3,35Ecolabel 2/1 30 35 11,10 3,35SPF (DAB) 2/1 30 35 5,71 3,71NF PAC 7/ 8 35 11,40 2,64Piemonte (Italy) 7/ 8 35 8,60 2,75NF PAC 7/6 40 45 15,20 3,26
2/1 45 10,90 2,63NF PAC 7/ 8 45 10,90 2,09Ecolabel 2/1 40 45 10,90 2,66EHPA 7/6 47 55 15,04 2,80EHPA 7/ 8 55 10,79 1,71
Certification programme Ta [°C] EWC [°C] LWC [°C] CC [kW] EER
Minim
umrequ
ired
EER
Ecolabel
Minim
umrequ
ired
EER
ItalyD1
Floor Ecolabel, Italy D1 35 23 18 12,13 3,98Fan coil Ecolabel 35 12 7 11,72 2,72
Floor Ecolabel, Italy D1 35 23 18 12,72 3,96Fan coil Ecolabel 35 12 7 12,55 2,47
Floor Ecolabel, Italy D1 35 23 18 13,79 3,69Fan coil Ecolabel 35 12 7 13,12 2,29
Certification programme
NF PAC 22WNF PAC 25WNF PAC 22WNF PAC 25WNF PAC 22WNF PAC 25W
SymbolsCC= Cooling capacity at nominal operating frequency, measured according to EN14511.HC= Heating capacity at nominal operating frequency, measured according to EN14511.
COP/EER= Coefficient of Performance/Energy efficiency ratio according to EN 14511.LWE= Leaving water evaporator temperature [°C]LWC= Leaving water condensor temperature [°C]
Ta= Ambient temperature [°C DB/WB]
*RLQ016C* W1
*RLQ014C* W1*RLQ016C* V3
*RLQ011C* W1*RLQ014C* V3
Rated data for certification programmes standby power consumption
*RLQ011C* V3
*RLQ016C*2,20 3,602,20
*RLQ014C*2,20 3,602,20
Rated data for certification programmes cooling mode
*RLQ011C*2,20 3,602,20
Radiator
Fan coil
2,702,60
1,60
2,10
3,103,71
3,10
*RLQ016C*
Floor
3,40
2,60
Radiator
1,60Fan coil
2,70
3,712,10
3,103,10
*RLQ014C*
Floor
3,40
Radiator
Fan coil
2,702,60
1,60
3,712,10
3,103,10
Rated data for certification programmes heating mode
*RLQ011C*
Floor
3,40
3TW60332 3F
• Heating • ERLQ-CV3 97
• Outdoor Unit • ERLQ-CV3
5
98
5 Dimensional drawings5 - 1 Dimensional Drawings
ERLQ011-016CV3
3TW60334-2
Hole for anchor 1 Gas pipe connection Ø15.9 � are2 Liquid connection pipe Ø9.5 flare3 Service port (in the unit)4 Electronic connection and grounding terminal M5 (in switchbox)5 Refrigerant piping intake6 Power supply wiring intake (knock hole Ø34)7 Control wiring intake (knock hole Ø27)8 Drain outlet
• Heating • ERLQ-CV3
3
6
• Outdoor Unit • ERLQ-CV3
6 Centre of gravity6 - 1 Centre of Gravity
ERLQ011-016CV3
4TW31729-4
• Heating • ERLQ-CV3 99
3
8
• Outdoor Unit • ERLQ-CV3
8 Wiring diagrams8 - 1 Wiring Diagrams - Single Phase
∼
∼
∼
∼
• Heating • ERLQ-CV3 101
• Outdoor Unit • ERLQ-CV3
8
102
8 Wiring diagrams8 - 1 Wiring Diagrams - Single Phase
ERLQ011-016CV3
A1P Printed circuit board (main) K2R Magnetic relay (Y3S) R5T Thermistor (heat exchanger middle)A2P Printed circuit board (service) K3R Magnetic relay (E1H) R6T Thermistor (liquid)A3P Printed circuit board (noise � lter) K4R Magnetic relay (E1HC) RC Signal receiver circuitA4P Printed circuit board (communication) K10R Magnetic relay (upload) R10T Thermistor (fin)BS1~BS4 Push button switch K11R Magnetic relay (main) S1NPH Pressure sensorC1~C4 Capacitor L1R Reactor S1PH Pressure switch (high)DS1 Dip switch M1C Motor (compressor) TC Signal transmission circuitE1H Bottomplate heater M1F Motor (fan) (upper) V1R Power moduleE1HC Crankcase heater M2F Motor (fan) (lower) V2R,V3R Diode module F1U,F3U,F4U Fuse (T 3.6A / 250V) PS Swtiching power supply V1T IGBTF6U Fuse (T 5.0A / 250V) Q1DI Earth leakage circuit breaker X1M Terminal strip (power supply)F7U,F8U Fuse (F 1.0A / 250V) R1 Resistor Y1E Electronic expansion valve (main)
H1P~7P (A2P)
Light emit. diode (serv. monitor-orange)[H2P] Pepare, test ............................ � ickering Malfunction detection ..................light up
R2 Resistor Y3E Electronic expansion valve (inj)R1T Thermistor (air) Y1S Solenoid valve (4 way valve)R2T Thermistor (discharge) Y3S Solenoid valve (hot gas pass)
HAP(A1P)
Light emitting diode(Service monitor green)
R3T Thermistor (suction) Z1C~Z3C Noise filter (ferrity core)R4T Thermistor (heat exchanger) Z1F~Z4F Noise filter
K1R Magnetic relay (Y1S)
NOTES
1. This wiring diagram only applies to the outdoor unit2. L: live, N: neutral, : � eld wiring3. : terminal strip, : connector, : connection, : protective earth (screw), : connector, : noiseless earth, : terminal4. Refer to the option manual, for connecting wiring to X6A.5. Refer to the ‘wiring diagram sticker’ (on back of front plate) on how to use BS1~BS4 and DS1 switch6. Do not operate the unit by short-circuiting protection device S1PH7. Colors: = blue, = brown, = green, = red, = white, = yellow, = orange, = black8. Con� rm the method of setting the selector switches (DS1) by service manual; Factory setting of all switches: “off”9. : option, : wiring dependent on model
2TW60336-2
1N~50Hz230V
Wire entrance
HAP
A1P(Back) (Front)
El. compo. assy.(position of elements)
Position of compressor
terminal
(Note 4)
Indoor
Outdoor
• Heating • ERLQ-CV3
3
9
• Outdoor Unit • ERLQ-CV3
9 Sound data9 - 1 Sound Power Spectrum Quiet Mode
NOTES
1 Data is valid at free field condition (measured in a semi-anachoic room).2 dBA = A-weighted sound pressure level. (A-scale according to IEC)3 Reference acoustic pressure 0dB = 20 Pa.4 If the sound is measured under actual installation conditions, the measured value will be
higher due to environmental noise and sound reflections.5 Data is valid at night quiet mode level 2
Measuring location (discharge side):
Soun
d pre
ssur
e lev
el (d
B)
Soun
d pre
ssur
e lev
el (d
B)
Soun
d pre
ssur
e lev
el (d
B)
Cooling
Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz)
3TW60337-3
NOTES
1 Data is valid at free field condition (measured in a semi-anachoic room).2 dBA = A-weighted sound pressure level. (A-scale according to IEC)3 Reference acoustic pressure 0dB = 20 Pa.4 If the sound is measured under actual installation conditions, the measured value will be
higher due to environmental noise and sound reflections.5 Data is valid at night quiet mode level 2
Measuring location (discharge side):
Soun
d pre
ssur
e lev
el (d
B)
Soun
d pre
ssur
e lev
el (d
B)
Soun
d pre
ssur
e lev
el (d
B)
Heating
Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz)
3TW60337-4
• Heating • ERLQ-CV3 103
• Outdoor Unit • ERLQ-CV3
9
104
9 Sound data9 - 2 Sound Pressure Spectrum - Cooling
• Heating • ERLQ-CV3
3
9
• Outdoor Unit • ERLQ-CV3
9 Sound data9 - 2 Sound Pressure Spectrum - Cooling
NOTES
1 Data is valid at free field condition (measured in a semi-anachoic room).2 dBA = A-weighted sound pressure level. (A-scale according to IEC)3 Reference acoustic pressure 0dB = 20 Pa.4 If the sound is measured under actual installation conditions, the measured value will be
higher due to environmental noise and sound reflections.5 Data is valid at nominal capacity
Measuring location (discharge side):
Soun
d pre
ssur
e lev
el (d
B)
Soun
d pre
ssur
e lev
el (d
B)
Soun
d pre
ssur
e lev
el (d
B)
Cooling
Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz)
3TW60337-1
• Heating • ERLQ-CV3 105
• Outdoor Unit • ERLQ-CV3
9
106
9 Sound data9 - 3 Sound Pressure Spectrum - Heating
NOTES
1 Data is valid at free field condition (measured in a semi-anachoic room).2 dBA = A-weighted sound pressure level. (A-scale according to IEC)3 Reference acoustic pressure 0dB = 20 Pa.4 If the sound is measured under actual installation conditions, the measured value will be
higher due to environmental noise and sound reflections.5 Data is valid at nominal capacity
Measuring location (discharge side):
Soun
d pre
ssur
e lev
el (d
B)
Soun
d pre
ssur
e lev
el (d
B)
Soun
d pre
ssur
e lev
el (d
B)
Heating
Octave band center frequency (Hz) Octave band center frequency (Hz) Octave band center frequency (Hz)
3TW60337-2
ERLQ004-008CV3Heating
Notes1. Data is valid at free field condition.
Measured in a semi-anechoic chamber2. Data is valid at nominal operation condition.3. dBA = A-weighted sound pressure level (A scale according to IEC).4. Reference acoustic pressure 0 dB = 20 μPa5. If the sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and
sound reflections.
NR0 NR5 NR10 NR15NR20
NR25
NR30
NR35NR40
NR45
NR50
NR55
NR60
NR65
NR70
NR75
10
20
30
40
50
60
70
10
15
20
25
30
35
40
45
50
55
60
65
70
63 125 250 500 1000 2000 4000 8000 dBA
ERLQ008CA*
NR0 NR5 NR10 NR15NR20
NR25
NR30
NR35NR40
NR45
NR50
NR55
NR60
NR65
NR70
NR75
10
20
30
40
50
60
70
10
15
20
25
30
35
40
45
50
55
60
65
70
63 125 250 500 1000 2000 4000 8000 dBA
ERLQ006CA*
NR0 NR5 NR10 NR15NR20
NR25
NR30
NR35NR40
NR45
NR50
NR55
NR60
NR65
NR70
NR75
10
20
30
40
50
60
70
10
15
20
25
30
35
40
45
50
55
60
65
70
63 125 250 500 1000 2000 4000 8000 dBA
ERLQ004CA*
Octave band centre frequency [Hz]Octave band centre frequency [Hz]Octave band centre frequency [Hz]
Soun
d pr
essu
re le
vel [
dB]
Soun
d pr
essu
re le
vel [
dB]
Soun
d pr
essu
re le
vel [
dB]
3,28Ft(1m)
4,92Ft
(1,5m)
3TW60817-2B
• Heating • ERLQ-CV3
3
10
• Outdoor Unit • ERLQ-CV3
10 Installation10 - 1 Installation Method
ERLQ011-016C
3TW60339-1
Installation servicing space
A B1 B2 C D1 D2 E L1/L2200
200 200 200200 500 1000
300 300 300 500 1000 1500
500 500 1000L1<L2 200 500L2<L1 200 500
L1<L2 L1 H 350 500 750 1000 0<L1 1/2H
21000 0<L1 1/2H
H<L1 L1 H
L2<L1 L2 H 200 1000 500 1000 0<L2 1/2H300 1/2H<L2 H
H<L2 L2 H
NOTES
Legend (Unit: mm)Suction side obstacleDischarge side obstacleLeft side obstacleRight side obstacleTop side obstacleObstacle is present
This situation is not allowed
1 Recommended installation set-up for the ERLQ011~016*(to prevent exposure to wind or that the heat exchanger coil is affected by snow)
2 In these cases, close bottom of the installation frame to prevent discharged air from being bypassed
• Heating • ERLQ-CV3 107
• Outdoor Unit • ERLQ-CV3
10
108
10 Installation10 - 1 Installation Method
ERLQ011-016C
4TW60339-2
Installation guidelines / precautions Daikin AlthermaOutdoor unitInstallation location (general)
Select an installation site that meets the following requirements:• The foundation must be strong enough to support the weight of the unit. The floor is flat to prevent vibrations and noise
generation and to have sufficient stability.• The space around the unit is adequate for maintenance/servicing and allows for sufficient air circulation.(Refer to “Installation
and service space” information sheet}• There is no danger of fire due to leakage of inflammable gas.• The equipment is not intended for use in a potentially explosive atmosphere.• Select the location of the unit in such a way that the sound and discharged cold/hot air generated by the unit does not disturb
anyone, and the location is selected according the applicable legislation.• All piping lengths and distances have been taken into consideration (refer to “Technical specification” information sheet).• Take care that in the event of a water leak, water cannot cause any damage to the installation space and surroundings.• Install units, power cords and inter-unit cables at least 3 m away from television and radio sets. This is to prevent
interference to images and sounds.• Depending on radio wave conditions, electromagnetic interference may still occur even if installed more than 3 m away.
Do not install in the following locations:• Locations where sulphurous acids and other corrosive gases may be present in the atmosphere.• Locations where a mineral oil mist, spray or vapour may be present in the atmosphere.• Locations where flammable gases may leak, where thinner, gasoline and other volatile substances are handled, or where
carbon dust and other incendiary substances are found in the atmosphere.• In areas where the air contains high levels of salt such as that near the ocean.• To prevent exposure to wind, install the outdoor unit with its suction side facing the wall.• Never install the outdoor unit at a site where the suction side (left and back) may be exposed directly to wind, snow. (See
“Installation and Service space” information sheet and figure 1)
Installation location (in cold climates)• To prevent exposure to wind, install a baffle plate on the air discharge side of the outdoor unit.• Unit should be installed in a way that a minimum of 10 cm free space is assured below the unit’s bottom plate at all
conditions (prevent burying in snow), e.g.: heavy snowfall (if necessary construct a pedestal).• In heavy snowfall areas it is very important to select an installation site where the snow will not affect the unit. Make sure that
the heat exchanger coil (left and back side) is not affected by the snow (if necessary construct a lateral canopy and baffle plate on the air side).
• Recommended installation set-up. (See “Installation and Service space” information sheet and figure 2)
Figure 1: construction to prevent exposure to wind and
snow
Figure 2: construction to prevent affect of snow to the
unit
• Heating • ERLQ-CV3
3
11
• Outdoor Unit • ERLQ-CV3
11 Operation range11 - 1 Operation Range
���
��
��
��
�
��
��
��
��
�
�
��
�
�� �� ��
��
�� ��
����
���
��
��
��
��
��
��
��
� ��
��
�� ��
��
��
����
��
�
�
�
��
�
�� �� ��
�� �����
��
��
��
��
�� ��
����
��
��
���
��
�
��
��
��
�
��
��
��
���� �
��
��
��
��
�� �� ���
��
������
��
��
��
����
��
��
��� ��
��
��
��
�
�� ��
• Heating • ERLQ-CV3 109
Daikin Europe N.V. Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR OostendeDaikin Europe N.V. participates in the Eurovent Certifica-tion programme for Liquid Chilling Packages (LCP), Airhandling units (AHU), Fan coil units (FCU) and variablerefrigerant flow systems (VRF) Check ongoing validity ofcertificate online: www.eurovent-certification.com or us-ing: www.certiflash.com
EEDEN 09/16
The present leaflet is drawn up by way of information only and does not constitute an offer bindingupon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of itsknowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fit-ness for particular purpose of its content and the products and services presented therein. Specifica-tions are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability forany direct or indirect damage, in the broadest sense, arising from or related to the use and/or inter-pretation of this leaflet. All content is copyrighted by Daikin Europe N.V.